Вы находитесь на странице: 1из 24

Installation Manual

Mini-Split System
Condensing Units
9,000 - 60,000 Btuh
TTK Series 50/60 Hz

50Hz Models 60Hz Models


Cooling Only Cooling Only
TTK 509 PB TTK 512 P1
TTK 512 PB TTK 518 P1
TTK 512 LB TTK 524 P1
TTK 518 PB TTK 530 P1
TTK 518 LB TTK 536 K1
TTK 524 PB TTK 536 K4
TTK 524 LB TTK 042 K4
TTK 530 PB TTK 048 K1
TTK 530 KB TTK 048 K4
TTK 536 KB TTK 060 K1
TTK 536 KD TTK 060 K4
TTK 042 KD
TTK 048 KD
TTK 060 KD

January 2003 TTK-SVN001-EN

Layout 1 14/1/03, 10:16 AM

Black
General Information

Introduction Reception Storage


This Installation Manual is given as On arrival, inspect the unit before Take precautions to prevent
a guide to good practice in the signing the delivery note. Verify condensate from forming inside
installation by the installer of mini- that the nameplate data matches the unit’s electrical board and
split system. Installation the date on the sales order, motors if the unit is stored before it
procedures should be performed in submittal data and delivery note is installed.
the sequence that they appear in (including electrical data) to insure The Trane Company will not
this manual. the proper unit was shipped. assume any responsibility for unit
For installing the unit to operate Specify any damage of the unit on damage resulting from condensate
properly and reliably, it must be the delivery note, and send a accumulation on the unit’s
installed in accordance with these registered letter of protest to the electrical and/or mechanical
instructions. Also, the services of a last carrier of the goods within 72 components.
qualified service technician should hours of delivery. Notify the dealer
be employed, through the at the same time. The unit should About this Manual
maintenance contract with a be totally inspected within 7 days Cautions and warnings appear at
reputable service company. of delivery. If any concealed appropriate places in this
Read these Installation Manual damage is discovered, send a instruction manual. Your personal
completely before installing the registered letter of protest to the safety and the proper operation of
condensing unit. carrier within 7 days of delivery this machine require that you
and notify the dealer. follow them carefully.
About the Unit The Trane Company assumes no
The units are assembled, pressure Warranty liability for installations or servicing
tested, dehydrated, charged and Warranty is based on the general performed by unqualified
run tested before shipment. The terms and conditions by country. personnel. All phases of the
information contained in this The warranty is void if the installation of this air conditioning
manual applies to units that are equipment is modified or repaired system must conform to all
designed to operate in cooling only without the written approval of The national, provincial, state and local
mode. Trane Company, if the operating codes.
limits are exceeded or if the control
Important system or the electrical wiring is Warning
This document is customer modified. Damage due to Warnings are provided at
property and is to remain with unit. inappropriate installation, lack of appropriate places in this manual
Please place in service information knowledge or failure to comply to indicate to installers, operators
pack upon completion of work. with the manufacturer’s and service personnel of
These instructions do not cover all instructions, is not covered by the potentially hazardous situations
variations in systems, nor do they warranty obligation. If the installer which, if not avoided, COULD
provide for every possible does not conform to the rules result in death or serious injury.
contingency to be met in described in Installation Manual, it
connection with installation. may entail cancellation of warranty
and liabilities by The Trane Caution
Should further information be Cautions are provided at
desired or should particular Company.
appropriate places in this manual
problems arise which are not to indicate to installers, operators,
covered sufficiently in this manual, and service personnel of
the matter should be referred to potentially hazardous situations
your Trane sales representative. which, if not avoided, MAY result in
minor or moderate injury or
malfunction of the unit.

© American Standard Inc.2000 TTKSVN001-EN

Layout 2 14/1/03, 10:16 AM

Black
Contents

General Information 2
Pre-Installation Check 4
Item Required for Installation
Location and Preparation of Units & 5
Unit Installation
Selecting the Mounting Locations
Condensing Units Installation
Connection of Refrigerant Tubing 6
Connection the Unit with Flaring Procedure
Evacuation and Refrigerant Charge 8
Air Evacuation and Charging
Additional Charge
Gas Leakage Inspection
Electrical Installation 10
Condensing Unit Wiring
Finishing & Run Tests 11
Finishing
Run Tests
Typical Wiring Diagram 12
Dimensional Data 17
Notes 22

TTK-SVN001-EN 3

Layout 3 14/1/03, 10:16 AM

Black
Pre-Installation Check

Items Required for Note: Purchase equal lengths of


both tubes and insulation required.
Installation Cut the appropriate tube lengths,
30 cm to 50 cm (12 to 20 in.)
Copper tubing, fittings and longer on each one to dampen
insulation to interconnect the vibration between units. Wall
suction (wide pipe) and liquid thickness of copper tube should
(narrow pipe) refrigerant lines be 0.8 mm (0.0314 in.).
between the indoor and outdoor
units can be purchased locally. It is
necessary to purchase the
following items: (Table 1)

Table 1 - Items Required for Installation


Item Use or specification
Deoxidizied annealed Interconnection between the indoor unit and
outdoor unit.
copper tube
Foamed polyethylene Diameter: According to outside diameter of
copper pipe.
Insulated copper wire See local codes according to unit nameplate.
Pipe heat insulation Thickness: No less than 6 mm (0.25").
Saddles or clamps Hold refrigerant piping.
Insulated clamps or Connecting wire.
staples
Refrigerant oil
Vinyl tape Armored.
Bolts and nuts Secure the unit.
Expansion shield
Putty or similar filter

4 TTK-SVN001-EN

Layout 4 14/1/03, 10:16 AM

Black
Location and Preparation of
Units & Unit Installation

Selecting the Mounting


Locations

Determine the mounting location 300 mm (12") or more


with the customer as follows: 300 mm (12") or more
1. Leave the spacing shown in
Figure 1 for required air flow.
Figure 1 illustrates the
minimum operating and
service clearances for either a
single or multiple unit
installation. These clearances
are the minimum distances
necessary to assure
adequate serviceability, 500 mm (20") or more
cataloged unit capacity, and
peak operating efficiency. 1200 mm (48") or more
Providing less than the
recommended clearances
may result in condenser coil
starvation, “short-circuiting” Unit Clearance
of exhaust and lack of airflow,
or recirculation of hot
Figure 1
condenser air.
2. Do not install the unit near a
source of heat, steam,
flammable gas or exhaust fan. Caution 4. When the unit is mounted on
3. Do not install the unit where a Install the unit such that it will not a roof, be sure the roof will
strong wind consistently be tilted by more than 5º from carry the unit’s weight.
blows or where it is extremely vertical in any plane. Vibration isolation is
dusty. recommended to prevent
4. Do not install the unit where 3. Do not set the unit directly on transmission to the building
people pass in front of the fan the ground. Unit shall be structure.
discharge grille. secured to the concrete pad 5. When the unit is mounted on
5. The unit should be installed using bolts (not supplied to the wall, the unit should be
as close to the indoor unit as prevent abnormal noise and installed on a cantilever/L
possible. vibration and to avoid the support capable of carrying
effect of moisture). The the unit’s weight. The support
Condensing Unit minimum height of the should be rigidly fixed to the
concrete pad should be 100 wall using expansion shields.
Installation
mm (4"), and the concrete
pad must be positioned a
1. Install the unit mounting pads minimum of 200 mm (8") from
(4 places) into the bottom any wall and surrounding
channels by tapping gently shrubbery.
with a plastic or rubber
tipped hammer (optional).
Note: This step applies only
to models with such
installation items supplied.
2. Set the unit on a level
reinforced surface such as
one made of concrete to
minimize shock and vibration.
TTK-SVN001-EN 5

Layout 5 14/1/03, 10:16 AM

Black
Connection of Refrigerant
Tubing

The principal concerns in


refrigeration tubing are:
• Uniform oil return to the Flare nut
compressor.
• Pressure drops and their Copper
effect on system capacity. tubing
• Tubing routing and isolation Reamer
Copper
to avoid line breakage,
tubing
vibration and sound
transmission. Regarding this, Flare tool
the interconnecting Figure 2
refrigerant lines should be
simple and shorter as much
as possible. Deburring

