ABHIJEET MADC NAGPUR ENERGY

PRIVATE LIMITED
TEST REPORT FOR CURRENT TRANSFORMER
1. Designation:

CURRENT TRANSFORMER

Location:

220/33KV Switchyard Bus Coupler (Bay- 7)

2. Name Plate Details:

Date

Make:

AREVA

Ratio

1600 - 800/1 - 1 - 1 - 1 - 1

Core No.

Rated Primary Current (Amp)


Rated Sec. Current

(Amp)

Accuracy Class

15 - 7.5

10

PS

PS

5P

0.2S

PS

20

<5

I.S.F./A.I.F.
Ohms)

6.4 -3.2

6.4 - 3.2

6.4 - 3.2

6.4 - 3.2

(V)

1200 - 600

1200 - 600

(mA)

20 - 40

20 - 40

KPV
Iexc at Vk/2

4
1600

Output (VA)

Rct at 750 C

22/1/11

Freq: 50Hz

Ith: 40/3 kA/Sec.

HSV/ NSV : 245/220 Kv

BIL: 460/1050 KV

Idyn: 100 kAp

Oil Weight: 300kg

Total Weight: 1400 Kg

Primary/Secondary Current (A)

1600/1

800/1

Primary Connection

P1 - P2

P1 - P2

1S1 - 1S3

1S1 - 1S2

Core 2

2S1 - 2S3

2S1 - 2S2

Core 3

3S1 - 3S3

3S1 - 3S2

Core 4

4S1 - 4S3 S

4S1 - 4S2 S

Core 5

5S1 - 5S3

5S1 - 5S2

Secondary connection

Core 1

SCHEMATIC DIAGRAM AND CONNECTION

P1

P2

C
A

1S1
EARTHING

1S2

1S3 2S1

2S2

2S3 3S1

3S2

3S3 4S1

4S2

4S3

5S1

5S2

5S3

3. INSULATION RESISTANCE VAULE (G)


R

42090701069

42090701068

42090701067

PRIMARY TO EARTH

1.14 (T)

107

335

TIME

30 Sec.

30 Sec.

30 Sec.

SR. NO.

REMARKS: TEST RESULT FOUND SATISFACTORY


Engg.

Date

Mr. Stalin

22/1/11

VENUS
AINL

Sign.

ABHIJEET MADC NAGPUR ENERGY


PRIVATE LIMITED

TEST REPORT FOR CURRENT TRANSFORMER


1. Designation:

CURRENT TRANSFORMER

Location:

220/33KV Switchyard Transformer - 2 (Bay - 4)

2. Name Plate Details:

Date

Make:

AREVA

Ratio

300 200/1 1 1A, 1600 800/ 1, 300 200/1A

Core No.

Rated Primary Current (Amp)


Rated Sec. Current

300 200

(Amp)

06/12/10

1600 800 300 - 200

20 -10

7.5

Accuracy Class

5P

PS

0.2S

PS

PS

I.S.F./A.I.F.

20

<5

Ohms)

2.5 1.7

2.5 1.7

12.6

2.5 1.7

(V)

650 - 400

1200 -600

650 - 400

(mA)

25 - 40

20 40

25 - 40

Output (VA)

Rct at 75 C
KPV
Iexc at Vk/2

Freq: 50Hz

Ith: 40/3 kA/Sec.

HSV/ NSV : 245/220 Kv

BIL: 460/1050 KV

Idyn: 100 kAp

Oil Weight: 300kg

Total Weight: 1400 Kg

Primary/Secondary Current (A)

300/1

200/1

800/1

1600/1

P1 - P2

P1 - P2

P1 - P2

P1 - P2

1S1 - 1S3

1S1 1S2

Core 2

2S1 - 2S3

2S1 - 2S2

Core 3

3S1 - 3S3 S

3S1 - 3S2 S

Core 4

4S1 - 4S2

4S1 - 4S3

Core 5

5S1 - 5S3

5S1 - 5S2

Primary Connection
Secondary connection

Core 1

SCHEMATIC DIAGRAM AND CONNECTION

P1

P2

C
A

1S1

EARTHING

1S2

1S3 2S1

2S2

2S33S1

3S2

3S3 4S1

4S2

4S35S1

5S2

5S3

3. INSULATION RESISTANCE VAULE (G)

SR. NO.
PRIMARY TO EARTH
TIME

42090701061

42090701059

42090701057

568

532

1.02 (T)

60 Sec.

60 Sec.

60 Sec.

Engg.

Date

Sign.

Mr. Stalin

6/12/10

REMARKS: TEST RESULT FOUND SATISFACTORY


VENUS
AINL

ABHIJEET MADC NAGPUR ENERGY


PRIVATE LIMITED

TEST REPORT FOR CURRENT TRANSFORMER


1. Designation:

CURRENT TRANSFORMER

Location:

220/33KV Switchyard IPP Line - 2 (Bay-5)

2. Name Plate Details:

Date

Make:

AREVA

Ratio

1600 - 800/1 - 1 - 1 - 1 - 1

Rated Primary Current (Amp)

1600

Core No.
Rated Sec. Current

15 - 7.5

10

PS

PS

5P

0.2S

PS

20

<5

(Amp)

Output (VA)
Accuracy Class
I.S.F./A.I.F.
Rct at 750 C

Ohms)

6.4 -3.2

6.4 - 3.2

6.4 - 3.2

6.4 - 3.2

(V)

1200 - 600

1200 - 600

(mA)

20 - 40

20 - 40

KPV
Iexc at Vk/2

09/12/10

Freq: 50Hz

Ith: 40/3 kA/Sec.

