Stack Emission Analysis Report


- Stack Emission Monitoring - 08.07.2011 - Gopi Krishan Processors Pvt. Ltd., Panduri Waraich Road, Amritsar, Punjab Stack attached to APCD of Thermopac & Boiler Furnace - Coal - Metal - 30.48 - 110 - 40 - SPM and CO2 Trimua Cyclone & Wet Scrubber in Thermopac and Multi Cyclone in Boiler Furnace - 110 - 28 - 8.56
RESULTS

Description Date of Sampling Name& Address of the Industry Stack Identification Fuel Used Type of Stack (ACC/Metal) Stack Height (meter) Diameter of Stack (cm) Sampling Duration (Minutes) Parameters Monitored Control Measures (if any) Stack Temperature (oC) Ambient Temperature (oC) Average Stack Velocity (m/s)
PARAMETERS

Particulate Matter (as PM), (12 % CO2 Correction) (mg/Nm3) Carbon Dioxide (as CO2) % Sulphur Dioxide (as SO2), (mg/Nm3)

412 9.4 40.5