Академический Документы
Профессиональный Документы
Культура Документы
0 A Merlin Gerin
ndice
seleccionar el tipo de neutro ................................................................................................ 9 principio de regulacin ........................................................................................................ 10 regular Micrologic 2.0 A ...................................................................................................... 11 regular Micrologic 5.0 A ...................................................................................................... 12 regular Micrologic 6.0 A ...................................................................................................... 13 regular Micrologic 7.0 A ...................................................................................................... 14
15
resetear la sealizacin de defecto y controlar el estado de la pila ................................... 15 testear las funciones diferencial y defecto a tierra .............................................................. 16
mens
17
acceder a los mens ........................................................................................................... 17 medir las intensidades por fase .......................................................................................... 18 consultar los mximos de intensidad .................................................................................. 19 actualizar los mximos de intensidad ................................................................................. 20 consultar las regulaciones ................................................................................................... 21
anexo tcnico
22
curvas de disparo ................................................................................................................ 22 cambio del regulador de largo retardo ................................................................................ 24 selectividad lgica (ZSI) ...................................................................................................... 25 visualizacin alfanumrica .................................................................................................. 26 memoria trmica ................................................................................................................. 27
MERLIN GERIN
100 %
40 %
menu
long time
Ir .7 .6 .5 .4
.8
x In
alarm
Ir
Isd
instantaneous
Isd
3 4 5 6 8 10 x Ir
setting
2.5 2 1.5
Micrologic 5.0 A X Y Z
X : tipo de proteccin: c 2 para una proteccin de base. c 5 para una proteccin selectiva. c 6 para una proteccin selectiva + tierra. c 7 para una proteccin selectiva + diferencial. Y : versin de la unidad de control: identificacin de las diferentes generaciones de unidades de control: 0 para la 1.a versin. Z : tipo de medida: c A para "ampermetro". c P para "potencia". c H para "armnico".
100 %
40 %
menu
long time
Ir .7 .6 .5 .4
.8
x In
alarm
0
instantaneous
Ir
Isd
Ii
short time
Isd
4 5 3 6 8 10 x Ir
tsd
(s)
.4 .4 .3
0
Ii
2.5 2 1.5
on
.3 .2 .1
.2 .1
I t
delay
6 4 3 2
setting
8 10 12 15 off x In
I t on
100 %
40 %
I t off
menu
long time
Ir .7 .6 .5 .4 Isd
.8
x In
alarm
Ir
Isd
Ii
Ig
short time
instantaneous
3 2.5 2 1.5
4 5 6 8 10 x Ir
tsd
(s)
on tg
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
Ii 4 3
8 10 12 15 off 2 x In
test
setting
Ig
D E F G C H B I A
ground fault
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
Proteccin tierra
off
100 %
40 %
menu
long time
Ir .7 .6 .5 .4
.8
x In
alarm
0
10 12 15 off
test
Ir
Isd
Ii
In
short time
tsd
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
Ii
instantaneous
6 4 3 2
off
x In
Proteccin diferencial
MERLIN GERIN
01 02 03 04 05 06 07 08 09 10 11 12 13
