Appendix 12.

Operational Noise Calculations and Results

Operational Noise Calculations and Results


Absorption Coefficient/SRI Data
Absorption
Coefficient Data
Standard brickwork
Solid timber door
Ventilation grille per
m2
20g galvanised sheet
steel
Smooth unpainted
concrete

Reference

63

125

250

500

1000

2000

4000

8000

A
B

0.05
0.14

0.05
0.14

0.05
0.14

0.04
0.10

0.02
0.06

0.04
0.08

0.05
0.10

0.05
0.10

0.60

0.60

0.60

0.60

0.60

0.60

0.60

0.60

0.35

0.35

0.39

0.44

0.49

0.54

0.57

0.57

0.01

0.01

0.01

0.02

0.02

0.02

0.05

0.05

Reference

63

125

250

500

1000

2000

4000

8000

36

37

40

46

54

56

56

56

19

22

26

24

23

20

20

20

10

10

10

10

10

10

10

10

14

20

26

32

38

38

38

REFERENCES
Danish Buildings Research Institute (derived from other sources - ODEON)
Bobran, H.W., "Handbuch der Bauphysik" Verlag Ilstein Berlin 1973 (Odeon)
Flakt Woods, Practical guide to noise control. 5th Edition
Acoustics in the Built Environment, Duncan Templeton, Butterworth Architecture, 1993
NRCC, Noise Control in Buildings, Cyril M.Harris
Building Bulletin 93

C
B
A
D
E
F

SOUND
REDUCTION DATA
Single leaf block
work fair faced
Solid core wood
door, no seals
around perimeter
Ventilation grille
20g galvanised sheet
steel

Noise Breakout from Gas Compressor Housing


Room Constant Calculation
North Wall Elevation
Dimensions
Total Area
31 x 5.8 = 179.8m2
Assumptions
2 x Roller shutter doors 7.2 x 3.8 = 27.4m2 x 2 = 54.8m2
1 Access door 2.4 x 1.2 = 2.9m2
Total brick wall area 179.8 54.8 2.9 = 122.1m2
South Wall Elevation
Dimensions
Total Area
31 x 5.8 = 179.8m2
Assumptions
Wall is all brickwork with x2 ventilation grilles 1.5 x 9.5 = 14.25 x 2 = 28.5m2
East/West Wall Elevation
Total Area
11.8 x 5.8 = 68.4m2
(11.8 x 2.5)/2 = 14.8m2
Total area = 68.4 + 14.8 = 83.2m2
Assumptions
Wall is all brickwork
Floor Area
Total Area
31.0. x 11.8 = 365.8m2
Assumptions
Floor is all unpainted concrete

Ceiling Area
Total Area
2.52 + 4.152 = 23.5 SQROOT 23.5 =4.8
4.8 x 31 = 148.8 x 2 = 297.6m2
Assumptions
No ceiling treatment applied

BRICK
NORTH
SOUTH
EAST
WEST
FLOOR
CEILING
TOTAL

TIMBER
DOOR

122.1
2.9
151.3
0
83.2
0
83.2
0
0
0
0
0
468.3
2.9
TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
VENTS
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

ROLLER
SHUTTER
DOOR
54.8
0
0
0
0
0
54.8

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
365.8
0
365.8

297.6
0
0
0
0
0
297.6
1217.9

0
28.5
0
0
0
0
28.5

63
23.4
3.0
0.4
3.7
17.1
0.5
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
23.4
23.4
18.7
9.4
18.7
23.4
3.0
3.0
6.0
6.0
6.0
8.9
0.4
0.4
0.3
0.2
0.2
0.3
3.7
3.7
7.3
7.3
7.3
18.3
17.1
17.1
17.1
17.1
17.1
17.1
0.5
0.5
1.1
1.1
1.1
1.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
23.4
8.9
0.3
18.3
17.1
1.6
0.0
0.0

48.1

48.1

69.7

48.1

50.5

41.0

50.4

69.7

0.039 0.039 0.039 0.041 0.034 0.041 0.057 0.057


50.1

50.1

50.1

52.7

42.4

52.6

73.9

73.9

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Compressor Building
2 x Mopico compressors@ 107.2Lw and 6 x control valves @ 75 Lw
Total internal sound power level
107.2 +107.2 = 110.2dB
75+75+75+75+75+75 = 82.8dB
110.2 + 82.8 = 110.2dB (control valves are negligible)
63

1
2
3
4
5
6

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1
10 X LOG [4]
SWL + [5]

125

250

500

1000

2000

4000

8000

110.2 110.2 110.2 110.2 110.2 110.2 110.2 110.2


50.1 50.1 50.1 52.7 42.4 52.6 73.9 73.9
0.08 0.08 0.08 0.08 0.09 0.08 0.05 0.05
2
2
2
2
2
2
2
0.04 0.04 0.04 0.04 0.04 0.04 0.04
0.12 0.12 0.12 0.12 0.13 0.12 0.09
-9.2
-9.2
-9.2
-9.4
-8.7
-9.4 -10.3
101.0 101.0 101.0 100.8 101.5 100.8 99.9

