LSIS Pro-MEC VCB is user-friendly to give more convenience and safety by providing high speed interrupting time (3cycles), adopting the rapid auto-reclosing method, and having wide range of accessories.
Pro-MEC
VCB/VI
H1-4 H1-8 H1-9 H1-10 H1-19 H1-24 H1-27 H1-35 H1-40
Contents
H1
Vacuum Interrupter
Features & Ordering information VI internal structure Basic functions and interrupting action VI endurance by interrupting current Dimensions Technical data H1-43 H1-44 H1-45 H1-46 H1-48 H1-50
Latch checking switch TOC (Truck operated cell switch) Charge indicator Code plate (Miss insertion prevention) Position padlock Capacitor trip device Earthing switch Note 1) Rectifier
Note 1) The earthing switch is not available for 17.5kV VCB.
H1-3
LVB-06-32D (kV) (A) (Hz) (kA) (MVA) (kA/3sec) (kAp) (Cycle) (sec) (sec) (kV/min) (kV/1.250) 1250 7.2 2000 50/60 31.5 390 31.5 82 3 0.04 0.06 20 60 O-0.3s-CO-3min-CO M2 (10,000 times) E2 (List1) C2 20000 30000 20000 30000 4a4b, 10a10b Visible, Fixed Visible, Tulip Visible, Tulip T (kg) (kg) (kg) (kg) (kg) (kg) Visible, Tulip Enclosed, Tulip Enclosed, Tulip 131.5 132.5 132.5(159) 52 60 54.5 62.5 62.5(110) 135(117) 155 IEC 62271-100 134.5 135.5 135.5(160) 210 211 220 131 135 Visible, Fixed Visible, Clip Visible, Tulip Visible, Tulip 3150 1250
LVB-06-40D 7.2 2000 50/60 40 500 40 104 3 0.04 0.06 20 60 O-0.3s-CO-3min-CO M2 (10,000 times) E2 (List1) C2 20000 30000 20000 30000 4a4b, 10a10b Visible, Fixed Visible, Tulip Visible, Tulip Visible, Tulip Enclosed, Tulip Enclosed, Tulip 135 136 136(162.5) 52 54.5 62.5(110) 138 139 139(163.5) 60 62.5 135(117) IEC 62271-100 Visible, Fixed Visible, Tulip Visible, Tulip Visible, Tulip 210 211 220 131 135 155 3150
Without maintenance (Time) Maintenance Maintenance (Time) (Time) Without maintenance (Time)
Note 1) Applied cable-charging current switching test 2) In the event of ordering Enclosed Tulip type for G class VCB, please add T in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T) 3) ( )* indicates the weight of Enclosed Tulip installing method VCB. 4) KERI: Korea Electrotechnology Research Institute
H1-4
Type Rated voltage Rated normal current Rated frequency Rated short-circuit breaking current Rated short-circuit breaking capacity Rated short-time withstand current Rated short-circuit making current Rated breaking time Rated opening time No-load closing time Withstand Power frequency voltage Impulse Rated operating sequence Type test Mechanical Electrical Capacitive current switching Note) Mechanical Lifetime Electrical Auxiliary switch Fixed Installing Method E-TYPE Draw-out type F-TYPE G-TYPE M-TYPE E-TYPE VCB Weight Cradle Applied standard Test laboratory
Note) Applied cable-charging current switching test
LVB-12-32D/12, 20-T, 30 (kV) (A) (Hz) (kA) (MVA) (kA/3sec) (kAp) (Cycle) (sec) (sec) (kV/min) (kV/1.250) 1250 12 2000 31.5 650 31.5 81.9 3 0.04 0.06 28 75 O-0.3s-CO-3min-CO M2 (10,000 times) E2 (List 1) C2 20,000 30,000 20,000 30,000 4a4b, 10a10b Enclosed, Tulip Enclosed, Tulip (kg) (kg) (kg) (kg) (kg) (kg) 159 110 160 117 220 155 Visible, Tulip (Time) (Time) 3150
LVB-12-40D/12, 20, 30 12 1250 2000 40 831 40 104 3 0.04 0.06 28 75 O-0.3s-CO-3min-CO M2 (10,000 times) E2 (List 1) C2 20,000 30,000 20,000 30,000 4a4b, 10a10b Enclosed, Tulip 162 110 163 117 IEC 62271-100 220 155 Visible, Tulip 3150
LVB-17-40D/12, 20, 30 17.5 1250 2000 60 40 1200 40 104 3 0.04 0.06 38 95 O-0.3s-CO-3min-CO M2 (10,000 times) E2 (List 1) C2 20,000 30,000 20,000 30,000 4a4b, 10a10b Visible, Tulip 200 175 205 175 KEMA, PT & T 260 200 3150
60(E1,E2,C2: PT & T)
H1-5
Note 1) Applied cable-charging breaking current 2) In the event of ordering Enclosed Tulip type for G class VCB, please add T in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
E-type cradle
F-type cradle
H1-6
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
Rated voltage DC 48V DC 110V DC 125V DC 220V
Note 1) Range of the normal operating voltage: 85~110% 2) DC 24V is the underdeveloped rating.
