Вы находитесь на странице: 1из 74

POWER PROTECTION

Series AP4300 UPS AP4300 Three Phase 7.5 to 20kVA 50 or 60Hz.

Installation Operation and Maintenance Manual

AP4300
AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

AP4300

Manual Part Number 04569270-3

IOM Manual
Table of Contents
Important Instructions For Safe Use . . . . . . . . . . . . . . . . . . . . . . . . . . v Important Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi

Chapter 1 - General Description


Introduction . . . . . . . . . . . . . . . . . . . . . . Equipment construction . . . . . . . . . . . . . . . . Principle of operation . . . . . . . . . . . . . . . . . Basic Concept . . . . . . . . . . . . . . . . . Primary Power Path . . . . . . . . . . . . . . Static switch . . . . . . . . . . . . . . . . . . Maintenance bypass line . . . . . . . . . . . . System operation . . . . . . . . . . . . . . . . . . . Operation during normal conditions . . . . . Operation during input power supply failure . Operation during abnormal / fault conditions . Maintenance bypass. . . . . . . . . . . . . . . Electrical switches . . . . . . . . . . . . . . . . . . . Circuit breakers and fuses . . . . . . . . . . . Control switches . . . . . . . . . . . . . . . . Internal Cutout Relays . . . . . . . . . . . . . Operator control switches . . . . . . . . . . . . . . . Main control switch . . . . . . . . . . . . . . Input/Battery fuse holders . . . . . . . . . . . Output Off Switch (SW2) . . . . . . . . . . . LCD controls - on/off command. . . . . . . . Remote Stop Switch (optional) . . . . . . . . . . . . . . . . . . . . Optional operator controls . . . . . . . . . . . Emergency Shutdown . . . . . . . . . . . . . Operator Control & Display Panel . . . . . . . . . . LCD Display, Controls & Screen . . . . . . . LED Displays . . . . . . . . . . . . . . . . . Indicator Bars . . . . . . . . . . . . . . . . . Alarm indicator & horn cancel button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-1 1-1 1-1 1-1 1-2 1-2 1-2 1-2 1-2 1-3 1-3 1-3 1-3 1-4 1-4 1-4 1-4 1-5 1-6 1-6 1-6 1-6 1-6 1-7 1-7 1-8 1-9 1-9

Chapter 2 - Operating Instructions


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 The Operating procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Fault Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Cold Start Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 NORMAL operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Setting Date, Time & Language . . . . . . . . . . . . . . . . . . . . . . . 2-4 UPS Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Switching the Output Off/On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Output Off Switch SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Operation from the UPS control panel . . . . . . . . . . . . . . . . . . . . 2-6 Switching with External Commands . . . . . . . . . . . . . . . . . . . . . 2-8 Input Power Supply Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 Input Supply Failure when On Load . . . . . . . . . . . . . . . . . . . . . 2-8 Input Supply Failure when Off Load . . . . . . . . . . . . . . . . . . . . . 2-9 Applying Power to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10 Starting up the UPS on battery ( black start) . . . . . . . . . . . . . . . . . . . 2-11 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 To Put the Load on Maintenance Bypass (MBP) . . . . . . . . . . . . . . . . . . 2-11 Removing Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12

Issue 3 (01/03/98)

AP4300
Chapter 3 - Installation Instructions
Safety warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 On Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Weight considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Extended battery option . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Removal from Shipping Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Units shipped with batteries . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Units shipped without batteries. . . . . . . . . . . . . . . . . . . . . . . . 3-5 Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 Connecting the UPS Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 General introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 Cable sizing consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 Input supply protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Terminal connection points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Procedure for connecting the UPS to the power supply . . . . . . . . . . . . . . 3-12 Common input/bypass supply system . . . . . . . . . . . . . . . . . . . . 3-12 Split input/bypass supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Electrical Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13

Chapter 4 - Options and Features


Introduction . . . . . . . . . . . . . . . . . . . . . Standard Features . . . . . . . . . . . . . . . . . . Auto-restart Inhibit. . . . . . . . . . . . . . Common Bypass Links . . . . . . . . . . . Remote stop . . . . . . . . . . . . . . . . . Hot Standby Configuration . . . . . . . . . Remote Control/ Communications Facilities . . . . RS232 Interface and External Relay Board . SNMP Interface . . . . . . . . . . . . . . . Interface Software . . . . . . . . . . . . . . Remote Alarm Monitor . . . . . . . . . . . Extended Battery Options . . . . . . . . . . . . . . Extended Battery . . . . . . . . . . . . . . Remote Battery. . . . . . . . . . . . . . . . Power Options . . . . . . . . . . . . . . . . . . . . Input Harmonic Filter . . . . . . . . . . . . Isolation Transformer . . . . . . . . . . . . Filter &Transformer . . . . . . . . . . . . . External Bypass Enclosure . . . . . . . . . Distribution Cabinet . . . . . . . . . . . . . Frequency Changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4-1 4-1 4-1 4-1 4-1 4-2 4-2 4-5 4-5 4-6 4-7 4-7 4-7 4-8 4-8 4-8 4-8 4-8 4-9 4-9

ii

Issue 3 (01/03/98)

IOM Manual
Chapter 5 - Troubleshooting
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm indications . . . . . . . . . . . . . . . . . . . . . . . . . . Audible Alarm Horn . . . . . . . . . . . . . . . . . . . . . LED Indications . . . . . . . . . . . . . . . . . . . . . . . Messages in the LCD Text Window . . . . . . . . . . . . Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . Fault Records. . . . . . . . . . . . . . . . . . . . . . . . . Alarm Interpretation and Corrective action . . . . . . . . . Troubleshooting Charts . . . . . . . . . . . . . . . . . . . . . . . Checking the input and bypass circuit breakers, and battery fuses Battery fuse check . . . . . . . . . . . . . . . . . . . . . . Circuit breaker check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5-1 5-1 5-1 5-2 5-3 5-3 5-3 5-4 5-8 5-8 5-8 6-1 6-1 6-1 6-1 6-3 6-4 6-4

Chapter 6 - Maintenance
Routine Maintenance Checks by the Operator . . . Introduction . . . . . . . . . . . . . . . . . Checks at weekly intervals. . . . . . . . . . Checks at monthly intervals . . . . . . . . . Annual checks . . . . . . . . . . . . . . . . Annual Maintenance Checks by Service Engineer . Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 7 - Liebert Warranty


Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Life Support Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1

AP4300 Series UPS Specification 8-1 Parameter Settings for the AP4300 8-3

Issue 3 (01/03/98)

iii

AP4300
This equipment has been designed and manufactured by Liebert, market leaders in the field of Uninterruptible Power Systems (UPS); and, if installed and used correctly, will provide years of trouble-free operation. This manual contains the information necessary for the correct operation and safe installation of the AP4300 Series UPS. Please read the manual carefully before you attempt to install your UPS, or connect any equipment to it. For your safety it is important that you comply with the instructions for safe use. Please keep this manual safe for future reference. PLEASE NOTE: The AP4300 Series UPS has been designed for Commercial/Industrial use only. Please refer to warranty for restrictions on use.
This manual describes the following AP4300 series UPS models: MODEL NUMBER
AP4307 AP4310 AP4315 AP4320 AP4307 AP4310 AP4315 AP4320

DESCRIPTION
7.5kVA 50 Hz. UPS 10kVA 50 Hz. UPS 15kVA 50 Hz. UPS 20kVA 50 Hz. UPS 7.5kVA 60 Hz. UPS 10kVA 60 Hz. UPS 15kVA 60 Hz. UPS 20kVA 60 Hz. UPS 75407002 75410002 75415202 75420202 75407602 75410602 75415602 75420602

PART NUMBER
Without Batteries With Batteries 75407102 75410102 75415302 75420302 75407652 75410652 75415652 75420652

Importatnt: All models in the UPS range are similar in operation and use. The illustrations in this manual depict the 10kVA model (AP4310) unless otherwise stated.

If you encounter any problems with the equipment or the procedures contained in this manual you should seek immediate assistance from the Liebert distributor from whom the equipment was purchased. Alternatively contact Liebert's Customer Service & Support Department at the address shown below: Technical Support Department,, Liebert Global Services Globe Park, Marlow, Bucks, SL7 1YG, U.K. Telephone +44 (0) 1628 403200 - Fax +44 (0) 1628 403203 This department also arranges service contracts and full commissioning service.

Liebert Corporation pursues a policy of continual product development and reserves the right to make changes to equipment design without notice.

