1 2 3 4 5
Antecedentes....................................................................................................... 1 Situacin, emplazamiento y propiedad......................................................... 1 Reglamentacin especfica............................................................................... 2 Descripcin general de la instalacin ............................................................ 3 Obra civil............................................................................................................. 4
5.1 Adaptacin del terreno .................................................................................................. 4 5.2 Lnea lmite de edificacin............................................................................................. 5 5.3 Red de abastecimiento de agua .................................................................................... 5 5.4 Red de saneamiento ....................................................................................................... 7 5.5 Edificio ........................................................................................................................... 11 5.6 Marquesina .................................................................................................................... 15 5.7 Monoposte ..................................................................................................................... 15 5.8 Aparcamientos .............................................................................................................. 16 5.9 rea de abastecimiento y descarga ............................................................................ 17 5.10 Cerramiento exterior y acceso................................................................................... 17 5.11 Firmes y pavimentos .................................................................................................. 18 5.12 Sealizacin................................................................................................................. 18
Instalacin Mecnica....................................................................................... 19
6.1 Tanques enterrados para almacenamiento ............................................................... 19 6.2 Red de tuberas ............................................................................................................. 38 6.3 Suministro de combustible.......................................................................................... 44
Instalacin elctrica......................................................................................... 47
7.1 Potencia instalada ......................................................................................................... 47 7.2 Clasificacin de zonas .................................................................................................. 48 7.3 Conductores .................................................................................................................. 52 7.4 Canalizaciones .............................................................................................................. 53 7.5 Conexin a red general ................................................................................................ 53 7.6 Lneas de distribucin.................................................................................................. 56 7.7 Cuadros de distribucin .............................................................................................. 57 7.8 Red de fuerza ................................................................................................................ 57 7.9 Red de alumbrado ........................................................................................................ 58 7.10 Red de tierra ................................................................................................................ 61
ndice 7.11 Sistema de proteccin para descarga de camiones cisterna.................................. 68 7.12 Proteccin contra sobretensiones atmosfricas ...................................................... 68 7.13 Sistema de alimentacin ininterrumpida ................................................................ 69
Captulo 2
1 2 3
Clculos..........................................................................................1
Resultados ........................................................................................................... 6
4.1 Marquesina ...................................................................................................................... 6 4.2 Monoposte ..................................................................................................................... 18
Captulo 3
1
Estudio econmico........................................................................1
Captulo 4
1 2 3 4 5
Procesos productivos en la instalacin .......................................................... 1 Materias primas utilizadas............................................................................... 1 Energa consumida ............................................................................................ 1 Caudales de abastecimiento de agua ............................................................. 1 Productos y subproductos obtenidos............................................................. 1
ndice
6 7
Composicin de las emisiones gaseosas ....................................................... 2 Composicin de vertidos y residuos, productos, cantidades y destino de
los mismos ................................................................................................................... 2 8 9 Niveles sonoros y vibraciones emitidas ........................................................ 2 Tcnicas propuestas de prevencin, reduccin y sistemas de control de
Captulo 5
1 2
4 5
ndice
Condiciones legales........................................................................................... 4
2.1 Condiciones generales ................................................................................................... 4 2.2 Condiciones facultativas legales................................................................................... 4 2.3 Seguridad en el trabajo .................................................................................................. 6 2.4 Seguridad Pblica........................................................................................................... 7 2.5 Inspeccin y vigilancia de las obras ............................................................................. 8 2.6 Disposiciones legales.................................................................................................... 10 2.7 Responsabilidad del contratista.................................................................................. 10
ndice 3.17 Condiciones generales de ejecucin de los trabajos............................................... 17 3.18 Obras ocultas............................................................................................................... 18 3.19 Trabajos defectuosos .................................................................................................. 18 3.20 Vicios ocultos .............................................................................................................. 19 3.21 De los materiales y aparatos y su procedencia ....................................................... 19 3.22 Empleo de los materiales y aparatos........................................................................ 20 3.23 Materiales no utilizables ............................................................................................ 20 3.24 Materiales y aparatos defectuosos............................................................................ 20 3.25 Medios auxiliares........................................................................................................ 21 3.26 Recepciones provisionales......................................................................................... 21 3.27 Conservacin de las obras recibidas provisionalmente ........................................ 22 3.28 Programa de trabajos ................................................................................................. 23 3.29 Mejoras y variaciones del proyecto.......................................................................... 23 3.30 Recepcin del material............................................................................................... 23 3.31 Organizacin ............................................................................................................... 24 3.32 Ejecucin de las obra .................................................................................................. 24 3.33 Mtodos constructivos ............................................................................................... 25 3.34 Equipos de obra .......................................................................................................... 26 3.35 Responsabilidad del Contratista............................................................................... 26 3.36 Realizacin de los trabajos......................................................................................... 27 3.37 Obras definidas completamente en este Pliego ...................................................... 27
Captulo 2
ndice
1 2
Instalacin elctrica........................................................................................... 8
4.1 Acometida y centro de transformacin ....................................................................... 8 4.2 Cuadros elctricos .......................................................................................................... 8 4.3 Conductores .................................................................................................................... 9 4.4 Diferenciales e interruptores magnetotrmicos ....................................................... 10 4.5 Interruptores, conmutadores y enchufes................................................................... 10 4.6 Tomas de tierra ............................................................................................................. 11
Materiales.......................................................................................................... 12
5.1 Agua ............................................................................................................................... 12 5.2 Cemento ......................................................................................................................... 12 5.3 ridos............................................................................................................................. 12 5.4 Morteros......................................................................................................................... 13 5.5 Hormigones................................................................................................................... 13 5.6 Yeso ................................................................................................................................ 14 5.7 Obras de fbrica ............................................................................................................ 14 5.8 Aceros............................................................................................................................. 15
Normativa.......................................................................................................... 15
Parte IV
1
Presupuesto .......................................................................................1
ndice
Marquesina ......................................................................................................... 8
3.1 Cimentacin .................................................................................................................... 8 3.2 Estructura ........................................................................................................................ 8 3.3 Revestimiento y pintura ................................................................................................ 8
Sealizacin........................................................................................................ 9
4.1 Cimentacin .................................................................................................................... 9 4.2 Estructura ........................................................................................................................ 9
5 6
7 8
Parte I MEMORIA
Memoria-Descripcin
Captulo 1 DESCRIPCIN
1 Antecedentes
Se ha recibido el encargo por parte de la empresa FeBB, S.A. de proyectar un gasocentro en la provincia de Valladolid. La eleccin del lugar se ha debido a que la densidad de pueblos en la zona, la cercana de ciudades grandes y la ausencia de instalaciones de este tipo pueden ser un factor determinante en la rentabilidad de la instalacin.
Memoria-Descripcin
3 Reglamentacin especfica
En la realizacin del presente proyecto se siguen las normas vigentes aplicables a este tipo de instalaciones. Se ha tenido en cuenta la Instruccin Tcnica Complementaria (ITC) MI-IP02 Parques de almacenamiento de lquidos petrolferos modificada
Memoria-Descripcin
por Real Decreto 1562/1998, de 17 de Julio (BOE del 8 de Agosto de 1998), adems de las diferentes normativas recogidas en el ANEXO N 1.
Memoria-Descripcin
Todos los elementos del gasocentro se ajustan a la normativa vigente y quedan perfectamente descritos en sus documentos
correspondientes.
5 Obra civil
5.1 Adaptacin del terreno 5.1.1 Estudio del terreno Se estudiar la capacidad portante del terreno, la presencia de manto fretico, la agresividad y la acidez del terreno.
5.1.2 Movimiento de tierras 5.1.2.1 Preparacin del terreno La explanacin se realiza en funcin de los accesos y la rasante de la va. Se debe desbrozar el terreno y retirar la tierra frtil antes de escarificar y compactar la superficie. A continuacin se procede a la explanacin de la superficie de la parcela hasta conseguir una cota tal que, tras compactar el terreno, se pueda asfaltar quedando a nivel rasante con la va. Se llevar a cabo de forma que el firme de la instalacin presente una pendiente de entre el uno y el dos por ciento para asegurar la escorrenta de agua.
5.1.2.2 Preparacin de accesos Se construir un acceso que sirva de entrada y salida. Se construirn tambin isletas y elementos separadores de circulacin con su
Memoria-Descripcin
correspondiente sealizacin vertical y de suelo que facilite el trnsito por el interior del gasocentro.
5.2 Lnea lmite de edificacin Este lmite se define en el artculo 25 de la Ley de Carreteras como la distancia permitida entre la arista del muro o la valla de la instalacin (o en su defecto del lmite edificable de la parcela) y la arista ms prxima de la carretera. Todos los elementos del gasocentro quedarn detrs de esta lnea excepto los destinados a facilitar la entrada o salida de vehculos, por ejemplo isletas o viales. Los seis primeros metros desde la arista de la calzada slo se podrn destinar a zonas verdes.
5.3 Red de abastecimiento de agua Para el suministro de agua ser de necesario establecer una conexin con la red municipal, de acuerdo con el reglamento establecido por el Ayto. de Valladolid y Aguas de Valladolid S.A. Dicha conexin se situar donde autorice el organismo competente mediante una arqueta de registro. Entre la red municipal y la arqueta de distribucin interna de la instalacin debern aparecer como mnimo los siguientes dispositivos: Llave o vlvula de toma que permite interrumpir el suministro de agua. Dicha toma es responsabilidad y propiedad de la empresa suministradora y deber situarse junto a la toma de la tubera principal o donde la vlvula de registro de la compaa, lo ms cercano posible al lmite de la propiedad.
Memoria-Descripcin
Llave de paso, nada ms entrar en la propiedad con una vlvula de retencin para evitar que el agua pueda retornar a la red. Un contador entre la llave de paso y la de retencin. Un dispositivo que permita la conexin de aparatos de medida sin desmontajes. Desde la llave de paso hasta la de abonado, todos los elementos estarn contenidos en una cmara donde debern ser visibles. Esta cmara dispondr de desage de dimensin suficiente para evacuar el lquido que pudiera quedar retenido. Junto a la acometida se instalarn los elementos necesarios para poder medir caudal y presin. Todo lo anterior estar comprendido en el contador central. La tubera principal desembocar en una arqueta desde la que saldrn tuberas de distribucin hasta los distintos puntos de consumo del gasocentro, desde los que se podr regular el caudal de salida con vlvulas de corte independientes, a saber: Edificio. Sistema de extincin de incendios.
El tramo comprendido entre la red principal y la acometida de la base de suministro ser de ejecucin y maniobra exclusiva de la compaa suministradora. Se emplear tubera de PVC de 150 mm. de dimetro. En el exterior de los elementos construidos irn enterradas a una profundidad de 60 cm. respecto al nivel inferior del pavimento. En el interior de los edificios se empotrarn en las paredes por encima de los aparatos a los que suministra agua. Los sanitarios dispondrn de su propia llave de paso.
Memoria-Descripcin
5.4 Red de saneamiento Esta red tendr como propsito tanto el abastecimiento de agua como la evacuacin de aguas fecales, pluviales e hidrocarburadas. Normas referentes a fontanera: Normas bsicas para las instalaciones en interiores de suministros de agua (9 de diciembre de 1975). Reglamento e instrucciones tcnicas de la instalaciones de agua corriente sanitaria. Normas particulares de la empresa suministradora.
5.4.1 Red de aguas fecales Recoger las aguas fecales del edificio principal para conectarlas a la red de saneamiento municipal a travs de un decantador de productos slidos. Las tuberas de recogida de aguas fecales sern de PVC de 200 mm. de dimetro e irn enterradas asegurando una pendiente mnima del dos por ciento y una profundidad mnima de 60 cm. Medidos desde la generatriz superior de las tuberas. Los sistemas que conecten con esta red lo harn a travs de sifones que eviten la salida de gases.
5.4.2 Red de aguas pluviales Recoger el agua proveniente de la lluvia por escorrenta en la marquesina y el edificio, para lo cul stos se disearan de forma que se asegure una pendiente suficiente y tal que el agua recogida se distribuya hacia los puntos correspondientes de recogida donde se dispondr una cazoleta sifnica de PVC como cierre inodoro.
Memoria-Descripcin
Los canalones debern tener un inclinacin mnima del tres por ciento. Las bajantes acabarn en unas arquetas mediante las cuales se unirn a la red de tuberas que lleva las aguas pluviales.
5.4.3 Red de aguas hidrocarburadas Las aguas que pudieran estar contaminadas por vertidos de hidrocarburos sern arrastradas en los sumideros, a los que llegarn mediante escorrenta desde el pavimento (la zona crtica en cuanto a hidrocarburos ser la de carga y descarga de camiones cisterna). La pendiente del pavimento en esta zona ser tal que permita que cualquier derrame fluya rpidamente hacia un sumidero situado fuera de la proyeccin vertical del vehculo evitando que alcance la red de alcantarillado. Esta pendiente estar distribuida por todo el pavimento del gasocentro y deber tener una pendiente de entre el dos y el tres por ciento hacia los sumideros. Los sumideros sern del tipo sifnico para evitar salidas de gases y olores. Las tuberas sern estancas de 160 mm. de dimetro en el inicio del ramal y 200 mm. segn vaya avanzando la red. Adems debern ir enterradas a una profundidad de 60 cm. medidos desde la generatriz superior de la tubera. Dichas tuberas se dirigirn a una arqueta donde se unirn todas las conducciones de aguas hidrocarburadas para su tratamiento en el sistema separador antes de su vertido a la red de alcantarillado municipal. Toda la red ir provista de las arquetas correspondientes no
pudiendo haber ms de 40 m. entre ellas. Tampoco se permiten quiebros sin arqueta. En la entrada y la salida del gasocentro habr canaletas de hormign con rejilla de hierro fundido para evitar la entrada o salida de aguas de escorrenta.
Memoria-Descripcin
5.4.4 Sistema de depuracin de aguas Las aguas hidrocarburadas deben ser depuradas antes de incorporarse a la red de alcantarillado municipal. Para ello se utilizar una arqueta arenera que har la funcin de primer filtro. A continuacin se colocar un separador de hidrocarburos contenidos en el agua que dejar el agua en las condiciones permitidas para su vertido en el alcantarillado municipal.
5.4.4.1 Separador de hidrocarburos Un separador de hidrocarburos tiene como misin la separacin de restos de aceites y grasas minerales, combustibles y otras fases flotantes presentes en las aguas del vertido. El motivo es preservar el medio ambiente de la agresin que provocara el vertido directo y evitar las complicaciones que surgiran en las depuradoras municipales. Este vertido se caracteriza por la presencia de aceites vegetales y minerales en concentraciones que van desde 100 ppm hasta 500ppm. El lmite de vertido fijado por la norma es 50 ppm. Debido a que se emplear la misma red para la recogida de aguas pluviales e hidrocarburadas, se tendr en cuenta la pluviometra de Valladolid al seleccionar el separador de hidrocarburos para asegurar que no se pueda producir un desbordamiento del sistema. Adems se dotar al sistema de una vlvula de by-pass para evitar, en caso de lluvias torrenciales, que el agua limpia pase innecesariamente por el separador. Valladolid (Ao 2007): 435 mm. de precipitaciones rea del gasocentro: 6.000 m2 Precipitacin mxima en 24h: 90,8 mm. Volumen mximo diario a tratar:
6.000 90,8 = 544,800 m
3
da
= 22.700 litros
h .
Memoria-Descripcin
10
Por lo tanto se instalar un separador de hidrocarburos de 25.000 l. El funcionamiento del separador de hidrocarburos se basa en la separacin por gravedad de fluidos no solubles en agua. Las aguas cargadas de hidrocarburos penetran en el tanque a travs de un difusor que les obliga a posarse en el fondo evitando las turbulencias de la superficie. En la parte central del depsito los hidrocarburos de densidad inferior a la del agua suben a la superficie, donde se retienen para su extraccin. El agua separada de los hidrocarburos pasa por debajo de la masa flotante saliendo al alcantarillado a travs de una vlvula de seguridad cuando el volumen de hidrocarburos es superior al del agua. Rendimiento en hidrocarburos 99,982%. Clase 1.
Refuerzos horizontales y verticales debidamente situados que le dotan de una mayor resistencia a la presin de las tierras.
Tubos de entrada y salida segn capacidad. Tapa de 400 mm de dimetro. Vlvula obturadora de seguridad situada a la salida de lquidos.
5.4.4.2 Sistema de evacuacin de aguas Para un adecuado drenaje del pavimento del gasocentro se emplear un sistema de arquetas de sumidero con rejillas de fcil instalacin sobre el canal. El canal lleva nervios de anclaje que permiten mantener el sistema en la posicin de diseo. Dichas rejillas estarn hechas de fundicin con acabado protector para instalaciones de suministro de combustible. En la entrada y la salida
Memoria-Descripcin
11
del recinto del gasocentro se instalarn unos sumideros para evitar la entrada y salida de aguas. El terreno ser pavimentado con especial atencin para conseguir los desniveles necesarios para poder evacuar las aguas hacia los sumideros sin que queden puntos muertos o de agua estancada. Previo al vertido de agua a la red de alcantarillado municipal se deber filtrar el agua por el separador de grasas e hidrocarburos. La acometida a la red de alcantarillado se har segn la norma NTSE-ISA Alcantarillado y atenindose a lo establecido en las Ordenanzas y Reglamentos Municipales de Valladolid. Dicha arqueta ser accesible desde el exterior del complejo y ser utilizada para la toma de muestras y medidas por parte del organismo estatal competente. Dicho organismo poseer una llave de clausura de la arqueta, que ser nica.
5.5 Edificio La estructura del edificio se construir segn la norma NBE-EA/95 y se encargar atendiendo a la norma NBE-AE/88. Ser de acero A42 y estar soportada por zapatas de hormign armado. Las uniones sern soldadas segn las normas vigentes y sern realizadas por soldadores cualificados. El edificio tendr una superficie total de 96 m2.
5.5.1 Cimentacin Ser de hormign armado con resistencia caracterstica de 200 kg/cm2 para el hormign y 4.200 kg/cm2 de tensin de rotura para el acero. Los materiales a emplear para los hormigones y el acero se ajustarn a las condiciones especificadas en la EH-91, debindose proceder a los controles indicados en esa norma durante la ejecucin de la obra.
Memoria-Descripcin
12
5.5.2 Cerramiento y cubierta El cerramiento se construir en fbrica de ladrillo perforado de 7 cm., de 0,5 pies de espesor enfoscado interiormente con mortero de cemento y un zcalo de hormign tambin enfoscado de 0,5 m. provisto de cmara de aire de 5 cm. y tabique de ladrillo hueco sencillos, recibido con mortero de cemento y arena de ro 1/6. La carpintera exterior ser de aluminio lacado con doble acristalamiento tipo Isolar Glas. La cubierta se realizar a base de doble tablero cermico, sobre tabiquillos con aislamiento interior de manta de fibra de vidrio, impermeabilizada con membrana de betn modificado de 4 mm. de espesor protegida con capa de mortero y capa de gravilla de 3 cm. de espesor. Dicha cubierta contar con la pendiente necesaria para facilitar el trnsito de las aguas pluviales hacia las arquetas de recogida.
5.5.3 Elementos interiores La tabiquera interior ser de ladrillo hueco sencillo, recibido con mortero de cemento y arena de ro 1/6, enfoscado y maestreado. El suelo ser de plaqueta de buena calidad, las puertas interiores sern de madera de pino y los aseos estarn alicatados hasta el techo.
5.5.4 Calefaccin y aire acondicionado Debido a las pequeas dimensiones del edificio ser suficiente con situar en al oficina de control un equipo de aire acondicionado con bomba de calor 2x1 con 2150+3010 frig/h.
Memoria-Descripcin
13
5.5.5 Distribucin 5.5.5.1 Oficina de control Dependencia destinada a la gestin y control del gasocentro. Desde los ventanales se podr observar cmodamente tanto el acceso al gasocentro como la zona de abastecimiento. Su superficie ser 26,75 m2. El control del gasocentro se realizar desde la oficina mediante computadora. Se registrarn los siguientes datos.
Control de nivel de tanques por sondeo. Control de precios de combustible, descuentos, precios especiales.
Emisin de facturas. Alarma de fugas. Almacenamiento de ltimos movimientos (pagos y cobros). Contabilidad. Control de inventario.
5.5.5.2 Sala de equipos El acceso ser a travs de la oficina de control, de forma que se tenga controlado en todo momento quin accede al mismo. Su superficie ser de 12,05 m2. Contendr el material de oficina, el SAI y todos los dems equipos elctricos.
5.5.5.3 Almacn El acceso ser travs de la oficina de forma que se controle en todo momento quin accede al mismo. Dispondr de una puerta al exterior de doble hoja para facilitar la entrada y salida de material.
Memoria-Descripcin
14
La superficie del almacn ser de 22,24 m2. Contendr el material de oficina, herramientas y material necesario para el correcto funcionamiento del gasocentro.
5.5.5.4 Vestuarios La instalacin dispondr de un vestuario para seoras y otro para caballeros, ambos de 3,9 m2 de superficie. Ambos vestuarios dispondrn de:
Banco de madera Percha sobre pared Lavabo de porcelana vitrificada, de 56 x 46 cm. sobre un pedestal y anclado a la pared con grifo monomando cromado con rompechorros.
Espejo de 300 x 500 cm. Dosificador de jabn lquido en el bao fijado a la pared mediante anclajes.
5.5.5.5 Aseos La instalacin dispondr de un aseo para seoras y otro para caballeros, ambos de 1,95 m2 de superficie y estarn alicatados hasta el techo con azulejos blancos. Se instalarn en los dos aseos inodoros de
Memoria-Descripcin
15
tanque bajo de porcelana vitrificada, con asiento y tapa de resina termoendurecida y portarrollos anclado a la pared.
5.6 Marquesina 5.6.1 Descripcin Se trata de una nave a dos aguas con prticos de tres vanos cuya descripcin tcnica se encuentra en los planos correspondientes.
5.6.2 Cimentacin Ser de hormign armado con resistencia caracterstica 200 kg/cm2 para el hormign y 4.200 kg/cm2 de tensin de rotura para el acero. Los materiales a emplear para los hormigones y el acero se ajustarn a las condiciones especificados en la EH-91, debindose proceder a los controles indicados en esa norma durante la ejecucin de la obra.
5.6.3 Estructura La estructura de la marquesina se construir segn la norma NBEEA/95 y se cargar atendiendo a la norma NBE-AE/88. Ser de acero A42 y estar soportada por zapatas de hormign armado. Las uniones sern soldadas segn las normas vigentes y sern realizadas por soldadores cualificados.
5.7 Monoposte 5.7.1 Descripcin La base ser un perfil hueco circular de acero sobre el que se dispondr una estructura plana orientada hacia la direccin de acceso al
Memoria-Descripcin
16
polgono. El dimensionado del monoposte se ha calculado en funcin de la visibilidad que proporciona la zona. En este caso tendr una altura de 20 m. La estructura sobre la que se colocar la publicidad tendr 2 m. de alto y una anchura de 8 m.
5.7.2 Cimentacin Ser de hormign armado con resistencia caracterstica 200 kg/cm2 para el hormign y 4.200 kg/cm2 de tensin de rotura para el acero. Los materiales a emplear para los hormigones y el acero se ajustarn a las condiciones especificados en la EH-91, debindose proceder a los controles indicados en esa norma durante la ejecucin de la obra.
5.7.3 Estructura La estructura del monoposte se construir segn la norma NBEEA/95 y se cargar atendiendo a la norma NBE-AE/88. Ser de acero A42 y estar soportada por zapatas de hormign armado.
5.8 Aparcamientos 5.8.1 Turismos Los aparcamientos para turismos estarn fuera del recinto del gasocentro, de esta forma se evita, o al menos se dificultan posibles robos dentro del recinto.
5.8.2 Camiones cisterna La instalacin contar con cuatro plazas de aparcamiento para camiones cisterna de 14 x 4 m2 cada una.
Memoria-Descripcin
17
La zona de aparcamiento dispondr de suficiente espacio para facilitar las maniobras a los conductores y estar situada cerca del edificio para mayor comodidad de los conductores que hagan uso de las instalaciones del centro.
5.9 rea de abastecimiento y descarga Dicha rea estar situada de forma que los camiones que se dirijan a ella puedan entrar y salir sin problemas. Esta zona se ha diseado con el propsito de que los camiones cisterna, en posicin de suministro o descarga, se encuentren siempre de cara a la salida del recinto facilitando la evacuacin de los mismos en caso de producirse cualquier problema en el gasocentro. El pavimento ser impermeable para evitar filtraciones al suelo y ser fcil de limpiar y conservar.
5.10 Cerramiento exterior y acceso El recinto estar rodeado por un muro de 11 hiladas de bloque de hormign blanco consiguiendo 2,20 m de altura. Sobre el muro se colocar una malla de hierro galvanizado de 2m de altura sobre la que se colocarn 30 cm de alambre de espino. La altura total del vallado ser, por tanto, 4,5 m. El acceso de vehculos a la instalacin se llevar a cabo mediante una puerta corredera. El recinto permanecer cerrado siempre y la apertura de la puerta corredera se realizar mediante llave electrnica o llamando al timbre para que abran desde la oficina de control. El acceso peatonal se realizar por una puerta situada prxima al acceso de vehculos.
Memoria-Descripcin
18
5.11 Firmes y pavimentos El firme y el pavimento debern repartir uniformemente las cargas sobre el terreno, siendo a su vez resistentes e impermeables a los hidrocarburos. Adems deber tener gastos de conservacin y limpieza mnimos. El firme estar formado por dos capas de zahorra artificial de 15 cm y una capa de asfalto impermeable y resistente a los hidrocarburos. Las isletas y aceras tendrn en su contorno un bordillo de hormign prefabricado asentado sobre una solera de hormign de 125 kg/cm2 que sobresaldr 15 cm sobre el pavimento. Las aceras que rodean la caseta y la isleta estarn enlosadas con baldosas hidrulicas de cuatro pastillas y se colocarn sobre una solera de hormign.
5.12 Sealizacin La circulacin dentro de la instalacin estar regida por la sealizacin. sta ser sencilla, difana y evitar la necesidad de realizar maniobras. Las seales se colocarn conforme a la Norma 8.1.-IC Seales Verticales y al Catlogo de Seales de Circulacin de la Direccin General de Carreteras, realizndose segn el artculo 700 del PG-3-75. Las lneas y seales sobre el pavimento se pintarn conforme a la Orden Circular n 292/86 T Marcas Viales, que dirigir la circulacin y el estacionamiento de vehculos.
Memoria-Descripcin
19
6 Instalacin Mecnica
6.1 Tanques enterrados para almacenamiento 6.1.1 Definicin Los tanques se disearn y construirn conforme a las
correspondientes normas: UNE EN 976-1, UNE EN 53.432, UNE EN 53.496, UNE EN 62.350, UNE EN 62.352. En ausencia de normas para el clculo se justificar como mnimo lo siguiente:
Resistencia del material utilizado. Para el clculo se usar un valor menor o igual al 40% de resistencia a la rotura y al 80% del lmite.
Resistencia mecnica del tanque lleno de agua. Presin y depresin en carga y descarga. Medidas suplementarias por condiciones de corrosin interior o exterior.
El gasocentro dispondr de tanques para almacenar hidrocarburos lquidos (gasleos B y C) a temperatura y presin atmosfricas. Sern depsitos enterrados, cilndricos con generatriz horizontal y cerrados por dos fondos abombados. Los tanques sern de doble pared de acero para poder instalar el detector de fugas y evitar otros sistemas de control de prdidas. Los tanques tendrn tambin una capa de polister reforzado con fibra de vidrio (prfv) con arquetas prefabricadas de prfv que garantizan la estanqueidad de las zonas consideradas como zonas de riesgo de contaminacin de productos petrolferos. La pared interna estar construida en chapa de acero al carbono. La eleccin es obvia ya que este tipo de acero es el ms resistente ante la
Memoria-Descripcin
20
accin de los hidrocarburos y sus aditivos. La pared exterior debe soportar la accin de la corrosin del medio externo, para lo que se utilizar plstico reforzado con fibra de vidrio, debido a la estabilidad qumica del material y su elevada capacidad para resistir el ataque de agentes corrosivos. Todos los tanques enterrados para almacenamiento de
combustibles cumplirn el criterio de doble contencin, utilizando paredes doble con espacio anular para detectar y contener posibles fugas del producto almacenado en el tanque primario. En dicho espacio anular se encontrar el dispositivo de deteccin de fugas que ser detallado ms adelante. Este sensor detectar filtraciones que penetren por la capa secundaria (exterior) o el producto que se pudiese fugar por la primaria. Estas medidas responden a la necesidad de evitar la contaminacin del suelo, de acuerdo a las leyes medioambientales y de los productos petrolferos por la prdida econmica subsiguiente.
