SM-DCEM User Manual

Features introduction
A billing meter for the load of DC power system. The unit can provide two communication modes: CAN and RS 485 and can be used for -48V and +24V system.

No. 1 2 3 4 5 6 7 8

Signal IN1-IN1IN1+IN1+ IN2-IN2IN2+IN2+ IN3IN3+IN3+ IN4-IN4IN4+IN4+

Signal description First-way load shunt voltage, low potential First-way load shunt voltage, high potential Second-way load shunt voltage, low potential Second-way load shunt voltage, high potential Third-way load shunt voltage, low potential Third-way load shunt voltage, high potential Fourth-way load shunt voltage, low potential Fourth-way load shunt voltage, high potential

Signal specification 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal 0~100mV, level signal

Installation
Mounting screws is mainly adopted on the mounting surface. The mounting method is as follows: fix the SM-DCEM on the corresponding mounting place by using four screws respectively to pass through the mounting hole.

Electrical connection
The SM-DCEM has four sockets: power socket, sampling input socket for 4-way load shunt, RS485 socket and CAN communication socket for external electric connection.

Description of terminal J5:


No. 1 Signal CAN_LCAN_L Signal description CAN communication negative CAN communication positive Signal specification Standard CAN level Standard CAN level

CAN_HCAN_H

Description of terminal J3:


No. 1 RS485ARS485A 2 GNDGND 3 Signal Signal description RS485 communication positive Communication reference grounding RS485 communication negative Signal specification Standard RS485 level Reference grounding Standard RS485 level

J4

J2

J5

J3

RS485BRS485B

The wiring diagram of the SM-DCEM is as follows: The definition of interface is as follows:
No. 1 VBUS+VBUS+ Signal Signal description Power supply input port and bus voltage detection, positive pole Power supply input port and bus voltage detection, negative pole Signal specification 0~60V, power supply Reference grounding
SM-DCEM
Power system

Description of terminal J4:

2 VBUS-VBUS-

Description of terminal J2:


Emerson Network Power Co., Ltd.

Wiring description: Connect the two ends of sampling wiring terminal of each shunt to the voltage sampling input terminal of the DCEM shunt. Connect power supply wiring and relative low potential to power supply Vterminal, connect high potential to V+ terminal. Note One end of the shunt of power system shall be directly connected to the negative bus of the system output voltage to avoid the influence of the common mode voltage in event of contactor disconnection and fuse burnout. Note The negative end of each shunt shall be directly connected to sampling terminal to ensure measurement precision. It is not recommended to connect the negative end of the shunt to the sampling terminal after the serial connection of the negative end of the shunt.

CAN address is equal to the value of dialing A [3..1] , while RS485 address is equal to the value of dialing A[3..1]+1. For instance:

The communication address of RS485 equipment is A[3..1]+1 = 2 to explain that RS485 uses 9600 Baud rates. The address of CAN communication equipment is 1.

Performance index
Environmental requirement Operating temperature: 1050 Operating humidity : 95 Atmospheric pressure86kPa106kPa Power input and voltage sampling Rated voltage: DC 48V Voltage range: DC 20V60V Operating current: 25mA Shunt voltage sampling The maximum sampling is shunt voltage for 4 groups, the voltage range of sampling point is 0 100mVdc. Noise Noise at the distance of 1.5m < 50dB Mechanical parameters Dimensions: 20mm (Height) x 100mm (Width) x105 mm (Length) Weight: < 0.5kg

Use
1. The Run LED (green): if the CAN communication is normal, Run LED does not flash. If the CAN communication is abnormal, Run LED flashes once every second. When the high level monitoring selects the unit in the menu, it flashes once every 3 seconds. It flashes once every 1/4 second once RS 485 data appears. 2. DIP switch has 4 bits. Different switch combinations correspond to different alarm deviation threshold set-points (hereafter referred to as alarm threshold set-point). The relationship between Switch state and alarm threshold set-point is as follows: the operation introduction to mini DIP switch for SM-DCEM is shown as the following figure:

The first bit of the DIP switch is used for setting S485 communication Baud rate. When the switch is on, the Baud rate is 9600 n 8 1. When the switch is off, the Baud rate is 19200 n 8 1. CANs Baud rate is consistent, 125K. The combination of bits 2, 3, 4 of toggle can be used as the address setting of the equipment. When the status is on, the value of address is zero. When the status is off, the value is 1.A1 is low bit and A3 is high bit. Their corresponding actual address is different in RS485 and CAN protocol.
Emerson Network Power Co., Ltd.