Flat roof, open balcony, verandah roof ,When the line passes above the building a vertical clearance from the highest point
2.5 Meter
Line passes adjacent to the building a horizontal clearance from the nearest point
1.2 Meter
2.5 Meter
1.2 Meter
11 KV to 33 KV
3.7 Meter
Above 33 KV
3.7+(0.3
for
every
additional 33 KV )
Up to 11 KV
The horizontal clearance between the nearer conductor and any part of such building
1.2 Meter
11 KV to 33 KV
The horizontal clearance between the nearer conductor and any part of such building
2.0 Meter
Above 33 KV
The horizontal clearance between the nearer conductor and any part ofsuch building
Across a street
5.8 Meter
High Voltage
Across a street
6.1 Meter
Along a street
5.5 Meter
High Voltage
Along a street
5.8 Meter
4.0 Meter
High Voltage
5.2 Meter
33 KV & EHV
Clearance above ground(Add 0.3 Meter for every 33 KV Volts in 5.2 Meter)