Академический Документы
Профессиональный Документы
Культура Документы
3 Connection Examples
Figure A-14
525
A Appendix
Figure A-15
Connection example 7UT613 for an earthed auto-transformer with current transformer between starpoint and earthing point
526
Figure A-16
Connection example 7UT613 for an earthed auto-transformer with brought-out delta winding capable of carrying load (tertiary winding) and current transformer between starpoint and earthing point
527
A Appendix
Figure A-17
Connection example 7UT613 for an auto-transformer bank with protected object auto-transformer branchpoints, with individually accessible earthing electrodes equipped with CTs (M3). The CTs on the earthing side constitute a separate side for current comparison for each transformer of the bank. The starpoint of the CTs at M3 is routed via an auxiliary input (IZ1), which allows realisation of restricted earth fault protection and/or earth overcurrent protection.
528
Figure A-18
Connection example 7UT613 for a single-phase power transformer with current transformer between starpoint and earthing point
Figure A-19
Connection example 7UT613 for a single-phase power transformer with only one current transformer (right side)
529
A Appendix
Figure A-20
Figure A-21
Connection example 7UT613 as transversal differential protection for a generator with two windings per phase
530
Figure A-22
Connection example 7UT613 for an earthed shunt reactor with current transformer between starpoint and earthing point
531
A Appendix
Figure A-23
Connection example 7UT613 as high-impedance protection on a transformer winding with earthed starpoint (the illustration shows the partial connection of the high-impedance protection); IZ3 is connected to the high-sensitivity input
532
Figure A-24
Connection example 7UT613 for a three-phase power transformer with current transformers between starpoint and earthing point, additional connection for high-impedance protection; IZ3 connected to the highsensitivity input
533
A Appendix
Figure A-25
Connection example 7UT613 as single-phase busbar protection for 7 feeders, illustrated for phase L1
534
Figure A-26
Connection example 7UT613 as busbar protection for 6 feeders, connected via external summation transformers (SCT) partial illustration for feeders 1, 2 and 6
535
A Appendix
A.3.2
Figure A-27
Voltage connections to three wye-connected voltage transformers (only in 7UT613 and 7UT633)
536
Figure A-28
Voltage connections to three wye-connected voltage transformers with additional open-delta windings (e-nwindings; only in 7UT613 and 7UT633)
537
A Appendix
A.3.3
Figure A-29
538
A.4
= rated symmetrical short-circuit current factor (example: CT 5P20 KSSC = 20) = effective symmetrical short-circuit current factor = rated transient dimensioning factor = maximum symmetrical through flowing fault current = CT rated primary current = CT rated secondary current = secondary winding d.c. resistance at 75 oC (or other specified temperature) = rated resistive burden = Rlead + Rrelay = connected resistive burden = primary time constant (net time constant) = knee-point voltage in V (r.m.s.) = relay burden
with: I A = single conductor length from CT to relay in m = specified resistance = 0.0175 mm2/m (copper wires) at 20 oC (or other specified temperature) conductor cross-section in mm2
The transient rated dimensioning factor Ktd depends on the device version and the primary time constant Tp. For the devices 7UT613/63x with a required saturation-free time of only 1/4 period, the influence of Tp is negligible. For CT's that are defined by the rated symmetrical short-circuit current factor Kssc and the rated burden Rb (e.g. 5P, 10P), the effective Kssc can be calculated by the formula:
539
A Appendix
The values of an IEC class P transformer can be converted to the values for an IEC class PX (BS class X) transformer by using the following formula:
Class C of this standard defines the CT by its secondary terminal voltage at 20 times rated current, for which the ratio error shall not exceed 10%. Standard classes are C100, C200, C400 and C800 for 5A rated secondary current. The approximate terminal voltage can be derived from the IEC values, as follows: ANSI transformer definition Us.t.max = 20 5A Rb Kssc/20 with: Rb = Pb/Isn2 and Isn = 5A one derives at Us.t.max = Pb Kssc/5A Example: IEC 60044: 600/5, 5P20, 25VA ANSI C57.13: Us.t.max = 25VA 20/5A = 100V, in accordance with class C100
The calculations listed above are simplified in order to facilitate a quick and safe CT calculation/verification. An accurate calculation/verification can be carried out with the Siemens CTDIM program as from V3.21. The results of the CTDIM program have been released by the device manufacturer.
540
where: InO UnO INrelay SNmax = rated current of the protected object (in relation to the parameterised rated current) = parameterised rated current of the protected object = nominal device current = maximum (rated) power of the protected object (for transformers: side with the largest (rated) load)
Caution: If earth fault differential protection is used, the requirement for the phase current transformer of the REF side is as follows: 1/4 FAdap 4, (for the starpoint transformer remains 1/8 FAdap 8)
Figure A-30
The CB layout within the power station unit is not specified. xd Uk Rrelay = sub-transient direct-axis reactance of the generator in p.u. = transformer short-circuit voltage HV - LV in % = assumed with 0.1 , (the consumption of the above devices is below 0.1 VA)
541
A Appendix
with: c SNO
M
= voltage factor (for generators: 1,1) = nominal power of the transformer in kVA = nominal voltage of the transformer in kV = nominal power of the generator in kVA = nominal voltage of the generator in kV
UNO
M
SNG UNG
542
A.5
Default Settings
When the device leaves the factory, a large number of LED indicators, binary inputs and outputs as well as function keys are already preset. They are summarized in the following tables.
A.5.1
LEDs
Table A-1 LEDs LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11 LED12 LED13 LED14 LED Indication Presettings Allocated Function Relay TRIP Relay PICKUP >Buchh. Trip no default setting no default setting no default setting no default setting no default setting no default setting no default setting no default setting no default setting Error Sum Alarm Alarm Sum Event FaultConfig/Set Function No. 511 501 392 140 160 311 Description Relay GENERAL TRIP command Relay PICKUP >Tripp. stage from Buchholz protection Error with a summary alarm Alarm Summary Event Fault in configuration / setting
A.5.2
Binary Input
Table A-2 Binary Input BI1 BI2 Binary input presettings for all devices and ordering variants Allocated Function >Reset LED >Buchh. Trip Function No. 5 392 Description >Reset LED >Tripp. stage from Buchholz protection
A.5.3
Binary Output
Table A-3 Output relay presettings for all devices and ordering variants Allocated Function Relay TRIP Relay PICKUP >Buchh. Trip Error Sum Alarm Alarm Sum Event Function No. 511 501 392 140 160 Description Relay GENERAL TRIP command Relay PICKUP >Tripp. stage from Buchholz protection Error with a summary alarm Alarm Summary Event
543
A Appendix
A.5.4
Function Keys
Table A-4 Applies to all devices and ordered variants Allocated Function Display of operational instructions Display of primary operational measured values An overview of the last 8 network faults >QuitG-TRP Resetting the reclosure interlocking Function No. Description
Function Keys F1 F2
F3 F4
544
A.5.5
Default Display
For devices with a four-line display, you can scroll among the basic displays shown below. The numerical values shown are examples. The device will display only those values that make sense for the current application. For instance, voltages will only be shown if the device is provided with voltage inputs and these inputs have been configured; with single-phase transformers there will be no phase L2.
Figure A-31 *)
545
A Appendix
For devices with a graphic display, the basic displays shown below may appear: The device will display only those values that make sense for the current application. For instance, voltages and powers will only be shown if the device is provided with voltage inputs and these inputs have been configured; with single-phase transformers there will be no phase L2.
Figure A-32 *)
546
A.5.6
Figure A-33
The first chart converts the binary input >DataStop from a single-point indication (SP) into an internal single-point indication (IM). The second chart implements a reclosure interlocking feature which prevents a reclosure of the circuit breaker following a device trip until the trip has been acknowledged manually.
547
A Appendix
A.6
Protocol-dependent Functions
IEC IEC 61850 Eth60870-5-103 ernet (EN100) PROFIBUS FMS PROFIBUS DP DNP3.0 Modbus ASCII/RTU Additional Service interface (optional) Yes
Protocol Function
Yes
Yes
Yes
Yes
Yes
Yes Yes
Yes Yes
Yes No. Only via additional service interface No. Only via additional service interface
Yes No. Only via additional service interface No. Only via additional service interface
Yes
Yes
No. Yes Only via additional service interface No. Yes Only via additional service interface
Yes
Yes
User-defined User-defined User-defined Yes annunciaannunciaannunciations in CFC tions in CFC tions in CFC Via protocol; DCF77/IRIG B; Interface; Binary input Yes Via protocol; DCF77/IRIG B; Interface; Binary input Yes Via DCF77/IRIG B; Interface; Binary input No Yes
Time synchroni- Via sation protocol; DCF77/IRIG B; Interface; Binary input Annunciations Yes with time stamp Commissioning tools Indication measured value blocking Generation of test annunciations (DIGSI) Mode Transmission mode Baud rate Connection to device Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Physical properties Asynchronous Cyclical/event 4800 to 38400 Synchronous Cyclical/event Asynchronous Cyclical/event Asynchronous Cyclical up to 1.5 Mbaud Electrical: RS485 optical: ST connector (double ring) Asynchronous Cyclical/event 2400 to 19200 Electrical: RS485 optical: ST connector Asynchronous Cyclical 2400 to 19200 Electrical: RS485 optical: ST connector 2400 to 38400 Electrical: RS232 RS485 optical. ST connector Yes
up to 100 Mbaud up to 1.5 Mbaud Electrical: RS485 optical: ST connector (single or double ring)
RTD-box 7XV5662-xAD
548
A.7
Addr. 103 105
Functional Scope
Parameter Grp Chge OPTION PROT. OBJECT Setting Options Disabled Enabled 3 phase transf. 1 phase transf. Autotransf. Autotr. node Generator/Motor 3ph Busbar 1ph Busbar Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Enabled Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Default Setting Disabled 3 phase transf. Comments Setting Group Change Option Protection Object
DIFF. PROT. REF PROT. REF PROT. 2 COLDLOAD PICKUP DMT/IDMT Phase
Differential Protection Restricted earth fault protection Restricted earth fault protection 2 Cold Load Pickup DMT / IDMT Phase
122
DMT/IDMT 3I0
Disabled
124
DMT/IDMT Earth
Disabled
127 130
Disabled Disabled
132
DMT/IDMT Phase3
Disabled
549
A Appendix
Addr. 134
Setting Options Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled Definite Time TOC IEC TOC ANSI DT/thermal Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Enabled Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled 2 Binary Inputs 1 Binary Input
136
DMT/IDMT 3I0 3
Disabled
138
DMT/IDMT Earth2
Disabled
140
UNBALANCE LOAD
Disabled
142
THERM. OVERLOAD
Disabled
143 144
Disabled Disabled
150 151 152 153 156 170 171 180 181 182
REVERSE POWER FORWARD POWER UNDERVOLTAGE OVERVOLTAGE FREQUENCY Prot. BREAKER FAILURE BREAKER FAIL. 2 DISCON.MEAS.LOC M.V. SUPERV Trip Cir. Sup.
Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Enabled Disabled
Reverse Power Protection Forward Power Supervision Undervoltage Protection Overvoltage Protection Over / Underfrequency Protection Breaker Failure Protection Breaker Failure Protection 2 Disconnect measurment location Measured Values Supervision Trip Circuit Supervision
550