There are two types of connections


available to interconnect refrigerant L
tubes between indoor and outdoor
units.
- Flare connections for TTK5
(4th digit in model No.) series. Before After
- Quick connections for TTK7
(4th digit in model No.) series. Figure 3
Caution
Do not open the liquid and gas line
service valves until tubing
installation and system evacuation Check if (L) is flared uniformly
is completed. and is not cracked or scratched.
L Dimension:
1.4 to 1.7 mm (6.35 mm dia)
Connection the Unit with 1.8 to 2.0 mm (9.53 mm dia)
Flaring Procedure When reaming, hold the tube 1.9 to 2.2 mm (12.7 mm dia)
end downward and be sure 2.1 to 2.4 mm (15.88 mm dia)
that no copper scraps fall into
Flaring (If tubing is procured or the tube.
cut at the site). Figure 4
3. Remove the flare nut from the
1. Cut the copper tube to the service valve and be sure to
required length with a tube insert the flare nut onto tube.
cutter. It is recommended to 4. Make a flare at the end of
cut approx. 30 cm-50 cm copper tube with a flare tool
(12" to 20") longer than the (Figure 4).
tubing length you estimate.
2. Hold each tube downward A good flare should have the
when cutting, remove burrs at following characteristics:
the end of the copper tube - Inside surface is glossy and
with a tube reamer or file. smooth.
This process is important and - Edge is smooth.
should be done carefully to - Tapered sides are of uniform
make a good flare (Figure 2 length.
and Figure 3).

6 TTK-SVN001-EN

Layout 6 14/1/03, 10:16 AM

Black
Bending Connection
5. When bending the tube, be 9. For proper connection, align
careful not to crush it. To the union tube and flare tube
prevent crushing of the tube, straight with each other, then
bent it gently and do not screw in the flare nut lightly at
bend the tube at a radius first to obtain a smooth
curvature of less than match (Figure 6).
100 mm.
6. If the copper tube is bent or
pulled too often, it will Indoor unit
Wrench
become stiff. Do not bend the pipe
(adjustable)
pipe more than three times at
one place.

Cautions Before Union Flare nut


Torque
Connecting Tubes Tightly wrench
7. Be sure to apply a sealing Connection pipe
cap or water-proof tape to Flare nut
prevent dust or water from
Figure 6 Figure 7
getting into the tubes before
they are used.
8. Be sure to apply refrigerant
10.Tighten the flare nut to the 11.Repeat the process above
lubricant to the matching
specified tightening torque for the remaining line.
surfaces of the flare and
with torque wrench and
union before connecting them
adjustable wrench (Figure 7).
together. This is effective for
reducing gas leaks (Figure 5).
Table 2 - Flare Nut Tightening Torque
Flare nut / Piping size Tightening torque
kgf - cm lbf- in
6.35 mm (1/4") dia. 150~200 130~170
9.53 mm (3/8") dia. 350~400 300~340
12.7 mm (1/2") dia. 500~550 430~470
15.88 mm (5/8") dia. 600~650 520~570
Apply refrigerant
lubricant here

Figure 5

TTK-SVN001-EN 7

Layout 7 14/1/03, 10:16 AM

Black
Evacuation and Refrigerant
Charge

Air Evacuation and 4. If vacuum gauge does not Refrigerant


rise above 500 microns in pipe (flare)
Charging one minute, the evacuation is
complete.
The outdoor unit is factory 5. With vacuum pump and
charged. Unit name-plate charge is micron gauge blanked off,
the total required system charge remove the valve caps and
with 7.5 meters (25 feet) of fully open the liquid and
interconnecting lines. Since the suction service valves with a Service valve
outdoor unit will not have to be hexagon wrench (Figure 10). Outdoor
evacuated unless charge has been (Torque: 70 to 90 kgf - cm). unit
completely lost, leave the suction 6. Disconnect the service
and liquid shut-off valves closed. hoses, replace service
1. Upon completion of pressure tap port caps and
installation, remove the valve stem caps. These caps
service pressure tap cap and must be replaced to prevent
connect the gauge manifold leaks. Replace valve stem
and the vacuum pump to the cap finger tight, then tighten Valve cap
charging port using the an additional 1/6 turn. Charging port
service hoses (Figure 8). (Tightening torque: 70 to
2. Pump the indoor unit and the 90 kgf - cm).
connecting tubes until the
pressure in them lowers to
below 1.5 mmHg
(350 microns) of vacuum
(Figure 9).
3. Stop the vacuum pump and Service hose
with valve core Pressure tap cap
close the gauge manifold
valve, observe the micron
gauge, if gauge pressure Figure 8
rises above 2.1 mmHg
(500 microns) in one (1)
minute, then evacuation is
in-completed or system has a Suction pressure
leak.
• Attach appropriate hose from Micron gauge
manifold gauge to suction Electrical Liquid pressure
and liquid line valves service connection
ports.
• Attached center hose of
manifold gauges to vacuum
pump.