Conformidad con la norma UNE 62.350-4 y el proyecto de norma europea PREN 12-285-1.
Soldadura automtica interior y exterior del tanque primario. Doble marco en boca hombre que garantiza la inalterabilidad de la cmara y la posibilidad de colocacin de arquetas estancas.
Sin necesidad de instalacin de proteccin catdica. Posibilidad de incorporacin de cualquier detector de fugas en el espacio anular: variacin de presin, sensor de lquidos y sensor de vaco.
Memoria-Descripcin
21
Construccin inalterable de la cmara intersticial. Esto se conseguir mediante un diseo interior tridimensional
indeformable con lo que se adquirir la capacidad de detectar cualquier fuga en la capacidad total del depsito.
El fabricante deber garantizar que los tanques han sido sometidos a un examen dimensional y visual minucioso, as como a un ensayo de fugas y cargas debidas a su enterramiento, demostrando as su hermeticidad y estanqueidad. Deber existir, por tanto, un certificado emitido por el propio fabricante en el que se justifique el cumplimiento de dichos ensayos.
6.1.2 Posicionamiento de los depsitos En la instalacin se localizarn tanques de 50.000 litros, cuatro para gasleo C, dos para gasleo B y uno para biocombustible, enterrados en un cubeto de hormign y separados segn el tipo de hidrocarburo que contengan por medio de tabiques estancos. La separacin mnima entre depsitos ser de 1m y la dimensin mnima del foso ser tal que contenga al grupo de depsitos correspondiente dejando un espacio perimetral de al menos 50 cm. para facilitar cualquier futura operacin, ya sea revisin, mantenimiento o emergencia La distancia mnima desde el borde de cualquier foso a muros, pilares, cimientos o cualquier elemento estructural no ser menor que 2 metros.
Memoria-Descripcin
22
6.1.3 Diseo Se emplear un cdigo de diseo de reconocido prestigio y aceptado internacionalmente. Los cdigos de diseo vigentes en la U.E. se respetarn siempre que garanticen de forma satisfactoria el nivel de seguridad exigido. Una vez elegido el cdigo se aplicar en su totalidad en el proyecto sin poderse efectuar mezclas de clculos de diferentes cdigos excepto en el caso de que el cdigo utilizado sea incompleto, momento en el cual s se podr recurrir a otro, igualmente de reconocido prestigio. El nmero de chapas para la construccin de las virolas y de los fondos del depsito, as como en la boca de hombre, se ajustarn a lo especificado en la norma UNE 36.080 (EN 10025), con calidad mnima A310-0 u otra forma de seguridad equivalente. Estas chapas en ningn caso tendrn ms de 0,06% de azufre o fsforo en su composicin y estarn libres de impurezas, segregaciones de colada, escamas o picados de laminacin y no presentarn defectos de fabricacin que disminuyan sus caractersticas mecnicas. En lo referente a las resinas sintticas destinadas a la realizacin de la pared exterior, debern reunir las condiciones especificadas en la norma UNE 53361. El material de refuerzo utilizado ser de fibra de vidrio, incorporndose a la resina.
6.1.3.1 Fondos El radio de acuerdo para unir la envolvente cilndrica con los fondos ser como mnimo de 50 mm para depsitos de capacidad igual o inferior a 50.000 litros. La longitud mnima de la pestaa para ser soldada a la envolvente cilndrica ser como mnimo 4 veces el espesor del fondo. Los fondos sern de una pieza hasta un dimetro de 1.500 mm. Para dimetros superiores se admite una nica soldadura diametral.
Memoria-Descripcin
23
6.1.3.2 Ovalizacin Es la diferencia entre el dimetro mximo y el mnimo (en una misma seccin transversal, medidos lo ms prximo al centro), dividida por el dimetro medio. Si las deformaciones diametrales entre el depsito vaco y descansado sobre una superficie plana y ese mismo depsito lleno y en comunicacin con el ambiente sobrepasan el valor de 2% hay que prever el uso de anillos de refuerzo.
6.1.3.3 Anillos de refuerzo Los anillos de refuerzo se componen de perfiles de acero laminado o acero inoxidable si corresponde, curvados en forma circular. Resultan necesarios para no sobrepasar el valor de ovalizacin prescrito. Se dispondrn anillos de refuerzo en nmero suficiente. Se situarn en el interior de las virolas a las que estarn fijados mediante soldadura en ngulo discontinua, con costuras alternadas sobre los dos lados del alma, con una interrupcin en la generatriz inferior para dar paso al lquido y una en la parte superior para los vapores. No debern cubrir ni total ni parcialmente las soldaduras salvo cuando cruce con las soldaduras longitudinales.
6.1.3.4 Soldaduras Las juntas se harn por arco elctrico por ambas caras y se realizarn con procedimiento de soldadura homologado y por soldadores cualificados segn UNE-EN 287 (Partes 1 y 2) y segn UNE-EN 288
Memoria-Descripcin
24
(Partes 1 a 4). La homologacin se realizar a travs del Comit de Certificacin CTC084. El procedimiento empleado, el mtodo utilizado y la preparacin de los bordes deben conseguir una soldadura sana a lo largo de las juntas, as como en l totalidad de su espesor, Deber asegurarse tambin una penetracin total, con soldadura por ambas caras. Las soldaduras longitudinales de las virolas se alternarn de manera que no estn en prolongacin las unas de las otras, con una separacin mnima de 100 mm. Si las virolas no pueden ser de una pieza, estas no podrn estar formadas por ms de dos chapas soldadas, situndose las soldaduras en la mitad superior de los depsitos, simtricamente, a uno y otro lado del plano vertical de simetra. Ninguna soldadura de accesorios tales como tubuladuras, virola de boca de hombre, dispositivos de elevacin, etc., deber encontrarse a menos de 50 mm de cualquier otra soldadura. La pared exterior se realizar mediante uniones qumicas que tendrn como mnimo las caractersticas mecnicas y qumicas exigidas para las piezas a unir segn lo especificado en la norma UNE 53.361. As mismo, los agujeros practicados para el montaje de tubuladuras y boca de hombre debern dotarse de refuerzos compensatorios.
6.1.3.5 Capacidad La capacidad real de los depsitos no deber exceder un 3% de la capacidad nominal, sin contar con la capacidad de la virola de la boca de hombre. En el gasocentro proyectado, por tanto, dicha capacidad no podr exceder de 51.500 litros para los depsitos de gasleo B, C, ni biomasa.
Memoria-Descripcin
25
6.1.3.6 Materiales Sern depsitos de doble pared de acero y prfv. Todos los materiales que se utilicen debern estar debidamente acreditados mediante certificacin del fabricante, la cual deber acompaar a cada uno de los depsitos.
6.1.4 Equipamiento de los depsitos 6.1.4.1 Tubuladuras Son conexiones preparadas para unin mediante bridas, roscas u otros medios, de tuberas que cumplirn funciones de ventilacin, llenado, aspiracin, etc. Las tubuladuras de los depsitos sern tubos de acero conformes con la norma UNE 19040, de material St37.0 segn DIN 1629. Estarn unidas a las chapas de los depsitos por medio de soldaduras en ngulo interiores y exteriores, penetrando en el interior del depsito al menos 15 mm. Debern estar situadas sobre las tapas de la boca de hombre o sobre la generatriz superior. Las tubuladuras con las que estn provistos los depsitos son:
Tubera de carga, de 4 de dimetro. Tubera de ventilacin, de 2 de dimetro. Tubera de impulsin, de 4 de dimetro. Medida de nivel, de 2 de dimetro.
Las tubuladuras no utilizadas estarn obturadas hermticamente para evitar posibles fugas de combustible. No se requieren tubuladuras de recuperacin de gases debido a que se trabaja con gasleo.
Memoria-Descripcin
26
6.1.4.2 Bocas de hombre Se conoce como boca de hombre a la tapa de registro del depsito. Debe estar formada por tantos orificios como tubuladuras se han mencionado anteriormente. Dicha boca ser circular con dimetro 500 mm y de forma que su virola est como mnimo a 50 mm de cualquier otra soldadura. No podr haber ningn punto del depsito a ms de 5 m de una boca de hombre por lo que se prevn 2 bocas para los depsitos de ms de 10 m de longitud, como es el caso de los de 50.000 litros. En stos una de las bocas se utilizar nicamente para el acceso al interior del depsito y debe quedar libre de tuberas. El espesor de chapa de cuello de la boca de hombre tendr como mnimo el mismo espesor que las virolas de la envolvente cilndrica. La chapa que conforma el cuello de la boca de hombre estar unida a la chapa de las virolas del depsito con una soldadura de ngulo por ambos lados, penetrando al menos 15 mm en el interior del depsito.
6.1.4.3 Arquetas Cada depsito dispondr de una arqueta de boca de hombre que estar debidamente anclada al a boca de hombre, con la finalidad de contener las posibles fugas que pudieran tener lugar en al tubuladuras. Por otro lado tambin son tiles dichas arquetas para evitar la entrada de agua desde el exterior. Estas arquetas han de ser lo suficientemente amplias como para permitir la manipulacin y acceso a todas las conexiones de tubos, as como poder realizar sin dificultad todos los trabajos y verificaciones necesarias.
Memoria-Descripcin
27
En las arquetas se ubicarn las vlvulas de control de apertura y cierre del depsito. La anchura libre de las arquetas no podr ser inferior a 1.000 mm y como mnimo deber ser mayor que el dimetro de la tapa. Los depsitos seleccionados vienen provistos de arquetas de prfv que garantizan la estanqueidad de la zona donde van ubicadas, conforme con la reglamentacin vigente.
6.1.4.4 Tapa y bridas Se sometern a prueba de presin hidrulica sin que se aprecien deformaciones ni se produzcan fugas. Adems la tapa deber poder extraerse hacia arriba para evitar filtraciones.
6.1.4.5 Juntas Sern resistentes a los hidrocarburos y a los aditivos que puedan contener, asegurando estanqueidad y facilitando su sustitucin.
6.1.4.6 Tornillos Sern de un material que resista la corrosin y permita fcil sustitucin.
6.1.4.7 Deteccin de fugas Sistema para depsito de doble pared ISC. Clasificado como sistema de clase I segn prEN-13160. Est construido segn normas europeas para deteccin de fugas y evita la eventualidad de falsas fugas ya que dispone de un control de estanqueidad de la propia cmara.
Memoria-Descripcin
28
Correcto /
Deteccin de fugas en funcin de volumen de prdida. Indicacin analgica y digital de la presin en la cmara. Posibilidad de comprobacin de ajustes en las alarmas. Rango de trabajo hasta 400 mbares. Opcional: Seal de entrada 4-20 mA. Seal de salida para regulacin de cmaras. Testeo de seales luminosas y acsticas. Posibilidad de simular alarmas. Pulsador de paro de alarma y salida de alarma por rel. Indicacin en display n de tanque. Conectable a sistema de mantenimiento de cmara ISC.
Especificaciones elctricas:
Alimentacin: 220 V 15%. Frecuencia: 50/60 Hz. 10%. Consumo: 10W. Seal de entrada: 4/20 mA 2 hilos. Alimentacin externa: 16/24 V.D.C. Seal salida: Rel 8. Temp. Trabajo: -20/60
Memoria-Descripcin
29
Especificaciones neumticas:
Presin
Vlvula presin (Seguridad 400 mbar). Rango mximo: 400 mbar. Umbral alarma: 325 mbar.
Conducciones
Lnea de medida: Ref. T1D6R0 6.
Generales (CNVP-75)
Format: 110 x 190 x 40 Proteccin: IP-20 Peso: 400 gramos Montaje: Pared Aprobacin barrera Zener: clase [EE x ia] II C
Producto conforme a las normas CE: EN 50081-1/EN 50082-1 Proyecto norma EN 13260-1/EN 13260-2. ste sistema estar conectado a la computadora encargada de la gestin del gasocentro, la cual controlar todos los parmetros de seguridad.
6.1.4.8 Sistema de sondeo Ser un sistema electrnico que reportar los resultados de las medidas a la computadora de control. Permitir conocer el nivel existente en cada depsito. Contar con una precisin en la medida de nivel de 2 mm y resolucin de 0.15 mm y estar cableado para su conexin a la red con cable H07 RN 5 x 1 mm2.
Memoria-Descripcin
30
Cada depsito dispondr de una varilla calibrada con la que se podr medir manualmente el nivel de combustible en cualquier momento como alternativa al sistema electrnico. Esto es una medida de prevencin por si fallase el sistema electrnico.
6.1.4.9 Dispositivo de manejo de tanques En la generatriz superior de los depsitos se montarn dos orejetas de rizado de forma simtrica en relacin con el centro de gravedad de los depsitos vacos. Se calcularn como mnimo para una carga igual al doble del peso del depsito vaco. Sern diseadas para no transmitir esfuerzos anmalos a la estructura del depsito.
6.1.5 Enterramiento de depsitos Se emplear un cubeto estanco para alojar los depsitos que contengan el mismo producto. Sus dimensiones deben superar las de los depsitos en medio metro en todo su contorno. Los depsitos distarn entre s un metro como mnimo. El cubeto estar cerrado por un muro de hormign de 1 pie de espesor enfoscado en todo su contorno sobre losa de hormign armado H200 y AEH-400N. En l se realizar un lecho de arena silcea lavada, seca y exenta de sustancias que puedan atacar qumicamente a los materiales del tanque. El tamao de los granos de arena ser de entre 0,1 y 0.2 mm, Esta arena estar convenientemente mullida y tendr 50 cm. de espesor.
Memoria-Descripcin
31
El cubeto, una vez colocados los tanques, se rellenar con la misma arena que el lecho, con cuidado de no daarlos. La arena cubrir incluso la parte superior de los tanques con un espesor de 50 cm., como mnimo, independientemente de las capas necesarias para alcanzar el nivel del pavimento a construir, siendo la resultante mnima 1 metro por encima de la generatriz superior. Sobre la arena se coloca una capa de zahorra compactada de 20 cm. de espesor. Sobre sta se coloca otra capa del mismo espesor de zahorra natural. Para terminar se extiende una tercera capa de zahorra compactada de 20 cm. La profundidad final por tanto es de 1,6 m. desde la generatriz superior de los tanques. Sobre estas capas se har una losa de hormign armado H-200 y AEH-400N de 20 cm. sobre la que descansar el pavimento. En cada depsito y sobra cada boca de hombre, conforme a la norma UNE-109504 IN sobre la obligatoriedad de arquetas estancas, se pondr una arqueta estanca de prfv sobre la que ir asentada una tapa que sobresaldr 1,5 cm. sobre el pavimento para evitar la entrada de lquidos dentro de la arqueta.
6.1.6 Llenado de depsitos Las conexiones de llenado de los tanques se instalarn en el interior de arquetas estancas a fin de contener pequeos derrames que se puedan producir. Adems dispondrn de un sistema de recogida de los mismos. A todos los tanques se les acoplarn dispositivos para evitar un rebose por llenado excesivo (vlvulas de sobrellenado).
6.1.7 Proteccin contra corrosin Adems de los sistemas de medida y de control de fugas, los depsitos debern estar protegidos contra la corrosin. Se entiende por
Memoria-Descripcin
32
corrosin todo proceso electroqumico de degradacin por oxidacinreduccin de los materiales de construccin de tanques, tuberas y estructuras enterrados, sumergidos o en contacto con un medio conductor. La corrosin est relacionada por tanto con una reaccin de transferencia de electrones y en consecuencia con el paso de una corriente elctrica de corrosin entre un nodo y un ctodo a travs de un medio conductor (agua, suelo). La destruccin o perdida de las caractersticas constructivas de estos materiales es la consecuencia inmediata de la corrosin y la velocidad de la misma, tambin llamada velocidad de prdida de material es la medida empleada para determinar los riesgos que sta conlleva. La velocidad de corrosin crece con el aumento de la superficie de las zonas andicas, la disminucin de la resistividad del medio conductor y con la presencia de factores aceleradores como pueden ser bacterias especficas, entre otros. La corrosin puede provocar perforaciones y debilitamiento de tanques y tuberas de acero enterradas, sumergidas o que contengan un fluido conductor, aunque tambin afecta a las estructuras mecnicas de soporte y a todos los sistemas de puesta a tierra. En general puede suponer:
Aumento del riesgo de accidentes personales. Aumento del riesgo de incendio y explosin. Aumento del riesgo de contaminacin ambiental Prdida de producto. Paros del proceso o servicio. Contaminacin del producto. Elevados costes de reparacin. Degradacin de estructuras y sistemas.
Memoria-Descripcin
33
Ha de evitarse la corrosin de todos los componentes de la instalacin. Para ello ser aislado elctricamente cualquier elemento metlico que se encuentre enterrado para cortar el paso a las corrientes de corrosin. Este aislamiento podr ser de dos tipos distintos, activo y pasivo.
6.1.7.1 Proteccin Activa Corresponde al empleo de un sistema de proteccin catdica en caso de que el estudio de agresividad del terreno lo recomiende. La proteccin catdica funciona gracias al a descarga de corriente desde una cama de nodos hacia tierra y dichos materiales estn sujetos a corrosin, por lo que es deseable que dichos materiales se desgasten o corroan a menores velocidades que los materiales que protegen. La finalidad de la proteccin catdica es garantizar un potencial entre l y el suelo que, medido respecto al electrodo de referencia cobresulfato de cobre, sea igual o inferior a -0,85 V. Se tendr -0,95 V como mximo cuando haya riesgo de corrosin por bacterias sulfatorreductoras. El objetivo es polarizar el ctodo con una corriente externa ms all del potencial de corrosin hasta alcanzar como mnimo el potencial del nodo en circuito abierto. Al adquirir ambos el mismo potencial se elimina la corrosin. De esta forma el metal ms atractivo es el andico, corroyndose ste ms que el que queremos proteger. Para el nodo utilizaremos un metal con mayor potencial que el acero, por ejemplo magnesio, que adems est libre de pasivizacin. Estos nodos estn diseados para obtener el mximo rendimiento y se enterrarn a lo largo de todo el permetro de la superficie a proteger. Las ventajas de emplear este sistema frente a otros, como por ejemplo la proteccin por corriente impresa son:
Memoria-Descripcin
34
Voltaje de aplicacin elevado. Amperaje limitado, evitando las sobreprotecciones. Aplicable en casos de corriente pequea, econmico hasta 5 A. til en medios de baja resistividad. La interferencia con estructuras encerradas es prcticamente nula.
Mantenimiento simple.
6.1.7.2 Proteccin Pasiva Se estudiar el caso de existencia de aguas selenitosas, corrosivas u otro elemento agresivo en la zona del enterramiento.
Como mnimo en medio no agresivo el revestimiento deber
El tipo de tanques de almacenamiento empleado evita la necesidad de aplicar recubrimiento exterior mediante capa de pintura, al ir revestidos de prfv. Se comprobar el estado del revestimiento exterior inmediatamente antes de ser enterrado. El interior de los depsitos se limpiar de aceites, grasa, etc., aplicndose un tratamiento de cepillado manual o mecnico para conseguir que la superficie presente un aspecto de brillo metlico. En caso
Memoria-Descripcin
35
de haber una proteccin pasiva interior, el producto empleado debe ser compatible con el combustible a contener. Se usar por tanto pintura resistente a hidrocarburos.
6.1.8 Pruebas y exmenes en fabricacin Antes de la instalacin de los depsitos se debern realizar una serie de controles de los mismos para verificar su correcto estado. 1) Control dimensional:
Tolerancias. Espesores nominales de chapas y de fondos: UNE 36.559
(EN10029 y EN10029AC).
Longitudes: +1/-0 %. Capacidad nominal: +3/-0 %. Ovalizacin: Se mide antes y despus del llenado de agua,
quedndose los depsitos de comunicacin al aire libre. Sus valores no superarn el 2%.
prueba de presin.
3) Examen de soldaduras a tope o asimiladas: Se examinarn visualmente las soldaduras longitudinales y circulares para poner en evidencia los posibles defectos, que no pueden exceder los siguientes lmites:
Memoria-Descripcin
36
Soldaduras longitudinales: 1 mm. Soldaduras circulares: 2 mm. Punto de inflexin local: h/l. Falta de espesor de soldadura: 0 mm. Sobreespesor de soldaduras: 1 mm.
4) Grietas, fisuras, sopladuras e inclusiones desembocando en superficie: Estos defectos siempre dan lugar a reparaciones.
5) Mordeduras:
Profundidad mxima: 0,5 mm. Longitud mxima 40 mm.
La longitud mnima de zona sana para que un defecto de estos dos ltimos grupos se considere aislado es de 6 veces la longitud del defecto ms corto. Est prohibido sanear un punto de fuga o una falta de material con el depsito lleno.
6) Examen de soldaduras en ngulo: Tendrn una altura de garganta como mnimo de 0,7 veces el espesor de la ms fina de las chapas soldadas.
Memoria-Descripcin
37
7) Pruebas de presin: Con las tubuladuras tapadas y las tapas de las bocas de hombre en su sitio, el depsito se someter a una prueba de presin de 0,75 bar. sta resulta satisfactoria si durante todo el tiempo necesario para el examen de las soldaduras no se observa fuga alguna en el depsito. La duracin mnima de esta prueba es de dos horas. Cualquier reparacin en el tanque obligar a una nueva prueba de presin. Certificacin: El fabricante emitir un certificado de cumplimiento de las pruebas y exmenes indicados, desglosando material empleado, presin de prueba, espesores de virola y fondos y posibles limitaciones de uso.
6.1.9 Pruebas en el lugar de emplazamiento Antes de colocar los depsitos en su alojamiento se sometern a un control para comprobar que no han sufrido daos durante el transporte y descarga. Despus sern sometidos a una prueba de estanqueidad hidrulica o neumtica a una presin manomtrica superior a 20 KPa (0,2 kg/cm2) y no superior a 34 KPa (0,35 kg/cm2). Se realizar tambin una prueba de medicin dielctrica. Todas estas pruebas sern certificadas por un organismo de control competente debidamente acreditado.
Memoria-Descripcin
38
6.2 Red de tuberas 6.2.1 Materiales y dimensiones 6.2.1.1 Tuberas y accesorios El material de las tuberas para las condiciones de los gasleos ser acero al carbono que cumplir las siguientes normas: UNE 19.011, UNE 19.040, UNE 19.041, UNE 19.045, UNE 19.046. De esta forma se asegura el cumplimiento de los siguientes requisitos: 1) Resistencia interna y externa a los productos petrolferos. 2) Permeabilidad nula a los vapores de los productos petrolferos. 3) Resistencia mecnica adecuada a la presin de prueba. Las uniones de los tubos entre s y de estos con los accesorios se harn de acuerdo con los materiales en contacto y de forma que el sistema utilizado asegure la resistencia y la estanqueidad sin que sta pueda verse afectada por el gasleo que conduzcan. Las conducciones tendrn el menor nmero posible de uniones en su recorrido. Para ello se montarn las tuberas en tramos de la mayor longitud posible unidos mediante bridas o soldadura a tope. Las conexiones roscadas se limitarn a vlvulas o equipos, no siendo admisibles las uniones en los dems elementos que no puedan ser inspeccionadas visualmente. El dimetro de las tuberas y de sus elementos accesorios se calcular atendiendo al caudal, a la longitud de la tubera y la viscosidad del lquido a la temperatura mnima que pueda alcanzar. Los materiales empleados y las dimensiones de las tuberas y accesorios se ajustarn como mnimo a las especificaciones de la norma UNE 19.040, de material St37.0 segn DIN 1629, u otras normas de seguridad equivalentes.
Memoria-Descripcin
39
Cuando las tuberas se conecten a tubuladuras situadas en la boca de hombre, se realizarn mediante uniones desmontables de forma que permitan liberar completamente el acceso de la boca de hombre. Para ello dispondrn de los acoplamientos necesarios para su desconexin. Los cambios de direccin en tuberas se practicarn mediante el curvado en fro, tal como se indica en la norma UNE 37.505 al ser galvanizadas. Si el radio de curvatura fuera inferior al mnimo establecido en normas, el cambio de direccin se resolver mediante la utilizacin de codos de acero para soldar segn norma UNE 19.071 o mediante codos y curvas de fundicin maleable definidas en la norma UNE-EN 10.242. Cualquier tubera enterrada bajo el suelo tendr una pendiente continua al menos del 1% de forma que no se formen retenciones de lquido en un lugar inaccesible.
6.2.1.2 Vlvulas Sern de materiales que resistan la corrosin. La estopada ser hermtica y resistente a hidrocarburos, asegurar la continuidad elctrica de la tubera y de no ser as se puentear con cables.
6.2.1.3 Uniones Las tuberas y sus accesorios se unirn mediante soldadura a tope por arco elctrico y se realizar con procedimiento de soldadura homologado y por soldadores cualificados El procedimiento y la preparacin de los bordes deben permitir conseguir una soldadura sana en toda la junta, as como en la totalidad de su espesor.
Memoria-Descripcin
40
6.2.2 Conexiones 6.2.2.1 Carga del tanque La carga o llenado se realizar por conexiones formadas por dos acoplamientos rpidos abiertos, uno macho y otro hembra, gracias a los cuales se puedan hacer transferencias de gasleos de forma estanca y segura. Sern del tipo acoplamiento rpido, construidos de acuerdo con una norma de reconocido prestigio. Ser obligatorio que sean compatibles entre la manguera del camin cisterna y la boca de carga del depsito. Las conexiones rpidas sern de materiales que no puedan producir chispas en el choque con otros materiales. Dispondrn de un sistema de cierre hermtico a la desconexin de la manguera de descarga. El acoplamiento debe garantizar su fijacin y no permitir un desacoplamiento fortuito. Los acoplamientos deben asegurar continuidad elctrica. Tanto la tapa de la arqueta como la tapa de la boca de llenado estarn identificadas mediante inscripciones claramente legibles de la denominacin del producto a cargar. La tubera de carga entrar en el tanque hasta 15 cm. del fondo y terminar preferentemente cortada en pico de flauta y su dimetro no podr ser inferior al del acoplamiento de descarga. La carga de los tanques, al estar stos enterrados, se har por gravedad. La tubera de conexin entre la boca de llenado y el tanque tendr una pendiente mnima del 1% y un dimetro de 4. Se evitar en todo momento la presurizacin de los depsitos. Las arquetas estancas en el interior de la arqueta de la boca de hombre para contener los pequeos derrames que se puedan producir sern del tipo SP1 o similar e irn roscadas sobre las tuberas.
Memoria-Descripcin
41
6.2.2.2 Ventilacin La tubera de ventilacin tendr en su salida de los tanques un dimetro de 2, calculado de forma que la evacuacin del os gases no provoque sobrepresin en el tanque. La tubera tendr una pendiente hacia el tanque tal que permita la evacuacin de los posibles condensados y tendr un valor mnimo del 1%. Se conectarn las tres salidas de ventilacin de tanques B a un nico tubo de dimetro 2 al que se unir tambin las salidas de ventilacin de los tanques C. Finalmente estas canalizaciones accedern al aire, a dos metros y medio sobre el nivel del terreno, lugar en que los vapores expulsados no pueden penetrar en instalaciones ni entrar en contacto con alguna fuente que pudiera provocar su inflamacin. Su salida estar provista de una proteccin contra la entrada de productos u objetos extraos. La boca de la salida ir provista de rejilla cortafuegos.