fijacin superior fijacin inferior tapa de proteccin de las regulaciones apertura de la tapa de proteccin de las regulaciones precinto de la tapa de proteccin de las regulaciones regulador de largo retardo tornillo de fijacin del regulador de largo retardo conexin con el interruptor automtico unin infrarrojos con interface de comunicacin bornero de conexionado exterior ubicacin de la pila visualizacin alfanumrica ampermetro y diagrama de barras trifsico
1 10
Micro logic 7.0 A
31 12 11 13
100 %
9
7
alarm
30 29
40 %
menu
Ir
long
time
tr
.8 .9 .7 .95 .6 .98 .5 1 .4 x In
(s) 4
2 1 .5
8 12 16 20 24
Ir at 6
5 6 3 4
Selectores de regulacin 14 15 16 17 18 19 20 21 22 23 umbral largo retardo Ir temporizacin largo retardo tr umbral corto retardo Isd temporizacin corto retardo tsd umbral instantneo Isd umbral instantneo Ii umbral Ig de proteccin tierra temporizacin tg de proteccin tierra umbral In de proteccin de intensidad diferencial temporizacin t de proteccin de corriente diferencial
Micrologic 7.0 A
Micrologic 2.0 A 28
long time
24 25 26 27
Ir
Micrologic 7.0 A
14 15
.7 .6 .5 .4
.8
tr
(s) 4 .9 .95 2 .98 1 1 .5
alarm
x In
at 6 Ir
12 16 20 24
instantaneous
Isd
31
3 4 5 6 8 10 x Ir
18
2.5 2 1.5
Sealizacin
setting
12
24 led de sealizacin de disparo largo retardo 25 led de sealizacin de corto retardo o instantneo 26 led de sealizacin de disparo por defecto a tierra o diferencial 27 led de sealizacin de disparo despus de una autoproteccin 28 testigo luminoso de sobrecarga Navegacin 29 tecla de navegacin de los mens 30 tecla de navegacin de los submens 31 tecla de confirmacin de sealizacin de disparo y de control de estado de la pila Test 32 botn test de proteccin de intensidad diferencial o defecto a tierra 33 toma de test
33
13
100 %
Micrologic 5.0 A
28
long time
40 %
14
Ir .7 .6 .5 .4
.8
tr .9 .95 .98 1
(s) 4
alarm
2 1 .5
at 6 Ir
29 14 15 16 17 22 23
Ir
menu
30
alarm
15 16 17 19
x In
12 16 20 24
instantaneous
short time
Isd
3 4 5 6 8 10 x Ir
setting
tsd
(s)
.4 .4 .3 .2 .1
I t
delay 2
Ii 4 3
long time
.7 .6 .5 .4
.8
x In
28 7
2.5 2 1.5
.3 .2 .1
on
6 8 10 12 15 off 2 x In
short time
instantaneous
Isd
3 4 5 6 8 10 x Ir
setting
tsd
(s)
2.5 2 1.5
on
.3 .2 .1
.4 .4 .3
2
Ii
.2 .1
33
4 3 2 x In
I t
0 off
10 12 15 off
test
19 32 33
Micrologic 6.0 A 15 14 17 16 21 20
long time
delay
IDn
(A)
DI 5 7
(ms)
230
350
800
2 1 .5
10 140 20 30 60
earth leakage
Ir .7 .6 .5 .4
.8
x In
alarm
28 7
short time
instantaneous
tsd
(s)
.4 .4 .3 .2 .1 0 off
Ii 6 4 3 2
.3 .2 .1
on tg
I t
delay
x In
10 12 15 off
test
19 32 33
Ig D C B A
F G H I
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
off
ground fault
MERLIN GERIN
Micrologic 2.0 A
t 1
3 0 Ir Isd I
1: umbral Ir (largo retardo) 2: temporizacin tr (largo retardo) 3: umbral Isd (instantneo) Micrologic 5.0 A, 6.0 A, 7.0 A
t 1
I t on
2
Micrologic 6.0 A
t
I t on
2
Micrologic 7.0 A
t
2
I t off
2
3 4 5 0 Ir Isd Ii I
0 Ig
1 2
I t off
1 2
In
1: umbral Ir (largo retardo) 2: temporizacin tr (largo retardo) 3: umbral Isd (corto retardo) 4: temporizacin tsd (corto retardo) 5: umbral Ii (instantneo)
La proteccin largo retardo protege los cables (fases y neutro) contra las sobrecargas. La medida se da en valor eficaz (RMS). Memoria trmica La memoria trmica representa el modo permanente del estado de calentamiento de los cables antes y despus del disparo del aparato, independientemente del valor de la intensidad (sobrecarga o no). La memoria trmica optimiza el tiempo de disparo de largo retardo del interruptor automtico en funcin del calentamiento de los cables. El tiempo de enfriamiento de los cables tenido en cuenta por la memoria trmica es del orden de 15 min.
2.0 A y 5.0 A
0,4 0,5 0,6 0,7 0,8 0,9 0,95 0,98 1 otros umbrales de regulacin o anulacin por cambio del regulador 12,5 25 0,5 1 0,34 0,69 50 2 1,38 100 4 2,7 200 8 5,5 300 12 8,3 400 16 11 500 20 13,8 600 24 16,6
tr a 1,5 Ir tr a 6 Ir tr a 7,2 Ir
Usted tiene la posibilidad de precisar el valor del umbral Ir cambiando el regulador de largo retardo de la unidad de control. Para efectuar este cambio, remtase al anexo tcnico Cambio del regulador de largo retardo.