Total Internal Reverberant Sound Pressure Level @ 500Hz 100.8 dB

2
0.04
0.09
-10.3
99.9

NORTHERN WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500Hz
46
24
10
26

179.8
122.1
2.9
0
54.8
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00306701
0.01154511
0.00000000
0.13765138
0.00000000
0.00000000
0.00000000
0.00084685
30.7
100.8
64.1

SOUTHERN WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500Hz
46
24
10
26

179.8
151.3
0
28.5
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00380048
0.00000000
2.85000000
0.00000000
0.00000000
0.00000000
0.00000000
0.01587208
18.0
100.8
76.8

EASTERN/WESTERN
WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL
TOTAL EXTERNAL SPL

500
46
24
10
26

83.2
83.2
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00208989
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
100.8
48.8

ROOF
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL
TOTAL EXTERNAL SPL

500
46
24
10
26

297.6
0
0
0
297.6
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.74753740
0.00000000
0.00000000
0.00000000
0.00251189
26.0
100.8
68.8

Noise Breakout from Seawater Pumping Station


Room Constant Calculation
North/South Wall Elevation
Dimensions
Total Area
40 x 5.0 = 200.0m2
Assumptions
5 Access door 2.4 x 1.2 = 2.9m2 x 5 = 14.6m2
Total brick wall area 200 14.6 = 185.4m2
East Wall Elevation
Total Area
13.5 x 5.0 = 67.5m2
(13.5 x 2)/2 = 13.5m2
Total area = 67.5 + 13.5 = 81.0m2
Assumptions
Wall has roller shutter door and 2 access doors
Roller Door 4 x 4.4 = 18.0m2
Access Door 2.4 x 1.2 = 2.9m2 x 2 = 5.8m2
Total brick area = 81 18 5.8 = 57.2m2
West Wall Elevation
Total Area
13.5 x 5.0 = 67.5m2
(13.5 x 2)/2 = 13.5m2
Total area = 67.5 + 13.5 = 81.0m2
Assumptions
Wall has x2 Access doors
2.4 x 1.2 = 2.9m2 x 2 = 5.8m2
Total brick area = 81 5.76 = 75.2m2

Floor Area
Total Area
40.0. x 13.5 = 540m2
Assumptions
Floor is all unpainted concrete
Ceiling Area
Total Area
2.02 + 6.752 = 49.6 SQROOT 49.6 =7.0
7.0 x 40 = 280 x 2 = 560m2
Assumptions
No ceiling treatment applied

BRICK
NORTH
SOUTH
EAST
WEST
FLOOR
CEILING
TOTAL

TIMBER
DOOR

185.4
14.6
185.4
14.6
57.2
5.8
75.2
5.8
0
0
0
0
503.2
40.8
TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

ROLLER
SHUTTER
DOOR
0
0
18.0
0
0
0
18.0

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
540.0
0
540.0

0
0
0
0
0
560.0
560.0
1662.0

0
0
0
0
0
0
0

63
25.2
5.6
5.7
5.4
0.0
0.2
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
25.2
25.2
20.1
10.1
20.1
25.2
5.6
5.6
11.2
11.2
11.2
16.8
5.7
5.7
4.1
2.4
3.3
4.1
5.4
5.4
10.8
10.8
10.8
27.0
0.0
0.0
0.0
0.0
0.0
0.0
0.2
0.2
0.4
0.4
0.4
0.5
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
25.2
16.8
4.1
27.0
0.0
0.5
0.0
0.0

42.1

42.1

73.6

42.1

46.6

34.9

45.8

73.6

0.025 0.025 0.025 0.028 0.021 0.028 0.044 0.044


43.1

43.1

43.1

47.9

10

35.6

47.0

77.0

77.0

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Seawater Pumping Station Building
7 x Salt Water Pumps@ 85.0Lw and Electrical Switch Gear @ 75 Lw
Total internal sound power level
85 x7 = 93.5dB
93.5 + 75.0 = 93.5dB (Switch Gear is negligible)

1
2
3
4

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1

5 10 X LOG [4]
6 SWL + [5]

63

125

250

500

1000 2000 4000 8000

93.5
43.1
0.09

93.5
43.1
0.09

93.5
43.1
0.09

93.5
47.9
0.08

93.5
35.6
0.11

93.5
47.0
0.09

93.5
77.0
0.05

93.5
77.0
0.05

2
0.04
0.13

2
0.04
0.13

2
0.04
0.13

2
0.04
0.12

2
0.04
0.15

2
0.04
0.12

-8.8
84.7

-8.8
84.7

-8.8
84.7

-9.1
84.4

-8.2
85.3

-9.0
84.5

2
0.04
0.09
10.4
83.1

2
0.04
0.09
10.4
83.1

Total Internal Reverberant Sound Pressure Level is@500Hz 84.4 dB

11

NORTHERN/SOUTHERN
WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
200
185.4
14.6
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00465704
0.05812365
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00031390
35.0
84.4
43.4