6.2.2.3 Extraccin del producto del tanque La extraccin del gasleo se har por impulsin. La tubera de extraccin se dimensionar de acuerdo al caudal de suministro de los equipos correspondientes y a las normas que los fabricantes de los mismos recomienden. La tubera se situar en el fondo del tanque. Con el fin de evitar el vaciado de la tubera hacia el equipo dispondr de vlvulas antirretorno en los puntos en los que sea necesario. La tubera situada en el fondo del tanque deber dejar una altura libre de 15 cm. por ser los tanques de capacidad superior a 3.000 litros, que evite el estrangulamiento de la aspiracin. Se emplearn, a la salida del tanque, tuberas de acero al carbono estirado, sin soldaduras, de 4 de dimetro, con una pendiente del 1%
Memoria-Descripcin
42
llegando hasta una altura de 20 cm. del fondo del depsito. Las 3 tuberas procedentes de los tanques de gasleo B concurren en una de 6 de dimetro del mismo material. Lo mismo ocurre con las 3 tuberas procedentes de los tanques de gasleo C. Biomasa?? Se dispondr de vlvulas de retencin en escuadra de 4 de dimetro del mismo material. No se permitirn sifones ni puntos bajos en todo el recorrido de las tuberas de aspiracin.
6.2.2.4 Conectores flexibles Ser admisible la utilizacin de elementos flexibles en las conexiones entre tubera rgida y equipos, en las tubuladuras de los tanques y en los equipos de consumo, trasiego, bombeo, etc. Estarn construidos con material apropiado para la conduccin de combustibles lquidos y reforzados o protegidos exteriormente por una funda metlica u otro material de proteccin mecnica equivalente. Los conectores flexibles debern ser accesibles de forma
6.2.3 Proteccin 6.2.3.1 Activa La red general de tierras es de cable de cobre trenzado desnudo y picas de zinc. Las tuberas tendrn continuidad con la red de tierras. Los tubos de venteo y de descarga no tendrn juntas aislantes, no se unirn a la red general y se conectarn a la tierra local de zinc junto a l a pinza del camin. Como las bombas son sumergidas, su tierra no se unir a la red general de cobre y s a la red local de zinc.
Memoria-Descripcin
43
Es esencial evitar el contacto entre las tuberas de acero enterradas y la red general de tierra de cobre. Las tuberas de impulsin de acero de simple pared tendrn proteccin activa.
6.2.3.2 Pasiva Las tuberas de acero enterradas sern protegidas contra la corrosin provocada por la humedad y agresividad del terreno mediante una capa de imprimacin antioxidante y revestimientos inalterables por los hidrocarburos que aseguren una tensin de perforacin mnima de 15 kV.
6.2.3.3 Enterramiento Se colocarn las tuberas sobre una cama de material granular exento de aristas o elementos agresivos de 10 cm. de espesor, como mnimo, protegindose las mismas con 20 cm. de espesor del mismo material. La separacin entre tubos deber ser de, al menos, la longitud equivalente al dimetro de los tubos
De resistencia y estanqueidad:
Antes de enterrar las tuberas se sometern a una prueba de resistencia y estanqueidad de 2 bar. (medida relativa) durante una hora.
Memoria-Descripcin
44
Las tuberas de impulsin, en la instalacin con bomba, se sometern a una prueba de resistencia y estanqueidad de 1,5 veces la presin mxima de trabajo de la bomba durante una hora. Durante la prueba de resistencia se comprobar la ausencia de fugas en las uniones, soldaduras, juntas y racores mediante la aplicacin de productos especiales destinados a este fin.
Controles:
Antes de enterrar las tuberas es controlar que las protecciones mecnicas de las mismas tienen continuidad y no se aprecien desperfectos visuales. Se comprobar que las tuberas estn instaladas con pendiente continua hacia el tanque.
6.3 Suministro de combustible 6.3.1 Sistema de bombeo Se instalar una bomba de paletas por cada tanque de almacenamiento. Sern sumergidas, autoaspirantes, con vlvula de bypass incorporada, reductor y motor elctrico antideflagrante de 1.500 rpm, 400/690 V 50 Hz de 10 CV, para arranque estrella-tringulo. El caudal real ser de 980 l/min. En la entrada de la bomba se situar un filtro.
6.3.2 Brazos de carga Se emplearn 2 brazos de carga superior, uno para cada tipo de gasleo, sobre estructura soporte compuesta por escaleras y plataformas unidas por pasarelas, adems de escaleras plegables para facilitar al operario la colocacin del brazo en la operacin de carga, todo ello con el
Memoria-Descripcin
45
fin de minimizar el riesgo de cada de los operarios durante las operaciones de carga. El hecho de emplear un brazo de carga para suministrar cada clase de gasleo evita la mezcla de distintos tipos de gasleo adems de reducir las esperas de los camiones.
6.3.3 Medidor de caudal Se instalar un medidor por cada brazo, de caudal mximo 1.000 l/min. Y caudal mnimo 39 l/min. Son volumtricos de paletas rotativas. Estn compuestos por filtro, degasificador, contador de cinco dgitos de puesta a cero manual, totalizador de ocho cifras, predeterminador con vlvula de corte de dos etapas y vlvula air check.
6.3.4 Conexin a computadora Se realizar mediante terminal con interfaz para gestin del consumo y el stock.
6.3.5 Dispositivos de seguridad Toda la instalacin junto con las tuberas estar interconectada elctricamente entre s y a una puesta a tierra. Junto al puesto de suministro habr un conductor conectado por un extremo a tierra y por el otro, mediante una pinza, a la masa del camin cisterna.
En la modalidad de carga superior, donde normalmente hay vapores inflamables, los compartimentos deben estar elctricamente conexionados al brazo de carga, tuberas de llenado y a la estructura del
Memoria-Descripcin
46
cargadero. Si la unin se hace a sta ltima, es preciso que la tubera y la estructura estn interconexionadas. La conexin debe hacerse antes de proceder a la apertura de la boca de carga, debiendo mantenerse hasta que se cierre aquella, una vez completada la carga. Una resistencia de conexin de hasta 1 Mohm es recomendable a los efectos de disipacin de la electricidad esttica. De usarse las pinzas es importante el establecimiento de aletas para la conexin equipotencial, tanto en la cisterna como en el recipiente de llenado o vaciado. Los cables de conexin pueden ser aislados o no. El uso de stos ltimos permite visualizar la continuidad elctrica. En el caso de utilizar los aislados se precisa una comprobacin que constate su continuidad. Estos registros, en modo continuo, operan en conjuncin con seales luminosas o de parpadeo, impidiendo la seleccin y puesta en marcha de los grupos de bombeo, ante deficiencias de un contacto idneo.
En la modalidad de de carga superior todas la partes metlicas del dispositivo de laimentacin deben tener continuidad elctrica a partir del punto de conexin. Es decir, deben evitarse situaciones como intercalar una manguera no conductora equipada con acoplamientos metlicos, a menos que el acoplamiento est conexionado a la tubera de alimentacin.
Brazos de carga:
La descarga por electricidad esttica puede presentarse incluso estando correctamente conectado el camin cisterna, proveniente de la superficie libre del lquido. La turbulencia de flujo que originan los brazos de carga puede contribuir a la generacin de cargas. Por ello en la carga superior de lquidos de baja/ intermedia presin de vapor, antes de que se inicie la carga, el brazo o tubo buzo, cuyo extremo ser de material blanco antichispa, debe alcanzar el fondo del compartimento utilizando en la
Memoria-Descripcin
47
medida de lo posible deflectores o biseles a fin de evitar turbulencias. En su defecto, necesariamente se debe limitar la velocidad de flujo a 1 m/s. hasta que no quede sumergido el extremo del brazo, pudindose entonces elevar el caudal. Las velocidades de carga pueden controlarse usando dos regmenes de velocidades, uno de los cuales limita la velocidad al valor mencionado anteriormente (1 m/s). Esta caracterstica la incorporan actualmente los sistemas automatizados de carga.
7 Instalacin elctrica
La instalacin elctrica se realizar de acuerdo con lo indicado en la ITC MI-IP02 y de conformidad con la normativa especfica vigente. La instalacin elctrica no es objeto del presente proyecto, no obstante, a continuacin se dan pautas para el diseo.
7.1 Potencia instalada Todos los elementos elctricos del gasocentro cumplirn las normas y reglamentos de alta y baja tensin adems de los conceptos expuestos en la ITC MP-IP02.
Memoria-Descripcin
48
7.500 W
La potencia total estimada es de 40,55 KW. Es necesario un centro de transformacin para pasar de media tensin (suministrada por la compaa elctrica) a baja tensin. El transformador deber cubrir con solvencia la potencia total demandada.
7.2 Clasificacin de zonas La clasificacin de los emplazamientos se realizar segn el procedimiento indicado en el REBT. sta se definir teniendo en cuenta lo siguiente: a. La clase de emplazamiento. Vendr determinado por el tipo de sustancias presentes. Las instalaciones para suministro a vehculos se consideran emplazamiento de Clase 1 por ser lugares en los que hay o puede haber gases, vapores o nieblas en cantidad suficiente para producir atmsferas explosivas o inflamables. La clasificacin de emplazamientos peligrosos se realizar segn UNE-EN60079-10. b. Cada una de las zonas y su extensin. Las zonas se clasifican en Zona 0, Zona 1 y Zona 2. La definicin de cada zona se realizar mediante el anlisis de los siguiente factores:
Memoria-Descripcin
49
o Grado de la fuente de escape, que se clasifica en continuo, primario o secundario. Las fuentes de escape a considerar son: Cuerpo de los aparatos surtidores. Prensaestopas giratorios. Tanques de almacenamiento. Venteos de descarga. o Influencia de la ventilacin. Es esencial considerar que las instalaciones, al estar situadas al aire libre, tienen un ndice de ventilacin (renovaciones/hora) elevado, de forma que el grado de peligrosidad de la instalacin puede llegar incluso a no peligroso. Por lo tanto, an en el caso de una fuente de escape de grado continuo, las condiciones de ventilacin pueden crear ms tiempo de zona alrededor de la fuente de escape o una zona de tipo y extensin diferente. Teniendo en cuenta los puntos anteriores se procede a la determinacin de la extensin de las zonas:
Zona 0: El interior de los tanques de almacenamiento,
de
cierre
de
los
brazos
arquetas de registro o bocas de carga se clasifica como zona 0, debido a su situacin bajo el nivel de suelo y por tener puntos de escape, bien por la descarga de cisternas, bien por la operacin normal de medicin de tanques o
mantenimiento de la instalacin. En el interior de las arquetas de registro de zona 0 se procurar no instalar ningn equipo elctrico. Si hubiese que instalarlos, estarn
Memoria-Descripcin
50
de acuerdo por lo que respecta a materiales y canalizaciones con los apartados 5.2 y 6.
Zona 1: Los cuerpos de los equipos, donde van alojadas las
electrobombas pertenecientes a las instalaciones para suministro a vehculos, pueden considerarse como
deficientemente ventilados debido a la envolvente metlica. El interior de la envolvente de los surtidores se clasificar como zona 1 porque en l se prev una atmosfera de gas explosiva de forma peridica u ocasionalmente, durante el funcionamiento normal y adems no tiene una buena ventilacin. Por encima del nivel del suelo se origina un emplazamiento peligroso clasificado como zona 1 que ocupar un volumen igual al de una esfera de 1 m de radio con centro en el punto superior de las arquetas de registro o bocas de carga. En los emplazamientos peligrosos originados por los venteos de descarga de los tanques de
almacenamiento, ptimamente ventilados, se clasifica como zona 1 la parte que ocupa un volumen igual a una esfera de 1 m de radio con centro en el extremo ms alto de la tubera de ventilacin.
Zona 2: La envolventes exteriores de los cuerpos de los
surtidores y las de todos aquellos elementos pertenecientes a los mismos en los que se pueda originar un escape, se clasifican como zona 2 porque en ellas, o la atmsfera explosiva no est presente en funcionamiento normal y si lo est ser de forma poco frecuente y de corta duracin, o an dndose las condiciones anteriores, el grado de ventilacin es ptimo. Inmediato a la esfera de radio 1 m con centro en el punto superior de las arquetas de registro o bocas de carga, clasificada como zona 1, se clasifica una zona 2 tambin esfrica, de radio 2 m y centro tambin en el punto superior
Memoria-Descripcin
51
de dichas arquetas. Inmediato a la esfera de radio 1 m y centro en el extremo ms alto de la tubera de ventilacin, clasificada como zona 1, se clasifica una zona 2 tambin esfrica, de radio 2 m y centro en el extremo ms alto de la tubera de ventilacin.
Barreras: La extensin de cada zona anteriormente indicada
puede limitarse utilizando barreras de vapor que impidan el paso de los gases, vapores o lquidos inflamables de un emplazamiento peligroso a otro no peligroso. El aparato surtidor contar con una barrera de tipo 2 (por tratarse de un aparato surtidor con cabezal electrnico separado de su cuerpo a distancia no inferior a 15 mm) que cumplir los siguientes requisitos: 1. La barrera permitir el paso de tuberas, cables y ejes rgidamente instalados. 2. Las barreras de vapor superarn la prueba de respiracin restringida (CEI 79.15) y consistirn en dos barreras separadas por una zona de aire libre de no menos de 15 mm. 3. El paso del cable en ambas barreras se realizar por medio de prensaestopas IP54 o EExe. 4. El grado de proteccin de cada barrera ser IP54. La zona 2 para el aparato surtidor con la barrera de tipo 2 se extiende a una distancia de 1 m del aparato en cualquier direccin.
Memoria-Descripcin
52
7.3 Conductores Los cables utilizados en estas instalaciones sern segn UNE-EN 50265. El tipo de instalacin y las intensidades mximas estarn de acuerdo con las IC MIE BT 017 o MIE BT 029, segn se trate de instalaciones en zonas no clasificadas o en zonas clasificadas con peligro de explosin. Loas cables que dispongan de proteccin mecnica, o que dispongan de armadura a base de hilos de acero galvanizado, tendrn una seccin mnima de 2,5 mm2, para alimentaciones de fuerza; para alumbrado y control tendrn una seccin mnima de 1 mm2. Para el clculo de la seccin de los cables, la intensidad admisible de los conductores deber disminuirse en un 15%, adems de aplicar los factores de correccin dependiendo de las caractersticas de la instalacin. Todas las acometidas a receptores de longitud superior a 5 m debern disponer de una proteccin contra cortocircuitos y contra sobrecargas si estas son previsibles. Los cables en general sern con conductor de proteccin. En alimentaciones trifsicas, tres fases y conductor de proteccin, en circuitos monofsicos, fase, neutro y conductor de proteccin. Para la interconexin entre los elementos del surtidor (emisor de impulsos, solenoides, calculador, etc.), se considera suficiente la utilizacin de cable con cubierta exterior de PVC/policloropreno resistente a los hidrocarburos, de tipo no armado ya que al ser IP23 como mnimo el grado de proteccin mecnica del surtidor, en condiciones normales de operacin no es posible ejercer acciones mecnicas que puedan daar la integridad de los cables. Los efectos mecnicos, tales como eventuales vibraciones generadas por los equipos rotativos del surtidor, son despreciables, ya que lo cables van sujetos al mismo chasis. No se producir vibracin relativa entre
Memoria-Descripcin
53
chasis y cables. Las labores de mantenimiento y reparaciones se realizarn sin tensin y por personal cualificado.
7.4 Canalizaciones Las canalizaciones estarn de acuerdo con las ITC MIE BT02 o MIE BT029, segn se trate de instalaciones en zonas no clasificadas o en zonas clasificadas con peligro de explosin. Las canalizaciones subterrneas, cuando se utilicen cables armados, se realizarn en zanjas rellenas de arena o en tubos rgidos de PVC. Los tubos de acero sern sin soldadura, galvanizado interior y exterior, el roscado de los mismos deber cumplir las exigencias relativas al tipo de ejecucin de seguridad. Las canalizaciones de equipos porttiles o mviles sern con tubos metlicos flexibles, corrugados, protegidos exteriormente contra la oxidacin. Los racores y accesorios debern cumplir las condiciones del tipo de construccin correspondientes a su ejecucin de seguridad. En el punto de transicin de una canalizacin elctrica a otra, o de un emplazamiento peligroso a otro no peligroso, as como en las entradas y salidas de las envolventes metlicas de equipos elctricos que puedan producir arcos o temperaturas elevadas, cuando se empleen tubos de acero se deber evitar el paso de gas o vapores inflamables, para ello se realizar el sellado de estos pasos mediante cortafuegos.
7.5 Conexin a red general 7.5.1 Desviacin y acometida Se solicitar a la compaa suministradora. sta garantiza:
Tensin nominal: 20 kV. Intensidad nominal: 400 A.
Memoria-Descripcin
54
La acometida ser mediante lnea subterrnea por medio de conductores enterrados directamente en zanja. sta ir instalada en una zanja de 60 cm de ancho y 75 cm de profundidad. Los conductores irn enterrados en arena de ro apisonada y sobre un lecho de esta misma arena compactada y con un espesor de 10 cm. Sobre esta arena se coloca la proteccin mecnica para advertencia en caso de apertura de la zanja y que, generalmente, se compone de rasillas, macizos, ladrillos o placas de hormign. A 15 cm de esta placa se coloca la cinta de sealizacin de la existencia de cable enterrado. Esta cinta se encuentra enterrada en tierra de relleno apisonada; la zanja se completa finalmente con pavimento o tierra segn el caso. Formada por conductores de cobre de 3,5 x 70 mm2 de seccin, tipo RV 0,6/1 kV canalizado bajo tubo de PVC rgido de 110 mm de dimetro y llegar hasta el centro de transformacin. La acometida se har en bucle para poder reanillar el bucle ajeno a la avera en caso de una falta en la instalacin. Dicha lnea llegar hasta el cuadro general de proteccin situado en la sala de equipos. La funcin del CGP es proteger la instalacin interior, as como al usuario frente a contacto directos.
7.5.2 Centro de transformacin, caseta y celdas de potencia El equipo de transformacin estar formado por un conjunto de celdas homologadas, fabricadas y ensayadas bajo las normativas MIERAT, UNESA 64041A, UNE 200099 y UNE 20104. Podrn ser celdas MTU24 o similares por ser stas ideales para su aplicacin en centros de transformacin, maniobra y proteccin de Media Tensin, siendo los requerimientos de vigilancia y mantenimiento prcticamente nulos.
Memoria-Descripcin
55
Dicha celdas se construirn en forma monobloque con chapa de acero de 3 mm de espesor, plegada y soldada segn UNESA 64041A y designacin UNE 200099. El transformador realizar la reduccin de tensin desde 20 kV a 380/220V para alimentar los consumos de Baja Tensin. El transformador ser de servicio continuo y refrigeracin natural por aire. Sus caractersticas son:
Potencia: 100 KVA. Tensin en primario: 20 kV. Tensin en secundario: 380/220V. Frecuencia: 50 Hz. Grupo de conexin: Dyn11. Prdidas en vaco: 1000 W. Corriente de vaco: 1,5%. Tensin de cortocircuito: 6%. Factor de potencia y V a plena carga: 0,8; 4,48. Factor de potencia y a plena carga: 0,8; 98%. Dimensiones: 1500 x 900 x 1430 cm. Nivel de ruido: 50 dB. Tensin soportada a 50 Hz durante 1 min.: 50 kV eficaces. Tensin soportada ante rayo: 125 kV. Conjunta del circuito electromagntico protegido contra
corrosin por una capa de imprimacin y otra de acabado, a base de resina epoxi.
Dispositivo de control de temperatura. Envolvente metlica con grado de proteccin IP-239.
Estar situado en una caseta, en la que se alojarn tambin las distintas celdas de potencia.
Memoria-Descripcin
56
El piso de la caseta del transformador, situada de la sala de equipos, soportar una sobrecarga de 3.500 kg/m2. uniformemente repartida. En la caseta se evitar la entrada de agua desde el exterior sobreelevndola 30 cm sobre el suelo. Adems la caseta vendr equipada con instalacin automtica de inundacin total a base de anhdrido carbnico.
7.5.3 Caja general de proteccin y medida Al tratarse de una instalacin para un nico usuario, se permite la conjuncin en un mismo lugar de la CGP y los aparatos de medida. E situar a la salida del centro de transformacin. Los aparatos de medida son los siguientes:
Mdulo de caja general de proteccin de 250 A trifsica y 440
V de tensin nominal conteniendo bases portafusibles de tamao 1 con neutro seccionable, bornes pasacables y envolventes. Se puede emplear para salida de
transformadores. Usa cartuchos fusibles de amperaje 80, 100, 125, 160, 200, 250 A. Tiene capacidad para cables hasta 150 mm2 de seccin.
Dos
mdulos
de
contadores
preparados
para
alojar
seccin tipo RV 0,6/1 kV. Totalmente instalado. 7.6 Lneas de distribucin Las lneas de distribucin se encargarn de llevar la corriente elctrica a los distintos cuadros de distribucin desde las barras del cuadro general de baja tensin a travs de proteccin magnetotrmica. La aparamenta de los cuadros segn el REBT e Instrucciones Complementarias correspondientes, constar de:
Memoria-Descripcin
57
corrientes de defecto. Las lneas de distribucin sern conductores de cobre RMV 0,6/1 kV bajo tubo rgido de PVC de 110 mm de dimetro enterrados. Las lneas que discurren por el interior del edificio son de 0,6/1 kV, bajo tubo rgido. Los cables sern resistentes a la accin de los hidrocarburos.
Las partes metlicas estarn puestas a tierra convenientemente mediante barra colectora de tierra en el interior de los cuadros. Las tensin suministrada a los cuadros secundarios en baja tensin ser de 380/220 V.
7.8 Red de fuerza La seleccin del material elctrico ser realizada de acuerdo con los establecido en la IC MIE BT 029. Las entradas de los cables y de los tubos a los equipos elctricos se realizar de acuerdo con el modo de proteccin previsto.
Memoria-Descripcin
58
Los orificios del material elctrico, para entradas de cables no utilizados, debern cerrarse mediante piezas acordes, al objeto de mantener el modo de proteccin de la envolvente. La distribucin de fuerza se realizar desde un cuadro de distribucin, compuesto por un interruptor automtico de proteccin general, un diferencial ms una serie de salidas separadas por cada receptor, cada una con proteccin contra cortocircuitos y sobrecargas. Siempre que sea posible, el cuadro de distribucin general, se instalar en el edificio de servicio en un lugar no peligroso. En cada circuito de fuerza se instalarn interruptores diferenciales de corte de intensidad de defecto con sensibilidad mxima de 30 mA. Se llevarn distintas tomas de corriente a los puntos de consumo. Las tomas monofsicas sern de 16 A con fase, neutro y tierra; las trifsicas tetrapolares de 25 A con dos fases, neutro y tierra.
7.9 Red de alumbrado La iluminacin general de las instalaciones se llevar a cabo con la mxima intensidad y amplitud posible, suplementando con aparatos locales donde se requiera observacin y vigilancia. La iluminacin se establecer de manera que procure la mayor seguridad del personal que trabaje de noche, en las operaciones que deban ser realizadas, e intensificada en los puntos de actuacin personal. Se procurar que los aparatos de alumbrado sean instalados fuera de los emplazamientos peligrosos. Los aparatos de alumbrado a instalar en emplazamientos peligrosos tendrn el modo de proteccin de acuerdo con el tipo de zona; los cuales estn definidos en la IC MIE BT 029. Debern incluir en su marcado la tensin y frecuencia nominales, la potencia mxima y el tipo de lmpara con que pueden ser utilizados.
Memoria-Descripcin
59
La instalacin de alumbrado se realizar con circuitos separados para cada servicio, alumbrado de marquesina, bculos de alumbrado, alumbrado de edificio de servicios, tomas de alumbrado, etc., los sern monofsicos, protegidos con interruptores automticos unipolares de 1,5 A como mximo.
7.9.1 Alumbrado interior Se realizar con equipos de fluorescencia. Estos estarn formados por tubos fluorescentes con condensadores de forma que se eleve con ellos el factor de potencia. Se emplearn lmparas de fluorescencia lineal de 2 x 36 W, clase elctrica 1 y sistema ptico IP-55. Se colocarn ocho luminarias distribuidas de la siguiente manera:
2 luminarias en el pasillo. 2 luminarias en la oficina de control. 1 luminaria en el almacn. 1 luminaria en la sala de equipos. 1 luminaria en vestuario de caballeros. 1 luminaria en vestuario de seoras.
Los aseos se iluminarn con lmparas de fluorescencia lineal de 35 W, clase elctrica 1 y sistema ptico IP-65.
7.9.2 Alumbrado exterior La intensidad mxima en las lneas de alumbrado exterior ser de 15 A. Se distinguen dos zonas:
Alumbrado de la marquesina.
Memoria-Descripcin
60
El alumbrado se realizar mediante 12 luminarias de marquesina de haz simtrico. La seccin mnima de los conductores ser de 2,5 mm2. Los materiales sern adecuados para las instalaciones al aire libre. Se emplearn lmparas H (halogenuros metlicos) de 250 W, clase elctrica 1 y sistema ptico IP-65.
Alumbrado del rea exterior
Se emplear luminaria exterior sobre bculo con equipo elctrico a 220 V y lmpara de 250 W sobre bculo de acero galvanizado y pintado de 10 m de altura. Se conectarn y desconectarn por medio de un rel fotoelctrico. Los conductores sern subterrneos a una profundidad mnima de 0,4 m. Se emplearn lmparas M (vapor de mercurio) de 250 W, clase elctrica 1 y sistema ptico y alojamiento de equipo IP-23.
sealizacin, fluorescente de 125 lmenes de flujo luminoso y 1 hora de autonoma. Descripcin: Cuerpo rectangular con aristas redondeadas que consta de una carcasa fabricada en policarbonato y difusor en idntico material. Contiene dos tubos, uno de emergencia que solo se ilumina si falla el suministro de red y otro que funciona como una luminaria normal que puede encenderse o apagarse a voluntad mientras se le suministre tensin. Caractersticas:
Funcionamiento combinado. Autonoma: 1 hora. Formato: Nova.
Memoria-Descripcin
61
Lmpara en emergencia: FL 8 W. Piloto testigo de carga: Led. Lmpara en red: FL 8 W. Grado de proteccin: IP44 IK04. Aislamiento elctrico: Clase II. Dispositivo verificacin: No. Puesta en reposo a distancia. Si. Tensin de alimentacin: 230V 50Hz. Color carcasa: Blanco. Difusor: Plano moleteado. Sin pulsador.
7.10 Red de tierra 7.10.1 Consideraciones generales La instalacin del sistema de puesta a tierra deber cumplir con las ITC BT 018 del REBT. Se instalar un sistema completo de puesta a tierra en toda la instalacin, a fin de asegurar proteccin adecuada para:
Seguridad del personal contra descargas de los equipos
elctricos.
Proteccin de los equipos elctricos contra averas. Proteccin contra la inflamacin de mezclas combustibles
por electricidad esttica. Para ello todas las partes metlicas de los equipos y aparatos elctricos se conectarn a tierra travs del conductor de proteccin.
Memoria-Descripcin
62
Adems, en todos los circuitos de fuerza se dispondrn dispositivos de corte por corriente diferencial residual mediante interruptores diferenciales, con sensibilidad mxima 30 mA. Para asegurar la proteccin contra electricidad esttica deber realizarse una unin equipotencial de masas. Todas las partes de material conductor externo (areo) debern estar conectadas a esta red: estructuras metlicas, aparatos surtidores y conductores de proteccin de los aparatos elctricos. En los tiempos de descarga del camin cisterna se dejarn sin tensin los circuitos de la marquesina, debido a que la salida de gases en esta operacin pueden provocar deflagraciones. Para evitar esto se instalarn sistemas adecuados de prevencin y corte a travs de los detectores de flujo en las bocas de carga. Existir una conexin mvil de tierra que permita la conexin del camin cisterna a tierra durante la carga y la descarga. Dicha conexin constar de un seccionador de cobre y de una pinza. Los postes de alumbrado exterior estarn provistos de una pica de puesta a tierra de las dimensiones adecuadas para evitar contactos directos.
