STANDARD SPECIFICATION

TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM (2 11 015)

0
Rev

08.06.2012
Date

Issued As Standard
Purpose

PS
Prepared By

MLS
Checked By

MLS
Approved By

a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification

NOTE SHEET

PROJECT NO: 110389 PROJECT NAME: CHIMIQUE CONNECTIVITY SPURLINE PROJECT

TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM

Doc No.

Rev

2 11 - 015
Page 2 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification

CONTENTS

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0

GENERAL FIRE DETECTION SYSTEMS GAS DETECTION SYSTEM FIELD ANNUNCIATION DEVICES FIRE AND GAS ALARM /MONITORING PANEL PORTABLE CALIBRATOR AREA CLASSIFICATION POWER SUPPLY FIRE DETECTION LOCATION PLAN

TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM

Doc No.

Rev

2 11 - 015
Page 3 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification 1. GENERAL This document defines the technical requirements for Design, engineering, Fabrication / manufacturing, assembly, testing at works, packing and supply of Fire and Gas Detection systems in well packed condition.

2. 2.1

FIRE DETECTION SYSTEMS SMOKE DETECTION Smoke detectors shall be provided in control building. The detectors shall be installed in control room inside cable trenches, inside building in various rooms, electrical equipment room. High sensitivity photo cell type (optical type) smoke detectors shall be provided. All smoke detectors shall have self checking facility. Each detector shall have a LED indicating the status of the detector. For smoke Detectors installed above false ceiling and in cable trenches remote indicator shall be provided in fire and gas panel. Circuit type: 2 wire. Open and short circuit shall be monitored by end of line resistor. All smoke detectors shall have facility for remote reset. Mounting type: on ceiling with base. Alarm indication shall be LED.

2.2

HEAT DETECTORS Heat detectors shall be provided in battery room. Rate of temp. rise type detectors shall be provided as these provide rapid response while the ambient temp. is subject to fluctuations. Quantity and installation requirements are given in data provided in this specification. Temp set point: 85 Deg C. Mounting: on ceiling with base. Circuit type: 2 wire. Alarm indication: LED. Open and short circuit shall be monitored by end of line resistor. All heat detectors shall be auto reset type.

2.3

Manual Call Points: Manual Call Points (MCP) shall be positioned in such a way that they stand out against the Background i.e. they shall be clearly recognizable from a distance either by day or Night. Manual call points shall be located; a) Two nos at each end outside control building b) Outside guard room (one no.) c) One no. as decided in field by Engineer-in-charge. Type: Break glass type. TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM
Doc No. Rev

2 11 - 015
Page 4 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification Operation: By hammer. Hammer and chain shall be provided. Housing material: UV resistant GRP for break glass installed outside control building IP 65. MCPs installed outdoors in field shall be in addition be suitable for hazardous area classified Housing colour:- Red paint two coat epoxy type. Each manual call point shall have SS tag / label with wording Manual alarm call station, & Break glass to activate 3.0 3.1 Gas Detection system. Open path gas detectors:IR absorption type gas detectors shall be provided as follows: 2 nos detectors near each pig launcher / pig receiver 2 nos around isolation valve in SV station. 4 nos detectors around metering skid. Power supply: 24 VDC. Area classification:-Zone1,Gr IIA,IIB,T3. Weather proof protection: IP65. Out put :-4-20 ma DC. Accuracy:-+/-3% full scale. Response time:-T 95<5 secs. Range :8 LEL meters/100 meters minimum. Housing Material:-Aluminium alloy/SS 316. Mounting: Swivel mounting. Lens cleaning fluid shall be supplied by contractor. Beam blockage more than 10 secs. Shall give BEAM BLOCKED warning after 60 secs Shall give fault alarm. Calibration Accessories. Hand held calibrator suitable for area classified with battery and charging unit, TEST FILM etc; Tag plate :-SS 316. 3.2 Fixed point gas detectors.: IR absorption type detectors shall be provided as follows: 2 nos detectors near each pig launcher/pig receiver. 2 nos around isolation valve in SV station 4 nos detectors in metering skid. Power supply: 24 V DC. Area classification :- Zone 1,Gr. II A.IIB.T3. TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM
Doc No. Rev

2 11 - 015
Page 5 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification Weather proof protection:-IP65. Detection Range:-100% LEL. Out put: 4-20 mA DC Accuracy : +/- 3% full scale. Response time : TT90< 15 Secs. Housing material: aluminium alloy/ss316. Tag plate: SS required with tag details. Each detector shall be equipped with facilities for site calibration and testing. The detection Range shall be adjustable between 0 and 100% LEL. 4.0 Field Annunciation Devices. Alarm Beacons / Flash Lights. Alarm beacons shall be rotating type with a coloured lens and dual high intensity halogen Bulbs. One no. red (for fire alarm) and one no. blue (for gas alarms) shall be supplied and installed at highly visible location outside control building. 5.0 Fire and gas alarm /monitoring panel. A fire and gas alarm monitoring panel shall be supplied and installed in each control room. This panel shall have following minimum facilities /equipments. a) For gas detectors Single channel gas monitors shall be provided with 0-100% LEL indication (LCD) ,alarms adjustable over 100% LEL range ) for low and high LEL.,AND fault alarm.(LEDs). Shall have test/acknowledge alarm, reset push buttons. Alarm annunciator showing zone wise fire alarms, and remote indication for smoke Detectors installed above false ceiling and inside cable trenches. A horn installed above fire /gas alarm panel, and high sound level (120 DbA) Guard room. The panel shall be wall mounting type suitable for safe area installation. 6.0 Portable Calibrator: 6.1. Three portable calibrator for fixed point detectors consisting of all accessories like volume bottles, containing known gas / mixture, a pressure regulator, a flexible hose adapter cap shall be supplied to enable field calibration of the sensors/detectors without dismantling them from the field. Calibration range shall be suitable for the sensors supplied, 0-100% LEL. Sufficient quantity of calibration gas shall be supplied to enable calibration of all the Sensors / detectors at least twice. installed

b)

c)

6.2 6.3

7.0.

Area classification The Hazardous area classification is Zone 1, gas Group IIA/IIB, Temp. Class T3. Certification requirement for instruments items are as below: For

TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM

Doc No.

Rev

2 11 - 015
Page 6 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd

Standard Specification For all flame proof equipment / instrument / systems, which is manufactured abroad (outside India) certification by any approving authority like BASEEFA, FM, UL, PTB, LCIE. ATEX etc shall be required. For units manufactured in India certificate from CMRI will be required. 8.0 Power supply Power supply available is 24V DC., Contractor to convert from this level to other levels

9.0

FIRE DETECTOR ALLOCATION PLAN Sl. no

Area Description

OSD

HD

MCP

ZONE

Control room / UPS room a) above false ceiling

__

__

Zone-1

b) Below false ceiling 2 Inside cable ducts in Control room, Electrical room. Battery room Electrical Equip room Manual Call points Outside control room, Electrical room, In field. Guard room.

2 2

__ __

_ __

Zone-2 Zone-3

3 4 5

__ 2 __

4 __ __

__ __ 3

Zone-4 Zone-5 Zone-6

Zone-7

OSD - Optical smoke detector HD - Heat detector MCP Manual call point

TECHNICAL SPECIFICATION FOR FIRE & GAS DETECTION SYSTEM

Doc No.

Rev

2 11 - 015
Page 7 of 7

0
a trading name of Wood Group Kenny India Pvt. Ltd