Auxiliary switch
Standard 4a4b / Optional 10a10b
Classification AC Contact Ratings DC 125V 30V 10 250V 10 125V 10 250V 10 10 General load (A) Inductive load (A) 5 5 5 5 5 4a4b 10a10b Contact configuration
Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing sp ring contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch, Truck operated cell switch.
Charged
Counter
Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option) H1-7
Manual charge
Insert the charge handle into the manual charge hole in the front of a VCB, and rotate it to clockwise over 40times and the charge complete with a metal sound.
Motor charge
If you apply the control power to a VCB, the closing spring will be charged automatically by a motor and then the control power will be turned off by the built-in limit s/w. Please use the same control voltage for motor, Closing coil, Trip coil.
H1-8
: External terminal of VCB 52: Vacuum circuit breaker M: Spring charging motor TC: Trip coil TC1: Secondary Trip coil C: Closing coil Y: Anti-pump relay 52a: Auxiliary switch (NO)
52b: Auxiliary switch (NC) LS1: Closing interlock limit switch (only withdrawable type) LS2: Motor stopping, closing spring charged indication LS3: Anti-closing, anti-pumping limit switch LCS1: Opening latch checking switch(preventing closing unless the trip latch is properly reset) LS4, LS5: Position s/w (close in test position) LS6, LS7: Position s/w (close in run position)
4) TC1: Secondary trip coil (Preparatory trip coil Terminal No.: 82,83)
H1-9
Above circuit diagram is based on OFF status of VCB. and closing spring is charged.
Front
Side
H1-10
(Unit: mm)
Front
Side
H1-11
(Unit: mm)
LVB-06F-32D, 40D
Front
H1-12
LVB-06G-32D, 40D
Front
(Unit: mm)
Top
H1-13
(Unit: mm)
LCL-06E-32D, 40D
Front
H1-14
LCL-06F-32D, 40D
Front
(Unit: mm)
LCL-06F-32D, 40D
Front
Top
H1-15
Top
Rating A 1250A 2000A 10 20
<Terminal conductor>
H1-16
(Unit: mm)
Top
<Terminal conductor>
Rating A B
H1-17
(Unit: mm)
Top
<Terminal conductor>
H1-18
(Unit: mm)
LVB-12G-40D
Front
470
Top
150 150
726.5
295
549
438
40kA 1250/2000A
G class
10
496
288
33.5
355
69
H1-19
668
(Unit: mm)
806.6
747
502
Top
210 210
40kA 3150A
676
G class
H1-20
10
714
290
348.5
360
(Unit: mm)
Top
<Terminal conductor>
Rating A B
H1-21
(Unit: mm)
1250A:12t 2000A:25t
40kA 1250/2000A
G class
Top
<Terminal conductor>
150 150 60 26 83 RUN 26
600
560
100
662
H1-22
150
150
630
1235
LCL-12G-32D/LCL-12G-40D
Front
(Unit: mm)
40kA 3150A
G class
Top
<Terminal conductor>
230 230 120 70 35
439 800 760 4-14 Mount hole 100 724 210 210 145
H1-23
1100
(Unit: mm)
LVB-17G-40D
Front
H1-24
H1-24
LCL-17G-40D
Side
(Unit: mm)
Top
<Terminal conductor>
H1-25
(Unit: mm)
H1-26
<Terminal conductor>
E, F class - (630/1250/2000A)
<Enclosed, Tulip contact>
Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.
H1-27
(Unit: mm)
Note 1) (
): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm. 2) IP Cover applied both sides in case of 265mm phase distance.
H1-28
H1-28
(Unit: mm)
Top
<Terminal conductor>
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-29
(Unit: mm)
280
115
Top
630A
20 40 67
<Terminal conductor>
1250A
90 47
2000A
42 100 45
25
40.5
265
820
145
2-14
4-14
4-14
40 80
210.5
265
40
40
20
40
20
40
245
202
40 80
20
7-14
110
400
400
210
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-30
100
40
90
300
300
340 1033
265
265
15
(Unit: mm)
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-31
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-32
(Unit: mm)
Top
<Terminal conductor>
H1-33
Top
<Terminal conductor>
210mm
Note) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T, LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
Earthing Switch
H1-34
Accessories
Accessories for VCB
Key lock
When it is locked by a key, the closing operation is not available (electrically and mechanically) without a Key.
Button padlock
Button padlock protects 'ON' or 'OFF' button when accident is occurred by operation at discretion. It is available to operate after release button padlock.
Button cover
Button cover protects 'ON' of 'OFF' button when accident is occurred by operation at discretion. It is available to operate by push bar.
<Push bar>
<G class>
Note) In case that position of VCB changed to Run or Test position, a contact will be closed.
H1-35
Charge indicator
Remotely indicates the charging is completed. (Standard Feature) - Terminal No.: 9, 10
Position padlock
The hole to prevent the draw-in and out of a VCB from the present position.('Run' or 'Test') Standard option in the interlock lever of the E, F class draw-out type VCB. (Hole size = 8)
H1-36
Position switch of the earthing switch (for G class draw-out type only)
Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)
H1-37
Mechanically operated cell switch (MOC) -for G class draw-out type only
The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition of a VCB, but operated only when the VCB is in 'Run' state. (Installed in the bottom of a cradle)
Truck operated cell switch (TOC) -for G class draw-out type only
The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB and is operated by the movement of a VCB frame. (Installed in the bottom of a cradle)
Code plate (Miss insertion prevention) -for E, F class draw-out type only
To prevent the insert a VCB to a cradle, when the ratings of VCB and cradle are different.
Padlock
To prevent the insert draw-in/out handle to a screw hole by operating G class VCB temporarily
H1-38
Optional accessories
Capacitor trip device (CTD)
When the control power is off, the CTD supply the power for tripping a VCB.
Dimension
Ratings Type CB-T1 Rated input voltage Freguency (Hz) Charging volt(V) Charging time Tripping time Allowable Input voltage range Capacitor rating( F)
Connection diagram
CDT
Within 10 Sec. after the AC power off Within 30 Sec. after the AC power off 85% ~ 100% 1000 85% ~ 110% 560
Rectifier
When the DC power is not available, rectify the AC power and get the DC power for closing coil.
Type VCB-X AC Input voltage Output current 1 100/110V 1 200/220V 40A DC Rating time
Dimension
150
10 sec.
100
80
40
Connection diagram
Standard tool
E, F class G class
29.5
25
70 +
12
G
Installation method G M G class draw-out type G class draw-out type + Bushing
32
D
Revision No. D Pro-MEC
12
1A
Control voltage 1A 1B 1C 1E DC110V DC220V DC48V DC125V
2B
B, C1, D1
Auxiliary switch 2B 4a4b(A type connector) 2E 10a10b(A type connector) 2G 4a4b(B type connector) 2H 10a10b(B type connector) Accessories B Position Switch (RUN/TEST:2a2a) C1 Button Padlock (ON) C2 Button Padlock (OFF) C3 Button Padlock (ON/OFF) D1 Button Cover (ON) D2 Button Cover (OFF) D3 Button Cover (ON/OFF) E Button padlock (ON)+ Button cover (OFF) F Button padlock (OFF)+ Button cover (ON) G Key Lock H Secondary Trip Coil(Preparatory trip coil) J Fire-endurable wiring cable assy K Opening Latch Checking Switch S Pad Lock (G class) T Enclosed type, Tulip contact
Cradle
LCL
LS Cradle
12
G
Installation method G G class draw-out type
32
Breaking current 32 40 31.5kA 40kA
D
Revision No. D Pro-MEC
12
Rated current 12 20 30 1250A 2000A 3000A
A, B, C
Accessories T Enclosed type, Tulip contact
H1-40
17.5kV
LVB
LS VCB
17
G
Installation method P E F Fixed type E class draw-out type F class draw-out type G class draw-out type
40
D
Revision No. D Pro-MEC
12
1A
Control voltage 1A 1B 1C 1E DC110V DC220V DC48V DC125V
2B
B, C1, D1
Auxiliary switch 2B 4a4b(A type connector) 2E 10a10b(A type connector) 2G 4a4b(B type connector) 2H 10a10b(B type connector) Accessories B Position Switch (RUN/TEST:2a2a) C1 Button Padlock (ON) C2 Button Padlock (OFF) C3 Button Padlock (ON/OFF) D1 Button Cover (ON) D2 Button Cover (OFF) D3 Button Cover (ON/OFF) E Button padlock (ON) + Button cover (OFF) F Button padlock (OFF) + Button cover (ON) G Key Lock H Secondary Trip Coil(Preparatory trip coil) K Opening Latch Checking Switch S Pad Lock (G class) J Fire-endurable wiring cable assy
Cradle
LCL
LS Cradle
17
40
Breaking current
D
Revision No. D Pro-MEC
12
Rated current 12 20 30 1250A 2000A 3150A A
A, B, C
Accessories MOC (3a4b) + TOC (3a4b)
Note) A is for G class only
Installation method E F G E class draw-out type F class draw-out type G class draw-out type
H1-41
20
G
Installation method Fixed type E class draw-out type F class draw-out type G class draw-out type G class draw-out type + Bushing
13
D
Revision No. D Pro-MEC
Note1)
06
1A
Control voltage 00 1A 1B 1C 1E 1F 1H 1T DC110V DC220V DC48V DC125V AC220(M), DC110(TC) AC220(M), DC220(TC) AC110(M), DC110(TC) Auxiliary switch
