SPLIT-TYPE AIR CONDITIONER

INDOOR UNIT
Basic : AQV12NSA Model : AQV09NSB AQV12NSB Model Code : AQV09NSBN AQV12NSBN AQV09NSBX AQV12NSBX

OUTDOOR UNIT

AIR CONDITIONER

THE FEATURE OF PRODUCT High Energy Efficiency BLDC Air Conditioner Simple Flat Grille Design

good'sleep Mode : good'sleep Mode can help you sleep quickly and
AQV09FCN, AQV12FCN, AQV09NSAN,AQV12NSAN

soundly and wake up refreshed.

Multi Functional Cleaning System : Silver Nano Health System and Deodorizing/
Catechin Filter are adopted.

Silence Mode : When you use the "Silence Mode", you can
experience extremely quiet operation of your air conditioner.

AQV09FCX, AQV12FCX, AQV09NSAX,AQV12NSAX

Refer to the service manual in the GSPN(see the rear cover) for the more information.

Operating Instructions and Installation

Contents
11. Precautions ........................................................................................................................................ 1-1
1-1 Installing the air conditioner
.......................................................................................................... .................................................................................................

1-1 1-1 1-1 1-2 1-2

1-2 Power supply and circuit breaker 1-4 Disposing of the unit 1-5 Others

1-3 During operation ..............................................................................................................................


....................................................................................................................... .................................................................................................................................................

12. Product Specifications ............................................................................................................... 2-1


2-1 The Feature of Product .................................................................................................................... 2-2 Product Specifications ..................................................................................................................... 2-3 The Comparative Specifications of Product ................................................................................ 2-4 Accessory and Option Specifications
...........................................................................................

2-1 2-2 2-3 2-5

13. Alignment and Adjustments ................................................................................................. 3-1


3-1 Test Mode ........................................................................................................................................... 3-2 Indoor Display Error and Check Method 3-4 Setting Option Setup Method
.....................................................................................

3-1 3-2 3-3 3-4

3-3 Outdoor LED Error Display and Check Method ..........................................................................


.......................................................................................................

14. Disassembly and Reassembly


4-2 Outdoor Unit

..............................................................................................

4-1
4-2 4-5

4-1 Indoor Unit .........................................................................................................................................


....................................................................................................................................

15. Exploded Views and Parts List ............................................................................................. 5-1


5-1 Indoor Unit ......................................................................................................................................... 5-2 Outdoor Unit
..................................................................................................................................... .................................................................................................................................

5-1 5-3 5-5 5-7

5-3 Assy Control In

5-4 Assy Control Out ..............................................................................................................................

16. Electrical Parts List 17. Wiring Diagram


7-2 Outdoor Unit

.......................................................................................................................

6-1 7-1
7-1 7-2

..............................................................................................................................

7-1 Indoor Unit .........................................................................................................................................


....................................................................................................................................

18. Schematic Diagram ...................................................................................................................... 8-1


8-1 Indoor Unit ......................................................................................................................................... 8-2 Outdoor Unit
....................................................................................................................................

8-1 8-2

Samsung Electronics

Operating Instructions and Installation

Contents
19. Circuit Descriptions ...................................................................................................................... 9-1
9-1 PCB Circuit Descriptions .................................................................................................................. 9-2 Refrigerating Cycle Diagram .......................................................................................................... 9-1 9-3

10. PCB Diagram ..................................................................................................................................... 10-1


10-1 Indoor PCB ....................................................................................................................................... 10-1 10-2 Outdoor PCB
...................................................................................................................................

10-2

11. Operating Instructions .............................................................................................................. 11-1


11-1 Name of Each Part .......................................................................................................................... 11-1 11-2 Wireless Remote Control-Buttons and Display
........................................................................

11-3

11-3 Main Function ................................................................................................................................. 11-4

12. Troubleshooting ............................................................................................................................ 12-1


12-1 Items to be checked first 12-3 PCB Inspection Method
..............................................................................................................

12-1 12-20 12-22

12-2 Fault Diagnosis by Symptom ....................................................................................................... 12-2


................................................................................................................ ......................................................................................................

12-4 Main Part Inspection Method

13. Block Diagram


13-1 Indoor Unit

.................................................................................................................................

13-1
13-1

......................................................................................................................................

13-2 Outdoor Unit ................................................................................................................................... 13-3

14. Reference Sheet .............................................................................................................................. 14-1


14-1 Index for Model Name
.................................................................................................................. .......................................................................................

14-1 14-2 14-3 14-4 14-7 14-9 14-10

14-2 Low Refrigerant Pressure Distribution 14-3 Pressure & Capacity mark 14-4 Q & A for Non-trouble 14-6 Installation 14-5 Cleaning/Filter Change

.............................................................................................................

................................................................................................................... .................................................................................................................

....................................................................................................................................... ..........................................................

14-7 Installation Diagram of Indoor Unit and Outdoor Unit

Samsung Electronics

1. Precautions
1-1 Installing the air conditioner
Users should not install the air conditioner by themselves. Ask the dealer or authorized company to install the air conditioner except the window-type air conditioner in U.S.A and Canada. If you dont install the air conditioner properly, it may cause a fire, a water leakage or an electric shock. You must install the air conditioner according to the national wiring regulations and safety regulations. Install the indoor unit higher than 2.5m from the floor to avoid the injury caused by the operation of the fan. (except the window-type air conditioner) The manufacturer is not responsible for any accidents or injury caused by an incorrect installation. When installing the built-in type air conditioner, keep all electric cables such as the power cable and the connection cord in pipes, ducts, or cable channels to protect them from the danger of impact or any other incidents.

1-2 Power supply and circuit breaker


If the power cord of the air conditioner is damaged, it must be replaced by the manufacturer or a qualified person in order to avoid a hazard. The air conditioner must be plugged into an independent circuit if applicable or connect the power cable to the auxiliary circuit breaker. An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm. Do not extend an electric cord to the air conditioner. The air conditioner must be plugged in after you complete the installation.

1-3 During operation


Do not repair the air conditioner at your discretion. It is recommended to contact a service center directly. Never spill any kind of liquid on the air conditioner. If this happens, turn off the air conditioner and contact an authorized service center. Do not insert anything between the airflow blades to prevent damage of the inner fan and consequent injury. Keep children away from the air conditioner. Do not place any obstacles in front of the air conditioner. Do not spray any kind of liquid into the indoor unit. If this happens, turn off the air conditioner and contact a service center. Make sure that the air conditioner is well ventilated at all times: Do not place a cloth or other materials over it. Remove the batteries if you dont use the remote control for a long time. (If applicable) Use the remote control within 7 meters from the indoor unit. (If applicable)

Samsung Electronics

1-1

1-4 Disposing of the unit


Before throwing out the air conditioner, remove the batteries from the remote control. When you dispose of the air conditioner, consult your dealer. If pipes are removed incorrectly, refrigerant may blow out and cause air pollution. When it contacts with your skin, it can cause skin injury. The package of the air conditioner should be recycled or disposed of properly for environmental reasons.

1-5 Others
Never store or load the air conditioner upside down or sideways to prevent the damage to the compressor. Young children or infirm persons should be always supervised when they use the air conditioner. Max current is measured according to IEC standard for safety. Current is measured according to ISO standard for energy efficiency.

1-2

Samsung Electronics

2. Product Specifications
2-1 The Feature of Product
High Energy Efficiency BLDC Air Conditioner
BLDC Technique arises the efficiency of air conditioner and makes a room cool and warm with high energy saving.

Simple Flat Grille Design


With a Smart and fashionable style, the high impressive interior design allow this product to set place in anywhere.

good'sleep Mode
good'sleep Mode can help you sleep quickly and soundly and wake up refreshed.

Multi functional cleaning system


With Silver Nano Health System and Deodorizing/Catechin Filters makes your room more refreshed.

Silence Mode
When you use the Silence Mode, you can experience extremely quiet operation of your air conditioner.

Samsung Electronics

2-1

2-2 Product Specifications


Model Item Type Capacity Cooling Heating Cooling Heating kW (Low / Std / Max) Hz (Low / Std / Max) /h Cooling Heating Cooling Heating Cooling Heating /min (H/M/L) dB (H/L) W/W (Std) ph-V-Hz Cooling Heating Cooling Heating Cooling Heating Length Power Cord Number of Core Wire Capacity Outer Dimension Weight (Net) Refrigerant Pipe Drain Hose Size Type Compressor Motor Type Rated Output Liquid Gas WxHxD A mm kg mm x L(m) mm x L(m) D x L(mm) 825x285x189 7.8 6.35 x 5 9.52 x 5 18 x 550 Rotary, G4C090LUDER Hermetic 853W FREOL68ES-T Type Blower Motor Type Rated Output W Cross-flow Resin / Steel 27 2 Row 10 Step Propeller Resin / Steel 50 1 Row 20 Step W (Low / Std / Max) A (Low / Std / Max) % (Low / Std / Max) m 7.2/5.8/4.0 7.8/6.6/4.6 43 / 25 43 / 25 3.40 3.63 1-220/240-50 270 / 735 / 980 300 / 910 / 1100 1.6 / 3.5 / 4.5 1.7 / 4.4 / 5.2 70 / 85 / 90 70 / 85 / 90 2 3 10 720x548x265 31.5 825x285x189 9.4 6.35 x 5 9.52 x 5 18 x 550 Rotary, G4C090LUDER Hermetic 853W FREOL68ES-T Cross-flow Resin / Steel 27 2 Row 10 Step Propeller Resin / Steel 50 1 Row 20 Step AQV09NSA/AQV09FC Indoor Unit Outdoor Unit AQV12NSA/AQV12FC Indoor Unit Outdoor Unit

Wall-mounted 0.99 / 2.50 / 3.20 1.20 / 3.30 / 4.20 20 / 52 / 70 25 / 64 / 75 1.3 30 29 53 53

Wall-mounted 0.99 / 3.30 / 3.80 1.40 / 4.00 / 4.70 25 / 69 / 79 30 / 76 / 88 1.6 8.5/6.9/5.2 9.2/7.5/6.0 43 / 25 43 / 25 3.21 3.61 1-220/240-50 320 / 1028 / 1210 350 / 1108 / 1400 1.9 / 4.9 / 5.5 2.2 / 5.2 / 6.2 70 / 90 / 90 70 / 90 / 90 2 3 10 720x548x265 31.5 30 29 53 53

Running Frequency Dehumidifying Performance Air Volume

Noise

Energy Efficiency Ratio Power Power Consumtion

Operating Current Power

Power Factor

Oil Type

Heat Exchanger Refrigerant Control Unit Freezer Oil Capacity Refrigerant to Change (R410A) Protection Device (OLP) Cooling Test Condition Heating Test Condition cooling Operation conditon range heating indoor Outdoor indoor Outdoor cc g

Check Valve, Capillary 320 800 None Indoor Unit : DB27C WB 19C Indoor Unit : DB20C WB 15C 16C ~ 32C -10C ~ 43C 27C or less -15C ~ 24C

Check Valve, Capillary 320 850 None Outdoor Unit : DB35C WB 24C Outdoor Unit : DB7C WB 6C 16C ~ 32C -10C ~ 43C 27Cor less -15C ~ 24C

2-2

Samsung Electronics

2-3 The Comparative Specifications of Product


Item Development Model AQV09NSAN/AQV09FCN Comparative Model AQV09FAN

Indoor Unit

Design

Outdoor Unit

Net Weight

Indoor Unit Outdoor Unit

7.8kg 31.5kg 825 x 285 x 189 (mm) 720 x 548 x 265(mm) 43dB 53dB Silver Nano Evaporator Catechin Filter Deodorizing Fiter Three Color LED Display Development Model AQV12NSAN/AQV12FCN

7.8kg 31.5kg 825 x 285 x 189 (mm) 720 x 548 x 265(mm) 43dB 53dB Silver Nano Evaporator Catechin Filter Deodorizing Fiter Three Color LED Display Comparative Model AQV12FAN

Indoor Unit Outer Dimension (WidthxHeightxDepth) Outdoor Unit Noise Indoor Unit Outdoor Unit Filter

Air Purifying System Indoor Display

Item

Indoor Unit

Design

Outdoor Unit

Net Weight

Indoor Unit Outdoor Unit

9.4kg 31.5kg 825 x 285 x 189 (mm) 720 x 548 x 265(mm) 43dB 53dB Silver Nano Evaporator Catechin Filter Deodorizing Fiter Three Color LED Display

8.4kg 31.5kg 825 x 285 x 189 (mm) 720 x 548 x 265(mm) 43dB 53dB Silver Nano Evaporator Catechin Filter Deodorizing Fiter Three Color LED Display

Indoor Unit Outer Dimension (WidthxHeightxDepth) Outdoor Unit Noise Indoor Unit Outdoor Unit Filter

Air Purifying System Indoor Display

Samsung Electronics

2-3

2-4 Accessory and Option Specifications


2-4-1 Accessories
Item Descriptions Code-No. Q'TY Remark

Ass'y Plate Hanger

DB7-02851B

Remote Control

DB93-03170S

Batteries for Remote Control

DB47-90024A

Indoor Unit
TIONS OWNER'S INSTRUC CIONES INSTRUC MANUAL DE L'USO PER ISTRUZIONIINSTRUES MANUAL DE ATION MANUEL D'UTILIS EISUNG GEBRAUCHSANW
Air ConditionerSplit Splut-type Room domstico sistema Aire acondicionado ambienti ad unit Separate d'aria per Split Condizionatore ar condicionado tipo Aparelho de de type spar Climatiseur e Geteilte raumklimaanlag

Users Manual

DB98-28490A

TIONS OWNER'S INSTRUC CIONES INSTRUC MANUAL DE L'USO PER ISTRUZIONIINSTRUES MANUAL DE ATION MANUEL D'UTILIS EISUNG GEBRAUCHSANW
Air ConditionerSplit Splut-type Room domstico sistema Aire acondicionado ambienti ad unit Separate d'aria per Split Condizionatore ar condicionado tipo Aparelho de de type spar Climatiseur e Geteilte raumklimaanlag

Installation Manual

DB98-28492A

DB93-01549F (Europe) 3-wire Power Cable DB93-02431A (Australia) 1

2-4

Samsung Electronics

Item

Descriptions

Code-No.

Q'TY

Remark

4-wire Assembly Cable

DB39-01092B (Only Australia)

Drain Plug

DB67-20011A

Outdoor Unit

Rubber Leg

DB73-00182A

Assembly Pipe, 6.35mm

DB96-10453B

Assembly Pipe, 9.52mm

DB96-10453F

PE T3 Foam Tube Insulation

DB72-50165A

Accessory Box

Vinyl Tape, Width 50mm

DB72-00459A

Drain Plug

DB67-20011A

Samsung Electronics

2-5

Product Specifications and Installation Operating Instructions

Accessories(cont.)
Item Descriptions Code-No. Q'TY Remark

Rubber Leg

DB73-00182A

Pipe Clamps A

DB39-20224A

Pipe Clamps B

DB39-20224B

Cement Nail

Accessory Box

M4x16 Tapping Screws

6002-000215

10

Drain Hose, length 2m

DB62-00487A

Putty 100g

DB98-10568A

2-6

Samsung Electronics

3. Alignment and Adjustments


3-1 Test Mode
How to Approach Test Mode
You can approach the Test Mode by pressing the on/off switch of indoor unit for 5 seconds.

on/off switch

Test Mode Operation Option


After installing the air conditioner, check whether each subordinate is normally operated or not by operating the Test Mode. When an error occurs, display the Error Mode. Operation Mode : Cool mode. Operate the cool mode by operating the compressor by force without the compressor ON/OFF according to the set temperature/indoor temperature. (Do not follow the antifreeze control) Up-down louver : Up-down swing mode Indoor Fan : High

Because the Test Mode operate the cool mode by force not related to the set temperature / indoor temperature, check whether each subordinate is operated normally or not after completing installation and must turn off the power of the air conditioner.

Samsung Electronics

3-1

3-2 Indoor Display Error and Check Method


LAMP Description OPERATION TIMER TURBO Main Checking Point

Indoor unit room temperature sensor error (open or short) Indoor unit heat exchanger temperature sensor error (open or short) Indoor fan motor malfunction

: Lamp on,

3-2P

3-3P

3-4P

EEPROM error Option error (option wasnt set up or option data error) Outdoor unit error

Option Setting

Option Setting Remote Control on/off Outdoor Unit Power Reset : Lamp off, : Lamp blink

3-2

Samsung Electronics

3-3 Outdoor LED Error Display and Check Method


No.
1 2

LED Display Yellow


Green

Red
Abnormal Serial communication Power off/ VDD NG IPM Over Current(O.C)

Explanation

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Compressor Starting error Normal Operation Compressor Lock error DC-Link voltage under/over error Outdoor temperature sensor error Discharge over temperature Discharge temperature sensor error Current sensor error Compressor limit error Coil temperature sensor error 1min. Time out Communication Fan error OTP error Compressor rotation error Operation condition secession(Dual only) DC-Link voltage sensor error I_Trip error / PFC Over current GAS Leak error AC Line Zero Cross Signal out Power ON reset(1sec) Capacity miss match Test Operation at Cooling Mode Test Operation at Heating Mode : LED ON, : LED OFF, : LED BLINK

Samsung Electronics

3-3

3-4 Setting Option Setup Method


ex) Option No. :
Step 1 : Enter the Option Setup mode. 1st Take out the batteries of remote control. 2nd Press the temperature the battery again. button simultaneously and insert

3rd Make sure the remocon display shown as

Step 2 : Enter the Option Setup mode and select your option according to the following procedure.

1
The default value is Otherwise, push the repeatedly.

. button to . or

Every time you push the button, the display panel reads

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

Push the 10

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

Push the

button to set the display panel to

Every time you push the button, the display panel reads Setting is not required if you must a value which has a default.

. . . repeatedly.

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

3-4

Samsung Electronics

Alignment and Adjustments

7 1
Press button, then the default value is .

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

10

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

11

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

12
Setting is not required if you must a value which has a default.

Push the

button to set the display panel to

Every time you push the button, the display panel reads

. . . repeatedly.

Step 3 : Upon completion of the selection, check you made right selections. Press the Mode Selection key, to set the display part to and check the display part.
The display part shows

. to set the display part to . and check the display part.

Press the Mode Selection key,


The display part shows

) Step 4 : Pressing the ON/OFF button ( When pressing the operation ON/OFF key with the direction of remote control for unit, the sound Ding or Diriring is heard and the OPERATION ICON( ) lamp of the display is flickering at the same time, then the input of option is completed. (If the diriring sound isnt heard, try again pressing the ON/OFF button.) Step 5 : Unit operation test-run First, Remove the battery from the remote control. Second, Re-insert the battery into the remote control. Third, Press ON/OFF key with the direction of remote control for set.

Error Mode 1st 2nd If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model.

Samsung Electronics

3-5

Alignment Instructions and Installation Operating and Adjustments

OPTION ITEMS
REMOCON MODEL AQV09NSAN AQV09FCN AQV12NSAN AQV12FCN SEG1
0 0

SEG2
8 9

SEG3
4 4

SEG4
7 7

SEG5
7 7

SEG6
7 7

SEG7
1 1

SEG8
7 7

SEG9
5 5

SEG10 SEG11 SEG12


2 2 4 4 E E

3-6

Samsung Electronics

4. Disassembly and Reassembly


Necessary Tools
Item Remark

+SCREW DRIVER

MONKEY SPANNER

Samsung Electronics

4-1

4-1 Indoor Unit


No 1 Parts Front Grille Procedure 1) Stop the air conditioner operation and shut off the main power. Remark

2) Open the Front Grille by pulling right and left sides of the hook.

3) Loosen 1 of the right screw(CCW) and detach the Terminal Cover. (Use +Screw Driver.) 4) Detach the thermistor from the Front Grille.

5) Loosen 2 fixing screws(CCW) of Front Grille.

6) Unlock 3 hooks to fix Panel Front and Tray Drain. (Use +Screw Driver.)

4-2

Samsung Electronics

Disassembly and Reassembly

No

Parts

Procedure 7) Unlock 3 hooks to fix Panel Front and Back-Body.

Remark

Control-In (Main PCB)

1) Take all the connector of PCB upper side out. (Inclusion Power Cord) 2) Detach the outdoor unit connection wire from the Terminal Block. 3) Loosen 4 fixing screws(CCW) of Ass'y Control-In. (Use +Screw Driver.) You can disassembly Ass'y Control In without evaporator disassembled.

Tray Drain

1) Pull Tray Drain out from the Back Body.

Samsung Electronics

4-3

Disassembly and Reassembly

No 4

Parts Heat Exchanger

Procedure 1) Loosen 2 fixing earth screws(CCW) of right side. (Use +Screw Driver.) 2) Detach the Connection Pipe. 3) Detach the Holder Pipe at the rear side.

Remark

4) Loosen the 4 fixing screws(CCW) of right and left side. (Use +Screw Driver.) 5) Lifting the Heat Exchanger up a little to push the up side for separation from the indoor unit. First, check Comp. Down and then disconnect the connection pipes before you disassemble the Evaporator from indoor unit.

Fan Motor & Cross Fan

1) Loosen the fixing screw(CCW). (Use +Screw Driver.) 2) Detach the Fan Motor from the Fan. 3) Detach the Fan From the left Holder Bearing.

4-4

Samsung Electronics

4-2 Outdoor Unit


No 1 Parts Common Work Procedure 1) Loosen 1 fixing screw(CCW) of the Cover-Side. (Use +Screw Driver.) Remark

2) Loosen each 4 screws(CCW) on both right and left Cabinet Side edges and a fixing screw on the Cabinet Front lower to detach the Cabinet Front. (Use +Screw Driver.)

3) Detach the Cabinet Front like the picture on the right side.

4) Loosen 1 screw(CCW) fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.)

Samsung Electronics

4-5

Disassembly and Reassembly

No

Parts

Procedure 5) Loosen 2 fixing screws(CCW) on the rear side of Cabinet-Side RH. (Use +Screw Driver.)

Remark

6) Loosen 3 screws(CCW) fixed to assemble Bracket Valve with Cabinet-Side RH. (Use +Screw Driver.)

7) Loosen 2 fixing screws(CCW) of Cabinet Side LF. (Use +Screw Driver.)

4-6

Samsung Electronics

Disassembly and Reassembly

No 2

Parts Assy Control Out

Procedure 1) Detach the Motor Wire from the PCB of Assy Control Out.

Remark

2) Detach several connectors from the PCB of Ass y Control Out.

3) Detach 2 Connect Wires from Reactor.

4) Loosen 1 screw(CCW) fixed to assemble Assy Control Out with Partition. (Use +Screw Driver.)

Samsung Electronics

4-7

Disassembly and Reassembly

No 3

Parts Fan & Motor

Procedure 1) Release the refrigerant at first. 2) Loosen fixing screw(CW). (Use Monkey Spanner.) 3) Disassemble the pipes in both inlet and outlet with welding torch. 4) Detach the Heat Exchanger.

Remark

Heat Exchanger

1) Loosen 2 fixing screws(CCW) on both sides. (Use +Screw Driver.) 2) Disassemble the pipes in both inlet and outlet with welding torch. 3) Detach the Heat Exchanger. Before you disassemble the pipes and Condenser, be sure that there should be no refrigerant remained in the unit.

Assy Valve 4-Way & Assy Valve EEV

1) Loosen 4 bolts(CCW) fixed to assemble Valve Service with Bracket Valve like the picture on the right side. (Use Monkey Spanner.) 2) Disassemble the pipes assembled the suction and discharge sides of the Compressor with welding torch.

Compressor

1) Loosen the Nut(CCW) of Terminal Cover. (Use Monkey Spanner.) 2) Detach the Terminal Cover and detach the Connect Comp Wire from Compressor. 3) Disassemble the Felt Comp Sound. 4) Loosen the 3 bolts(CCW) at the bottom of Compressor like the picture on the right side. (Use Monkey Spanner.)