Note: Unnecessary switching of Suction line


hoses and complete evacuation of Liquid line
all lines leading to sealed system
can be accomplished by placing a
“T” in manifold center hose and
connecting branch hose to cylinder
of R-22.
Service hose Vacuum pump

R-22

Figure 9

8 TTK-SVN001-EN

Layout 8 14/1/03, 10:16 AM

Black
Gas Leakage Inspection
To the indoor unit

Close Hex
Wrench
After charging with refrigerant,
Cap Open check the joints for gas leakage
with gas leak detector or a soap
bubble solution (Figure 11).
Liquid line Liquid line

To the indoor unit


Leak detection Soap
Soap
Hex
Cap Close Wrench

Open

Pressure Pressure
tap tap
Suction line Suction line

Figure 10 Figure 11

Additional Charge Caution


• FREON GAS “R22” ONLY.
Refrigerant suitable for a tube • Always evacuate air from the
length of 3.5 to 7.5 meters is tubing before adding
charged in the outdoor unit at the refrigerant.
factory. When the tube is longer • Add refrigerant through the
than 7.5 m, additional charging is charging port of liquid line
necessary. For the additional valve after the completion of
amount, using the following table evacuation step 5.
for recommended amounts: • The refrigerant provided by
the manufacturer meets all
Table 3 - Additional Charge the requirements of our units.
When using recycled or
Piping sizes per each additional
reprocessed refrigerant, it is
meter of
advisable to ensure its quality
Liquid - Suction interconnecting line
is equivalent to that of a new
length
refrigerant. For this, it is
1/4" - 3/8" 25 Grams / Meter necessary to have a precise
1/4" - 1/2" 26 Grams / Meter analysis made by a
3/8" - 5/8" 59 Grams / Meter specialized laboratory. If this
condition is not respected,
the manufacturer’s warranty
could be cancelled.

TTK-SVN001-EN 9

Layout 9 14/1/03, 10:16 AM

Black
Electrical Installation

Condensing Unit Wiring 3. Ground the outdoor unit per


local code requirements.
4. Provide flexible electrical
Warning conduit whenever vibration
• Do not allow the electrical transmission may create a
wires inside the compressor noise problem within the
compartment to come in structure.
contact with refrigerant pipes 5. Remove the outdoor unit
compressor or moving parts. terminal cover (Figure 12).
• Wiring and grounding must 6. Route the connection cable
comply with NATIONAL and through the cable entry
LOCAL CODES. bushing and strain relief and
• The manufacturer will have up to the terminal block.
no responsibility for the 7. Insert the end of the cable
problems caused by wires into the terminal block
unauthorized change in the connectors as shown on the
internal wiring. unit wiring diagram.
• Each country has their own 8. Tighten the terminal block
field wiring rules and connector screws (Torque:
regulations. Be sure the 7-12 kgf - cm).
installation complies with
local electrical codes. Caution
1. Check the unit nameplate for Insert the connection cable
electrical rating. Be sure wires into the terminal block
wiring is according to local firmly. Incorrect insertion may
codes and wiring system cause a safety problem.
diagram.
2. A separate power supply 9. Replace the outdoor unit
disconnect and a circuit terminal cover.
breaker for overcurrent
protection should be
provided in the external
power supply line.