12

EASTERN WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
81
57.2
5.8
0
18
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00143680
0.02309022
0.00000000
0.04521396
0.00000000
0.00000000
0.00000000
0.00086100
30.6
84.4
47.8

13

WESTERN WALL
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
81
75.2
5.8
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00188894
0.02309022
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00030838
35.1
84.4
43.3

14

ROOF
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
560
0
0
0
560
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
1.40665640
0.00000000
0.00000000
0.00000000
0.00251189
26.0
84.4
52.4

15

Noise Breakout from Pump Hall


Room Constant Calculation
Wall 1 and 3
Dimensions
Total Area
24.5 x 5.0 = 122.5m2
Assumptions
All brick wall
Wall 2
Total Area
10.5 x 5.0 = 52.5m2
2.5 x 5.25 = 13.1m2
Total area = 52.5 + 13.1 = 65.6m2
Assumptions
All brick wall
Wall 4
Total Area
10.5 x 5.0 = 52.5m2
2.5 x 5.25 = 13.1m2
Total area = 52.5 + 13.1 = 65.6m2
Assumptions
Wall has access door
4 x 3 = 12.0m2
Total brick area = 65.6 12.0 = 53.6m2
Floor Area
Total Area
25.7 x 10.0 = 257.3m2
Assumptions
Floor is all unpainted concrete
16

Ceiling Area
Total Area
2.52 + 5.252 = 33.8 SQROOT 33.8 =5.8m
5.8 x 24.5 = 142.1 x 2 = 284.2m2
Assumptions
No ceiling treatment applied

BRICK

TIMBER
DOOR

122.5
65.6
122.5
53.6
0
0

0
0
0
12.0
0
0

1
2
3
4
FLOOR
CEILING
TOTAL

ROLLER
SHUTTER
DOOR
0
0
0
0
0
0

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
257.3
0

0
0
0
0
0
284.2

0
0
0
0
0
0
0

TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

63
0.05
0.35
0.14
0.01
0.6
0.35
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
0.05
0.05
0.04
0.02
0.04
0.05
0.35
0.39
0.44
0.49
0.54
0.57
0.14
0.14
0.1
0.06
0.08
0.1
0.01
0.01
0.02
0.02
0.02
0.05
0.6
0.6
0.6
0.6
0.6
0.6
0.35
0.39
0.44
0.49
0.54
0.57
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
0.05
0.57
0.1
0.05
0.6
0.57
0.0
0.0

123.1 123.1 134.4 148.3 154.7 176.4 200.0 200.0


0.1

0.1

0.1

0.1

0.1

0.2

0.2

0.2

139.7 139.7 154.6 173.1 182.0 212.8 248.1 248.1

17

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Seawater Pumping Station Building
12 x Salt Water Discharge Pumps@ 85.0 Lw and 12 x Control Valves @ 75.0 Lw
Total internal sound power level
85 x12 = 95.8dB
75 x12 = 85.8dB
95.8 + 85.8 = 96.2dB
63

1
2
3
4
5
6

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1
10 X LOG [4]
SWL + [5]

125

250

500

1000

2000

4000

8000

96.2 96.2 96.2 96.2 96.2 96.2 96.2 96.2


139.7 139.7 154.6 173.1 182.0 212.8 248.1 248.1
0.03 0.03 0.03 0.02 0.02 0.02 0.02 0.02
2
0.04
0.07
-11.6
84.6

2
0.04
0.07
-11.6
84.6

2
0.04
0.07
-11.8
84.4

2
0.04
0.06
-12.0
84.2

2
0.04
0.06
-12.1
84.1

Total Internal Reverberant Sound Pressure Level @500Hz 84.2 dB


Wall 3 not included as it is adjacent to ECE and Control Room

18

2
0.04
0.06
-12.3
83.9

2
0.04
0.06
-12.5
83.7

2
0.04
0.06
-12.5
83.7

Wall 1
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
112.5
112.5
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00282587
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
84.2
32.2

19

WALL 2
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
65.6
65.6
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00164780
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
84.2
32.2

20

WALL 4
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
65.6
53.6
12
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00134637
0.04777286
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00074877
31.3
84.2
46.9

21

ROOF
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
284.2
0
0
0
284.2
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.71387812
0.00000000
0.00000000
0.00000000
0.00251189
26.0
84.2
52.2

