Вы находитесь на странице: 1из 18

DOC NO.

:
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

I REGION :

II DATE OF III DATE OF


ERECTION : ENERGISATION :

IV DETAILS OF EQUIPMENT :

LOA NO :

MAKE :

TYPE :

SL NO. : R - PHASE Y - PHASE B - PHASE

YEAR OF MANUFACTURE :

V FEEDER NAME :

VI OPERATING VOLTAGE : kV TYPE OF OPERATING


MECHANISM :
VII CURRENT CARRYING CAPACITY : AMPERE

VIII CONTROL VOLTAGE : VOLT DC

IX DETAILS :

SL. DESCRIPTION STATUS REMARK


NO YES NO RECORD DEFICIENCIES, IF ANY
1 EQUIPMENT IS FREE FROM DIRT/DUST
FOREIGN MATERIALS ETC.

2 EQUIPMENT IS FREE FROM ALL VISIBLE


DEFECTS ON PHYSICAL INSPECTION

3 SUPPORT STRUCTURES, MARSHALLING BOX


HAS BEEN PROVIDED WITH TWO EARTHING
PADS / POINTS

4 ALL NUTS AND BOLTS ARE TIGHTENED


CORRECTLY AS PER SPECIFIED TORQUE

5 EQUIPMENT ERECTION IS COMPLETE IN


ALL RESPECT AS PER INSTRUCTION MANUAL
(ATTACH REMAINING ACTIVITIES,IF ANY)

6 PERMANENT ISOLATOR LAVELLING AND


IDENTIFICATION IS DONE

7 LEVELLING AND ALIGNMENT OF STRUCTURE


AND BASE FRAME IS CHECKED

PAGE 1 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

PAGE 2 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

SL. DESCRIPTION STATUS REMARK


NO YES NO RECORD DEFICIENCIES, IF ANY
8 CONTROL BOX / MARSHALLING KIOSK IS
FREE FROM ANY PHYSICAL DEFECTS

9 TIGHTNESS OF NUTS BOLTS OF TERMINAL


CONNECTORS ARE CHECKED

10 AUXILLARY CONTACTS AND RELAYS HAVE


BEEN CLEANED AND FREE FROM RUST /
DAMAGE

11 CORONA RINGS ARE PROVIDED AND


PROPERLY FIXED

12 CABLE TERMINATION AND TIGHTNESS


CHECKED AND UNUSED HOLES SEALED

13 EXTERNAL CABLING IS COMPLETED IN ALL


RESPECT

14 ALL THE CABLE IDENTIFICATION TAGS


PROVIDED AND ALL CORES ARE PROVIDED
WITH IDENTIFICATION FERRULES AT M.B.

15 ALL MOVING PARTS ARE LUBRICATED

16 ALIGNMENT OF ISOLATOR ALREADY MADE


AND LOCKING BOLT PROVIDED, IF ANY

17 FREENESS OF MANNUAL OPERATION IS OK

18 GREASING HAS BEEN MADE ON THE MAIN


CONTACTS ACCORDING TO THE MANUFA-
CTURERS INSTRUCTION

19 FUCTIONAL CKECKING OF AUXILLARY


CONTACTS FOR INDICATIONS AND INTERLOCKS

20 ERECTION COMPLETION CERTIFICATE ALONG


WITH LIST OF OUTSTANDING ACTIVITIES
REVIEWED

21 ALL SPARE WIRES ARE TERMINATED AT


THE TERMINAL BLOCKS

22 EARTH SWITCH CONNECTED TO EARTH


THROUGH BRAIDED WIRES

PAGE 3 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

X MOTOR DETAILS R PHASE Y PHASE B PHASE


MAKE :
SL NO :
TYPE :
VOLT :
AMPERES :
HP / KW :
YR. OF MANUFACTURE :
OVERLOAD SETTING :
(THERMAL OVERLOAD )
XI INSULATION RESISTANCE VALUE OF MOTOR WINDING

( USING A 500 VOLT MEGGER MEASURE RESISTANCE


BETWEEN THE WINDING OF MOTOR AND EARTH )

BETWEEN PHASE
R- PHASE Y- PHASE B- PHASE
WINDING TO EARTH

XII OPERATIONAL CHECKS :

