GSPL203 - 75-3510
CABLE SIZING CALCULATION-SV3 STATION @ BERAJA
PASAYA
DATE REVISION DFSCRIPTIVALDEL ENGINEERS & JPAGE No.2 of 6
‘CONSTRUCTORS. REVISION STATUS SHEET
[DOCUMENT No. GSPL203-75-3510
JDOCUMENT TITLE CABLE SIZING CALCULATION
SVB Station (@ Beraja Pasaya)
‘DOL REV. | PAGENs. | REV] ADDL.
PAGE No.
m
7128)
7128)
730)
732,
134,
135,
136
138
730)
“10
s|a|e/¢\e/sle/ale
a2,
743,
144
45;
146.
407
18
749
TH
IF REVISION REQUIRES ADDITIONAL PAGES TO BE INSERTED IN BETWEEN THE DOCUMENT, THE NUMBER OF THE
PAGE AT INSERTION SHALL BE NUMBERED WITH DECIMAL (ag. INSERTION BETWEEN PAGE 10 AND 11 SHALL
BE NUMBERED AS 1044, 102.)
Fram {Waldeisbs68veoc\TO GLIENTICABLE SINGIREV OTGSPL209 75301452MAYTAS NAFTOGAS BUD CONSORTIUM GSPL203-75-3510
Revo
OBJECTIVE:
‘The purpose ofthis calculation is to determine the cross sections of the low voltage cable to
be installed in SV3 Station @ Beraja Pasaya,
ABBREVIATIONS:
GEB = Gujarat Electricity Board
2) MEDB = Main Electrical Distribution board
OLDB = Outdoor Lighting Distribution Board
REFERENCE DOCUMENTS:
@ | strtte3.0105 since LINE DIAGRAM: Sva STATION AT BERAIA PASAYA
2) 61111-C-14-0205 — PLOT PLAN SV3 STATION @ BERAJA PASAYA
3) GSPL203-753503 ELECTRICAL LOAD DATASV3 STATION @ BERAJA PASAYA
4) 61111-€-15-0804 CABLE TRENCH LAYOUT CONTROL ROOM BUILDING SV3 STATION @
BERAJA PASAYA
5) 61109/16/11/E/51/0006 -ELECTRICAL DESIGN BASIS.
4 INPUTS / ASSUMPTIONS:
| CABLE DETAILS
1. Voltage Grade 1100V
2.Type ot Cable 1.1 kV PVC insulated, Extruded PVC inner sheath & PVC outer sheath,
steelstripiwire armoured, outer sheath shall have FRLS characteristics
3, Power Cable ‘Stranded Annealed Copper Conductor up to 16 sq.mm
Stranded Aluminium Conducta from 25 sq.mm and above
4. Permisible Vottage drop : 5%
5. The main incoming cable from GEB & DG set to MEDB shall be buried directly underground
e All other cables are route in concrete trenches via cable trays
6. The Current ratings, rating factors, resistance & reactance values are taken from
the cable manufacturer's catalogue (Refer Attachment)
Ml Calculation of Combined Derating factor
For calculating Derating factor, ground temperature is assumed as 35 degree celsius and
thermal resistivity of soil is taken as 200 deg c.cm/w
‘A. Rating factor for variation in ground temperature 0.94
8 - Rating factor for variation in thermal resistivity of soil og
C- Rating factor for variation in depth of faying 0.99 (for 800mm)
D- Rating factor for laying cables in horizontal formation 0.79 (2 cables in groups touching)
[DOC.NO.: GSPL203-75-35 10
VALDEL ENGINEERS |PROJECT: BHARUCH JAMNAGAR PIPELINE PROJECT
& CONSTRUCTORS frifte : CABLE SIZING CALCULATION-
8V3 STATION @ BERAJA PASAYA
Cable sizing Calculation
8V3 Station @ Beraja Pasaya Page 3 of 6