22

Noise Breakout from Booster Pump ECE Room


Room Constant Calculation
Wall 1
Dimensions
Total Area
12 x 2.5 = 30.0m2
Assumptions
1 doorway
Door - 2 x 2 = 4.0m2
Wall - 30 - 4 = 26.0m2
Wall 2
Total Area
10.5 x 2.5 = 26.3m2
2.5 x 5.25 = 13.1m2
Total area = 26.3 + 13.1 = 39.4m2
Assumptions
All brick wall with 1 doorway
2.4 x 1.2 = 2.9m2
Total brick wall area
39.4 2.9 = 36.5m2
Wall 3
Total Area
12.0 x 2.5 = 30.0m2
Assumptions
Wall is all brick
Wall 4
Same as wall 2 but no door, all brick
26.3 + 13.1 = 39.4m2

23

Floor Area
Total Area
12.0. x 10.5 = 126m2
Assumptions
Floor is all unpainted concrete
Ceiling Area
Total Area
52 + 5.252 = 52.6 SQROOT 52.5 = 7.3m
7.3 x 12 = 87 x 2 = 174m2
Assumptions
No ceiling treatment applied

BRICK
1
2
3
4
FLOOR
CEILING
TOTAL

26.0
36.5
30.0
39.4
0.0
0.0

TIMBER
DOOR
4.0
2.9
0.0
0.0
0.0
0.0

ROLLER
SHUTTER
DOOR
0.0
0.0
0.0
0.0
0.0
0.0

CONCRETE
CEILING LOUVRES
FLOOR
0.0
0.0
0.0
0.0
126.0
0.0

0.0
0.0
0.0
0.0
0.0
174.0

0.0
0.0
0.0
0.0
0.0
0.0

TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

63
6.6
60.9
1.0
3.7
0.0
0.0
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
6.6
6.6
5.3
2.6
5.3
6.6
60.9
67.9
76.6
85.3
94.0
99.2
1.0
1.0
0.7
0.4
0.6
0.7
3.7
3.7
7.4
7.4
7.4
18.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

72.2

72.2

79.1

90.0

95.8

0.1

0.1

0.1

0.1

0.1

80.7

80.7

89.5

8000
6.6
99.2
0.7
18.6
0.0
0.0
0.0
0.0

107.2 125.1 125.1


0.2

0.2

0.2

103.6 111.3 127.1 153.0 153.0

24

Reverberant Sound Pressure Level Inside Building


Assumed Contents of ECE Building
Electrical Control Equipment @75dB Lw

1
2
3
4

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1

5 10 X LOG [4]
6 SWL + [5]

63

125

250

500

1000

75
80.7
0.05

75
80.7
0.05

75
75
75
75
75
75
89.5 103.6 111.3 127.1 153.0 153.0
0.04 0.04 0.04 0.03 0.03 0.03

2
0.04
0.09
10.5
64.5

2
0.04
0.09
10.5
64.5

2
0.04
0.08
10.7
64.3

4000

8000

2
0.04
0.08

2
0.04
0.08

2
0.04
0.07

2
0.04
0.07

2
0.04
0.07

-11.1
63.9

-11.2
63.8

-11.5
63.5

-11.8
63.2

-11.8
63.2

Total Internal Reverberant Sound Pressure Level is 63.9 dB


Wall 3 not included as it is adjacent to ECE and Control Room

25

2000

Wall 1
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
26
22
4
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00055262
0.01592429
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00063373
32.0
63.9
26.0

26

WALL 3 and 4
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
30
30
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00075357
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
63.9
11.9

27

Roof
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
174
0
0
0
174
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.43706824
0.00000000
0.00000000
0.00000000
0.00251189
26.0
63.9
31.9

28

Noise Breakout from Booster Pump Control Room


Room Constant Calculation
Wall 1
Dimensions
Total Area
5 x 1 = 5m2
5/2 = 2.5m2
2.5 + 5 = 7.5m2
Assumptions
1 doorway
Door 2.4 x 1.2 = 2.9m2
Wall 7.5 2.9 = 4.6m2
Wall 2
Total Area
4 x 10 = 40.0m2
Assumptions
All brick wall with 1 doorway
2.4 x 1.2 = 2.9m2
Total brick wall area
40.0 2.9 = 37.1m2
Wall 3
Same as wall 1 but with no door, all brick
7.5m2
Assumptions
Wall is all brick
Wall 4
Same as wall 2 but no door, all brick
4 + 10 = 40.0m2

29

Floor Area
Total Area
5.5 x 10 = 55m2
Assumptions
Floor is all unpainted concrete
Ceiling Area
Total Area
52 x 12 = 26.0 SQROOT= 5.1m2
5.1 x 10 = 51m2
Assumptions
No ceiling treatment applied

