110KV PYKARA - METTUPALAYAM FEEDER

(ANNUAL RELAY TESTING)


DATE OF TEST :

LC . NO :

DATE OF LAST TEST :

1) FEEDER PROTECTION RELAY : ( MAIN )


Name Plate Details :
Make :GEC ALSTHOM
Type : PYTS 204
Sl . No :97113218003

Settings :
K1 = 0.5 , K2 = 1.6 , K3 = 2.1 , Kin = 0.7 , KZ = 10 , Kzn = 5 , KC = 1 , P = b , θ = 60° , KD = 1 ,
K A,B,C = 20 , tp = 40 , ZPK = 30 , tz2 = 0.4 , tz4 = 6 (Max) , tz3 = 1
☻ Remove PT fuse fail relay (97) and short 1 & 2 terminal for DC supply to main relay
a) Earth Fault :
Zone Expected Obtained % Error Impedance
AN BN CN AN BN CN X R
1 60 % 4 6

2 53 % 5 9

3 69 % 5 9

Reverse : Not operated

b) Phase Fault :
Zone Expected Obtained % Error Impedance
AB BC CA AB BC CA X R
1 72 % 4 6

2 64 % 5 9

3 82 % 5 9

c) Stater Checkup :
1. Remove PSB Module
2. Timing of all Zones set at maximum
3. Moniter Box 22 (+) , 24 (-) AØ
20 (+) , 24 (-) BØ
21 (+) , 24 (-) CØ
4. Apply single phase supply (current & voltage) Gradually through Veriyack
AppliedVoltage Applied Current Obtained Current
AØ BØ CØ
0V 0.25 A

38.1 V 0.25 A

63.5 V 3.2 A

d) PSB Check (YØ – only)


Monitor box 4 (+) , 24 (-)
☻ Insert PSB module , Note :- PSB LED Glows when PSB Operates
Applied Voltage Applied Current Obtained Current
0V 0.15 A

38.1 V 0.15 A

63.5 V Up to 6A relay not operated


e) Zone Timing :
☻ For this test actual settings should be set
Zone Expected Obtained Contact :
1 Instant B1 & B2

2 0.4 Sec

3 1 Sec

2) FEEDER PROTECTION RELAY : ( BACK UP )


Name Plate Details :
Make :GEC ALSTHOM
Type : CDD
Sl . No : 9712 4169 001 - AØ - 67A
9712 4169 010 - CØ - 67C
9712 4157 001 - BØ - 67N
Settings Available :
Current TMS
O/L 0.5 , 0.75 , 1 , 1.25 , 1.5 , 1.75 , 2 0–1
E/L 0.2 , 0.3 , 0.4 , 0.5 , 0.6 , 0.7 , 0.8 0–1
Settings Adopted :
Current TMS
O/L 2 0.16
E/L 0.4 0.34
Applied Expected O/L Applied Expected E/L Voltage :
Current Current & Obtained Current Current & Obtained 7,8
Time AØ CØ Time BØ
Pick up 2A Pick up 0.4 A Current :
9 , 10
4A 1.364 Sec 0.8 A 2.056 Sec
Contact :
8A 0.6772 Sec 1.6 A 1.0208 Sec 3,4

16 A 0.4484 Sec 3.2 A 0.6758 Sec

20 A 0.404 Sec 4A 0.6089 Sec

Directional Check : - OK
3) Open Delta Voltage Measurnment :
( Voltage should measured in E/L Relay 7 , 8 )

All PT Supply available =

RØ PT Voltage Fail =

YØ PT Voltage Fail =

BØ PT Voltage Fail =

4) Breaker Testing :
a) Open / Close Time interval :
RØ YØ BØ J1 (+)
Close Close = K21
Open = K5
Open

b) Trip Coil Current :


TC1 = J1 (+) , K5 (-)

TC2 = J5 (+) , K305 (-)


c) Dip in Voltage :
Station battery voltage =

TC1 = K5 (+) , J2 (-)

TC2 = K305 (+) , J6 (-)


d) 52a Opening time : ( U7 , U5 ) =

5) CT Secondary IR Value :
Protection Core ( Main ) - A71 =

Protection Core ( Back up ) - C71 =

Metering Core - D71 =

6) SOFT Check :
Creat a fault current to relay through ZFB kit at the same time close the breaker
Note that the Breaker will not close.

7) Protection Trip Check :


a) Earth fault Zone1 AN created in ZFB kit , Kit Operated Breaker tripped wit Zone1 AN Relay
Indication , wit 86M relay operated and Distance protection Annoncation
b) Back up relay 67A , 67C , 67N operated manually , Breaker tripped with , 86B Relay operated
with Directional O/L & E/L Protection Operated Annoncation.

AEE / P&C / MSG AE / GRT / MSG