Copyright 1996 Liebert Corporation Unauthorised reproduction prohibited. All rights reserved.

iv

Issue 3 (01/03/98)

IOM Manual
Important Instructions For Safe Use

q q

q q

q q q

The UPS must be commissioned by a Liebert approved engineer before it is put into service. Failure to observe this condition will invalidate any implied warranty. Do not apply power to this equipment before it has been commissioned by a Liebert approved engineer. He will validate the installation work and install site information into the microcontroller memory. This information is required to substantiate any warranty claims that might be made. These units contain no user serviceable parts. Under no circumstances attempt to gain access internally, due to risk of electrical shock or burn. Do not continue to use your UPS if the front panel indications are not in accordance with these operating instructions, or the UPS performance alters in use. Refer all faults to your dealer. The UPS is for indoor use only. It must be protected from rain or excessive moisture and installed in a clean environment, free from flammable liquids, gasses, or corrosive substances. Do not put drinks, plants, or any other containers holding liquids, on top of the unit. Competent personnel should be consulted if liquid spills into the product. Ventilation grills are provided beneath (and on the left hand side on 15/20kVA models) and at the rear of the cabinet. Do not block or cover these openings otherwise overheating may occur and UPS operation become unreliable. Never insert any object into these ventilation holes or openings. Do not place magnetic storage media on top of the unit as it can corrupt the data stored on them. The front control and display panel is designed for hand operation. Do not press with sharp or pointed objects. The following definitions are given for your information and safety: Operator/User Personnel who have received instruction on the correct operation of the UPS controls - limited to operation of Switch 1, Switch 2 and the Front Control Panel - not permitted to remove any panels which are retained by screws. Competent Personnel Personnel who are aware of the dangers appropriate to working with hazardous voltages and are deemed to have sufficient technical skills/training to make electrical connections, install batteries, close and open circuit breakers/fuses etc. (i.e. a qualified electrician). Service Personnel Engineers who have received the relevant Liebert training and are password authorised.

ELECTROMAGNETIC COMPATABILITY This equipment complies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only. WARNING THIS IS A CLASS A - UNINTERRUPTIBLE POWER SYSTEM PRODUCT. IN A DOMESTIC ENVIRONMENT, THIS PRODUCT MAY CAUSE RADIO INTERFERENCE, IN WHICH CASE, THE USER MAY BE REQUIRED TO TAKE ADDITIONAL MEASURES. WARNING THIS UPS SHOULD NOT BE SUPPLIED FROM ELECTRICAL POWER SYSTEMS OF THE IT (IMPDANCE TERRE) TYPE. (IEC 364 - ELECTRICAL INSTALLATION OF BUILDINGS) Note: Where use on IT systems is required we offer the optional input isolation transformer see chapter 4 for more information.

Issue 3 (01/03/98)

AP4300
Important Symbols
Symbols used on the AP4300 series UPS are in two categories SAFETY and OPERATIONAL, and are listed below.
SAFETY SYMBOLS.

WARNING - HAZARDOUS VOLTAGE

WEIGHT

MAXIMUM OPERATING TEMPERATURE 40oC

VALVE REGULATED LEAD ACID BATTERY (VRLA)

WARNING - THE BATTERY CONTAINS CORROSIVE MATERIAL


OPERATIONAL SYMBOLS.

BATTERY ISOLATION FUSES

READ THE INSTRUCTION MANUAL

CAUTION: NOTE THE FOLLOWING INSTRUCTION

INPUT AC SUPPLY

UPS AC OUTPUT

vi

Issue 3 (01/03/98)

Chapter 1 - General Description

1.1

Introduction

1.3

Principle of operation
Main Switch SW1 Output to Load

This chapter describes the purpose, principle of operation and user controls of the AP4300 series on-line Uninterruptible Power System (UPS). The AP4300 series UPS is connected between a critical load, such as a computer, and its input power supply. Its purpose is to provide the load with well regulated power under all rated load and input supply conditions; i.e. the power provided by the UPS will be protected from any voltage or frequency variations on the incoming power supply, or variations in the supply due to electrical noise, and will continue during periods of input power supply failure. A battery provides a standby power source for the UPS when the input a.c. supply fails.

Maintenance Bypass Line

Bypass Supply
Input Rectifier

Static Switch

Resonant Circuit

High Frequency Rectifier

Inverter

1.2

Equipment construction

Input Supply
Battery

Battery Charger

Figure 1-2 UPS Basic block diagram


AP4300 UPS hh:mm:ss NORMAL NO ALARMS dd:mm:yy

AP4300

1.3.1

Basic Concept

Figure 1-1 Front view of the cabinet The equipment is constructed around a steel frame with removable panels. The right-hand front panel can be lifted off to give easy access to the input & bypass circuit breakers and the operator control switch, while protecting them from accidental operation. The left-hand front, and left-hand side panels are located on spigots and secured to the frame by screws. A display and control panel on the front of the cabinet permits the operator to monitor the performance of the UPS. The cabinet houses both the power components and the batteries. It is carried on six wheels. Jacking feet help to support the UPS, and also prevent it from moving once it has been wheeled into its final position. These feet are also used to secure the equipment to its shipping pallet during transit. Dimensions of all available models are given in the Specification at the end of this manual. Cooling is by a set of internal fans. Air is drawn in through the UPS and exhausted via ventilation grills in the rear and side panels. These areas must be kept free of anything that may impede the air flow into and out of the unit.

The UPS acts as an AC - DC - AC converter. The arrangement of the main components is shown as a block diagram in figure 1-2. The AC - DC stage comprises three steps; in the first step the a.c. is converted by a rectifier to d.c.; in the second step a resonant converter converts the d.c. to high frequency a.c.; and in the third step a rectifier converts the high frequency a.c. to high voltage d.c. A battery, to provide power when the input to the rectifier fails, is charged by a battery charger which is run from the resonant converter. The DC - AC stage comprises a high frequency inverter which converts power from the high voltage d.c. rectifier back to a.c. at the input supply voltage and frequency. The use of a high frequency converter and a high d.c. voltage bring advantages of size and weight reduction while permitting a wide input voltage range. The main switch permits the operator to connect the output terminals directly to an a.c. input supply via the maintenance bypass line, and a static switch permits the UPS to do the same automatically, if necessary. 1.3.2 Primary Power Path The Input rectifier converts the incoming 3-phase 50Hz a.c. input supply to d.c. power at a nominal 580V at its output - i.e. the primary d.c. busbar. The rectifier is uncontrolled and the voltage on the d.c. busbar will vary as the input voltage varies. The resonant converter comprises a resonant circuit, isolation transformer and a high frequency rectifier. The rectified 3-phase input supply is converted to single phase a.c. power at high frequency, and then converted to high voltage d.c. by a high frequency rectifier. The d.c. output is regulated by the converter controller to 800V d.c. which is 400V, with respect to neutral, to power a high frequency transformerless inverter. The inverter converts the 800V d.c. power to 3-phase, 50Hz, a.c. power at the output for use by the critical load. The control electronics ensure that the inverter output is synchronised with the bypass supply.

Issue 3 (01/03/98)

1-1

Chapter 1 - General Description


High frequency harmonics are filtered so the load sees a clean, sinusoidal waveform with low harmonic distortion. The battery charger is a.c. coupled to the converter and converts the high frequency sine wave to 435V d.c. for charging the battery. A standard AP4300 system uses one set of thirty-two 12 V batteries, connected in series, to provide a nominal battery voltage of 384V d.c. (the standard 15/20kVA models contain two sets of thirty-two 12 V batteries). When the input supply becomes unavailable the input rectifier stops maintaining the d.c. bus voltage. The battery then provides power to the primary d.c. bus, and the battery charger becomes inactive. 1.3.3 Static switch The static bypass (SBP) switch is an electronically-controlled switch which, when turned on by the UPS, connects an a.c. input supply directly to the UPS output terminals (a load transfer). The load is then supplied directly from the a.c. input supply. The a.c. supply to the static switch, annotated bypass supply in figure 1-2, can be taken from the same source as that supplying the input terminals, or may be taken from a separate source (Split Bypass). Two conditions cause the static switch to perform a load transfer: 1) when the UPS control electronics automatically shut down the inverter because of an overload condition or a UPS internal failure such as an inverter fault; the static switch closes simultaneously so as to transfer the load to the bypass supply. 2) where the bypass supply to the UPS is taken from a separate source (Split Bypass), and the battery has discharged after supplying power to the load following either a failure of the input power supply to the input terminals or an input overvoltage. During start up and normal operation, the inverter control logic ensures that, provided the bypass supply voltage and frequency are within defined limits, the inverter output and the static bypass supply will be synchronised within specified limits. Transfers between the inverter output and the static bypass supply can then take place without a break in the power supply to the load. However, if the bypass supply voltage or frequency go outside their set limits, the UPS can no longer automatically transfer the load to the bypass, and a message on the LCD display panel warns of this condition. Whenever power is supplied to the SBP during a start up or after a bypass input failure, the control system checks that the supply voltage and frequency are within tolerance and that the phase rotation is correct, and then tests the operation of the SBP switch by briefly transferring to bypass. During the test a [UPS ON BYPASS] message is displayed on the LCD panel (see Section 1.7.1.LCD Display - Controls & Screen). Caution When the load is being supplied through the static switch or the maintenance bypass line, it is connected directly to the input power supply and is therefore no longer protected against power failures or power supply fluctuations. 1.3.4 Maintenance bypass line The maintenance bypass line provides a direct connection between the load and the bypass supply for use when the UPS is shut down for maintenance or troubleshooting. The load is switched to the maintenance bypass line manually with the main control switch, SW1. Note: A manual transfer to bypass is not recommended if a bypass alarm is present, unless a message on the LCD display panel requests it.