4-8

Samsung Electronics

MEMO

Samsung Electronics

4-9

5. Exploded Views and Parts List


5-1 Indoor Unit

5-1

Samsung Electronics

Exploded Views and Parts List

Parts List
No.
1

Code No.
DB94-00454J DB94-00454H

Description
ASSY BACK BODY ASSY BACK BODY BACK BODY CUSHION BACK BODY ASSY SUPPORT EVAP RH ASSY SUPPORT EVAP RH MOTOR IN ASSY CROSS FAN ASSY BOLT SPECIAL ASSY RUBBER BEARING ASSY BEARING MOTOR CUSHION EVAP UP ASSY EVAP TOTAL ASSY EVAP TOTAL COVER BEARING ASSY EVAP ASSY EVAP ASSY TRAY DRAIN TRAY DRAIN BLADE-H BLADE-V TRAY STABILIZER CUSHION EPS TRAY RH RUBBER CAP DRAIN ASSY MOTOR STEPPING ASSY DRAIN HOSE ASSY CONTROL IN ASSY PANEL FRONT PANEL FRONT ASSY GRILLE AIR INLET(AQV**NSAN) ASSY GRILLE AIR INLET(AQV**FCN) ASSY COVER DISPLAY GUARD AIR FILTER ASSY PLATE HANGER HOLDER PIPE COVER TERMINAL ASSY REMOCON ASSY ASSY HIPS EPS HIPS HIPS

Specification

Q'TY AQV09NSAN AQV12NSAN AQV12FCN AQV09FCN


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1

SA/SNA
SA SA SNA SNA SA SA SA SA SNA SNA SA SA SA SA SNA SNA SNA SA SNA SA SA SNA SA SNA SA SA SA SA SA SA SA SA SNA SNA SNA SA SA

1-1 1-2 1-3

DB61-01632D DB69-00834A DB96-03149A DB96-03149B

1-4 1-5 1-6 1-7 1-8 1-9 2

DB31-00219A DB94-00456A DB97-02075A DB94-00455A DB94-40007A DB69-00833A DB96-06862B DB96-06716B

220-240V~,50/60Hz,Class E OD92xL635 ASSY ASSY BEARING EPS ASSY ASSY ABS ASSY ASSY ASSY ABS HIPS PP ABS EPS GUM-EPM 220-240V~,50/60Hz,Class E ASSY ASSY ASSY HIPS ASSY ASSY ASSY PP ASSY PS ABS ARH-463

2-1 2-2

DB63-00850A DB96-03171K DB96-06563B

3 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 4 5 5-1 5-2

DB94-00457J DB63-00848A DB61-01635C DB61-01636A DB63-00849A DB69-00839A DB73-00180A DB31-00371A DB94-00458B DB93-05853A DB92-01237B DB64-00989E DB92-01207B DB92-00848J

5-3 5-4 6 7 8 9

DB90-03094A DB63-01591A DB97-02851B DB61-01638B DB63-00844D DB93-05083C

Samsung Electronics

5-2

5-2 Outdoor Unit

5-3

Samsung Electronics

Exploded Views and Parts List

Parts List
No.
1 2 3 4 5 6 7 8 9 10 11 12

Code No.
DB90-03870A DB63-02004A DB90-01330L DB99-00401B DB67-00397A DB60-30028A DB31-00220B DB61-01644A DB97-02225A DB94-01180B DB27-00041A DB96-06562C DB96-06562D

Description
ASSY CABI FRONT GUARD FAN ASSY BASE OUT ASSY BRACKET VALVE FAN-PROPELLER NUT-HEXAGON MOTOR FAN OUT BRACKET MOTOR ASSY SUPPORT PLATE B/M ASSY PARTITION REACTOR ASSY COND UNIT ASSY COND UNIT COVER CONTROL ASSY CABINET SIDE RH ASSY CABINET SIDE LF COMPRESSOR GROMMET ISOLATOR SCREW HEX SCREW MACHINE COVER TERMINAL GASKET FELT COMP SIDE FELT COMP BASE FELT COMP UPPER FELT COMP SIDE OUT FELT COMP UPPER OUT ASSY VALVE 4WAY 4WAY VALVE VALVE SERVICE ASSY VALVE CHECK ASSY VALVE CHECK VALVE SERVICE ASSY CONTROL OUT ASSY CONTROL OUT SCREEN COND BAR THERMISTOR OUT/DIS THERMISTOR COND CONNECT WIRE COMP

Specification
ASSY,SC-94445T HIPS,SC-90073R ASSY,SC-94445T ASSY,SC-94445T AS+G/F20%,400 M6 AC Motor SGCC-M SGCC-M ASSY,SGCC-M PPS,5mH,10A ASSY ASSY PP,SC-90073R ASSY,SC-94445T SECC-P,SC-94445T ROTARY,BLDC NR M8 M5 PBT(G/F 15%) EPDM FELT+PVC Sheet FELT+PVC Sheet FELT+PVC Sheet FELT+PVC Sheet FELT+PVC Sheet ASSY R410A,SANHUA R410A,SANHUA,3/8 ASSY ASSY R410A,SANHUA,1/4 ASSY ASSY P.E.H 100% ASSY ASSY ASSY

Q'TY AQV09NSAX AQV12NSAX AQV09FCX AQV12FCX


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

SA/SNA
SA SA SA SA SA SA SA SA SA SA SA SA SA SA SA SA SNA SNA SNA SNA SNA SNA SA SA SA SA SA SA SNA SNA SA SA SNA SA SA SA SA SA SA

13 14 15 17 17-1 17-2 17-3 17-4 17-5 18 19

DB63-00843A DB90-01546N DB90-01332A G4C090LUDER DB63-01967A DB60-30028A DB60-30004A DB63-00816A DB63-00817A DB63-01647A DB63-01950A DB63-01710A DB63-01948A DB63-01949A

20 20-1 20-2 21

DB99-00967A DB62-02286A DB62-02284A DB99-00969A DB99-00968A

21-2 22

DB62-02283A DB93-05534D DB93-05534C

23 24 25 26

DB71-00090F DB32-00176E DB32-00121B DB93-04489A

Samsung Electronics

5-4

5-3 Ass'y Control In : DB93-05853A

Parts List
No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Code No.
DB61-01637A DB93-05866A DB65-00181B DB93-03117A DB61-01639A DB61-01097A 6001-000929 6001-001054 DB93-04685A DB93-04685A DB93-04487A DB32-00020A DB63-00851A DB73-00242B DB39-00514B DB39-00148A DB93-01549F 6001-000725

Description
CASE CONTROL-IN ASSY PCB MAIN-IN TERMINAL BLOCK-ASSY ASSY PCB SUB PLATE-CONTROL IN HOLDER-WIRE CLAMP SCREW-MACHINE SCREW-MACHINE SCREW-SPECIAL ASSY CONNECTOR WIRE ASSY CONNECTOR WIRE THERMISTOR-WIRE ASSY COVER-DRAIN RUBBER-BAND CONNECTOR WIRE EARTH PLATE EARTH WIRE ASSY-POWER CORD SCREW-MACHINE

Specification
SS-P/J,ABS,-,-,-,BLK,SSEC FORTE,ASSY PCB MAIN AQV12FA,12K_In ASK(P)13WHWE,WW1,TSE,GRN/GRN/RED -,SGCC-M,T1.0,-,160,-,SSEC,SS-PJT -,ABS,-,-,-,BLK,V21-PJ PH,+,-,M3,L22,ZPC(WHT),SWRCH18A,UP,TH,+,-,M4,L10,ZPC(WHT),SM20C,-,TH, M4xL8 FORTE1-PJT,UL1007 26AWG FORTE-PJT,UL1007 28AWG 103AT,-,-,-20~+100,-,-,-,-,SS-PJT,ABS,-,-,-,-,-,NO,SSEC WW2-P/J,SILICON RUBBER,-,-,-,BLACK,-,-,SSEC,L120xW15xT0.3 YEL/GRN YEL/GRN MID,E,CB TH,+,-,M4,L16,ZPC(WHT),SWRCH18A,UP,-

Q'TY
1 1 1 1 1 1 1 3 1 1 1 1 1 1 3

SA/SNA
SA SA SNA SA SNA SA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SA SNA

5-5

Samsung Electronics

MEMO

Samsung Electronics

5-6

5-4 Ass'y Control Out


AQV09NSAX : DB93-05534C QV12NSAX : DB93-05534D A

5-7

Samsung Electronics

Exploded Views and Parts List

Parts List
Qty AQV09NSAX AQV12NSAX 1 1 3 5 1 1 2 1 1 1 1 1 1 1 1 M4,L10 KFR-35(25)GW/GPI M4,L8 M4,L10 L100MM Unitgram 2 1 2 1 1 2 1 1 3 5 1 1 2 1 1 1 1 1 1 1 1 2 1 2 1 1 2

No 1 2 3 4 5

Code No. DB61-02249A DB62-04566A 6002-000630 DB91-00306A DB93-05543D DB93-05543C

Description CASE CONTROL-COVER SEAL-CASE CONTROL COVER SCREW ASSY-SCREW MACHINE ASSY-PCB OUT ASSY-PCB OUT HEAT SINK SCREW-TAPPING ASSY-PCB EMI CASE CONTROL-BASE PLATE-CONTROL OUT SEAL-CASE CONTROL C-FILM,LEAD-OTHER SCREW-TAPPING TERMINAL BLOCK HOLDER-WIRE CLAMP SCREW INSULATOR-KFR SCREW SCREW CABLE-TIE ASSY

Specification ABS V0,T2.0,AS12BPBX AS12BPBX,FOAM-LEX 2S,M3,L8 M3,L16 FORTE 12K FORTE 9K KFR-35(25)GW/GPI,AL M4,2S,L10 FORTE/VIACE 12K/9K ABS V0,T2.0,AS12BPBX FORTE 12K/9K KFR-35GW/WCI 450V M3,20 INV,DAF-3P

SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

DB62-03155A 6002-000560 DB93-04264A DB61-02250A DB70-00547A DB62-02332P 2301-001377 DB91-00309A DB95-01140B DB61-00250A 6002-000527 DB81-00547B 6009-001001 6001-001054 DB65-10088D DB98-24813A

Samsung Electronics

5-8

6. Electrical Parts List


Indoor MAIN PBA DB93-05866A
Location No. CD11 D101 PC02 PC01 IC07 IC02 IC01 R701 IC05,IC06,IC08 IC09 IC59 SS71 F701 CN71 CN43 CN61 CN93 CN92 CN44 IC04 C502,C503,C504,C505,C506,C 507,C508,C509,C510 C202,C203,C404 C102,C201 C104,C106,C402,C403,C407,C 501,C801,C901 C401,C405,C406 BD71 ZD11 ZD13 ZD12 D701 Q201,Q401,Q601,Q603 Q602 Q101 R405,R406,R412 R209,R301,R605,R801,R908 R607,R608 R103,R104 R102 R606,R909 R210,R211,R401,R402,R404,R 409,R503,R602,R604,R610,R6 11 R504 R101 R106 R201,R202,R203,R204,R205,R 206,R207,R208 R407,R408,R411 R505 R403,R802 R502 Code No. Description Specification ST02D-82 ES1D H11AA814A300 PC123X2YSZ0F TD62783AFW KA78L05AZTA TNY266P 200-J ULN2003D013TR 93LC56B S-80142ANMC-JC3-T2 AQG22212 YW396-03AV SMW200-04 SMW200-05 SMW200-02 SMW200-06 SMW250-03 MB90F823 100nF 10nF 100nF 100nF 1nF DF06S BZX84C3V6 BZX84C4V3 BZX84-C11 UF4007 2SC2412K MMST2907A DTC114EKA 330-J 10K-J 470-J 12M-J 2.2K-J 4.7K-J 1K-J 5.1K-F 100-J 4.7K-J 47K-J 6.8K-F 0-J 6.8K-J 20K-J QTY 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 9 3 2 8 3 1 1 1 1 1 4 1 1 3 5 2 2 1 2 11 1 1 1 8 3 1 2 1 SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA 0406-001086 DIODE-TVS 0402-001427 DIODE-RECTIFIER PHOTO-COUPLER;TR,500604-001003 150%,200mW,DIP-4,ST 0604-001038 PHOTO-COUPLER 1003-001462 IC-SOURCE DRIVER 1203-000429 IC-POSI.FIXED REG. 1203-002545 IC-PWM CONTROLLER 2006-001080 R-CEMENT(S) 0506-000175 TR-ARRAY 1103-001175 IC-EEPROM 1203-003334 IC-RESET 3502-000115 SSR DB61-00924A FUSE-BLOCK 3711-003404 HEADER-BOARD TO CABLE 3711-004379 CONNECTOR-HEADER 3711-004484 CONNECTOR-HEADER 3711-003942 HEADER-BOARD TO CABLE 3711-004236 CONNECTOR-HEADER 3711-000879 HEADER-BOARD TO CABLE DB91-00573A IC MICOM 2203-000189 C-CER,CHIP 2203-000257 C-CER,CHIP 2203-000192 C-CER,CHIP 2203-005249 C-CER,CHIP 2203-000440 0402-001298 0403-000252 0403-000466 0403-001285 0402-000012 0501-000534 0501-002296 0504-001064 2007-000076 2007-000090 2007-000077 2002-001104 2007-000493 2007-000084 C-CER,CHIP DIODE-BRIDGE DIODE-ZENER DIODE-ZENER DIODE-ZENER DIODE-RECTIFIER TR-SMALL SIGNAL TR-SMALL SIGNAL TR-DIGITAL R-CHIP R-CHIP R-CHIP R-COMPOSITION R-CHIP R-CHIP

2007-000078 R-CHIP 2007-000962 R-CHIP 2007-000290 R-CHIP 2007-000872 R-CHIP 2007-000944 R-CHIP 2007-001068 2007-000070 2007-000087 2007-000093 R-CHIP R-CHIP R-CHIP R-CHIP

6-1

Samsung Electronics

Location No. R410,R501 R609 R105 VA71 C601 C105 C103 C111,C112 RY74 RY71 C110 C107,C108 C109 XTAL51 XC71,XC72 CR71 L101 FT71 BZ61 F701-1 F702 CN72 ST11 EARTH PCB