MERLIN GERIN
Para consultar las caractersticas y el tipo de cableado externo ZSI, remtase al anexo tcnico selectividad lgica. La maleta de ensayo permite testear el cableado de la selectividad lgica (entre varios interruptores automticos). c La proteccin corto retardo protege la red contra los cortocircuitos impedantes. c La parametrizacin de la temporizacin corto retardo permite asegurar la selectividad con un interruptor aguas abajo. c La medida es de tipo valor eficaz (RMS). c La opcin I2t ON y I2t OFF permite mejorar la selectividad con las protecciones aguas abajo. c Seleccin de las curvas I2t en proteccin corto retardo: v I2t OFF seleccionado: la proteccin es a tiempo constante. v I2t ON seleccionado: la proteccin es a tiempo inverso en I2t hasta 10 Ir. A partir de aqu, la proteccin es a tiempo constante. c Selectividad lgica (ZSI). Las protecciones corto retardo y tierra permiten una selectividad cronomtrica temporizando los aparatos aguas arriba para dejar tiempo a los aparatos aguas abajo de eliminar el defecto. La selectividad lgica (Zone Selective Interlocking) permite obtener una selectividad total entre interruptores por cableado externo. Umbral Isd y temporizacin tsd
Proteccin instantnea
c La proteccin instantnea protege la red contra los cortocircuitos francos. A diferencia de la proteccin corto retardo, la proteccin instantnea no tiene regulacin de la temporizacin. La orden de apertura viene dada al interruptor automtico cuando la intensidad supera un umbral determinado, con una temporizacin fija de 20 ms. c La medida de la intensidad es en valor eficaz (RMS). Umbral Isd
2.0 A
1,5 2 2,5 3 4 5 6 8 10
Umbral Ii
MERLIN GERIN
Tipo de neutro
Neutro no protegido Neutro mitad proteccin
Descripcin
La red no necesita proteccin del neutro. La seccin del conductor de neutro es la mitad de la de los conductores de las fases: c El umbral largo retardo Ir para el neutro es igual a la mitad de su umbral de regulacin. c El umbral corto retardo Isd para el neutro es igual a la mitad de su umbral de regulacin. c El umbral instantneo Isd (Micrologic 2.0 A) para el neutro es igual a la mitad de su umbral de regulacin. c El umbral instantneo Ii (Micrologic 5.0 A) para el neutro es igual a la mitad de su umbral de regulacin. La seccin del conductor de neutro es idntica a la de los conductores de fase: c El umbral de largo retardo Ir para el neutro es igual a su umbral de regulacin. c El umbral de corto retardo Isd para el neutro es igual a su umbral de regulacin. c El umbral instantneo Ii o Isd para el neutro es igual a su umbral de regulacin.
c Una intensidad de fuga a tierra circulando por los conductores de proteccin, puede provocar un calentamiento local a nivel de defecto, dependiendo del conductor. La proteccin de tierra tiene por objeto eliminar este tipo de defecto. c La proteccin de tierra comporta dos variantes:
Tipo
Residual
Descripcin
c Determina la intensidad homopolar, es decir, la suma vectorial de las intensidades de fase y neutro. c Detecta los defectos aguas abajo del interruptor automtico. Source Ground Return c Mide directamente por un captador exterior especfico la intensidad de defecto que vuelve al transformador por la toma de tierra. c Detecta los defectos aguas arriba y abajo del interruptor automtico. c Admite una distancia mxima entre el captador y el aparato de 10 m c La proteccin de neutro y la proteccin de tierra son independientes y por tanto acumulables. Umbral Ig y temporizacin tg El umbral y la temporizacin son regulables e independientes uno del otro y son idnticos en residual o Source Ground Return.
6.0 A
A 0,3 0,2 500 A 0 20 80 B 0,3 0,3 640 A 0,1 0,1 80 140 C 0,4 0,4 720 A 0,2 0,2 140 200 D 0,5 0,5 800 A 0,3 0,3 230 320 E 0,6 0,6 880 A 0,4 0,4 350 500 F G 0,7 0,8 0,7 0,8 960 A 1040 A H 0,9 0,9 1120 A I 1 1 1200 A
MERLIN GERIN
c La proteccin diferencial protege principalmente los bienes de equipo contra los contactos indirectos, una intensidad de fuga a tierra puede provocar una subida de tensin de las masas de los bienes de equipo. El umbral de proteccin de In es visualizado directamente en amperios, la temporizacin es a tiempo constante. c Esta proteccin necesita la instalacin de un trafo sumador externo. c En ausencia del regulador de largo retardo, la proteccin diferencial es inoperante. c d inmunizado contra los riesgos de disparos intempestivos. c k Resistencia a las componentes continuas clase A hasta 10 A. Umbral In y temporizacin t
7.0 A
0,5 1 2 3 5 7 10 20 30
60 140
140 200
230 320
350 500
800 1000
long time
Ir .7 .6 .5 .4
.8
x In
alarm
short time
instantaneous
tsd
(s)
on t
(ms)
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
Ii 4 3
6 8 10 12 15 2 off x In
test
100 %
In
(A)
230
350
800
40 %
2 1 .5
10 140 20 30 60
earth leakage
Sealizacin de defecto La autoproteccin (temperatura excesiva o cortocircuito superior a los lmites del aparato) ocasiona el disparo y el encendido del led Ap. Atencin! Si el interruptor automtico permanece cerrado y el led de sealizacin Ap est encendido: Abra el I.A. y contacte con el servicio Post-Venta de Schneider. Atencin! La pila permite el mantenimiento de las sealizaciones de disparo. (Verifique su estado en caso de ausencia de sealizacin)
Seal de disparo despus de una superacin del umbral de largo retardo Ir.
Seal de disparo despus de una superacin del umbral de corto retardo Isd o del umbral instantneo Ii / Isd.
Micrologic 7.0 A
Micrologic 7.0 A
Seal de un disparo despus de la superacin del umbral Ig de proteccin tierra o del umbral In de proteccin diferencial.
Micrologic 7.0 A
Micrologic 7.0 A
MERLIN GERIN
100 %
40 %
MERLIN GERIN
3D+N 3D 4P
/2 4D 4P
MERLIN GERIN
Microlo
gic 7.0
A Microlo
gic 7.0
Ir=
100 %
100 %
40 %
40 %
menu
menu
Microlo
gic 7.0
2. Seleccione el selector. El valor regulado se visualiza automticamente en la pantalla alfanumrica en valor absoluto y segn la unidad de control que se trate. c Intensidad: amperios (A y KA). c Temporizacin: segundos (s). 3. Si no se visualiza ninguna informacin, remtase al anexo tcnico visualizacin alfanumrica. Si no hay intervencin sobre el teclado durante varios segundos, la pantalla vuelve al men principal. 4. Cerrar la tapa de proteccin y proteja las parametrizaciones con un precinto si fuera necesario.
100 %
40 %
menu
La toma de test permite conectar una maleta de ensayo a fin de testear el buen funcionamiento de la unidad de control.
Microlo
gic 7.0
A Microlo
gic 7.0
100 %
100 %
40 %
40 %
menu
menu
10
MERLIN GERIN
.7 .6 .5 .4 Isd
.8
alarm
x In
.9 .95 .98 1
instantaneous
3 4 5 2.5 6 2 8 10 1.5 x Ir
setting
In = 2000 A
In = 2000 A
t Ir
Regular la temporizacin
long time
tr = 1 s
tr
(s)
alarm
2 1 .5
at 6 Ir
12 16 20 24
tr
MERLIN GERIN
11
In = 2000 A
alarm
.8 .9 .95 .6 .98 .5 .4 1 x In .7
short time
Ir = 0.7 Isd = 2
instantaneous
Ii = 3
4 5 6 8 10 x Ir
Ii 4 3
6 8 10 12 15 2 off x In
setting
In = 2000 A
In = 2000 A
Regular las temporizaciones Remtase a las pginas 4 y 7 para seleccionar los intervalos de regulacin.
Umbrales Curva I2t ON
t Ir
long time
tr
(s)
8 12 16 2 1 20 24 .5 4
at 6 Ir
alarm
tr = 1 s
tsd = 0.2 s
short time
tsd
(s)
on
.4 .4 .3 .2 .3 .2 .1 .1 2 0
I t
delay
I2t on
I2t off
Isd Ii 0 I
Isd Ii 0 I
tr
tr
tsd
tsd
12
MERLIN GERIN
.8
alarm
x In
.9 .95 .98 1 Ii
instantaneous
short time
4 3
6 8 10 12 15 2 x In off
test
Isd = 2 Ii = 3 B
Ig D E F C B A I G H
ground fault
In = 2000 A
In = 2000 A
Regular las temporizaciones Remtase a las pginas 4 y 5 para seleccionar los intervalos de regulacin.
Umbrales Curva I2t ON
t Ir
long time
tr
(s) 4
alarm
2 1 .5
at 6 Ir
12 16 20 24
tr = 1 s
short time
tsd
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
tsd = 0.2 s
I2t on
test
off
I2t off
Isd Ii 0 I 0
Isd Ii I
ground fault
tg
(s)
.4 .4 .3
2
.3 .2 .1
on
.2 .1
I t
0 off
tg = 0.2 s
Ig
Ig
tr
tr
tsd
tsd
0 t
0 t
tg
tg
MERLIN GERIN
13
.8 .9 .95 .98 x In 1 Ii
alarm
In = 2000 A Ir = 0.7
instantaneous
short time
Isd = 2 Ii = 3 In = 1 A
6 8 10 4 12 3 15 off 2 x In
test
In
(A)
3 5 7 10 20 30
2 1 .5
ground fault
In = 2000 A
In = 2000 A
Regular las temporizaciones Remtase a las pginas 4 y 7 para seleccionar los intervalos de regulacin.
Umbrales Curva I2t ON
t Ir
long time
tr
(s)
4 8 12 16 2 20 1 24 .5
at 6 Ir
alarm
tr = 1 s
short time
tsd
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
tsd = 0.2 s
off
test
I2t on
I2t off
Isd Ii 0 t I
Isd Ii 0 I
ground fault
(ms) 230
350
800
140 60
t = 140 ms
In
tr
tr
tsd
tsd
0 t
14
MERLIN GERIN
Micrologic 7.0 A
Una presin sobre la tecla test de la unidad de control permite visualizar el estado de la pila.
Cambio de la pila de la unidad de control En caso de reposicin, utilizar obligatoriamente una pila de las caractersticas siguientes: c Pila de litio. c Tamao: 1,2 AA 3,6 V - 850 mA/H. c Tipo: SAFT LS3 SONNENSCHEIN TEL-S. c Duracin: 10 aos.
2. Extraer la pila.
100 %
40 %
100 %
40 %
MERLIN GERIN
15
Microlo
gic 7.0
100 %
40 %
menu
16
MERLIN GERIN
mens
acceder a los mens
Simbolismo utilizado:
Las unidades de control Micrologic permiten acceder a tres mens: c Medida de intensidades por fase I1, I2, I3, In, as como la intensidad de tierra Ig para la unidad de control Micrologic 6.0 A y diferencial In para la unidad de control Micrologic 7.0 A. c Memorizacin de las intensidades mx. de las fases I1, I2, I3, In, as como la intensidad de tierra mx. Ig para la unidad de control Micrologic 6.0 A y de intensidad diferencial m x. In para la unidad de control Micrologic 7.0 A. c Consulta de los umbrales y temporizaciones de regulacin. 1. medidas 2. maxmetro
Max
3. consulta
Ir=
Usted puede en cualquier instante dejar de intervenir sobre las medidas de intensidades, intensidades mximas registradas en el maxmetro o consultar las regulaciones: Micrologic vuelve automticamente al cabo de varios segundos al men principal de la intensidad de fase ms cargada. Gracias a los selectores de regulacin de las protecciones se puede visualizar directamente en la pantalla alfanumrica el valor del parmetro regulado.
100 %
100 %
100 %
40 %
menu
40 %
menu
40 %
menu
Presionar en men para acceder a los valores de las intensidades mximas medidas por el maxmetro.
100 %
40 %
MERLIN GERIN
17
mens
medir las intensidades por fase
La lectura de las intensidades se efecta a partir del men principal. Despus de intervenir sobre el aparato, la unidad visualiza el valor de la intensidad de la fase ms cargada.
Men medidas Ejemplo: la fase 1 es la ms cargada.
100 %
100 %
40 %
40 %
100 %
Presionar la tecla indicada para pasar a la medidad de intensidad I2. Medir la intensidad I3.
Presionar la tecla indicada para ver la medida de la intensidad I3. Medir la intensidad In.
40 %
100 %
100 %
40 %
40 %
Presionar la tecla indicada para pasar a la medida de intensidad In si el aparato est conectado al neutro. Medir la intensidad Ig (Micrologic 6.0 A) o In (Micrologic 7.0 A).
Presionar la tecla indicada para pasar a la medida de la intensidad de proteccin tierra Ig o a la intensidad diferencial In. Volver a la medida de intensidad I1.
100 %
100 %
40 %
40 %
Presionar la tecla indicada para pasar a la medida de intensidad I1. 18 MERLIN GERIN
mens
consultar los mximos de intensidad
La lectura de intensidades mximas se efecta a partir de un men de consulta de mximos de intensidad. Despus de intervenir sobre el aparato, la unidad de control vuelve al men principal.
Men maxmetro.
100 %
100 %
40 %
Max A
40 %
Presionar la tecla indicada para pasar a la lectura de intensidad I3 mx. Consultar la intensidad In mx.
MAX
MAX A
100 %
100 %
40 %
40 %
Presione en la tecla indicada para pasar a la lectura de intensidad In mx. si el aparato est conectado al neutro. Consultar la intensidad mx. o In mx.
MAX A
Presionar en la tecla indicada para pasar a la lectura de intensidad Ig mx. (Micrologic 6.0 A) o In mx. (Micrologic 7.0 A). Consultar la intensidad I1 mx.
