SITE INSPECTION AND TEST RECORD

Description: Order no.: End Client:

OVER CURRENT RELAY MICOM P139


Customer:

AL- ALBABTAIN BABTAIN Record no. :


Sheet:

SEC-COA
Site:

SEC-COA
Panel / Designation / Location no.:

1 of 4
Project no.:

S/S 8153
PP P

13.8 Kv Switchgear Section-A

11031066/00

1. GENERAL DATA AND INFORMATION: Circuit Reference : ________________ Manufacturer Model No. : : Schneider Electric P139 / 40TE Designation Serial No. Frequency Aux. Voltage : _______________ : _______________ : : 60 HZ (48 - 250) Vac/dc

Draw. & Sh. No. : ________________ CT Ratio :

2. MECHANICAL CHECKS AND VISUAL INSPECTION: ITEM 1 2 3 5 7 8 DESCRIPTION Inspect for physical damage / defects. Verify Connections as per approved drawings. Check tightness of all connections. Check apparatus lists. Test Switch checked for correct function. Check case earthing. CHECKED

3. OPERATING DC SUPPLY CURRENT: DC VOLT.(V) DC CURRENT W/O FAULT(mA) DC CURRENT DURING FAULT(mA) CALCULATED WATT(W)

(Relays de-energized/energized): 40 TE case: approx. 12.6 W / 34.1 W (Relays de-energized/energized): 84 TE case: approx. 14.5 W / 42.3 W Technical Data page: 2-17 4. ELECTRICAL TESTS: (With relay energized condition) Measured auxiliary supply. Clock set at local time. Time maintained when auxiliary supply removed. Relay healthy (green) LED working. Trip (red) LED working. Note for testing: Load rating: continuous 4 Inom For 10 s: 30 Inom For 1 s: 100 Inom Nominal surge current: 250 Inom 5. INPUTS AND OUTPUTS TESTS:
Tested by: Name : ENG/ Witnessed by: Name ENG/ Signature & Date:

HARI KUMAR

Signature & Date:

SITE INSPECTION AND TEST RECORD


Description: Order no.: End Client:

OVER CURRENT RELAY MICOM P139


Customer:

AL- ALBABTAIN BABTAIN Record no. :


Sheet:

SEC-COA
Site:

SEC-COA
Panel / Designation / Location no.:

2 of 4
Project no.:

S/S 8153 Binary inputs: Type X 241 V X Binary Output : Type V X BI U_1. U_24 U_1 . U_4 U_01...U_06 BO K_1..K8 K_01..K_06 Result

13.8 Kv Switchgear Section-A

11031066/00

Result

6. Measurements Accuracy checks: Applied Value 0.1In 0.5In 1 In 1.5In Deviation measurement: 1 % at 20C Technical Data page: 2-14
Elements Phase Over current element & Earth fault Trigger Reset Ratio Time Deviation DMT : 1% + 20 ms to 40 ms

Expected Value ( A ) 120 600 1200 1800

Displayed value ( A )

5%

approx. 0.95

IDMT : 5 % + 10 to 25 ms at I>2Iref

Note: for "extremely inverse" IEC characteristics and for thermal overload characteristics: 7.5 % + 10 to 20 ms Operate time for relay is 40 ms, Technical Data page: 2-112-13 7.1) DT PICK UP AND DROP OFF ( I> & IN> Sensitivity Test ) : Current Setting 0.5 In 1.0 In 1.2 In 7.2) DT TIME CHARACTERISTIC TEST ( I> & IN> ) : Time Setting (s) 3
Tested by: Name : ENG/

R P/U D/O

OVER CURRENT RELAY Y B P/U D/O P/U D/O

Reset Ratio

Current Setting 0.2In 0.4In 0.8In P/U

E/F RELAY D/O Ratio

OVER CURRENT RELAY Y


Witnessed by: Name ENG/ Signature & Date:

E/F RELAY

HARI KUMAR

Signature & Date:

SITE INSPECTION AND TEST RECORD


Description: Order no.: End Client:

OVER CURRENT RELAY MICOM P139


Customer:

AL- ALBABTAIN BABTAIN Record no. :


Sheet:

SEC-COA
Site:

SEC-COA
Panel / Designation / Location no.:

3 of 4
Project no.:

S/S 8153

13.8 Kv Switchgear Section-A

11031066/00

20 40 7.3) DT PICK UP AND DROP OFF ( I>> & IN>> Sensitivity Test ) : Current Setting 0.8 In 1.5 In 2.0 In 7.4) DT TIME CHARACTERISTIC TEST ( I>> & IN>> ) : Time Setting (s) 0 50 7.5) DT PICK UP AND DROP OFF (I>>> & IN>>> Sensitivity Test ) : Current Setting 1.0 In 2.0 In 3.0 In 7.6) DT TIME CHARACTERISTIC TEST (I>>> & IN>>> ) : P/U R D/O OVER CURRENT RELAY Y B P/U D/O P/U D/O Reset Ratio Current Setting 1.0In 1.3In 2.0In P/U E/F RELAY D/O Ratio R OVER CURRENT RELAY Y B E/F RELAY P/U R D/O OVER CURRENT RELAY Y B P/U D/O P/U D/O Reset Ratio Current Setting 0.5In 0.8In 1.0In P/U E/F RELAY D/O Ratio

Time Setting (s) 0 50

OVER CURRENT RELAY Y

E/F RELAY

7.7) IDMT CHARACTERISTICS TEST ( I> & IN> ) : Time multiplier = 1 Function
Tested by: Name : ENG/

Operating Time (s)


Witnessed by: Name ENG/ Signature & Date:

HARI KUMAR

Signature & Date:

SITE INSPECTION AND TEST RECORD


Description: Order no.: End Client:

OVER CURRENT RELAY MICOM P139


Customer:

AL- ALBABTAIN BABTAIN Record no. :


Sheet:

SEC-COA
Site:

SEC-COA
Panel / Designation / Location no.:

4 of 4
Project no.:

S/S 8153 Current IEC SI Curve IEC VI Curve IEC EI Curve IEC LTI Curve 0.2In Setting 0.2In 0.2In 0.2In 0.2In 0.2In 0.2In 0.2In Injected 2*Is Current 10*Is 2*Is 10*Is 2*Is 10*Is 2*Is 10*Is Calculated 10.02 Value (s) 2.970 13.5 1.5 26.67 0.808 120 13.33

13.8 Kv Switchgear Section-A R Y B

11031066/00

7.8) TIME MULTIPLIER TESTS ( IN> ) : IN> = 0.2In I inject = 2 Is Time multiplier 0.2 0.5 7.9) Breaker Failure Protection (50BF) Phase R Y B R Y B Communication with PC Check : _______________ Event Record Check : _______________ Disturbance Record Check : ________________ 80% In 500 ms 1.0 sec 20% In 150 ms 300 ms Current ( A ) Set Pickup Drop-off Set Stage 1 Optd Set Stage 2 Optd Remark Curve: SI N Calculated Value 2.01 5.03

Tested by: Name : ENG/

HARI KUMAR

Witnessed by: Name ENG/ Signature & Date:

Signature & Date: