Table of Contents
0 1 2 3 4 5 6 7 8 9 10 11 12 13
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-1
Bulletin 809S/813S/814S/817S
0 1 2 3 4
Enhanced Protection
The MachineAlert family of dedicated function motor protection relays offers state-of-the-art supplementary protective functions that are easily added and applied to your motor control circuits. This full range of products allows selective addition of motor protective enhancing functions to meet your specific application requirements for supplemental voltage-, current-, thermistor-, power-, and power factorbased protection. Additionally, MachineAlert relays are your economical choice for protecting equipment investments and minimizing production downtime.
Standards Compliance
EN 60664, EN 60038 UL 508
Certifications
cULus Listed (File E14840, Guide NKCR, NKCR7)
Typical Applications
Blowers Conveyors Compressors Cutting and Drilling Machines Fans Mixers Pumps VFD-Controlled Motors
5 6 7 8
Voltage monitoring relay Guards against the damaging effects of phase loss, under- and overvoltage, phase imbalance, phase reversal, and voltage quality of incoming power line Current monitoring relay Provides under- and overcurrent detection Thermistor monitoring relay Protects equipment from overtemperature conditions Power (kW) monitoring relay Monitors for under- and over active power, as well as power direction Power factor (PF) monitoring relay Monitors for under- and over power factor detection
809S C1 10A 48
a a
Bulletin Number
b b
Type Bulletin 809S
d c
Measurement Rating Bulletin 809S Code 10A 500V 110V 230V 400V 480V 690V 480V10A 690V10A Description 110 A AC/DC Bulletin 813S 2500V AC/DC (Type V1) 110115V AC (Type V3) 208240V AC (Type V3) 380415V AC (Type V3) 440480V AC (Type V3) 600690V AC (Type V3) Bulletin 814S 380480V AC & 110 A AC 600690V AC & 110 A AC Bulletin 817S
9 10 11 12 13
Description Current Monitoring Relay Voltage Monitoring Relay Power Monitoring Relay Thermistor Monitoring Relay V1 V3 Code C1
Description Single-Phase Current Monitoring Relay Bulletin 813S Single-Phase Voltage Monitoring Relay Three-Phase Voltage Monitoring Relay Bulletin 814S Three-Phase Power (kW) Monitoring Relay Three-Phase Power Factor Monitoring Relay Bulletin 817S Thermistor Monitoring Relay
d
External Power Code Bulletin 809S Code 48 230 48 230 48 115 230 Description 24/48V AC/DC 115/230V AC Bulletin 813S 24/48V AC/DC (Type V1 only) 115/230V AC (Type V1 only) Bulletin 814S Bulletin 817S 24/48V AC/DC 115V AC 230V AC PTC W3 PF3
www.ab.com/catalogs
3-2
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1
Type
2 3 4 5 6 7 8 9 10 11 12 13
Operating range
Under- and overcurrent protection Under- and overvoltage protection Phase loss protection Phase imbalance Phase reversal Minimum and maximum cos () protection Under- and over active power (kW) protection Overtemperature protection Adjustable time delay settings Programmable latching or inhibit at set level Changeover Contacts (SPDT) Automatic Reset LED status indicator Dimensions (W x H x D) 22.5 x 80 x 99.5 mm 1
1 2 1 1 1
22.5 x 80 x 99.5 mm
45 x 80 x 99.5 mm
45 x 80 x 99.5 mm
45 x 80 x 99.5 mm
22.5 x 80 x 99.5 mm
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-3
Bulletin 809S/813S/814S/817S
0 1 2 3
Bulletin 814S Power Monitoring Relays Bulletin 813S Voltage Monitoring Relays
809S-C1-10A-230
Single-phase voltage monitoring relay, 2500V AC/DC; 24/48V AC/DC control power Single-phase voltage monitoring relay, 2500V AC/DC; 115/230V AC control power Three-phase voltage monitoring relay, 110115V AC Three-phase voltage monitoring relay, 208240V AC Three-phase voltage monitoring relay, 380415V AC Three-phase voltage monitoring relay, 440480V AC Three-phase voltage monitoring relay, 600690V AC Three-phase power (kW) monitoring relay, 380480V AC & 110 A AC Three-phase power (kW) monitoring relay, 600690V AC & 110 A AC Three-phase power factor monitoring relay, 380480V AC & 110 A AC Three-phase power factor monitoring relay, 600690V AC & 110 A AC Thermistor monitoring relay, 24/48V AC/DC control power Thermistor monitoring relay, 115V AC control power Bulletin 817 Thermistor Monitoring Relay Thermistor monitoring relay, 230V AC control power
813S-V1-500V-48 813S-V1-500V-230 813S-V3-110V 813S-V3-230V 813S-V3-400V 813S-V3-480V 813S-V3-690V 814S-W3-480V-10A 814S-W3-690V-10A 814S-PF3-480V-10A 814S-PF3-690V-10A 817S-PTC-48 817S-PTC-115 817S-PTC-230
4 5 6 7 8 9 10 11 12 13
Current Transformers
Use only with Cat No. 809S-C1.
