Basics of Duct Design


The AIRAH Queensland Division have been conducting a very successful series of “back to basics” seminars
focusing on all aspects of air conditioning and refrigeration design. JJW (Bill) Siganto, AM, F.AIRAH
presented the Duct Design seminar and his thoughts on this topic make interesting reading.

Good duct design optimises: size where velocity is the criterion, the limiting factor is
• Duct size (manufacturing costs) noise breakout. His choice if 1.2 Pa/m as the mid range
• Duct systems pressure losses (operation cost) friction gradient is higher than that used by many designers.
• Duct systems acoustics (environmental costs) For the smaller sizes the proposed velocity limit often
• Air balance procedures (commissioning costs) produces a high friction gradient. Consequent dynamic losses
are quite low with the resultant velocity pressure around
Of these, duct sizing is the simplest. In a few minutes, even
12Pa.
the most complex systems can be sized with a duct sizing
slide rule. The various texts suggest three methods: Velocity Pressure (or Velocity Head) In this paper, the
• Constant friction gradient terms velocity pressure and velocity head are interchangeable.
• Constant velocity For air at comfort temperature the velocity pressure is 0.6
• Static pressure regain times the square of the duct velocity.
Most designers use the constant friction gradient. Static Pv = 0.6 x v2, in Pascals (Pa), if v is measured in
pressure regain is a generally discredited procedure. per second.
A pragmatic solution To optimise the conflicting elements in Static Pressure Friction causes static pressure loss. The
duct design, the late W R (Roy) Ahern, offered the following calculation of the friction gradient “f” (Pa/m) is complex,
approach (1) for the sizing of low-pressure air conditioning involving velocity pressure, duct diameter and duct surface
ductwork; roughness. Modern computers can make it routine. However,
most designers still rely on duct sizing slide rules.
• For air quantities greater than 4500 l/s size
duct at 10m/s. The static pressure loss in a section of duct is,
• For air quantities less than 180 l/s, size duct at 4.5 m/s.
PT = f x L, where L is the duct length in meters.
• For air quantities greater than 180 l/s
But less than 4500 l/s Fitting lengths should be included in the estimation of “L”.
Then size duct on basis of friction loss of 1.2 Pa/m Where a fitting involves a change in velocity than fitting
For these rules, Ahern offered no references other than his should be included in the duct section with the higher
own extensive experience backed by his unerring ability to velocity.
reduce all technical programs to first principles. In the larger

Photos courtesy of CETEC, Melbourne 2002

24 THE OFFICIAL JOURNAL OF AIRAH - October 2002


FORUM

Total Pressure Total Pressure is the sum of Static Pressure concerned Ahern 50 years ago that he designed his own
and Velocity Pressure. fittings and calculated K values from unassailable first
principles.
PT = PS + PV
Long runout of flexible duct were not extensively used in
Since one of the variables of friction gradient is velocity
Ahern’s time, but these days it is reasonable practice to limit
pressure, it follows that total pressure is dependent on the
velocity to 3.5m/s and for friction loss calculation purposes
velocity pressure, which for a given duct area varies as the
to allow twice the measured length.
square of the flow. As air flows through a duct system from a
fan to terminal the total pressure is always decreasing. The almost universal use of “cushion head” involves an
Because of changes in velocity, the same cannot be said of additional pressure loss of at least one and a half velocity
velocity pressure and static pressure. heads(1).
Fittings When a fitting changes the direction of airflow or its Balancing Designers should ensure that the duct system is
velocity, then as well as the friction loss referred to above, a proper Unless the designer considers how the duct systems
dynamic loss is involved. The quantum of dynamic loss is can be properly balanced, more than likely it won’t be. The
expressed in total pressure. Various fittings are assigned a following is considered fundamental:
“fitting loss factor” (K). The dynamics loss through the
• Design for application of proportional balancing methods
fittings is then calculated from,
• Provide adequate dampers for balance of sub systems
PT (Pa) = PV • Do not rely on splitter devices as balancing aids
Where the velocity pressures is usually related to the References
maximum velocity occurring in the fitting. AIRAH (2), ASHARE 1 Ahern WR, AIRAH Journal Vol.16, No.6 :”Duct sizing”, June 1977
(3)
and SMACNA (4) are the most widely used references for 2 AIRAH Application Manual “ Duct Design DA3”, 1987
fitting loss factors. Duct designers are often frustrated by the 3 ASHRAE “Handbook of Fundamentals” 2001
disparity between the references for K values for the same 4 SMACNA “HVAC Systems Duct Design” 3rd Edition 1990.
fitting, particularly for those involving divided flow. This so

THE OFFICIAL JOURNAL OF AIRAH - October 2002 25