Summary Of SPLN D3.

009-1:2010
1 Phase Prepayment Active Energy Meter Standard Transfer Specification
No. 1 Feature & Specification Ability explanation Keypad meter with STS standard one way communication (information sent by Vending System to energy meter not contrary) flat tariff 1 phase 2 wire prepayment active energy meter IP 54 Accuracy class : 1.0s Install for low voltage customer (230 V) Direct connected SPLN 1: 1995 Tegangan-tegangan Standar. SPLN D5.001: 2008, Pedoman Pemilihan dan Penggunaan Meter Energi Listrik IEC 62055-31: 2005-09, Electricity metering Payment sistems Part 31: Particular requirements Static payment meters for active energy (classes 1 and 2) IEC 62055-41: 2007-05, Electricity metering Payment sistem Part 41: Standard transfer specification (STS) Application layer protocol for one-way token carrier sistems IEC 62055-51: 2007-05, Electricity metering Payment sistem Part 51: Standard transfer specification (STS) Physical layer protocol for one-way numeric and magnetic card token carriers. IEC 62052-11: 2003, Electricity metering equipment (AC) General requirements, tests and test conditions, Part 11: Metering equipment. IEC 62053-21: 2003, Electricity metering equipment Part 21: Static meter for active energy (classes 1 and 2). IEC 62056-21: 2002-05, Electricity metering Data exchange for meter reading, tariff and load control. Part 21 Direct local data exchange. SPLN D3. 005-1: 2008 Meter statik energi aktif fase tunggal kelas 1,0 Meters must have the ability to detect and measure the energy and electric power totally up to the 15th harmonic from two directions (forward and reverse) Measure energy using higher current flow in 2 current sensor (phase & neutral current sensor). This start when different current is 0.003*Ib = 0.003*5=0.015A between current flow in phase & neutral. Voltage : 230V Current : 5(60)A Ib (I base) = 5A & Im (I max)=60A Starting current : 0.002*Ib = 0.002*5A = 0.01A Frequency : 50Hz Class : 1.0 Installment Construction : IP 54 Voltage circuit power consumption (maximum): 2W and 10VA Current circuit power consumption (maximum): 4VA Temperature : 10C up to +45C Temperature limit : 25C s/d +55C Storage & Transportation : 25C s/d +85C The main components of the energy meter, namely: micro-processor, display screen (display), capacitors for power supplies, components for measurement systems, relay / contactors, varistors, super capacitors, system converters (ADCs / DACs), and the crystal, must have industrial grade quality and evidenced by a certificate of authenticity of the product (certificate of origin) or supporting data from the component manufacturer. Super capacitor must be able to reach its full capacity when energized maximum

Type of meter

Standard

3 Measurement

Specification

Component

Minimum Feature

Ability for detect & protect from tampering

8 Protection Seal 9

Mechanical Specification

of 60 minutes and should be able to distribute power to display and for meter system for a minimum 48 hours of continuous light. Measure parameter: Total active energy, current, voltage & active power Display : 8 digits (6 unit & 2 decimal) Low credit threshold: adjustable using keypad with code 456xx, which xx is 2 digits kWh with minimum 05kWh power limit: adjustable using engineering token Respond to over load : Respond to credit limit : By the time the credit value reaches the low-limit, green LED indication changes to red-flashing and the buzzer sounded. The sound can be stopped by pressing any key on the keypad. If within xxx minutes later, there is no credit token is entered, the buzzer rang again. More lower the credit token, the duration of sound getting faster. Delay time of buzzer sound can be set via the keypad with code 123xxx, with xxx = the time in minutes. Respond to tampering : Respond to internal process fail : Meters must be able to provide safeguards against abuse efforts (tampering), includes: Wiring reversed. current circuits connected directly (by-pass) The neutral wire is disconnected at inlet cable service (utility side). The neutral wire is disconnected on utility side cable and voltage regulator mounted on a customer installation. Injection of current in the phase and/or neutral wire. Induction external magnetic field of at least 400 mT (4000 Gauss) Open the terminal cover (including the no-power state) If there is tampering other than opening the terminal cover, meter should continue to measure the normal and increase the use of kWh(reducing the credit tokens) and the meter can not charge new credit token(except engineering token). When the credit reaches zero, the relay should be opened to cut off power supply to consumers. For all types of tampering, prior to repair, the meter must be able to record the event and / or provide continuous indication depend of its ability to activate the appropriate display. At the time of display meters can be active again and the tamper has not been fixed, then the meter must be capable of displaying the indication of misuse. Meters should have facilities for the security seal comprising: Two metrological seal mounted on meter box lid One PLN Seals, mounted on the cap terminal General Follow the requirements of IEC 62055-31 point 5 for meter indoor installment, with additional provisions, including: PCB, Relay, auxiliary components must be installed strong and unaffected by the shock. Meter Box : Construction meter box so that it can not be opened without damaging the seal The box can be constructed in an integrated meter with MCB, the shape is not specifically defined, but the meter must be equipped with base plate (base plate) of metal and rust resistant. Terms of the seals on the meter box this type of follow SPLN D3.003: 2008. Terminal : Terminals shall be of screw type press system (bolt fasteners are equipped with cable conductor plate pressure) and able to accept input cable size 6 to 16 mm of the type of aluminum or copper. Grounding terminal must be electrically connected with the neutral terminal and the metal-bodied meters are accessible. Configuration and arrangement of terminals can be seen in below figure :

