Czech Technical University in Prague Department of Microenvironmental and Building Services Engineering http://tzb.fsv.cvut.

cz 125BEE2 Ventilation, MK Air handling unit design

TE

TI

Example: Air handling unit design (summer + winter) Office room max 40 person (no smoking), room-south wall 20m, west wall 20m, height 3,5m Heat loss: 10 W/m3, Heat gains: south windows 20m2, internal blind, electrical equipments 4kW (Calculation without moisture production) Air parameters: Winter Te=-12C, rh=80% Ti=20C, rh=60% Summer Te=30C, rh=40% Ti=26C, rh=60% Calculation: Heat loss: QL=15*20*3,5*10= 10,5kW Heat gains: External QGE=20*185=3,7kW QGEwall=50*10=0,5kW Internal QI PERSON=40*150=6kW QI ELECTRICAL=4kW QG=3,7+0,5+6+4=14,2kW

Czech Technical University in Prague Department of Microenvironmental and Building Services Engineering http://tzb.fsv.cvut.cz 125BEE2 Ventilation, MK Summer Summer dT=5C = supply air T=26-5=21C Supply air flow VSA in accord with Gains: Q VSA = =14200 / (1010*1,2*5)=2,343m3/s=8436m3/h c. .T Voutside air in accord with Persons: VOA=40*50=2000m3/h Recirculated air VCA=8436-2000=6436m3/h Winter Supply air temperature TSA QLOSS TSA = + T =(10500 / (2,343*1,2*1010))+20=23,7 => 24C (VSA . SA .c ) I Air preheating TE1=5C QH 1 = VOA . .c.(TE1 TE ) =0,556*1,2*1010*(5+12)=11,5kW or Energy recovery TSA = TE + (TI TE ) . TSA=-12+(20+12)*0,7=10,4C Mixing T .V + T .V Tmix = I CA E1 OA =(20*6436+5*2000) / (6436+2000)=16,44 =>16,5C VCA + VOA Air heating QH 2 = VOA . .c. (TSA TMIX ) =2,343*1,2*1010*(24-16,5)=21,5kW

Czech Technical University in Prague Department of Microenvironmental and Building Services Engineering http://tzb.fsv.cvut.cz 125BEE2 Ventilation, MK Moisture production (persons): Mw=m*n=116*40=4640g/h=4,64kg/h Air moisture change : M x = =6960 / (1,2*8436)=0,69 g/kg .VSA

Вам также может понравиться