BRICK
1
2
3
4
FLOOR
CEILING
TOTAL

4.6
37.1
7.5
40.0
0
0

ROLLER
SHUTTER
DOOR

TIMBER
DOOR
2.9
2.9
0
0
0
0

0
0
0
0
0
0

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
40
0

0
0
0
0
0
51

0
0
0
0
0
0

TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

63
4.5
17.9
0.8
3.7
0.0
0.0
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
4.5
4.5
3.6
1.8
3.6
4.5
17.9
19.9
22.4
25.0
27.5
29.1
0.8
0.8
0.6
0.3
0.5
0.6
3.7
3.7
7.4
7.4
7.4
18.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
4.5
29.1
0.6
18.6
0.0
0.0
0.0
0.0

26.8

26.8

28.9

34.0

34.6

39.0

52.7

52.7

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

28.3

28.3

30.6

36.4

37.0

42.2

58.7

58.7

30

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Control Room Building
Electrical Control Equipment @75dB Lw

1
2
3
4
5
6

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1
10 X LOG [4]
SWL + [5]

63

125

250

500

1000 2000 4000 8000

75
28.3
0.14

75
28.3
0.14

75
30.6
0.13

75
36.4
0.11

75
37.0
0.11

75
42.2
0.09

75
58.7
0.07

75
58.7
0.07

2
0.04
0.18
-7.4
67.6

2
0.04
0.18
-7.4
67.6

2
0.04
0.17
-7.7
67.3

2
0.04
0.15
-8.3
66.7

2
0.04
0.15
-8.3
66.7

2
0.04
0.13
-8.7
66.3

2
0.04
0.11
-9.7
65.3

2
0.04
0.11
-9.7
65.3

Total Internal Reverberant Sound Pressure Level @500Hz 66.7 dB


Wall 2 and 3 not included as it is adjacent to ECE and Pump Hall

31

Wall 1
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
7.5
4.6
2.9
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00011555
0.01154511
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00155475
28.1
66.7
32.7

32

WALL 3 and 4
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
40
40
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00100475
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
66.7
14.7

33

Roof
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
51
0
0
0
51
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.12810621
0.00000000
0.00000000
0.00000000
0.00251189
26.0
66.7
34.7

34

Noise Breakout from Switch Gear Room


Room Constant Calculation
Wall 1
Dimensions
Total Area
4.5 x 2.5 = 11.25m2
Assumptions
1 doorway
Door 2 x 2 = 4.0m2
Wall 11.25 4.0 = 7.25m2
Wall 2 and 4
Total Area
7 x 2.5 = 17.5m2
1.5 x 3.5 = 5.25m2
5.25 + 17.5 = 22.75m2

Assumptions
All brick wall
Wall 3
Total Area
4.5 x 25 = 11.25m2
Assumptions
Wall is all brick
Floor Area
Total Area
4.5 x 7 = 31.5m2
Assumptions
Floor is all unpainted concrete

35

Ceiling Area
Total Area
1.52 x 3.52 = 14.5 SQROOT= 3.8m2
3.8 x 4.5 = 17.1 x 2= 34.2m2
Assumptions
No ceiling treatment applied

BRICK
1
2
3
4
FLOOR
CEILING
TOTAL

7.25
22.75
11.25
22.75
0
0

ROLLER
SHUTTER
DOOR

TIMBER
DOOR
4.0
0
0
0
0
0

0
0
0
0
0
0

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
31.5
0

0
0
0
0
0
34.2

0
0
0
0
0
0

63
3.2
12.0
0.6
3.7
0.0
0.0
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
3.2
3.2
2.6
1.3
2.6
3.2
12.0
13.3
15.0
16.8
18.5
19.5
0.6
0.6
0.4
0.2
0.3
0.4
3.7
3.7
7.4
7.4
7.4
18.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
3.2
19.5
0.4
18.6
0.0
0.0
0.0
0.0

19.5

19.5

20.8

25.4

25.7

28.8

41.7

41.7

0.04

0.04

0.04

0.05

0.05

0.06

0.09

0.09

20.3

20.3

21.8

26.9

27.2

30.6

45.7

45.7

TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

36

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Control Room Building
Switch Gear @ 75dB Lw

1
2
3
4
5
6

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1
10 X LOG [4]
SWL + [5]

63

125

250

500

1000 2000 4000 8000

75
20.3
0.20

75
20.3
0.20

75
21.8
0.18

75
26.9
0.15

75
27.2
0.15

75
30.6
0.13

75
45.7
0.09

75
45.7
0.09

2
0.04
0.24
-6.3
68.7

2
0.04
0.24
-6.3
68.7

2
0.04
0.22
-6.5
68.5

2
0.04
0.19
-7.2
67.8

2
0.04
0.19
-7.3
67.7

2
0.04
0.17
-7.7
67.3

2
0.04
0.13
-9.0
66.0

2
0.04
0.13
-9.0
66.0

Total Internal Reverberant Sound Pressure Level @ 500Hz 67.8 dB


Wall 2 and 4 not included as it is adjacent to ECE room

37

Wall 1
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
11.25
7.25
4
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00018211
0.01592429
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00143168
28.4
67.8
33.3

