Вы находитесь на странице: 1из 11

Copyright 2005 IEEE. Reprinted from IEEE PCIC CONFERENCE, SEPTEMBER 2005, PAPER 32.

. This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of any products or services of Powell Electrical Manufacturing Company. Internal or personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution must be obtained from the IEEE by writing to pubs-permissions@ieee.org. By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

CT SATURATION CALCULATIONS ARE THEY APPLICABLE IN THE MODERN WORLD? PART I, THE QUESTION
Copyright Material IEEE Paper No. PCIC-2005-32 Roy E. Coss, Jr., P.E. Senior Member, IEEE Powell Electrical Systems, Inc. 8550 Mosley Houston, Texas 77075 USA rcosse@powl.com Donald G. Dunn Senior Member, IEEE Lyondell Chemical Company 2502 Sheldon Road Channelview, Texas 77530 USA donald.dunn@ieee.org Robert M. Spiewak, P.E. Member, IEEE PolAmex Engineering & Design Svc, Inc. 14135 Haynes Drive Houston, Texas 77069 USA robert_spiewak@polamexinc.com

Abstract - Previously, ANSI/IEEE relay current transformer (CT) sizing criteria was based on traditional symmetrical calculations usually discussed by technical articles and manufacturers guidelines. In 1996, IEEE Standard C37.1101996 [1] introduced (1 + X/R) offset multiplying, current asymmetry and current distortion factors; officially changing the CT sizing guideline. A critical concern is the performance of fast protective schemes (instantaneous or differential elements) during severe saturation of low ratio CTs. Will the instantaneous element operate before the upstream breaker relay trips? Will the differential element mis-operate for out-ofzone faults? The use of electromagnetic and analog relay technology does not assure selectivity. Modern microprocessor relays introduce additional uncertainty into the design/verification process with different sampling techniques and proprietary sensing/recognition/trip algorithms. This paper discusses the application of standard CT accuracy classes with modern ANSI/IEEE CT calculation methodology. This paper is the first of a two-part series; Part II, the Findings provides analytical waveform analysis discussions to illustrate the concepts conveyed in Part I. Index Terms Accuracy Class, Asymmetrical Current, CT Burden, CT Saturation, DC Offset, Digital Filter, and X/R ratio.

symmetrical primary current as the basis when performing CT calculations. Parts I and II of this paper review modern CT sizing calculations using 1+X/R to determine if the results are practical and if standard CTs can be used. To augment the 1+X/R consideration, a waveform approach is introduced. Because modern industrial electrical power systems are typically resistance grounded, ground relaying is considered beyond the present scope of this paper. Although the paper focus is microprocessor based relays, the CT discussions are applicable to both traditional and modern relays.

52

Feeder Relay

Fig. 1. Typical Feeder Relay Example.

I. INTRODUCTION
Initially, CT sizing criteria was based on traditional symmetrical calculations usually explained by technical articles from major electrical equipment manufacturers. In the mid-1980s, relay performance and asymmetrical secondary current waveforms appeared as part of a continuing investigation by Stanley Zocholl and William Kothheimer; this is evidenced by the series of technical papers they published concerning this topic [2, 3, 4, 5, 6, 7 and 8]. Later, the IEEE Power Engineering Society Relay Committee and other notable authors wrote technical papers addressing this topic [9, 10]. In 1996, IEEE Standard C37.110-1996 formalized some of this prior work by introducing (1 + X/R) offset multiplying factor for determining the CT secondary voltage requirement. This officially changed the guideline basis for sizing CTs. Because C37-110.1996 recognizes primary current asymmetry and CT saturation due to the DC offset current component, it is no longer acceptable to use

II. THE CONCERNS


A critical concern is the performance of the relays instantaneous element during severe saturation of low ratio CTs. Will the instantaneous element operate before the upstream main breaker relay trips? It is obvious the instantaneous element will eventually trip, but will it trip in an anticipated, repeatable manner before the upstream main breaker relay operates? Typical applications that involve either non-operation or nuisance tripping concerns are as follows (Fig. 1): 1) Feeder instantaneous overcurrent (ANSI 50) relay 2) Motor self-balancing differential (ANSI 87M) instantaneous relay 3) Generator differential (ANSI 87G) protection relay This paper focuses on traditional CT sizing criteria during fault conditions for instantaneous element (ANSI device 50) only.