Code No. 2007-000109 2007-000119 2007-000931 1405-000154 R-CHIP R-CHIP R-CHIP VARISTOR

Description

Specification 1M-J 560-J 470-J INR14D561K-RS 47uF,20%,50V,GP,TP,105 ,6.3x11,5 470uF,20%,16V,GP,TP,8x11 .5,5,85 1000uF,20%,25V,GP,TP,10x 20,5 6.8uF,20%,450V,GP,TP,10x 16mm,5 PCJ-112D3MH,501X PCF-112D1M-2,20A 1nF 2.2nF 0.082nF 4MHZ 100nF 1.2uF 5mH SSU10V-1500S CBE2220BP 521-3150-401 LT-5-010-H YW396-05AV, WHT/ VH-5A,WHT,24(CWB) JT1916-01 EARTH CEM3 AC_COM

QTY 2 1 1 1 1 1 1 2 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1

SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

2401-002300 C-AL 2401-000037 C-AL 2401-000151 C-AL 2401-003518 C-AL 3501-001154 3501-001169 2201-000983 2201-000987 2201-002193 2802-001179 2301-001220 2301-001251 2702-001118 DB27-00017A 3002-001129 3601-000263 3601-001209 RELAY-MINIATURE RELAY-POWER C-CERAMIC,DISC C-CERAMIC,DISC C-CERAMIC,DISC RESONATOR-CERAMIC C-FILM,LEAD-PPF C-FILM,LEAD-PPF INDUCTOR-RADIAL COIL CHOKE BUZZER-PIEZO FUSE-CARTRIDGE FUSE-RADIAL LEAD

3711-000262 CONNECTOR-HEADER DB26-00015A DB93-04814A DB41-00526A DB93-04256B TRANS SWITCHING CONNECT WIRE PCB MAIN-INDDOR INDOOR SUB PBA

Samsung Electronics

6-2

Electrical Parts List

Indoor SUB PBA DB93-04256B


Location No. D701,D702,D703 ZD71 PC31,PC32 R703,R704 R701,R702 CN11 C302,C303 Q301,Q302 R302 R301 R303 R707 R706 C301 C705 C706 C703,C704 C701 C702 CN12 PCB Code No. 0402-001213 0403-001492 0604-001172 2003-002007 2003-000656 3711-006040 2203-000257 0504-001064 2007-000077 2007-000078 2007-000084 2007-000030 2007-000282 2203-000440 2203-001562 2203-000444 2301-000256 2401-000058 2301-000141 DB93-04350B DB41-00677A Description DIODE-RECTIFIER DIODE-ZENER PHOTO-COUPLER R-METAL OXIDE(S) R-METAL OXIDE(S) HEADER-BOARD TO BOARD C-CER,CHIP TR-DIGITAL R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP C-CER,CHIP C-CER,CHIP C-CER,CHIP C-FILM,LEAD-PEF C-AL C-FILM,LEADPEF;10nF,10%,630V, TP,16x11x7.5mm,5 CONNECT WIRE PCB SUB-INDDOR AC Specification MRA4005 1N4756 TLP181-GRH-TPL 4.7K-J 33K-J 25430WR-10A00 10nF,10% DTC114EKA 470-J 1K-J 4.7K-J 560-J 100K-J 1nF,10% 10nF,+80-20% 1nF,10% 4.7nF,10% 220uF,20%,100V,GP,TP,12.5x25,5,SHL 10nF 4P CEM3 QTY 3 1 2 2 2 1 2 2 1 1 1 1 1 1 1 1 2 1 1 1 1 SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

DISPLAY PCB : DB93-03117A


Location No.
C91 C92 CN92 COOL D91 R91 R92 RM91 SW91 TIMER TURBO

Code No.
2202-000780 2202-000173 3711-003846 0601-000552 0401-000005 2001-000109 2001-000109 0609-001204 3404-001220 0601-000552 0601-001373 DB41-00352A

Description
C-CERAMIC,MLC-AXIAL C-CERAMIC,MLC-AXIAL HEADER-BOARD TO CABLE LED DIODE-SWITCHING R-CARBON(S) R-CARBON(S) MODULE REMOCON SWITCH-TACT LED LED PCB SUB

Specification
100nF,+80-20%,50V,Y5V,-,3.5x19mm,1nF,10%,50V,Y5P,-,1.9x3.5mm,BOX,8P,1R,2mm,ANGLE,SN ROUND,GRN,3mm,570nm 1N4148,75V,150mA,DO-35,TP 470ohm,5%,1/2W,AA,TP,2.4x6.4mm 470ohm,5%,1/2W,AA,TP,2.4x6.4mm HORIZONTAL,6.5mm,TR 12V,50mA,160gf,6.1x6.1x5.0mm,SPST ROUND,GRN,3mm,570nm ROUND,RED,3mm,630nm WW1-P/J,TSE,FR-1,1,00,T1.6,-,-,-,-,DISP/MODULE/SWITCH

QTY 1 1 1 1 1 1 1 1 1 1 1 1

SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

6-3

Samsung Electronics

Electrical Parts List

OUTDOOR MAIN PCB : DB93-05543C(AQV09NSAX) DB93-05543D(AQV12NSAX)


Location No. D451,D452,D453,D454 D104,D105,D106,D301 D102,D107,D401,D402,D403 ZD31 ZD451,ZD452,ZD501,ZD502 ZD11 D201 Q301,Q302,Q801,*Q902 IC55,IC56 Q803 LED2 LED1 LED3 IC12,IC31,IC32 IC21 IC19 IC13 R301,R307 R107 R101 R418 R308 R419,R420,R421,R422,R423,R 424,R425 R505,R506,R508,R553 R303,R304,R323,R342 R302 R207,R208 R104,R413 R305,R315,R324,R325,R327,R 328,R415 R105 R552,R554,R555,R557,R558,R 560,R561,R562,R563,R573,R5 74,R902,R908 R601,R602 R306 R205,R206 R805,*R901 R116 R539,R540,R541 R807 R502 R407,R408,R409 R113,R114,R115 R808 R806 R501,R504 R462,R463,R464 R103 Code No. 0401-000133 0402-001427 0402-001429 0403-001492 0403-000258 0403-001499 0407-000123 0504-000127 0506-000175 0508-001132 DB98-16600A DB98-16601A DB98-16602A 0604-001172 1202-000104 1203-000274 1203-002948 2003-000685 2003-000699 2003-000855 2006-001013 2007-000070 Description DIODE-SWITCHING;RLS4148,75V,150mA,LL-34,TP DIODE-RECTIFIER;ES1D,200V,1A,DO-214AC,TP DIODE-RECTIFIER;US1J,600V,1A,DO-214AC,TP DIODE-ZENER DIODE-ZENER;MMBZ5232B,5%,225mW,SOT-23,TP DIODE-ZENER;MMSZ5252,5%,500MW,SOD-123,TP DIODE-ARRAY;DAN202K,80V,100mA,CA2-3,SOT23,TP TR-DIGITAL;FJV3102RMTF,NPN,200MW,10K/ 10K,SOT-23,T TR-ARRAY;2003,NPN,7,1W,SOP-16,ST,1000 TR-IGBT;-,600V,40A,2.6V,1200UJ,160W,TO-3P ASSY-LED GREEN;---------------------------------ASSY-LED RED;---------------------------------ASSY-LED YEL;---------------------------------PHOTO-COUPLER;TR,100-300,200mW,SOP,TP IC-VOLTAGE COMP.;393,SOP,8P,150MIL,DUAL,36V,C MO IC-POSI.FIXED REG.;7805,TO-220,3P,-,PLASTIC,4.8/5 IC-POSI.ADJUST REG.;TL431ACD,SOP,8P,4.9X3.9MM, PLA R-METAL OXIDE(S);4.7Kohm,5%,2W,AA,TP,4x12mm R-METAL OXIDE(S);470ohm,5%,1W,AA,TP,3.3x9mm R-METAL OXIDE(S);47Kohm,5%,3W,AA,TP,6x16mm R-CEMENT;0.02ohm,5%,7W,CA,BK,35x9.5x9.5mm R-CHIP;0ohm,5%,1/10W,TP,1608 Specification RLS4148 ES1D US1J 1N4756A MMBZ5232B MMSZ5252BD4 KDS184 FJV3102RMTF ULN2003D013TR SGH40N60UF TLPG5600 TLPR5600 TLPY5600 TLP181-GRH-TPL KIA393F KA7805A TL431ACD 4.7K-J 470-J 47K-J 0.02-J 0-J 100-J 330-J 470-J 560-J 2K-J 3.3K-J 4.7K-J 6.8K-J 10K-J 22Kohm 560-J 1.82K-F 10K-J 14.3K-F 2.2K-J 20-J 24K-F 33-J 470K-F 470-J 47-J 5.1K-F 5.6-J 680-J QTY 4 4 5 1 4 1 1 3 2 1 1 1 1 3 1 1 1 2 1 1 1 1 7 4 4 1 2 2 7 1 13 2 1 2 1 1 3 1 1 3 3 1 1 2 3 1 SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

2007-000074 R-CHIP;100ohm,5%,1/10W,TP,1608 2007-000076 2007-000077 2007-000119 2007-000080 2007-000082 R-CHIP;330ohm,5%,1/10W,TP,1608 R-CHIP;470ohm,5%,1/10W,TP,1608 R-CHIP;560ohm,5%,1/10W,TP,1608 R-CHIP;2Kohm,5%,1/10W,TP,1608 R-CHIP;3.3Kohm,5%,1/10W,TP,1608

2007-000084 R-CHIP;4.7Kohm,5%,1/10W,TP,1608 2007-000087 R-CHIP;6.8Kohm,5%,1/10W,TP,1608 2007-000090 R-CHIP;10Kohm,5%,1/10W,TP,1608 2007-000094 2007-000119 2007-000263 2007-000300 2007-000385 2007-000493 2007-000553 2007-000614 2007-000781 2007-000924 2007-000931 2007-000950 2007-000962 2007-000987 2007-001118 R-CHIP;22Kohm,5%,1/10W,TP,1608 R-CHIP;560ohm,5%,1/10W,TP,1608 R-CHIP;1.82Kohm,1%,1/8W,TP,2012 R-CHIP;10Kohm,5%,1/8W,TP,2012 R-CHIP;14.3Kohm,1%,1/4W,TP,3216 R-CHIP;2.2Kohm,5%,1/8W,TP,2012 R-CHIP;20ohm,5%,1/4W,TP,3216 R-CHIP;24Kohm,1%,1/10W,TP,1608 R-CHIP;33ohm,5%,1/8W,TP,2012 R-CHIP;470Kohm,1%,1/4W,TP,3216 R-CHIP;470ohm,5%,1/8W,TP,2012 R-CHIP;47ohm,5%,1/4W,TP,3216 R-CHIP;5.1Kohm,1%,1/10W,TP,1608 R-CHIP;5.6ohm,5%,1/8W,TP,2012 R-CHIP;680ohm,5%,1/8W,TP,2012

Samsung Electronics

6-4

Electrical Parts List

OUTDOOR MAIN PCB : DB93-05543C(AQV09NSAX) DB93-05543D(AQV12NSAX)(cont.)


Location No. R201,R202,R203,R204 R110,R111,R112 C106,C107,C304,*C901 C401,C402,C403,C404,C405,C 406 C201,C203,C204,C205,C302,C 305,C306,C307,C451,C453,C5 67,C906 C303,C408,C421,C601,C602 C308,C318,C319,C320,C321 C105,C802
C108,C112,C116,C121,C202,C400,C41 2,C413,C414,C415, C417,C419,C452,C 454,C513,C514,C516,C518,C519,C553, C554,C560,C561,C563,C565,C568,C57 0,C575,C576,C803 ,C907,C910

Code No.