38

WALL 3
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
11.25
11.25
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00028259
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
67.8
15.8

39

Roof
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
34.2
0
0
0
34.2
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.08590652
0.00000000
0.00000000
0.00000000
0.00251189
26.0
67.8
35.8

40

Noise Breakout from Standby Generator Room


Room Constant Calculation
Wall 1
Dimensions
Total Area
2.5 x 3 = 7.5m2
Assumptions
1 doorway
Door 2 x 2 = 4.0m2
Wall 7.5 4.0 = 3.5m2
Wall 2 and 4
Total Area
7 x 2.5 = 17.5m2
1.5 x 3.5 = 5.25m2
5.25 + 17.25 = 22.75m2

Assumptions
All brick wall
Wall 3
Total Area
2.5 x 3 = 7.5m2
Assumptions
Wall is all brick
Floor Area
Total Area
3 x 7 = 21m2
Assumptions
Floor is all unpainted concrete

41

Ceiling Area
Total Area
1.52 x 3.52 = 14.5 SQROOT= 3.8m2
3.8 x 3 = 11.4 x 2= 22.8m2
Assumptions
No ceiling treatment applied

BRICK
1
2
3
4
FLOOR
CEILING
TOTAL

4.0
22.75
7.5
22.75
0
0

ROLLER
SHUTTER
DOOR

TIMBER
DOOR
3.5
0
0
0
0
0

0
0
0
0
0
0

CONCRETE
CEILING LOUVRES
FLOOR
0
0
0
0
21
0

0
0
0
0
0
34.2

0
0
0
0
0
0

63
2.9
12.0
0.5
3.7
0.0
0.0
0.0
0.0

OCTAVE BAND CENTRE FREQUENCY


125
250
500
1000 2000 4000
2.9
2.9
2.3
1.1
2.3
2.9
12.0
13.3
15.0
16.8
18.5
19.5
0.5
0.5
0.4
0.2
0.3
0.4
3.7
3.7
7.4
7.4
7.4
18.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

8000
2.9
19.5
0.4
18.6
0.0
0.0
0.0
0.0

19.0

19.0

20.4

25.1

25.5

28.5

41.3

41.3

0.04

0.04

0.04

0.05

0.05

0.06

0.09

0.09

19.8

19.8

21.3

26.5

27.0

30.3

45.3

45.3

TOTAL SURFACE AREA

WALLS
CEILING
TIMBER DOOR
FLOOR
LOUVRES
ROLLER DOOR

TOTAL
ABSORPTION
AVERAGE
ABSORPTION
ROOM
CONSTANT

42

Reverberant Sound Pressure Level Inside Building


Assumed Contents of Control Room Building
Diesel Generator 102dB Lw from BS 5228 Ref 53 Table D.7

1
2
3
4
5
6

Total Internal Sound


Power Level
ROOM CONSTANT
4/Rc
Q {DIRECTIVITY
FACTOR}
Q/{4X3.142X.r SQ}
3+1
10 X LOG [4]
SWL + [5]

63

125

250

500

1000 2000 4000 8000

102
19.8
0.20

102
19.8
0.20

102
21.3
0.19

102
26.5
0.15

102
27.0
0.15

102
30.3
0.13

102
45.3
0.09

102
45.3
0.09

2
0.04
0.24
-6.2
95.8

2
0.04
0.24
-6.2
95.8

2
0.04
0.23
-6.4
95.6

2
0.04
0.19
-7.2
94.8

2
0.04
0.19
-7.3
94.7

2
0.04
0.17
-7.7
94.3

2
0.04
0.13
-8.9
93.1

2
0.04
0.13
-8.9
93.1

Total Internal Reverberant Sound Pressure Level @500Hz 94.8 dB


Wall 2 not included as it is adjacent to switch gear room

43

Wall 1
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
7.5
4
3.5
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00010048
0.01393375
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00187123
27.3
94.8
61.5

44

WALL 3
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
7.5
7.5
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00018839
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
94.8
42.8

45

Wall 4
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
22.75
22.75
0
0
0
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00057145
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00000000
0.00002512
46.0
94.8
42.8

46

Roof
Single leaf brick
Timber Door
Vent
20g galvanised sheet
steel

total Area
Wall
Door
Vent
Roller Shutter Door

T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
T=10^(-C5/10)
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Area x T
Sum
COMPOSITE SRI
REVERBERANT SPL
EXTERNAL SPL

500
46
24
10
26
0
0
0
22.8
0
0
0
22.8
0
0
0
0.00002512
0.00398107
0.10000000
0.00251189
1.00000000
1.00000000
1.00000000
0.00000000
0.00000000
0.00000000
0.05727101
0.00000000
0.00000000
0.00000000
0.00251189
26.0
67.8
35.8