MAX A
100 %
100 %
40 %
40 %
Presionar la tecla indicada para volver a la lectura de la intensidad I1 mx. MERLIN GERIN 19
mens
actualizar los mximos de intensidad
La actualizacin de los mximos de intensidad se efecta a partir de un men de consulta de los mximos de intensidad. Despus de intervenir sobre la unidad, sta vuelve al men principal.
Men maxmetro.
Actualice.
MAX A
MAX A
Max A
100 %
100 %
100 %
40 %
40 %
40 %
100 %
40 %
menu
Presionar la tecla indicada durante 3 o 4 segundos: el valor de la intensidad parpadea y vuelve al valor de intensidad.
Presionar la tecla indicada para seleccionar otro valor mximo a actualizar o volver al men principal.
20
MERLIN GERIN
mens
consultar las regulaciones
Unidad de control Acceder al men de consulta de las regulaciones de proteccin: el umbral Ir es el primer parmetro presentado.
Umbral instantneo Ii
MERLIN GERIN
21
anexo tcnico
curvas de disparo
Proteccin largo retardo e instantneo Micrologic 2.0 A
Proteccin largo retardo, corto retardo e instantneo Micrologic 5.0 A, 6.0 A y 7.0 A
22
MERLIN GERIN
MERLIN GERIN
23
anexo tcnico
cambio del regulador de largo retardo
Seleccionar el regulador largo retardo
Las unidades de control Micrologic A permiten la eleccin de ms de un intervalo de regulacin de largo retardo lr. Esto se consigue cambiando el regulador largo retardo. Los reguladores de largo retardo disponibles son los siguientes:
Referencia
33542 33543 33544 33545
Efectuar las operaciones siguientes: 1. Abrir el interruptor automtico. 2. Abrir la tapa de proteccin de la unidad de control. 3. Desatornillar completamente el tornillo de fijacin del regulador.
Atencin! Toda intervencin sobre el regulador largo retardo precisa la verificacin y la regulacin de todos los parmetros de proteccin.
4. Extraer el regulador.
Atencin! En caso de ausencia del regulador de largo retardo, la unidad de control puede funcionar incorrectamente de las siguientes maneras: c Que el umbral Ir de proteccin largo retardo sea de 0,4. c Que la temporizacin tr de proteccin largo retardo corresponda al valor del selector. c Que la proteccin diferencial est inoperante.
24
MERLIN GERIN
anexo tcnico
selectividad logica (ZSI)
Principio de funcionamiento
c Defecto en A. El aparato aguas abajo n. 2 elimina el defecto y enva la informacin al aparato aguas arriba n.1 que respeta la temporizacin corto retardo tsd o tierra tg en los que est regulada. c Defecto en B. El aparato aguas arriba detecta el defecto sin informacin por parte del aparato aguas abajo n. 2. Este dispara inmediatamente sin tener en cuenta la temporizacin a la que est regulado y enva, si est conectado, la informacin a un aparato que hubiere aguas arriba que respetara su temporizacin tsd o tg.
Nota: No regular la temporizacin tsd o tg a cero de un interruptor susceptible de recibir una orden ZSI ya que se perdera la selectividad.
La selectividad lgica (Zone Selective Interlocking) permite la unin entre aparatos aguas arriba y abajo por una seal elctrica lgica (0 o 5 voltios). c Micrologic 5.0 A, 6.0 A, 7.0 A. c Micrologic 5.0 P, 6.0 P, 7.0 P. c Micrologic 5.0 H, 6.0 H, 7.0 H.
Cableado Atencin! Los aparatos equipados con la proteccin ZSI, deben, en el caso de no utilizar dicha proteccin, estar equipados de un puente cortocircuitante de las bornas Z3, Z4, Z5. Si este puente no se instala, las temporizaciones de la proteccin corto retardo y tierra sern cero por defecto, sea cual sea la posicin de los selectores. Las indicaciones Z1 a Z5 corresponden a la de los borneros del aparato.
c Impedancia mx.: 2,7 / 300 m. c Capacidad de los bornes: 0,4 a 2,5 mm2. c Seccin mx. de los hilos (conductores y aislante): 3,5 mm2. c Tipo: mono o multibrins. c Longitud mx.: 3000 m. c Lmites de interconexin entre aparatos: v El comn ZSI - OUT - SOURCE (Z1) y la salida ZSI - OUT (Z2) pueden ser conectados en 10 entradas como mximo. v 100 aparatos como mximo pueden ser conectados en una entrada ZSI IN CR (Z4) o GF (Z5). c El cableado se realiza de la salida ZSI OUT (Z2) del aparato aguas arriba hacia las entradas ZSI IN CR (Z4) y / o GF (Z5) del aparato aguas abajo.