IP

IDEAL CT

IST IE VS ZE

IS

RS

XL

CT TERMINAL

VB

ZB

N1 where IP N2 :N1 Vs IST IE ZE is is is is is is

N2 IS RS XL VB ZB leads) is is is is is

CT TERMINAL the secondary load current the secondary resistance the leakage reactance (negligible in Class C CT's) the CT terminal voltage across external burden the burden impedance (includes RR-secondary devices and RW-

the primary current the CT turns ratio the secondary exciting voltage the total secondary current the exciting current the exciting impedance

Fig. 2. Equivalent circuit of a current transformer [1].

III. TRADITIONAL CT CALCULATION SIZING APPROACH


Protective relaying has always combined art and applied physics, with the goal of issuing tripping commands during abnormal electrical system conditions. Protective relaying systems are typically straight forward with current transformers, wiring and relays. Fig. 2 shows the equivalent circuit of a current transformer with a load impedance [2]. Traditionally, manufacturers literature and industry standards provided calculation analysis guidance to ensure CTs were adequately sized for both ratio and accuracy class. One authors professional development of performing CT saturation calculations began with (1) to determine the minimum CT Accuracy class.

than the ANSI switchgear interrupting X/R rating (X/R=17). Modern industrial electrical power systems, particularly systems with generators or large synchronous motors, may have X/R magnitudes significantly greater than 14. Some large industrial system generators have X/R greater than 100, and large industrial transformers may have X/R of 30 to 40. Example 1 Typical Industrial 13.8kV Switchgear Feeder with high-ratio CTs. 600/5 CT with C200 Accuracy Class 18 kA RMS Short-Circuit Magnitude System X/R = 14 RCT =RS= 0.193 ohms RWIRE =RW= 0.032 ohms RRELAY=RR= 0.01 ohms

VS = I S RMS (RS + RW + RB )

(1)

5 VS = 18kA 0.235 = 35.3 VRMS 600


5 VS = 2 18kA 0.235 = 70.5 VRMS 600 5 VS = 2 2 18kA 0.235 = 99.7 VRMS 600 5 VS = (1 + 14 ) 18kA 0.235 = 528.8 VRMS 600

(5) (6) (7) (8)

When the offset waveform concept was introduced, (2) was used.

VS = 2 I S RMS (RS + RW + RB )
Introduction of waveform peak resulted in (3) calculations.

(2)

VS = 2 2 I S RMS (RS + RW + RB )

(3)

Finally, the ANSI C37.110-1996 addition of (1 + X/R) for CT saturation calculation resulted in (4).

X VS = 1 + I S RMS (RS + RW + RB ) R

(4)

To show the impact of introducing the (1+X/R) term, two industrial examples are selected. Using (1) through (4), calculation results, the significant change introduced by (4) is shown. Examples 1 and 2 use a system X/R=14; this is less

IEEE Std. C57.13-1993 (R2003) [11], Section 6.4.1 defines relaying accuracy ratings as a designation by a classification and a terminal voltage rating. These effectively describe the steady-state performance. The secondary voltage rating is the voltage the current transformer can deliver to a standard burden at 20 times rated secondary current without exceeding 10% ratio correction factor [11]. Fig. 3 shows a 600/5 CT saturation curve with a C200 accuracy class that may be used in Example 1. The C refers to a calculated ratio magnitude; the 200 means the ratio correction will not exceed 10% at any secondary current

from 1 to 20 times rated secondary current value with a standard 2.0 ohm burden.

5 VS = 2 18kA 0.096 = 86.4 VRMS 200 5 VS = 2 2 18kA 0.096 = 122.2 VRMS 200 5 VS = (1 + 14 ) 18kA 0.074 = 648.0 VRMS 600

(11) (12) (13)

Obviously, the low-ratio CT is underrated for an 18kA fault magnitude with a system X/R of 14. This is the commonly unrecognized dilemma using underrated low-ratio CTs with protection relays. Industrial systems with large supply transformers, large motors or local generators could have a short-circuit X/R ratio in excess of 50 value, making the DC offset condition more severe.

IV. IEEE STANDARD C37.20.2-1999


Fig. 3. CT saturation curve for 600/5, C200. The following indicates the secondary terminal voltage at 20 times rated current of 5A:
VS = 2.00 5 A 20 = 200.0VRMS

(9)

Traditionally, switchgear CT sizing assistance has been provided from IEEE Standard C37.20.2-1999 [12], IEEE Standard for Metal-Clad Switchgear [12], Table 4, shows standard CTs supplied by manufacturers considered adequate for most applications. Table I reproduces only the CT ratio and relaying accuracy class portions of Table 4 and footnote c. TABLE I
EXCERPT FROM C37.20.2-1999 [12]