47

PLANT AND EQUIPMENT SOUND POWER LEVELS


USED IN ASSESSMENT
Plant / Equipment
Deaerator Bund
Deaerator Tanks
Cavity Sump Pumps
Air-Compressed gas
Air-Regeneration gas
CO2 Package
Condensate Tank
Control Valves
Control Valves Gas
Service
Control Valves Liquid
Service
Corrosion inhibitor
package incl tank &
pumps
Dry Glycol Tank
Electrical Switch Yard
Fuel Gas Package
Fuel gas package
Gas - Glycol Heat
Exchanger
Gas Heaters
Glycol Contactor
Glycol Filters
Glycol Make-up Pump
Glycol Make-up Tank
Glycol Regeneration
Unit
Glycol Separator
Heating Medium
Circulation Pumps
Heating Medium Makeup Pump
Heating Medium Makeup Tank
Heating Medium
Package
Heating Medium Surge
Vessel
HP Compressor Cooler
HP Compressor Suction
Drum
HP Glycol Pumps

Sound Power
Lw
70
0
70
90
73.1
70
75
80

Plant / Equipment
NTS Gas Filter Coalesces
Pig Receivers
Pipe work Gas Service
Pipe work Liquid Service
Pipe work Vent System
Pressure Letdown Valves
Regeneration Gas Heater
Slug catchers

Sound Power
Lw
75
75
75
75
75
91
85
75

75

Sump Pumps

75

75

Vent KO Drum

75

92

Nitrogen Stack Silencer

80

75
85
85
70

Vent Stack
VSD Cooling System Coolers
Wet Glycol Tank
Nitrogen Generation Package

110
88
75
70

75

Air-Regeneration gas

73.1

75
75
75
80
75

Control Valves Gas Service


Control Valves Liquid Service
Methanol Injection Pumps
Control Valves
Glycol Make-up Pump

75
75
75
80
80

93

Heating Medium Make-up Pump

80

75

Miscellaneous Pumps

80

88

Nitrogen Stack Silencer NO

80

80

Nitrogen Vent Stack NO

80

75

Heating Medium Package

83

83

Saltwater Discharge Pumps

85

75

Electrical Switch Yard

85

93

Fuel Gas Package

85

75

Regeneration Gas Heater

85

90

Heating Medium Circulation


Pumps

88

48

Plant / Equipment
LP Compressor Cooler
LP Compressor
SuctionDrum
Methanol Injection
Pumps
Methanol Pumps
Methanol Storage Tank
Miscellaneous Pumps
Nitrogen Back-up
System
Nitrogen Generation
Package

Sound Power
Lw
93

Plant / Equipment
VSD Cooling System Coolers

Sound Power
Lw
88

75

Air-Compressed gas

90

75

HP Glycol Pumps

90

90
75
80

Methanol Pumps
Pressure Letdown Valves
HP Compressor Cooler

90
91
93

70

LP Compressor Cooler

93

70

Nitrogen Vent Stack

80

Vent Stack*

110

*Vent stack has not been included in results. The vents are only used for routine
maintenance and for emergencies. During normal operation the flow will be essentially
zero. During an emergency the plant is depressurised in zones, each event is a high flow,
but only for 15 minutes.

Predicted Noise Levels


Extract from scope of BS 4142
The method is not suitable for assessing the noise measured inside buildings or when the
background and rating noise levels are both very low. NOTE. For the purposes of this
standard, background noise levels below about 30 dB and rating levels below about 35 dB
are considered to be very low.
The above extract suggests that BS 4142 may not be applicable for this project as
background noise levels are below 30dB and the highest rating noise level is 37.1 (with
5dB penalty applied).
Table below provides a comparison of levels against BS4142 (with 5dB penalty), World
Health Organisation levels, BS8233 internal noise levels and Minerals Policy Statement 2.

