Академический Документы
Профессиональный Документы
Культура Документы
Features
The SureCross DX80 is a radio frequency network system built around a Gateway and one or more Nodes. Internal three-axis magnetoresistive-based technology senses three dimensional changes to the Earths magnetic field caused by the presence of ferrous objects Designed to minimize the effects of temperature changes and destabilizing magnetic fields Sensor learns ambient background and stores settings in non-volatile memory FlexPower technology driven off one lithium primary battery integrated into the housing Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access (TDMA) control architecture combine to ensure reliable data delivery within the unlicensed Industrial, Scientific, and Medical (ISM) frequency bands Transceivers provide two-way communication between the Gateway and Node, including fully acknowledged data transmission Lost RF links are detected and relevant outputs set to user-defined conditions Sealed housing contains the battery, sensor, and antenna for a completely wireless solution For additional information please refer to Banner Engineerings Web site.
Models
Model
DX80N9X2S0P0Z0 DX80N2X2S0P0Z0
FlexPower
3.6V dc Battery
Frequency
900 MHz ISM Band 2.4 GHz ISM Band
I/O
Internal M-GAGE (no additional I/O points)
Theory of Operation
The sensor uses three mutually perpendicular magnetoresistive transducers, with each transducer detecting magnetic field changes along one axis. Incorporating three sensing elements produces maximum sensor sensitivity. A ferrous object alters the local (ambient) magnetic field surrounding the object, as shown in Figure 1. The magnitude of this magnetic field change depends both on the object (size, shape, orientation, and composition) and on the ambient magnetic field strength and orientation. During a simple programming procedure, the M-GAGE sensor measures the ambient magnetic field. When a large ferrous object alters that magnetic field, the sensor detects the magnetic field changes (anomalies). When the degree of magnetic field change reaches the sensors threshold, the device reports a change of state.
Field A: Baseline magnetic field with slight disturbances caused by permanent ferrousmetal objects within or near the sensor.
The sensor detects changes in the ambient magnetic field in all directions. As with other sensors, the range depends upon the target. The strong disturbance of a large ferrous object decreases as distance from the sensor increases; the magnitude and shape of the disturbance depends upon the objects shape and content. The sensor can be programmed to react to magnetic field disturbances of greater or lesser intensity, using three adjustments: baseline, threshold, and hysteresis. Note: The sensor continues to sense a vehicle in its sensing field even when the vehicle is stopped.
Field B: After a large object is introduced, the magnetic field changes. The sensor detects the changes in the fields strength and orientation between the ambient field and Field B. If the differential is greater than the sensitivity threshold, the device reports a change of state. Figure 1: Magnetic Detection Overview
The M-GAGE value in I/O 1 is the deviation between the total measured magnetic field in the X, Y, and Z axes and the stored baseline. The lowest significant bit (LSB) indicates the discrete on and off value, within the threshold and hysteresis. For example, if the M-GAGE threshold is set to 100, any value returned from the M-GAGE above 100 is equivalent to a discrete ON and the lowest significant bit will be set to 1. There are sixteen Modbus holding registers for each device. Calculate the holding register number for each device using the equation: Register number = I/O# + (Node# 16). Since the Gateway is always Node 0, the Gateways holding registers are registers 1 through 16 while registers for Node 1 are 17 through 32.
Using the equation, the register number for I/O point 15 for Node 7 is 127.
Configuration
All wireless M-GAGE configuration is performed using the Web Configurator and/or Modbus commands. The two sensor parameters are the baseline magnetic field level and sensing thresholds.
Baseline
For a host-connected system, set the baseline magnetic field by writing to a Modbus register. Sending the value of 4096 (0x1000) to the Nodes I/O point 15 (Control Message) triggers the M-GAGE to read the existing magnetic field as the new baseline. For non-host connected systems, use the special M-GAGE Gateway to set the baseline. The inputs of the M-GAGE Gateway are mapped to the M-GAGE Nodes I/O point 14. Activating the Gateways input triggers the M-GAGE to use the existing magnetic field as the new baseline.
Use the parameter control codes to write to the specific I/O points of given Node. Parameter Number
8, 9 8, 9
Description
Write I/O 1 Read I/O 1
Parameter numbers indicate which specific parameters are being changed. Definition
Threshold - (bits 15:0)
Description
Disable: 0. Default: 100. The trigger point or threshold for an analog input. When an analog input is greater than or equal to the active threshold value, a ON or 1 event is reported. If the analog input does not reach the active threshold value, no event change is reported. The parameter is a two byte value between 1 and 65535. Disable: 0 Default: 30. Works with the active threshold parameter to define when to disable event reporting of an analog input. The hysteresis parameter defines how much below the active threshold the input is required to be before the input is considered to be off. The parameter is a two byte value between 1 and 65535.
Example
To change Node 5s M-GAGE threshold, use control code 129 (Write I/O 1, hex 81), parameter 8, sent to register 15 of Node 5, which is Modbus register 15 + 5 16 = 95 (hex 5E). Send the new parameter setting to Node 5s register 16. Each parameter has specific values defined in the Parameter Number table. The example Modbus command (in hex) to write a value of 640 would read something like the following table.