A OPERATE THE ISOLATOR AND RECORD THE MOTOR CURRENT

ISOLATOR OPERATION TIME


OPERAT- R - PHASE Y - PHASE B - PHASE
ION FACTORY SITE FACTORY SITE FACTORY SITE
CLOSE
OPEN

B OPERATION OF ISOLATOR FROM LOCAL / REMOTE OK / NOT OK

ISOLATOR CONTROL PANEL


OPERATION LOCAL REMOTE
CLOSE
OPEN

C MEASUREMENT OF OPERATING TIME

OPERATION PHASE
R- PHASE Y- PHASE B- PHASE
OPENING TIME SEC
CLOSING TIME SEC

PAGE 4 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

D AUXILLARY CONTACTS CHECKING


ISOLATOR AUXILLARY OPERATION TIME
OPERAT- RELAY R - PHASE Y - PHASE B - PHASE
ION TYPE NO NC NO NC NO NC

CLOSE

OPEN

REFERENCE DRAWING NO :

E OPERATION ON UNDER VOLTAGE CONDITION :

CONDITION COIL PHASE


R- PHASE Y- PHASE B- PHASE
PICK UP CLOSING VOLT DC
VOLTAGE OPENING VOLT DC
INTERLOCK VOLT DC
DROP CLOSING VOLT DC
VOLTAGE OPENING VOLT DC
INTERLOCK VOLT DC

XIII INSULATION RESISTANCE TEST


( USING 5000 VOLT MEGGER )
A ISOLATOR CLOSE CONDITION
BETWEEN PHASE
R- PHASE Y- PHASE B- PHASE
MALE SIDE TO GROUND
FEMALE SIDE TO GROUND
B ISOLATOR OPEN CONDITION
BETWEEN PHASE
R- PHASE Y- PHASE B- PHASE
MALE SIDE TO GROUND
FEMALE SIDE TO GROUND
MALE SIDE TO FEMALE SIDE

XIV CONTACT RESISTANCE MEASUREMENT


(COMTACT RESISTANCE SHOULD BE LESS THAN 5 MICRO OHMS / CONNECTOR)
A ISOLATOR CLOSE CONDITION
ACROSS PHASE
R- PHASE Y- PHASE B- PHASE
CONNECTOR (MALE SIDE) MICRO-OHM
CONNECTOR (FEMALE SIDE) MICRO-OHM
MAIN CONTACT (MALE & FEMALE) MICRO-OHM

B ISOLATOR OPEN CONDITION & GROUND SWITCH CLOSE


ACROSS PHASE
R- PHASE Y- PHASE B- PHASE
MAIN CONTACT (MALE & FEMALE) MICRO-OHM
(GROUND SWITCH)

PAGE 5 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

PAGE 6 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

XV CKECKING OF INTERLOCKS

TYPICAL ________ \_____________X_____________ \_______ > BUS SIDE


CIRCUIT 89A 89AE 52 89BE 89B

INTERLOCK OBJECT CONDITION INITIATION RESULT


EQUIPMENT LOCATION CLOSE /
OPEN
LOCAL / REMOTE LOCAL / REMOTE ISOLATOR LOCAL CLOSE CLOSED
OPERATION SWITCH IN THE 89A CONTROL OPEN OPENED
CONTROL BOX IN REMOTE CLOSE NOT CLOSE
LOCAL CONTROL OPEN * NOT OPEN
89A OPENED (CONTROL * (CLOSE 89A BEFORE
89B OPENED PANEL) GIVING OPEN COMMAND)
52 OPEN
LOCAL / REMOTE ISOLATOR REMOTE CLOSE CLOSED
SWITCH IN THE 89A CONTROL OPEN OPENED
CONTROL BOX IN
REMOTE LOCAL CLOSE NOT CLOSE
89A OPENED CONTROL OPEN * NOT OPEN
89B OPENED * (CLOSE 89A BEFORE
52 OPEN GIVING OPEN COMMAND)
LOCAL / REMOTE ISOLATOR LOCAL CLOSE CLOSED
SWITCH IN THE 89B CONTROL OPEN OPENED
CONTROL BOX IN
LOCAL REMOTE CLOSE NOT CLOSE
89B OPENED CONTROL OPEN * NOT OPEN
89A OPENED * (CLOSE 89B BEFORE
52 OPEN GIVING OPEN COMMAND)
LOCAL / REMOTE ISOLATOR REMOTE CLOSE CLOSED
SWITCH POSITION 89B OPEN OPENED
IN CONTROL BOX IN
REMOTE LOCAL CLOSE NOT CLOSE
89B OPENED
89A OPENED
52 OPEN
89B CLOSED ISOLATOR LOCAL OPEN NOT OPEN
89A OPENED 89B
52 OPEN
GROUND SWITCH LOCAL / REMOTE GROUND LOCAL CLOSE CLOSED
OPERATION SWITCH POSITION SWITCH OPEN OPENED
IN CONTROL BOX IN 89AE
LOCAL GROUND LOCAL CLOSE CLOSED
89A OPENED SWITCH OPEN OPENED
89B OPENED 89BE
52 OPEN