Terminal cover

Terminal block

Cable entry

Figure 12

10 TTK-SVN001-EN

Layout 10 14/1/03, 10:16 AM

Black
Finishing & Run Tests

Finishing Run Tests 6. Check electrical wire size


used is as specified.
7. Check all field wiring for tight
1. Insulate the entire piping of Check the system before start up. connection.
gas line and liquid line with Once the unit is installed, a check 8. Make sure that electrical
proper pipe heat insulation to of the system is recommended wires inside the unit do not
prevent heat loss and any before starting the units. contact with refrigerant pipes.
condensate water drops over 9. Check the fan rotates freely.
surrounding materials which Warning
could be damaged • Never open the unit without Start the system and check items
(Figure 13). having previously cut the 1 through 3 below.
2. Securely wrap the insulated power supply. For the system start procedure,
pipes with vinyl tape. Electrical shock can cause refer to the Owner’s Manual for the
(Starting at the lowest end of personal injury or death indoor evaporator unit.
the pipes, each wrap should • Do not stand on the unit.
be about 1/3 of the tape
width so that water does not
Outdoor Unit
1. Check that field connections 1. Is there any abnormal noise
enter). It is possible to bind are correctly made.
into a single bundle the and vibration during
2. Check that units are correctly operation?
refrigerant lines and the installed and there is no tool
interconnecting wiring 2. Will noise, air flow, or drain
or debris near or on top of water from the unit disturb
between the units (Figure 14 the unit.
and Figure 15). the neighbors?
3. Check the tubing and the 3. Is there any refrigerant gas
3. Secure the insulated pipes to connections for leaks.
the outside wall with clamps, leakage?
4. Check that unit has a proper 4. Give the installation
etc. ground wiring. instruction to the customer.
5. Check for proper voltage and
Note: fuse size.
• Do not try to bend the tube Remark: Filter driers are not
after installation. Insulation provided with condensing units
• The pressure tap on the according to Trane Standard,
service valve of suction line Installers should install filter driers
can be used to measure: into the systems at the job site.
- an intake pressure on a TTK
/ TWK in cooling mode.
- a discharge pressure on a
TWK in heat pump mode.

Minimum thickness 6 mm

Figure 15
Pipes insulation Connection
Figure 13 pipe (heat
insulation)
Pipe
insulation

Indoor unit
pipe (heat
insulation)
(Vinyl tape)

Pipes bundle
Figure 14
TTK-SVN001-EN 11

Layout 11 14/1/03, 10:16 AM

Black
Typical Wiring Diagram

Models Models Note: For models that are not


50Hz 60Hz 50Hz 60Hz covered in the following table,
wiring diagram please refer to the
TTK 512 PB TTK 512 P1 TTK 524 PB TTK 536 K1 diagram printed in the sticker that
TTK 512 LB TTK 518 P1 TTK 524 LB located on the unit control box.
TTK 518 PB TTK 524 P1 TTK 530 PB
TTK 518 LB TTK 530 P1 TTK 530 KB
TTK 536 KB
200-240V/1PH/60Hz
220-240V/1PH/50Hz
L N

MS-1 L N MS-2

G C1 MS C2
RD
R FROM INDOOR UNIT
BLK
CR CPR C
BL 200-240V/1PH/60Hz
S 220-240V/1PH/50Hz
1 2

(NOTE 3) (NOTE 3)
WH R
FAN BLK
CF C
BR MTR
S
GN/YL

LEGEND
COLOR CODE
CPR COMPRESSOR
BL BLUE
CF FAN CAPACITOR
CR COMPRESSOR RUN CAPACITOR BLK BLACK
FAN MTR FAN MOTOR BR BROWN
MS COMPRESSOR MOTOR CONTACTOR GN GREEN
TERMINAL GR GRAY
JUNCTION OR ORANGE
IDENTIFIED TERMINAL RD RED
COIL WH WHITE
TERMINAL BOARD BY OTHERS YL YELLOW
TERMINAL BOARD BY FACTORY
FIELD WIRING
FACTORY WIRING
RELAY CONTACT N.O.
CAPACITOR
NOTES:
APPLY FOR DOUBLE POLE
1. POWER WIRING AND GROUNDING OF
CONTACTOR ONLY
EQUIPMENT MUST COMPLY WITH
(FOR SINGLE POLE CONTACTOR, LOCAL CODES.
CONNECT ELECTRIC LINE FROM 2. USE COPPER CONDUCTORS ONLY.
3. TERMINALS 1 AND 2 ARE
COMPRESSOR-C AND FAN MOTOR-C
LOCATED ON INDOOR TERMINAL
DIRECT TO TERMINAL-N)
BOARD OF INDOOR UNITS.

12 TTK-SVN001-EN

Layout 12 14/1/03, 10:16 AM

Black
Models
50Hz
TTK 509 PB/MA/M1
TTK 512 PB/MA/M1
TTK 518 MA
TTK 524 MA

CONTROL, POWER
SUPPLY, AND GROUND
WIRING FROM INDOOR UNIT
220-240/1/50
OR
200-240/1/60
(ELEC.WIRE LENGTH 5.5 M. FOR DOMESTIC ONLY)

X1 FAN MOTOR
9
WH
8 L CF M

WH RD BR GN/YL
7

BLK
6 N BLK

5 RD R
GR CR M
GN/YL S
BL
N C
BLK
L COMPRESSOR

Color Code
X1 = Terminal Strip BL = Blue
L = LINE (From indoor control unit) BLK = Black
N = Neutral GN/YL = Green with
= Ground Yellow Stripe
CD = Fan Capacitor RD = Red
CR = Compressor Run Capacitor GR = Green
WH = White
BR = Brown
Notes:
1. Power wiring and grounding of
equipment must comply with
local codes.
2. Use copper conductor only.

