Вы находитесь на странице: 1из 13

ANNEXURE-2

Project Customer Consultant : 1.5MTPY Grinding Unit : M/s.Sonar Bangla Cements, Wets Bengal : Developments Consultants Private Limited.

Bill of Materials
ITEM.NO 1 1 2 3 4 5 6 7 8 9 10 Note: TYPE ACDB (As given in Page 2 & 3) ACDB (As given in Page 3 & 4) Junction Box -Type-1 ( As given in Page 5) Junction Box -Type-2 ( As given in Page 5) Lighting Panel ( As given in Page 5 & 6) 16A, AC, 240V, 1ph, 3Pin Plug & socket (As given in Page 7) 16A, AC, 240V, 1ph, 3Pin Plug & socket (Optional for Item no.5) (As given in Page 7) 100A, AC, 415V, 3ph, 5Pin Plug & socket (As given in Page 8) 100A, AC, 415V, 3ph, 5Pin Plug & socket (Optional for Item no.7 ) (As given in Page 8) Marshalling Box - Type-1 (As given in page 9) Marshalling Box - Type-2 - (Optional for Item.No.9) (As given in page 9) QTY 1 1 5 10 4 2 2 2 2 1 1 UNIT No No Nos Nos Nos Nos Nos Nos Nos No No UNIT PRICE To be furnished by vendor To be furnished by vendor -do-do-do-do-do-do-do-do-doTOTAL To be furnished by vendor To be furnished by vendor -do-do-do-do-do-do-do-do-do-

The above qty is subjected to variation of +/- 20% of the total.

Summary Sheet

Page 1 of 1

Item : AC Power Distribution Board


S.No 1 Description AC Distribution board as given below Qty Unit

Feeder Details S.No. Description Incomer Outgoings Other Features 1 2 Construction Mounting Type of material Thickness of the material Type of Mounting Equipment mounting (Door / Frame) Front / Rear / Side Compartmentalised \ Non-Comp Type of IP Protection against fire Seismic Protection Type of cable entry Cable chamber provision Provision of undrilled gland plate / Drilled gland plate Type of cable lugs Single / Double opening Hinged Door / ??? Type of Gaskets RYB Indications ON / OFF Indications for outgoing feeders. Phase reversal Indication Digital ammeter with selector switch Digital voltmeter with selector switch CT Rating CT Type MFM Meter Type of Auto / Manual changeover Specific Changeover switches Design kA rating (Air) Type of conductor Size of the busbar Insulation of busbar Busbar sizing calculation Busbar Support Type of jointing Neutral busbar size & Material Earth bus size and material Panel outside Painting Panel inside painting Type of painting Type of wire for Power circuit Colour code for the Power circuit Material Type of wire for control circuit Colour code for the Power circuit Material Type of Power termination 2 Way Terminals Bolted busconnection Termination for type of lug??? Space heater with suitable rating with ON/OFF Switch Thermostat for auto control. Type of lamp Door limit switch provided or not (Y/N) SLD General notes incorporating all the features 3ph Power line diagram General arrangement Fixing Plate diagram

Rating (Amps)

Type

Qty

Access

Protection

5 6

Cable Entry Door

Indication

Metering

Changeover Scheme

Busbars

10

Painting

Wiring

11 Termination

12 13

Space Heater Illumination

14

Drawings

Page 1 of 4

Item : AC Power Distribution Board


Protection & Schemes 15 16 Earthing requirements

Page 2 of 4

Unit

Page 3 of 4

Page 4 of 4

Item : AC Power Distribution Board


S.No 1 Description AC Distribution board as given below Qty 1 Unit No.

Feeder Details S.No. Description Incomer Outgoings For Sockets 3Ph, Welding Sockets For Power Transformer 3Ph, Main supply for Trafo 3Ph, Stand by supply for Trafo For HT Board 240V, 1Ph, AC Supply For Circuit Breaker 240V, 1Ph, AC Supply For Isolator 415V, 3ph Supply For Lighting 240V, 1Ph, AC Supply Spare Spare Spare Other Features 1 2 3 4 Construction Monting Access Protection

Rating (Amps) Type 200A TPN-MCCB

Qty 1

Unit No

100 32 32 32 20 20 40 100 20 32

TPN-MCCB TPN-MCB TPN-MCB DP MCB DP MCB TPN-MCB DP MCB TPN-MCCB DP MCB TPN MCB

1 2 2 2 Motor Duty 3 Motor Duty 6 2 1 4 2

Nos Nos Nos Nos Nos Nos Nos No Nos Nos

5 6 7 8

Cable Entry Door Indication Metering Busbars Main Busbar Neutral Busbar Earth busbar Painting Wiring Power Control Earthing Space Heater Illumination