Figure 1 Terminal Cover : Terminal cover should be able to close all the terminals, bolts fasteners cable conductor and a portion of the cable insulation. LED indicator : Meters must be equipped with at least three lamps LED indicator light, colors and functions provided as follows: Red: Imp / kWh (output pulse) Yellow: abuse (tamper) Green: power supply and low credit information. For credit is low, the color turns to red and flashes. Each LED should be written functions.

10

The keypad is made of polymer material with there is a sign of the number 5 key arises (node) and must be protected from the possibility of fluid leakage. Each button must be able to operate a minimum of 20,000 times. Construction of the keyboard can become one with the meter or a separate (remote). If a separate keypad must be completed in the form of electronic display screen displays. Configuring the numbers follow a standard 12-digit telephone (3 columns - 4 lines) as in below figure : Keypad

Figure 2 11 The screen made from the LCD and use the light background (back-light) or use another system better and more efficiently, such as LEDs or other more advanced technologies The displays must be supported by non-erased memory (non-volatile), minimum 4 kbyte, equipped with super capacitors for power supply providers if the power goes out. Super capacitors must have the ability to distribute power display a minimum of 48 hours continuous light. The displays have two lines of information: The first line for the symbols and codes, with a minimum character height 4.5 mm The second line for Text in Indonesian, with a minimum character sizes: width 4 mm and a height of 8 mm.

Display and indicator

Figure 3 Symbol on first line shows figure : Inform the level of usage charges Inform reverse wiring Inform tampering indication appears when the text shows the remaining credits and accumulated energy Inform relay open state The code on the first line displays information about: Short code number The number of digits from the tokens that have been entered on the second line of text Text on the second row, have at least 8 digits within a unity of time and running from the right to left, showing: A. Number token that has entered through the keypad An example is Figure 3, which shows the view after the token 2341-2453-2318-13466750 has been successfully entered. 346-6750 was 7 the last digit displayed on the screen. The number from the digits entered appear in the Code of 20 Note : Enter in the charging process after 20-digit token token included, can use the method of delay time of approval, or pressing the B. Information on the intake response token, as shown in Table 3 If the token is received will be shown the value of kWh purchased and then the total number of remaining kWh. Changes in the appearance value of kWh purchased and the total kWh intermittent 1 second with a flame display information 2 seconds, followed by the symbol 'kWh' Example: 12345678901234567890 (token number is entered) from the meter) - 156 (kWh purchase value) - 245 (total value of kWh) No. 1 2 3 4 5 6 7 8 9 Condition Token accepted Token rejected Token used Token expired (more than 50th token) Over load Over load > 5 times Tampering Meter error Data empty Text display *) (information

Note : *) For a text display that uses 7-LED system. If the display uses a better system then the text can be customized.
C. Information about measuring parameter : Information parameters that must be displayed continuously is the residual value / credit balances and the kWh symbol Information for short code D. Short code by push keypad button with certain code Minimum give information: - Credit (kWh) - Total Energy (kWh) - Voltage (V) - Current (A) - Active Power (W) - Power Limit (W) - Serial Number (11 digits) - Tariff Index (in decimal format) - Total cut off because of overload - Total power off - Alarm duration - Low credit threshold Short code in Attachment 1 Short Code For evaluation, data/event/history store in nonvolatile memory & can save minimum last 50 event, include: meter off, overload, tamper, opening of terminal cover & meter cover, credit run out, meter reset, credit token (20 digit). Transfer data (download) using a computer with a standard reference for IEC 62056-21: 2002-05, meters continuously send data to the synchronization every 30 seconds with send speed baud rate: 4800 bps or 9600 bps. E. Indication & overload warning if load is more than maximum power load setting, meter must Respond with buzzer

sound and appearance of the text " " and if : Over-load lasted continuously for 45 seconds, the relay should open and close again automatically after 150 seconds for 30 minutes there is not continuous over load several times with a cumulative time of 45 seconds, relay should be opened and closed automatically after 150 seconds When the accumulated time is less than 45 seconds, the data accumulated time is reset back to zero. for 30 minutes of opening relay happens because over load 5 times in succession, the relay should open and close again automatically after 45 minutes.

F. Information about Tamper Meters must be able to respond to tampering like table below : Display Meter Tampering reaction text symbol Opening terminal - Relay open cover when power on - Data record Opening terminal - Relay open cover when power off - Data record Normal measure Reverse wiring - Data record Normal Bypass measure Current injection on Normal phase or neutral wire measure Neutral cut from load Normal side(utility side/SMP) measure Neutral cut from load side and install Normal voltage regulator on measure customer side(IML) Normal measure

Yellow LED Active Active Active Active Active

How Fix Token Token

to

Fix and token Fix and token Fix and token Fix and token Fix and token

Active

External magnetic - relay is not induction 400 mT affected by induction

Active

Fix and token

12

Meter Faceplate

G. Information about internal process fail Meters must be able to detect the failure of internal processes and capable of giving orders to open relay to disconnect power supply. In this condition meter can not be used again, all the LED goes off, the buzzer sounds continuously every second and the meter must be replaced. Should give information minimum on table below : Information Writing sample Trademark Meter type Name & Manufacture location (city) Standar SPLN D3.009-1 : 2010 Wiring Fase tunggal 2 kawat Sensor & relay Fungsi 2S 2R Serial Number Production year voltage identifier 230 V Base current & Max. Current 5 (60) A frequency 50 Hz Meter Constant imp/kWh ........... imp/kWh Accuracy class 1,0 Double Signs square for meters with protection class II ID meter SGC

13
Connection Wiring

Circuit diagram shall be installed in sections around the terminal Must stated around terminal & each terminal must stated its identification label (which terminal for incoming line, outgoing line, ground, incoming neutral & outgoing neutral). Qty of sensor, qty of relay & terminal identification label must stated in connection wiring

Attachment 1 Short Code


CODE
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 - 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

DESCRIPTION
Test all LCD display Test the load switch Display Test Tests the buzzer as well. Total kWh Register Display Key Revision Number & Type Display Tariff Index Test the token reader device Display Power Limit kW Display Tamper Status Display Power Consumption Display software version Display phase power unbalance limit RESERVED BY STS Credit balance (kWh) Cummulative energy (kWh) Voltage rms (V) Current rms (A) Power (W) Total number of token accepted Last credit token accepted Last 2 nd credit token accepted Last 3 rd credit token accepted Last 4 th credit token accepted Last 5 th credit token accepted Last credit kWh Last 2 nd credit kWh

CODE
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99

DESCRIPTION
Last 3 rd credit kWh Last 4 th credit kWh Last 5 th credit kWh Total technical token accepted Last technical token accepted Last 2 nd technical token accepted Last 3 rd technical token accepted Total trip because over load Total meter off Total terminal cover open Total meter cover open Total tampering Energy consumption negative credit Hardware version No. ID Meter Meter Constant Supply Group Code (SGC) Alarm Duration Limit credit threshold Forecast time till the credit is over Last tampering Energy consumption last month Energy consumption last 2 nd month Energy consumption last 3 rd month Over load trip last time (day and time) Over load trip last 2 nd time Last meter off (day and time) Last 2 nd meter off Last terminal meter open Last 2 nd terminal meter open Last cover meter open Maximum power this month Time at maximum power this month Current time Current date Checksum software + fitur

NOTE:
- Short code Number 00-36, adjusted for the terms in the STS system and IEC 62055-41, 2007 "permissible control field values". - italics No. 81 s / d 96, prepared for meters that use the RTC.