TTK-SVN001-EN 13

Layout 13 14/1/03, 10:16 AM

Black
Models
50Hz 60Hz
TTK 536 KD TTK 536 K4
TTK 042 KD TTK 042 K4

380-415/3/50 220-240/1/50
460/3/60 200-240/1/60

G L1 L2 L3 LL1 LL2

MS-3
BLK RD YL
CF
BR
2 S
FAN
MTR
WH R C BLK
MS-1
CPR MS-2
1 3

C1 MS C2

FROM INDOOR UNIT


220-240V/1PH/50Hz
200-240V/1PH/60Hz

LEGEND
CPR COMPRESSOR NOTES:
CF FAN CAPACITOR
1. POWER WIRING AND GROUNDING OF
FAN MTR FAN MOTOR
EQUIPMENT MUST COMPLY WITH
MS COMPRESSOR MOTOR CONTACTOR
LOCAL CODES.
TERMINAL
2. USE COPPER CONDUCTORS ONLY.
JUNCTION
3. THREE PHASE CONDENSING UNITS
IDENTIFIED TERMINAL
REQUIRE TWO POWER SUPPLY
COIL
SOURCES AS SHOWN.
TERMINAL BOARD BY OTHERS
TERMINAL BOARD BY FACTORY
FIELD WIRING
FACTORY WIRING COLOR CODE
RELAY CONTACT N.O. BL BLUE
CAPACITOR BLK BLACK
BR BROWN
GR GRAY
OR ORANGE
RD RED
WH WHITE
YL YELLOW

14 TTK-SVN001-EN

Layout 14 14/1/03, 10:16 AM

Black
Models
50Hz 60Hz
TTK 048 KD TTK 048 K4
TTK 060 KD TTK 060 K4

380-415/3/50 220-240/1/50
460/3/60 200-240/1/60

G L1 L2 L3 LL1 LL2

BLK RD YL
MS-3
CF1
BR
2 S
FAN
MTR1
WH R C BLK
MS-1
CPR MS-2
1 3 CF2
BLK YL BR
S
FAN
MTR2
WH R C BLK
LPCO HPCO
C1 MS C2
BL BLK

FROM INDOOR UNIT


220-240V/1pH/50Hz
200-240V/1pH/60Hz

NOTES:
LEGEND
CPR COMPRESSOR 1. POWER WIRING AND GROUNDING OF
CF1, 2 FAN CAPACITOR EQUIPMENT MUST COMPLY WITH
FAN MTR1, 2 FAN MOTOR LOCAL CODES.
HPCO HIGH PRESSURE CUT-OUT 2. USE COPPER CONDUCTORS ONLY.
LPCO LOW PRESSURE CUT-OUT 3. THREE PHASE CONDENSING UNITS
MS COMPRESSOR MOTOR CONTACTOR REQUIRE TWO POWER SUPPLY
TERMINAL SOURCES AS SHOWN.
JUNCTION
IDENTIFIED TERMINAL
COIL
TERMINAL BOARD BY OTHERS COLOR CODE
TERMINAL BOARD BY FACTORY BL BLUE
FIELD WIRING BLK BLACK
FACTORY WIRING BR BROWN
RELAY CONTACT N.O. GR GRAY
CAPACITOR OR ORANGE
PRESSURE SENSING SWITCH RD RED
WH WHITE
YL YELLOW