HSV/ NSV : 245/220 Kv

BIL: 460/1050 KV

Idyn: 100 kAp

Oil Weight: 300kg

Total Weight: 1400 Kg

Primary/Secondary Current (A)

1600/1

800/1

Primary Connection

P1 - P2

P1 - P2

1S1 - 1S3

1S1 - 1S2

Core 2

2S1 - 2S3

2S1 - 2S2

Core 3

3S1 - 3S3

3S1 - 3S2

Core 4

4S1 - 4S3

4S1 - 4S2

Core 5

5S1 - 5S3

5S1 - 5S2

Secondary connection

Core 1

SCHEMATIC DIAGRAM AND CONNECTION

P1

P2

C
A

1S1
EARTHING

1S2

1S3 2S1

2S2

2S33S1

3S2

3S3 4S1

4S2

4S35S1

5S2

5S3

3. INSULATION RESISTANCE VAULE (G)

SR. NO.
PRIMARY TO EARTH
TIME

42100300181

42100300177

42100300176

243

366

323

60 Sec.

60 Sec.

60 Sec.

Engg.

Date

Sign.

Mr. Stalin

09/12/10

REMARKS: TEST RESULT FOUND SATISFACTORY


VENUS
AINL

ABHIJEET MADC NAGPUR ENERGY


PRIVATE LIMITED

TEST REPORT FOR CURRENT TRANSFORMER


1. Designation:

CURRENT TRANSFORMER

Location:

220/33KV Switchyard Transformer - 3 (Bay - 6)

2. Name Plate Details:

Date

Make:

AREVA

Ratio

300 200/1 1 1A, 1600 800/ 1, 300 200/1A

Core No.

Rated Primary Current (Amp)


Rated Sec. Current

300 200

(Amp)

18/01/11

1600 800 300 - 200

20 -10

7.5

Accuracy Class

5P

PS

0.2S

PS

PS

I.S.F./A.I.F.

20

<5

Ohms)

2.5 1.7

2.5 1.7

12.6

2.5 1.7

(V)

650 - 400

1200 -600

650 - 400

(mA)

25 - 40

20 40

25 - 40

Output (VA)

Rct at 75 C
KPV
Iexc at Vk/2

Freq: 50Hz

Ith: 40/3 kA/Sec.

HSV/ NSV : 245/220 Kv

BIL: 460/1050 KV

Idyn: 100 kAp

Oil Weight: 300kg

Total Weight: 1400 Kg

Primary/Secondary Current (A)

300/1

200/1

800/1

1600/1

P1 - P2

P1 - P2

P1 - P2

P1 - P2

1S1 - 1S3

1S1 1S2

Core 2

2S1 - 2S3

2S1 - 2S2

Core 3

3S1 - 3S3 S

3S1 - 3S2 S

Core 4

4S1 - 4S2

4S1 - 4S3

Core 5

5S1 - 5S3

5S1 - 5S2

Primary Connection
Secondary connection

Core 1

SCHEMATIC DIAGRAM AND CONNECTION

P1

P2

C
A

1S1

EARTHING

1S2

1S3 2S1

2S2

2S33S1

3S2

3S3 4S1

4S2

4S35S1

5S2

5S3

3. INSULATION RESISTANCE VAULE (G)

SR. NO.
PRIMARY TO EARTH
TIME

42090701063

42090701062

420907010

319

265

60 Sec.

60 Sec.

60 Sec.

Engg.

Date

Sign.

Mr. Stalin

18/1/11

REMARKS: TEST RESULT FOUND SATISFACTORY


VENUS
AINL

ABHIJEET MADC NAGPUR ENERGY


PRIVATE LIMITED

TEST REPORT FOR CURRENT TRANSFORMER


1. Designation:

CURRENT TRANSFORMER

Location:

220/33KV Switchyard Transformer - 4 (Bay 8)

2. Name Plate Details:

Date

Make:

AREVA

Ratio

300 200/1 1 1A, 1600 800/ 1, 300 200/1A

Core No.

Rated Primary Current (Amp)


Rated Sec. Current

300 200

(Amp)

11/01/11

1600 800 300 - 200

20 -10

7.5

Accuracy Class

5P

PS

0.2S

PS

PS

I.S.F./A.I.F.

20

<5

Ohms)

2.5 1.7

2.5 1.7

12.6

2.5 1.7

(V)

650 - 400

1200 -600

650 - 400

(mA)

25 - 40

20 40

25 - 40

Output (VA)

Rct at 75 C
KPV
Iexc at Vk/2

Freq: 50Hz

Ith: 40/3 kA/Sec.

HSV/ NSV : 245/220 Kv

BIL: 460/1050 KV

Idyn: 100 kAp

Oil Weight: 300kg

Total Weight: 1400 Kg

Primary/Secondary Current (A)

300/1

200/1

800/1

1600/1

P1 - P2

P1 - P2

P1 - P2

P1 - P2

1S1 - 1S3

1S1 1S2

Core 2

2S1 - 2S3

2S1 - 2S2

Core 3

3S1 - 3S3 S

3S1 - 3S2 S

Core 4

4S1 - 4S2

4S1 - 4S3

Core 5

5S1 - 5S3

5S1 - 5S2

Primary Connection
Secondary connection

Core 1

SCHEMATIC DIAGRAM AND CONNECTION

P1

P2

C
A

1S1

EARTHING

1S2

1S3 2S1

2S2

2S33S1

3S2

3S3 4S1

4S2

4S35S1

5S2

5S3

3. INSULATION RESISTANCE VAULE (G)

SR. NO.
PRIMARY TO EARTH
TIME

42100100098

420100100097

420100100096

880

813

329

60 Sec.

60 Sec.

60 Sec.

Engg.

Date

Sign.

Mr. Stalin

11/1/11

REMARKS: TEST RESULT FOUND SATISFACTORY


VENUS
AINL