49

PREDICTED
NOISE
LEVEL

RATING
NOISE
LEVEL

BACKGROUND
NOISE
DAY
NIGHT

DAY

NIGHT

DAY

Cote Walls Farm South Faade


Cote Walls Farm North Faade
Cote Walls Farm West Faade

30.0
21.8
29.1

35.0
26.8
34.1

32.2
32.2
32.2

24.8
24.8
24.8

2.8
-5.4
1.9

10.2
2.0
9.3

Cote Walls Farm East Faade

32.2

37.2

32.2

24.8

5.0

Ivy Cottages

27.3

32.3

32.2

24.8

Park Farm

28.9

33.9

32.2

24.8

Carters Farm

15.9

20.9

34.9

Elm Farm

12.5

17.5

Corcas Farm

27.2

Rossall Hospital

NIGHT

BS8233
INTERNAL
LEVEL

DAY

NIGHT

-25.0
-33.2
-25.9

-10.0
-18.2
-10.9

-10.0
-18.2
-10.9

-25.0
-33.2
-25.9

-12.0
-20.2
-12.9

12.4

-22.8

-7.8

-7.8

-22.8

-9.8

0.1

7.5

-27.7

-12.7

-12.7

-27.7

-14.7

1.7

9.1

-26.1

-11.1

-11.1

-26.1

-13.1

29.5

-14.0

-8.6

-39.1

-24.1

-24.1

-39.1

-26.1

38.6

N/A

-21.1

N/A

-42.5

-27.5

-27.5

-42.5

-29.5

32.2

32.2

24.8

0.0

7.4

-27.8

-12.8

-12.8

-27.8

-14.8

28.7

33.7

41.7

37.4

-8.0

-3.7

-26.3

-11.3

-11.3

-26.3

-13.3

Rossall School

17.8

22.8

41.7

37.4

-18.9

-14.6

-37.2

-22.2

-22.2

-37.2

-24.2

Blackpool and The Fylde College

13.1

18.1

41.7

37.4

-23.6

-19.3

-41.9

-26.9

-26.9

-41.9

-28.9

Sportsmans Cottage and Caravan Park

23.6

28.6

34.8

29.8

-6.2

-1.2

-31.4

-16.4

-16.4

-31.4

-18.4

Riverside Cottage

24.5

29.5

34.8

29.8

-5.3

-0.3

-30.5

-15.5

-15.5

-30.5

-17.5

Little Height o th Hill

23.3

28.3

34.9

29.5

-6.6

-1.2

-31.7

-16.7

-16.7

-31.7

-18.7

Height o th Hill

23.2

28.2

34.9

29.5

-6.7

-1.3

-31.8

-16.8

-16.8

-31.8

-18.8

The Grange

23.2

28.2

32.2

24.8

-4.0

3.4

-31.8

-16.8

-16.8

-31.8

-18.8

Stanah House Caravan Park

9.6

14.6

36.9

33.2

-22.3

-18.6

-45.4

-30.4

-30.4

-45.4

-32.4

Harbour Village Development

26.6

31.6

35.6

32.2

-4.0

-0.6

-28.4

-13.4

-13.4

-28.4

-15.4

Broadwater Caravan Park

13.9

18.9

47.7

34.1

-28.8

-15.2

-41.1

-26.1

-26.1

-41.1

-28.1

Residential Dwellings Along West Way

18.8

23.8

36.9

33.2

-13.1

-9.4

-36.2

-21.2

-21.2

-36.2

-23.2

Residential Dwellings Along South Strand

13.6

18.6

35.6

32.2

-17.0

-13.6

-41.4

-26.4

-26.4

-41.4

-28.4

RECEPTOR

BS4142

WHO

Red cell indicates rating level in excess of 10dB of background noise level.
Amber cell indicates rating level in excess of 5dB but less than 10dB of background noise level.
Green cell indicate rating noise level less than background noise level.
50

MPS 2

Predicted Construction and Operation Noise Levels


BACKGROUND
NOISE

WHO

DAY

NIGHT

DAY

NIGHT

BS8233
INTERNAL
LEVEL

34.1

32.2

24.8

-20.9

-5.9

31.8

31.8

32.2

24.8

-23.2

Cote Walls Farm West Faade

33.0

33.0

32.2

24.8

Cote Walls Farm East Faade

34.7

34.7

32.2

Ivy Cottages

36.1

28.3

Park Farm

32.1

Corcas Farm

PREDICTED
NOISE
LEVEL
DAYTIME

PREDICTED
NOISE
LEVEL
NIGHT TIME

Cote Walls Farm South Faade

34.1

Cote Walls Farm North Faade

RECEPTOR

MPS 2
DAY

NIGHT

-5.9

-20.9

-7.9

-8.2

-8.2

-23.2

-10.2

-22

-7.0

-7.0

-22

-9.0

24.8

-20.3

-5.3

-5.3

-20.3

-7.3

32.2

24.8

-18.9

-11.7

-11.7

-18.9

-13.7

29.6

32.2

24.8

-22.9

-10.4

-10.4

-22.9

-12.4

28.7

28.2

32.2

24.8

-26.3

-11.8

-11.8

-26.3

-13.8

Sportsman Cottage and Caravan Park

26.0

26.0

34.8

29.8

-29

-14.0

-14.0

-29

-16.0

Riverside Cottage

26.5

26.5

34.8

29.8

-28.5

-13.5

-13.5

-28.5

-15.5

Little Height o th Hill

26.1

25.9

34.9

29.5

-28.9

-14.1

-14.1

-28.9

-16.1

Height o th Hill

26.2

25.8

34.9

29.5

-28.8

-14.2

-14.2

-28.8

-16.2

The Grange

26.4

25.9

32.2

24.8

-28.6

-14.1

-14.1

-28.6

-16.1

51

Вам также может понравиться