Manufacturing Plant

Evaluation: Economizer w/ Fluke


DAY: November 19. 2010
POWER AND ENERGY
DEMAND

KW sep-17 oct-18
AVERAGE 76757.51 55162.08
MINIMUM 45760.01 21973.34
MAXIMUM 112253.35 87400.01

THE TABLES SHOW A 20,000 KW AVERAGE DIFFERENCE WHICH IS A GOOD INDICATOR THAT THE
ECONOMIZER IS FUNCTIONING

Manufacturing Plant
CURRENT 9/17 CURRENT 10/18

CURRENT
A1 A2 A3
CURRENT sep-17 oct-18 sep-17 oct-18 sep-17 oct-18
AVERAGE 127.10 97.25 121.96 93.24 129.23 97.95
MINIMUM 70.60 33.60 68.10 35.10 78.10 42.00
MAXIMUM 177.90 164.00 170.20 153.60 179.90 158.40

AVERAGE AMPERAGE WAS REDUCED BY MORE THAN 30 AMPS WHICH INDICATES GOOD
RESULTS FROM THE USE OF THE ECONOMIZER.

Manufacturing Plant
VOLTAGE 9/17 VOLTAGE 10/18

VOLTAGE READINGS SEEM MORE STABLE WITH THE USE OF THE ECONOMIZER.
AS INDICATED BY THE TABLES, VOLTAGE PEAKS OR SPIKES HAVE BEEN
ELIMINATED FROM AVERAGE HIGHS OF 290 VOLTS TO 285 VOLTS.

Manufacturing Plant
POWER FACTOR POWER FACTOR
9/17/10 9/18/10

POWER FACTOR

P.F sep-17 oct-18


AVERAGE 0.7712 0.7509
MINIMUM 0.7100 0.6900
MAXIMUM 0.8200 0.8000

THE POWER FACTOR READINGS REMAIN SIMILAR IN BOTH TABLES. THE POWER FACTOR VALUES ARE
WELL BELOW THE OPTIMUM OF .9. IT IS IMPORTANT TO UNDERSTAND THAT THE ECONOMIZER IS
NOT A SUBSTITUTE FOR A CAPACITOR BANK. THE RESULTS OF THESE POWER FACTOR READINGS IS TO
ADVISE CUSTOMERS THAT THIS ISSUE SHOULD BE ADDRESSED WITH A LICENSED ELECTRICAL
CONTRACTOR.
Manufacturing Plant
THE RESULTS SHOW AN EXCELLANT 38% DROP IN ELECTRICAL ENERGY
CONSUMPTION AS COMPARED TO READINGS WITHOUT THE ECONOMIZER.
IT SHOULD BE NOTED THAT THESE RESULTS ARE ALSO AFFECTED BY THE
DEMAND VARIATIONS AS NOTED ON PREVIOUS TABLES

Manufacturing Plant
POWER AND ENERGY SAVINGS
KW 35%
KVA 28%
KVAR 16%
MWH 38%

Manufacturing Plant