Description

Specification

QTY 4 3 3 6 12 5 5 2 32 1 1 1 1 5 7 3 1 1 1 1 2 1 1 2 1 2 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1

SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

2007-002667 R-CHIP;90.9Kohm,1%,1/4W,TP,3216 90.9K-F 2007-008023 R-CHIP;100Kohm,5%,1W,TP,6432 100K-J 2201-000322 C-CERAMIC,DISC;2.2NF,10%,2KV,Y5P,TP,13X5MM,10 2.2nF 2203-000236 C-CER,CHIP;0.1NF,5%,50V,C0G,TP,1608 2203-000257 C-CER,CHIP;10nF,10%,50V,X7R,TP,1608 2203-000440 C-CER,CHIP;1nF,10%,50V,X7R,TP,1608,2203-002002 C-CER,CHIP;33pF,5%,50V,NPO,BK,1608,2203-002398 C-CER,CHIP;22nF,10%,50V,X7R,1608 2203-005249 C-CER,CHIP;100nF,10%,50V,X7R,TP,1608,2203-006348 C-CER,CHIP;1000nF,10%,25V,X5R,1608 C-FILM,LEAD2301-000141 PEF;10nF,10%,630V,TP,16x11x7.5mm,5 2301-001331 C-FILM,LEAD-PEF;10nF,5%,100V,TP,7.5x4x7mm,5 2306-000123 C-FILM,LEAD-PPF;100nF,5%,630V,BK,26x16.5x8.5,2 2401-000832 C-AL;220uF,20%,25V,GP,TP,8x11.5,5 2401-001907 C-AL;10uF,20%,16V,BP,TP,5x11mm,5mm 2401-002300 2401-002598 2401-003541 2401-003736 2802-001198 C-AL;47uF,20%,50V,GP,TP,6.3x11,5 C-AL;220uF,20%,50V,GP,TP,10x16,5 C-AL;10uF,20% ,450V,WT,TP,12.5x20mm,5 C-AL;22UF,20%,50V,WT,TP,5X11MM,2 RESONATOR-CERAMIC;10MHZ,0.5%,BK,8X3X5.5MM
RELAY-

0.1nF 10nF 1nF 33pF 22nF 100nF 1000nF 10nF 10nF 100nF 220uF 10uF 47uF 220uF 10uF 22uF 10MHZ PCJ112D3MH,501X SMW250-06 SMW200-10 TAB MN103SFA7K ACS712 FSBS15CH60 GS1B2560 FEP30JP KFR-35GW/GPI 1.8K-F TLP351 FSDH321 470uF FORTE1 12K FORTE1 9K EARTH 4WAY COMM-N COMP REACTOR MOTOR MONBLANC

C113 C001 C301 C418 C110,C114,C119,C123,C804 C552,C559,C562,C564,C569,C 574,C577 C409,C410,C411 C416,*C905 C122 C104 XTAL RY501,*RY502 CN54 CN30 AC_L,AC_N IC01 IC451,IC452 IPM BD01 D101 PT02 R106 IC81 IC11 C101,C102,C103 IC501 IC501

WIRE-FAN 160*140

3501-001154 MINIATURE;12Vdc,200mW,3000mA,1FormA,10mS,10m HEADER-BOARD TO CABLE;BOX,6P,1R,2.5mm,STRAI 3711-001036 GHT,SN CONNECTOR3711-004182 HEADER;BOX,10P,1R,2MM,STRAIGHT,SN,NTR 3712-001139 CONNECTOR-TERMINAL;TAB,MALE,-,6.35X0.8MM Montblanc1 OUTDOOR Inv DB91-00532A Micom,MN103SFA7K,80P, ROM Size: 256K bytes SENSOR MAG-CT SENSOR;ASC712,5HP DB32-00173A INVERTER,-,-40~150 DB95-00599A ASSY-IPM;KFR-35GW/GPI,INVERTER DB98-16586A ASSY-DIODE;GS1B2560 DB98-16591A ASSY-DIODE RECTIFIER;FEP30JP DB98-20602A ASSY-PULSE TRANS;KFR-35GW/GPI,INVERTER DB98-20665A ASSY-RESISTOR;KFR-35(25)GW/GPI,1.8k F 1608 DB98-20678A ASSY-PHOTOCOUPLER;KFR-35(25)GW/GPI,TLP351 DB98-20679A ASSY-FPS;KFR-35(25)GW/GPI,FSDH321 DB98-21655A ASSY-CAP;KFR-35(25)GW,KMH400VS470 DB91-00531A EEPROM DATA DB91-00530A EEPROM DATA DB39-00514F CONNECT WIRE DB93-04349A CONNECT WIRE DB93-04348C CONNECT WIRE DB93-04336A CONNECT WIRE DB93-04348B CONNECT WIRE DB93-06156A CONNECT WIRE DB41-00626A PCB

6-5

Samsung Electronics

Electrical Parts List

OUTDOOR EMI PBA DB93-04264A


Location No. FUSE DSA FT00,FT01 FUSECLIP LEAD WIE EARTH L/W AC_L L/W AC_N TB-L,TB-N PCB VA04,VA07,VA08,VA09 C001,C002,C010,C011 C003 C004 Code No. Description Specification 326-020 DA38-362 LS615044 / TF4330-361M10R0 HF-005/T LEAD WIRE-EARTH L/W AC_L L/W AC_N CBF LEAD WIRE-POWER FR1 TVR14561KORSY / GNR14D561KCG 4.7nF 680nF 330nF 4.0*3.0*2.3mm 5.0*3.0*4.3mm QTY 1 1 2 2 1 1 1 1 1 4 4 1 1 8 4 SA/SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA SNA

3601-001159 FUSE-CARTRIDGE 4715-001093 POSISTOR DB98-17990A ASSY-EMI FILTER 3602-001038 DB39-00514F DB39-00961T DB39-00961U DB39-00998C DB41-00532A 1405-000154 2201-000540 2301-001285 2301-001325 6042-001009 6042-001012 FUSE-CLIP CONNECT WIRE LEAD WIRE LEAD WIRE C/W POWER PCB OUTDOOR EMI VARISTOR C-CERAMIC,DISC C-FILM,LEAD-PPF C-FILM,LEAD-PPF EYELET EYELET

Samsung Electronics

6-6

7. Wiring Diagram
7-1 Indoor Unit

This Document can not be used without Samsungs authorization.

7-1

Samsung Electronics

7-2 Outdoor Unit

This Document can not be used without Samsungs authorization.

Samsung Electronics

7-2

8. Schematic Diagram
8-1 Indoor Unit

This Document can not be used without Samsungs authorization.

Samsung Electronics

8-1

8-2 Outdoor Unit

This Document can not be used without Samsungs authorization.

Samsung Electronics

8-2

9. Circuit Descriptions
9-1 PCB Circuit Descriptions
9-1-1 Indoor Unit

SMPS
INDOOR FAN CONTROL ZERO CROSSING PART INDOOR TEMPERATURE SENSOR

BUZZER PART
SUB PCB CONNECTOR DISPLAY STEP MOTOR & ION

This Document can not be used without Samsungs authorization.

Samsung Electronics

9-1

Circuit Descriptions

Circuit Descriptions

9-1-2 Outdoor Unit

TEMPERATURE SENSOR & EEV BLDC FAN COMMUNICATION PFC SMPS INVERTER

This Document can not be used without Samsungs authorization.

Samsung Electronics

9-2

9-2 Refrigerating Cycle Diagram

Indoor Unit

Outdoor Unit

Capillary tube T1 Liquid side 2 way valve

Check valve

Capillary tube Cross Fan Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Propeller Fan

T2 Gas side 3 way valve 4 way valve Cooling Compressor Heating Gas Leak Check Point

9-3

Samsung Electronics

10. PCB Diagram


10-1 Indoor PCB
The red number connecter is not used.
7 2 3 6 4 5

8 9 10

11

12

1 2 3 4 5 6

Power Motor RPM Feedback Remocon Module Humidity Sensor Anions MPI

7 8 9 10 11 12

Temperature Sensor Auto Grill HVPS(High voltage Generator) BLADE-H Step Motor Display Indoor Fan Motor

Samsung Electronics

10-1

10-2 Outdoor PCB


The red number connecter is not used.

10

1 2 3 4 5

Power N Power L BLDC FAN AC FAN Communication 485

6 7 8 9 10

COND/OLP Temperature Sensor DIS/OUT Temperature Sensor EEV Connector Comp. Connector Wire Reactor Connector Wire

10-2

Samsung Electronics

11. Operating Instructions


11-1 Name of Each Part
11-1-1 Indoor Unit

The design and shape are subject to change according to the model.

Air Inlet

Temperature sensor

Power(On/Off) button Air filter (under the grille) Air flow blades (outlet)

Operation indicator (GREEN) Timer indicator (GREEN) Turbo indicator (RED) Power(On/Off) button

Samsung Electronics

11-1

Operating Instructions

11-1-2 Outdoor Unit

Air Inlet (Rear)

Air Outlet

Connection Valve

Air Inlet (Rear)

Air Outlet

Connection Valve

11-2

Samsung Electronics

11-2 Wireless Remote Control-Buttons and Display

Remote control transmission indicator Operating mode indicator ( AUTO, COOL, DRY, FAN, HEAT) Temperature setting Turbo function indicator

Mode selection button (AUTO, COOL, DRY, FAN, HEAT) Temperature adjustment buttons

Turbo button Good Sleep mode indicator Fan speed & Silence indicator Air ow direction On Timer indicator Fan speed adjustment button & Silence mode button Swing button On Timer button O Timer button

O Timer indicator Battery discharge indicator

Good Sleep button

On/O & Timer Set/Cancel button

Samsung Electronics

11-3

11-3 Main Function


11-3-1 Basic Function
Mode Auto Mode
Press the

Explanation
button on the remote control until is displayed.

Remark

Cool Mode

Press the

button on the remote control until

is displayed.

Press the is displayed.

button to select the fan speed until the required setting )

Automatic (rotated : Low Medium High Maximum Silence mode

Heat Mode

Press the

button on the remote control until

is displayed.

Press the is displayed.

button to select the fan speed until the required setting

Automatic (rotated : Low Medium High Maximum Silence mode

11-4

Samsung Electronics

Operating Instructions

Basic Function(cont.)
Mode Dry Mode
Press the

Explanation
button on the remote control until is displayed.

Remark

Fan Mode

Press the

button on the remote control until

is displayed.

11-3-2 Applied Function


Mode Turbo Function
Press the button.

Explanation

Remark

After 30 minutes, the air conditioner is reset automatically to the


previous mode, temperature and fan settings.

You can select the Turbo function in the Auto, Cool and Heat mode.
If you select this function in the Dry or Fan mode, it will return to the Auto mode.

good'sleep Mode

Press the button one or more times until remote control.

is displayed on your

Samsung Electronics

11-5

12. Troubleshooting
12-1 Items to be checked first
1. The input voltage should be rating voltage 10% range. The air conditioner may not operate properly if the voltage is out of this range. Is the link cable linking the indoor unit and the outdoor unit linked properly? The indoor unit and the outdoor unit shall be linked by 5 cables. Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. Otherwise the air conditioner may not operate properly. When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the malfunction of the air conditioner.
No 1 Operation of air conditioner The OPERATION indication LED(BLUE) blinks when a power plug of the indoor unit is plugged in for the first time. Explanation It indicates power is on. The LED stops blinking if the operation ON/OFF button on the remote control unit is pushed.

2.

3.

In a COOL operation mode, the compressor does not operate at a room temperature higher than the setting temperature that the INDOOR FAN should operate. [In case of heat pump model] In a HEAT operation mode, the compressor does not operate at a room temperature lower than the setting temperature that indoor fan should operate. Fan speed setting is not allowed in DRY( ) mode.

In happens after a delay of 3 minutes when the compressor is reoperated. The same phenomenon occurs when a power is on. As a phenomenon that the compressor is reoperated after a delay of 3 minutes, the indoor fan is adjusted automatically with reference to a temperature of the air blew.

The speed of the indoor fan is set to LL in DRY mode. Fan speed is selected automatically in AUTO mode. ) Compressor operation is controlled automatically in DRY mode depending on the room temperature and humidity. Timer is being activated and the unit is in ready mode. The unit operates normally if the timer operation is cancelled. The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozen depending on the inside/outside air temperature. When the unit is turned off while de-ice is activated, the compressor continues operation for up to 9 minutes(maximum) until the deice is completed. The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protect the compressor from overheated air in a HEAT mode. The compressor operates in a reverse cycle to remove exterior ice in a HEAT mode, and indoor fan and outdoor fan do not operate intermittently for within 20% of the total heater operation

Compressor stops operation intermittently in DRY( mode.

Timer LED(ORANGE) of the indoor unit lights up and the air conditioner does not operate. The compressor stops intermittently in a COOL mode or DRY mode, and fan speed of the indoor unit decreases.

[In case of heat pump model] Compressor of the outdoor unit is operating although it is turned off in a HEAT mode. [In case of heat pump model] The compressor and indoor fan stop intermittently in HEAT mode. [In case of heat pump model] Indoor fan and outdoor fan stop operation intermittently in a HEAT mode.

12-1

Samsung Electronics

12-2 Fault Diagnosis by Symptom


12-2-1 No Power (completely dead)-Initial diagnosis
1. Checklist : 1) Is input voltage normal? 2) Is AC power linked correctly? 3) Is input voltage of DC regulator IC KA7805 (IC02) normal? (11VDC-12.5VDC) 4) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC) 2. Troubleshooting procedure

Unplug the power cord and plug it after 30 seconds

Press the Power Button on the remote control unit to operate the air conditioner does not operate Check the indoor unit control board Yes

operate

Check the display board

Check whether 2 wires of power cord are connected correctly to the terminal block and control board.