With a known CT internal resistance and CT saturation curve, the CT maximum terminal voltage can be estimated. Obviously, the CT accuracy rating must be greater than the required CT voltage. In Example 1, with 18kA primary fault current and 600/5 ratio, the CT secondary current is 150A. This is 30 times the CT 5A nominal secondary current rating (150A/5A = 30 x 5A CT rating). This exceeds the 20 times CT secondary rating requirement of Section 6.4.1 [11]; hence, predictable CT performance with no more than 10% ratio correction is not guaranteed because CT performance may become non-linear. Equations (5), (6) and (7) results indicate the selected 600/5 CT is adequate. However, (8) results indicate a C200 accuracy class is significantly underrated for the (1+X/R) DC offset conditions. Because protective relays are designed for an undistorted waveform input, it is important to provide CTs that are capable of accurately reproducing the primary system short-circuit waveform on the CT secondary. Example 1 shows the results with high-ratio CTs on feeder circuits. At this point the application question could be asked, what is required for typical 13.8kV switchgear feeders with low-ratio CTs? Example 2 - Typical industrial 13.8kV feeder with low-ratio CTs. 200/5 CT with C20 Accuracy Class 18 kA RMS Short-Circuit Magnitude System X/R = 14 RCT =RS= 0.054 ohms RWIRE =RW= 0.032 ohms RRELAY=RB= 0.01 ohms

CT Ratio 50/5 75/5 100/5 150/5 200/5 300/5 400/5 600/5 800/5 1200/5 1500/5 2000/5 3000/5 4000/5
c

Relaying accuracyc C or T10 C or T10 C or T10 C or T20 C or T20 C or T20 C or T50 C or T50 C or T50 C100 C100 C100 C100 C100

(see text for footnote)

5 VS = 18kA 0.096 = 43.2 VRMS 200

(10)

At first glance, the industrial user may attempt to use Table 4 for a company standard or project specification. When compared to examples 1 and 2 above, it is intuitively obvious that the minimum CTs supplied as standard by manufacturers for industrial relaying purposes are typically not adequate. Upon further inspection, Table 4, footnote c states, These accuracies may not be sufficient for proper relaying performance under all conditions. To ensure proper relaying performance, the user should make a careful analysis of CT performance considering the relaying requirements for the specific short-circuit currents and secondary circuit impedances (see 8.7.1). Section 8.7.1 of C37.20.2-1999 [12]

is titled Current Transformers and provides a synopsis of the application of current transformers in metal-clad switchgear. That the accuracies listed in Table 4 are the standard supplied in the usual design of this equipment, and are adequate for most applications. If an application requires higher accuracies, it should be specified by the user [12]. Considerations in the proper selection of CTs are listed, i.e., circuit load current, continuous, mechanical and short-time current rating factors, accuracy class, secondary burden, protection type, and available fault current. When the current transformer ratio is selected primarily to meet the full load and overload protection requirements of the protected load, the ratio and accuracy may be too low to ensure proper operation of the short-circuit protection at the maximum available fault current. Improper protective relay operation resulting from current transformer saturation may cause mis-operation or non-operation of the circuit breaker [12]. The standard indicates two considerations to overcome the undesirable condition of relay/circuit breaker maloperation because of CT saturation: 1) special accuracy CTs from the manufacturer or 2) two sets of CTs (a low-ratio CT set for overload protection and a much higher CT ratio/accuracy set determined from the fault current and the CT secondary burden). At the end of Section 8.7.1 two references are included, [9] and [10]. These references discuss the transient response of CTs and relay performance when applying low-ratio CTs in high-magnitude fault conditions. The C37.20.2-1999, Section 8.7.1 directives send a mixed message. Section 8.7.1 initial statements instruct the user that Table 4 CTs represent the standard supplied in the usual design of this equipment, and are adequate for most applications; however, the remainder of Section 8.7.1 provides a list of qualifications for applying the Table 4 standard. Table 4 may be adequate for utility industry applications with X/R ratios of 4 to 8, but it should be used cautiously by industrial users. The application question arises, what should the industrial user do? 1) Use Table 4? Example 2 showed that low-ratio CTs are inadequate with an 18kA fault current and system X/R=14. With typical industrial equipment symmetrical interrupting ratings of 50kA or 63kA, the low-ratio CTs may be inadequate for typical heavy industry applications. 2) Provide two sets of CTs; one set for overload conditions and the second CT set for fault conditions? This could resolve the concern of relay maloperation during fault conditions, but may require an additional metering device, adding cost to the switchgear. Although two sets of CTs are a viable solution, it has not been adopted as common practice by the heavy industries. However, this is the recommendation of [9] as indicated in section VI. 3) Apply Table 4, footnote c, and perform a careful analysis by applying [7] and [8]? This would be consistent with a rigorous engineering investigation approach. Part I and Part II of this paper provide discussions concerning the use of Table 4 CT accuracy recommendations for modern heavy industrial applications.

Another source of CT sizing guidance is the Buff Book, ANSI/IEEE Standard 242-2001 [13]. Buff Book Chapter 3 discusses Instrument Transformers, and Section 3.2.9 Examples of Accuracy Calculations provides three point-bypoint calculated relaying examples with symmetrical calculations only. However, the symmetrical calculations are followed by Section 3.1.10 titled Saturation, where CT saturation effects are very briefly considered with the following general guides. 1) Where fault currents of more than 20 times the current transformer nameplate rating are anticipated, a different current transformer, or different current transformer ratio, or less burden may be required. 2) A comprehensive review of saturation and its effect on transient response of current transformers is presented in IEEE Publication 76 CH 1130-4 PWR. [9] Again, there is a mixed message when CT saturation is introduced. The example calculations are symmetrical without reference to the DC component or X/R ratio, yet there is a caveat when short-circuit currents result in greater than 20 times the CT nameplate rating or other transient conditions. Table II is a simple tabulation based on the 20 times CT rating criteria. Table II shows typical CT capabilities for maximum ANSI standard switchgear ratings from 25kA to 63kA without including DC component (1+X/R) concerns. This most basic criterion illustrates that only high-ratio CTs are adequate for protective relaying during maximum fault conditions and the DC offset component ignored.

VI. IEEE PUBLICATION 76 CH 1130-4 PWR, TRANSIENT RESPONSE OF CURRENT TRANSFORMERS


IEEE Publication 76 CH 1130-4 PWR, Transient Response of Current Transformers January 1976 [9] provides analysis details for determining CT performance during transient conditions. This publication was a primary reference in the 1995, IEEE Transactions on Industry Applications, Vol. 31, No. 2, March/April 1995, Relay Performance Considerations with Low-Ratio CTs and High Fault Currents [10], which focused on the typical industrial application of low-ratio CTs and high-magnitude fault currents. The purpose of the paper was to notify industrial, power plant, and cogeneration engineers of the concerns of using low-ratio CTs and alternative application solutions. On the first page, definitive statements are provided for correct CT application during both overload and short-circuit conditions. For applications addressed by this report, this requirement will usually mean the provision of two CTs: A low ratio for overload and a high ratio (in the order of 2000-4000 to 5A) for short-circuit protection. Although based on detailed investigations, this recommendation has typically not been implemented by the heavy industries. To assist application engineers in determining the CT output waveform into the relay, a BASIC computer program was included as a fundamental tool to aid in analyzing relay performance. By including this type of rudimentary analytical tool, it is intuitive to conclude that symmetrical hand calculations are not completely adequate for evaluating CT/Relay performance during severe transient fault conditions.

V. BUFF BOOK ANSI/IEEE STANDARD 242-2001, CHAPTER 3

In the mid-1980s, Stanley Zocholl, William Kothheimer and others began publishing technical conference papers discussing CT saturation and the impact on relay response. Previously, electro-mechanical relays were tested to confirm expected operation during severe fault conditions; however, testing is a costly activity. Microprocessor-based relays use modern digital simulation confirmation; a more cost effective approach. The Zocholl, Kothheimer, et. al., papers continued to highlight the concern of relay response with saturated CTs, particularly the effect of significant X/R ratio (DC component) and CT remanence. Kothheimer even produced CT saturation waveform programs for both one CT and two CTs (differential application). This introduced the era of CT saturation and relay response via waveform analysis.

VII. MODERN CT CALCULATION SIZING APPROACH


In 1996, ANSI C37.110-1996 adopted the continuing work of Stanley Zocholl and William Kotheimer to include the (1+X/R) DC offset component and waveform analysis into CT sizing criteria. Now, industrial applications should comply with a CT standard that requires significantly increased CT accuracy class requirements. Table III and Table IV apply modern ANSI CT sizing requirements to ANSI standard switchgear ratings during maximum rated fault conditions. Table III and Table IV results show that typically used switchgear accuracy class CTs may not be adequate for industrial applications. Obviously, modern ANSI CT sizing criteria is more stringent than ANSI C57.13-1993 (R 2003) [11], but what method should be used? Basic calculations are only part of the CT selection process because relay response must also be considered. The answer is provided by an ongoing application research activity formalized by the Power System Relay Committee in the 1976 IEEE publication 76 CH 1130-4 PWR [9] and continued by Stanley Zocholl, William Kotheimer and others Relay Response to CT Output Waveforms. It is a two step process. 1) Determine the CT secondary output waveform. 2) Using the CT secondary output waveform as input to the relay or relay model, determine the relay response to confirm the relay responds as anticipated for an ANSI device 50 relay, i.e. an immediate trip with only relay response time delay is anticipated.

3) Commercial computational application software may be procured and programmed from basic physics and electrical engineering principles. 4) Electro-magnetic transient program (EMTP), such as, free licensing alternative transient program (ATP) or commercial versions may be programmed with basic physics and electrical engineering principles. Obviously, with the use of any computer simulation tool, simulation computations should be verified. Compare the computer results with test results from the users specific application or known test results is desired, a check is performed to confirm the computer results match the realworld response. This means the application engineer should determine the CT output waveform and the subsequent relay response via significantly more analysis than traditional calculation methods. Section IX begins to address the relay response concerns by providing some fundamental building block modules for microprocessor relays.

IX. MICROPROCESSOR RELAY BASICS


Analyzing relay response to CT output waveforms is a multi-part task. Here are some typical concerns, when investigating relay response to a CT secondary output waveform. 1) What does the primary power circuit short-circuit waveform look like? 2) What does the CT secondary waveform into the relay look like? 3) How does the relay process the input waveform? 4) What is the relay response? 5) Is a trip provided as anticipated? 6) Is an additional delay incurred by the relay? These and other questions are discussed in this section and Part II of this paper. Fig. 4 shows a typical CT/Relay application with pertinent microprocessor relay modules. It provides a minimal fundamental discussion of a modern CT/microprocessor relay protection system by briefly describing the function of the CT/relay modules and illustrating example waveforms at pertinent CT/relay test points [18, 19, 20 and 21]. Fig. 4 CT/Relay Test Point Discussion: Primary CT - The purpose of the Primary CT is to reproduce the primary current waveform to the RELAY AUX CT. This is extremely important because microprocessor relays are typically designed for symmetrical waveforms. Significantly distorted current sinusoidal wave input into the relay presents a challenge to microprocessor relays because the relay recognition algorithm is anticipating a non-symmetrical sinusoidal wave input. This illustrates another reason for true reproduction of the primary fault current waveform on the CT secondary. Relay Aux CT block - The microprocessor relay has a Relay Aux CT block that converts the waveform input into a useable scaled voltage quantity. Providing a waveform input that exceeds the design limits of the switchgear installed CT secondary current is discouraged because of potential RELAY AUX CT block saturation and decreased relay response performance.

VIII. CT WAVEFORM SATURATION SOFTWARE


Determining the relay response to CT output waveforms is complex and requires computer simulation. Typically available CT saturation software is freeware or developed by programming commercial computational software tool. The following list indicates some types of available software; others may be available [14, 15, 16 and 17]. 1) The Power System Relay Committee BASICA freeware software from [5] yields unrefined CT output waveform results, utilizing many assumptions. 2) More refined, proprietary CT output waveform software from relay manufacturers may be available upon request with a proprietary agreement.

Fig. 4(a)

Fig. 4(b)

Sampling Frequency

Fig. 4(c) Digital Filter

Fig. 4(d)

Anti-Aliasing Filter

A/D Conversion

Algorithm

Trip Output

Relay AuxCT Primary CT

Fig. 4. Rudimentary CT/microprocessor relay block diagram with waveform test points [5]. Anti-Aliasing Filter - An Anti-Aliasing Filter conditions the analog waveform via a low-pass filter to remove any high frequency content. A/D Conversion - An analog-to-digital converter (A/D) converts the signal to a digital value of current at a sample rate. Digital Filter - A Digital Filter extracts the fundamental frequency and rejects all harmonics. Algorithm - The fundamental is then compared with the tripping algorithm. If the trip setting is exceeded, a trip command is issued to the output trip relay. Example waveforms at pertinent Fig. 4 test points are included to promote insight into operation of the CT/relay system.

Fig. 4(b). Relay Aux CT and anti-aliasing filter output. Fig. 4(b) shows the RelayAuxCT output to the anti-aliasing filter, a scaled voltage waveform of the primary CT secondary; and illustrates anti-aliasing filter removal of high-frequencies.

Fig. 4(a). I Primary (scaled to secondary) and I Secondary currents. Fig. 4(a) shows a primary system fault current waveform and a scaled waveform on the Primary CT Secondary.

Fig. 4(c). A/D converter output. Fig. 4(c) shows the A/D conversion.

applications and considered adequate for most applications; however, many qualifications and confirmations are required. Table II suggests a minimum of 1200/5 CT ratio per ANSI/IEEE Standard 242-2001, Section 3.1.10 Saturation. IEEE Publication 76 CH 1130-4 PWR, Transient Response of Current Transformers January 1976 and IEEE Transactions on Industry Applications, Vol. 31, No. 2, March/April 1995, Relay Performance Considerations with Low-Ratio CTs and High Fault Currents. propose the use of a low-ratio CT for overload and a high-ratio CT for short-circuit conditions. This has not been typical industrial practice. A modern CT sizing approach is introduced with waveform analysis as the evaluation basis, rather than a symmetrical hand calculation. A fundamental CT/microprocessor relay block diagram and sequential test point waveforms are included to illustrate this modern approach.

XI. CONCLUSIONS
Fig. 4(d). Digital filter and relay output. Fig. 4(d) shows the waveform input to the digital filter where the fundamental frequency waveform is extracted by the digital filter and the RMS value of the waveform is calculated. The RMS value is compared to the settings of ANSI element 50 in the relay Tripping Logic and a trip is initiated by logic. In this example, a trip occurs in approximately one cycle from the fault occurrence, an acceptable response for instantaneous protection. This is the modern CT/relay protection system which application engineers should understand. Further waveform analysis at CT/relay test points can be found in the following application references: 1) The Impact of High Fault Current and CT Rating Limits on Overcurrent Protection, G. Benmouyal and S. Zocholl, 2002 [2]. 2) Primary High Current Testing of Relays with Low Ratio Current Transformers, S. Zocholl and J. Mooney, 2003 [6]. Although this process may seem a straightforward, it is imperative that the input waveform to the relay reproduces the primary current fault for anticipated predictable relay response during fault conditions. Hence, the CT must be adequate for the application, with a ratio and accuracy class consistent with the fault current characteristic and the CT/relay protection system hardware and software algorithms. Part II of this paper expands on this discussion by providing waveform analysis to determine CT accuracy class guidance for CTs. When IEEE Standard C37.110-1996 formally introduced the (1+X/R) multiplier for CT saturation calculations, CT accuracy class requirements significantly increased for heavy industrial applications with low-ratio CTs on typical mediumvoltage feeder applications because the X/R ratio is high (14 or greater). This did not appreciably affect utility transmission applications because the utility industry X/R range is low (4 to 8). Because the (1+X/R) multiplier may require significant CT accuracy requirements, a modern method is needed to confirm the CT ratio and accuracy class and relay response during fault conditions. In Part 2 of this paper, typical examples utilizing waveform analysis will be discussed to provide guidance for the required CT accuracy class and to evaluate if low-ratio CTs are adequate for typical industrial medium-voltage feeder instantaneous applications.

X. ACKNOWLEDGMENTS
The authors thank Stan Zocholl, Terry Hazel and Tony Zhao for their helpful suggestions.

XI. REFERENCES
[1] [2] IEEE Std. C37.110-1996, IEEE Guide for the Application of Current Transformers Used fro Protective Relaying Purposes S.E. Zocholl, G. Benmoyal, How Microprocessor Relays Respond to Harmonics, Saturation, and Other Wave Distortions, Schweitzer Engineering Laboratories, Inc., Pullman, WA. W.A. Elmore, C.A. Kramer, S.E. Zocholl, Effect of Waveform Distortion on Protective Relays, IEEE Trans. On Industrial Applications, Vol. 29, (2), pp. 404-411, 1991. S.E. Zocholl, W.C. Kotheimer, F.Y. Tajaddodi, An Analytic Approach to the Application of Current rd Transformers for Protective Relaying, 43 Annual Georgia Tech Protective Relaying Conference, May 3-5, 1989

X. SUMMARY
Modern IEEE Standard C37.110-1996 CT saturation calculations include a (1+X/R) multiplier that significantly increases the required CT accuracy class during fault conditions in medium-voltage industrial power feeder circuit applications, particularly when low-ratio CTs are implemented. Tables III and IV show typical industrial CT accuracy class examples using ANSI C37.110-1996 (1+X/R) methodology and that practical CT accuracy class sizes are not achieved. IEEE Standard C37.20.2-1999, Table 4 indicates minimum accuracy class CTs provided as a standard for usual

[3]

[4]

[5] [6]

[7]

[8]

[9] [10]

[11] [12] [13] [14]

[15]

[16]

[17] [18] [19] [20] [21]