7.10.2 Puesta a tierra de depsitos y tuberas Todas las tuberas y elementos metlicos se conectarn a la red general de tierra. Para evitar riesgo de corrosin o para conseguir una proteccin catdica correcta, los tubos de acero y fundicin enterrados no se unirn a un sistema de tierra en el que existan metales galvnicamente desfavorables para el acero, como el cobre, en contacto directo con el terreno.
Memoria-Descripcin
63
Los elementos enterrados de acero, tanques y tuberas, no se unirn a la red general por existir riesgo galvnico para los mismos al estar esta red construida con cable de cobre y picas de cinc y se aislarn de la red general de cobre. Para la puesta a tierra se tendr en cuenta lo especificado en el informe UNE 109 100. La pinza y la borna de puesta a tierra para el control de la electricidad esttica cumplirn la norma UNE 109 108 partes 1 y 2.
7.10.3 Puesta a tierra del centro de transformacin Se disear de acuerdo con el Reglamento sobre Condicione Tcnicas y Garantas de Seguridad en Centrales Elctricas, Subestaciones y Centros de Transformacin (RAT 13) y por el REBT MIE 029. Se verificar que las masas puestas a tierra del gasocentro as como los conductores de proteccin asociados a ellas no estn unidos a la toma de tierra de las masas del centro de transformacin. La toma de tierra se realizar mediante picas de acero con recubrimiento de 2 mm de cobre de 19 mm de dimetro y 2,5 m de longitud. Las picas estarn unidas mediante conductor de cobre trenzado y desnudo de 50 mm2. Este conductor cubrir el permetro de la caseta donde ir ubicado el centro de transformacin. La resistencia de puesta a tierra no podr sobrepasar los 10 . Si fuera superior se colocarn picas suficientes para reducir la resistencia a un valor admisible.
7.10.4 Instalacin de tierra Es una instalacin conductora de cobre que discurre paralela a la instalacin de enlace, desde la caja general de proteccin hasta el ltimo punto de toma de luz o de corriente.
Memoria-Descripcin
64
Conectar tambin con los tanques y tuberas. Antes de la puesta a tierra final mediante picas se establecer una unin entre todas las masas metlicas (tanques, tuberas, cuadros elctricos, brazos de carga, elementos estructurales, cimentaciones y los distintos puntos de servicio o proteccin) para conseguir equipotencialidad mediante un anillo conductor. En ste se colocar un puente de comprobacin que se situar en una arqueta. La proteccin se conseguir mediante interruptores magnetotrmicos y diferenciales. Se establecer una continuidad elctrica en todas las conducciones de gasleo para evitar el riesgo de chispas y electrosttica que se puedan producir. En las bocas de carga y descarga se colocar una pinza para equipotenciar los camiones antes y despus de la maniobra que vayan a realizar. La instalacin consta de tres partes: a. Lnea principal de tierra Comprendida entre el punto de puesta a tierra y el comienzo de la lnea secundaria de tierra. De cada punto de puesta a tierra parte una de estas lneas. o Lnea principal de la CGP. o Lnea principal del contador. o Lnea principal de la red equipotencial de baos y aseos. o Lnea principal de tierra de otros elementos. Ante una derivacin a travs de esta lnea, el tiempo mximo de circulacin de la corriente de defecto ser de 2 segundo, tiempo suficiente para que salten las protecciones. La seccin mnima de esta lnea viene dada por la seccin de los conductores de fase de la instalacin protegida. En el caso que nos ocupa, por ser todos los conductores de fase de una seccin menor
Memoria-Descripcin
65
o igual que 35 mm2, la lnea principal tendr una seccin mnima de 16 mm2. b. Lnea secundaria de tierra Enlaza la lnea principal con los conductores de proteccin de la instalacin interior. Ser de cobre y, por ser todos los conductores de fase de una seccin menor o igual que 35 mm2, la lnea secundaria tendr una seccin mnima de 16 mm2. En cuanto a su instalacin, ir entubada junto a los conductores activos, no pudiendo estar sometida a esfuerzos mecnicos. Estos conductores deben estar aislados. Los empalmes se realizarn con soldadura aluminotrmica asegurando que el empalme tenga baja resistencia de contacto. La unin de la lnea secundaria a las masas se realizar empleando tambin soldadura aluminotrmica. c. Conductores de proteccin Unen las lneas secundarias de tierra con las masas de una instalacin y los elementos metlicos conductores que puedan existir. Sern conductores de cobre y su seccin depender del conductor de fase al que acompae. As, para conductores de fase con seccin menor o igual que 16 mm2, la seccin del correspondiente conductor de proteccin ser la misma que la del conductor de fase. Para secciones del conductor de fase entre 16 mm2 y 35 mm2, el conductor de proteccin ser de 16 mm2. Las secciones mnimas son 2,5 mm2 con proteccin mecnica y 4 sin ella. Su aislamiento ser amarillo-verde a rayas.
Memoria-Descripcin
66
7.10.5 Tomas de tierra Se encarga de canalizar, absorber y disipar en el terreno las corrientes de falta o de origen atmosfrico que son trasladadas a travs de las lneas principales de tierra. Consta de las siguientes partes: d. Punto de puesta a tierra Une la lnea principal de tierra y la lnea de enlace con tierra. Por tanto, une la toma de tierra con el circuito de puesta a tierra. Se aloja en el interior de una arqueta formada por: o Muro aparejado de 12 cm de espesor y ladrillo macizo que ofrezca una resistencia de 100 Kg/cm2. o Tapa de hormign con resistencia de 175 Kg/cm2. o Tubo de fibrocemento de 60 mm de dimetro. o Solera de hormign con resistencia de 100 Kg/cm2. Al punto de puesta a tierra se le suelda a un lado la lnea principal y al otro la lnea de enlace. Ser de cobre, recubierto de cadmio y con dimensiones 33 cm de largo, 2,5 cm de ancho y 0,4 cm de espesor. Los puntos de puesta a tierra se ubicarn como puntos de puesta a tierra directos en los cuadros secundarios a travs de barra colectora de tierra. e. Lnea de enlace con tierra Une el electrodo, conjunto de electrodo o anillo con el punto de puesta a tierra. Ser de cobre o algn otro metal de alto punto de fusin. Tendr una seccin mnima de 16 mm2. f. Electrodos Introducen en el terreno las corrientes de falta o de origen atmosfrico. Con la puesta a tierra se pretende que el electrodo est a potencial 0. Deben procurar la resistencia de paso a tierra menor posible. Podrn ser:
Memoria-Descripcin
67
o Acero galvanizado (25 mm de dimetro exterior mnimo). o Perfiles de acero galvanizado (60 mm de lado como mnimo). o Barras de cobre o de acero recubierto de cobre (19 mm de dimetro mnimo). Su longitud ser de al menos 2 m y vendr dada por la resistencia de paso a tierra mxima admisible (5 para no superar los 24 V) y la resistividad del terreno segn la frmula R=/L. Para la resistividad del terreno objeto de estudio se concluye que la longitud del electrodo necesaria es de 2,5 m. Se emplear alma de acero recubierta de cobre, concretamente barras de acero recubierto de cobre electroltico de 19 mm de dimetro, siendo el recubrimiento de 2 mm de espesor. Un extremo ser roscado con manguito y tornillo sufridera y el otro extremo acabar en punta. Se emplear una colocacin de picas en paralelo con lo que la distancia entre cada par de picas ser mayor o igual a 2 veces la longitud enterrada (es decir 5 m) y se unirn entre s con un conductor de cobre trenzado y desnudo de 50 mm2 constituyendo un anillo. Las uniones se realizarn mediante soldadura
aluminotrmica tipo CADWELD. Las lneas de enlace con tierra sern de cobre trenzado y desnudo de 35 mm2 y se soldarn al anillo principal mediante soldadura aluminotrmica tipo
CADWELD. Al ser la red general de cobre desnudo, los tubos y tanques y tanques metlicos enterrados se unirn a una tierra local de cinc y se aislarn de la red general de cobre.
Memoria-Descripcin
68
7.11 Sistema de proteccin para descarga de camiones cisterna La instalacin llevar un sistema de puesta a tierra de las cisternas de los camiones, para descargar la electricidad esttica. El sistema estar compuesto de la siguiente forma:
Un cable conectado por un extremo a la red local de puesta a
tierra. El otro extremo provisto de una pinza se conectar a un terminal situado en el vehculo en ntimo contacto con la cisterna.
El cable de puesta a tierra ser extra flexible, con aislamiento,
interruptor, con modo de proteccin adecuado al tipo de zona del emplazamiento donde va instalado. El cierre del interruptor se realizar siempre despus de la conexin de la pinza al camin cisterna.
La tierra para el camin se unir a la red general de tierras si
7.12 Proteccin contra sobretensiones atmosfricas Este apartado tiene por objeto la definicin tcnica de los sistemas de proteccin contra sobretensiones y descargas atmosfricas en los equipos electrnicos instalados en el gasocentro. Con el concepto de sistemas de proteccin se engloban una serie de equipos destinados a reducir y evitar los efectos que producen la transmisin de sobretensiones ocasionadas por la descarga del rayo y los campos electromagnticos asociados, as como por sobretensiones transmitidas por las lneas entrantes al edificio, las cuales se producen por descargas en dichas rede, procesos de conmutacin en la red de alta
Memoria-Descripcin
69
tensin, maniobras red-grupo-red, arranque de motores y elevacin del potencial de la toma de tierra debido a descargas en las proximidades de la instalacin. Su objetivo es la proteccin de los equipos electrnicos y elctricos, lo primeros de gran vulnerabilidad, dadas las pequeas tensiones de aislamiento y su gran sensibilidad a las perturbaciones reseadas anteriormente. Se instalar un pararrayos del tipo inico, no radiactivo con un dimetro de proteccin apropiado a las dimensiones de A.F. y la u.S. La instalacin del pararrayos se efectuar en el monoposte, conectndolo a tierra lo ms directamente posible mediante un cable de cobre de 70 mm2.
7.13 Sistema de alimentacin ininterrumpida El SAI se destinar a garantizar la alimentacin elctrica de alta calidad a los equipos electrnicos. El SAI se alimenta desde el cuadro general de distribucin y mando tiene una potencia de 1.800 W. La distribucin de circuitos de alimentacin ininterrumpida se realiza desde el cuadro general de distribucin y mando en un espacio separado para esta proteccin especfica. Las condiciones de la instalacin son similares a las indicadas para la instalacin normal y estn bsicamente en funcin de las zonas en las que estn instalados.
Memoria-Descripcin
70
Reglamento de Seguridad Contra Incendios en los establecimientos industriales del Real Decreto 2267/2004 de 3 de Diciembre de 2004 (BOE de 17 de Diciembre de 2004).
8.1 Generalidades Las instalaciones, los equipos y sus componentes destinados a la proteccin contra incendios se ajustarn a lo establecido en el vigente Reglamento de Instalaciones de Proteccin contra Incendios. La proteccin contra incendios estar determinada por el tipo de lquido, la forma de almacenamiento, su situacin y la distancia a otros almacenamientos y por las operaciones de manipulacin, por lo que en cada caso ser seleccionado el sistema y agente extintor que ms convenga, siempre que cumpla los requisitos mnimos. En la Instruccin Tcnica Complementaria, se clasifican los productos a almacenar en clases. En el caso de este proyecto el producto a almacenar es gasleo. La clase, en la ITC MIE-APQ1, viene determinada por el punto de inflamacin del producto. Segn sea ste se tiene:
Clase A: Productos licuados cuya presin absoluta de vapor
100C. Para determinar el punto de inflamacin arriba mencionado, se aplicarn los procedimientos prescritos en la norma UNE 51.024, para los
Memoria-Descripcin
71
productos de la clase B; en la norma UNE 51.022, para los productos de la clase C y en la norma UNE 51.023, para los productos de la clase D. El punto de inflamacin del gasleo es de entre 35C y 70C, por lo que no queda claro si es de clase B o C, por lo tanto, a la hora de cumplir las exigencias de las Instrucciones Tcnicas Complementarias, se tomarn las ms restrictivas para las clases B o C, resultando con ello clasificado el gasleo como clase C. La seleccin del tipo de extintor se realiza teniendo en cuenta para qu clase de fuego se quiere el mismo. Para ello se considera lo expuesto en el Reglamento de Instalaciones de Proteccin Contra Incendios (R.D. 1942/1993. BOE 14.12.1993).
Notas:
En fuegos poco profundos (profundidad inferior a 5 mm)
agentes extintores el agua a chorro ni la espuma; el resto de los agentes extintores podrn utilizarse en aquellos
Memoria-Descripcin
72
En funcin de la tabla anterior se emplearn extintores de polvo ABC (polvo polivalente) de presin permanente.
8.2 Instalaciones en el interior de edificaciones 8.2.1 Proteccin con extintores En el interior del edificio de colocarn extintores porttiles de polvo polivalente ABC, de 6 Kg., con eficiencia 183B localizados en los siguientes puntos:
Oficina de control. Almacn. Sala de equipos. Pasillo.
La eficiencia 183B supera la mnima que exige la norma, 144B. Los extintores estn dispuestos de tal forma que la distancia a recorrer horizontalmente, desde cualquier punto del rea protegida hasta alcanzar el extintor adecuado ms prximo no exceda de 10 m, tal y como exige la norma. La norma exige que en la sala de equipos, donde se encuentran los cuadros elctricos, se site un extintor de eficacia extintora 21B, lo que equivale a un extintor de 1 Kg. En lugar de esto, por mayor seguridad, se colocar uno de 6 Kg y eficacia 183B. Por ltimo, se situar en la sala de control un extintor de 5 Kg de anhdrido carbnico especialmente indicado para fuegos de origen elctrico, ya que pese a que la normativa no lo exige, se considera importante para poder extinguir cualquier fuego que se pudiera originar en el ordenador o en los equipos elctricos. Los extintores porttiles debern ser sometidos a inspecciones peridicas, tal y como indica la normativa vigente, para asegurar su
Memoria-Descripcin
73
correcto funcionamiento cuando sea requerido. stas debern ser realizadas, generalmente por la empresa proveedora de los equipos.
8.2.2 Alarma Se colocarn detectores de humo en todas las habitaciones del edificio y tambin a lo largo del pasillo, que accionarn, en caso de incendio, una alarma acstica perfectamente audible en toda la zona.
8.2.3 Estabilidad ante el fuego No se considera necesario estabilizar ante el fuego ningn elemento interior por no darse la existencia de soportes o apoyos crticos, debido a la simplicidad de la estructura del edificio.
8.3 Instalaciones en el exterior de edificaciones 8.3.1 Proteccin de extintores Se colocarn 6 extintores porttiles de polvo polivalente ABC, de 6 Kg, con eficiencia 183B localizados en los pilares de la marquesina, de tal forma que la distancia a recorrer horizontalmente desde cualquier punto del rea protegida hasta alcanzar el extintor adecuado ms prximo no exceda de 15 m, ni exceda de dicho valor la distancia desde los extintores hasta los puntos de suministro, tal y como exige la norma. Se localizarn en la zona de descarga de camiones cisterna 2 extintores sobre carro de polvo equivalente ABC de 50 Kg con eficiencia 610B. La norma slo exige localizar uno en dicha zona pero se considera oportuno poner dos debido a que no supone molestia y s un aadido a la seguridad de una zona potencialmente conflictiva.
Memoria-Descripcin
74
Los extintores porttiles debern ser sometidos a revisin peridica para asegurar su correcto funcionamiento cuando sea requerido. Estas revisiones corrern a cargo de la empresa proveedora de los equipos.
8.3.2 Red de agua La instalacin llevar un sistema de proteccin contra incendios adicional, compuesto por un tanque de agua de 50 m3, que se conectar mediante tuberas visibles a una serie de monitores disparadores de agua, estratgicamente colocados.
8.3.3 Alarma Se colocarn puestos de accionamiento manual de alarma en cada pilar de la marquesina, de manera que se posibilite el rpido accionamiento de la misma ante cualquier emergencia que se produzca en la zona de carga. Adems se vigilar la zona de carga de forma continua desde la sala de control por medio de un circuito cerrado de televisin. Se establecer alarma acstica perfectamente audible en toda la zona, tal y como exige la norma.
8.3.4 Estabilidad ante el fuego Los pilares de la marquesina tendrn una estabilidad ante el fuego EF-180 como mnimo por considerarse soportes o apoyos crticos. La proteccin de los soportes contra el fuego se realizar con material resistente a la accin mecnica de los chorros de agua contra incendios.
Memoria-Descripcin
75
8.4 Sealizacin Un factor importante tanto en la prevencin como en la extincin de incendios es la sealizacin. En lugar visible se expondrn carteles anunciadores en los que se indique:
Prohibido fumar o encender fuego Prohibido repostar con la luces encendidas o con el motor
Memoria-Clculos
Captulo 2 CLCULOS
1 Normativa
Para llevar a cabo los clculos de cargas se emplear el Cdigo Tcnico de la Edificacin corregido en Marzo de 2006.
2 Software de clculo
Los clculos estructurales se efectuarn mediante el software CYPE 2009.
3 Cargas
3.1 Sobrecarga de uso Se considera sobrecarga de uso al peso de todos los objetos que puedan encontrarse sobre el elemento por razn de uso: personas, muebles, materiales, etc. Los valores de la sobrecarga se obtendrn de la tabla de la Figura 3.1:
Suso = 100 Kg m2
3.1.1 Edificio El valor de sobrecarga ser el correspondiente a azotea accesible para observacin.
Suso = 100 Kg m2
Memoria-Clculos
Tabla 3. 1
3.1.2 Marquesina El valor de sobrecarga comprender el correspondiente a azotea accesible para conservacin. 3.1.3 Monoposte No se consideran sobrecargas de uso. 3.2 Sobrecarga de nieve Se considera sobrecarga de nieve al peso de la nieve que pueda acumularse sobre la superficie en las condiciones climatolgicas ms desfavorables. Se emplearn los datos de la Tabla 3.2:
Memoria-Clculos
Tabla 3. 2
3.2.1 Edificio Tomando la altitud topogrfica de Valladolid (698 m) e introduciendo dicho valor en la tabla 3.2 se obtiene la sobrecarga de nieve.
Snieve = 80 Kg m2
3.2.2 Marquesina Mismo valor que en el caso del edificio. 3.2.3 Monoposte No se considera sobrecarga de nieve. 3.3 Acciones del viento La presin dinmica que se considerar en el clculo de los elementos estructurales, funcin de la altura de su coronacin y de su situacin topogrfica, se da en la Figura 3.3.
Tabla 3. 3
El viento produce sobre cada elemento superficial orientado tanto a barlovento como a sotavento, una sobrecarga p (kg/m2) en la direccin de
Memoria-Clculos
p= cw
donde w es la presin dinmica del viento y c el coeficiente elico, positivo para presin o negativo para succin, que depende de la configuracin de la construccin, de la posicin del elemento y el ngulo de incidencia del viento en la superficie (Ver Figura 3.4).
Tabla 3. 4
3.3.1 Edificio Por ser su altura mxima menor de 10 m y al estar localizado en una situacin topogrfica normal, la presin dinmica tomar el siguiente valor:
w = 50 kg m2
El viento predominante en Valladolid es Noroeste con una velocidad media de 15 m/s. El lado ms permeable del edificio es la cara Sureste por lo que el ngulo de incidencia es aproximadamente igual a 10. De ah se obtiene:
Memoria-Clculos
c 3 = 0 , c 4 = 0,8
3.3.2 Marquesina No hay superficie que soporte la presin dinmica del viento por lo que no se tiene en cuenta.
3.3.3 Monoposte Por ser su altura de coronacin 20 m y estando localizado en una situacin topogrfica normal, la presin dinmica tomar el siguiente valor:
w = 75 kg m2
c3 = 0 , c4 = 0
3.4 Acciones ssmicas La provincia de Valladolid se encuentra en una zona de sismicidad reducida con grado de intensidad IV (ver Figura 3.1). Por lo tanto no es preceptiva su consideracin.
Figura 3. 1
Memoria-Clculos
3.5 Peso propio El peso de las estructuras ser tenido en cuenta por el propio programa de clculo.
4 Resultados
4.1 Marquesina 4.1.1 Barras P1, P2:
Cargas puntuales, uniformes, en faja y momentos puntuales: 'P1' es el valor de la carga. 'P2' no se utiliza. Cargas trapezoidales: 'P1' es el valor de la carga en el punto donde comienza (L1) y 'P2' es el valor de la carga en el punto donde termina (L2). Cargas triangulares: 'P1' es el valor mximo de la carga. 'P2' no se utiliza. Incrementos de temperatura: 'P1' y 'P2' son los valores de la temperatura en las caras exteriores o paramentos de la pieza. La orientacin de la variacin del incremento de temperatura sobre la seccin transversal depender de la direccin seleccionada.
L1, L2:
Cargas y momentos puntuales: 'L1' es la distancia entre el nudo inicial de la barra y la posicin donde se aplica la carga. 'L2' no se utiliza. Cargas trapezoidales, en faja, y triangulares: 'L1' es la distancia entre el nudo inicial de la barra y la posicin donde comienza la carga, 'L2' es la distancia entre el nudo inicial de la barra y la posicin donde termina la carga.
Unidades:
Cargas puntuales: Tn Momentos puntuales: Tnm. Cargas uniformes, en faja, triangulares y trapezoidales: Tn/m. Incrementos de temperatura: C.