TTK-SVN001-EN 15

Layout 15 14/1/03, 10:16 AM

Black
Models
60Hz
TTK 048 K1
TTK 060 K1
200-240/1/60

L N G

MS-1 MS-2

RD
R
BLK
CPR C
CR
BL
S

SR

BL BLK
2 5
CS
RD
1

WH
R
FAN BLK
CF1 MTR 1 C
BR
S

WH
R
FAN BLK
C
CF2 MTR 2
BR
S

LPCO HPCO
C1 MS C2
BL BLK

FROM INDOOR UNIT


200-240V/1pH/60Hz

LEGEND
CPR COMPRESSOR
CF1, 2 FAN CAPACITOR NOTES:
CR COMPRESSOR RUN CAPACITOR
1. POWER WIRING AND GROUNDING OF
CS COMPRESSOR START CAPACITOR EQUIPMENT MUST COMPLY WITH
FAN MTR1, 2 FAN MOTOR LOCAL CODES.
HPCO HIGH PRESSURE CUT-OUT 2. USE COPPER CONDUCTORS ONLY.
LPCO LOW PRESSURE CUT-OUT
MS COMPRESSOR MOTOR CONTACTOR
SR COMPRESSOR START RELAY
TERMINAL
JUNCTION COLOR CODE
IDENTIFIED TERMINAL
COIL BL BLUE
TERMINAL BOARD BY OTHERS BLK BLACK
TERMINAL BOARD BY FACTORY BR BROWN
FIELD WIRING GR GRAY
FACTORY WIRING OR ORANGE
RELAY CONTACT N.O. RD RED
RELAY CONTACT N.C. WH WHITE
CAPACITOR YL YELLOW
PRESSURE SENSING SWITCH

16 TTK-SVN001-EN

Layout 16 14/1/03, 10:16 AM

Black
Dimensional Data

Models
50Hz 60Hz
TTK 509 PB TTK 512 P1
TTK 512 PB MOUNTING DETAIL

1.5 [37.0]
Ø0.5 [12.0]

Ø1.0 [26.0]
1.5 [37.5]
0.9 [21.8]
10.4 [264.0]

(MOUTING HOLES)

18.7 [475.0]

AIR FLOW DIRECTION

27.6 [700.0] 9.8 [250.0]

WIRING IN
20.9 [530.6]

SUCTION LINE
LIQUID LINE
9.4 [239.0]

1.4 [35.1]
4.9 [123.5]

7.3 [185.9]
1.2 [30.5]

REFRIG. LINE DIA.


MODEL
LIQUID SUCTION

TTK509 1/4" (6.35) 3/8" (9.35)

TTK512 1/4" (6.35) 1/2" (12.70)

NOTES 1. SUCTION AND LIQUID LINES ARE FLARE TYPE CONNECTIONS


2. DIMENSIONS : INCHES (MILLIMETERS) : 1 IN. = 25.40 MM.

TTK-SVN001-EN 17

Layout 17 14/1/03, 10:16 AM

Black
MOUNTING DETAIL

Models

1.02 (26.0)
0.59 (15.0)
50Hz 60Hz 1.97 (50.0)
TTK 518 PB TTK 518 P1 0.98 (25.0)
TTK 524 PB TTK 524 P1 Ø0.38 (10.0)
TTK 530 PB TTK 530 P1 (MOUNTING HOLES)

TTK 530 KB
13.0 (330.0)

11.81 (300.0)

AIR FLOW DIRECTION

4.45 (113.0)
13.0 (330.0) 32.67 (830.0) 11.81 (300.0)
4.17 (106.0)
4.61 (117.0)
27.24 (692.0)

KNOCK OUT
HOLE (20.0 MM)
0.83 (21.0)

6.06 (154.0)

8.54 (217.0)
3.70 (94.0)

19.12 (485.6)

14.96 (380.0) 21.22 (539.0)

5.57 (141.5) 5.57(141.5)


LIQUID LINE

SUCTION LINE

REFRIG. LINE DIA.


MODEL
LIQUID SUCTION
NOTE 1) SUCTION AND LIQUID LINE ARE FLARE TYPE CONNECTIONS.
TTK518PB/P1
TTK512PBHEF ;
2) DIMENSIONS : INCHES (MILIMETERS) ; 1 IN = 25.40 MM
TTK518PBHEF 1/4 (6.4) 1/2 (12.7)
TTK018QB00B
TTK524PB/P1
TTK530PB/P1
TTK024QB00B 3/8 (9.5) 5/8 (15.9)
TTK030QB00D
TTK530KB00F

18 TTK-SVN001-EN

Layout 18 14/1/03, 10:16 AM

Black
Models
50Hz 60Hz
TTK 530 KB TTK 530 K1

OUTDOOR UNIT

MOUNTING DETAIL
1.93 (49.0)

40.0 (1018.0)
1.85 (47)

1.18 (30.0)
(330.0)

(360.0)
14.17
13.0

(49.0)
1.93

SLOTS 10.0 x 25.0


(MM.) 0.78 (20.0)
AIR FLOW DIRECTION

14.17 5.12 (130.0)


(360.0)
40.0 (1018.0) 5.51 (140.0)
13.0
(330.0) 13.66 (347.0) 14.17 (360.0)

5.65 (143.5)
15.11 (384.0)

31.3 (795.0)

KNOCK OUT
HOLE (20.0 MM)
3.22
(82.0)
21.85 (555.0)
5.95 (151.0)
3.58 (91.0)

LIQUID VALVE
42.44 (1078.0)
SUCTION VALVE

REFRIG. LINE DIA.