2B
B, C, D
Accessories B C1 C2 C3 D1 D2 D3 E F G H Position Switch (RUN/TEST:2a2a) Button Padlock (ON) Button Padlock (OFF) Button Padlock (ON/OFF) Button Cover (ON) Button Cover (OFF) Button Cover (ON/OFF) Button padlock (ON) + Button cover (OFF) Button padlock (OFF) + Button cover (ON) Key Lock Secondary Trip Coil (Preparatory trip coil) Fire-endurable wiring cable assy Opening Latch Checking Switch Dummy VCB(AMP Jack) Dummy VCB(Phoenix Jack) Earthing Truck(Lower terminal earthing) Earthing Truck(Upper terminal earthing) Pad Lock (G class) Enclosed type, Tulip contact Option
00
2B 4a4b(A type connector) 2E 10a10b(A type connector) 2G 4a4b(B type connector) 2H 10a10b(B type connector)
J K P1 P2 Q R S T
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm. 2. "00" is used for ordering Earthing Truck and Dummy VCB 4. Accessory only for versions D and E
Cradle
LCL
LS Cradle E F Rated voltage 20 24kV
20
G
Installation method E class draw-out type F class draw-out type
13
Breaking current 13 16 25 12.5kA 16kA 25kA
Note1)
D
Revision No. A Conventional D E Pro-MEC Pro-MEC (Minimized type)
06
Rated current 06 12 20 630A 1250A 2000A
Note2) Note2)
A, B, C
Accessories A MOS(3a4b)+ TOC(3a4b) B Earthing Switch C T PS Earthing Switch Position Switch+ Earthing Switch Locking coil Enclosed type, Tulip contact Position S/W Block (24kV E/F class only)
Note2)
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm. 2. Versions A, B and C are available only at G class VCB.
H1-42
Vacuum Interrupter
Features & Ordering information
Features
Accumulation of more than 20 years of vacuum-related technologies Simplified arc extinguishing system Spiral contact structure with Radial magnetic field provides effective dispersing of the acr energy. Simple structure and high quality Sealing after complete removal of gas in the vacuum chamber in order to secure a long vacuum confidentiality Small size and light weight The new contact material used to enhance the competitiveness of the size Wide rated coverages Wide interrupting range from 6kV up to 40.5kV 40kA High reliability and electrical life Certification by KERI and KEMA according to the latest standard IEC62271-100 (2008) E2, LIST3, M2
Modeling system
LV7
Revision No A, B
Null P C E G
ETC. Straight type Potting type Wave type Embedded type Gas Insulation type
H1-43
Vacuum Interrupter
VI internal structure
Largely movable and fixed electrodes and main shield compose the Susol VI. The main components are shown in the following.
Fixed electrode
Fixed shield
Contacts
Arc shield
Bellows shield
Ceramic
Bellows
The vacuum rate within the VI is very high(approximately 5x10-5 Torr) and the spacing between fixed contact and movable contact is about 6 ~ 20mm, depending on the voltage. The contacts are in a structure that arc can easily be extinguished and the surfaces of the contacts are made of special alloy (copper - chromium) and the interior is completely sealed to prevent loss of vacuum. Therefore the wearing of the contacts can be minimized in the event of short-circuit and the arc energy by overvoltage or switching can be reduced effectively.
H1-44
In case of using the flat contact any of the designs do not reflect on when contacts are opening the arc with high temperature is contracted and fixed in the center of the contacts, Which is called pinch effect. To prevent the effect two kinds of contact shapes are designed. One is Axial magnetic field which spreads the arc before its contraction, and the other is Radial magnetic field which permits the contraction of the arc but makes it rotated to disperse the energy. Because contracted arc is shaped like a cylinder it is called Contracted arc or columnar arc.
Arc voltage waveforms and arc image captured during arcing time
Spiral contact structure (Radial magnetic field ), using the force (F = j B) generated by the interaction of the radial magnetic field caused by the current flowing through the arc between two contacts, disperse the arc energy evenly on the surface of contact by rotating the arc that is contracted by the pinch effect so as to minimize contact damage. The images show arc behavior during the arcing time of about 8ms by shooting with high-speed camera capable of shooting 10,000 frames per sec. (0.1ms/frame) by focusing on parts of the arcing time on the above graph and simultaneously measured arc voltage also represented to show arc state by section
H1-45
Vacuum Interrupter
VI endurance by interrupting current
Number[ops.]