Memoria-Clculos
Barras Valores Barra N1/N2 N3/N4 Hiptesis Carga permanente Carga permanente Tipo Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Faja Uniforme Faja P1 0.103 0.103 0.066 0.016 0.166 0.004 0.473 0.028 0.000 0.029 0.181 0.124 0.095 0.266 0.302 0.195 0.112 0.056 0.112 0.066 0.016 0.016 0.166 0.029 0.181 0.101 0.124 0.124 0.095 0.266 0.195 0.112 0.112 0.056 0.056 0.112 0.112 0.066 0.016 0.181 0.124 0.473 0.004 0.166 0.029 0.000 0.028 0.095 0.266 0.302 0.195 0.112 P2 Posicin L1 (m) L2 (m) Ejes Globales Globales Globales Direccin X 0.000 0.000 0.000 0.000 Y Z
N2/N31 Carga permanente N2/N31 Carga permanente N2/N31 V1(0) N2/N31 V1(0) N2/N31 V1(0) N2/N31 V2(0) N2/N31 V2(0) N2/N31 V2(0) N2/N31 V1(180) N2/N31 V2(180) N2/N31 V(90) N2/N31 V(90) N2/N31 V(90) N2/N31 V(270) N2/N31 N1 N2/N31 N2 N2/N31 N3 N31/N5 Carga permanente N31/N5 Carga permanente N31/N5 Carga permanente N31/N5 V1(0) N31/N5 V2(0) N31/N5 V1(180) N31/N5 V1(180) N31/N5 V2(180) N31/N5 V2(180) N31/N5 V(90) N31/N5 V(90) N31/N5 V(270) N31/N5 N1 N31/N5 N1 N31/N5 N2 N31/N5 N2 N31/N5 N3 N31/N5 N3 N4/N33 Carga permanente N4/N33 Carga permanente N4/N33 V1(0) N4/N33 V2(0) N4/N33 V1(180) N4/N33 V1(180) N4/N33 V1(180) N4/N33 V2(180) N4/N33 V2(180) N4/N33 V2(180) N4/N33 V(90) N4/N33 V(90) N4/N33 V(90) N4/N33 V(270) N4/N33 N1
0.000 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.158 -0.987 0.158 -0.987 0.158 -0.987
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
5.064 6.329 Globales 0.000 5.064 Globales Globales 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 2.279 Globales 2.279 6.329 Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987 0.987
0.000 4.304 Globales 4.304 6.329 Globales 4.304 6.329 Globales 0.000 4.304 Globales Globales Globales Globales
2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales Globales 0.000 6.329 Globales
Globales -0.000 0.158 Globales -0.000 0.158 0.000 0.000 0.000 0.158 0.158 0.158
0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales Globales 5.064 6.329 Globales 0.000 5.064 Globales Globales 0.000 6.329 Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987
0.000 -1.000
Memoria-Clculos
N4/N33 N2 N4/N33 N3 N33/N5 Carga permanente N33/N5 Carga permanente N33/N5 Carga permanente N33/N5 V1(0) N33/N5 V1(0) N33/N5 V2(0) N33/N5 V2(0) N33/N5 V1(180) N33/N5 V2(180) N33/N5 V(90) N33/N5 V(90) N33/N5 V(270) N33/N5 N1 N33/N5 N1 N33/N5 N2 N33/N5 N2 N33/N5 N3 N33/N5 N3 N6/N7 N8/N9 Carga permanente Carga permanente Faja Faja Uniforme Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Uniforme 0.112 0.056 0.066 0.016 0.016 0.101 0.181 0.124 0.124 0.166 0.029 0.095 0.266 0.195 0.112 0.112 0.112 0.112 0.056 0.056 0.103 0.103 0.066 0.033 0.333 0.434 0.381 0.023 0.034 0.057 0.361 0.247 0.430 0.058 0.066 0.390 0.224 0.112 0.224 0.066 0.033 0.333 0.057 0.203 0.361 0.247 0.247 0.058 0.430 0.390 0.224 0.112 0.224 0.066 0.033 0.361 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 2.279 Globales 2.279 6.329 Globales 4.304 6.329 Globales 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158 4.304 6.329 Globales Globales Globales Globales Globales Globales 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158 0.158
2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
N7/N35 Carga permanente N7/N35 Carga permanente N7/N35 V1(0) N7/N35 V1(0) N7/N35 V1(0) N7/N35 V2(0) N7/N35 V2(0) N7/N35 V2(0) N7/N35 V1(180) N7/N35 V2(180) N7/N35 V(90) N7/N35 V(90) N7/N35 V(90) N7/N35 V(270) N7/N35 N1 N7/N35 N2 N7/N35 N3 N35/N10 Carga permanente N35/N10 Carga permanente N35/N10 V1(0) N35/N10 V2(0) N35/N10 V1(180) N35/N10 V1(180) N35/N10 V2(180) N35/N10 V2(180) N35/N10 V(90) N35/N10 V(90) N35/N10 V(270) N35/N10 N1 N35/N10 N2 N35/N10 N3 N9/N41 Carga permanente N9/N41 Carga permanente N9/N41 V1(0)
0.000 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.158 -0.987 0.158 -0.987 0.158 -0.987
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
5.064 6.329 Globales 0.000 5.064 Globales Globales 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales Globales Globales 0.000 6.329 Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987
4.304 6.329 Globales 0.000 4.304 Globales 4.304 6.329 Globales 0.000 4.304 Globales Globales Globales Globales
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales
Memoria-Clculos
N9/N41 V2(0) N9/N41 V1(180) N9/N41 V1(180) N9/N41 V1(180) N9/N41 V2(180) N9/N41 V2(180) N9/N41 V2(180) N9/N41 V(90) N9/N41 V(90) N9/N41 V(90) N9/N41 V(270) N9/N41 N1 N9/N41 N2 N9/N41 N3 N41/N10 Carga permanente N41/N10 Carga permanente N41/N10 V1(0) N41/N10 V1(0) N41/N10 V2(0) N41/N10 V2(0) N41/N10 V1(180) N41/N10 V2(180) N41/N10 V(90) N41/N10 V(90) N41/N10 V(270) N41/N10 N1 N41/N10 N2 N41/N10 N3 N11/N12 Carga permanente N13/N14 Carga permanente N12/N38 Carga permanente N12/N38 Carga permanente N12/N38 V1(0) N12/N38 V1(0) N12/N38 V2(0) N12/N38 V2(0) N12/N38 V1(180) N12/N38 V2(180) N12/N38 V(90) N12/N38 V(90) N12/N38 V(270) N12/N38 V(270) N12/N38 N1 N12/N38 N2 N12/N38 N3 N38/N15 Carga permanente N38/N15 Carga permanente N38/N15 V1(0) N38/N15 V2(0) N38/N15 V1(180) N38/N15 V1(180) N38/N15 V2(180) N38/N15 V2(180) N38/N15 V(90) N38/N15 V(90) N38/N15 V(270) Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme 0.247 0.381 0.434 0.333 0.057 0.034 0.023 0.430 0.058 0.066 0.390 0.224 0.224 0.112 0.066 0.033 0.203 0.361 0.247 0.247 0.333 0.057 0.430 0.058 0.390 0.224 0.224 0.112 0.103 0.103 0.066 0.033 0.722 0.333 0.057 0.057 0.361 0.247 0.143 0.291 0.005 0.386 0.224 0.112 0.224 0.066 0.033 0.333 0.057 0.361 0.203 0.247 0.247 0.143 0.291 0.005 Globales -0.000 0.158 0.000 0.000 0.000 0.158 0.158 0.158 0.987 0.987 0.987 0.987
0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales Globales 5.064 6.329 Globales 0.000 5.064 Globales Globales 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales 4.304 6.329 Globales 4.304 6.329 Globales Globales Globales Globales Globales Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 0.158 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
0.000 6.329 Globales 0.000 2.025 Globales 2.025 6.329 Globales 0.000 2.025 Globales 2.025 6.329 Globales Globales Globales Globales Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.158 -0.987 0.158 -0.987
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales Globales Globales 0.000 6.329 Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987
0.000 4.304 Globales 4.304 6.329 Globales 4.304 6.329 Globales 0.000 4.304 Globales Globales Globales Globales
Memoria-Clculos
N38/N15 V(270) N38/N15 N1 N38/N15 N2 N38/N15 N3 N14/N40 Carga permanente N14/N40 Carga permanente N14/N40 V1(0) N14/N40 V2(0) N14/N40 V1(180) N14/N40 V1(180) N14/N40 V2(180) N14/N40 V2(180) N14/N40 V(90) N14/N40 V(90) N14/N40 V(270) N14/N40 V(270) N14/N40 N1 N14/N40 N2 N14/N40 N3 N40/N15 Carga permanente N40/N15 Carga permanente N40/N15 V1(0) N40/N15 V1(0) N40/N15 V2(0) N40/N15 V2(0) N40/N15 V1(180) N40/N15 V2(180) N40/N15 V(90) N40/N15 V(90) N40/N15 V(270) N40/N15 V(270) N40/N15 N1 N40/N15 N2 N40/N15 N3 N16/N17 Carga permanente N18/N19 Carga permanente N17/N37 Carga permanente N17/N37 Carga permanente N17/N37 V1(0) N17/N37 V1(0) N17/N37 V2(0) N17/N37 V2(0) N17/N37 V1(180) N17/N37 V2(180) N17/N37 V(90) N17/N37 V(90) N17/N37 V(270) N17/N37 V(270) N17/N37 N1 N17/N37 N2 N17/N37 N3 N37/N20 Carga permanente N37/N20 Carga permanente N37/N20 Carga permanente N37/N20 V1(0) N37/N20 V2(0) Uniforme Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Faja Uniforme Uniforme 0.386 0.224 0.112 0.224 0.066 0.033 0.361 0.247 0.722 0.333 0.057 0.057 0.143 0.291 0.005 0.386 0.224 0.224 0.112 0.066 0.033 0.361 0.203 0.247 0.247 0.333 0.057 0.143 0.291 0.005 0.386 0.224 0.224 0.112 0.103 0.103 0.066 0.033 0.722 0.333 0.057 0.057 0.361 0.247 0.386 0.005 0.291 0.143 0.224 0.112 0.224 0.066 0.033 0.033 0.333 0.057 Globales 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987
10
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales
Globales -0.000 0.158 Globales -0.000 0.158 0.000 0.000 0.158 0.158
0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales Globales Globales Globales Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales 4.304 6.329 Globales 4.304 6.329 Globales Globales Globales Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.158 0.158 0.158 0.158 0.158 0.158 0.158
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
0.000 6.329 Globales 0.000 2.025 Globales 2.025 6.329 Globales 0.000 2.025 Globales 2.025 6.329 Globales Globales Globales Globales Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.158 -0.987 0.158 -0.987
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 3.519 Globales 3.519 6.329 Globales Globales Globales
Memoria-Clculos
N37/N20 V1(180) N37/N20 V1(180) N37/N20 V2(180) N37/N20 V2(180) N37/N20 V(90) N37/N20 V(90) N37/N20 V(270) N37/N20 V(270) N37/N20 N1 N37/N20 N1 N37/N20 N2 N37/N20 N2 N37/N20 N3 N37/N20 N3 N19/N36 Carga permanente N19/N36 Carga permanente N19/N36 V1(0) N19/N36 V2(0) N19/N36 V1(180) N19/N36 V1(180) N19/N36 V2(180) N19/N36 V2(180) N19/N36 V(90) N19/N36 V(90) N19/N36 V(270) N19/N36 V(270) N19/N36 N1 N19/N36 N2 N19/N36 N3 N36/N20 Carga permanente N36/N20 Carga permanente N36/N20 V1(0) N36/N20 V1(0) N36/N20 V2(0) N36/N20 V2(0) N36/N20 V1(180) N36/N20 V2(180) N36/N20 V(90) N36/N20 V(90) N36/N20 V(270) N36/N20 V(270) N36/N20 N1 N36/N20 N2 N36/N20 N3 N21/N22 Carga permanente N23/N24 Carga permanente N22/N39 Carga permanente N22/N39 Carga permanente N22/N39 Carga permanente N22/N39 V1(0) N22/N39 V1(0) N22/N39 V1(0) N22/N39 V2(0) N22/N39 V2(0) N22/N39 V2(0) N22/N39 V1(180) Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Faja Faja Uniforme 0.361 0.203 0.247 0.247 0.005 0.386 0.291 0.143 0.224 0.224 0.112 0.112 0.224 0.224 0.066 0.033 0.361 0.247 0.722 0.333 0.057 0.057 0.386 0.005 0.291 0.143 0.224 0.224 0.112 0.066 0.033 0.361 0.203 0.247 0.247 0.333 0.057 0.386 0.005 0.291 0.143 0.224 0.224 0.112 0.103 0.103 0.066 0.033 0.033 0.381 0.434 0.333 0.057 0.023 0.034 0.361 0.000 4.304 Globales 4.304 6.329 Globales 0.000 4.304 Globales 4.304 6.329 Globales Globales Globales Globales Globales 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987
11
3.519 6.329 Globales 0.000 3.519 Globales 0.000 3.519 Globales 3.519 6.329 Globales 0.000 3.519 Globales 3.519 6.329 Globales Globales 0.000 6.329 Globales
Globales -0.000 0.158 Globales -0.000 0.158 0.000 0.000 0.158 0.158
0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales Globales Globales Globales Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales 4.304 6.329 Globales 4.304 6.329 Globales Globales Globales Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.158 0.158 0.158 0.158 0.158 0.158 0.158
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
0.000 4.030 Globales 4.030 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.158 -0.987 0.158 -0.987 0.158 -0.987
Memoria-Clculos
N22/N39 V2(180) N22/N39 V(90) N22/N39 V(270) N22/N39 V(270) N22/N39 V(270) N22/N39 N1 N22/N39 N1 N22/N39 N2 N22/N39 N2 N22/N39 N3 N22/N39 N3 N39/N25 Carga permanente N39/N25 Carga permanente N39/N25 V1(0) N39/N25 V2(0) N39/N25 V1(180) N39/N25 V1(180) N39/N25 V2(180) N39/N25 V2(180) N39/N25 V(90) N39/N25 V(270) N39/N25 V(270) N39/N25 N1 N39/N25 N2 N39/N25 N3 N24/N42 Carga permanente N24/N42 Carga permanente N24/N42 V1(0) N24/N42 V2(0) N24/N42 V1(180) N24/N42 V1(180) N24/N42 V1(180) N24/N42 V2(180) N24/N42 V2(180) N24/N42 V2(180) N24/N42 V(90) N24/N42 V(270) N24/N42 V(270) N24/N42 V(270) N24/N42 N1 N24/N42 N2 N24/N42 N3 N42/N25 Carga permanente N42/N25 Carga permanente N42/N25 V1(0) N42/N25 V1(0) N42/N25 V2(0) N42/N25 V2(0) N42/N25 V1(180) N42/N25 V2(180) N42/N25 V(90) N42/N25 V(270) N42/N25 V(270) N42/N25 N1 N42/N25 N2 N42/N25 N3 Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja 0.247 0.390 0.430 0.058 0.066 0.224 0.224 0.112 0.112 0.224 0.224 0.066 0.033 0.333 0.057 0.203 0.361 0.247 0.247 0.390 0.430 0.058 0.224 0.112 0.224 0.066 0.033 0.361 0.247 0.434 0.381 0.333 0.057 0.023 0.034 0.390 0.066 0.058 0.430 0.224 0.224 0.112 0.066 0.033 0.203 0.361 0.247 0.247 0.333 0.057 0.390 0.058 0.430 0.224 0.224 0.112 Globales Globales Globales 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
12
5.064 6.329 Globales -0.000 -0.158 0.987 0.000 5.064 Globales 4.030 6.329 Globales 0.000 4.030 Globales 0.000 4.030 Globales 4.030 6.329 Globales 4.030 6.329 Globales 0.000 4.030 Globales Globales Globales Globales 0.000 6.329 Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987 0.987
4.304 6.329 Globales 0.000 4.304 Globales 4.304 6.329 Globales 0.000 4.304 Globales Globales Globales
0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales
Globales -0.000 0.158 Globales -0.000 0.158 0.000 0.000 0.000 0.158 0.158 0.158
0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales Globales 0.000 5.064 Globales Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.987 0.987 0.987 0.987
5.064 6.329 Globales -0.000 0.158 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 6.329 Globales 4.304 6.329 Globales 4.304 6.329 Globales Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 0.158 0.158 0.158 0.158 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158
Memoria-Clculos
N26/N27 Carga permanente N28/N29 Carga permanente N27/N32 Carga permanente N27/N32 Carga permanente N27/N32 V1(0) N27/N32 V1(0) N27/N32 V1(0) N27/N32 V2(0) N27/N32 V2(0) N27/N32 V2(0) N27/N32 V1(180) N27/N32 V2(180) N27/N32 V(90) N27/N32 V(270) N27/N32 V(270) N27/N32 V(270) N27/N32 N1 N27/N32 N2 N27/N32 N3 N32/N30 Carga permanente N32/N30 Carga permanente N32/N30 Carga permanente N32/N30 V1(0) N32/N30 V2(0) N32/N30 V1(180) N32/N30 V1(180) N32/N30 V2(180) N32/N30 V2(180) N32/N30 V(90) N32/N30 V(270) N32/N30 V(270) N32/N30 N1 N32/N30 N1 N32/N30 N2 N32/N30 N2 N32/N30 N3 N32/N30 N3 N29/N34 Carga permanente N29/N34 Carga permanente N29/N34 V1(0) N29/N34 V2(0) N29/N34 V1(180) N29/N34 V1(180) N29/N34 V1(180) N29/N34 V2(180) N29/N34 V2(180) N29/N34 V2(180) N29/N34 V(90) N29/N34 V(270) N29/N34 V(270) N29/N34 V(270) N29/N34 N1 N29/N34 N2 N29/N34 N3 N34/N30 Carga permanente N34/N30 Carga permanente Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja Faja Uniforme Uniforme Faja Faja Faja Faja Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Faja Faja Uniforme Faja Faja Faja Uniforme Faja 0.103 0.103 0.066 0.016 0.166 0.473 0.004 0.000 0.028 0.029 0.181 0.124 0.195 0.302 0.266 0.095 0.112 0.056 0.112 0.066 0.016 0.016 0.166 0.029 0.181 0.101 0.124 0.124 0.195 0.266 0.095 0.112 0.112 0.056 0.056 0.112 0.112 0.066 0.016 0.181 0.124 0.004 0.473 0.166 0.029 0.028 0.000 0.195 0.302 0.266 0.095 0.112 0.112 0.056 0.066 0.016 Globales Globales Globales 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
13
0.000 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.158 -0.987 0.158 -0.987 0.158 -0.987
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.158 -0.987
5.064 6.329 Globales -0.000 -0.158 0.987 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 2.279 Globales 2.279 6.329 Globales Globales Globales
0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 -0.158 0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.987 0.987 0.987 0.987 0.987
0.000 4.304 Globales 4.304 6.329 Globales 4.304 6.329 Globales 0.000 4.304 Globales Globales Globales
2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales Globales 0.000 6.329 Globales
Globales -0.000 0.158 Globales -0.000 0.158 0.000 0.000 0.000 0.158 0.158 0.158
0.000 2.025 Globales 0.000 2.025 Globales 2.025 6.329 Globales 2.025 6.329 Globales 0.000 2.025 Globales 0.000 2.025 Globales Globales 0.000 5.064 Globales Globales
0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 -0.158 -0.987 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.987 0.987 0.987 0.987
5.064 6.329 Globales -0.000 0.158 0.000 6.329 Globales 0.000 6.329 Globales 0.000 6.329 Globales Globales 0.000 2.279 Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
Memoria-Clculos
N34/N30 Carga permanente N34/N30 V1(0) N34/N30 V1(0) N34/N30 V2(0) N34/N30 V2(0) N34/N30 V1(180) N34/N30 V2(180) N34/N30 V(90) N34/N30 V(270) N34/N30 V(270) N34/N30 N1 N34/N30 N1 N34/N30 N2 N34/N30 N2 N34/N30 N3 N34/N30 N3 N31/N35 Carga permanente N35/N38 Carga permanente N38/N37 Carga permanente N37/N39 Carga permanente N39/N32 Carga permanente N33/N41 Carga permanente N41/N40 Carga permanente N40/N36 Carga permanente N36/N42 Carga permanente N42/N34 Carga permanente N5/N10 Carga permanente N10/N15 Carga permanente N15/N20 Carga permanente N20/N25 Carga permanente N25/N30 Carga permanente N2/N7 Carga permanente N12/N17 Carga permanente N22/N27 Carga permanente N4/N9 Carga permanente N14/N19 Carga permanente N24/N29 Carga permanente Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Faja Faja Faja Faja Faja Faja Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme Uniforme 0.016 0.101 0.181 0.124 0.124 0.166 0.029 0.195 0.266 0.095 0.112 0.112 0.112 0.112 0.056 0.056 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 0.036 2.279 6.329 Globales 4.304 6.329 Globales 0.000 0.000 0.000 -1.000 0.158 0.987 0.987 0.987 0.987 0.987 0.987 0.987 0.987
14
0.000 4.304 Globales -0.000 0.158 0.000 4.304 Globales -0.000 0.158 4.304 6.329 Globales Globales Globales Globales Globales 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.158 0.158 0.158 0.158
2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales 2.279 6.329 Globales 0.000 2.279 Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales Globales
0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000 0.000 -1.000
Todas las vigas horizontales son perfiles IPE 270, los pilares HEB 280 y los dinteles de los prticos IPE 400. Los tirantes sern redondos de 10 cm de dimetro.
4.1.2 Nudos
En cuanto a las uniones, se llevarn a cabo siguiendo los siguientes esquemas constructivos.
Memoria-Clculos
15
Nudos (16): N1, N2, N3, N4, N6, N7, N8, N9, N21, N22, N23, N24, N26, N27, N28 y N29.
Memoria-Clculos
16
Memoria-Clculos
17
Nudos (40): N2, N4, N7, N9, 2xN10, N12, N14, 2xN15, N17, N19, 2xN20, N22, N24, 2xN25, N27, N29, N31, N32, N33, N34, 2xN35, 2xN36, 2xN37, 2xN38, 2xN39, 2xN40, 2xN41 y 2xN42.
Memoria-Clculos
18
Nudos (8): N6, N8, N11, N13, N16, N18, N21 y N23
4.2 Monoposte El monoposte estar formado por un pilar HEB 160 empotrado con cimentacin de zapata. Las caractersticas generales de ambos se adjuntan en las tablas correspondientes. 4.2.1 Pilar Ni: Nudo inicial Nf: Nudo final xy: Coeficiente de pandeo en el plano 'XY' xz: Coeficiente de pandeo en el plano 'XZ'
Memoria-Clculos
19
LbSup.: Separacin entre arriostramientos del ala superior LbInf.: Separacin entre arriostramientos del ala inferior
Descripcin Barra Pieza Longitud xy xz LbSup. LbInf. Material Perfil(Serie) (m) (m) (Ni/Nf) (Ni/Nf) (m) N1/N2 N1/N2 Acero (S450) HEB-160 (HEB) 8.00 1.00 1.00 -
Caractersticas mecnicas A Iyy Izz Ixx Tipo Material Descripcin (cm) (cm4) (cm4) (cm4) 1 Acero (S450) HEB-160, Perfil simple, (HEB) 54.30 2492.00 889.00 33.20
4.2.2 Cimentacin
Referencias N1
Geometra Armado Zapata cuadrada X: 316 c/ 25 Ancho: 75.0 cm Y: 316 c/ 25 Canto: 40.0 cm
Referencia: N1 B 400 S, CN Nombre de armado 16 3x0.95 Parrilla inferior - Armado X Longitud (m) Peso (kg) 3x1.50 Parrilla inferior - Armado Y Longitud (m) 3x0.95 Peso (kg) 3x1.50 Totales Longitud (m) 5.70 Peso (kg) 9.00 Total con mermas Longitud (m) 6.27 (10.00%) Peso (kg) 9.90
Memoria-Estudio Econmico
1.2 Contexto Se ha fijado el valor residual de la instalacin en 135.000 euros. El presupuesto final de la instalacin es de 445.888,62 euros (Ver Parte IV). Para simplificar se considerar una depreciacin lineal del modelo con lo que la amortizacin anual resultar: Amortizacin = Valori Valorf
20 = 15.544,43 euros
Cada ao se efectuar el pago del impuesto de sociedades, que est establecido en un 33% del beneficio neto anual. El coste de oportunidad quedar fijado en un 15% y se contabilizar un gasto aproximado de 50.000 euros para mantenimiento y reparaciones.
Memoria-Estudio Econmico
1.3 Flujos de caja 1.3.1 Ingresos Considerando los siguientes consumos en la zona de influencia del gasocentro: 3.450.000 l/ao de gasleo B, 4.150.000 l/ao de gasleo C y 500.000 l/ao de biodiesel. Se estima que el gasocentro puede satisfacer alrededor del 35% de la demanda con un precio por litro de gasleo B y C de 1,0458 euros/l y de biodiesel de 0,97 euros/l de donde e obtendr un beneficio estimado de 0,15 euros por litro:
VentasGasleoB 3.450.000 0,35 1,0458 = 1.262.803,5 VentasGasleoC 4.150.000 0,35 1,0458 = 1.519.024,5 VentasBiodiesel 500.000 0,35 0,97 = 169.750
1.3.2 Gastos Los gastos de la instalacin expresados en euros son los siguientes:
Mantenimiento Sueldos Agua, electricidad y telfono Otros gastos Gastos totales 30.000 33.000 55.000 9.000 127.000
1.4 Resultados La inversin necesaria es la suma del presupuesto de materiales ms el coste de ingeniera, haciendo un total de 545.888,62 euros.
Memoria-Estudio Econmico
Puesto que el VAN es mayor que 0 y el TIR es mayor que el 15%, la rentabilidad de la instalacin queda asegurada. No se ha contemplado la necesidad de pedir un prstamo pero con las cifras de rentabilidad obtenidas no habra problemas a la hora de conseguir crdito.
Memoria-Impacto Ambiental
3 Energa consumida
Se consume la energa suficiente para asegurar el correcto funcionamiento del sistema elctrico, tanto en red de fuerza como de alumbrado.
Memoria-Impacto Ambiental
Ser prcticamente nula por tratarse de gasleo. Emisiones de vehculos usuarios de la instalacin.
Slidos: Generados por la presencia de personas en la
sern enviadas a la red municipal. Aguas hidrocarburadas que sern enviadas a la red municipal tras su depuracin.
Memoria-Impacto Ambiental
el nivel del pavimento con envoltura de arena lavada e inerte, para la proteccin de aquel y a la distancia de edificaciones marcada por la normativa vigente.
Dotacin de boca de carga directa con cierre estanco y
electricidad.
Proteccin de los elementos de los aparatos surtidores, motor
Memoria-Impacto Ambiental
El principal tipo de contaminacin ambiental durante esta fase ser acstica motivada por el ruido de las obras.
Memoria-Impacto Ambiental
Fase de explotacin: En el diseo del gasocentro se ha procurado que no afecte negativamente al entorno. Excepto el monoposte ninguno de los elementos del gasocentro tiene mucha altura. Durante este fase por lo tanto la alteracin medioambiental es mnima. Fase de desmantelamiento: Se caracterizar por una alta contaminacin acstica, si bien se tomarn medidas necesarias para evitar otros tipos de
contaminacin. Se tratar con especial cuidado material de la instalacin mecnica del gasocentro para evitar contaminacin por filtracin de residuos hidrocarburados al suelo.
2 Obras
2.1 Trabajos previos a la realizacin de la obra Se proceder al vallado de la parcela con una malla de acero galvanizado de 2 cm de altura y postes de tubo galvanizado empotrados en el terreno. Se colocarn 2 tipos de puerta, para trnsito de vehculos y de peatones. En ellas se dispondrn las siguientes sealizaciones:
Prohibido aparcar
vehculos
Uso del casco obligatorio Prohibida la entrada a personas ajenas a la obra Balizas luminosas en la valla.
Tambin se instalar una caseta de aseo y se colocarn los cuadros generales de obra con sus correspondientes protecciones.
2.3 Estimacin de riesgos 2.3.1 Riesgos profesionales Unidades de construccin de obra civil:
Daos personales en accidentes no provocados. Atropellos por maquinaria y vehculos. Atrapamientos. Colisiones y vuelcos. Cadas a distinto nivel. Desprendimientos. Interferencias con lneas de alta tensin.
material.
Proyeccin de partculas a los ojos.
Riesgos elctricos:
Interferencias con lneas de alta tensin. Derivados de tiles elctricos.
Riesgo de incendios:
En oficinas, almacenes y en campo por voladuras.
2.4 Riesgos de dao a terceros Derivados de las voladuras por proyeccin de material sobre personas o bienes ajenos a las obras.
Los caminos atravesados por la obra suponen un riesgo debido a que circulan por ellos personas ajena a la misma.
visitantes.
Pantallas antipartculas. Pantallas de proteccin para soldadores. Gafas de montura universal para proteccin contra impactos. Mascarillas autofiltrantes y filtros mecnicos. Tapones para odos.
Tronco:
Mono de trabajo. Cinturones de seguridad anticada. Trajes impermeables. Mandiles de cuero. Cinturones antivibraciones.
Extremidades superiores:
Guantes de goma o neopreno para el trabajo con hormign. Guantes de cuero para descargas, maquinistas, etc. Manguitos y guantes para soldadores. Guantes y aislantes para electricistas. Aislamiento de seguridad en las herramientas usadas para el
trabajo elctrico.
Extremidades inferiores:
Botas impermeables. Botas de seguridad clase III. Botas aislantes para electricistas. Plantillas de proteccin para evitar el riesgo de perforacin. Polainas de cuero para soldadores.
3.2 Protecciones colectivas Proteccin contra incendios: Ver apartado 1. Excavacin: Se sealarn las excavaciones con cinta de balizamiento y seales indicativas de riesgo de cadas a distinto nivel. Estructura: Se usar mallazo para cubrir los huecos interiores, en los tiros de escalera se emplearn barandillas rgidas y se instalarn escaleras provisionales a base de peldaos de obra. Andamiaje: Se usarn obligatoriamente cinturones de seguridad anticada y los andamios debern ser firmes y estar bien sujetos. Albailera: Se proceder a la instalacin de barandillas y rodapis cuando las plataformas de trabajo superen los 2 metros. Para la bajada de escombros se usar una tolva telescpica. Instalacin elctrica: Se instalarn tomas de tierra, interruptores diferenciales y conductores de proteccin. Maquinaria: Se construirn prticos de proteccin.
3.3 Formacin Previamente al inicio de la obras y al inicio de la explotacin de la instalacin se formar a todo el personal de forma que todo trabajador
conozca los riesgos que conlleva su trabajo, la forma de aminorarlos y las acciones de debe realizar en caso de accidente. En todo grupo de trabajo debe haber por lo menos una persona que formada en materia de socorrismo de primeros auxilios, de forma que sean ellos los que acten si fuese necesario hasta que lleguen las autoridades sanitarias. A disposicin de los trabajadores y en lugar visible se situarn panfletos informativos sobre normas bsicas de seguridad en las obras.
3.4 Medicina preventiva y primeros auxilios Existir un botiqun completamente equipado en lugar visible y sealizado a disposicin de toda persona que lo requiera. Este botiqun dispondr de todos los elementos necesarios para los primeros auxilios. Junto al botiqun se colocar un listado con las principales direcciones y telfonos referentes a centros mdicos, ambulancias, bomberos, etc. ms cercanas a la zona de forma que pueda actuar rpida y eficazmente. En obra existirn vehculos preparados para el traslado de accidentados de forma cmoda y segura. Antes de empezar el trabajo se realizar a todas las personas que vayan a participar en l un reconocimiento mdico completo. La profundidad del estudio ser funcin del tipo de trabajo a realizar. Este reconocimiento tendr una frecuencia de un ao.
4 Servicios de prevencin
Son obligaciones de la empresa constructora el asesoramiento en materia de seguridad labora y la disponibilidad de un servicio mdico.
Se deber establecer un Comit de Seguridad e Higiene segn establece la Ordenanza Laboral de la Construccin o cuando lo solicite el Convenio Colectivo provincial. Se nombrar un vigilante de seguridad que vele por el cumplimiento de la normativa segn queda establecido en la Ordenanza General de Seguridad e Higiene en el Trabajo. En cuanto a las instalaciones, sern necesarias unas instalaciones para las actividades mdicas. Se dispondr de unas instalaciones que cumplan unos mnimos establecidos en cuestin de higiene y bienestar. Debe haber al menos un trabajador que se encargue de la limpieza y la conservacin de las instalaciones y otra persona para la reposicin de material sanitario. Se redactar un Plan de Seguridad e Higiene para las obras de las instalaciones y para el desarrollo de la actividad en la propia instalacin de consumo propio. Existir un libro de incidencias segn establece el artculo 13 del Real Decreto 1627/1997. El coordinador de las acciones en materia de seguridad e higiene podr hacer uso del mismo siempre que lo desee.
5.1 Protecciones personales Elemento Cascos Pantallas de seguridad Gafas Unidades 25 7 7 Precio unitario 2,16 9,24 11,09 Coste 54 64,68 77,63
7 7 25 7 25 7
5.2 Protecciones generales Elemento Seales Carteles de riesgo Cinta balizamiento Vallas Extintores de polvo Total Unidades 20 12 25 15 5 Precio unitario 27,72 6,16 1,17 27,72 61,6 Coste 554,4 73,92 29,25 415,8 308 1.381,37
5.3 Protecciones elctricas Elemento Instalacin de puesta a tierra Diferencial alta Unidades 1 1 Precio unitario 154,01 86,25 Coste 154,01 86,25
5.4 Elementos de higiene Elemento Caseta vestuario Caseta aseos Acometida agua Contenedores basura Limpieza y conservacin Total Unidades 2 2 1 5 1 Precio unitario 308,2 246,41 277,22 18,48 308,02 Coste 616,4 492,82 277,22 92,4 308,02 1.786,5
5.5 Medicina preventiva y primeros auxilios Elemento Botiqun Reconocimientos mdicos Total Unidades 4 25 Precio unitario 36,96 29,57 Coste 147,84 739,25 887,09
10
5.6 Resumen Elemento Protecciones personales Protecciones generales Protecciones elctricas Elementos de higiene Medicina Total Importe 969,12 1.381,37 351,15 1.786,5 887,09 5.375,23
El importe orientativo total de las medidas de Seguridad y Salud asciende a CINCO MIL TRESCIENTOS SETENTA Y CINCO EUROS CON 23 CNTIMOS.