y/o
Z1 Z2 Z3 Z4 Z5
Z1 Z2 Z3 Z4 Z5
anexo tcnico
visualizacin alfanumrica
Para la conexin de una alimentacin auxiliar, remtase a los esquemas elctricos existentes en el manual del usuario del aparato.
c La visualizacin de las medidas es a propia intensidad. La pantalla alfanumrica se borra cuando la intensidad es inferior a 0,2 In (In: intensidad nominal). c La lectura es inoperante en los casos siguientes: v Intensidad inferior a 1 In para 1 fase. v Intensidad inferior a 0,4 In para 2 fases. v Intensidad inferior a 0,2 In para 3 fases. c El maxmetro no funciona para intensidades estrictamente inferiores a 0,2 In. Estas tres funciones pueden ser mantenidas con la ayuda de la alimentacin auxiliar. En todos los casos, las protectiones largo retardo, corto retardo, instantneo y tierra son a propia intensidad.
26
MERLIN GERIN
anexo tcnico
memoria trmica
Memoria trmica
La memoria trmica permite simular el calentamiento y el enfriamiento inducidos en los conductores por las variaciones de intensidad. Estas variaciones pueden ser generadas por: c Arranque frecuente de motores. c Cargas fluctuantes cercanas a los umbrales de regulacin. c Cierres reiterados sobre defecto. Las unidades de control dotadas de memoria trmica (contrariamente a la proteccin trmica bilmina) no reaccionan frente a este tipo de sobrecargas cuya duracin es demasiado corta para provocar el disparo. Sin embargo, cada una de estas sobrecargas induce una elevacin de la temperatura cuyos efectos repetidos pueden provocar calentamientos en la instalacin. Durante una sobrecarga, las unidades de control, dotadas de memoria trmica, memorizan el calentamiento provocado por la intensidad. Toda sobrecarga intempestiva genera un calentamiento que es memorizado. La memorizacin de este valor comporta una reduccin del tiempo de disparo.
Todas las unidades de control estn dotadas de una memoria trmica en estndar. c Para todas las protecciones, antes de un disparo, las constantes de tiempo de calentamiento y de enfriamiento son idnticas y dependen de las temporizaciones correspondientes: v Si la temporizacin es pequea, la constante de tiempo es pequea. v Si la temporisation es elevada, la constante de tiempo es elevada. c En proteccin largo retardo, despus de disparo, la curva de enfriamiento es simulada por la unidad de control. Todo rearme del aparato antes de la expiracin de la constante de tiempo (del orden de 15 min), tiene como consecuencia la disminucin del tiempo de disparo dado por las curvas.
MERLIN GERIN
27
delegaciones:
ANDALUCIA OCCIDENTAL Avda. de la Innovacin, s/n Edificio Arena 2, planta 2 41020 SEVILLA Tel.: 95 499 92 10 Fax: 95 425 45 20 E-mail: del_sev@schneiderelectric.es ANDALUCIA ORIENTAL Avda. de Andaluca, 31, esc. dcha. Entreplanta, oficina 2 29006 MALAGA Tel.: 95 233 16 08 Fax: 95 231 25 55 ARAGON Polgono Argualas, nave 34 50012 ZARAGOZA Tel.: 976 35 76 61 Fax: 976 56 77 02 E-mail: del_zar@schneiderelectric.es CANARIAS General Vives, 35, bajos 35007 LAS PALMAS DE G. C. Tel.: 928 26 60 05 Fax: 928 22 05 52 E-mail: Del_Can@schneiderelectric.es CASTILLA-RIOJA Avda. Reyes Catlicos, 42, 1 09005 BURGOS Tel.: 947 24 43 70 Fax: 947 23 36 67 E-mail: del_bur@schneiderelectric.es CENTRO Ctra. de Andaluca, km 13 Polgono Industrial Los Angeles 28906 GETAFE (Madrid) Tel.: 91 624 55 00 Fax: 91 