Number[ops.]
Number[ops.]
Number[ops.]
H1-46
Number[ops.]
Number[ops.]
Number[ops.]
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB. 2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
H1-47
Vacuum Interrupter
Dimensions
LV2 LV3 LV4
LV5-P
0 17-0.3
LV5A
0 21-0.3
LV8
5.2+0.1 0
0 -0.1
20 +0.5 0
30 +0.5 0
+0.1 0
+0.1 0
H1-48
30 +0.3 0
6 +0.1 0
0 17 -0.3
LV7-P1 / LV8-P
LV7-C
LV10404
6 +0.1 0
0 -0.1
0 -0.1
+0.1 0
30 +0.3 0
30 +0.5 0
0 9
H1-49
Vacuum Interrupter
Technical data
Type LV2 LV3 LV4-E LV5-P
Outer view
Rated voltage Rated power frequency withstand voltage Electrical ratings Rated impulse withstand voltage Rated frequency Rated normal current Rated short circuit current Rated short circuit making current Rated duration of short-circuit Interrupter weight Mechanical data Moving part weight Outline dimension (mm)
(kV) (kV, rms) (kV, crest) (Hz) (Amp) (Sym.) (kA) (kA, peak) (sec) (kg) (kg) a b c 8 20.8
7.2 7.2 20 20 60 60 50/60 50/60 400/630 630/1250 12.5 20 32.5 33 0.8 0.3 0.7 132 158 91 105 62 80 61 10 0 7~1.0 22 0 7~1.0 22 80 154 8.5 12.6 33 M2 M2 227 0 7~1.0 1 12 0 7~1.0 1.4 1.2 52 25 65 41.6
Contact stroke Opening speed, average 0 to 75% of full stroke Mechanical requirements Overtravel during opening, Max. Closing speed, average last 33% of full stroke Contact bounce duration, Max. Added force from atmospheric pressure Contact force from atmospheric pressure Contact erosion limit Mechanical life
(mm) (m/s) (mm) (m/s) (sec) (kgf) (kgf) (mm) (10 4, Operations)
H1-50
LV5A
LV7-P1
LV7-C
LV8
LV8-P
LV10404
12/17.5 24/25.8 42 65 95 125 50/60 50/60 2000 20 52 34 3.0 1.0 220 272 160 80 101 12 0.7~1.0 22 0.7~1.0 0.7~1.0 22 154 227 12.6 25.5 33 M2 M2 227 306 367 227 216 145 1 1.0~1.3 7.3 2.2 25 65 2500 25 65 ~3150 31.5 40 81.9 104 25 65
40.5 17.5 95 38 185 95 50/60 50/60 ~3150 ~3150 31.5 81.9 44 9.8 6.6 2.6 2.2 390 272 329 210 145 135 17~19 12 1.3~1.5 1.0~1.3 22 0.7~1.0 0.7~1.0 22 306 25.1 25.8 33 M2 M2 367 460 227 1 17~19 40 104 50 130 25 65
36 70 170 50/60 ~3150 31.5 81.9 4 7.3 2.2 272 216 145 40 104
7.2/12 20/28 60/75 50/60 4000 40 104 4 8.7 2.0 317 210 135 101 17 50 130
25.8 70 150
3150 40 104 3
H1-51
Pro-MEC MCSG
VCB
H2-2 H2-4 H2-5
Contents
H2
Main functions
- Breaker : draw- in or out electrically or manually - Compartment : 3-positions
Standard
- IEC 62271-100
Name plate Manual closing button Keylock Manual trip button Manual charging hole Contact position indicator Closing spring charge indicator Operation counter Insertion & Draw-out screw Geared Mechanism
Compartment
Earthing switch
Bushings
Shutter
H2-2
Ratings
Type Rated voltage (kV) Rated normal current (A) Rated frequency (Hz) Rated short-circuit breaking current (kA) Rated short-circuit breaking capacity (MVA) Rated short-time withstand current (kA) Rated short-circuit making current (kA) Rated breaking time (Cycles) Withstand Power frequency (kV) voltage Impulse (kV/1.250 ) TRV rising rate (kV/ ) TRV max. (kV) Rated operating sequence Mechanical lifetime Electrical lifetime Rated control voltage (V) Rated trip voltage( V) Standard auxiliary switch Rated opening time (s) No-load closing time (s) Rated charging motor current (A) Rated closing coil current (A) Rated trip coil current (A) Closing spring charging time (s) Draw-in/out motor voltage (V) Draw-in/out motor current (A) Distance between phases (mm) breaker Weight (kg) compartment Installing Applied standard LVB25-25/06 630 2000 25.8 60 25 1100 25/3s 65 3 50/1min 125 0.47 41 O-0.3s-CO-3min-CO 10,000operations 10,000operations DC 110V DC 110V 4a4b, 8a8b 0.04 0.06 7 5 5 12 DC 110V 5 265 G IEC 62271-100 LVB25-25/20
236.5
Breaker
LVB
LS VCB
25
G
G
Installation method Gclass draw-out
25
I
Version
06
1A
Control voltage 1A DC110V 1B DC220V 1C DC48V 1E DC125V
2B
B,C,D
Accessories
B Position Switch C1 Button Padlock(ON) C2 Button Padlock(OFF) C3 Button Padlock(ON/OFF) D1 Button Cover(ON) D2 Button Cover(OFF) D3 Button Cover(ON/OFF) E Button Padlock(ON)+Button Cover(OFF) F Button Padlock(OFF)+Button Cover(ON) G Key Lock H Secondary Trip Coil