PAGE 7 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

TYPICAL ________ \____________X_______________ \_________ > BUS SIDE


CIRCUIT 89A 89AE 52 89BE 89B

INTERLOCK OBJECT CONDITION INITIATION RESULT


EQUIPMENT LOCATION CLOSE /
OPEN
INTERLOCKING 89A OPENED 89AE LOCAL CLOSE NOT CLOSE
BETWEEN GROUND 89B CLOSED
SWITCH AND 52 OPEN
ISOLATOR 89A CLOSED 89BE LOCAL CLOSE NOT CLOSE
89B OPENED
52 OPEN
89A CLOSED 89AE LOCAL CLOSE NOT CLOSE
89B -NA
52 - NA
89A -NA 89BE LOCAL CLOSE NOT CLOSE
89B CLOSED
52-NA
INTERLOCKING 89A OPENED 89B LOCAL CLOSE NOT CLOSE
BETWEEN ISOLATORS 89AE CLOSED REMOTE CLOSE NOT CLOSE
52 - NA
89B OPENED 89A LOCAL CLOSE NOT CLOSE
89BE CLOSED REMOTE CLOSE NOT CLOSE
52 - NA
INTERLOCKING 52 CLOSED 89A LOCAL CLOSE NOT CLOSE
BETWEEN BREAKER 89A OPENED REMOTE CLOSE NOT CLOSE
AND ISOLATOR 89B OPENED 89B LOCAL CLOSE NOT CLOSE
REMOTE CLOSE NOT CLOSE
52 OPENED 52 LOCAL CLOSE NOT CLOSE
89A CLOSED REMOTE CLOSE NOT CLOSE
89B OPENED
52 OPENED 52 LOCAL CLOSE NOT CLOSE
89A OPENED REMOTE CLOSE NOT CLOSE
89B CLOSED
52 CLOSED 89A LOCAL OPEN NOT OPEN
89A CLOSED REMOTE OPEN NOT OPEN
89B CLOSED 89B LOCAL OPEN NOT OPEN
REMOTE OPEN NOT OPEN
NORMAL OPERATION 89A CLOSED LOCAL CLOSE CLOSED
89B CLOSED 52 CONTROL OPEN OPENED
52 OPENED REMOTE CLOSE CLOSED
CONTROL OPEN OPENED

PAGE 8 OF 7
DOC NO. :
SUB STATION :
BAY NO :
PRE-COMMISSIONING OF ISOLATOR AND GROUND SWITCH EQUIPMENT IDENTIFICATION NO :
COMMISSIONING FORMATS DATE OF TESTING :

XVI FINAL DOCUMENTATION REVIEW :

A FINAL DOCUMENT OF PRE-COMMISSIONING CHECKS


REVIEWED AND APPROVED YES NO

B DOCUMENTS REGARDING SPARES, EQUIPMENT, O & M


MANNUALS ETC AVAILABLE AT SITE FOR O & M PURPOSE YES NO

C AFTER MODIFICATION, IF ANY, "AS BUILT DRAWINGS"


ARE AVAILABLE AT SITE YES NO

SIGNATURE SIGNATURE SIGNATURE SIGNATURE


NAME NAME NAME NAME
DESIG. DESIG. DESIG. DESIG.
COMPANY COMPANY COMPANY ( POWERGRID )
( SUPPLIER REPRESENTATIVE ) ( ERECTION AGENCY ) COMMISSIONING

SIGNATURE SIGNATURE
NAME NAME
DESIG. DESIG.
COMPANY COMPANY
( SUPPLIER REPRESENTATIVE ) ( ERECTION AGENCY )

PAGE 9 OF 7
CIES, IF ANY

PAGE 10 OF 7
PAGE 11 OF 7
CIES, IF ANY

PAGE 12 OF 7
SWITCH

PAGE 13 OF 7
PAGE 14 OF 7
PAGE 15 OF 7
REMARK

MAND)

MAND)

MAND)

PAGE 16 OF 7
REMARK

PAGE 17 OF 7
RGRID )
SIONING

PAGE 18 OF 7