AP4300
1.4 System operation

The resonant converter, battery charger, inverter and static switch are controlled by a microcontroller board. Figures 1-3 to 1-7 illustrate the load power paths through the UPS during its major operating modes. The resonant converter, the high frequency transformer and the high frequency rectifier are shown as a single block in these diagrams. The solid black lines represent the active power paths. 1.4.1 Operation during normal conditions During normal operation, the input rectifier provides power, via the resonant converter and high frequency rectifier, to the inverter. The inverter provides power to the load, and the battery charger float charges the battery at 435V. See figure1-3
Maintenance Bypass Line Main Switch SW1 Output to Load Bypass Supply
Input Rectifier Static Switch

Resonant Converter

Inverter

Input Supply
Battery

Battery Charger

Figure 1-3 UPS Normal operation 1.4.2 Operation during input power supply failure If the a.c. input power supply to the UPS fails, the rectifier stops supplying power to the inverter; the battery is automatically connected to the d.c. busbar via an SCR so that the inverter takes its power from the battery, as shown in figure 1-4; and the battery charger becomes inactive. The period for which the load is supplied by the battery after a input power supply failure (the Autonomy Time) depends upon both the battery capacity, and the percentage of the rated load being supplied. Refer to the equipment specification at the end of this manual.
Maintenance Bypass Line Main Switch SW1 Output to Load

Bypass Supply
Input Rectifier

Static Switch

Resonant Converter

Inverter

Input Supply
Battery

Battery Charger

Figure 1-4 Operation from the battery after an input power supply failure

1-2

Issue 3 (01/03/98)

IOM Manual
When the battery is fully discharged, the action taken by the UPS depends on whether the bypass supply is taken from the same source as the main input (common bypass), or from a separate source (split bypass). Units with split bypass When the end of battery discharge is reached in a split bypass system, the UPS transfers the load to the bypass supply, closing the static switch and switching off the battery SCR, as shown in figure1-5. Caution When the load is being supplied from the bypass line through the static switch, it is connected directly to the input power supply and is therefore no longer protected against input power supply disturbances. If, later, the input power supply returns, the input rectifier powers up and the UPS automatically re-starts the inverter, opening the static switch to transfer the load back to the inverter. The system is then in the normal operating condition and recharging the batteries.
Maintenance Bypass Line Main Switch SW1 Bypass Supply
Input Rectifier

Chapter 1 - General Description


Maintenance Bypass Line Main Switch SW1

Output to Load Bypass Supply


Input Rectifier Static Switch

Resonant Converter

Inverter

Input Supply
Battery

Battery Charger

Figure 1-6 UPS Operation on static bypass after an inverter fault condition.
Maintenance Bypass Line Main Switch SW1 Output to Load
Static Switch

Bypass Supply
Input Rectifier

Static Switch

Resonant Converter

Inverter

Input Supply
Inverter

Resonant Converter

Battery Charger
Battery

Input Supply
Battery

Output to Load

Battery Charger

Figure 1-7 UPS Maintenance Bypass Selected. 1.4.4 Maintenance bypass.

Figure 1-5 Split Bypass - Load is transferred to bypass when end of battery discharge is reached. Units with common bypass When the end of battery discharge is reached in a common bypass system, the inverter shuts down and power to the load is lost. Automatic restart facility: A UPS with a common bypass will automatically restart if the input power supply returns after the autonomy time expires, provided the control switches have not been operated in the meantime.

Setting the main control switch, SW1, to Maintenance Bypass connects the UPS output terminals directly to the bypass supply terminals via the internal maintenance bypass line, as shown in fig. 1-7, so that the critical load is powered from the bypass supply. The inverter and converter are shut down and the static bypass switch disabled. This isolates the critical load totally from the inverter output so that UPS faults can be investigated without affecting the power supply to the load. Refer to the section on the Operator's Controls later in this chapter for details. Caution When operating on maintenance bypass power, the load is unprotected against input power supply disturbances. Therefore the load user should be informed when this mode is selected.

Note: The auto-restart facility may be disabled by an entry on the control panel. If the auto-restart facility has been disabled, a message on the LCD panel will indicate this when the supply returns. Restart the UPS by using the controls on the LCD panel to switch the output on. Refer to Chapter 2 - Operating Instructions.
1.4.3 Operation during abnormal / fault conditions

1.5
1.5.1

Electrical switches
Circuit breakers and fuses

If the inverter develops a fault, or suffers a severe overload or overtemperature condition, the UPS automatically transfers the critical load to the bypass supply by closing the static switch and shutting down the inverter see figure1-6. The battery charger will remain active.

Circuit breakers CB1 - CB3 connect the supply from the bypass terminals to the static switch; circuit breakers CB4 - CB6 connect the supply from the input terminals to the UPS; and the battery fuses FS1, FS2 are contained in fuse holders carried in a fused switch which disconnects the UPS from its batteries (FS3 in the 15/20kVA units is used to disconnect the second set of batteries only). The fuses are isolated from the circuit when the switch is opened so that the fuses can be replaced safely.

Issue 3 (01/03/98)

1-3

Chapter 1 - General Description

AP4300

Caution Fuse holders and circuit breakers should be opened/closed only by competent personnel when required. It is not necessary to open or close them during normal operation. 1.5.2 Control switches The UPS is controlled by the Main Control Switch (SW1), which is a four position switch, and an OUTPUT OFF' switch (SW2). The location and use of these switches is described later in this chapter. The UPS can also be controlled from the front panel see section 1.7 . 1.5.3 Internal Cutout Relays Input Overvoltage Cutout If the input voltage exceeds 477V, the UPS will isolate the power components from the input by opening the Input Overvoltage Cutout Relay, located in the input circuit between the circuit breakers (CB4 to CB6) and the input rectifier, and will switch to battery operation; refer to Section 1.4.2. - Operation during input power supply failure for details. Powering the load from the Maintenance Bypass line is not recommended when this relay has opened in a common bypass system. Inverter Output Cutout If an internal fault turns off the resonant converter, the UPS will transfer the load to bypass automatically. The Inverter Output Cutout Relay, located in the circuit between the inverter output and the rotary switch, SW1, will open to protect the inverter from the possibility of damage due to reverse power from the bypass line.

LOAD nn.n KVA O/P VOLTS nnn Vac UPS NORMAL NO ALARMS hh:mm:ss dd-mm-yy

ESC

AP4300

MAINT

TEST

OFF (0)

UPS

MAINT

TEST

SW1

OFF

UPS

SW1
Figure 1-9 View of the cabinet with the front panel removed to show the location of the main control switch, (SW1). pushing up on its lower edge and lifting it away from the cabinet, as shown in fig.1-8. The four switch positions are: OFF; MAINTENANCE (MAINT); TEST; and UPS. Off position SW1 is turned to OFF when the output must be turned off. In the OFF position all SW1 contacts are open (fig.1-10) and there is no power at the UPS output terminals.
MAINT TEST

1.6

Operator control switches

The equipment contains two switches that are used by the operator, in addition to the pushbuttons on the display panel. These are the Main Control switch and the Output Off switch. Their locations are shown in figs.1-9 & 1-16. Note: If any alarms are triggered when SW1 is at OFF or MAINT, ignore the alarm, otherwise refer to Chapter 5 Troubleshooting for the appropriate action. 1.6.1 Main control switch The Main Control Switch (SW1) is a four position rotary switch fitted behind the right hand front panel on the front of the UPS (see fig.1-9). The panel is held in place by means of two angled slots cut in each side of the panel. These slots hook over corresponding spigots on the cabinet frame. Remove this panel by
Static bypass

OFF

UPS

To Load

SW1
MAINT TEST

UPS Power train

OFF

UPS

Figure 1-10 Power off & SW1 at OFF

Maintenance position When SW1 is set to MAINT, it connects the UPS output terminals directly to the bypass supply (fig.1-11) if this supply is available. It will power the critical load while leaving the UPS shut down for maintenance or repairs on-site.

AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

AP4300

MAINT

TEST

Maintenance bypass Static bypass

OFF

UPS

To Load

SW1

MAINT

TEST

UPS Power train

OFF

UPS

Figure 1-8 Removing the front panel to get access to the main switch (SW1).

Figure 1-11 On maintenance bypass

1-4

Issue 3 (01/03/98)

IOM Manual
Test position When set to the TEST position the UPS power train neutral is connected to the neutral line. The load continues to be powered via the maintenance bypass (MBP), and the UPS control system starts to test the converter, battery charger, inverter, phase rotation and static bypass switch in sequence. The default window shows the message Testing. Each section is enabled when the tests on it are completed satisfactorily. Finally, if no faults are found, the static bypass switch closes automatically. The default window message changes to Tests Passed, Turn SW1 to UPS. Note that the load is still powered via the MBP line (fig.1-12), and will not be connected to the UPS output until switch SW1 has been set to UPS.
MAINT TEST

Chapter 1 - General Description


The load is now supplied by the static bypass line alone (fig.113). Finally, the control system, after a six second delay, transfers the load from the static bypass line to the inverter (fig.1-14).
MAINT TEST

Maintenance bypass Static bypass

OFF

UPS

To Load

SW1
MAINT TEST

UPS Power train

OFF

UPS

Maintenance bypass Static bypass

Figure 1-14 On UPS (After transfer to UPS - i.e. normal operation)


To Load

OFF

UPS

SW1
MAINT TEST

1.6.2

Input/Battery fuse holders

UPS Power train

OFF

UPS

Figure 1-12 Tests OK; static bypass turned on. If any problems are found, they will be indicated on the display panel, and the UPS will inhibit the transfer of the load to the inverter. This ensures that if SW1 is subsequently set to UPS while a fault exists, the load will not be supplied by the inverter but by the static bypass. Faults found can then be corrected before they can affect the power supply to the load. This position is also useful for testing the UPS manually after repairs, while the UPS continues to be powered from the maintenance bypass. UPS position (normal operation) When SW1 is set to UPS, the load switches from the maintenance line to the UPS output without a break in the power supply to the load. A mechanical overlap ensures break free switching; i.e. the load is connected briefly to both the maintenance line and the static bypass line during the switchover with SW1.
MAINT TEST

The UPS circuit breakers for the input and bypass supplies and the fused switches for the battery fuses, (fig.1-15), are located behind the front detachable panel, (fig. 1-8). These serve as switches which should be operated only by competent personnel, when required. There is no need to open or close them during normal operation. Note: To refit the front panel, first engage the slots on the panel with the corresponding spigots on the cabinet, and then allow the panel to drop into place.