1F AC220(M), DC110(TC) 1H AC220(M), DC220(TC) 1T AC110(M), DC110(TC) Auxiliary switch 2G 4a4b(B type connector) 2H 8a8b(B type connector)
Cradle(Compartment)
LCL
LS VCB 25
25
Rated voltage 25.8kV C
C
Installation method Bushing 25
13
Breaking current 25kA
D
Version 06 20
06
Rated current 630A 2000A
A,B,C
Accessories B Earthing Switch E Door
H2-3 3
4 34 35 52b 34 34
LS1
1 2
TC
A2 A6
23 25 27 29 41 43 45 47 37 39 51 53 55 57 59 71
10
H2-4
P
CW () Run 3 13 43 89X 44 1 LS6 LS5 1 89X 2 PS1 23 25 27 29 41 43 45 47 33 89Y 89X 33 37 39 51 53 55 57 59 71 2 4 PS2 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 1 3 89Y 22 8 2 21 1 2 21 14 14 44 89X 89Y 89Y 13 13 43 14 15 16 17 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 Test 1 CCW ()
P P
4a 4b
Position S/W
8a
Auxiliary switch
8b
A1
CS A3 CS A5
LS2 3 4
1 2
LS3
1 3 2 4
Ya
Yb
5 52a 22 8
1 5
89M
M
89X
9 9
52b
30 31
6'
89Y
A4 N
Note. Diagram shows the circuit breaker in position OFF closing spring Charged with
1 D 1 C 36 37 38 39 B
2 2
3 3
4 4
10 11 12 13 14 15 16 9 10 D
C 50 51 52 53
B 13 14 15 16 17
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ( 4a 4b )
1 D 1 C 36 37 38 39 B
2 2
3 3
4 4
10 11 12 13 14 15 16 9 10 D
C 50 51 52 53 54 55 56 57 58 59 70 71
B 13 14 15 16 17 42 43 44 45 46 47
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil TC1 : Secondary trip coil C : Closing coil Y : Anti-pump relay 52a : Auxiliary switch (NO) 52b : Auxiliary switch (NC) LS1 : Closing interlock limit switch(only withdrawable type) LS2 : Motor stopping, closing spring charged indication LS3 : Anti-closing, Anti-pumping limit switch LS5 : "Off" at Test Position LS6 : "Off" at Run Position PS1 : Position S/W("On" at Test Position) PS2 : Position S/W("On" at Run Position) 89X : Auxiliary Relay for Inserting 89Y : Auxiliary Relay for withdrawing 89M : Motor for withdrawing and Inserting
Dimensions
Cradle(Compartment) - w/o Earthing Switch
Front
A 70 103 75 Lead wire (2m)
Rear
45 372.6 60 425 2-13 30 265 425 265 175 (Earthing) 6.5 95 60 968 1000
1365
340
1365
425
1082
265
265 B 183.4
TEST RUN
(183.4)
(212.4)
B
1
15.4
95
652.4
35
53
894 1000
53
410
963
553
Earthing
Top
<Front>
410 65
<Rear>
3-1122 (Mounting Hole)
45
<C-View(Cover 2 Cutting)>
20
370
40
513
700
128 50
265
844
50
340
40
963
483
50
15
933
(15)
2000A
340 445
1013
50
608
340
30
86
340
26.8
3-10
190
86
H2-5
Front
A 125
Side
35
Rear
35 238.8 25t(2000A) 10t(630/1250A) Test st:310 Run 10-M8 POP NUT (DP:18) 45 398.6 415
500
1750
500
415
(Door) **Option
340
3-10
767.4
415
265 175
Test
415
1000
39
963
35
125
968
Top
<Front> <Rear>
25
<Terminal conductor>
26 17 60 2-13 26
50
140 150
50
340
40
483
50
H2-6
26
26
17
83
190
74
Test
Power Plants
VCB
H3-4 H3-5 H3-6 H3-8 H3-14
Contents
H3
H3-2
It is recognized for reliability by acquiring new IEC 62271-100 and ES150 (KEPCO standard specification on AC breakers)
H3-3
Rated short-circuit breaking current (kA) Rated short-circuit breaking capacity (MVA) Rated short-time withstand current (kA/3sec) Rated short-circuit making current (kAp) Rated breaking time Rated opening time No-load closing time Withstand voltage Power frequency Impulse (kV/1.2 (Cycle) (sec) (sec) (kV/min) 50 )
Rated operating sequence Rated charging motor current Rated closing coil current Rated shunt coil current Type test Mechanical Electrical Capacitive current switching Lifetime Mechanical Without maintenance Maintenance Electrical Without maintenance Maintenance Auxiliary switch Installing Draw-out G-type G-type G-type (kg)
Note) ES150: KEPCO's standard in which IEC62271-100 is applied KERI: Korea Electrotechnology Research Institute
H3-4
Auxiliary switch
Standard configuration : 3a3b1b of early-b contact function exists inside
Classification Contact Ratings DC 110V 10 125V 10 Resistive load (A) Inductive load (A) 5 5 Contact configuration 3a3b
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) are the same with that of the Aux. switch.
