P 760

f f' f'& Angle

11222500 3350 -60 8.56983738E-06 1.71E-05 6.82E-02 0.07


44890000 6700 72.35 -0.04661940299 -4.66E-02

82810000 9100 1 72.35 5.35133136E-06 1.07E-05 -5.57E-02 0.06


204490000 14300 1 -72.35 -0.15304807692 -1.53E-01 5.57E-02 0.06
380250000 19500 1 72.35 1021.94375

479610000 21900 1 72.35 5.73523583E-06 1.15E-05 -5.82E-02 0.06


689062500 26250 1 -72.35 -0.30941597305 -3.09E-01
936360000 30600 1 0 4097.88335315
Force

3.90 51.72

-3.19 42.23
3.19 42.23

-3.33 44.17
P/A between 1.4 - 3.5 Mpa
Balance at least SW + 50% of SDL
Since extra prestress force doesn't increase the cost, use maximum
5 strands per duct
Duct spacing = 0.8 - 1.2 m
Min radius of curvature = 2.5m
Interval of straight cable = 0.5m
Prestessing force determined by load balancing, but concrete stresses at transfer and full loading checked
Ultimate moment capacity checked
1m wide strip
Walls are 200mm

Cover 25 mm (AS3600; fire rating)


Ds 220 mm
yc 110 mm
bs 1000 mm
bw 2400 mm
As 2.20E+05 mm2
I 8.87E+08 mm4
bw 200 mm
Stirrup 0 mm
Duct 19 mm
Strand 12.7 mm Super, stress relieved
Strands/Duct 5
MBL 184 kN
fpu 1840 kPa
Pduct 782 kN
Lossi 8%
Losst 15%
emax 72.35 mm
e1 60 mm
e2 72.35 mm
e3 72.35 mm
esag,1 96.175 mm
esag,2 144.7 mm
esag,3 108.525 mm
f'c 32 MPa
SW 5.28 kN/m
SDL 1 kPa
G 6.28 kN/m
Q 3 kPa
wp,balance 5.78 kN/m (SW + 0.5*SDL; CCA Design Guide)
ys 0.70
yl 0.30
Span1 8m
Span2 12.8 m
Span3 10 m
Span1eff 6.70 m
Span2eff 10.4 m
Span3eff 8.7 m
Pe 760 kN -15%
Pi 894 kN -8%
Pj 972 kN
Pe/A 3.45 MPa
Spacing 804.64 mm
Pe 83.60 kNm (haunching moment)
wp1 13.03 kN/m
wp2 8.13 kN/m
wp3 8.72 kN/m
P1 51.72 kN
P2 42.23 kN
P3 42.23 kN
P4 44.17 kN

Elastic Stresses - Transfer - Midspans


w1 -7.75 kN/m
w2 -2.85 kN/m
w3 -3.44 kN/m
M1 -41.23 kNm
M2 -33.41 kNm
M3 -30.31 kNm
st,1 1.05 Mpa
sb,1 -9.18 Mpa
st,2 0.08 Mpa
sb,2 -8.21 Mpa
st,3 -0.31 Mpa
sb,3 -7.82 Mpa

Elastic Stresses - Service Load - Midspans


w1 -4.65 kN/m
w2 0.25 kN/m
w3 -0.34 kN/m
M1 -32.44 kNm
M2 -8.00 kNm
M3 -15.00 kNm
st,1 -0.04 Mpa
sb,1 -8.09 Mpa
st,2 -3.07 Mpa
sb,2 -5.06 Mpa
st,3 -2.20 Mpa
sb,3 -5.92 Mpa

Deflection
kcs 2.00
Dload,long 22.74 kN/m
Deff,1 9.71 kN/m
Deff,2 14.61 kN/m
Deff,3 14.02 kN/m
Span1/250 32 mm
Span2/250 51.2 mm
Span2/250 40 mm
Dtotal,1 4.52 mm
Dtotal,2 -41.83 mm
Dtotal,3 -20.6 mm

Flexural Strength - Midspan Design moments determined without haunching mom


Ap 500 mm2
Ep 200000 Mpa
eM 72.35 mm
Ec 30100 Mpa
g 0.826
a2 0.85
dn 43.26 mm
dp 182.35 mm
ec 0.003
spe 1520 MPa
epe 0.0076
ece 0.0003
ecp 0.0096
epy 0.00782
ep 0.01751 Prestress has yielded
dn/dp 0.24 Ductile
l 164.48 mm
C=T 782 kN
Mu 128.63 kNm
prop 0.80
w* 9.68 kN/m
M* 75.27 kNm OK

Flexural Strength - First Span


eM 60 mm
dn 43.26 mm
dp 170.00 mm
epe 0.0076
ece 0.0002
ecp 0.0088
epy 0.00782
ep 0.01661 Prestress has yielded
dn/dp 0.25 Ductile
l 152.13 mm
Mu 118.97 kNm
w* 9.68 kN/m
M* 31.57 kNm OK

Flexural Strength - End Span


eM 72.35 mm
dn 43.26 mm
dp 182.35 mm
epe 0.0076
ece 0.0003
ecp 0.0096
epy 0.00782
ep 0.01751 Prestress has yielded
dn/dp 0.24 Ductile
l 164.48 mm
Mu 128.63 kNm
w* 9.68 kN/m
M* 63.08 kNm OK
sfer and full loading checked
Lmin 0.5 m
Rmin 2.5 m
a1 0.4
a2 0.074397
h1 -18.81888 mm
a3L 0.11194 m
R2 57.78283 m
R3 57.35333 m
wp 13.1527

Crack Control

f'c 32 MPa
f'ci 25 MPa
Fti 1.25 MPa
Fci -12.50 MPa
Ft 2.83 MPa
Fc -14.40 MPa
ermined without haunching moments and downward force included
Cover 25 mm
D 220 mm
yc 110 mm
bw 2400 mm
As 5.28E+05 mm2
I 2.13E+09 mm4
Stirrup 12 mm
Duct 19 mm
Strand 12.7 mm
Strands/Du 5
MBL 184 kN
fpu 1840 kPa
Pduct 782 kN
Lossi 8%
Losst 15%
f'c 32 MPa
SW 12.67 kN/m
SDL 2.4 kN/m
G 15.072 kN/m
Q 7.2 kPa
ys 0.70
yl 0.30
wt 15.07 kN/m
ws 20.11 kN/m
Leff,1 6.5 m Subtract width of column
Leff,2 9.1 m
Leff,3 9.1 m
Leff,4 8.7 m
Leff,5 9.1 m
Leff,6 9.1 m
Leff,7 6.5 m
emax,mid 60.35 mm
emax,sup 41.35 mm Beam duct must go under the slab duct
e1,L 0 mm
e1 60.35 mm
e1,R 41.35 mm
e2 60.35 mm
e2,R 41.35 mm
e3 60.35 mm
e3,R 41.35 mm
e4 60.35 mm
e4,R 41.35 mm
e5 60.35 mm
e5,R 41.35 mm
e6 60.35 mm
e6,R 41.35 mm
e7 60.35 mm
e7,R 0 mm
esag,1 81.025 mm
esag,2 101.7 mm
esag,3 101.7 mm
esag,4 101.7 mm
esag,5 101.7 mm
esag,6 101.7 mm
esag,7 81.025 mm
Pe 1800 kN
Pi 2118 kN
Pj 2302 kN
Pe/A 3.41 MPa
Ducts 2.94 i.e. 3 ducts at 800 cts
Spacing 815.37 mm

Practical Tendon Profile