10 11

CRCA sheet, 2mm thickness non-load bearing members 3 mm thickness for load bearing members Free Standing floor mounted with suitable Base frame Non-Compatmentalised. Single Front, All Equipments shall be be having front access. It shall be possible to operate the MCBs without opening the fron door IP 42, Weather, dust and vermin proof All live parts shall be provided with shrouding Entry and exit shall be from Bottom, Cable chamber to be provided for Incoming and outgoing cables Undrilled detachable gland plate with 3mm thickness Considering 20% spare gland space Single Hinged door construction with neoprene gaskets R,Y,B Incdication shall be provided Digital ammeter with selector switch Digital voltmeter with selector switch 200 / 1 A, CL 1.0, 20VA CT shall be provided. Designed for 50kA for 1 sec short circuit Suitable size aluminium busbar, with RYB PVC sleeving. Adequate size with black colour PVC sleeving. 25 x 6 Al, Busbar shall be extended on both sides Busbar sizing calculation to be submitted. Siemens grey, RAL 7032. Copper, PVC - 6Sqmm Copper, PVC - 2.5Sqmm Copper, PVC - 6Sqmm, Green colour Space heater with suitable rating with ON/OFF Switch and thermostat for auto control. CFL Lamp shall be provided with Door limit switch SLD General notes incorporating all the features 3ph Power line diagram General arrangement Protection & Schemes

12 13

14

Drawings

Item : Junction Box


S.No 1 2 Description Type-1 Type-2 No.of Terminals No. of JB 25 40 5 10

Other Features 1 2 3 Construction Monting Protection CRCA sheet, 1.6mm thickness non-load bearing members 3 mm thickness for load bearing members Suitable for monting on lattice type tower. IP 55, Weather, dust and vermin proof Entry and exit shall be from Bottom, Type-1 JBs shall be having provision for glanding 3 Nos. of 7Cx2.5 sqmm Ar, cable, 3Nos of 3Cx2.5Sqmm cable Type-2 JBs shall be having provision for glanding 4 Nos. of 7Cx2.5 sqmm Ar, cable, 4Nos of 3Cx2.5Sqmm cable and 1No. Of 24Cx2.5Sqmm cable 20% Spare gland space shall be considered in all JBs Undrilled detachable gland plate with 3mm thickness Fixed Door Siemens grey, RAL 7032. 2 Nos. Earthing terminals shall be provided. Provision for Termnals group marking to be given General notes incorporating all the features General arrangement Gland space detail

Cable Entry

5 6 7 8 9

Door Painting Earthing Marking Drawings

Page 1 of 1

Item : Lighting Panel


S.No 1 Description Lighting Panel Qty 4 Unit Nos.

Feeder Details for one Lighting Panel S.No. Description Incomer-1 ( For AC Supply) Incomer-2 ( For DC supply) Outgoings For AC Lights For DC lights For Other Utility

Rating (Amps) Type 40 DB MCB 40 DB MCB 20 16 16 DB MCB DB MCB SP MCB

Qty 1 1 2 1 3

Unit No No Nos No Nos

Operating Principle:

AC, HPSV lamps will switch ON and switch OFF automatically with the help of timer. Emergency DC lights will switch ON in the event of failure of AC supply. Hence, suitable circuitry with auto changeover facility shall be provided with DC contactor which will switch ON emergency DC lights in case of AC supply failure during nights only. Necessary interlock with timer shall be provided so that Emergency lights will not switch on in case of AC power failure during day time. Please note that 110V DC will be made available at site for emergency lights and hence AC to DC convertor need not be considered in the scope. The requirement of components /accessories shall not be limited to the list but shall be complete for control of switch yard lighting with auto changeover facility as mentioned above. Lighting control scheme with auto changeover feature shall be submitted with the offer for review.

Other Features 1 2 4 5 6 10 Construction Monting Protection Cable Entry Door Painting CRCA sheet, 2mm thickness non-load bearing members 3 mm thickness for load bearing members Suitable for mounting on lattice type tower IP 55, Weather, dust and vermin proof with canopy All live parts shall be provided with shrouding Entry and exit shall be from Bottom, Undrilled detachable gland plate with 3mm thickness Considering 20% spare gland space Single Hinged door construction with neoprene gaskets Siemens grey, RAL 7032.

Page 1 of 2

Item : Lighting Panel


Wiring Power Control Earth Earthing Copper, PVC - 6Sqmm Copper, PVC - 2.5Sqmm Copper, PVC - 6Sqmm, Green colour 2 Nos. of Earth terminals shall be provided. SLD General notes incorporating all the features 3ph Power line diagram General arrangement Protection & Schemes

11

14

Drawings

Page 2 of 2

Item : Lighting Panel


S.No 1 Description Lighting Panel Qty 1 Unit No

Feeder Details for one Lighting Panel S.No. Description Incomer-1 ( For AC Supply) Incomer-2 ( For DC supply) Outgoings For AC For DC

Rating (Amps) Type 40 DB MCB 40 DB MCB 20 20 DB MCB DB MCB

Qty 1 1 8 3

Unit No No Nos No

Operating Principle:

AC, HPSV lamps will switch ON and switch OFF automatically with the help of timer. Emergency DC lights will switch ON in the event of failure of AC supply. Hence, suitable circuitry with auto changeover facility shall be provided with DC contactor which will switch ON emergency DC lights in case of AC supply failure during nights only. Necessary interlock with timer shall be provided so that Emergency lights will not switch on in case of AC power failure during day time. Please note that 110V DC will be made available at site for emergency lights and hence AC to DC convertor need not be considered in the scope. The requirement of components /accessories shall not be limited to the list but shall be complete for control of switch yard lighting with auto changeover facility as mentioned above. Lighting control scheme with auto changeover feature shall be submitted with the offer for review.