BIBLIOGRAFA
Ministerio de Fomento, Norma NBE-AE-88: Acciones en la edificacin. Ministerio de Fomento, Norma NBE-AE-95: Estructuras de acero en la edificacin. Ministerio de Fomento, Norma NBE-CPI-96: Condiciones de proteccin contra incendios en los edificios. Reglamento de Instalaciones Petrolferas e instrucciones tcnicas complementarias MI-IP-03 y MI-IP-04. Ministerio de Industria y Energa, Reglamento Electrotcnico de Baja Tensin. Ministerio de Industria y Energa, Decreto 2949/1892 de 15 de Octubre: Reglamento de acometidas elctricas. Ministerio de Industria y Energa, Decreto de 12 de Marzo de 1954: Reglamento de verificaciones elctricas y regularidad en el suministro elctrico de energa. Direccin General de Carreteras, Norma 8.1.-I.C. Seales
verticales y Catlogos de seales de circulacin, Norma 8.3.-I.C. Sealizacin obras Ministerio Complementaria de Industria y de Energa, Instruccin de Tcnica
Reglamento
Instalaciones
Calefaccin,
Climatizacin y Agua Caliente Sanitaria. Ley de Prevencin de Riesgos Laborales 31/95 de 8 de Noviembre. Pgina Web www.mundopetroleo.com, con enlaces a los distintos fabricantes.
Parte II PLANOS
1 ndice de planos
1. Localizacin 2. Implantacin 3. Instalacin mecnica 4. reas clasificadas 5. Saneamiento 6. Proteccin contra incendios 7. Esquema elctrico 8. Edificio principal 9. Marquesina 10. Marquesina - Tensiones
1 Condiciones generales
1.1 Objeto En este pliego se definirn exhaustivamente las condiciones econmicas y generales que regirn durante la ejecucin y garanta de este proyecto. Este pliego de condiciones econmicas y generales se
complementar con las disposiciones que con carcter general se especifican en el apartado siguiente.
1.2 Forma de descripcin de las instalaciones Todos los datos sobre las instalaciones que abarca el presente proyecto: materiales, formas constructivas, dimensiones, etc., se
encuentran detallados en los planos y la memoria, anteriormente presentados, siendo definidos en este pliego la relacin de calidades de los materiales a utilizar as como la forma en que debe desarrollarse la obra y dems condiciones tcnico-administrativas. Aquellos puntos que no queden definidos o sobre los que puedan existir dudas en cuanto a su ejecucin, se discutirn y se llevarn a cabo siguiendo las orientaciones e instrucciones del ingeniero o facultativo en que delegue la Direccin de Obra. Lo mencionado en el Pliego de Condiciones y omitido en los planos o viceversa, habr de ser ejecutado como si estuviera en ambos
documentos. En caso de contradiccin entre los planos y el presente Pliego de Condiciones prevalecer lo escrito en este ltimo, salvo criterio en contra del Ingeniero Director. Las omisiones en planos y Pliego de Condiciones, las descripciones errneas de los detalles de la obra que sean manifiestamente indispensables para llevar a cabo el espritu o intencin expuesto en los planos y Pliego de Condiciones y lo que, por uso y costumbre deba ser realizado, no slo no eximen al contratista de la obligacin de ejecutar estos detalles de obra omitidos o errneamente descritos, sino que, por el contrario, debern ser ejecutado como si hubieran sido completa y correctamente especificados en los planos y el Pliego de Condiciones.
1.3 Documentacin complementaria Los siguientes documentos y disposiciones completarn este pliego siempre y cuando no lo contradigan:
Disposiciones vigentes sobre la Seguridad e Higiene en el trabajo. Ley de Contratos de Trabajo y disposiciones vigentes. Normas oficiales aplicables an no siendo de obligado cumplimiento. Cada una de las obras necesarias para la ejecucin de la instalacin se realizar bajo estricto cumplimiento de los Reglamentos de Seguridad y de las Normas Tcnicas de obligado cumplimiento para esta instalacin, ya sean de mbito europeo, nacional, autonmico o municipal, al igual que todas las que sean obligatorias y que se especifican a lo largo de la Memoria Descriptiva de este proyecto.
El presente pliego ser complementado por las condiciones econmicas que se puedan fijar en la Escritura del Contrato asumida por el propietario y contratista de la obra. Todas las condiciones de este Pliego estarn sujetas a las a las modificaciones que se realicen de forma expresa en la Escritura del Contrato anteriormente en la Escritura del Contrato anteriormente citada.
1.4 Interpretacin La potestad de interpretacin recae sobre el Ingeniero Director, cuyas funciones son:
Exigir al contratista el cumplimiento de las condiciones contractuales. Velar por la ejecucin de la obra y que sta se atenga a lo establecido en el proyecto o a las modificaciones autorizadas.
Resolver las cuestiones tcnicas que surjan en la ejecucin, condiciones de materiales, interpretacin de planos siempre que no modifique las condiciones establecidas en el contrato.
Asumir personalmente y bajo su entera responsabilidad en casos de urgencia o gravedad la direccin de determinadas operaciones.
Acreditar al contratista las obras realizadas. Participar en las recepciones y redactar las liquidaciones en las obras conforme a las reglas legales establecidas.
El contratista deber realizar todo lo necesario para la perfecta ejecucin de la obra aunque no se halle especificado en lo documentos del Proyecto o en el Pliego de Condiciones.
1.5 Calidades Todo material que no cumpla, al menos, con las condiciones de calidad especificadas en la Memoria del presente Proyecto no ser admitido. Por esto todo material, mquina, elemento y todo concepto en el que pueda ser definible una calidad, sta ser la especificada en el Proyecto, fijada por una marca comercial o por una especificacin concreta si no estuviera en el mercado a niveles de primera calidad. El material necesario en la ejecucin del proyecto y que no haya sido especificado en ningn documento de este Proyecto deber ser de primera calidad y en ningn caso es utilizar sin la supervisin y aprobacin del Ingeniero Director. ste posee a facultad de rechazarlo si lo considera oportuno al no reunir, a su juicio, las condiciones exigidas para conseguir debidamente el objeto que motivar su empleo. El Contratista no tendr derecho a reclamar por las condiciones que se le exijan a este material.
2 Condiciones legales
2.1 Condiciones generales El Contratista est obligado al cumplimiento de la reglamentacin del trabajo correspondiente, la contratacin del seguro obligatorio, subsidio familiar y de vejez, seguro de enfermedad y todas aquellas reglamentaciones de carcter social vigentes. En particular deber cumplir lo dispuesto en la norma UNE 24042, Contratacin de obras. Condiciones generales, siempre que no modifique el presente Pliego de Condiciones.
2.2 Condiciones facultativas legales Adems de lo especificado en el presente documento, sern de aplicacin las siguientes disposiciones:
Pliego de clusulas administrativas generales para la contratacin de obras aprobado por decreto 2850/70 de 31 de Diciembre
Legislacin vigente sobre seguridad e higiene en el trabajo. Reglamento de Instalaciones Petrolferas (R.D. 20/85 del 20 de Octubre de 1994).
Norma UNE 19-040-93: Tubos roscables de acero de uso general. Medidas y masas. Serie normal.
Norma UNE 20-322-86: Clasificacin de emplazamientos con riesgo de explosin debido a la presencia de gases, vapores y nieblas inflamables.
Norma UNE 20-324-93 (EN 60529:91; EN 60529/AC:93): Grados de Proteccin proporcionados por las envolventes (Cdigo 1P).
Norma UNE 20-432-82, Parte 1 (HI 405.1S1:1983): Ensayos de los cables elctricos sometidos al fuego . Ensayo de un conductor aislado o de un cable expuesto a una llama.
Norma UNE 20-432-1M-93, Parte 1 (HD 405.1S1:83/1M:92): Ensayos de los cables elctricos sometidos al fuego . Ensayo de un conductor aislado o de un cable expuesto a una llama.
Norma UNE 21-316-94, Parte 1 (HI 559.1S1:91; CEI 243-1:88MOD): Mtodos de ensayo para la determinacin de la rigidez dielctrica de los materiales aislantes slidos. Parte 1: Ensayos a frecuencias industriales.
Norma UNE 21-316-94, Parte 2 (HI 559.2S1:91; CEI 243-2:90MOD): Mtodos de ensayo para la determinacin de la rigidez dielctrica de
los
materiales
aislantes
slidos.
Parte
2:
Prescripciones
Norma UNE 21-818-89 (EN 50018:1977): Material elctrico para atmsferas potencialmente explosivas. Envolvente antideflagrante.
Norma UNE 21-818-2M-91 (EN 50018/A2:1982): Material elctrico para atmsferas potencialmente explosivas. Envolvente antideflagrante <D>.
Norma UNE 21-818-3M-91 (EN 50018/A3:1982): Material elctrico para atmsferas potencialmente explosivas. Envolvente antideflagrante <D>.
Norma UNE EN 10025-94 (En 10025:1990; EN 10025/A:93): Productos laminados en caliente, de acero no aleado, para construcciones metlicas de uso general. Condiciones tcnicas de suministro.
Norma UNE 36-559-92 (EN 10029:1991+10029/AC1:1991): Chapas de acero laminadas en caliente, de espesor igual o superior a 3 mm. Tolerancias dimensionales sobre la forma y sobre la masa.
Norma UNE EN 287-92, Parte 1 (EN 287-1:1992): Cualificacin de los soldadores. Soldeo por fusin. Parte 1: aceros.
Norma UNE EN 288-93, Parte 1 (EN 288-1:1992): Especificacin y cualificacin de procedimientos de soldeo para los materiales metlicos. Parte 1: Reglas generales para el soldeo por fusin.
2.3 Seguridad en el trabajo El Contratista est obligado a cumplir la Ordenanza General de Seguridad e Higiene en el trabajo, aprobado por Orden del 9-3-71 del Ministerio de Trabajo. Asimismo deber proveer cuanto fuere preciso para el
El personal de la contrata viene obligado a usar todos los dispositivos y medios de proteccin personal, herramientas y prendas de seguridad exigido para eliminar o reducir los riesgos profesionales, tales como casco, gafas, banqueta aislante, etc., pudiendo el Director de Obra suspender los trabajos si estima que el personal de la contrata est expuesto a peligros que son evitables. Mientras los operarios trabajen en circuitos o equipos de tensin, o incluso en la proximidad de los mismo, usarn ropa sin accesorios metlicos y evitarn el uso innecesario de objetos de metal, como metros, reglas, mangos de aceiteras, tiles limpiadores, etc. El Director de Obra podr exigir del contratista, ordenndolo por escrito, el cese en la obra de cualquier empleado u obrero que, por imprudencia temeraria, fuera capaz de producir accidentes que hicieran peligrar la integridad fsica del propio trabajador o de sus compaeros. El Director de Obra podr exigir del Contratista en cualquier momento, antes o despus de la iniciacin de los trabajos, que presente los documentos acreditativos de haber formalizado los requisitos de Seguridad Social, de todo tipo: afiliacin, accidente, enfermedad, etc., en la forma legalmente establecida.
2.4 Seguridad Pblica El Contratista deber tomar las precauciones mximas en todas las operaciones y uso de equipos, para proteger a las personas a las personas, animales y cosas de los peligros procedentes del trabajo, siendo de su cuenta las responsabilidades que por tales accidentes se deriven. El Contratista mantendr pliza de seguros que proteja
suficientemente a l y a sus empleados u obreros, frente a la responsabilidad por daos, responsabilidad civil, etc., en que uno y otro pudieran incurrir para el Contratista o para terceros, como consecuencia de la ejecucin de los trabajos.
2.5 Inspeccin y vigilancia de las obras La inspeccin y vigilancia de las obras corresponde al Ingeniero Director de las mismas y al personal tcnico a sus rdenes. El Ingeniero Director decidir sobre la interpretacin de planos y de las condiciones del presente documento siendo el nico autorizado para modificarlos. Asimismo podr vigilar todos los trabajos y materiales que se empleen, pudiendo rechazar lo que no cumplan las condiciones exigidas. El Ingeniero Director, o su representante, tendrn acceso a todas las partes de la obra, estando el contratista obligado a prestarle toda la informacin y ayuda necesaria para llevar a cabo una inspeccin completa y detallada. Se podr ordenar remocin y sustitucin, a expensas del contratista, de toda la obra o de todos los materiales usados sin la supervisin de la Direccin de Obra. El Contratista comunicar con antelacin suficiente los materiales que tenga intencin de utilizar, facilitando los medios necesarios para su inspeccin. El Ingeniero Director podr exigir que el Contratista retire de la obra cualquier empleado u operario por incompetencia, falta de subordinacin o que sea susceptible de cualquier otra objecin. El Ingeniero Director podr rechazar cualquier mquina o elemento que juzgue inadecuado y podr exigir los que razonablemente considere necesarios. Tanto el personal como la maquinaria y restantes medios quedarn afectos a la obra y en ningn caso el Contratista podr retirarlos sin autorizacin expresa del Ingeniero Director. El Contratista aumentar los medios siempre que el Ingeniero Director lo estime necesario para el adecuado desarrollo de las obras en el plazo ofrecido.
El Contratista podr exigir que todas las rdenes del Ingeniero Director le sean dadas por escrito y firmadas con arreglo a las normas habituales en estas relaciones tcnico-administrativas. Se llevar un libro de rdenes, con hojas numeradas, en el que se expondrn, por duplicado, las que se dicten en el curso de las obras y sern firmadas por ambas partes, entregndose una copia firmada al contratista. Adems de la inspeccin y vigilancia de las obras efectuadas por parte del Ingeniero Director de las mismas y el personal tcnico a sus rdenes, si ste lo considera necesario, existir un vigilante de la ejecucin material durante la jornada legal, siendo de cuenta del Contratista el abono de su sueldo. Si el Contratista conviniese establecer ms de un turno de trabajo por da laborable, deber solicitarlo al Ingeniero Director y, si le fuera concedido, regirn las mismas reglas anteriores para el nombramiento y abono del sueldo del vigilante para el turno o turnos que se autoricen. Si antes de comenzar las obras, o durante su construccin, el Ingeniero Director acordase introducir en el proyecto modificaciones que impongan aumento, reduccin o sustitucin de una clase por otra, y an supresin de las cantidades de obra marcadas en el Presupuesto, sern obligatorias para el Contratista estas disposiciones sin que tenga derecho, en caso de reduccin o supresin de obra, a reclamar ninguna indemnizacin a pretexto de los posibles beneficios que hubiera podido obtener. Si se le comunican al Contratista con la debida anticipacin, no podr exigir indemnizacin alguna bajo ningn concepto. El Contratista tendr derecho, en caso de modificacin a que se prorrogue prudencialmente y a juicio del Ingeniero Director el plazo para la terminacin de las obras. El Contratista no podr hacer por su cuenta alteraciones en ninguna de las partes proyecto aprobado sin la autorizacin escrita del Ingeniero
10
Director, sin cuyo requisito no le sern de abono los aumentos que pudieran resultar a consecuencia de las variaciones no autorizadas.
2.6 Disposiciones legales Queda obligado el Contratista al cumplimiento de lo que obligan las leyes, debiendo estar al corriente en el pago de lo seguros sociales, de accidentes, mutualidades y dems seguros de ndole laboral, abono de fiestas y vacaciones, etc. En definitiva, al cumplimiento de todas las disposiciones legales, leyes, normas, reglamentaciones, etc., en vigor sobre legislacin social, as como las aplicables en la contratacin de obras privadas. Est tambin obligado al cumplimiento de cuanto el Director de Obra le dicte, encaminado a garantizar la seguridad de los obreros y buena marcha de las obras, bien entendido que, en ningn caso, dicho cumplimiento eximir al Contratista de responsabilidad. El Contratista deber cumplir todas las disposiciones vigentes sobre seguridad e higiene en el trabajo.
2.7 Responsabilidad del contratista El Contratista es responsable de la ejecucin de las obras en las condiciones establecidas en el contrato y en los documentos que componen el proyecto. Como consecuencia de su responsabilidad, el Contratista estar obligado a la demolicin y reconstruccin de todo lo que est mal ejecutado, no quedando eximido de ello por el examen y reconocimiento, durante las obras, por parte de la Direccin Facultativa, ni por el abono en liquidaciones parciales.
11
obliga a facilitar a la Direccin Facultativa la inspeccin y vigilancia necesaria sobre el cumplimiento de las condiciones de la contrata y del ritmo de realizacin de los trabajos, tal y como est previsto en la planificacin del presente Proyecto. A todos estos efectos el adjudicatario estar obligado a tener en la obra, durante la ejecucin de los trabajos, el personal tcnico, capataces y encargados necesarios que a juicio de la Direccin Facultativa sean necesarios para la debida conduccin y vigilancia de las obras e instalaciones.
3.3 Jefe de Obra Desde que se de comienzo a las obras hasta su recepcin provisional, el Contratista designar un jefe como su representante
12
autorizado que cuidar de que los trabajos sean llevados con diligencia y competencia. Este jefe estar expresamente autorizado por el Contratista para recibir notificacin de la rdenes escrita o verbales emitidas por la Direccin Facultativa y para asegurar que dichas rdenes se ejecuten. Asimismo estar expresamente autorizado para firmar y aceptar las mediciones realizadas por la Direccin Facultativa. Cualquier cambio que el Contratista desee efectuar respecto a sus representantes o personal cualificado y en especial del jefe de obra deber ser comunicado a las Direccin Facultativa no pudindose producir el relevo hasta la aceptacin por la Direccin Facultativa de las personas designadas. Cuando se falte a lo anteriormente prescrito se considerarn vlidas las notificaciones que se efecten al individuo ms caracterizado o de mayor categora tcnica de los empleados y operarios de cualquier rama, que como dependientes de la contrata intervengan en las obras. En ausencia de todo ellos sern vlidas las depositadas en la residencia designada como oficina del Contratista en el contrato de adjudicacin, an en ausencia o negativa de recibo por parte de los dependientes de la contrata.
3.4 Presencia del Contratista en la obra El Contratista en persona o por medio de sus facultativos, representantes o encargados, estar en la obra durante la jornada legal de trabajo y acompaar a la Direccin Facultativa en las visitas que haga a la obra. Asimismo asistir a la reuniones de obra que se convoquen, no pudiendo justificar por motivo de ausencia ninguna reclamacin a las rdenes cruzadas por la Direccin Facultativa en el transcurso de las reuniones.
13
3.5 Oficina de obra El Contratista habilitar en al obra una oficina en al que puedan extenderse y consultarse los planos. En dicha oficina el Contratista tendr siempre una copia autorizada de todos los documentos del proyecto que le hayan sido facilitados por la Direccin Facultativa y el libro de rdenes.
3.6 Interpretaciones, aclaraciones y modificaciones en los Documentos del Proyecto Cuando se trate de aclarar, modificar o interpretar preceptos de los Pliegos de Condiciones o indicaciones de los planos, las rdenes e instrucciones correspondientes se comunicarn de forma precisa y por escrito al Contratista. ste estar obligado, a su vez, a devolver los originales, suscribiendo con su firma el enterado, que figurar en todas las rdenes, avisos o instrucciones que reciba, tanto de la Propiedad como de la Direccin Tcnica. Cualquier reclamacin que, en contra de las disposiciones tomadas por la Propiedad o por la Direccin Tcnica, crea oportuno hacer el Contratista, deber dirigirla dentro del plazo de 15 das a la Direccin Facultativa, la cual dar al Contratista el correspondiente recibo, si ste lo solicitase.
3.7 Reclamaciones contra rdenes de la Direccin Facultativa Las reclamaciones que el Contratista quiera hacer contra las rdenes de la Direccin Facultativa, slo podr presentarlas, a travs de la misma, ante la Propiedad, si estas son de carcter econmico y de acuerdo con las condiciones estipuladas en los Pliegos de Condiciones correspondientes. Si las reclamaciones fueran contra disposiciones de orden tcnico o facultativo de la Direccin Facultativa no se admitir reclamacin alguna, pudiendo el Contratista salvar sus responsabilidades
14
si lo estima oportuno, mediante exposicin razonada dirigida a la Direccin Facultativa, la cual podr limitar su contestacin al acuse de recibo, que en todo caso ser obligatorio para este tipo de reclamaciones.
3.8 Recusacin por el Contratista del Personal Nombrado por la Ingeniera El Contratista no podr recusar al personal tcnico, encargado de la vigilancia de las obras o de cualquier ndole, dependiente de la Direccin Facultativa o de la Propiedad. Tampoco podr pedir que la Propiedad designe otros facultativos para los reconocimientos y menciones. Cuando se crea perjudicado con lo resultados de stos, proceder de acuerdo con lo estipulado en el artculo precedente, pero sin que por esta causa puedan interrumpirse o perturbarse la marcha de los trabajos.
3.9 Despidos por falta de subordinacin, incompetencia o manifiesta mala fe Por falta de respeto y obediencia a la Direccin Facultativa o al personal encargado de vigilancia de las obras, por manifestar incapacidad o por actos que comprometan o perturben la marcha de los trabajos, el Contratista tendr obligacin de despedir a sus dependientes y operarios a requerimiento de la Direccin Facultativa.
3.10 Libro de rdenes El Contratista tendr siempre en la oficina de obra y a disposicin de la Direccin Facultativa un libro de rdenes con sus hojas foliadas por duplicado visado por el colegio profesional correspondiente. En el mismo se redactarn todas las rdenes de la Direccin Facultativa crea oportuno dar al Contratista para que adopte las medidas de todo gnero que crea necesarias para subsanar o corregir las posibles
15
deficiencias constructivas que haya observado en las visitas a la obra y que pudieran repercutir sobre los obreros, los viandantes en general, las fincas colindantes o los inquilinos de las mismas y en general todas las medidas que juzgue indispensable para la ejecucin de la obra segn los documentos del Proyecto. Cada orden deber ser firmada por la Direccin Facultativa el
Enterado suscrito por el Contratista o su representante en obra. La copia de cada orden entendida quedar en poder de la Direccin Facultativa. El hecho de que en el citado libro no figuren redactadas las rdenes que ya preceptivamente tiene obligacin de cumplimentar el Contratista, de acuerdo con lo establecido en las normas oficiales, reglamentos, etc., no supone atenuante alguno para las responsabilidades que sean inherentes al contratista. Para toda reclamacin eventual del contratista no podr tener en cuenta ningn acontecimiento o documento que no haya quedado mencionado en su momento en el libro de rdenes. A falta de tal mencin, la opinin de la Direccin Facultativa sobre los hechos invocados en la reclamacin ser la nica a tener en cuenta.
3.11 Comienzo de la obra, ritmo de ejecucin de los trabajos El Contratista dar comienzo a las obras en el plazo marcado en el contrato de adjudicacin de la obra, desarrollndolas en las necesarias para que dentro de lo perodos parciales reseados queden ejecutadas las obras correspondientes y que, en consecuencia, la ejecucin total se lleve a cabo dentro del plazo exigido en el contrato.
3.12 Orden de los trabajos En general la determinacin del orden de los trabajos ser facultad potestativa de la contrata, salvo en aquellos casos en los que, por cualquier
16
circunstancia de orden tcnico o facultativo, estime conveniente su variacin la Direccin Facultativa. Estas rdenes debern comunicarse de forma precisa y por escrito a la contrata. sta a su vez estar obligada a su estricto cumplimiento, siendo directamente responsable de cualquier dao o perjuicio que pudiera sobrevenir por su incumplimiento.
3.13 Ampliacin del proyecto por causas imprevistas de fuerza mayor Cuando en el transcurso de las obras, por motivos imprevistos o cualquier accidente, sea necesario ampliar el proyecto, no se
interrumpirn los trabajos, continundolas segn las instrucciones dadas por la Direccin Facultativa, en tanto se formula o se tramita el proyecto reformado. El Contratista estar obligado a realizar con su personal y con sus materiales apuntalamientos, derribos, recalzos o cualquier otra obra de carcter urgente que la Direccin Facultativa de las obra disponga, anticipando de momento este servicio, cuyo importe le ser consignado en el presupuesto oficial o abonado directamente de acuerdo con lo que mutuamente se convenga.
3.14 Prrrogas por causas de fuerza mayor Si por causa de fuerza mayor o ajena a la voluntad del contratista, siempre que esta causa sea distinta de las especficas de rescisin de contrato, no le fuera posible terminar la obra en los plazos prefijados, comenzar su ejecucin o tuviera que suspenderla, se le otorgar una prrroga para el cumplimiento de la contrata, previo informe favorable de la Direccin Facultativa. Para ello el Contratista expondr por escrito, dirigido a la Direccin Facultativa, la causa que le impide la ejecucin o la
17
correcta marcha de los trabajos y el retraso que por ello originar en los plazos acordados, razonando la prrroga que por dicha causa solicita.
3.15 Responsabilidad de la Direccin Facultativa en el retraso de la obra El Contratista no podr excusarse de no haber cumplimentado los plazos de obra estipulados, alegando como causa la carencia de planos y rdenes de la Direccin Facultativa, a excepcin de que la contrata, en uso de las facultades que en este documento se le conceden, los haya solicitado por escrito a la Direccin Facultativa y sta no los haya entregado. En este nico caso, el Contratista queda facultado para recurrir ante los amigables componedores precisamente designados, los cuales decidirn sobre la procedencia o no del recurso. En caso afirmativo, la Direccin Facultativa ser la responsable del retraso sufrido, pero nicamente en las unidades de obra afectadas concretamente por el recurso del Contratista y las subsiguientes que estuvieran relacionadas con ellas.
3.16 Replanteo general El replanteo general se llevar a efecto de acuerdo con lo preceptuado en el proyecto, entendindose que si cursada por la Direccin Facultativa y recibida por el Contratista, la oportuna citacin para la ejecucin del Replanteo General, no asistiera ste o en su nombre un representante, debidamente autorizado, el replanteo se efectuar an en su ausencia.
3.17 Condiciones generales de ejecucin de los trabajos Todos los trabajos se ejecutarn con estricta sujecin al proyecto que haya servido de base a la contrata, a las modificaciones del mismo, que previamente hayan sido aprobadas y a las rdenes e instrucciones que
18
bajo su responsabilidad y por escrito entregue la Direccin Facultativa al Contratista, siempre que stas encajen dentro de la cifra a que ascienden los presupuestos aprobados.
3.18 Obras ocultas De todos los trabajos y unidades de obra que hayan de quedar ocultos a las terminacin de la obra, se levantarn los planos precisos e indispensables documentos se para que queden por perfectamente triplicado, definidos. Estos al
extendern
entregndose
uno
propietario, otro a la Direccin Facultativa y el tercero al Contratista. Todos los planos estarn firmados por la Direccin Facultativa y el Contratista. Dichos planos, que debern ir suficientemente acotados, se considerarn documentas indispensables e irrecusables para efectuar las mediciones.
3.19 Trabajos defectuosos El Contratista ha de emplear los materiales que cumplan las condiciones exigidas en las especificaciones de materiales y equipos del Pliego de Condiciones, y realizar todos y cada uno de los trabajos contratados de acuerdo con lo especificado tambin en el presente documento. Por ello, y hasta que tenga lugar la recepcin definitiva de las obra, el Contratista es el nico responsable de la ejecucin de los trabajos, faltas y defectos que en estos puedan ocurrir por su mala ejecucin, por la deficiente calidad de los materiales empleados o de los aparatos colocados. En esta responsabilidad el Contratista no puede alegar, para diminuir su responsabilidad, la circunstancia de que la Direccin Tcnica o sus subalternos no le hayan llamado la atencin sobre la falta o defecto,
19
ni tampoco el hecho de que hayan ido valoradas en las certificaciones parciales de la obra, que siempre se supone se extienden y abonan a buena cuenta. Como consecuencia de lo anteriormente expresado, cuando la Direccin Facultativa o su representante en la obra adviertan vicios o defectos en los trabajos ejecutados, o bien que los materiales empleados o aparatos colocados no renen las condiciones preceptuadas, ya sea en el curso de la ejecucin de los trabajos o finalizados stos, y antes de verificarse la recepcin definitiva de la obra, podr disponer que las partes defectuosas sean demolidas y reconstruidas de acuerdo con lo contratado, todo ello a expensas de la contrata. Si el Contratista no estimara justa la resolucin y se negase a la demolicin y reconstruccin ordenadas, se proceder de acuerdo con lo establecido en el presente documento.