S.E. Zocholl and G. Benmouyal, The Impact of High Fault Current and CT Rating Limits on Overcurrent Protection, 2003. S.E. Zocholl, J. Mooney, Primary High-Current Testing of Relays with Low Ratio Current Transformers, Schweitzer Engineering Laboratories, Inc., Pullman, WA, 2003. R. Garrett, W.C. Kothemier, and S.E. Zocholl, Computer Simulation of Current Transformers and Relays for Performance Analysis, presented before the th 14 Annual Western Relay Conference, Spokane, WA., October 20-23, 1987. W.C. Kothemier and S.E. Zocholl, CT Performance in Critical Relay Applications, presented at the Georgia Tech Protective Relay Conference, Atlanta, GA., May 13, 1991. Power System Relaying Committee of IEEE, Transient Response of Current Transformers, special publication 76 CH 1130-4 PWR, January 1976. Relay Performance Considerations with Low-Ratio Current Transformers and High Fault Currents Working Group, Relay Performance Considerations with Low Ratio CTS and High Fault Currents, IEEE Trans. On Power Delivery, Vol. 8, (3), pp. 884-897, 1993. IEEE Std. C57.13-1993 (R2003), IEEE Standard Requirements for Instrument Transformers IEEE Std. C37.20.2-1999, IEEE Standard for MetalClad Switchgear. ANSI/IEEE Std. 242-1986, IEEE Recommended Practice for Protection and Coordination of industrial and Commercial Power Systems (IEEE Buff Book). Working Group C-5, Mathematical Models for Current, Voltage, and Coupling Capacitor Voltage Transformers, IEEE Trans. On Power Delivery, Vol. 15, (1), pp. 62-72, 2000. M. Kezunovic, C.W. Fromen, F. Philips, Experimental Evaluation of EMTP-Based Current Transformer Models for Protective Relay Transient Study, IEEE Trans. On Power Delivery, Vol. 9, (1), pp. 405-413, 1994. L.A. Kojovic, CT Modeling Techniques for Relay Protection System Transient Studies, in IPST 2003 Conf. Proc., New Orleans September 28 - October 2, 2003. R. Folkers, Determine Current Transformer Suitability Using EMTP Models, Schweitzer Engineering Laboratories, Inc., Pullman, WA. J. Campbell, CT Saturation and Adaptive Filtering An SEL Innovation, Schweitzer Engineering Laboratories, Inc., Pullman, WA. E.O. Schweitzer, D. Hou, Filtering for Protective Relays, Schweitzer Engineering Laboratories, Inc., Pullman, WA. IEEE Std. C37.04-1999, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Working Group C-1, Software Models for Relays, IEEE Trans. On Power Delivery, Vol. 16, (2), pp. 238-245, 2001.

XII. VITAE

Roy E. Coss, Jr. received the BSEE (1968) and MSEE (1972) degrees from the University of Southwestern Louisiana, Lafayette, Louisiana. He has 30 plus years of Electrical Engineering experience in the Petrochemical, Marine, Pipeline, Cogeneration, and IPP Industries. His experience encompasses conceptual design, detailed engineering, training, startup, maintenance and operations. His specialty is power system analysis. He is a Professional Engineer in Texas and Louisiana. Mr. Coss is an IEEE Senior member. He is one of the original organizers of the IEEE Houston Continuing Education on Demand series; and he has presented technical seminars for this program. He has co-authored and presented IEEE conference technical papers. Mr. Coss is employed by Powell Electrical Manufacturing Company where he is Powell Apparatus Service Division Technical Director. Donald G. Dunn received a BSEE in 1991 from Prairie View A&M University and in 1993 attended West Texas A&M University pursuing an MBA. He was employed by Diamond Shamrock from 1992 to 1998 as an Instrument, Electrical & Control System Engineer and worked on many diverse capital projects. Since 1998, he has been employed by Lyondell Chemical Company and its predecessor company as a Principal IEA & Controls Engineer at the Channelview Complex. He is currently a senior member of the IEEE and the ISA. He has been a member of the IEEE for the past 18 years. He has co-authored six papers for PCIC. In addition, Mr. Dunn has been an invited presenter at various IEEE Regional conferences and the 2002 IEEE Sections Conference. He is the past chairman of the PCIC young engineers development subcommittee and Secretary of the Chemical Subcommittee. Mr. Dunn is the past chairman of IEEE-Houston Section and IEEE-Region 5 Technical and Educational Activities Committee. He is currently the IEEE Region 5 South Area Chairman in addition to being a member of several other subcommittees within the PCIC. He is a member of the IEEE Standards Association, IEEE 1242 Working Group and ISA Standards Committees SP3, SP5.6, & SP60. He is currently the chairman of ISA Standards working group SP18. Robert M. Spiewak earned BSEE equivalent from The Technical University of Krakow, Poland (1988) and a Master of Electrical Engineering from the University of Houston (1996). He has 14 years of professional experience, including extensive field and theoretical experience in Power, Marine, Petrochemical, Pipeline, IPP and OEM Industries. Mr. Spiewaks daily tasks include conceptual design, feasibility studies, detail engineering, startup, and maintenance. His areas of interest include power system design, control, and steady-state/transient analysis, electric machines, and electromechanical drive system controls. He specializes in industrial and power applications, power system relaying, power system analysis, and special applications. He is a Professional Engineer in state of Texas. He is a member of IEEE PES and IAS Societies. Mr. Spiewak is a principal engineer with Polamex Engineering & Design Services, Inc, an engineering consulting company. He is currently affiliated with W.S. Nelson and Company where he performs Senior Electrical Engineer functions.