TEST
OFF ON
Note) * applied in the VCB of which MOC is operable at the TEST position.
Charged
Counter
Mechanically counts the operation of the VCB by 5digits H3-5
Position interlock
The breaker is locked in each position-Disconnected, Test or Connected, thus it is necessory to release the lock before draw-in or out of a breaker from the present position.
Auto connection
When the breaker is moved to Test position from Disconnected position the connector for control powers is automatically connected. In case of reverse moving of the breaker the connector is automatically disconnected.
Code plate
When the breaker is inserted to the cradle, if the ratings does not match with the cradle, it mechanically prevents the breaker from being inserted into the cradle.
H3-6
H3-7
LS4 2 2
1 LS1 2
6 8
TC A6 N
23
H3-8
<TOC>
15 16 17
25 26 27
12 13 14
22 23 24
<MOC> P
Auxiliary switch
22 26 3a 24 54 58 3b 56
15 16 17
30 34 36 38 50 52
P A1
LS2 3 4 6 52a 23 25 22 24 26 27 7 1 4 Ya 6 54 55 LS3
P CS A5
25 26 27
31 35 37 39 51 53
12 13 14
6 22 24 26 28 40
CS A3
22 23 24
7 23 25 27 29 41
56 57
58 59
M Y
1 3 2 4 1 Yb 5 52b 30 31 3
A2 N
A4
25
27
55
57
59
Early b
Note) Diagram shows the circuit breaker in position OFF closing spring Charged with
A1 A3 A5 A2 A4 A6 22 24 26 23 25 27
56 57
54 55 58 59
A
13 14 15 16 17 18 19 20
A2 A4 A6 23 25 27 A1 A3 A5 22 24 26
1 2 3 4 5 6 7 8 9
55 57 59 54 56 58
10 11 12
: : : : : : : : : : : :
External terminal of VCB Vacuum circuit breaker Spring charging motor Trip coil Closing coil Anti-pump relay Auxiliary switch (NO) Auxiliary switch (NC) Closing interlock limit switch Motor stopping Anti-closing, Anti-pumping limit switch Motor Charging interlock limit switch
Dimensions - Breakers
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A)
Front
722
(unit : mm)
336
351.3
815.2
130
60 10
696 717
686.2
Top
254 254
<Conductor>
532
584
685.2
1200/1250/2000A
745
368.2
360
54(male conductor)
Side
H3-9
(unit : mm)
Front
722
Side
336
349.8
696 717
815.2
130
686.2
Top
254 254
<Conductor>
584
685.2
532
2500/3000/3150A
745
H3-10
(unit : mm)
Fixed contact
130
341.3
403.8
815.7
60 10
696 717
677.2
Top
254 254
532
745
584
676.2
368.2
54(male conductor)
H3-11
(unit : mm)
336
Moving contact
130
Top
254 254
532
H3-12
584
676.2
Cradles
(unit : mm)
4-M12 DP20
252 50 35
1134 361
218
79 148
14
(Earthing)
310 50
2500/3000/3150A
2-M12 DP20 252 35 374 240
140
123
235.5
218
36
148
310
54
Mounting 6- 12
Autocon(3a3b) M.O.C(6a6b)
1200/1250/2000A
338
59 61()
1035
644 61
151.5
T.O.C(6a6b)
1038.5
75.8
449.5
360
254
254
H3-13
LVB
LS VCB
06
G
Installation method G G class draw-out
40
J
Standard H J ESB150 IEC
12
1A
Control voltage 1A 1B 1E DC110V DC220V DC125V
2L
P3,Q,R
Option C1 Button padlock(ON) C2 Button padlock(OFF) C3 Button padlock(ON/OFF) D1 Button Cover(ON) D2 Button Cover(OFF) D3 Button Cover(ON/OFF) E Button padlock(ON)+ Button cover(OFF) Button padlock(OFF)+ Button cover(ON)
Auxiliary switch 2L
NOTE2)
3a3b(Autocon)
3000/3150A
G Key Lock
Note) 1.Rated current 2500A is available only at 7.2kV 40kA, IEC version(J) 2.Control voltage and Auxiliary switch are not applied to Dummy VCB and Earthing Truck
Cradle
LCL
LS Cradle
06
40
12
A1, A2
Option MOC(6a6b)+TOC(6a6b) MOC active only at RUN position MOC(6a6b)+TOC(6a6b) A2 MOC active only at TEST and RUN position
H3-14
VCB
H4-4 H4-5 H4-6 H4-8 H4-9 H4-11
Contents
H4
H4-2
Lifetime
Weight
H4-4
Ratings of Accessories