3.20 Vicios ocultos Si la Direccin Facultativa tuviese razones fundadas para creer en la existencia de vicios ocultos de construccin en las obras ejecutadas, ordenar efectuarse, en cualquier momento antes de la recepcin definitiva, las demoliciones que crea necesarias para reconocer los trabajos que suponga defectuosos. Los gastos de demolicin y reconstruccin que se ocasionen corrern a cargo del Contratista si haba realmente vicios y a cargo del propietario en caso contrario.
3.21 De los materiales y aparatos y su procedencia El Contratista tiene libertad de proveerse de los materiales y aparatos de toda clase en los puntos que estime conveniente, siempre que renan las condiciones exigidas en la Memoria, en el presente Pliego y en
20
el contrato, que estn preparados para el objeto a que se aplican y se cian a las instrucciones de la Direccin Facultativa.
3.22 Empleo de los materiales y aparatos No se proceder al empleo y colocacin de los materiales y de los aparatos sin que antes hayan sido examinado y aceptados por la Direccin Facultativa en los trminos que prescriben los Pliegos de Condiciones, depositando el Contratista a tal efecto las muestras y modelos necesarios, previamente contraseados, para efectuar con ellos las comprobaciones, ensayos o pruebas preceptuadas en el Pliego de Condiciones. Los gastos que ocasionen los ensayos, anlisis, pruebas, etc., antes indicadas, sern de cargo del Contratista.
3.23 Materiales no utilizables El Contratista, a su costa, transportar y colocar, agrupndolos ordenadamente y en el sitio de la obra, en el que, por no causar perjuicios a la marcha de los trabajos se designe, los materiales procedentes de las excavaciones, derribos, etc., que no sean utilizables en la obra. Se retirarn de sta o se llevarn al vertedero, cuando la Direccin Facultativa lo ordene, pero acordando previamente con el Contratista su justa tasacin, teniendo en cuenta el valor de dichos materiales y los gastos de su transporte.
3.24 Materiales y aparatos defectuosos Cuando los materiales y aparatos no fuesen de la calidad requerida o no estuviesen perfectamente preparados, la Direccin Facultativa dar orden al Contratista para que lo reemplace por otros que se justen a las condiciones requeridas por el Pliego de Condiciones. A falta de stas, se ajustar a las rdenes de la Direccin Facultativa.
21
La Direccin Facultativa podr, si las circunstancias o el estado de la obra lo aconsejan, permitir el empleo de aquellos materiales defectuosos que mejor le parezcan, descontando la diferencia de precio del material requerido al defectuoso empleado. La Direccin Facultativa tambin podr aceptar o imponer el empleo de otros materiales de calidad superior a la indicada en el Pliego, o no le fuera posible al Contratista suministrarlos de la calidad requerida, teniendo derecho el Contratista a presentar recurso.
3.25 Medios auxiliares Sern de cuenta del Contratista los andamios, cimbas, mquinas y dems medios auxiliares que para la debida marcha y ejecucin de los trabajos se necesiten, no cabiendo por tanto al propietario responsabilidad alguna por cualquier avera o accidente personal que pueda ocurrir en las obras por insuficiencia de dichos medios auxiliares. Todos stos quedarn a beneficio del Contratista, sin que ste pueda reclamar por insuficiencia de medios, cuando stos estn detallados en el Presupuesto y consignados por partida alzada e incluidos en los precios de las unidades de obra.
3.26 Recepciones provisionales Para proceder a la recepcin provisional de las obras ser necesaria la asistencia del propietario o de su representacin autorizada, que puede recaer en la Direccin Facultativa, que estar presente en todo caso y del Contratista o un representante debidamente autorizado. Del resultado de la recepcin se extender un acta por triplicado, firmado por los tres asistentes legales indicados. Si las obras se encuentran en buen estado y han ido ejecutadas con arreglo a las condiciones establecidas, se darn por recibidas
22
provisionalmente, comenzando a correr en dicha fecha el plazo de garanta sealado en la obra. Cuando las obras no se hallen en estado de ser recibidas, se har constar en el acta y se especificarn en la misma las precisas y detalladas instrucciones que la Direccin Facultativa deber sealar al Contratista para remediar los defectos observados, fijndose un plazo para subsanarlos. Expirado el plazo para subsanar las deficiencias, se efectuar un nuevo reconocimiento, en idnticas condiciones, a fin de proceder de nuevo a la recepcin de la obra. Si el Contratista no hubiera cumplido, perder la fianza, a no ser que el propietario acceda a concederle un nuevo e improrrogable plazo. La recepcin provisional de las obras tendr lugar dentro de la quincena siguiente a su terminacin. El Contratista comunicar por escrito al Director de Obra la fecha de terminacin total de la instalacin e incluir con esta notificacin los planos donde se reflejan todas las instalaciones efectuadas en la estacin. Antes de efectuar la recepcin provisional de la instalacin se podrn hacer las siguientes pruebas:
3.27 Conservacin de las obras recibidas provisionalmente Los gastos de conservacin, durante el plazo de garanta comprendido entre las recepciones parciales y la definitiva, corrern a cargo del Contratista. En caso de duda, ser juez inapelable la Direccin Facultativa, sin que contra su resolucin quede ulterior recurso.
23
3.28 Programa de trabajos El Contratista est obligado a cumplir el Programa de Trabajos siguiendo las indicaciones del Director de Obra. El Director de Obra, una vez que el Contratista est en posesin del proyecto, y antes de comenzar las obras debera hacer un replanteo de las mismas con especial atencin en los puntos singulares, entregando al Contratista las referencias y datos necesarios para fijar completamente la ubicacin de las mismas. Se levantar acta por duplicado, en la que constarn claramente los datos entregados y las firmas del Director de Obra y del representante del Contratista. Los gastos de replanteamiento sern de cuenta del Contratista.
3.29 Mejoras y variaciones del proyecto Slo se consideran como mejoras o variaciones del proyecto aquellas que hayan sido ordenadas expresamente por el Director de Obra y convenido el precio antes de proceder a su ejecucin. Las obras accesorias o delicadas, no incluidas en los precios de adjudicacin, Contratista. podrn ejecutarse con personal independiente del
3.30 Recepcin del material El Director de Obra de acuerdo con el Contratista dar a su debido tiempo su aprobacin sobre el material suministrado y confirmar que permita una instalacin correcta. La vigilancia y conservacin del material suministrado ser por cuenta del Contratista.
24
3.31 Organizacin El Contratista actuar de patrono legal, aceptando todas las responsabilidades correspondientes y quedando obligado al pago de salarios y cargas, que legalmente sean establecidas, en general, a todo cuanto se legisle, decrete u ordene sobre el particular antes o durante la ejecucin de la obra. Dentro de lo estipulado en el Pliego de Condiciones, la organizacin de la obra, as como la determinacin del a procedencia de lo materiales que se empleen, estar a cargo del Contratista, a quien corresponder la responsabilidad de la seguridad contra accidentes. El Contratista debera , sin embargo, informar al Director de Obra de todos los planes de organizacin tcnica de la obra, as como la procedencia de lo materiales y cumplimentar cuantas rdenes le sean requeridas en relacin con datos externos. El Contratista deber dar cuenta diaria al Director de Obra de la admisin de personal, compra de materiales, adquisicin o alquiler de elementos auxiliares y cuantos gastos haya de efectuar. Los contratos de trabajo, compra de materiales o alquiler de elementos auxiliares, cuyos salarios, precios o cuotas sobrepasen en ms de un 5% de los normales en el mercado, requerirn la aprobacin previa del Director de Obra, quien deber responder dentro de los ocho das siguientes a la peticin, salvo casos de reconocida urgencia, en los que se dar cuenta en plazo posterior.
3.32 Ejecucin de las obra Las obras se ejecutarn conforme al proyecto y a las condiciones del Pliego de Condiciones, y de acuerdo con las especificaciones sealadas en las condiciones tcnicas.
25
El Contratista, salvo aprobacin por escrito del Director de Obra, no podr hacer ninguna alteracin o modificacin de cualquier naturaleza, tanto en la ejecucin de la obra, en relacin al proyecto, como en las condiciones tcnicas especificadas, sin perjuicio de lo que en cada momento pueda ordenarse por el Director de Obra. El Contratista no podr utilizar en los trabajos personal que no sea de su exclusiva cuenta y cargo, salvo en el caso de obra de instalaciones auxiliares. Igualmente ser de su exclusiva cuenta y cargo aquel personal ajeno al propiamente manual y que sea necesario para el control administrativo del mismo. El Contratista deber tener en al frente de los trabajos un tcnico suficientemente especializado a juicio del Director de Obra. El Contratista deber obtener a su costa todos los permisos necesarios para la ejecucin de las obras, con excepcin de expropiaciones y servidumbres. Se incluyen, de modo especial, la solicitud de suministro a la compaa suministradora de energa, a la compaa suministradora de agua y la tramitacin necesaria ante el Ministerio de Industria, hasta la obtencin de la puesta en servicio del gasocentro.
3.33 Mtodos constructivos El Contratista podr emplear cualquier mtodo constructivo para la ejecucin de las obras siempre que su programa de trabajos se hubiera propuesto y aceptado por la Propiedad. Tambin podr variar los procedimientos durante la ejecucin de las obras, sin ms limitacin que la aprobacin previa y expresa del Ingeniero Director de las obras, el cual la otorgar en cuanto los nuevos mtodos no vulneren el presente documento, pero reservndose el
26
derecho a exigir los mtodos antiguos si comprobar la menor eficacia de los nuevos.
3.34 Equipos de obra Independientemente de las condiciones particulares o especficas que se exijan a los equipos necesarios para ejecutar las obras en los artculos del presente documento, todos los equipos que se empleen en la ejecucin de las obras debern cumplir en todo caso las condiciones siguientes:
Estar disponibles con suficiente anticipacin al comienzo del trabajo correspondiente, para que puedan ser examinados o aprobados por la Direccin de Obra.
Despus de aprobado un equipo por la Direccin de Obra, deber mantenerse en todo momento en condiciones de trabajo satisfactorias haciendo las sustituciones o reparaciones necesarias para ello.
Si durante la ejecucin de las obras la Direccin de Obra observase que, por cambio de las condiciones de trabajo o por cualquier otro motivo, el equipo o equipos aprobados no son idneos al fin propuesto, debern ser sustituidos por otros que lo sean.
3.35 Responsabilidad del Contratista Es obligacin del Contratista ejecutar cuanto sea necesario para la buena construccin y aspecto de las obras, an cuando no se haya estipulado en las condiciones de este documento, siempre que, sin separarse del espritu y recta interpretacin, lo disponga por escrito el Ingeniero Director. La Propiedad podr exigir del Contratista que curse las partes que crea convenientes, con la periodicidad que estime necesaria.
27
El Contratista estar obligado a colaborar con otros contratistas o subcontratistas en la medida en que le sea solicitado por la Direccin de Obra.
3.36 Realizacin de los trabajos Los distintos elementos de la instalacin sern montados de forma esmerada y con buen acabado. Durante el desarrollo de la obras, y hasta que tenga lugar la recepcin definitiva, el Contratista es el responsable de los defectos que puedan observarse en los materiales utilizados o en la realizacin de la instalacin. Los materiales que se utilicen en la instalacin podrn ser sometidos a las pruebas que se especifican en este documento o que se consideren necesarias para comprobar su idoneidad. Los ensayos durante la realizacin tienen carcter de simples antecedentes para la recepcin. Por consiguiente, la admisin de materiales u obras, en cualquier forma que se realicen, no atenan las obligaciones de subsanar o reponer, que el Contratista contrae, si las instalaciones resultasen inaceptables, parcial o totalmente, en el acto de reconocimiento final y pruebas de recepcin. Una vez terminada la instalacin, si lo estima necesario el Director de Obra, en presencia del Contratista, efectuar por s o con la colaboracin de un laboratorio oficial las mediciones que considere oportunas.
3.37 Obras definidas completamente en este Pliego Aquellas partes de las obras que no queden completamente definidas en el presente documento debern llevarse a cabo segn los detalles con que figuran reseados en los planos, segn las instrucciones
28
que por escrito pueda dar el ingeniero Director y teniendo presentes los buenos usos y costumbres de la construccin.
4 Condiciones econmicas
4.1 Recepcin de la obra Durante la obra o una vez finalizada la misma, el Director de Obra podr verificar que los trabajos realizados estn de acuerdo con las especificaciones del presente documento. Esta verificacin se realizar por cuenta del Contratista. Una vez finalizadas la instalaciones el Contratista deber solicitar la oportuna recepcin global de la obra. En la recepcin de la instalacin se incluirn las mediciones que la Direccin Facultativa considere oportunas. El Director de Obra contestar por escrito al Contratista, comunicando su conformidad a la instalacin o condicionando su recepcin a la modificacin de lo detalles que estime susceptibles de mejora. El Director de Obra podr encargar la ejecucin de ensayos. El Contratista tomar a su cargo la obras ejecutadas que hayan resultado de insuficiente calidad a la vista de los citados ensayos.
4.2 Accidentes de trabajo En el caso de accidentes ocurridos a los operarios con motivo de los trabajos para la ejecucin de las obras, el Contratista se atendr a lo dispuesto en la legislacin vigente, siendo en todo caso nico responsable de su incumplimiento y sin que, por ningn concepto, pueda quedar afectada la propiedad en cualquier aspecto.
29
El Contratista estar obligado a adoptar las medidas de seguridad que las disposiciones vigentes precepten para evitar accidentes a los obreros y a los viandantes en todos los lugares peligrosos de la obra. El Contratista, o sus representantes de la obra, sern los nicos responsables de los accidentes perjuicios de todo gnero que, por no cumplir con lo legislado sobre la materia, pudieran recaer o sobrevenir, ya que se considera que en los precios contratados estn incluidos todos los gastos precisos para cumplimentar debidamente dichas disposiciones legales. Ser preceptivo que en el tabln de anuncios de la obra, durante todo su transcurso, figure el presente artculo del Pliego de Condiciones, sometido previamente a la firma de la Direccin Facultativa.
4.3 Dao a terceros El Contratista ser responsable de todos los accidentes que por inexperiencia o descuido sobreviniesen, tanto en el emplazamiento donde se efectan las obras, como en los contiguos, ser por tanto de su cuenta el abono de las indemnizaciones, de todos los daos y perjuicios que puedan causarse en las operaciones de ejecucin de las obras, a quien correspondiera y cuando ello tuviera lugar. El Contratista cumplir los requisitos que prescriben las
disposiciones vigentes sobre la materia, debiendo exhibir cuando fuera requerido el justificante de tal cumplimiento.
4.4 Pago de rbitros El pago de impuestos y arbitrios en general, municipales o de otro origen, sobre vallas, alumbrado, etc., cuyo abono debe hacerse durante el tiempo de ejecucin de las obras y por concepto inherentes a los propios trabajos que se realizan, corrern a cargo de la contrata, siempre que en las
30
condiciones particulares del proyecto no se estipule lo contrario. No obstante, el Contratista deber ser reintegrado del importe de todos aquellos conceptos que la Direccin de Obra considere justo hacerlo.
4.5 Anuncios y carteles Sin previa autorizacin en la propiedad no podrn exhibirse ms inscripciones o anuncios que los convenientes al rgimen de los trabajos.
4.6 Copias de documentos El Contratista tiene derecho a sacar copias a su costa de los documentos del proyecto que considere oportuno. La Direccin Facultativa, si el Contratista lo solicita, autorizar estas copias con su firma una vez confrontadas.
4.7 Suministro de materiales Los materiales empleados en la instalacin sern entregados por el Contratista siempre y cuando la Direccin Facultativa no se pronuncie en contra. 4.8 Penalizacin por plazo de ejecucin de las obras Si el Contratista no ejecutase la obra en los plazos marcados se le impondr una multa de 500 euros por cada da de demora sobre el plazo previsto. En el caso de fuerza mayor, ser prorrogable el plazo de terminacin de las obras. Esta prrroga ser propuesta por el Director de Obra a peticin del Contratista. No sern consideradas causas de fuerza mayor las inclemencias atmosfricas.
31
4.9 Recepcin provisional de las obras Una vez terminadas las obras, la Direccin Facultativa practicar todos los reconocimientos que juzgue necesarios para cerciorarse de que las obras estn ejecutadas con arreglo a las condiciones del contrato, procedindose a la recepcin provisional y abono de las mismas.
4.10 Plazo de garanta Hecha la recepcin provisional, empezar a correr el plazo de garanta, que ser de un ao. Durante este perodo ser cuenta del Contratista todas las obras de conservacin y restauracin necesarias de acuerdo con lo dispuesto en los artculos 170 y 171 del Reglamento General de la Contratacin de 28 de Diciembre de 1967.
4.11 Suspensin de obras Cuando la entidad propietaria desee suspender la ejecucin de las obras, tendr que avisar con un mes de anticipacin y el Contratista tendr que suspender los trabajos sin derecho a indemnizacin, siempre que se le abone el importe de la obra ejecutada y el valor de los materiales acumulados a pie de obra, al precio corriente en la localidad. Se proceder de igual forma en los casos de rescisin justificada. Si la suspensin de la obras fuese motivada por el Contratista, el Propietario se reserva el derecho a la rescisin del contrato, abonando al Contratista tan slo la obra ejecutada, con prdida de garanta como indemnizacin de perjuicios producidos a la Propiedad, quedando siempre obligado el Contratista a responder de los perjuicios superiores.
32
4.12 Medicin y abono de obras Las obras se abonarn por unidades de volumen, superficie, longitud o peso segn se detalla en este captulo. Se abonarn al Contratista las obras que realmente ejecute, sea en ms o en menos de lo que aparece en el Presupuesto, sin que el nmero de unidades de cada clase en l asignadas pueda servir de pretexto o fundamento para establecer reclamaciones. Para valorar las unidades de obra se aplicar al total de cada una de aquellas el precio unitario con que figura en el presupuesto, aumentndose el resultado con el tanto por ciento de contrata y deduciendo la baja de subasta si la hubiera. En el precio unitario se consideran incluidos el valor de los materiales, el coste de los jornales y mano de obra con sus cargas sociales, los transportes, los medios auxiliares y, en general, cuanto trabajos sean necesarios para la ejecucin de la unidad de obra de que se trate. El beneficio industrial con su parte de inters del dinero adelantado, as como los imprevistos y la direccin y administracin del contratista, se comprenden dentro del porcentaje de la contrata. Se entiende por metro cbico de excavacin al espacio desalojado al ejecutarla. La excavacin se abonar segn volumen que resulte de acuerdo con las cotas de los perfiles longitudinales y los taludes indicados en los documento del proyecto, o aquellos que posteriormente ordene el Director de Obra. Slo sern de abono las excavaciones necesarias para la ejecucin de las obras conforme se define anteriormente y las que ordene por escrito el Ingeniero Director. No lo sern las que por su conveniencia practique por exceso el Contratista. En el precio de las excavaciones estn incluidos los costes de colocacin en caballeros, entibaciones, agotamientos, etc., que sea preciso realizar, as como las existentes para respetar su ubicacin. Este precio ser
33
el mimo cualquiera que sea la clase del terreno, si no se especifica lo contrario. Se entiende por metro cbico de relleno compactado el volumen medido por diferencia entre el volumen excavado que se abone y el que ocupe la obra de fbrica. En el precio del relleno se incluyen todas las operaciones precisas para realizarlo, incluida la compactacin , cualquiera que sea el tipo de material empleado, as como el transporte a vertedero de las cantidades sobrantes de excavacin. Se entiende por metro cbico de hormign el de obra terminada completamente con arreglo a las prescripciones del presente documento. En el precio del hormign estn incluidos todos los gastos de transportes, preparacin, puesta en obra, aditivos, pruebas y ensayos, juntas y material para sellado terminacin de la unidad de obra. Con la mencin de totalmente instalado en el presupuesto se entiende que incluye:
La totalidad de los materiales con sus recortes y apuntes. Todas las piezas auxiliares y pequeo material de cualquier tipo, necesario para el correcto funcionamiento de cada unidad, si estas piezas y material no estn definidas especficamente en el presupuesto.
Todas las piezas especiales o materiales de cualquier tipo, necesarios para su ejecucin, si stas no estn definidas especficamente en el presupuesto.
Mano de obra de ejecucin y pruebas de todas las cargas y seguros sociales que marca la ley, as como la direccin, gastos generales, beneficio industrial, etc.
Toda clase de impuestos. El transporte a obra de todos los materiales y equipo auxiliar, as como carga, descarga y movimientos dentro de la obra.
34
El precio sealado para cada unidad comprende el suministro, transporte, manipulacin y empleo de todos los materiales, maquinaria y mano de obra necesarios para su ejecucin, as como cuantas necesidades circunstanciales se requieran para que la obra sea ejecutada. Slo se liquidarn al Contratista, con cargo a las partidas alzadas, aquellas obras que bajo proyecto y rdenes del ingeniero se lleven a cabo, las cuales se abonarn por unidades a los precios del proyecto, o bien a los que se fije, de acuerdo al artculo de precios contradictorios del presente documento.
4.13 Obras incompletas Cuando por consecuencia de rescisin de contrato o por otra causa fuese preciso abonar obras incompletas se aplicarn los precio unitarios indicados en el Presupuesto del presente proyecto, el cual no admite descomposicin para este respecto. El Contratista deber preparar los materiales que tenga acopiados para que estn en disposicin de ser recibidos en el plazo que determina la Direccin de Obra, siendo abonadas de acuerdo con lo expresado en dicho cuadro de precios. En ninguno de estos casos tendr derecho el Contratista a reclamacin alguna fundada en la insuficiencia de los precios o en omisin de costo de cualquiera de los elementos que constituyen los precios.
4.14 Precios contradictorios Si fuese necesario fijar precio para unidades de obra o consignadas en el Presupuesto, se efectuarn entre el Ingeniero Director, como representante de la Propiedad, y el Contratista, conforme a las normas establecidas en los Pliegos Generales de Contratacin.
35
La fijacin de estos precios deber efectuarse antes de la ejecucin de las obras a las que hayan de aplicarse, pero si por cualquier causa hubieran sido ejecutas las obras, el Contratista queda obligado a aceptar los precios que seale el Director de Obra. Tanto una u otra forma de fijacin para estos nuevo precio quedan sujetas al aumento de un quince por ciento de contrata, como a la baja de la subasta si la hubiera.
1 Condiciones generales
Todos los materiales que se empleen en las obras, aunque no se haga mencin expresa en este documento, debern cumplir las mejores condiciones de calidad conocidas dentro de su clase. No se proceder al empleo de los materiales sin que stos hayan sido examinados y aceptados en los trminos que prescriben las respectivas condiciones estipuladas para cada clase de material. El reconocimiento previo no constituye su recepcin definitiva pudiendo ser rechazados por la Direccin de Obra, an despus de colocados, si no cumplieran con las condiciones debidas en las pruebas, ensayos o anlisis, todo ello en los trminos que se precisan en este documento, debiendo ser reemplazadas por el Contratista por otros que cumplan con las condiciones debidas. Se realizarn tantas pruebas se ordenen por el Director de Obra, siendo los gastos que se ocasionen por cuenta del Contratista. En el reconocimiento y admisin de materiales no se podrn emplear materiales que no hayan sido aceptados previamente por el Director de Obra y se realizarn cuantos ensayos y anlisis indique aunque no estn indicados en el Pliego de Condiciones.
2 Obra civil
2.1 Movimiento de tierras Previamente al inicio de los trabajos de obra, se proceder a realizar un estudio del subsuelo, por empresa reconocida, donde se requerirn la capacidad portante del terreno, la presencia de manto fretico y la agresividad del terreno del agua. La explanacin y el relleno se realizarn en funcin de las caractersticas de los terrenos, tenindose en cuenta los accesos por los viales existentes, de forma que el movimiento de tierras sea mnimo, a la vez que las pendientes del gasocentro se mantengan dentro de uno valores normales, aproximadamente en un uno por cierto. Antes de la realizacin de los pavimentos y firmes se retirar en toda la extensin de los viales la tierra vegetal, procediendo a continuacin al escarificado de la superficie del terreno y posterior compactacin. En donde se requiera se excavar el manto del terreno vegetal que se encuentra en el rea de construccin de las obras. A continuacin se proseguir con la excavacin y nivelacin de las zonas de emplazamiento de las obras hasta alcanzar la cota de explanacin general. El relleno estar formada por materiales terrosos procedentes de prstamos, que tengan como mnimo, las caractersticas de suelos tolerables excepto en los 50 cm ms superficiales en los que se emplearn suelos adecuados o seleccionados. Se compactarn por medios mecnicos y en tongada mximas de 30 cm. Las excavaciones, explanaciones y rellenos se realizarn de acuerdo con lo indicado en los captulos correspondientes del PG-3-1975 del MOPT. Los materiales exigidos para el relleno debern cumplir las condiciones las condiciones indicadas en el captulo correspondiente del citado PG-3-1975.
Zahorra artificial de 15 cm. Segunda capa de zahorra artificial de 15 cm. Asfalto impermeable y resistente a hidrocarburos.
Los accesos debern tener un ancho igual al de la carretera en la que se encuentran emplazados. Las sealizaciones se ajustarn a la norma 8.1 IC: Seales verticales y al Catlogo de seales de circulacin de la Direccin General de Carreteras, realizndose de acuerdo con el artculo 700 del PG3-75. Las lneas y seales pintadas sobre el pavimento se realizarn con un tipo de pintura que se ajuste a la Orden Circular n 292/86 T Marcas Viales. Las aceras del gasocentro tendrn en su contorno un bordillo de hormign prefabricado asentado sobre una solera de hormign, que sobresaldr 15 cm. sobre el pavimento. Las aceras estarn asoladas con baldosas hidrulicas
antideslizantes. Todas las juntas llevarn poliestireno expandido y se sellarn con un mastic resistente a los hidrocarburos.
2.3 Cimentaciones Para el clculo de las cimentaciones, se deber estudiar la tensin admisible del terreno. El Contratista tendr en cuenta el estudio geotcnico que se realice, para la posible reconsideracin de la capacidad portante del terreno.
Las cimentaciones y zapatas de las edificaciones, as como de la marquesina se proyectarn en hormign armado. Lo materiales a emplear debern cumplir las debidas condiciones, debindose realizar los ensayos e inspecciones indicadas en normas, para el control a nivel normal. A la Direccin de Obra, se le debern presentar los resultados de los ensayos realizados, para su aprobacin, pudiendo sta rechazar cualesquiera de los materiales que no cumplan o anteriormente indicado, as como la obra ya realizada que no se ajuste a las anteriores especificaciones.
2.4 Marquesinas Las caractersticas de las materiales a emplear sern las siguientes:
La cimentacin ser de hormign para armar, de 175 Kp/cm2 de resistencia caractersticas y armadura de acero AEH-400, debiendo cumplir ambos con lo especificado en la EH-91.
La estructura metlica de la marquesina estar constituida por perfiles laminados o vigas de alma llena, de acuerdo con las normas bsicas MV-103, 104, 106 y 107.
Todas las partes que hayan de quedar ocultas despus del montaje estarn debidamente recubiertas de un capa de imprimacin de silicato de zinc, excepto los elementos embebidos en el hormign. Las placas de asiento se nivelarn con tornillos de nivelacin e irn sobre 5 cm. de mortero de cemento sin retraccin. Lo pernos de anclaje estarn realizados por el taller que realice la estructura metlica de la marquesina y con las caractersticas indicadas en los planos. La pintura de la estructura metlica se llevar a cabo de acuerdo con las especificaciones.
3 Instalacin mecnica
3.1 Obra civil complementaria La obra civil necesaria para completar las instalaciones mecnicas se realizar de acuerdo con los materiales, unidades de obra y ejecucin de las mismas expresadas en el presente documento, debindose tener en cuenta, adems, lo siguiente:
La profundidad mnima para zanjas de tuberas se determinar de manera que las mismas resulten protegidas de los efectos del trfico, heladas y cargas exteriores, as como evitar interferencias con otros servicios.
Como norma general la profundidad mnima ser tal que la generatriz superior de la tubera quede a 60 cm. de la rasante definitiva del terreno.