No

Reconnect wires correctly

Yes Check whether the fuse on the control board is normal. FUSE(F701) : T3.15[A]/250[V]

No

Replace fuse

Yes

Check the output of SMPS on the control board. Input power: AC23015%[V] IC02 Input: DC12[V] IC02 output: DC5[V]

No

PCB should be replaced

Yes Check the setting temperature

Samsung Electronics

12-2

Troubleshooting

12-2-2 The Outdoor unit power supply error


1. Checklist : 1) Are the input power voltage and the power connection correct? 2) Is there no Fuse short in the indoor unit and outdoor unit? 3) Is the cable connected correctly between the indoor unit and outdoor unit in order. 4) Is the wire connected correctly to the terminal block of the indoor unit and outdoor unit? 2. Troubleshooting procedure

Is the voltage of indoor unit terminal block 1 and 2 correct after power input?

No

Is the R701 resistance of indoor PCB 200?

No

Exchange the PCB.

Yes Is the indoor unit fuse normal? Pull out the power cord and execute the following step after 30 seconds.

No

Exchange the fuse.

Is the outdoor unit normal? Yes Is the outdoor unit normal? Is the reactor connected correctly? Yes Is the +, - of C102 short?

No

Exchange the fuse.

No

Connect the reactor wire.

No

Disassemble the PCB from the case. Yes

Yes

Is there no error at the insertion of PCB? Yes

Exchange the PCB. Yes Is the +,- of C102 short? Yes Exchange the PCB. No

Exchange the PCB.

Are the BLDC FAN Wire 1 and 3 short? Yes Exchange the BLDC FAN.

Normal Operation

Exit

12-3

Samsung Electronics

Troubleshooting

12-2-3 When the Up/Down Louver Motor Does Not Operate. (Initial Diagnosis)
1. Checklist : 1) Is input voltage normal? 2) Is the Up/Down louver motor properly connected with the connector (CN61)? 2. Troubleshooting procedure

Unplug the power cord and plug it after 30 seconds

Is STD lamp blinking?

No

Check as in the procedure No Power.

Yes Does operation start when swing button of the remote control unit pushed? No Voltage at pin #30~#34 of micom (IC04) change?(Squarewave)

Yes

Normal

No

Micom (IC04) is faulty.

Yes Voltage at pin #2 ~ #5 of CN61(motor connector) change?(Squarewave) Yes Up/Down louver motor is faulty.

No

Driver IC05/06 (ULN2003A) is faulty.

Samsung Electronics

12-4

Troubleshooting

12-2-4 The Outdoor unit Fan error


1. Checklist : 1) Are the input power voltage and the power connection correct? 2) Is the motor wire connected to the outdoor PCB correctly? 3) Is there no assembly error or none-assembly in the terminal of motor wire connector? 4) Is there no obstacle at the surrounding of motor and propeller? 2. Troubleshooting procedure

Is the Pin voltage of CN01 #1, #3 over 250V? Yes Is the Pin voltage of CN01 #3, #5 within 1V~5V during the operation?

No

Follow the Check Procedure of outdoor unit power supply error check.

No

Does the Pin voltage of IC01(MICOM) No.13 change?(Square-Wave) Yes FAN DRIVE CIRCUIT (Q901,Q902 etc.) error

No

Exchange the PCB.

Yes

Exchange the PCB.

MICOM Error

Is the Pin voltage of CN01 #6 changed during the operation?(Square-Wave)

No

Pull out the power cord and execute the following step after 30 seconds.

Disassemble the BLDC FAN Wire.

Yes

Is the short between the BLDC FAN Wires? Yes Exchange the BLDC FAN MOTOR.

No

Exchange the PCB.

Exchange the PCB.

12-5

Samsung Electronics

Troubleshooting

12-2-5 Total current Trip error


1. Checklist : 1) Is the input power voltage proper? 2) Is the refrigerant charged properly? 3) Does the compressor rotate normally? (Reverse rotation, Locking etc.) 4) Dose the outdoor fan operate normally? (Fan propeller loss, Motor error etc.) 5) Is the installation condition of outdoor unit good? (Piping, Space etc.) 6) Is there no ventilation obstruction at the surrounding of outdoor? (Outdoor unit cover, Fan front obstruction etc.) 2. Troubleshooting procedure

Is the installation of outdoor unit good? Yes Dose the compressor rotate normally?

No

Reinstall and remove the obstruction.

No

Exchange the compressor.

Yes Is the assembly of R418, R413, IC41, C437 and the peripheral part good? Yes Pull out the power cord and exchange the PCB from the case after 30 seconds. No Exchange the PCB.

Is the assembly of Micom and peripheral circuit part good? Yes Check again after assembly of PCB.

No

Exchange the PCB.

Samsung Electronics

12-6

Troubleshooting

12-2-6 In case of heating at the cooling mode or cooling at the heating mode
1. Troubleshooting procedure

Is the Thermo off?

Yes

Change the setting temperature of remote control.

No Is the unit in the defrosting operation? Yes

Operate it with a heating mode as soon as the defrosting is finished.

No Is the compressor in 3 minutes off? Yes

After 3 minutes, cooling and heating start automatically.

No No

Indoor operation SW is on.

Turn the SW On.

Yes Is the outdoor air sensor and outdoor heat exchanger attached correctly? Yes No

Is much frost in the heat exchanger?

Yes

No

Attach the sensor correctly.

Over shortage of the refrigerant

Does the 4 way valve operate normally?

No

Is the 4 way valve connector connected correctly?

No

Connect the connecter correctly.

Yes Check the resistance value of 4 way valve coil. OK NG

4-WAY valve coil error

Dose the voltage of AC 220V apply to the connector of 4 way valve coil during the operation? Yes Go to the next page 4 way valve main body error

No

Exchange the outdoor PCB.

12-7

Samsung Electronics

Troubleshooting

In case of heating at the cooling mode or cooling at the heating mode(cont.)

From the previous page

Does the EEV operate normally?

No

Is much frost in the heat exchanger?

No Connect the connector.

Yes Check the resistance value of EEV coil. OK NG EEV coil error

Yes

Is much frost in the heat exchanger?

No

Exchange the out PCB.

Yes EEV main body error

Does the outdoor fan operate at the operation of compressor? No

Yes

The over shortage of refrigerant, Insufficient Capacity, Load estimation error

Is the outdoor fan connected correctly? Yes Check the resistance value of outdoor fan. OK

No

Connect the connector.

NG

Outdoor fan error

Dose the voltage of DC300V apply to the connector of outdoor fan during the operation of outdoor unit? No Outdoor PCB error

Yes Check the motor wire.

Samsung Electronics

12-8

Troubleshooting

12-2-7 Outdoor temperature sensor error


1. Checklist : 1) Is the sensor connector connected correctly? 2) Is the sensor placed correctly? 3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature? 4) Is the resistance value of sensor connection pull_up correct? 2. Troubleshooting procedure

Is the sensor connector connected correctly in accordance with a color? Yes No Is the temperature sensor connected correctly without separation? Yes Does the both terminal of sensor satisfy the resistance value in accordance with temperature? (Refer to the R/T TABLE) Yes No Is the resistance value of sensor connection pull_up 18.2K? Yes No No No

Reconnect the sensor connector.

Change the position of sensor.

Exchange the sensor.

Exchange the PCB.

Exchange the PCB.

Normal operation

Exit

400.0 350.0 300.0 250.0 200.0 150.0 100.0 50.0 0.0


-50 -41 -32 -23 -14 4 103 -5 13 22 31 40 49 58 67 76 85 94

12-9

Samsung Electronics

Troubleshooting

12-2-8 Discharge temperature sensor error


1. Checklist : 1) Is the sensor connector connected correctly? 2) Is the sensor placed correctly? 3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature? 4) Is the resistance value of sensor connection pull_up correct? 2. Troubleshooting procedure

Is the sensor connector connected correctly in accordance with a color? Yes No Is the temperature sensor connected correctly without separation? Yes Does the both terminal of sensor satisfy the resistance value in accordance with temperature? (Refer to the R/T TABLE) Yes No Is the resistance value of sensor connection pull_up 24K? Yes No No No

Reconnect the sensor connector.

Change the position of sensor.

Exchange the sensor.

Exchange the PCB.

Exchange the PCB.

Normal operation

Exit

600.0 500.0 400.0 300.0 200.0 100.0 0.0


0 8 104 112 120 128 136 144 152 160 16 24 32 40 48 56 64 72 80 88 96

Samsung Electronics

12-10

Troubleshooting

12-2-9 Coil temperature sensor error


1. Checklist : 1) Is the sensor connector connected correctly? 2) Is the sensor placed correctly? 3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature? 4) Is the resistance value of sensor connection pull_up correct? 2. Troubleshooting procedure

Is the sensor connector connected correctly in accordance with a color? Yes No Is the temperature sensor connected correctly without separation? Yes Does the both terminal of sensor satisfy the resistance value in accordance with temperature? (Refer to the R/T TABLE) Yes No Is the resistance value of sensor connection pull_up 18.2K? Yes No No No

Reconnect the sensor connector.

Change the position of sensor.

Exchange the sensor.

Exchange the PCB.

Exchange the PCB.

Normal operation

Exit

400.0 350.0 300.0 250.0 200.0 150.0 100.0 50.0 0.0


-50 -41 -32 -23 -14 4 103 -5 13 22 31 40 49 58 67 76 85 94

12-11

Samsung Electronics

Troubleshooting

12-2-10 Fan error


1. Checklist : 1) Isnt the fan locked? 2) Is the sensor placed correctly? 3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature? 4) Is the resistance value of sensor connection pull_up correct? 2. Troubleshooting procedure

Isn't the Fan locked?

Remove the Fan lock.

Yes Is the connector connected correctly? No

No Connect the connector.

Yes No Is the color of Fan wire matched correctly? No Exchange the Fan.

Yes Exchange the PCB. Normal operation

Exit

Samsung Electronics

12-12

Troubleshooting

12-2-11 DC-Link voltage sensor error


1. Checklist : 1) Is the voltage of indoor unit terminal block 1, 2 correct after power supply? 2) Is the capacitor(C101, C102, C103) for DC-Link assembled in accordance the specification? 3) Are R112, R113, R114 470 Kohm? 4) Is R115 14.3Kohm? 2. Troubleshooting procedure

Is the voltage of indoor unit terminal block 1, 2 correct after power supply? Yes Is the capacitor(C101, C102, C103) for DC-Link assembled in accordance the specification? Yes Are R113, R114, R115 470kohm? Yes Is R116 14.3kohm? Yes No No No

Apply the troubleshooting for outdoor unit power supply error.

No Connect the connector.

Exchange the PCB.

Exchange the Fan.

Exchange the PCB.

Normal operation

Exit

12-13

Samsung Electronics

Troubleshooting

12-2-12 O.C.(Over Current) error


1. Checklist : 1) Is the Shunt resistance value correct? 2) Is the condition of surrounding temperature abnormal overload? 3) Is there any problem as like the temperature sensor separation or measurement value error? 4) Is the interphase resistance of compressor normal? 2. Troubleshooting procedure

Restart after power off.

Is the O.C.(Over Current) error occurred? Yes Is the Shunt resistance value normal? Yes Is the interphase resistance value of compressor (uv, vw, wu) normal? Yes Is the compressor body and interphase resistance insulated? Yes Is the condition of indoor/outdoor temperature normal load?

No

Terminate the service.

No

Exchange the PCB.

No

Exchange the Compressor.

No

Exchange the Compressor.

No

Restart after returning to the normal load.

Yes Yes Is the O.C. error occurred again? No Terminate the service.

Is the position of temperature sensor and the sensing value normal? Yes Is the connection cable for the compressor and power terminal normal? Yes Exchange the PCB.

No

Correct the sensor position or exchange the sensor.

No

Correct the cable connection.

Samsung Electronics

12-14

Troubleshooting

12-2-13 Communication error


1. Checklist : 1) Is the communication cable between the indoor unit and outdoor unit connected correctly? 2) Isnt the power cable and communication cable error? 2. Troubleshooting procedure

Restart after power off.

Is the communication error occurred again? Yes Isn't the power cable and communication cable error? Yes Is the connection of communication cable normal? Yes Is it the outdoor 2 Micom(Inverter + Main) model? Yes Exchange the outdoor unit PCB.

No

Terminate the service.

No

Correct the wrong wiring.

No

Correct the connection of communication cable.

No

Exchange the indoor/outdoor unit PCB.

12-15

Samsung Electronics

Troubleshooting

12-2-14 Compressor start error


1. Checklist : 1) Is the connection of cable for the compressor and power? 2) Is the interphase resistance of compressor normal? 2. Troubleshooting procedure

Restart after power off.

Is the restart error occurred again? Yes Is the interphase resistance value of compressor (uv, vw, wu) normal? Yes Is the compressor body and interphase resistance insulated? Yes Is the connection cable for the compressor and power terminal normal? Yes Exchange the PCB.

No

Terminate the service.

No

Exchange the compressor.

No

Exchange the compressor.

No

Correct the cable connection.

Samsung Electronics

12-16

Troubleshooting

12-2-15 Compressor lock error


1. Checklist : 1) Is the connection of cable for the compressor and power? 2) Is the interphase resistance of compressor normal? 2. Troubleshooting procedure

Restart after power off.

