41 is the most common criterion for analyzing a bus transferbeing 1.33 p.u V/Hz. Other associated criteria are voltage, phase angle and motor inrush current. As per the working group of Power System Relaying Committee of IEEE Fast Transfer has been recommended as motor bus transfers in power plant applications, followed by parallel, residual voltage, slow and in phase. Therefore, the normal sync check relay cant be employed for such applications. Lack of supervisory relays in such devices used for such applications exposes the protected equipment to potential damages from out of phase conditions.