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
The peak value of the inrush current (A) 4.76kV 50kA DC 125V 15 15kV 40kA 15 Ratedcurrent(A) 4.76kV 50kA 5 15kV 40kA 5 90~140 360 8
Rated voltage
Rated voltage
Rated voltage
Auxiliary switch
Standard configuration : Reversible 8C(5a3b) and 2c(2b) with early-b contact function
Classification AC Contact Ratings DC 250V 125V 250V 125V 30V Resistive load(A) 10 10 10 10 10 Inductive load(A) 5 5 5 5 5 8c Contact configuration
TEST
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) are the same with that of the Aux. switch.
Charged
Counter
Mechanically counts the operation of the VCB by 5digits H4-5
Auto connection
When the breaker is moved to Test position from Disconnected position the connector for control powers is automatically connected. In case of reverse moving of the breaker the connector is automatically disconnected.
Reversible contact
10 auxiliary switches are provided. 8 of them consist of reversible 8c which can be changed from a(b) to b(a). Factory composition is 5a3b. And the other 2 switches are supplied as 2b with early-b contact function
Code plate
When the breaker is inserted to the cradle, if the ratings does not match with the cradle, it mechanically prevents the breaker from being inserted into the cradle.
Auto discharge
In case the breaker is drawn-out when the closing spring is charged in the position-Disconnected, Test or Connected, or the breaker is moved to Disconnected position from Test position the closing spring shall be automatically released.
H4-6
H4-7
H4-8
P CS
5a 22 24 26 28 40 54 56 58
P
Auxiliary switch
3b
CS A5
A1
A3
LS2 3
LS3
Yb 6 52a 23 34 25 36 27 38 29 50 41 52 6 1 22 35 24 37 26 39 28 51 40 53
2 1
4 Ya 6 43 54 45 56 47 58
M
7
52b
5 30
31
42 55 44 57 46 59
C Y
8
LS1
1 2 23 25 27 29 41
TC
A2 N
A4
A6
55
57
59
early b
13
14
15
16 17
18
19
20
21
22
23
24
A2 A4 A6 23 25 27 29 41 A1 A3 A5 22 24 26 28 40
1 2 3 4 5 6 7 8 9
55 54
10
57 59 56 58
11 12
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil C : Closing coil Y : Anti-pump relay 52a : Auxiliary switch (NO) 52b : Auxiliary switch (NC) LS1 : Closing interlock limit switch (only withdrawable type) LS2 : Motor stopping, closing spring charged indication LS3 : Anti-closing, Anti-pumping limit switch
Note) Diagram shows the circuit breaker in position OFF closing spring Charged with
Dimensions
Breaker
722 254 254
722 745
<Front view>
109
228
109
228
360
817
369
816
3000A
1200/2000A
<Side view>
360
H4-9
644 850
<Front view>
343 137
100
252 213
310
36
360
1070
2-M12 DP24
1200/2000A
449
50
157
195
630 1020
3000A
2-M12 DP24
<Side view>
H4-10
LVB
05
40
20
1A
2K
LS VCB
Version Pro-MEC 1A 1B 1C 1E
Auxiliary switch 8c
Cradle
LCL
05
40
20
LS Cradle G
Version Pro-MEC 1 2
H4-11
Memo
H4-12
For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
HEAD OFFICE
Global Network LSIS (Middle East) FZE Dubai, U.A.E. Dalian LSIS Co., Ltd. Dalian, China LSIS (Wuxi) Co., Ltd. Wuxi, China
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
Korea Gyeonggi-do Anyang-si dongan-gu LS-ro 127 (Hogye-dong) Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea
LSIS-VINA Co., Ltd. Hochiminh , Vietnam LSIS Shanghai Office Shanghai, China
LSIS Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, LSIS Guangzhou Office Guangzhou, China LSIS Chengdu Office Chengdu, China LSIS Qingdao Office Qingdao, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.