Abu Bedoo Contractor at roof

Hotel Project 1
FANS STATAIC PRESSURE CALCULATION ELBOW
SUPPLY&EXHAUST FAN 700 CFM 2
Max. Friction
Duct Size Equevlant Length Velocity
ITEM LINE CFM loss 3
in. (m) ft. FPM in. H2o/100ft.
1 BOX 700 12"X10" 2.8 9.19 1075 0.18 4
2 BOX 700 12"X10" 3.4 11.15 1075 0.18
3 BOX 630 12"X10" 3.4 11.15 1045 0.18 5
4 BOX 560 10"X10" 3.4 11.15 1010 0.18
5 BOX 490 10"X10" 3.4 11.15 980 0.18 6
6 BOX 420 10"X8" 3.4 11.15 945 0.18 7
7 BOX 350 10"X8" 3.4 11.15 900 0.18
8 BOX 280 10"X6" 3.4 11.15 855 0.18 8
9 BOX 210 10"X6" 3.4 11.15 790 0.18
10 BOX 140 6"X6" 3.4 11.15 720 0.18 9
11 BOX 70 6"X4" 5 16.40 610 0.18
12 Elbow 700 N= 2 2 13.12 1075 10
13 Elbow 70 N= 1 1 3.28 610
14 F.D 70 N= 2 0.25 1.64 610 11
15 V.D 70 N= 1 0.25 0.82 610
16 HPHR 700 1075 0.835 ELBOW 11 FD&V.D
Total length 135.66 ft
Total friction for duct line 0.24 in. H2o
Total friction for duct line+hood(0.34+0.25) 1.08 in. H2o RISER DIAGRAM FOR SUUPLY &EXHAUST FAN 700CFM
Total friction with 20%, S.F 1.30 in. H2o approximated 1.3
calculations according to equal friction method
friction loss for F.D &V.D based on manufacturers data CAPACITY=700 CFM
HPHR STATIC PRESSURE ACCORDING TO MANUFACTURERS DATA STATIC PRESSURE=1.3 in.wg
QTY =14 EXH+15 SYPPLY