Trip Current Range Continuous AC Amperes (5 A Secondary Winding) 4.250 17200 42500 1001200 Maximum Current [A] Continuous 75 300 750 1800 Inrush 350 1400 3500 8400 Cat. No. 809S-CT1 809S-CT2 809S-CT3 809S-CT4
www.ab.com/catalogs
3-4
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6 7 8 9 10 11 12 13
-22-2% of the nominal -22-2% of the nominal -22-2% of the nominal -22-2% of the nominal -22-2% of the nominal voltage voltage voltage voltage voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage 222% of the nominal voltage
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-5
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6 7 8 9 10 11 12 13
Cat. No. Input Specifications Input Voltage Current Measuring Ranges Power Factor (cos ) Upper Level Lower Level Direct Input Upper Level Lower Level Contact Input Disabled Enabled Pulse Width Hysteresis Output Specifications Type of Contact Rated Insulation Voltage Supply Specifications Rated Operational Power General Specifications Power ON Delay Environment Degree of Protection Pollution Degree Dimensions (W x H x D) Screw Terminals
0.10.99 0.10.99 110 A 50 A Terminals Z1, Y1 >10 k <500 >500 ms PF Approx. 0.1 (1) Form C 250V AC 13 VA @ 400V AC, 50 Hz 1 to 30 s +/- 0.5 s IP 20 3 45 x 80 x 99.5 mm Max. 0.5 Nm
0.10.99 0.10.99 110 A 50 A Terminals Z1, Y1 >10 k <500 >500 ms PF Approx. 0.1 (1) Form C 250V AC 21 VA @ 600V AC, 50 Hz 1 to 30 s +/- 0.5 s IP 20 3 45 x 80 x 99.5 mm Max. 0.5 Nm
www.ab.com/catalogs
3-6
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6 7 8 9 10 11 12 13
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-7
Bulletin 809S/813S/814S/817S
0 1 2 3
Latch/Inhibit Contact
Terminals
4 5 6 7 8 9
A1, A2 A3, A2
10 11 12 13
www.ab.com/catalogs Preferred availability cat. nos. are bold.
3-8
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1 2 3
4 5 6 7 8 9
10 11 12 13
Set Level
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-9
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6 7 8 9 10 11 12 13
www.ab.com/catalogs Preferred availability cat. nos. are bold.