Other Features 1 2 4 5 6 10 11 Construction Monting Protection Cable Entry Door Painting Wiring Power Control Earth Earthing CRCA sheet, 2mm thickness non-load bearing members 3 mm thickness for load bearing members Suitable for mounting on lattice type tower IP 55, Weather, dust and vermin proof with canopy All live parts shall be provided with shrouding Entry and exit shall be from Bottom, Undrilled detachable gland plate with 3mm thickness Considering 20% spare gland space Single Hinged door construction with neoprene gaskets Siemens grey, RAL 7032. Copper, PVC - 6Sqmm Copper, PVC - 2.5Sqmm Copper, PVC - 6Sqmm, Green colour 2 Nos. of Earth terminals shall be provided. SLD General notes incorporating all the features 3ph Power line diagram General arrangement Protection & Schemes

14

Drawings

Item
S.No. 1 2

: 16A, AC, 240V, Single Phase Plug and socket


Description 240V, AC, Single phase plug & socket 240V, AC, Single phase plug & socket (Optional item for above item) Rating (Amps) Type (1 Pole Load break switch / 16 SFU unit) 16 DB MCCB Qty 2 2 Unit Nos Nos

Other Features 1 3 2 6 4 Construction Monting Enclosure Door Protection Cable Entry 7 8 9 Painting Earthing Drawings CRCA sheet, 2mm thickness non-load bearing members 3 mm thickness for load bearing members metal clad gasketted construction, socket will be supplied with heavy duty plug and socket with chain Suitable for mounting on lattice type tower CRCA sheet, 2mm thickness, 3mm for Gland Plate Single Hinged door construction with neoprene gaskets IP 55, Weather, dust and vermin proof with canopy Undrilled detachable, gland plate with 3mm thickness for 2 Nos. of 4CX16Sqmm, Al, Armoured cable+ 20% spare gland space Siemens grey, RAL 7032. 2 Nos. of Earth terminals shall be provided. SLD General notes incorporating all the features General arrangement Wiring diagram

Page 1 of 1

Item : 100A, AC, 415V, 3ph, 5Pin Plug & socket


S.No. Description Rating (Amps) Type 100A, AC, 415V, 3ph, 5Pin (3Pole Load break 1 100 Plug & socket switch/SFU unit) 2 100A, AC, 415V, 3ph, 5Pin Plug & socket (Optional 100 item for above item) TP MCCB Qty 2 Unit Nos

Nos

Other Features 1 3 2 6 4 Construction Monting Enclosure Door Protection CRCA sheet, 2mm thickness non-load bearing members 3 mm thickness for load bearing members metal clad gasketted construction, receptacle will be supplied with heavy duty plug and socket with chain Suitable for mounting on wall/lattice type tower CRCA sheet, 2mm thickness, 3mm for Gland Plate Single Hinged door construction with neoprene gaskets IP 55, Weather, dust and vermin proof with canopy Operating handle of the rotary switch will be fixed in such a manner that it ill not be possible either to insert or withdraw the plug without switching off the supply. Undrilled detachable, gland plate with 3mm thickness for 2 No. of 3.5CX70Sqmm,Al, Armoured cable+ 20% spare gland space Siemens grey, RAL 7032. 2 Nos. of Earth terminals shall be provided. SLD General notes incorporating all the features General arrangement Wiring diagram

Cable Entry 7 8 9 Painting Earthing Drawings

Page 1 of 1

Item
Item.No 1 2

: Marshalling Box
Description No.of Terminals No. of JB 1 1

Type-1 100 Type-2 (Optional for Item No.1) 150

Other Features 1 2 3 Construction Monting Protection CRCA sheet, 1.6mm thickness non-load bearing members 3 mm thickness for load bearing members Suitable for monting on lattice type tower. IP 55, Weather, dust and vermin proof Entry and exit shall be from Bottom Type-1 JBs shall be having provision for glanding 10 Nos. of 7Cx2.5 sqmm Ar, cable, 15Nos of 3Cx2.5Sqmm cable and 10No. Of 24Cx2.5Sqmm cable Type-2 JBs shall be having provision for glanding 10 Nos. of 7Cx2.5 sqmm Ar, cable, 15Nos of 3Cx2.5Sqmm cable and 10No. Of 24Cx2.5Sqmm cable 20% Spare gland space shall be considered in all JBs Undrilled detachable gland plate with 3mm thickness Hinged door with neoprene gasket shall be provided Siemens grey, RAL 7032. Earth bus and 2 Nos. Earthing terminals shall be provided. Provision for Termnals group marking to be given General notes incorporating all the features General arrangement Gland space detail

Cable Entry

5 6 7 8 9

Door Painting Earthing Marking Drawings

Page 1 of 1

Вам также может понравиться