MAINT
AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

TEST

AP4300

OFF (0)
MAINT TEST O/P OFF UPS

UPS

SW1
FS1 FS2 CB1 CB2 CB3 CB4 CB5 CB6

Maintenance bypass Static bypass UPS Power train

OFF

UPS

To Load
BATTERY BYPASS FUSES INPUT

SW1
MAINT TEST

OFF

UPS

Figure 1-15 Input, bypass and battery fuse locations

Figure 1-13 On UPS

Issue 3 (01/03/98)

1-5

Chapter 1 - General Description


1.6.3 Output Off Switch (SW2) Caution Pressing the Output Off pushbutton will turn the inverter off and remove power from the load. When this switch is pressed, the control system shuts down the inverter and disables the static bypass switch. The UPS display remains active. The resonant converter is also turned off, but is switched on for 5 minutes at 1 hour intervals to permit battery charging. Refer to later sections for information on how to restore power to the load. The Output Off switch is mounted on the back panel of the UPS and is recessed into its housing to reduce the chance of accidental operation. 1.6.4 SW2 1.6.5

AP4300
Remote Stop Switch (optional) A connection is provided for a switch, which can be located remote from the UPS, and which has the same function as the Output Off switch. When it is operated it shuts down the inverter, and inhibits the static switch so that power is removed from the load. Caution Pressing the Remote Stop pushbutton will turn the inverter off and remove power from the load. WARNING The mains input, bypass input and battery terminals still carry lethal voltages after pressing the Remote Stop switch. Do not remove covers from these parts. Only competent personnel should remove external panels held in place with screws. The Remote Stop switch can be either a latching or a non-latching switch. However it has the highest priority so that, if a latching switch is used, it must be reset after operation before the UPS output can be enabled from any source.

Figure 1-16 View of the back of the cabinet showingthe location of the Output Off switch, (SW2).

LCD controls - on/off command Caution Selecting Output Off will turn the inverter off and remove power from the load.

1.6.6 Optional operator controls The operation of the UPS can be controlled from external locations if one or more of the available communication options is connected. Instructions from a remote terminal will be effective only when they are enabled. Any subsequent commands, from whatever source, will over-ride previous commands - but see the note below. Note: Any OFF command will have a higher priority than an ON command from another origin. If the UPS does not respond to the operator controls as expected, ensure that all OFF commands from any connected options have been unlatched The additional options are described in Chapter 4 - Options. 1.6.7 Emergency Shutdown In order to remove power from the output in an emergency, move SW1 rapidly to position OFF.

The Command feature, accessed from the main menu, is provided so that the operator can switch the UPS on and off by using the controls on the LCD display panel. This permits the operator to turn the UPS OFF as part of its day-to-day operation at the end of the working day for example - without having to repeat the full start-up sequence to turn the UPS back ON. When the output is selected OFF the microcontroller removes power to the load in the same way as when the Output Off switch is pressed and continues to monitor the UPS. When the output is set ON, the UPS control system tests the converter, inverter, and static bypass switch in sequence before switching on the converter and inverter. The UPS output and LED indications then return to normal.

1-6

Issue 3 (01/03/98)

IOM Manual
1.7 Operator Control & Display Panel
ESCAPE
ESC

Chapter 1 - General Description

An operator control and display panel, shown in fig.1-17, is fitted on the front of the UPS. It permits the operator to select text displays from a menu of options for display on an LCD (Liquid Crystal Display) screen by means of pushbuttons on the panel, and provides information on the basic operational and alarm status of the UPS by means of LEDs (Light Emitting Diodes) which can be on, off or flashing on/off.
1 2 3 4 5

Pressing ESCAPE cancels the most recent actions; i.e. when selecting options it returns the previous window to the screen; when setting parameters, it exits the window without saving the new settings. The UP pushbutton moves a cursor up the screen over options offered on certain windows, and moves a rectangular cursor to the next digit on the right when changing parameter values in others.

UP

DOWN The DOWN pushbutton moves a cursor down the screen over options offered on certain windows, and changes parameter values in others.

6 7 8
???????????????????? ???????????????????? ???????????????????? ????????????????????

The Menu Options A map of the routes to the options offered by the menu is provided in fig.2-2. Options include windows which show status information and windows which permit data to be entered, or parameters for equipment control to be set. The menu map shows that the routes pass from the main menu through different intermediate windows to reach the option targeted. The diagram shows each of the windows in the format in which it appears on the LCD screen. The initialising, default & main menu windows are described below.

ESC

10

Figure 1-17 Identification of the main parts ofthe operator panel

LCD Display Panel Messages The operator panel can be considered as two zones. The LED displays form an upper zone, which comprises five separate areas, Initialising Window: and the LCD screen and its associated cursor control pushbuttons After first connecting power to the UPS (with switch SW1 OFF), the message: form a lower zone. These parts of the screen are identified by labels in fig.1-17. The key to these labels is given below:

Key to Labels in Fig. 1-17 LED Display


1. 2. 3. 4. 5. Monitor mimic Battery Status Load Status Battery Charge State Alarm Indicator/Cancel Button 6. 7. 8. 9. 10.

AP4300 INITIALISING PLEASE WAIT

LCD & Controls


Cursor up Pushbutton Cursor down Pushbutton LCD Screen Enter Pushbutton Escape Pushbutton will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded. It is then followed by a message showing what the next action should be.

Default Window:

The message shown below, will be seen on the default screen whenever the UPS is operating normally (see fig.1-18): AP4300 UPS NORMAL NO ALARMS dd-mm-yy hh:mm:ss The top line gives the UPS model number; the third line displays the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date. If UP or DOWN pushbutton symbols, or both: appear between the time and date, as shown in the INTERNAL SHUTDOWN window in fig.2-2, then two or more faults have been detected. Use the UP/DOWN pushbuttons to scroll through the alarm messages. Refer to Chapter 5 - Troubleshooting, for more details.

1.7.1

LCD Display, Controls & Screen

Function The LCD zone consists of an LCD screen with 4 rows of 20 characters, and four pushbuttons, as shown in fig.1-17. The pushbuttons permit the operator either to select options from a menu for display on the screen, or else to change the value of certain parameters. The screen shows messages which, for example, provide status information or, when an alarm occurs, indicate the reason for the alarm. LCD Screen Pushbuttons ENTER Pressing ENTER, when selecting options, displays the next window in the direction of the arrows on the menu map. The next window is determined by the option which has been selected in the present window. When setting parameters, it saves the new parameter values.

Issue 3 (01/03/98)

1-7

Chapter 1 - General Description

AP4300
1.7.2 LED Displays The basic operational status of the UPS is displayed by means of LEDs in the five areas, (items 1-5), already identified in the upper zone of the operator panel in fig. 1-17. The LED display permits the status of the UPS to be seen when LCD screens other than the default window are in use. The LEDs are identified in fig. 1-18. The meaning of the LEDs when ON is summarised in the table below.

Main Menu Window: The main menu is selected from the default window by pressing the enter key:
STATUS COMMANDS SETUP MAINTENANCE The four windows accessed from the main menu offer further options which are described in the relevant chapters of this manual. The STATUS option gives access to windows which show the present values of measured parameters such as input & output voltages and current, load etc. These parameters are useful when determining the state of the UPS or the causes of alarms, and are described in more detail in Chapter 6 - Maintenance. The COMMANDS option permits the operator to switch the UPS output on and off; to set times when the UPS output switches on and off; to set the conditions when the UPS will respond to a shutdown command from an external system; and to initiate battery tests. See Chapter 2 - Operating Instructions. The SETUP option permits the operator to set the date, time and the language in which messages are displayed. Their use is described in Chapter 2 - Operating Instructions. The MAINTENANCE option provides the route to the windows where a service engineer can configure the UPS to suit its operational environment. Entry to these windows requires a password. This manual does not provide servicing instructions and the options accessed from this window are therefore not shown on the menu map in fig.2-1. Only trained service engineers should be authorised with a password. Refer to the Commissioning Manual for details. Option Selection Mode: If a window from which options can be selected is displayed, a pair of indicator arrows appear at the top of the screen:

AP4300 UPS NORMAL NO ALARMS dd-mm-yy hh:mm:ss

ESC

Figure 1-18 - Identification of the LEDs on the operator panel

Meaning of the Operator Panel Indicator LEDs (refer to fig.1-18) Key


1

LED
Input Power supply Static Switch Inverter Battery Status Overload Indicator Charger Fault Alarm