3-10
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6
7 8 9 10 11 12 13
www.ab.com/catalogs Preferred availability cat. nos. are bold. Publication A117-CA001A-EN-P
3-11
Bulletin 809S/813S/814S/817S
0 1 2 3 4 5 6 7 8 9 10 11 12 13
M/G
Latch/Inhibit Contact
M G
Power ON
Power ON
M G
Power ON
Power ON
Power ON
www.ab.com/catalogs
3-12
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1
Latch/Inhibit Contact
U1 I1 U2
cos cos I1
Z1
L1 L2 L3
16
18
2
I2 15
3
Three-Phase Power Factor Monitoring Relays
These self-powered devices are TRMS power factor monitoring relays for three-phase balanced systems. They can be used for monitoring the actual load of asynchronous motors and other symmetrical loads, where the power factor is almost proportional to the load. The relay measures the absolute value for the power factor of the system PF = Active Power / Apparent Power that is for balanced system with sinus waveforms the cosine of the angle between motor current and motor voltage (cos ). As cos varies with the load of the motor, underload and overload can be indirectly detected by the monitoring relay. With the built-in latch function, the ON-position of the relay output can be maintained. The inhibit function can be used to avoid relay operation when not desired. The LEDs indicate the state of the alarm and the output relay.
4 5 6 7
Hysteresys
Power ON Power ON
8 9 10
Hysteresys
Power ON
Power ON
11 12 13
3-13
Hysteresys
Power ON
www.ab.com/catalogs
Publication A117-CA001A-EN-P
Bulletin 809S/813S/814S/817S
0 1
These devices are motor temperature monitoring relays, used to monitor the temperature of the coils of a motor with built-in PTCs. The alarm status of the relay can be reset by either an external contact or an internal button. The test button allows the simulation of the fault condition. The LEDs indicate the alarm status.
A1 12 14
Reset contact
2 3 4
Z1 T1 T2
Z2
T
A2 N (-) 11
3100 1650
Relay ON
Approximate Dimensions
Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.
5 6 7 8 9 10 11 12 13
80 (3.15)
45 (1.77)
99.5 (3.91)
80 (3.15)
83.5 (3.29)
63 (2.48)
28.5 (1.12)
www.ab.com/catalogs Preferred availability cat. nos. are bold.
3-14
Publication A117-CA001A-EN-P
Bulletin 1409
Table of Contents
Product Selection ...... 3-16 Specifications.............. 3-17 Typical Wiring Diagrams....................... 3-17 Approximate Dimensions................... 3-18
0 1 2 3 4
Standards Compliance
CSA C22.2, No. 144 UL 1053
Certifications
Arcing Ground Fault Sensor Cat. No. 1409-N2
The Bulletin 1409 Arcing Ground Fault Detection Systems are intended for equipment protection only. These systems are not Ground-Fault Circuit-Interrupters for personnel protection as defined in Article 100 of the U.S. National Electric Code. Bulletin 1409 is available in two designs, Class I and Class II. The Class I systems are intended for use with shunt-trip circuit breakers or medium voltage controllers. These Class I systems do not contain a high-current inhibit circuit. The Class II Systems are designed for use with motor starters or contactors to interrupt low-level ground faults. They incorporate a highcurrent inhibit circuit that guards against the controller opening when the fault current exceeds the controller interrupting capacity. Ground fault currents exceeding the interrupting rating of the controllers are designed to be cleared by the short circuit protection device (fuse or circuit breaker). Both Class I and Class II Systems consist of two parts a relay and a sensor. The relay contains all the detection, adjustment and output circuitry. The sensor is a special two-winding current transformer. Operation of the ground fault detection system is indicated by the relay toggle.
5 6 7 8 9 10 11 12 13
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-15
Bulletin 1409
0 1
2 3
4 5 6 7 8 9 10 11 12 13
3-1/4 in.
1409-N3
4-1/4 in.
1409-N4
1 For a 3-phase system with one cable per phase except as indicated.
8000V cable select sensor to have a window diameter greater than 2.5 times the cable diameter.