MODEL
LIQUID SUCTION

TTK530KB/K1 3/8 (9.5) 5/8 (15.9)

TTK536KB/KD NOTE 1) SUCTION AND LIQUID VALVES ARE FLARE TYPE CONNECTIONS
3/8 (9.5) 3/4 (19.1)
TTK536K1/K4
2) DIMENSIONS : INCHES (MILIMETERS) ; 1 IN = 25.40 MM
TTK042KD/K4 3/8 (9.5) 7/8 (22.2)

TTK-SVN001-EN 19

Layout 19 14/1/03, 10:16 AM

Black
MOUNTING DETAIL

1.57 (40.0)
1.03 (26.0)

0.55 (14.0)
10.63 (270.0)

40.87 (1038.0)

39.92 (1014.0) Ø0.39 (10.0)


1.57 (40.0)

AIR FLOW DIRECTION


5.12 (130)

5.87 (149)
38.88 (988.0)
13.75 (350)

5.65 (143.5)
49.37 (1254.0)

2.0 (51.0)
1.0 (26.0)

8.38 (213.0)

36.14 (918)
3.54 (90.0)

5.90 (150.0)

KNOCK OUT
HOLE (20.0 MM)
LIQUID VALVE Ø3/8 (9.5)

SUCTION VALVE Ø1-1/8 (28.6)

NOTE 1) SUCTION AND LIQUID VALVE ARE SWEAT TYPE CONNECTIONS.


2) DIMENSIONS : INCHES (MILIMETERS) ; 1 IN = 25.40 MM

20 TTK-SVN001-EN

Layout 20 14/1/03, 10:16 AM

Black
Models
50Hz 60Hz
TTK 509 MB TTK 509 M1
TTK 512 LB/MB/KB TTK 512 L1/M1/K1 MOUNTING DETAIL

TTK 518 LB/MB/KB TTK 518 L1/M1/K1


TTK 524 LB/MB/KB TTK 524 L1/M1/K1

0.59 (15.0)
1.02 (26.0)
1.97 (50.0)
0.98 (25.0)
Ø0.38 (10.0)
(MOUNTING HOLES)
11.81 (300.0)
13.0 (330.0)

AIR FLOW DIRECTION

4.45 (113.0)
11.81 (300.0)
13.0 (330.0) 32.67 (830.0)
15.04 (128.0)

4.61 (117.0)
23.22 (590.0)

TM
KNOCK OUT
HOLE (20.0 MM)
1.02 (26.0)

16.54 (420.0)
3.70 (94.0)

6.06 (154.0)

8.54 (217.0)

14.96 (380.0) 21.22 (539.0)


5.57 (141.5) 5.57 (141.5)

LIQUID LINE

SUCTION LINE
REFRIG. LINE DIA.
MODEL
LIQUID SUCTION
TTK512LB
TTK512L1 NOTE 1) SUCTION AND LIQUID LINE ARE FLARE TYPE CONNECTIONS.
1/4 (6.4) 1/2 (12.7)
TTK518LB 2) DIMENSIONS : INCHES (MILIMETERS) ; 1 IN = 25.40 MM
TTK518L1
TTK524LB
3/8 (9.5) 5/8 (15.9)
TTK524L1

TTK-SVN001-EN 21

Layout 21 14/1/03, 10:16 AM

Black
Notes

22 TTK-SVN001-EN

Layout 22 14/1/03, 10:16 AM

Black
Notes

TTK-SVN001-EN 23

Layout 23 14/1/03, 10:16 AM

Black
Literature Order Number: TTK-SVN001-EN 0300
Trane Thailand
New
7th Follr, Ploenchit Center Building
2 Sukhumvit Road, Klongtoey Stocking Location: Bangkok, Thailand
Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road
Samrong Tai, Samutprakarn 10130 Since The Trane Company has a policy of continuous product and product data improvement,
http://www.trane.com it reserves the right to change design and specifications without notice.
An American Standard Company

Layout 24 14/1/03, 10:16 AM

Black

Вам также может понравиться