682 40 48 E-mail: del_mad@schneiderelectric.es CENTRO-NORTE Pso. Arco Ladrillo, 64 Centro Madrid, portal 1, planta 2, oficinas 17 y 18 47008 VALLADOLID Tel.: 983 47 94 16 - 983 22 46 25 Fax: 983 47 90 05 - 983 47 89 13 E-mail: del_vall@schneiderelectric.es EXTREMADURA Obispo San Juan de la Rivera, 9 Edificio Badajoz, 2 M 06001 BADAJOZ Tel.: 924 22 45 13 Fax: 924 22 47 98 LEVANTE Carrera de Malilla, 83 A 46026 VALENCIA Tel.: 96 335 51 30 Fax: 96 374 79 98 E-mail: del_val@schneiderelectric.es NORDESTE Sicilia, 91-97, 6 08013 BARCELONA Tel.: 93 484 31 01 Fax: 93 484 31 57 E-mail: del_bcn@schneiderelectric.es
NOROESTE Jos Luis Bugallal Marchesi, 20 Entreplanta (esc. de caracol) 15008 A CORUA Tel.: 981 16 90 26 Fax: 981 23 02 24 E-mail: del_cor@schneiderelectric.es NORTE Ribera de Axpe, 50, 2, Edif. Udondo 48950 ERANDIO (Vizcaya) Tel.: 94 480 46 85 Fax: 94 480 29 90 E-mail: del_bil@schneiderelectric.es
GALICIA SUR Ctra. Vella de Madrid, 33, bajos 36214 VIGO Tel.: 986 27 10 17 Fax: 986 27 70 64 E-mail: del_vig@schneiderelectric.es GIRONA Pl. Josep Pla, 4, 1, 1 17001 GIRONA Tel.: 972 22 70 65 Fax: 972 22 69 15 GUADALAJARA-CUENCA Ctra. de Andaluca, km 13 Polgono Industrial Los Angeles 28906 GETAFE (Madrid) Tel.: 91 624 55 00 Fax: 91 624 55 42 GUIPUZCOA Avda. de Rekalde, 59, 1 planta, Edificio Aguila 20009 SAN SEBASTIAN Tel.: 943 36 01 36* Fax: 943 36 48 30 E-mail: del_don@schneiderelectric.es LEON Moiss de Len, bloque 51, planta 1, letra E 24006 LEON Tel.: 987 20 05 75 Fax: 987 26 17 13 E-mail: del_leo@schneiderelectric.es LLEIDA Prat de la Riba, 18 25004 LLEIDA Tel.: 973 22 14 72 Fax: 973 23 50 46 MURCIA Avda. de los Pinos, 11, Edificio Azucena 30009 MURCIA Tel.: 968 28 14 61 Fax: 968 28 14 80 NAVARRA Polgono Ind. de Burlada, Iturrondo, 6 31600 BURLADA (Navarra) Tel.: 948 29 96 20 Fax: 948 29 96 25 RIOJA Po XII, 14, 11 F 26003 LOGROO Tel.: 941 25 70 19 Fax: 941 25 70 19 SANTANDER Avda. de los Castros, 139 D, 2 D 39005 SANTANDER Tel.: 942 32 10 38 - 942 32 10 68 Fax: 942 32 11 82 TENERIFE Custodios, 6, 2, El Cardonal 38108 LA LAGUNA (Tenerife) Tel.: 922 62 50 50 Fax: 922 62 50 60
subdelegaciones:
ALBACETE Paseo de la Cuba, 21, 1 A 02005 ALBACETE Tel.: 967 24 05 95 Fax: 967 24 06 49 ALICANTE Martin Luther King, 2 Portera 16/1, entreplanta B 03010 ALICANTE Tel.: 96 591 05 09 Fax: 96 525 46 53 ASTURIAS Muoz Degrain, 6, 1, oficinas 6 y 7 33007 OVIEDO Tel.: 98 527 12 91 Fax: 98 527 38 25 E-mail: del_ovi@schneiderelectric.es BALEARES Eusebio Estada, 86, bajos 07009 PALMA DE MALLORCA Tel.: 971 29 53 73 Fax: 971 75 77 64 CACERES Avda. de Alemania Edificio Descubrimiento, local TL 2 10001 CACERES Tel.: 927 21 33 13 Fax: 927 21 33 13 CADIZ-CEUTA San Cayetano, s/n Edif. San Cayetano, 1, 17 11402 JEREZ DE LA FRONTERA (Cdiz) Tel.: 956 34 33 66 - 956 34 34 00 Fax: 956 34 34 00 CASTELLON Bernat Artola, 9, 4 A 12004 CASTELLON Tel.: 964 26 09 50 Fax: 964 26 09 50 CORDOBA-JAEN Arfe, 18, planta 2 14011 CORDOBA Tel.: 957 23 20 56 Fax: 957 23 20 56
Pl. Dr. Letamendi, 5-7 08007 BARCELONA Tel.: 93 484 31 00 Fax: 93 484 33 07 http://www.schneiderelectric.es
En razn de la evolucin de las normativas y del material, las caractersticas indicadas por el texto y las imgenes de este documento no nos comprometen hasta despus de una confirmacin por parte de nuestros servicios.
020503 C00