Is the lock error occurred again? Yes Is the interphase resistance value of compressor (uv, vw, wu) normal? Yes Is the compressor body and interphase resistance insulated? Yes Is the connection cable for the compressor and power terminal normal? Yes Exchange the PCB.

No

Terminate the service.

No

Exchange the compressor.

No

Exchange the compressor.

No

Correct the cable connection.

12-17

Samsung Electronics

Troubleshooting

12-2-16 DC Link Over voltage/ Low voltage error


1. Checklist : 1) Is the power voltage normal? 2) Is the voltage of front and back terminal of indoor(outdoor) power relay normal? 3) Is the resistance value for DC Link voltage detection NORMAL? 4) Is the resistance value of DC Link discharge normal? 5) Is the appearance of DC Link Capacitor normal? 2. Troubleshooting procedure

Restart after power off.

Is the DC Link voltage error occurred again? Yes Is the power voltage normal? Yes Is the front and back terminal voltage of indoor/outdoor power relay normal? Yes Reassembly the PCB. Yes Is the appearance of DC Link Capacitor normal? Yes Is the resistance for the detection of DC Link voltage normal? Yes Is the resistance value of DC Link discharge normal? Yes Is the reactor insulation damaged? Yes Exchange the reactor.

No

Terminate the service.

No

Terminate the service.

No

Exchange the PCB.

No

Exchange the PCB.

No

Exchange the PCB.

No

Exchange the PCB.

No

Exchange the PCB.

Samsung Electronics

12-18

Troubleshooting

12-2-17 When the remote control is not receiving


1. Check if the connector was normally assembled. 2. Put the set in operation and check the voltage of No. 15(+) and No. 16(-) of the main PCB CN91 while operating the remote control. When the voltage descends below 3V, the assembly module PCB is normal and the main PCB is poor. Then replace the main PCB. 3. Replace the assembly display PCB because the module PCB is poor if the voltage between No. 15~16 of CN91 maintains 5V after the remote control starts operation.

12-2-18 The others


1. AC Line Zero Cross Signal OUT Check the assembly condition of peripheral part of IC21, ZD21, ZD20 and D200 on the PCB. 2. Capacity miss match Check again the indoor unit option code.

12-19

Samsung Electronics

12-3 PCB Inspection Method


12-3-1 Pre-inspection Notices
1. Check if you pulled out the AC power plug when you eliminate the PCB or front panel. 2. Dont hold the PCB side not impose excessive force on it to eliminate the PCB. 3. Dont pull the lead wire but hold the whole housing to connect or disconnect a connector to the PCB. 4. In case of outdoor PCB disassembly, check first the complete discharge of condenser (C103) after 30 seconds power off.

12-3-2 Inspection Procedure


1. Check connector connection and peeling of PCB or bronze coating pattern when you think the PCB is broken. 2. The PCB is composed of the 3 parts. 1. Indoor Main PCB Part : MICOM and surrounding circuit, relay, room fan motor driving circuit and control circuit, sensor driving circuit, power circuit of DC12V and DC5V, and buzzer driving circuit. 1. Display part : LED lamp, Switch, Remocon module 1. Outdoor Main PCB part : MICOM and surrounding circuit. IPM and PFC circuit and control circuit. 1. EMI PCB Part : Line filter and Noise Capacitor, Varistor

12-3-3 Indoor Detailed Inspection Procedure


No 1 Procedure Plug out and pull the PCB out of the electronic box. Check the PCB fuse. Supply power. If the operating lamp twinkles at this time, the above 1)~3) have no relation. Inspection Method 1) Is the fuse disconnected? Cause

Over current Indoor Fan Motor Short AC Part Pattern Short of the MAIN PCB

Checking the power voltage. 1) Is the DB71 input voltage AC200V~AC240V?

Power Cord is fault, Fuse open. Wrong Power


Cable Wiring, AC Part is faulty.

2) Is the voltage between both terminals of the C104 on the 2nd side of the transformer DC12V 0.5V? 3) Is the voltage between both terminals of OUT and GND of IC19(KA78L05) DC5V 0.5V? 3 Press the ON/OFF button. Checking the power voltage. 1) Is the voltage over AC180V being imposed on 1) terminal #3 and #5 of the fan motor connector(CN72)? 2) Check the voltage of both terminals of terminal block 1 and N(1) after 3 minute operation.: AC220V 4 Press the ON/OFF button. 1. FAN Speed [High] 2. Continuous Operation 1) Is the voltage over AC180V being imposed on 1) terminal #3 and #5 of the fan motor connector(CN72)? 2) The fan motor of the indoor unit doesnt run.

Switching Trans or Power Circuit is faulty

Power Circuit is faulty, Load Short

Relay(RY71) Coil Disconnection, IC05 is faulty

Relay(RY71) Contact is faulty

Fan Motor of the indoor is faulty

Fan Motor Connector(CN72) is faulty

3) The power voltage between terminal #3 and #5 of the connector(CN72) is 0V.

ASSY Main PCB is faulty Connection is faulty

Samsung Electronics

12-20

Troubleshooting

12-3-4 Outdoor Detailed Inspection Procedure


No 1 Procedure Wait 30 seconds over after disconnecting the power cable Check the outdoor PCB. Inspection Method 1) Is C101 discharged? 2) Is the resistance of both terminals of C101 opened? 3) Is the fuse of EMI PCB normal? 4) Is the reactor wire connected? Cause

Over Current Inner short of PCB BLDC FAN Motor Error

Check the Outdoor unit PCB.

1) Is R701 200ohm? 2) Does ry74 operate normally? (IC05 & 16:0V, 1:5V) 3) Is the fuse(F701) normal? 4) Is the Sub PCB assembled normally?

Outdoor PCB Error SUB Relay(RY74) Error IC05 Error Indoor PCB Error

Check the LED lighting after power supply.

1) Normal: Red: Light On, Green: Flickering, Yellow: Light Off? 2) Is the voltage of C101 250V over? 3) Is the input of IC19 8V, and the output 5V? 4) Recheck after disassembling BLDC FAN Wire.

Inner short of outdoor PCB Wrong assembly of outdoor PCB BLDC FAN Error

1) Is the green LED light on once per second? Check the condition of indoor & outdoor connec- 2) Is the indoor & outdoor connection able connected in order? tion cable. 3) Is the grounding wire connected to the both of indoor & outdoor unit? 4) Is the voltage of terminal block N(1), 225V? Check the Comp Wire. 1) Is it connected red, blue, and yellow in order in counterclockwise. 2) Are the valve and its installation condition good? 3) Is the installation condition of outdoor unit?

Wrong connection of Indoor/Outdoor wiring Wrong assembly of outdoor


communication circuit

Wrong assembly Installation condition is bad.

Check the BLDC Fan.

1) Is CN01 1, 3 over 250V? 2) Is CN01 3, 5 within 1V~5V? 3) Is the voltage of CN01 6 changed? 4) Is the resistance of BLDC Motor 1, 3 opened after power off?

Outdoor PCB Error BLDC Motor Error

12-21

Samsung Electronics

12-4 Main Part Inspection Method


Part Room Temperature Sensor Measure resistance with a tester Normal Abnormal Room Fan Motor At the normal temperature 37k~ 8.3k(-7C~+30C) *Refer to Table 12-3-4. , 0 . . . Open or Short Breakdown Inspection Method

Measure the resistance between terminals of the connector (CN72) with a tester. Normal At the normal temperature (10C ~ 30C)
Compare terminal Yellow, Blue Yellow, Red Resistance 404.4 10% 340 10% Remark Main Sub

Abnormal Stepping Motor

, 0 . . . Open or Short

Measure the resistance between the red wire and each terminal wire with a tester. Normal Abnormal About 300 at the normal temperature (20C ~ 30C) , 0 . . . Open or Short

Samsung Electronics

12-22

13. Block Diagram


13-1 Indoor Unit
CONTROLLER
IC-MCU
HEAT EXCHANGER SENSOR BLADE CONTROL ROOM TEMPERATURE SENSOR INFRARED SIGNAL INDOOR FAN MOTOR CONTROL OUTDOOR COMMUNICATION POWER RELAY CONTROL TEMPERATURE CONTROL TIMER BUZZER MELODY CONTROL ANION CONTROL OSCILLATION CIRCUIT DISPLAY PART TEMPERATURE OPERATION AUTO CLEAN TURBO ENERGY SAVING TIMER ANION FAN SPEED *: OPTION

REMOTE CONTROL

ZERO VOLTAGE DETECT

POWER ON/OFF COMPRESSOR CONTROL SIGNAL STEPPING MOTOR CONTROL SIGNAL BUZZER MELODY CONTROL SIGNAL ANION CONTROL SIGNAL*

TRIGGER SIGNAL

MODE (AUTO, COOL, DRY, FAN, HEAT)

SSR

INDOOR FAN MOTOR

TURBO OPERATION FAN SPEED SELECT (H/M/L/ AUTO) BLADE-H MOVING SELECT ON, OFF TIMER SELECT/CANCEL TEMPERATURE SELECT(UP/DOWN) SLEEP OPERATION

COMMUNICATION SIGNAL

OUTDOOR UNIT

STEPPING MOTOR DRIVE BUZZER DRIVE ANION DRIVE*

BUZZER

COMPRESSOR OUTDOOR FAN MOTOR 4-WAY VALVE

ANION STEPPING MOTOR : BLADE CONTROL

MELODY CONTROL PART DC5V VOLTAGE REGULATOR SPEAKER

ANION SELECT AUTO CLEAN SELECT

OPTION ENERGY SAVING SELECT DC12V SOUND ON/OFF SELECT DIGITAL ON/OFF SMPS POWER BLOCK

DC5V DC12V
AC INPUT

AC230V DC25V

13-1

Samsung Electronics

Block Diagram

INDOOR FAN CONTROL

BUZZER CONTROL

SMPS

AC COMMUNICATION SUB-PCB

Samsung Electronics

13-2

13-2 Outdoor Unit


CONTROLLER
IC-MCU
OUTDOOR TEMPERATURE SENSOR DISCHARGE TEMPERATURE SENSOR CONDENSOR TEMPERATURE SENSOR FAN CONTROL (AC, BLDC) EEV CONTROL 4 WAY CONTROL PFC CONTROL COMPRESSOR CONTROL(BLDC) LED CONTROL INDOOR COMMUNICATION EEPROM R/W

OSCILLATION CIRCUIT
AC ZERO CROSSING SIGNAL COMPRESSOR ZERO CROSSING SIGNAL BLDC FAN PULSE SIGNAL IPM FAULT SIGNAL DC VOLTAGE AC CURRENT

FAN

COMPRESSOR

FAN CONTROL SIGNAL EEV CONTROL SIGNAL 4 WAY CONTROL SIGNAL PFC CONTROL SIGNAL COMPRESSOR CONTROL(6P, BLDC) LED CONTROL SIGNAL INDOOR COMMUNICATION SIGNAL

4 WAY VALVE EEV

SMPS

INDOOR UNIT

PFC CIRCUIT

DC5V DC12V DC15V AC300V AC230V DC25V

AC INPUT

13-3

Samsung Electronics

Block Diagram

OUTDOOR FAN

IGBT

B/D

DIODE

DC_LINK CAP

SMPS

IPM

Samsung Electronics

13-4

14. Reference Sheet


14-1 Index for Model Name

Project model code for overseas from 2008(For RAC Export Models)

Model Code

Product Division AS AQ Cooling Only Heat Pump A B D F Inverter V None Inverter Non Inverter G H J L M Capacity 09 12 18 24 30 36 9,000 Btu 12,000 Btu 18,000 Btu 24,000 Btu 30,000 Btu 36,000 Btu N P T V

Product classification Mont Blanc(Premium) BIG Mont Blanc(Deluxe) Forte GP HB WW Premium Forte Deluxe Moderato Neo Forte Presto Tiffany Vivace WW Forte Extreme Tsar MID SER A B C

Version New Developed Model 1st VE Model 2nd VE Model

Buyer Code MIDDLE EAST RUSSIA

W X Z

: Use the " " digit for Grille Color deviation. : Dont use the digit for Basic White model. ex) Silver : S, Black : B, White : W, etc. : Use the " " digit for Electric Source deviation. : Only for "XAP", "XAX", "GEM" Buyer. : Use the " " digit for classification between indoor and outdoor. Indoor "N" & Outdoor "X". : Use the digit for KD models. "CKD" "1" & "SKD" "2".