TABLE II
20 TIMES CT PRIMARY RATING COMPARED TO SWITCHGEAR SYMMETRICAL RMS RATING.

CT Ratio 50/5 75/5 100/5 150/5 200/5 250/5 300/5 400/5 500/5 600/5 800/5 1000/5 1200/5 1500/5 2000/5 3000/5 4000/5
Notes:

20 Times CT Primary 25kA Fault 31.5kA Fault 40A Fault 50kA Fault 63kA Fault 1000 A 1500 A 2000 A 3000 A 4000 A 5000 A 6000 A 8000 A 10000 A 12000 A 16000 A 20000 A 24000 A CONFIRM 30000 A OK CONFIRM 40000 A OK OK CONFIRM 60000 A OK OK OK OK CONFIRM 80000 A OK OK OK OK OK
1. Metal-Clad switchgear half-cycle rating is based on X/R=25. 2. Metal-Clad switchgear interrupting rating is based on X/R=17. 3. "-" indicates the CT is not adequate for minimum accuracy class CT's.

TABLE III
SECONDARY EXCITING VOLTAGE (Vs) SUMMARY USING ANSI C37.110-1996, 1+X/R CALCULATION METHOD (STANDARD ACCURACY CLASS CT)

Standard CT Ratio 25kA Fault 31.5kA Fault 40A Fault 50kA Fault 63kA Fault No Class 50/5 1875 2363 3000 3750 4725 C10 75/5 1450 1827 2320 2900 3654 C10 100/5 1294 1630 2070 2588 3260 C20 150/5 1050 1323 1680 2100 2646 C20 200/5 900 1134 1440 1800 2268 C20 250/5 818 1030 1308 1635 2060 C20 300/5 869 1095 1390 1738 2189 C50 400/5 802 1010 1283 1603 2020 C50 500/5 761 959 1218 1523 1918 C100 600/5 734 925 1175 1469 1851 C100 800/5 703 886 1125 1406 1772 C100 1000/5 683 860 1092 1365 1720 C200 1200/5 670 845 1073 1341 1689 C200 1500/5 813 1024 1300 1625 2048 C200 2000/5 591 744 945 1181 1488 C200 3000/5 717 903 1147 1434 1807 C200 4000/5 523 659 837 1046 1318
TABLE IV

COMMENTS CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate

SECONDARY EXCITING VOLTAGE (Vs) SUMMARY USING ANSI C37.110-1996, 1+X/R CALCULATION METHOD (HIGH ACCURACY CLASS CT)

HI C10 C20 C20 C50 C50 C50 C100 C100 C100 C200 C200 C400 C400 C400 C400 C400 C400

CT Ratio 25kA Fault 31.5kA Fault 40A Fault 50kA Fault 63kA Fault 50/5 2625 3308 4200 5250 6615 75/5 2125 2678 3400 4250 5355 100/5 1856 2339 2970 3713 4678 150/5 1613 2032 2580 3225 4064 200/5 1481 1866 2370 2963 3733 250/5 1410 1777 2256 2820 3553 300/5 1356 1709 2170 2713 3418 400/5 1289 1624 2063 2578 3248 500/5 1249 1573 1998 2498 3147 600/5 1222 1540 1955 2444 3079 800/5 1191 1500 1905 2381 3000 1000/5 1170 1474 1872 2340 2948 1200/5 1158 1459 1853 2316 2918 1500/5 1428 1799 2284 2855 3597 2000/5 1041 1311 1665 2081 2622 3000/5 1285 1619 2056 2570 3238 4000/5 936 1179 1498 1872 2359

COMMENTS CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate CT not adequate

10

Вам также может понравиться