Colour Normal State


Green on

Indication when ON
Input power supply present

2 3 4 5 6 7 SELECT ADJUST DD-MM-YY 0-00-00 SET CANCEL HH:MM:SS 00:00:00

Amber Green Amber Amber Amber Red

off on off off off off

Load on bypass Load on UPS Battery is discharging UPS is on battery Output has exceeded 100% of full load Charger is faulty (LED flashes) A condition requiring attention has developed (LED flashes) (see below) State of charge of battery; each of the 5 LEDs represents 20 % of battery capacity (see below) Output load as % full load; each of the 5 LEDs represents a fraction of the load (see below)

The UP /DOWN pushbuttons move these up and down the screen over the options. When the arrows point at a chosen option, press ENTER to display the next window. Press ESCAPE to return the previous window to the screen. Parameter Change Mode: If a window where a parameter can be changed is displayed, the cursor appears as a flashing rectangle superimposed on the first digit of the parameter. The function of the pushbuttons in this mode of operation is shown below:

Battery Capacity Indicator O/P Load Indicator

Green

on

Press the DOWN pushbutton to adjust the value of the digit by increasing it. If it goes past the end of its range, it will return to zero. When the digit is at its required value, press the UP pushbutton to select the displayed value and move the cursor to the next digit. When all digits have been assigned, press ENTER to set, i.e. save, the new value for the parameter: the previous window returns to the screen. Pressing ESCAPE at any time cancels the new settings and returns the previous window to the screen without saving any of the changes.
ESC

Green

on

A number of these LEDs indicate alarms, when they occur, by flashing on/off. Several of these alarms are also accompanied by an audible warning from the alarm horn. In all cases a message in the LCD default eason for the alarm. Details are given in Chapter 5 - Troubleshooting.

1-8

Issue 3 (01/03/98)

IOM Manual
1.7.3 Indicator Bars 1.7.4

Chapter 1 - General Description


Alarm indicator & horn cancel button

Output load indicator These six LEDs operate as a percentage load indicator bar and indicate the load on the phase with the highest load.

The audible alarm cancel button carries a red LED that flashes on/off whenever the UPS detects certain fault conditions.

Figure 1-21 Fault indicator and audible alarm cancel button Figure 1-19 Output load indication Several fault conditions are also accompanied by an insistent audible warning signal which can normally be cancelled by The left-most five LEDs are green and illuminate progressively as pressing the horn cancel button. The LED will continue to indicate the alarm until the fault condition has cleared. Details of the load increases. The load ranges are 10-20, 20-40, 40-60, 6080 and 80-100 percent of the UPS full load rating. The sixth LED the audible alarms are given in Chapter 5 - Troubleshooting. is amber and illuminates when the output of any phase exceeds 100 percent. This LED is therefore normally accompanied by an OVERLOAD alarm and an audible warning. If an overload occurs, the UPS automatically transfers the load to the static bypass supply after a time interval which depends on the overload magnitude - the greater the overload, the shorter the time interval. Battery Capacity Indicator The first five LEDs are green and operate as a bar indicator to show the state of battery charge when charging, and to show battery capacity remaining when the UPS is operating on battery power. The sixth LED is amber and flashes to indicate when there is a charger fault.

Figure 1-20 Battery autonomy indicator During battery charging the bar indicator LEDs light progressively from left to right until all five LEDs are ON, and the battery is fully charged; the battery charger then turns OFF. The time taken to reach full charge will depend on the load: the higher the load, the higher the rate of charge. When the battery is fully charged, a burn and coast routine puts the battery on charge for one hour every twelve hours. Battery life is prolonged when it is kept fully charged in this way. When the UPS is operating on battery power, the battery bar indicates the battery capacity remaining. The bar indicator LEDs progressively extinguish as the battery discharges, each LED representing approximately 20% of the rated autonomy time at the current load.

Issue 3 (01/03/98)

1-9

Chapter 1 - General Description

AP4300

1-10

Issue 3 (01/03/98)

Chapter 2 - Operating Instructions

2.1

Introduction

Output Off - i.e. UPS on, but no power supplied to the On Maintenance Bypass - i.e. load isolated from inverter. Power off - i.e. UPS switched off and isolated from the mains
automatically after a input power supply failure. The UPS can also be started up manually On Battery with the UPS controls - i.e. a black start. Note: As soon as power is connected to the UPS the microcontroller and UPS display panel become active and LED1 will switch ON. Details of the Control switches, LED display panel and LCD screen referred to in the procedures can be found in Chapter 1 General Description. The control switches are accessed by removing the right hand front panel. The panel is held in place by means of two angled slots cut in each side of the panel. These slots hook over corresponding spigots on the cabinet frame. Remove this panel by pushing up on its lower edge and lifting it away from the cabinet, as shown in fig.2-1. The load is powered directly from the input power supply. supply. load.

WARNING OPERATION OF THE CONTROL SWITCH (SW1) FROM THE UPS (ON) POSITION THROUGH TO THE OFF POSITION PASSES THROUGH BOTH THE TEST AND MAINT POSITIONS. THE INTERNAL MAINTENANCE BYPASS SYSTEM IS THEREFORE ACTIVATED DURING THIS OPERATION. IF THE UPS HAD PREVIOUSLY BEEN SWITCHED OFF BY EITHER THE LOCAL OUTPUT OFF SWITCH (SW2) OR BY A REMOTE STOP PUSHBUTTON SWITCH, TURNING THE CONTROL SWITCH (SW1) FROM THE UPS (ON) POSITION TO THE OFF POSITION WILL ACTIVATE THE INTERNAL BYPASS SYSTEM AND THEREFORE APPLY POWER SUPPLIES TO THE LOAD. IN ORDER TO AVOID ACCIDENTALLY APPLYING POWER SUPPLIES TO THE LOAD VIA THE INTERNAL BYPASS SYSTEM, ISOLATE THE POWER SUPPLIES TO THE BYPASS SYSTEM BEFORE TURNING THE CONTROL SWITCH (SW1) THROUGH THE TEST OR MAINT POSITIONS. This chapter describes how to switch the UPS manually into any one of the following five operating modes:

On Battery - i.e. UPS running on battery: selected

Normal - i.e. supplying uninterruptible power to the load.

SW2
LOAD nn.n KVA O/P VOLTS nnn Vac UPS NORMAL NO ALARMS hh:mm:ss dd-mm-yy

ESC

AP4300

MAINT
AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

TEST

AP4300

OFF

UPS

MAINT

TEST

OFF (0)

UPS

SW1

SW1

Figure 2-1 Location of the main control switch, (SW1) and Output off switch (SW2).

Issue 3 (01/03/98)

2-1

Chapter 2 - Operating Instructions


2.2 The Operating procedures 2.3 Cold Start Procedure

AP4300

2.2.1 Introduction The procedures described in this chapter have been categorised into two sections as listed below, (a) for operator use and (b) for use by personnel deemed competent. (a) Operator Procedures 1. Starting up the UPS: i.e. cold start (p.2-2). 2. Setting Time, Date and Language (p.2-4). 3. Switching power to the load on or off without ever switching off the UPS; includes output off switch operation (p.2-6), control panel commands (p.2-6), and commands from external systems (p.2-8). 4. Running the UPS On Battery; i.e. when the supply fails (p.2-8). (b) Competent Personnel Procedures 1. Applying Power to the UPS (p.2-10). 2. Starting up the UPS on battery (black start) (p.2-11). 3. Powering the load via the Maintenance Bypass (p.2-11). 4. Removing power from the UPS (p.2-12). These procedures must be followed without deviating from them in any way. They comprise a sequence of actions and a description of the corresponding LED indications and LCD messages that appear on the screen.

Starts up the UPS from the DE-ENERGISED or MAINTENANCE states, and takes it to the NORMAL state. WARNING THE FOLLOWING PROCEDURE WILL APPLY POWER TO YOUR LOAD AND DISTRIBUTION SYSTEMS. ENSURE IT IS SAFE TO DO SO. During start-up, the LEDs indicate the current UPS state. An alarm is triggered if a fault is found, and the start up screen indicates the position to which the switch should then be set. Press the alarm reset push-button on the display panel to cancel the audible alarm, if required. Refer to Chapter 5 Troubleshooting for more information about alarms. 1. Pre-Start checks Remove the UPS front lift-off panel; see fig.2-1. The main control switch (SW1) is either in the OFF or MAINT position. If it is in the OFF position proceed as below; otherwise proceed to step 3. Ensure that the input and bypass circuit breakers and battery fuse holders are CLOSED. If they are open, refer to section 2.7. Ensure that the UPS input power supply, and bypass supply where a split bypass system is used, are switched ON externally. If they are off, refer to section 2.7. The LCD display will be displaying the start up screen, and a message indicates that the rotary switch (SW1) should be turned to TEST:

2.2.2 Fault Indications The UPS monitors its internal operation and input/output parameters continuously, and indicates any abnormal condition on the operator display panel. Abnormal conditions can be caused either by an internal malfunction within the UPS (UPS faults), or AP4300 by problems with the power supply or the load (external faults). TURN SW1 TO TEST When a fault condition is detected, an alarm is triggered. UPS OUTPUT OFF 14-02-95 14:35:00 Alarms are indicated by a warning horn and/or one or more flashing LEDs on the display panel. A message on the LCD screen identifies the reason for the alarm. The warning horn 2. Select MAINTENANCE with SW1. sounds when an alarm requires immediate attention from the The load is connected directly to the bypass supply via the operator. MBP line, and the third line on the LCD display changes: Refer to Chapter 5 - Troubleshooting for a description of the alarms and the action to be taken in response to them. AP4300 Important notes TURN SW1 TO TEST ON MAINTENANCE B/P 14-02-95 14:35:00 Note 1: The operator controls and LED indicators referred to in these procedures are fully described in Chapter 1. Note 2: When applying power to the UPS, if the displays do not respond as indicated in the procedures, and unprotected power to the load is required, select MAINTENANCE and seek assistance. Otherwise shut down the UPS immediately by turning switch SW1 to OFF, and then remove power from the UPS.

3. Select TEST with SW1. The UPS starts a self-test routine while the load is supplied by the MBP line. The message on the start up screen on the LCD Display Panel indicates that testing is in progress: TESTING PLEASE WAIT ON MAINTENANCE B/P 14-02-95 14:35:00

2-2

Issue 3 (01/03/98)

IOM Manual

Chapter 2 - Operating Instructions


The LCD Display Panel startup screen is replaced by the Default screen, shown below: AP4300 UPS NORMAL 14-02-95 NO ALARMS 14:35:00

Caution Wait until the message: turn SW1 to ****** appears on the display before taking any further action. If testing fails at any stage, an error message appears on line 1 of the start up screen, together with an error code: TESTS ABORTED NN TURN SW1 TO MAINT ON MAINTENANCE B/P 14-02-95 14:35:00 The two hexadecimal digits (indicated by: NN) in the error message permit the cause of the test failure to be identified (see Chapter 5 - Troubleshooting). If the tests proceed satisfactorily, the converter starts up, followed by the inverter a few seconds later; the inverter LED switches on; and the UPS fans start. The SBP switches on to transfer the UPS output to bypass; the bypass LED switches on; and the inverter LED switches off. Note that the load is not supplied via the SBP at this stage because the UPS output has not been connected to the load; i.e. SW1 has not been switched to UPS. The load is still connected to the MBP. The message on the screen indicates that SW1 should be turned to UPS. TESTS PASSED TURN SW1 TO UPS ON MAINTENANCE B/P 14-02-95 14:35:00 4. Select UPS with SW1. The load is connected to the UPS output in a break free operation and is initially supplied by the static bypass line. Provided the bypass and inverter outputs are synchronised and within specified limits, and there is no overload, the load is transferred to the inverter after a 6 second delay. The bypass LED switches OFF, and the inverter LED switches ON.

5. Refit the UPS front panel. The panel is held in place by means of two angled slots cut in each side of the panel, as shown in fig.2-1. Present the panel to the UPS so that these slots hook over corresponding spigots on the cabinet frame. Let the panel drop into place. If necessary press its top edge firmly back into the cabinet. 2.3.1 NORMAL operation

During NORMAL operation LED1 is ON, to indicate that the input power supply is available (and within specification) and LED3 is ON to indicate that the UPS is supplying the load. The battery capacity bar indicates the charge in the battery. The percentage load bar indicates the proportion of the maximum load being supplied. Note: When the UPS is started from cold for the first time, the indicated battery capacity may not be as specified until the battery is fully charged; i.e. until it has been on charge for twenty-four hours.

Issue 3 (01/03/98)

2-3

Chapter 2 - Operating Instructions


2.4 Settings

AP4300

2.4.1 Introduction At any time after power has been applied to the UPS successfully, the operator adjustable settings - date, time and language - can be reset if necessary. The date and time are included on the default and alarm history screens. The language which is selected determines which language is used for displaying LCD messages. 2.4.2 Setting Date, Time & Language When it is necessary to change the date, time or language used in the screens, display the default window, and press the ENTER pushbutton to display the main menu window: STATUS COMMANDS SETUP MAINTENANCE Use the UP / DOWN pushbuttons to point at the SETUP option in the main menu, and press ENTER. The screen below appears: SET DATE AND TIME SELECT LANGUAGE

Notes: 1. The procedure can be abandoned at any stage without resetting the date and time by pressing ESC. 2. Take care that out of range numbers (e.g. month 13) are not set inadvertently. Set Language The language in which messages are displayed on the LCD screen is selected from this screen (i.e. SETUP). 1. Move the cursor, with the UP / DOWN pushbuttons, to SELECT LANGUAGE, and press ENTER, to display the LANGUAGES window: ENGLISH FRANCAIS ITALIANO ESPANOL DEUTSCH

2.

Move the cursor, with the UP / DOWN pushbuttons, to point at the language required, and press ENTER. The selected language is now set and the SETUP screen returns to the display.

Note: The procedure can be abandoned at any stage without resetting the language by pressing ESC. (Press ESC to return to the default display when necessary). Set Date and Time Select SET DATE AND TIME to display a screen where the clock and calendar settings can be reset by using the UP/DOWN pushbuttons. SELECT SET ADJUST CANCEL DD-MM-YY HH:MM:SS 0-00-00 00:00:00 The digits below DD-MM-YY represent the pairs of digits for entering the Day, Month and Year for the date. Similarly those below HH:MM:SS represent the pairs of digits for entering Hours, Minutes and Seconds for time. A flashing cursor in the form of a grey rectangle will be seen over the first DAY digit. 1. Increment the first DAY digit by pressing the DOWN pushbutton until the correct digit is displayed. 2.4.3 UPS Configuration The UPS is configured for its application by assigning values to various parameters from configuration screens which are accessed from the MAINTENANCE option on the main menu screen. Only a Liebert approved commissioning engineer should set up the configuration. It must not be changed subsequently, except by an authorised engineer. The operator does not need to have access to these screens, and so access is protected by means of a password. Figure 2-2. shows a map of all screens that can accessed by the operator.

Note: If you step past your intended number, keep pressing the pushbutton to scroll through to zero and repeat the operation. 2. 3. 4. Advance the cursor to the next digit by pressing the UP pushbutton. Repeat steps 1 and 2 until the date digits are set correctly. When the date is set, the cursor moves on to the time digits. Repeat the procedure for the time and, when completed, exit by pressing the ENTER key. Pressing ENTER resets the internal clock to the new time and date and returns the SETUP screen to the display.

2-4

Issue 3 (01/03/98)

IOM Manual

Chapter 2 - Operating Instructions

TESTS ABORTED NN TURN SW1 TO MAINT ON MAINTENANCE B/P 14-02-94 14:35:00

FAULT

SWITCH ON AT MAIN ISOLATOR


INITIALISATION TESTS OK AP4300 INITIALISING PLEASE WAIT . . .

CLOSE BATTERY FUSES

UPS NORMAL NO ALARMS 14-02-94 14:35:00

START UP AP4300 TESTS PASSED TESTS OK TURN SW1 TO UPS TURN SW1 TO TEST ON MAINTENANCE B/P UPS OUTPUT OFF 14-02-94 14:35:00 14-02-94 14:35:00

STATUS COMMANDS SETUP MAINTENANCE

OUTPUT VOLTS L-N L2 L1 L3 240 240 240

OUTPUT VOLTS L-L L1-2 L2-3 L3-1 400 400 400

OUTPUT BYPASS BATTERY INTERNAL

OUTPUT FREQUENCY FREQUENCY(Hz) 50.0 SYNCHRONISED

OUTPUT CURRENT AMPS L1 L2 L3 1.4 1.5 1.4

OUTPUT POWER KW L1 L2 L3 0.88 089 0.88 TOTAL 2.65 KW

OUTPUT POWER KVA L1 L2 L3 0.87 0.87 0.87 TOTAL 2.61 KVA

BATTERY INFORMATION VOLTS CAP% CHARGER 420 100 ON TIME 00:41:24 DC BUS TEMPERATURES INFORMATION

BYPASS L1 L2 L3 240 240 240 FREQUENCY (HZ) 50.0 DC BUS VOLTS PRIMARY SECONDARY 400 800 TO RETURN

OUTPUT CONTROL OUTPUT OFF OUTPUT ON

CONV INV MAG

40 BAT 38 AMB 42

23 24

ERROR PAGE (status) (UPS action) (message/fault) UPS STATUS CONVERTER ON INVERTER ON BATTERY CHARGER ON 14-02-94 14:35:00 NORMAL #XX NO REPORT NO MESSAGE

OUTPUT CONTROL TIMED OP CONTROL SHUTDOWN CONDITION BATTERY TEST

TIMED OP CONTROL DELAYED OP ON DELAYED OP OFF CANCEL DELAY SHUTDOWN CONDITION ON BATTERY AT ANY TIME

ERROR PAGE UPS STATUS EVENT HISTORY

BATTERY TEST TEST BATTERY LAST TEST RESULT

COMMUNICATION FAULT AT ANY TIME

SET DATE AND TIME SELECT LANGUAGE

SELECT SET ADJUST CANCEL DD-MM-YY HH:MM:SS 00 - 00 - 00 00 : 00 : 00 ENGLISH ESPANOL FRANCAIS DEUTSCH ITALIANO

SET SELECT ADJUST CANCEL ENTER PASSWORD ****

AP4310 FATAL ERROR CALL FOR SERVICE 01793 553355

Figure 2-2 Map of the displays on the LCD screen accessible by the operator

Issue 3 (01/03/98)