14-1

Samsung Electronics

14-2 Low Refrigerant Pressure Distribution


Note : Please measure the refrigerant pressure after the air conditioner operates on testing cooling mode during more than 10 minutes. Indoor Temp. Variation : 20C ~ 32C Outdoor Temp. Variation : -5C ~ 45C

Low Refrigerant Pressure Distribution AQV09

AQV12

Samsung Electronics

14-2

14-3 Pressure & Capacity mark


ower/Heat P
W 1 4.1868 1.163 0.29307 745.7 9.8067 1.3558 cal/s 0.23885 1 0.27778 0.06999 178.11 2.3423 0.32383 kcal/h 0.85985 3.6 1 0.252 641.19 8.4322 1.1658 Btu/h 3.4121 14.286 3.9683 1 2,544.4 33.462 4.6262 HP 0.001341 0.0056146 0.0015596 3.9302x10-4 1 0.013151 0.0018182 kg . m/s 0.10197 0.42693 0.11859 0.029885 76.04 1 0.13826 Ib. m/s 0.73756 3.088 0.85778 0.21616 550 7.233 1

14-3

Samsung Electronics

14-4 Q & A for Non-trouble


Classification Class Q A The cooling is weak. When it is hot outside, its cooling capacity decreases due to the increase of the ambient temperature. When the dust filter gets blocked or warm outside air gets in, the cooling capacity will decrease. So, make sure to clean the dust filter frequently, prevent heat loss by closing the doors and insulate the cooling area by using curtains, blinds, shades or window tinting. The cooling is good generally. But, it gets weak when it is considerably hot. It occurs when the outdoor unit is exposed to direct sun light and heat-up air is not ventilated well.So, set up a sunblind over the outdoor unit and keep stuff away from the unit to increase the ventilation. When the cooling capacity decreases during a heat wave, clean the heat exchanger of the outdoor unit or spray some cold water to the heat exchanger to increase the cooling capability. The cooling is weak. Does it need refrigerant charging? It is not correct charging refrigerant regularly. Except that you have moved in several times or the connection pipes are broken, the refrigerant does not run low. So, when refrigerant is additionally charged, it could be costly and cause a product's failure. When the refrigerant leaks, all of it will escape in a short time resulting in cooling failure and no water coming out of the drain hose. So, if water comes out from the drain hose, it indicates the normal operation of the product and it does not need refrigerant charging. It fails to do cooling. When the air conditioner is set to Ventilation or the desired temperature is set higher than the current temperature, it fails to do cooling. In this case, select Cooling or set the desired temperature lower. It floods the floor. Place the drain hose properly. When it is not placed properly, the drain water would flow back flooding the floor. So, straighten out the drain hose for the water to be drained well. Water drips at the drain connection (service valve) of the outdoor unit. When a glass bottle is taken out of the refrigerator, moisture gets condensed on its surface due to the temperature differences. The same principle applies to the air conditioner. When cold refrigerant goes through the copper tube, moisture gets condensed on the surface of the tube and the connection areas. To prevent the water condensation, the pipes are insulated. But, the connection areas of the outdoor unit are not insulated for the purpose of maintenance or repair, and water gets condensed due to the temperature differences and drips down. Generally, it evaporates right away. But, when it drips much during muggy days, put a water pan on the floor. It leaks even though a drain pump is used. It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems. Whenever the air conditioner is turned on, it irritates my eyes and gives me a headache. There are no components in the air conditioner irritating the eyes and sending out chemical smells. But, when the air conditioner is turned on, other smell sources are sucked into the air conditioner and get out of it. So, find and root out the smell sources. Generally, it occurs at a interior renovated place, a pharmacy, a gasoline handling place, a tire shop, a second-hand book shop or an electronic component handling place; when its chemical or musty smells are sucked in and sent out, it can be misled that the air conditioner generates them. So, find and root out the problem or refresh the room frequently. Description

Q A

Cooling Q A

Q A

Q A

Q A

Leakage

Q A

Q A Smells

Samsung Electronics

14-4

Reference Sheet

Classification

Class Q A

Description Whenever the air conditioner is turned on, it stinks. There are no components in the air conditioner sending out chemical smells. But, when the air conditioner is turned on, other smell sources are sucked into the air conditioner and get out of it. So, find and root out the smell sources. Generally, when the drain hose is taken out to the washing room or there are sources of smells such as a diaper bin, a shoe shelf or a socks bin, bad smells generate. Also, it occurs where glass cleaners or air fresheners are used; when they are sucked in interacting with dusts and moistures inside, bad smells generate. These kinds of organic materials noxious to human bodies. So, we recommend against the use of them. Whenever the air conditioner is turned on, it smells sour. When the room is papered recently, its paste smells would be sucked inside. Also, when the air conditioner is installed in the study room of young boys loving sweat-generating activities such as the basketball, excessive sweats evaporate and get sucked into the air conditioner resulting in bad smells. So, find and root out the problem or refresh the room frequently. Whenever the air conditioner is turned on, it smells musty. It is due to the improper keeping of the product after its use. When keeping the product, dry up the inside with the operation of Ventilation to prevent must. When the product is kept without drying up the inside with Ventilation, mold would grow inside resulting in must. So, open the windows and switch on the Ventilation function to get rid of the saturated smell inside. Whenever the air conditioner is turned on, it sends out bad smells such as stale smells. It occurs generally when there are pet animals in the house. Their smells stay at the same place. But, when the air conditioner is turned on, the air gets circulated resulting in the circulation of the smells. So, find and root out the problem or refresh the room frequently. It sends out bad smells. When the air filter is filthy, it could send out bad smells. So, clean the filter and ventilate the room with the windows open while operating the Ventilation function. It won't start. There is a power failure or it is plugged out. Also, check if the power distribution panel is switched off. It goes off during operation. When the hot air does not escape properly, it goes off during operation. It occurs when it does not ventilate properly because the outdoor unit is covered, the back of the outdoor unit is blocked by a cardboard or a plywood panel, and the front of the outdoor unit is blocked by the closed window or other obstacles. Clear the above obstacles from the outdoor unit. It generally works properly. But, when it's considerably hot, it goes off during operation. It occurs when the outdoor unit is exposed to direct sunlight and the hot air does not escape properly. Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. The remote controller won't operate. When the batteries run out or the transmitter or receiver of the remote controller is blocked by obstacles, change the batteries or keep the obstacles away from the controlling area. Also, the remote controller may not work under intensive light from a 3-wave length lamp or a neon sign due to the EMI. In this case, take the remote controller closer to the receiver.

Q A

Smells

Q A

Q A

Q A

Q A Q A

Operation

Q A

Q A

14-5

Samsung Electronics

Reference Sheet

Classification

Class Q A

Description Who installs the air conditioner? (Relocation/Re-installation) When relocating or re-installing the air conditioner, make sure to contact Samsung Electronics Service Center or Authorized Service Agent and have them to do the job. (If not, it could cause personal injury or product damage.) The cost for the relocation/re-installation of the air conditioner is subject to the customer's expense. There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process. Is it possible to install the outdoor unit outside? It is possible to install it at a designated place in the apartment or on the rooftop nearby. But, it's illegal hanging an angle iron case with the outdoor unit in it outside the apartment. Also, it is illegal obstructing passers-by with the outdoor unit installed outside. What can be done to install the outdoor unit facing the road because it is a commercial building? The following is an excerpt from Building Code going into effect from JUNE 1st 2005. "The exhaust pipe of a cooling or ventilation facility installed in a building adjacent to the streets of commercial or residential areas shall be installed higher than 2 m to prevent the exhaust air from blowing directly to passers-by and the current facilities shall be corrected by MAY 31st 2005." So, please install it higher than 2 m or not to blow the hot exhausting air directly to passers-by. What about installing a windscreen during installation not to blow hot air directly to passers-by? When the hot air from the front of the outdoor unit is blocked, the product's performance will be affected and it will fail to operate properly. So, keep it at least 300mm away from its surrounding walls and give it good ventilation.

Q A Installation Q A

Q A

Samsung Electronics

14-6

14-5 Cleaning/Filter Change


14-5-1 Cleaning your Air Conditioner
To get the best possible use out of your air conditioner, you must clean it regularly to remove the dust that accumulates on the air filter.

Before cleaning your air conditioner, ensure that you have switched off the breaker used for the unit.

1. Open the upper front grille by pulling the lower right and left tabs of the grille.

2. 3. 4. 5.

Pull air filters out of each tab of the grille. Remove all dust on the air filters with a vacuum cleaner or brush. When you finished, insert air filters by fixing it to each tab of the grille. To close the front grille, fix it to hooks and push down the lower right and left tabs of the grille.

Front grille Air filter

Body groove Body

6. Clean the front grille with a damp cloth and mild detergent (do NOT use benzene, solvents or other chemicals).

Front grille Hook Body

Note : If you have not used the air conditioner for a long period of time, set the fan going for three to four hours to dry the inside of the air conditioner thoroughly.

14-7

Samsung Electronics

Reference Sheet

14-5-2 Cleaning Deodorizing and Bio filter (Option)


To remove minute dust particles and odors, deodorizing and Bio filter are installed in the air conditioner. You should clean the filters every 3 months.

1. Open the upper front grille by pulling the lower right and left tabs of the grille. 2. Pull out the deodorizing and Bio filter. 3. Wash the filters with clean water, then dry them in the shade. 4. Insert the filters into the original position. Note : You can change the position of filters with each other. 5. Close the front grille.
Bio Filter Deodorizing Filter

Samsung Electronics

14-8

14-6 Installation
14-6-1 Before Installation
Keep the air conditioner outlet and inlet free from its surroundings. In case of installation, keep the symmetry and fix it to prevent vibration. The pipe length shall meet the standard as far as possible.

14-6-2 Installation Procedure


Location
Install the product in an area to guarantee the best cooling effect, convenience of piping and electric work, and inexistence of vibration or wind.

Wall Drilling
Drill the wall downward in a diameter of 60 to 65mm.

Fixing Indoor Unit & Outdoor Unit


Fix the air conditioner indoor unit securely to the wall. Secure the outdoor unit in a suitable position.

Pipe Spooling & Connecting


You shall cut the pipe with a pipe cutter and grind all the burrs of the cut surface. Pipe expansion may continue until the pipe surface becomes uneven or torn apart. Be sure to use a torque wrench to tighten pipes or flare nuts. <Torque & Depth>
Outer Diameter(D) 6.35mm(1/4") 9.52mm(3/8") 12.70mm(1/2") 15.88mm(5/8") 19.05mm(3/4") Torque(kgfcm) 140~170 250~280 380~420 440~480 990~1,210 Depth(A) 1.3mm 1.8mm 2.0mm 2.2mm 2.2mm
D A

Leak Test
Put an inert gas like nitrogen in the outdoor unit pipe and put soap bubbles or other test liquids on the pipe surface for the leak test.

Drain Hose Connecting


Install the drain hose downward to drain water naturally. Be sure to pour water into the hose to check if it drains well.

Electric & Earth Work


Electric and earth work shall meet the "Electric Facility Technology Standard" and the "Internal Wire Regulation" of the Electric Business Laws.

Inspection & Trial Run


Upon completion of the tests, you shall make a trial run while you explain the main functions of the air conditioner to finish the installation.

14-9

Samsung Electronics

14-7 Installation Diagram of Indoor Unit and Outdoor Unit


14-7-1 Air-Purge Procedure
1) Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
Outdoor unit Indoor unit Gas pipe side

B
2) Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

Liquid pipe side

3) Open the valve of the low pressure side of manifold gauge counter-clockwise.

4) Purge the air from the system using vacuum pump for about 30 minutes. Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 30 minutes. This procedure is very important in order to avoid gas leak. Turn off the vacuum pump. Close the valve of the low pressure side of manifold gauge clockwise. Remove the hose of the low pressure side of manifold gauge.
Vacuum Pump

5) Set valve cork of both liquid side and gas side of packed valve to the open position.
Valve stem

6) Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 183kgfcm with a torque wrench.

Stem cap A (gas)

B (liquid)

7) Check for gas leakage. - At this time, especially check for gas leakage from the 3 way valves stem nuts, and from the service port cap.

Samsung Electronics

14-10

Reference Sheet

14-7-2 Pump down Procedure


Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area.

1) Remove the caps from the 3 way valve and the 3-Way valve.

2) Turn the 3-Way valve clockwise to close and connect a pressure gauge (low pressure side) to the service valve, and open the 3 way valve again.

3 way Valve

2 way Valve

3) Set the unit to cool operation mode. (Check if the compressor is operating.)

4) Turn the 3-Way valve clockwise to close.

5) When the pressure gauge indicates "0" turn the 3-Way valve clockwise to close.

6) Stop operation of the air conditioner.

7) Close the cap of each valve.

Relocation of the air conditioner Refer to this procedure when the unit is relocated. Carry out the pump down procedure (refer to the details of 'pump down'). Remove the power cord. Disconnect the assembly cable from the indoor and outdoor units. Remove the flare nut connecting the indoor unit and the pipe. At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. isconnect the pipe connected to the outdoor unit. D At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. Make sure you do not bend the connection pipes in the middle and store together with the cables. Move the indoor and outdoor units to a new location. Remove the mounting plate for the indoor unit and move it to a new location.

14-11

Samsung Electronics