Description
Modbus Write Multiple Registers Starting Register - 1 Register Count Byte Count Parameter Control Code Parameter Number Write/Read Parameter Data Function
Field Name
Hex Value
10 00 5E 00 02 04 81 08 02 80
Starting Address Hi Starting Address Lo Quantity of Registers Hi Quantity of Registers Lo Byte Count #1 Register Value Hi #1 Register Value Lo #2 Register Value Hi #2 Register Value Lo
The Write Single Holding Register command writes a single holding register in a remote device. The request specifies the address of the register to be written. Registers are addressed starting at zero; register 1 is addressed as 0. The normal response is an echo of the request, returned after the register contents have been written.
The Write Multiple Holding Registers command writes a block of contiguous registers (1 to approximately 120 registers) in a remote device. The requested written values are specified in the request data field. Data is packed as two bytes per register. The normal response returns the function code, starting address, and quantity of registers written.
Top View
(default)
M-GAGE Reading
600 500 400 300 200 100 0 0 0.5 m (1.6') 1.0 m (3.2') 1.5 m (4.8') 2.0 m (6.4')
Threshold Output OFF
7.3 m (24')
Output OFF Output ON Threshold
Side View
M-GAGE
2.5 m (8.0')
Figure 2: Sensor mounted one meter (.2 ft) above the ground.
-2.4 m (-8') -1.2 m (-4') 0 1.2 m (4') 2.4 m (8') 3.7 m (12') 4.9 m (16') 6.1 m (20') 7.3 m (24')
Top View
M-GAGE
600
M-GAGE Reading
500 400 300 200 100 0 -2.4 m -1.8 m -1.2 m -0.6 m (-8') (-6') (-4') (-2') 0m 0.6 m 1.2 m 1.8 m (2') (4') (6') 2.4 m (8') 3.1 m 3.7 m 4.3 m (10') (12') (14') 4.9 m (16') 5.5 m (18') 6.1 m (20') 6.7 m (22')
(default)
Side View
M-GAGE
Figure : Sensor mounted 0.25 meters (0.8 ft) below the ground.
Output ON
Determine the geometric center of the space the vehicle would normally occupy and mark this location as the center of the hole. Score the asphalt in an 8-inch square around the center point.
Using an 8-inch masonry or diamond blade in a circular saw, cut the marked square, leaving clean, sharp edges for patching later. Using a jackhammer or hammer and chisel, break away the asphalt to expose the aggregate underneath. Uncut asphalt in the corners of the square section do not have to be removed. Remove enough asphalt to allow the PVC enclosure to pass through easily. Clear the aggregate to make a hole approximately nine inches deep. Ensure the holes bottom surface is level, flat, and tightly packed before continuing.
Place the PVC enclosure into the hole so that the top of the enclosure rests approximately three inches below the pavements original surface. Backfill tightly around the perimeter of the enclosure with fresh Class 5 aggregate before patching the pavement with asphalt hot-patch. (Shown without PFC enclosure lid.)
Bad Placement
The drawing at left depicts a potential problem installation. While mounting the sensor at the side of a lane may be successful, this mounting location increases the potential for problems. To reliably detect a vehicle from the side, the sensor threshold must be increased to see objects further away in the lane of interest. Unfortunately, this enables the sensor to also detect a lawn mower operating behind the sensor or vehicles in adjacent lanes, causing false counts. Place the M-GAGE sensor at the edge of a traffic lane only if there is no possibility of the sensor detecting other objects. To avoid detecting other objects, ensure no vehicles will be within 10 feet of the sensor on the non-traffic side.
General
Power Mounting M5 fasteners Max. Tightening Torque Case Material Weight Indicators Switches 3.6V dc low power option #10 or M5 (M5 hardware included) 0.56 N/m (5 in/lbf) Polycarbonate 0.23 kg (0.50 lb.) Two LED, bi-color Two Push Buttons 900 MHz Range* Frequency Transmit Power Spread Spectrum Technology Link Timeout 1000 feet, line of sight 902 to 928 MHz ISM band 21 dBm Conducted FHSS (Frequency Hopping Spread Spectrum) Defined by Gateway 2.4 GHz 1000 feet, line of sight 2.4 to 2.4835 GHz ISM Band 18 dBm Conducted, 20 dBm EIRP FHSS (Frequency Hopping Spread Spectrum) Defined by Gateway
Radio
* The range depends upon the environment and line of sight and is lower when buried.
M-GAGE
Input Sample Rate Report Rate Ambient Temperature Effect Sensing Range Internal Magnetometer 250 milliseconds On Change of State Less than 0.5 milligauss/C See figures 2 and 3
Environmental
Environmental Rating Operating Temperature* Operating Humidity Shock & Vibration IEC IP67; NEMA 6 -40 to +85 C 95% max. relative (non-condensing) IEC 68-2-6 and IEC 68-2-7 Shock: 30g, 11 millisecond half sine wave, 18 shocks Vibration: 0.5 mm p-p, 10-60 Hz
* Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.
Compliance
900 MHz Models 2. GHz Models FCC ID TGUDX80 - This device complies with FCC Part 15, Subpart C, 15.247 FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart C, 15.247 ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05)