DESIGN PARAMETERS
1. THE ENTIRE BUILDING SHALL BE PROTECTED BY A NEW WET PIPE SPRINKLER SYSTEM. THE FIRE PROTECTION SYSTEM SHALL BE FED FROM AN EXISTING FIRE SYSTEM MAIN CONNECTED TO THE POST WATER SYSTEM. WATER FLOW DEMAND CALCULATIONS CAN BE FOUND ON THIS SHEET. THE SYSTEM SHALL BE HYDRAULICALLY CALCULATED FOR THE MOST HYDRAULICALLY REMOTE AREA. THE WATER FLOW DEMAND SHALL BE AS FOLLOWS:
in
ee
ring
& Servic
D es
iv i
Mark Description Date Appr.
2. 3. 4.
LIGHT HAZARD: DESIGN DENSITY: 0.1 GPM/SQUARE FOOT DESIGN AREA: 3000 SQUARE FEET HOSE ALLOWANCE: 250 GPM ORDINARY HAZARD, GROUP 1: DESIGN DENSITY: 0.15 GPM/SQUARE FOOT DESIGN AREA: 3000 SQUARE FEET HOSE ALLOWANCE: 500 GPM 5. THE FOLLOWING APPLICABLE STANDARDS WERE USED TO EVALUATE THE FIRE PROTECTION REQUIREMENTS: NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS, LATEST EDITION. UFC 3-600-01 DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES.
Task Order No: FOR BIDDING PURPOSES ONLY
PRESSURE, PSI
6. FIRE DETECTION AND ANNUNCIATION: THE FIRE ALARM SYSTEM SHALL SHOW TAMPER VALVE STATUS AND WATER FLOW TO INDIVIDUAL FIRE PROTECTION ZONES. A FIRE HORN AND STROBE SHALL BE PROVIDED ON THE EXTERIOR OF THE BUILDING. SEE THE SPECIFICATIONS FOR ADDITONAL REQUIREMENTS.
Rev.
N1.8 5 2000
JWR
Dwn by:
CHECK VALVE
RDY
WALL MOUNTED TEST HEADER B FIRE DEPARTMENT CONNECTION FREE STANDING SIAMESE EXISTING NEW
4" FLOW ALARM 4" CHECK VALVE & 1/2" BALL VALVE AS FULLY SPRINKLERED SPACE 4" STORZ FIRE DEPARTMENT PUMPER CONNECTION 10" SUCTION MAIN FIRE SYSTEM RISER FTR FAC FAC HVA A FCP BUILDING FIRE CONTROL PANEL FIRE ALARM TRANSMITTER FIRE SYSTEM ANNUNCIATOR FIRE ALARM COMMUNICATOR HVAC CONTROL PANEL CRAWL SPACE FIRST FLOOR 4" 10"
TS TS TS TS TS
BUILDING NO.
COL O
RA
I
REG I DO ST
P.
BR E S
L IN
EE
32681
K EV
1
F-001
SS
I ON
NG AL E
THE SEAL APPEARING ON THIS DOCUMENT WAS AUTHORIZED BY KEVIN P. BRESLIN JR. P.E. 32681 ON 11/12/09
IN
(2) 4" ALARM CHECK VALVE & 2" MAIN DRAIN VALVE & PIPING - DRAIN TO FLOOR DRAIN.
422
Contr No.
F-001
4"
4"
CONSULTING ENGINEERS 6243 I.H. 10 W., SUITE 200 SAN ANTONIO, TEXAS 78201-2022 FAX 210-736-9258 PH 210-736-6623
JWR
RDY
Submitted by:
Reviewed by:
Designed by:
DESIGN FILE:
Ckd by:
Contract No: