TOTAL NO OF FEEDER 13 13 13 13 13 LOAD(VA) UNIT ITEM 2.5 10 20 10 5 TOTAL LOAD(VA) 80.5 130 260 130 65
S.NO
DESCRIPTION Indicating lamps for HV sw.bd (33kV) Numerical relay Aux.relay Anti pumping relay Timer Annunciation panel loads
QTY
1 2 3 4 5
6 per feeder 1 per feeder 2 per bkr feeder 1 per feeder 1 per feeder 1 no per transformer feeder
10
70
S.NO
DESCRIPTION
QTY
TOTAL NO OF PANEL
TOTAL LOAD(VA)
1 no. per feeder 1 no. per feeder 1 no. per feeder 1 no per incomer 1no per incomer 1no per incomer
13 150 13 40
1950
520
13
40
520
50
100
40
80
40
80
S.NO
TOTAL NO OF FEEDER 13
13
150
1950
1) Total continious load (110 V DC System) on HT Panel of 33 KV = 735.5 VA 2) Total instantaneous (tripping) load (110 V DC System) on HT Panel of 33 KV = ( Tripping coil load + Other than tripping coil load ) = ( 1950 + 1300 ) = 3250 VA 3) Total instantaneous (closing) load (110 V DC System) on HT Panel of 33 KV = 3900 VA
S.NO
DESCRIPTION Indicating lamps for HV sw.bd (33kV) Numerical relay Aux.relay Anti pumping relay Annunciation panel loads
QTY
TOTAL NO OF FEEDER 15 15 15 15
1 2 3 4
4 per feeder 1 per feeder 2 per bkr feeder 1 per feeder 1 no per transformer feeder
10
50
1 no. per feeder 1 no. per feeder 1 no. per feeder 1no per incomer
15 150 15 40
2250
600
15
40
600
40
80
4) Total continious load (110 V DC System) on LT Panel (415 V PCC) = 800 VA 5) Total instantaneous (tripping) load (110 V DC System) on LT Panel (415 V PCC) = ( Tripping coil load + Other than tripping coil load ) = ( 2250 + 1280 ) = 3530 VA 1C) LT PANEL(415 V MCC INCOMER) 110 V DC LOAD (CONTINIOUS) :
DESCRIPTION Indicating lamps for LT (415 V) Numerical relay Aux.relay Anti pumping relay QTY TOTAL NO OF FEEDER 2 2 2 2 LOAD(VA) UNIT ITEM 2.5 10 20 10 TOTAL LOAD(VA) 20 20 40 20
S.NO
1 2 3 4
S.NO
DESCRIPTION
QTY
1 no. per feeder 1 no. per feeder 1 no. per feeder 1no per incomer
2 150 2 40
300
80
40
80
40
80
6) Total continious load (110 V DC System) on LT Panel (415 V MCC) = 100 VA 7) Total instantaneous (tripping) load (110 V DC System) on LT Panel (415 V MCC) = ( Tripping coil load + Other than tripping coil load ) = ( 300 + 240 ) = 540 VA
a) Total continious load = ( 735.5 + 800 + 100 ) = 1635.5 VA b) It is assumed that maximum 13 breaker will trip at a time,so total wattage consumed for this is ( 13 x 150) or 1950 VA. So, total tripping load = ( Wattage consumed by 13 nos of tripping coil + other than tripping coil load liable for instantanious trip) = 1950 + ( 1300 + 1280 +240) = 4770 VA
Total load VA = Continious load + Total tripping load = (1635.5 + 4770) VA = 6405.5 VA Total load current = (6405.5 / 110) = 58.23 Amp Taking 10 % design margin load current = 58.23 + (58.23 x 0.10 ) = 64.05 Amp