CT Value Caculation Sheet:

Client: City of Chaffee


Chaffee, MO

Primary Contact Tank Water Temperature = 59.0 Farenheit


Length (shortest distance) = 30.0 ft Water Temperature = 15.0 Celsius
Width = 12.8 ft Water pH = 7.3
Depth = 7.4 ft Flow Rate = 400.0 GPM
Volume = 21,255.2 Gallons
Baffling Factor = 0.1 N/A Contact Time = 10.2 Minutes
Total Calculated CT Volume in Tank = 2,125.5 Gallons CT Value for 4 Log Inactivation
from DNR Chart (Free Chlorine)= 4.0 Minutes-mg/l
Clearwell Contact Tank
Length = 15.0 ft Minimum Free Chlorine Residual = 0.5 mg/l
Width = 15.0 ft
Depth = 12.0 ft CT Value for System = 5.1 Minutes-mg/l
Volume = 20,196.0 Gallons
Baffling Factor = 0.0 N/A Since the CT Value for the system is larger than the CT
Total Calculated CT Volume in Tank = 0.0 Gallons value from the Chart, the System meets the 4-Log removal.
(21.7 > 4 Minutes-mg/l)
Filters
Total Number = 2.0 Each
Volume Each = 1,000.0 Gallons
Total Filter Volume = 2,000.0 Gallons
Baffling Factor = 0.3 N/A
Total Calculated CT Volume in Tank = 600.0 Gallons

Elevated Tank
Tank Volume = 30,000.0 Gallons (Not Counted Because of Single Line In & Out)
Bowl Height = 22.0 ft
Average Gallons/Ft in Tank = 1,363.6 Gal/ft
Operating Range in Feet = 5.0 ft
Volume Available Below Operating Range = 23,181.8 Gallons
Baffling Factor (DNR Handout) = 0.0 N/A
Total Calculated CT Volume in Tank = 0.0 Gallons
Wet Riser Diameter= 0.5 ft
Wet Riser Height = 120.0 ft
Wet Riser Volume = 176.2 Gallons
Baffling Factor (DNR Handout) = 0.0 N/A
Total Calculated CT Volume in Riser = 0.0 Gallons
Line Work
Influent Line Length (ft) = 930.0 ft
Influent Line Size (in) = 6.0 in
Influent Line Volume = 1,365.9 Gallons
Baffling Factor = 0.9 N/A
Total Calculated CT Volume in Pipe = 1,229.3 Gallons

Total Volume with Baffling Figured = 4,091.4 Gallons