Arcing Ground Fault Relays Class I without High Current Inhibit Feature
Application Shunt-Trip Circuit Breaker Medium Voltage Controller Max. Line Voltage [V] 600 7200 Cat. No. 1409-MV
www.ab.com/catalogs
3-16
Publication A117-CA001A-EN-P
Bulletin 1409
0 1 2 3
OLs
L1 M
L2 M
L3 M
Test Winding
CT4 CT3
4 5
Motor
Operate Winding
CT2 CT1
CT2 CT1
6 7
Circuit Breaker
8
To Source of 120V, 60 Hz Shunt Trip Power Source
CT4 CT3
9 10
Test Winding
Internal Printed Circuit Typical when used with shunt trip circuit breaker
Operate Winding
CT2 CT1
CT2 CT1
Motor
11 12 13
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-17
Bulletin 1409
0 1 2 3
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
4
Arcing Ground Fault Sensors
5 6 7 8 9 10
Cat. No. A 92.6 (3-21/32) 91.4 (3-19/32) 73.2 (2-7/8) 77.2 (3-1/32)
4 closed slots 12.7 (1/2) x 5.6 (7/32) Dia. (Cat. No. 1409-N2 only)
H Dia.
4 open slots Cat. No. 1409-N1: 12.7 (1/2) x 7.1 dia. (9/32) Cat. No. 1409-N2: 12.7 (1/2) x 11.1 dia. (7/16)
H Dia.
Cat. No. 1409-N3 Cat. No. 1409-N4 B 88.9 (3-1/2) 115.8 (4-9/16) 144 (5-11/16) 169.9 (6-11/16) C 104 (4-3/32) 131.8 (5-3/16) 157.2 (6-3/16) 182.6 (7-3/16) D 74 (2-15/16) 77 (3-1/32) 54.9 (2-5/32) 59.5 (2-11/32) E 67.3 (2-21/32) 88.9 (3-1/2) 96.8 (3-13/16) 123.7 (4-7/8) F 56.4 (2-7/32) 88.9 (3-1/2) 119.4 (4-23/32) 138.2 (5-7/16) G 92.9 (3-21/32) 120.6 (4-3/4) 146.1 (5-3/4) 171.5 (6-3/4) H 39.6 (1-9/16) 63.5 (2-1/2) 82.6 (3-1/4) 108 (4-1/4) J 69.8 (2-3/4) K 54.9 (2-5/32)
11 12 13
www.ab.com/catalogs
3-18
Publication A117-CA001A-EN-P
Bulletin 1410
Standards Compliance
CSA C22.2, No. 14 UL 508
0 1 2 3 4
Certifications
CSA Certified (LR 1234) UL Listed (File E56639, Guide NMTR)
Product Selection1
3-Phase Motor Voltage, +10%, -5%, 60 Hz 230 460 575 230 460 575 230 460 575 230 460 575 3-Phase Hp Rating 1550 25100 25100 50100 100200 100200 100200 200400 200400 200300 400600 400600 Cat. No. 1410-EOA47 1410-EOB50 1410-EOC50 1410-FOA50 1410-FOB54 1410-FOC54 1410-GOA54 1410-GOB59 1410-GOC59 1410-HOA57 1410-HOB62 1410-HOC62
Specifications
Output Voltage Regulation Ambient Temperature Range Voltage applied to motor winding will vary 5% maximum for line voltage variations of +10%, 15%.
Operating 050 C (32122 F) Storage 25+85 C (13+184 F) Metal oxide varistor protects against voltage surges. RC snubber circuit limits rate of change of circuit voltage. Approximately 15% of full load current. Approximately 13 W/Hp.
5 6 7 8 9 10 11 12 13
Additional SCR Protection True RMS Output Current Power Delivered to the Motor
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes
from those listed, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
Connection Diagram
See Applicable Codes and Laws.
Motor Branch Circuit Protection
L1 M LT1 L2 L3 LT2 LT3 OLs T1
To Motor
T2 T3
To L2
To L3
To LT2
Cat. No. 1410-EOA47 1410-EOB50 1410-EOC50 1410-FOA50 1410-FOB54 1410-FOC54 1410-GOA54 1410-GOB59 1410-GOC59 1410-HOA57 1410-HOB62 1410-HOC62
www.ab.com/catalogs
Publication A117-CA001A-EN-P
3-19
0 1 2 3 4 5 6 7 8 9 10 11 12 13
www.ab.com/catalogs Preferred availability cat. nos. are bold.
3-20
Publication A117-CA001A-EN-P