Las excavaciones necesarias para la ejecucin de uniones de las tuberas se realizarn despus de que el fondo de la zanja haya sido nivelado, con el fin de que la tubera descanse sobre el fondo ya nivelado. Se tendr mucho cuidado de anclar por medio de bloques de
hormign todos aquellos elementos que puedan originar desviaciones perjudiciales para la conduccin. Si las pendientes fueran excesivas, para evitar los deslizamientos de la tubera, se anclarn stas mediante abrazaderas metlicas de hormign. Se colocar una capa de fieltro asfltico de 1 cm. de espesor entre el hormign y la tubera, para que evitar posibles defectos debidos a punzonamiento de los ridos del hormign. A medida que avance el montaje de la tubera, sta se probar hidrulicamente por tramos parciales. Previo a las pruebas, las tuberas debern ser purgadas y limpiadas.
Las zanjas se rellenarn con materiales que no contengan piedras ni terrones de gran tamao, en tongadas de 30 cm., compactadas hasta lograr el cubrimiento completo de la zanja. La colocacin de la tubera en la zanja se efectuar de forma que toda ella repose slidamente sobre el lecho de arena en la zanja, que llevar excavados huecos para realizar las uniones correspondientes. Antes de colocar la tubera en la zanja sta deber estar totalmente limpia. Las zanjas se mantendrn exentas de agua y no se efectuar ningn tendido de tubera cuando el estado de la zanja o del tiempo sea inadecuado.
3.2 Tanques de combustible, fosos y canalizaciones Lo tanques destinados al almacenamiento de combustible sern los reglamentarios, con los espesores no inferiores a 5 mm. en el cuerpo y 6 mm. en los fondos. Los tanques sern suministrados, una vez calibrados por la casa constructora, con sus correspondientes tablas y varillas. No obstante, cuando los mismos se encuentren instalados y enterrados, se proceder a su verificacin, si fuera necesario. Cada tanque dispondr de una boca de hombre en la generatriz superior con los orificios necesarios para el paso de las tuberas de carga, ventilacin, aspiracin y sondeo. Antes de proceder al enterramiento de los tanques, se sometern a una prueba de presin hidrulica de 2 bar, medida en la parte superior durante un tiempo de 2 horas, como mnimo. Cualquier reclamacin que se efecte requerir una nueva prueba. Los depsitos irn enterrados a una profundidad de 1 m como mnimo, medidos desde su generatriz superior hasta la parte inferior del paquete de firmes. En el interior del cubeto los tanques distarn entre s un espacio de 1 m como mnimo y 2 m a edificaciones y muros. La distancia de los tanques a edificaciones ajenas al centro ser de 10 m.
La arena utilizada en el relleno ser silcea y estar lavada, limpia, seca y exenta de arcillas, limos, componentes de azufre, materia orgnica y de cualquier otra sustancia que pudiera atacar qumicamente a los materiales del depsito. El tamao de los granos estar comprendido entre 0,1 y 2 mm. En la arqueta de la boca de hombre quedarn alojadas todas las tuberas de carga, aspiracin, ventilacin y sondeo, siendo su amplitud la suficiente para poder ser desmontada la boca de hombre para poder efectuar la limpieza del mismo.
3.3 Tuberas Las tuberas y accesorios para la conduccin de hidrocarburos sern de acero estirado, de tramos rectos y de la mayor longitud posible, unidos por soldadura a tope por arco elctrico. Las vlvulas sern de material resistente a la corrosin y a los hidrocarburos debiendo asegurar la continuidad elctrica de las tuberas (si no fuese as se puentearn mediante cable). Todos los acoplamientos debern asegurar la continuidad elctrica. Las tuberas de carga se introducirn en el depsito hasta 15 cm. del fondo, tendrn 4 de dimetro y en el extremo se colocarn las bocas de carga normalizadas. Las tuberas de aspiracin sern independientes para cada boquerel, tendrn un dimetro de 2, e irn equipadas con una vlvula de retencin en escuadra antirretorno para impedir el descebado de la bomba. Dichas tuberas se dispondrn con una pendiente hacia igual o superior al 2%, no permitindose sifones o puntos bajos en todo su recorrido. El punto ms bajo de aspiracin estar situado a 15 cm del fondo del depsito. Se impedirn los desplazamientos laterales y las vibraciones de las tuberas. Adems se las proteger con pinturas antioxidantes, de caractersticas apropiadas al ambiente donde se ubiquen.
Toda tubera enterrada, o no, inspeccionable visualmente se proteger de la corrosin mediante una capa de imprimacin antioxidante, as como mediante revestimientos por cintas aislantes de polietileno, autoadhesivas, que aseguren un espesor de 2 mm y una rigidez dielctrica de 15 kV con respecto al terreno. Antes de encintar las tuberas, se someter la instalacin a una prueba de resistencia y estanqueidad de 2 bar durante 24 horas. Cada reparacin requerir una nueva prueba. Todas las tuberas y accesorios metlicos estarn conectados a la red de tierra.
3.4 Brazos de carga y sistema de impulsin Constar de grupo de bombeo de 1000 l/min. a 3 bar con bomba de paletas, vlvula de by-pass y motor elctrico antideflagrante a 1500 rpm. Dispondr de contador electrnico ME 2000 o similar y de 3 brazos de carga con 3 articulaciones aptos para instalaciones con radio de accin variable.
4 Instalacin elctrica
4.1 Acometida y centro de transformacin De acuerdo con las especificaciones de la compaa suministradora de energa, la conexin de BT tendr lugar en el punto de acometida que se nos indique.
4.2 Cuadros elctricos Estarn construidos con material no inflamable y tendrn unas dimensiones adecuadas para acoger los puestos definidos en los planos unificares correspondientes.
En cuanto al cuadro exterior de alumbrado de accesos y aparcamiento ser estanco y dispondr de un grado de proteccin adecuado. Todos los cuadros se sealizarn mediante placa indicadora.
4.3 Conductores Estarn constituidos por un aislamiento de PVC que posea un grado apropiado de termoplasticidad y les permita funcionar en servicio permanente, con temperaturas en cobre de 75 a 80 C, no presentando en ningn caso defectos por autocalentamiento. El conductor consistir en un hilo de cobre electroltico recocido, disponiendo cada cable de tantos conductores como sean necesarios en la instalacin y constando cada uno de ellos de una cubierta de cinta de tela y de una envoltura aislante de material termoplstico. Estos cables soportarn una tensin de prueba entre fases de 3000 V durante 15 min. y una tensin de servicio de 1000 V (LW-21029). Los conductores debern ser fcilmente identificables, especialmente los conductores neutro y de proteccin:
Neutro Proteccin Fases
La cajas de derivacin sern la adecuadas para cada modelo de bandeja y en caso de canalizacin empotrada, sern de material aislante y tapa del mismo material ajustable a presin, rosca o tornillos y llevarn huellas de ruptura al paso de los tubos. Los conductores activos deben poder seccionarse en cualquier punto de la instalacin en que se deriven, utilizando un borne de conexin de forma que permite la separacin de cada circuito derivado del resto de la instalacin. Los conductores sern los que figuran en el presente proyecto y debern estar de acuerdo con la recomendacin UNESA-3403, con las
10
especificaciones de la norma UNE-21016 y con las normas de la Compaa Suministradora, H.E.S.A. El cobre empleado en los conductores ser cobre puro de calidad y resistencia mecnica del 99% de cobre electroltico. Los cables de cobre cumplirn la norma UNE-21012.
4.4 Diferenciales e interruptores magnetotrmicos Los diferenciales estarn constituidos por envolvente con sistema aislante de conexiones y dispositivo de proteccin de defecto y desconexin. Los interruptores automticos magnetotrmicos estarn
constituidos por una envolvente del sistema de conexiones y de proteccin contra sobrecargas y cortocircuitos. El poder de corte ser el especificado en los planos para cada interruptor.
4.5 Interruptores, conmutadores y enchufes Los interruptores y conmutadores sern empotrables, constituidos por bases aislantes con bornes para conexin de conductores, mecanismo de interrupcin o conmutacin, soporte metlico de fijacin con dispositivo de sujecin a la caja, mando accionable y placa de cierre aislante. La conexin de los interruptores se realizar sobre el conductor de fase. La intensidad nominal de estos mecanismos en ningn caso ser inferior a 10 A. Las bases de los enchufes sern empotradas, constituidas por bases aislantes con bornes para la conexin de conductores de fase, neutro y proteccin. Dos alvolos para enchufe de clavija y dos patillas laterales para contacto del conductor de proteccin.
11
En algunos casos, en lugar de estas patillas se dispondr de un tercer alvolo que dispondr tambin de soporte metlico con dispositivo de fijacin a la caja de cierre aislante. Todas las tomas de corriente, sin excepcin, estarn provistas de un contacto de puesta a tierra.
4.6 Tomas de tierra A fin de limitar la tensin que puedan presentar en un momento dado las masas metlicas de los bculos o columnas del alumbrado y los centros de mando se instalar en todos ellos la correspondiente toma de tierra para lograr una resistencia que no pueda dar lugar a tensiones superiores a 24 V. La seccin de un electrodo no debe ser inferior a de la seccin del conductor que constituye la lnea principal de tierra. Las longitudes mnimas de estos electrodos no sern inferiores a 2 m, si son necesarias dos picas en paralelo, con el fin de conseguir una resistencia de tierra admisible, la separacin entre ellas es recomendable que sea igual, por lo menos, a la longitud enterrada de las mismas; si son necesarias varia picas conectadas en paralelo la separacin entre ellas deber ser mayor que el caso anterior. El electrodo se dimensionar de forma que su resistencia de tierra no sea superior al valor especificado para ella en cada caso. Este valor de resistencia ser tal que cualquier masa no pueda dar lugar a tensiones superiores a 24 V en local o emplazamiento conductor y 50 V en los dems casos. La revisin de las tomas de tierra deber ser obligatoriamente comprobada por los servicios oficiales en el momento de dar de alta la instalacin para su funcionamiento.
12
La comprobacin se har anualmente en la poca en que el terreno est ms seco, en lugares poco favorables para la buena conservacin del electrodo y cada cinco aos.
5 Materiales
A continuacin se establecen las condiciones que deben cumplir los materiales necesarios. Si alguno no se considerara en este Pliego y fuera necesario, se escogera de primera calidad y no se podr utilizar mientras el Ingeniero Director no lo haya reconocido y haya dado su aprobacin. Podr rechazarlo si considerara que no se cumplen las condiciones necesarias para el objetivo que cubra dicho material. 5.1 Agua La instruccin para el proyecto y ejecucin de obras de hormign establece las condiciones necesarias del agua para el lavado de arenas, piedras y ladrillos y para la composicin del hormign. Se considerarn admisibles sin necesidad de ensayos previos las aguas que por sus caractersticas fsico-qumicas sean potables. Por el contrario las aguas cenagosas estarn prohibidas.
5.2 Cemento Se usar cualquier cemento Portland de fraguado lento que cumpla las condiciones establecidas en el vigente Pliego de Prescripciones Tcnicas Generales para la Recepcin de Cemento.
5.3 ridos Para la fabricacin de morteros y hormigones se utilizarn arenas y gravas que tengan cualidades iguales o superiores que las exigidas para el hormign que con ellos se va a fabricar.
13
La arena estar limpia, no contendr impurezas orgnicas y arcillosas y proceder de ros o de cualquier otro lugar siempre que cumpla las condiciones citadas. La grava no ser lajosa, estar limpia de tierras y materiales ajenos. En cuanto a su tamao, no predominar un mismo tipo.
5.4 Morteros El mortero estar formado por rido fino, cemento y agua. Si fuera necesario mejorar alguna propiedad del mismo se usarn productos de adicin. El rido ser exclusivamente de procedencia natural o de machaqueo de productos de cantera. La proporcin entre los componentes se establece de la siguiente forma: una parte de cemento, tres parte de ridos finos y aguas suficiente para dar a la mezcla la consistencia necesaria segn aplicacin. Las partes de cemento y de ridos se miden en volumen. No se permitir el uso de mortero rebajado. La fabricacin del mortero asegurar una buena calidad del mismo. El mortero no se emplear transcurrida media hora desde que se empez a amasar.
5.5 Hormigones En el Pliego que nos ocupa, el hormign quedar definido segn la resistencia caracterstica definida en la instruccin del hormign. El hormign ser plstico de forma que no se produzcan coqueras y refluya la pasta. No se usarn hormigones con un contenido en agua superior al correspondiente a la consistencia fluida. Para la mejora de la trabajabilidad del hormign se usarn plastificantes o superplastificantes pero nunca un aumento de la cantidad
14
5.7 Obras de fbrica Las obras de ladrillo se realizarn con un acabado perfecto en las juntas que vayan a quedar vistas, de forma que el grueso de la junta ms el doble de la anchura de un ladrillo sean igual a la longitud de ste. Los ladrillos se remojarn previamente a su empleo y se deslizarn de forma que tengan trabazn en todos los sentidos, siempre y cuando lo permita el espesor de la obra. El mortero ser de cemento para obras de ladrillo macizo y de yeso para tabiques. Los ladrillos debern estar exentos de cal, piedras o cualquier impureza. Sern duros y homogneos y estarn bien cocidos. No se aceptarn ladrillos con deformaciones en sus aristas. La superficie de rotura presentar un aspecto uniforme, de grano fino. No se exfoliarn ni se secarn rpidamente ni presentarn eflorescencias bajo la accin atmosfrica. Debern absorber una cantidad de agua menor que el 16% de su peso. Las superficies se revestirn con materiales de calidad superior y segn establecen las normas de buena construccin. Las juntas entre losas y baldosines quedarn alineadas en ambas direcciones. Las superficies pintadas no presentarn resaltos ni depresiones.
15
5.8 Aceros Se usar acero A-520-b en todas las estructuras metlicas. Ser dulce y laminado. Las soldaduras se situarn en las secciones indicadas en los planos de ejecucin. Quedarn con las mismas caractersticas que los perfiles continuos. Antes de colocar ningn perfil la Direccin de Obra comprobar que la soldadura es correcta. Las cerchas se construirn segn los planos y medidas sealadas en el proyecto. Las superficies sern regulares y sin defectos superficiales. En caso de que existieran se eliminaran con buril o muela, manteniendo siempre las dimensiones fijadas con las tolerancias necesarias. Ninguna pieza deber presentar pelos, grietas, fisuras, estras y sopladuras. Las unidades que sean agrias en su comportamiento se rechazarn. Se aplicarn pinturas anticorrosivas sobre las superficies una vez limpiadas de xido y de calamina no adherente. Se aplicarn con brocha y pincel, dando dos manos de minio de plomo cubriendo todas las partes metlicas.
6 Normativa
En el siguiente listado se especifican las normas que rigen el diseo y la realizacin del proyecto que nos ocupa:
LEY 34/1998, de 7 de Octubre, sector hidrocarburos. Norma UNE 62.350-99, Tanques de acero para almacenamiento de carburantes y combustibles lquidos. Tanques de capacidad mayor de 3000 litros.
16
Norma UNE 288-93, Especificacin y Cualificacin de procedimientos de soldeo para los materiales metlicos.
Serie UNE 23.500 sobre sistemas contra incendios. Norma UNE 20.322-86, Clasificacin de emplazamientos con riesgo de explosin debido a la presencia de gases, vapores y nieblas inflamables.
Norma UNE 109.502 Informe, Instalacin de tanques de acero enterrados para almacenamiento de carburante y combustibles lquidos.
Parte IV PRESUPUESTO
Presupuesto
002
m2
6.400
1,49
9.536
003 004
m2 m3
6.400 180
0,39 5,50
2.496 990
005
m3
180
6,00
1.080
Total
17.430
007
m2
245
20,25
4.961
008
m2
5.020
12,05
60.491
009
534
9,28
4.956
Presupuesto 010 Solado de aceras con baldosas de vibrazo de 20x20, en color gris, incluso material de agarre, enlechado y formacin de juntas cada 10 cm Seal de trfico vertical de acuerdo a la normativa vigente. Pintado de indicaciones relativas a la circulacin aparcamiento. m2 78 13,36 1.042
ud ud
3 1
186,39 390,00
014
35,3
25,08
885,32
015
36,1
28,69
1.035,71
016
10,4
29,12
302,85
017
11,5
30,73
353,40
018
ud
138,45
1.246,05
019
m3
17,8
13,15
234,07
Presupuesto 020 Canaleta para recogida de aguas formada por solera de hormign, formando canal, fbrica de ladrillo de 1 pie de espesor, enfoscado y bruido interior, suministro y colocacin de rejilla de fundicin de 40 cm de ancho, arqueta ciega para conexin con saneamiento de pluviales, completamente terminada Arqueta sumidero de 40x40x40 cm. Formada por solera de hormign, fbrica de ladrillo cermico de 0,5 pies de espesor, enfoscado y bruido interior rejilla de hierro fundido, completamente terminada Arqueta de registro de 38x26x50 cm. Realizada en fbrica de ladrillo macizo de 0,5 pies de espesor recibido con mortero de cemento, enfoscada y bruida en su interior, solera de hormign (HN-20 N/mm2) y tapa de hormign armado Pozo de registro de 1 m dimetro interior y 3 m de profundidad, formado por solera de hormign, fbrica d ladrillo cermico de 1 pie de espesor, enfoscado, incluido cerco y tapa de hierro fundido, completamente terminado Suministro y colocacin de separador de hidrocarburos prefabricado, marca PASSAVANT modelo COALISTOR o similar, capacidad 5 l/s, volumen total 4.000 l, con sedimentador incorporado, incluo obra civil necesaria y 2 tapas resistentes al trfico ligero y colocado. Conexin al saneamiento existente, incluso grifo y obra civil para toma de muestras y reposicin de pavimentos. m 72,6 50,74
3 3.683,72
021
ud
102,36
409,44
022
ud
53,75
53,75
023
ud
537,42
537,42
024
ud
5.559
5.559
025
ud
638,73
638,73
Total
16.671,96
Presupuesto
027
8,3
15,25
126,58
028
28,8
29,12
839,53
029
ud
1.315
1.315
030 031
ud ud
1 1
74 134,79
74 134,79
032 033
ud ud
1 1
302,56 453,57
302,56 453,57
Total
3.299,62
Presupuesto 035 Arqueta de registro de 38x26x50 cm. Realizada en fbrica de ladrillo macizo de 0,5 pies de espesor recibido con mortero de cemento, enfoscada y bruida en su interior, solera de hormign (HN-20 N/mm2) y tapa de hormign armado Tubera de PVC de 150 mm serie F de Saenger gris, incluidos injertos y dems accesorios, totalmente instalada Tubera de PVC de 200 mm serie F de Saenger gris, incluidos injertos y dems accesorios, totalmente instalada Tubera de PVC de 250 mm serie F de Saenger gris, incluidos injertos y dems accesorios, totalmente instalada ud 1 52,75 52,75
036
60,7
18,75
1.138,13
037
36,4
25,08
912,91
038
6,7
28,69
192,22
Total
2.572,9
040
ud
220,1
220,1
041 042
ud m
1 16,3
120 8,16
120 133,01
Total
596,5
Presupuesto
Total
21.411
2 Edificio principal
2.1 Cimentacin
N 044 045 Concepto Encofrados y desencofrados en zunchos de cimentacin Hormign HA-25 armado superior e inferiormente, con acero B500S, 6D16 c/20 Solera de hormign armado de 20 cm de espesor con armado mnimo Hormign HA-25 armado inferiormente, con acero B500S, D12 c/25 (zapata corrida) Unidad m2 m3 Cantidad 30,54 12,615 Precio unitario 15,11 106,08 Importe total 461,46 1.338,2
046
m2
136,7
26,3
3.595,21
047
m3
13,43
97,5
1.309,43
Total
6.704,29
2.2 Estructura
N 048 Concepto Muro de fbrica de ladrillo de 1 pie de espesor, enfoscado en su interior (segn proyecto) Pilares de acero S275 de seccin circular hueca de 8 cm de dimetro Pilares de acero S275 B500S, HEB-120 Losa de 16 cm de espesor, armada superior e inferiormente con redondos en B500S de dimetro 12 cada 20 cm (zuncho de borde incluido) Unidad m2 Cantidad 51,4 Precio unitario 40,8 Importe total 2.097,12
049
m3
205,69
1,63
335,3
050 051
m2 m3
492,3 160,92
1,6 64,6
802,45 10.389
Total
13.623,84
Presupuesto
053 054
ud ud
2 2
118 124
236 248
055
m2
17,7
254
4.496
056 057
m2 m3
48,8 112,75
17,2 29,15
841,31 3.286,7
058
m2
31,4
33,4
1.049,7
Total
10.721,14
ud m2 ud ud ud
1 130 1 1 1
Presupuesto
3 Marquesina
3.1 Cimentacin
N 065 Concepto Hormign HA-25 armado superior e inferiormente, con acero B500S, 3D16 c/25 (zapatas y vigas de atado aprox.) Encofrados y desencofrados en zunchos de cimentacin Unidad m3 Cantidad 34,8 Precio unitario 106,1 Importe total 3.691,58
066 Total
m2
55,6
15,1
840 4.531,7
3.2 Estructura
N 067 068 069 070 Total Concepto Perfil IPE-400 en acero S-275 Perfil IPE-160 en acero S-275 Perfil HEB-220 en acero S-275 Cubierta plana de acero Unidad kg kg kg m2 Cantidad 3.120 2.308 2.185 280 Precio unitario 1,63 1,63 1,63 49,31 Importe total 5.085,6 3.762,04 3.561,55 13.807 26.215,99
Presupuesto
4 Sealizacin
4.1 Cimentacin
N 072 Concepto Hormign H-25, armado superior e inferior en acero B500S, 9D16 c/25 Encofrados y desencofrados en zunchos de cimentacin Unidad m3 Cantidad 3,90 Precio unitario 106,08 Importe total 413,71
073 Total
m2
8,04
15,11
121,48 535,20
4.2 Estructura
N 076 077 Total Concepto Acero S275 en perfil HEB-300 + Platabandas Panel en aluminio (estructura rigidizadora incluida) Unidad kg ud Cantidad 1.639,7 1 Precio unitario 1,63 1.875 Importe total 2.672,7 1.875 4.547,73
5 Vallado exterior
N 078 Concepto Hormign HA-25, armado inferior en acero B500S, D12 c/25 (zapata corrida) Muro de fbrica de ladrillo de 1 pie de espesor, enfoscado en su interior Alambre para vallado (instalacin de barras soportes incluida) Unidad m3 Cantidad 86,92 Precio unitario 106,08 Importe total 9.220,47
080
m2
575,23
40,8
23.469,38
081
m2
343
7,75
2.658,25
Total
35.348,11
Presupuesto
10
6 Instalacin elctrica
6.1 Cableado y conductos
N 082 Concepto Cable de lnea de derivacin del edificio, PVC 0,6/1 4x4 y tubo hueco para conducto elctrico en PVC D20 mm Cable de la lnea de derivacin de la instalacin mecnica, PVC 0,6/1 4x6 y tubo hueco para conducto ectrico en PVC D25 mm Cable de la lnea de derivacin de la puerta corrediza, PVC 0,6/1 2x2,5 y tubo hueco para conducto ectrico en PVC D16 mm Cable de las lnea de derivacin de iluminacin, PVC 0,6/1 4x10 y tubo hueco para conducto ectrico en PVC D32 mm Cable de la lnea de derivacin de acometida, PVC 0,6/1 4x16 y tubo hueco para conducto ectrico en PVC D32 mm Cable de las lneas de la edificacin en H03 VV-K 2 2,5 y tubo hueco para conducto elctrico en PVC D16 mm Cable de alimentacin a bombas y sondas, RMV-06/1 4x2,5 y tubo hueco para conducto elctrico en PVC D16 mm Unidad m Cantidad 17,11 Precio unitario 6,54 Importe total 111,90
083
80,32
7,12
571,88
084
48,22
6,38
307,64
085
190,57
7,48
1.425,46
086
95,32
8,02
764,47
087
78,28
5,27
412,54
088
40,94
6,12
250,55
Total
3.844,44
Presupuesto
11
6.2 Aparamenta
N 089 Concepto Caja general de mando y proteccin con nivel de seguridad IP-53. -1 Int. Aut. Mag-term. 32 A -1 Int. Aut. Mag-term. 25 A -1 Int. Aut Mag-term. 16 A -1 Int. Aut. Mag-term. 10 A -2 Int. Aut. Mag-term. 6 A -5 Int. Aut. Dif. 25 A 30 mA -1 Int. Aut. Dif. 40 A 30 mA Cuadro tipo de distribucin, proteccin y mando para uso privado con grado de proteccin IP-53 -4 Int. Aut. Mag-term. 6 A -1 Int. Aut. Mag-term 10 A Cuadro tipo de distribucin, proteccin y mando para uso privado con grado de proteccin IP-3x -5 Int. Aut. Mag-term. 6 A -1 Int. Aut Mag-term. 10 A Cuadro tipo de distribucin, proteccin y mando para uso privado con grado de proteccin IP-53 -1 Contactor In 4 A -1 Fusible am. In 4 A -1 Int. Aut. Mag-term. 10 A Unidad ud Cantidad 1 Precio unitario 896 Importe total 896
090
ud
865
865
091
ud
620
620
092
ud
420
420
Total
2.801
094
ud
103,31
413
095
ud
153
920
096
ud
75
150
Presupuesto 097 Luminaria fluorescente de dos unidades con consumo previsto de 2x65 W (instalacin y conexionado incluidos) Suministro y montaje de la instalacin de fuerza del edificio formada por 12 bases de enchufe (conexionado y accesorios incluidos) Suministro y montaje de red de alumbrado del edificio ud 7 177,86
12 1.245,02
098
ud
193,42
386,8
099 Total
ud
379,44
379,4 5.343,36
101
370
3,25
1.203
102
ud
497,3
497,3
103 Total
ud
575
575 2.360,18
105 Total
ud
203,86
611,58 1.305,28
Presupuesto
13
8 Instalacin mecnica
8.1 Depsitos
N 106 Concepto Excavacin de los fosos para cubetos con excavadora incluido transporte posterior Cubeto para la instalacin de los tanques (con solera de hormign armado H-200 de 30 cm de espesor fbrica de ladrillo macizo de 1 pie de espesor enfoscado) Arena de relleno, silcea, con un tamao de grano entre 0,1 y 2 mm, lavada, limpia, seca y exenta de arcillas, limos, componentes de azufre, materia orgnica y cualquier otra sustancia agresiva Tanque de almacenamiento de hidrocarburos lquidos de 50 m3. Doble pared, acero laminado. Revestidos interiormente con pintura resistente a los derivados del petrleo y exteriormente contra la corrosin y realizados segn norma UNE correspondiente Arqueta de boca de hombre con forma troncocnica de ladrillo macizo de 1 pie de espesor, enfoscada interiormente Tapa para arqueta segn norma Sistema electrnico de sondeo (precisin estndar). Elementos necesarios para su conexin a PC e instalacin incluidas Sistema de deteccin de fugas, elementos necesarios para su conexin a PC e instalacin incluidas Instalacin electrnica para gestin de la instalacin Vlvula de sobrellenado 4", incluida instalacin y accesorios para montaje Unidad m3 Cantidad 1.045 Precio unitario 6 Importe total 6.270
107
21.078
63.234
108
m3
630
4,8
3.024
109
ud
4.150,35
29.052,45
110
ud
453,67
3.175,69
111 112
ud ud
7 1
630,5 6.247,37
4.413,5 6.247,37
113
ud
228,86
1.602,02
114 115
ud ud
1 7
4.550 382,7
4.550 2.678,76
Total
124.247,8
Presupuesto
14
117
ud
413
2.891
118 119
ud ud
7 7
101 105
707 735
120
61,45
50,45
3.100,15
121 Total
ud
453,67
3.175,69 14.745,6
123
ud
95
50,45
4.793
124
ud
3.250
3.250
125
ud
3.175
3.175
Presupuesto Total
15 28.426,3
9 Presupuesto final
Urbanizacin del rea de servicio Edificio central Marquesina Sealizado Vallado exterior Instalacin elctrica Instalacin contra incendios Instalacin mecnica Total 151.210,9 5 35.889,77 34.747,69 5.618,12 35.348,11 14.348,98 1.305,28 167.419,7 445.888,6 2