2-5

Chapter 2 - Operating Instructions


2.5 Switching the Output Off/On
2.5.2 Operation from the UPS control panel

AP4300

This section describes how to switch the UPS output off in a way that enables it to be switched on again without repeating the full start-up sequence. The facility is provided for use as part of day-to-day operation when the UPS output is turned off only for a short period, (i.e. put into Standby mode); e.g. at the end of the working day, when the UPS is turned off overnight. The battery is kept charged up while the UPS is in Output Off mode. The UPS output can be switched off by operating SW2 on the back of the UPS, by using the controls on the UPS control panel, or by sending commands from an external system via an optional communications interface. When the output is selected OFF the microcontroller removes power to the load from the UPS output terminals by switching the inverter off; it also inhibits the static switch, but continues to monitor the UPS. When the output is set ON, the inverter switches on, and the UPS output and LED indications then return to normal. 2.5.1 Output Off Switch SW2 Caution Pressing the Output Off pushbutton will cut off power to the load. 1. To switch output off - Press SW2 and hold it pressed briefly. The bypass and inverter LEDs switch OFF, while the input LED stays ON. If the default screen is not displayed, press Escape on the LCD control panel several times until it is. The screen will show that the output is OFF: AP4300 UPS OUTPUT OFF 14-02-95 14:35:00 The DOWN arrow on the fourth line shows that another status message has also been triggered. Pressing the DOWN button displays it: AP4300 LOCALLY STOPPED 14-02-95 14:35:00 The message LOCALLY STOPPED shows that the UPS was switched off with SW2. WARNING IF THE DISPLAY DOES NOT INDICATE THAT THE UPS OUTPUT IS OFF AND LOCALLY STOPPED, THEN REMOVE THE LIFT'OFF COVER, AND TURN SW1 TO OFF. 2. To return to normal operation, use the operator panel controls (see below).

Immediate Switching The operator can switch the UPS output ON or OFF, without using the main switch, SW1, by using the controls on the LCD control panel instead. 1. Select COMMAND from the main menu display to obtain the Control screen. The cursor is at OUTPUT CONTROL: OUTPUT CONTROL TIMED OP CONTROL SHUTDOWN CONDITION BATTERY TEST 2. Press Enter; the display below appears: OUTPUT CONTROL OUTPUT OFF OUTPUT ON

To turn the UPS output off: Caution Selecting the OUTPUT OFF will cut off power to the load. With the cursor set at OUTPUT OFF, press Enter; the display asks for confirmation: OUTPUT CONTROL OUTPUT OFF OUTPUT ON PRESS TO CONFIRM Press Enter a second time. The inverter LED switches off as the inverter shuts down, and the load loses power. Press Escape several times to return to the default window. The message: AP4300 UPS OUTPUT OFF 14-02-95 14:35:00 will appear. the UPS will stay in this state, with the battery on charge, until either the UPS output is switched on, or the input power supply fails.

2-6

Issue 3 (01/03/98)

IOM Manual
To turn the UPS output on: WARNING THE FOLLOWING PROCEDURE WILL APPLY POWER TO YOUR LOAD AND DISTRIBUTION SYSTEMS. ENSURE IT IS SAFE TO DO SO. Select COMMANDS from the main menu display to obtain the Output Control screen. Press the Down button to set the cursor at OUTPUT ON, and press Enter; the display asks for confirmation: OUTPUT CONTROL OUTPUT OFF OUTPUT ON PRESS TO CONFIRM Press Enter a second time. The inverter LED switches on briefly, as the inverter starts supplying the load; the bypass LED switches on, and the inverter LED switches off as a bypass test is performed; if the default screen is selected (by pressing Escape several times) it will indicate the UPS status as: UPS ON BYPASS while the test is in progress; finally the inverter LED switches on and the bypass LED switches off, as the bypass test is completed and the inverter supplies the load. At the end of the sequence, which is completed in about ten seconds, the default window indicates the status as: UPS OUTPUT ON

Chapter 2 - Operating Instructions


The cursor will be aligned with DELAYED OP ON; press Enter. The screen which allows a date and time to be set is displayed: SELECT SET ADJUST CANCEL DD-MM-YY HH:MM:SS 0-00-00 00:00:00 Refer to Section - Setting Date, Time & Language on p.2-4 for details of how to set these parameters. The character in the area between the time and date settings indicates how often the output switches on. The switching frequency selected can be one of the four options shown in the table below. The character that indicates each option is also shown in the table. 1 2 Single occasion; i.e. only at the set time on the set date. Daily occasion; i.e. at the set time on the set date and at the same time every day afterwards, until cancelled. Weekly occasion; i.e. at the set time on the set date and at the same time on the same day every week afterwards, until cancelled. Cancel current selection

1 D W

Notes: 1. The default setting is: ; i.e. no times selected for switching the output on. 2. The time & date must always be set in the future. To select the switching frequency, press the UP pushbutton after the time has been set, so that the cursor moves to the position for the character for the switching frequency; press the DOWN pushbutton to scroll round the options until the correct character is displayed; press the UP pushbutton to move the cursor to the data area for the date and set the required date as described in Section 2.4.2 referred to above. When this screen is first displayed it will show the switching frequency and the time and date currently set for it. If the character shown is cancel, then the actual time will be shown, stopped at the moment when the screen was entered. To set a time when the UPS output will switch OFF (DELAYED OP OFF) Caution Setting parameters for DELAYED OP OFF will cut off power to the load at the designated time(s). Move the cursor down so that it is aligned with DELAYED OP OFF; press Enter. The screen which allows a date and time to be set is displayed, as described above; follow the same procedure, but the switching action now will switch the output off instead of on.

Scheduled Switching This facility permits times when the UPS automatically switches the output on, and/or switches it off, to be set. Select COMMANDS from the main menu display; move the cursor to TIMED OP CONTROL (Timed Output Control) and press Enter. Three options are presented on the screen: DELAYED OP ON DELAYED OP OFF CANCEL ALL DELAYS

To set a time when the UPS output will switch ON - (DELAYED OP ON) WARNING SETTING PARAMETERS FOR DELAYED OP ON WILL APPLY MAINS VOLTAGE TO THE LOAD EQUIPMENT AT THE DESIGNATED TIME(S). IF APPROPRIATE A NOTICE STATING WHEN THIS WILL HAPPEN SHOULD BE PLACED BESIDE ALL LOAD EQUIPMENT.

Issue 3 (01/03/98)

2-7

Chapter 2 - Operating Instructions


To delete all automatic switching settings - (CANCEL ALL DELAYS) Select COMMANDS from the main menu display; move the cursor to TIMED OP CONTROL (Timed Output Control) and press Enter. Move the cursor down to CANCEL ALL DELAYS and press Enter. The display asks for confirmation: DELAYED OP ON DELAYED OP OFF CANCEL ALL DELAYS PRESS TO CONFIRM Press Enter to confirm (ESC to cancel). The previous screen (the COMMANDS menu) returns. 2.5.3 Switching with External Commands

AP4300
Press Enter to confirm (ESC to cancel). The previous screen (the COMMANDS menu) returns. Status display When the default screen is next displayed after the UPS output has been switched off by an external command, the status will be shown on line 3 of the screen; e.g. after a command from an external system to switch the output off, the default screen shows: AP4300 UPS OUTPUT OFF 14-02-95 14:35:00 The UPS will stay in this state with the battery on charge until either it is switched on, or the input power supply fails.

General The UPS output can be switched on or off by means of commands from an external system via an optional SNMP card or an RS232 interface connected to the communications board in the UPS. These are described in Chapter 4 - Optional Equipment. The user can set how the UPS will respond when it receives an external shutdown command - see below. Shutdown Condition The Shutdown Condition setting determines what the state of the UPS must be before it will switch the output off when an operator sends a shutdown command. One of two conditions can be selected: 1. On Battery - The UPS will switch the output off only if it is running on battery when the operator sends the shutdown command. 2. At Any Time - The UPS will switch the output off at any time, (i.e. it can be running on the input power supply or on battery power) when the operator sends the shutdown command. Procedure With the COMMANDS menu on the display. Set the cursor at SHUTDOWN CONDITION, and press Enter. The screen shown below will appear: SHUTDOWN CONDITION ON BATTERY AT ANY TIME

2.6

Input Power Supply Failure

2.6.1 General When the input power supply fails, the UPS runs On Battery. You should consider shutting down your load in a controlled manner e.g. save data. The way in which the UPS responds to a input power supply failure depends on whether it is on-load or off-load when the input power supply failure occurs. 2.6.2 Input Supply Failure when On Load If the UPS loses its input power supply the amber batteryon-load indicator (LED 4) will illuminate; the warning horn will sound a single half second long tone every 10 seconds and cannot be cancelled. On a common bypass system, LED2 will flash, indicating a loss of the bypass supply, and LED 1 will switch off. Note: For units with a separate bypass supply, LED 2 will not flash while the bypass supply is present, but will be OFF. The battery time remaining, at the present load, is shown on the second line of the LCD panel as follows: AP4300 TIME 03:50:40 UPS ON BATTERY 14-02-95 14:35:00

As the battery discharges, the battery time decreases, and the battery capacity bar LEDs extinguish progressively from the right; each LED represents 20% of capacity. When the battery Move the cursor to the option required by using the up/down autonomy time remaining falls below a user set value (set during pushbuttons. Select the ON BATTERY option if the UPS output must commissioning), the warning horn will beep every 5 secs. only be switched off when it is running on battery power; select If the input power supply returns before the battery time expires the AT ANY TIME option if the UPS output must be switched off the battery charger switches on automatically, and the UPS when the UPS is running on either the input power or battery returns to normal operation after a short time delay. power. When the battery becomes discharged, the UPS will attempt to After selecting the required option, press Enter. The display asks transfer the load to bypass. If the bypass is available (split bypass for confirmation: system) the transfer will succeed. If no bypass is available (common bypass system) the UPS turns the output off which will also remove power from the control circuits. SHUTDOWN CONDITION ON BATTERY AT ANY TIME PRESS TO CONFIRM

2-8

Issue 3 (01/03/98)

IOM Manual
Re-starting from a input power supply failure on load Common bypass system Autorestart Enabled (default):- An Automatic Restart facility ensures that a UPS with a common bypass will automatically restart if the input power supply returns after the autonomy time expires, provided the control switches have not been operated in the meantime. The facility can be disabled during commissioning if necessary. Caution Check the battery capacity after each discharge. If the battery has been heavily discharged the UPS will shut down without warning, with loss of power to the load, if a second power failure occurs whilst the autonomy time is zero. A unique feature of the AP4300 permits the operator to observe the battery condition by referring to the BATTERY screen. From the main menu window align the cursor with STATUS and press the ENTER key. Select BATTERY on the screen that is displayed and press the ENTER key. The state of the battery will be shown in the following form: BATTERY INFORMATION VOLTS CAP % CHARGER 420 0 ON TIME 00:00:00 2.6.3

Chapter 2 - Operating Instructions


Input Supply Failure when Off Load

If the input supply fails after the UPS output has been switched off - i.e. an OUTPUT OFF message is displayed on the default screen - the amber battery-on-load indicator (LED 4) will illuminate; the warning horn will sound; and LED2 will respond in the same way as when there is a Failure On Load, described above. The default screen shows the autonomy time remaining, on the second line: AP4300 TIME 03:50:40 UPS ON BATTERY 14-02-95 14:35:54 The autonomy time slowly counts down as battery power is consumed. When a period of fifteen minutes has elapsed after the input supply first failed, the control system shuts down the UPS to conserve battery power. The LCD screen goes blank and the LEDs extinguish. Re-starting from a failure off load When the input supply is restored, the screen below will be seen on the display: AP4300 UPS OUTPUT OFF 14-02-95 15:51:00

It is recommended that the UPS is then started using one of the This display shows that the battery is unable to support the load if a failure was to occur: the battery capacity is zero, and following methods: a) Use the controls on the operator panel and follow the the autonomy time at the current load is zero. procedure to turn the UPS output on under Operation from Autorestart Disabled:- The auto-restart facility may have the control panel - Immediate Switching on p.2-6. been disabled on commissioning. When the supply returns b) Switch the UPS output on by means of a command from an with the auto-restart disabled, the LCD panel will show the external system sent over a communications link; refer to message: section on p.2-8. UPS OUTPUT OFF Restart the UPS by using the controls on the LCD panel to switch the output on. Refer to Operation from the control panel - Immediate Switching on p.2-6. Split bypass system When the input supply returns, the input rectifier powers up and the UPS automatically re-starts the inverter, opening the static switch to transfer the load back to the inverter. The system is then in the normal operating condition and recharging the batteries.

Issue 3 (01/03/98)

2-9

Chapter 2 - Operating Instructions

AP4300

The following procedures of Chapter 2 are for competent personnel only

2.7

Applying Power to the UPS

If, instead of the start-up screen, the screen below is displayed: SETUP DATA ERROR RELOADING DEFAULTS PRESS TO CONTINUE

Starts the UPS from the POWER OFF state and sets it in the DEENERGISED state ready for a Cold Start. WARNING ENSURE THE EQUIPMENT HAS BEEN COMMISSIONED BY A LIEBERT APPROVED SERVICE ENGINEER BEFORE PROCEEDING. 1. Initial checks Remove the UPS front lift-off panel see fig.2-1. Ensure that the main control switch (SW1) is in the OFF position. Ensure that the optional Remote Switch, if connected, is set at on. Ensure that the input, and bypass circuit breakers (fig.3-17) are CLOSED. WARNING IF YOU CLOSE THE BATTERY FUSE HOLDERS WHEN SW1 IS AT UPS AND AUTO-RESTART IS ENABLED, THE UPS WILL FOLLOW THE START UP SEQUENCE AUTOMATICALLY; ENERGISE THE OUTPUT; AND POWER THE LOAD VIA THE UPS. 2. Close the battery fuse holders, FS1 & FS2 (fig.3-17) & FS3 (15/20kVA). The battery, and on-battery LEDs will switch on. If the UPS detects an internal fault, the following screen appears: AP4300 INT FAILURE XXXX CALL FOR SERVICE

then the system has detected that the parameter settings have become corrupted during initialisation, and a SETUP error message has been generated. Press Enter to accept (user has no option); the screen below is then displayed: OUTPUT WILL RUN AT 230V PRESS TO CONTINUE

Caution If the load will be damaged by being supplied with power at 230V then open the battery fuse holders and call for a service engineer to reset the parameters. If an output voltage of 230V is acceptable, press Enter to accept; the default parameter settings (listed in the table of parameter settings at the end of this manual) will be reloaded. While the new data is being loaded and checked, the LEDs on the load & battery bargraphs repeatedly switch on & off successively from one end to the other and back again. They continue cycling in this way, with the sequences in the upper and lower bargraphs switching in opposite directions, until the parameters have been re-loaded, when the start-up screen shown above is displayed. Continue with the procedure at step 3 below. 3. Power up the UPS by switching the input power supply ON at the external isolator(s). The on-battery LED will switch off, and the input LED will switch on; the start-up screen shown above continues to be displayed and indicates the position to which the main control switch should be turned next. This will be TURN SW1 TO TEST if no problems have been detected. After each switch operation during start up, the position to which the main control switch should be turned next is updated. The cold start procedure in the operator section can now be followed.

Otherwise, after about five seconds, the initialising message: AP4300 INITIALISING PLEASE WAIT

will appear on the LCD screen. It persists for approximately 2 secs while the control firmware is initialised. If all is well, then the start-up screen: AP4300 TURN SW1 TO TEST UPS OUTPUT OFF 14-02-95 14:35:00 is displayed and the procedure should continue with step 3 below.

2-10

Issue 3 (01/03/98)

IOM Manual
2.8
2.8.1

Chapter 2 - Operating Instructions


2.9 To Put the Load on Maintenance Bypass (MBP)

Starting up the UPS on battery ( black start)


General

While it is possible to start the UPS from cold without the supply connected, this is not a normal way to start up. 2.8.2 Procedure

These instructions describe how to shut down the UPS while the load continues to be powered via the MBP line. Caution The load will not be protected from variations in the input power supply when supplied via the MBP line. Caution The following actions will shut down the UPS. Note: In the following procedure ignore the second line on the LCD screen; it shows where SW1 should be turned next if the UPS is being started up. 1. Select the default screen on the LCD Display Panel, and remove the UPS front lift-off panel see fig.2-1. 2. Select TEST with SW1. WARNING IF THE OUTPUT OF THE UPS HAS BEEN TURNED OFF, TURNING SW1 TO TEST WILL RE-APPLY INPUT POWER TO THE LOAD EQUIPMENT/DISTRIBUTION SYSTEM. ENSURE THAT IT IS SAFE TO DO SO. The load is transferred briefly to the static bypass while the switch is operated and then to the MBP supply line. The LEDs indicate the current status - i.e. LED(1) ON, LED(2, 3) OFF. The LCD screen shows the current status of the UPS on its third line; i.e. load on maintenance bypass: TESTS PASSED TURN SW1 TO UPS ON MAINTENANCE B/P 14-02-95 14:35:00 3. Turn SW1 to MAINT position. The LEDs indicate that the UPS status is the same as in step 2 above. The LCD screen also shows that the current status is unchanged: AP4300 TURN SW1 TO TEST ON MAINTENANCE B/P 14-02-95 14:35:00 The UPS is now supplying the load via its MBP line. 4. Isolation of the internal components of the UPS. Open the input and bypass circuit breakers, CB1 to CB6. Open the battery fuse carriers, FS1 & FS2. The LCD display and all LEDs will switch off as the power to the internal components of the UPS decays. It is safe to remove the battery fuses and for trained electricians to carry out maintenance on the UPS while it is on MBP. Note that the only parts of the UPS that are still live are the terminals and the hot box behind them.

Starts the UPS from the POWER OFF state, sets it in the ONBATTERY state and supplies the load with power. WARNING ENSURE THE EQUIPMENT HAS BEEN COMMISSIONED BY A LIEBERT APPROVED ENGINEER BEFORE PROCEEDING. 1. Initial checks Check that input power is not available. Remove the UPS front lift-off panel see fig.2-1. Ensure that the main control switch (SW1) is in the OFF position. Ensure that the optional Remote Switch, if connected, is set at on. 2. Turn SW1 to UPS. 3. Close the battery fuse holders, FS1 & FS2 and FS3 (15/20kVA units). The battery, and on-battery LEDs will switch on. After about five seconds, the initialising message: AP4300 INITIALISING PLEASE WAIT

will appear on the LCD screen. It persists for approximately 2 secs while the control firmware is initialised. Replace the UPS front lift-off panel removed in step 1 above, see fig.2-1. 4. Turn the UPS output on. WARNING THE FOLLOWING PROCEDURE WILL APPLY POWER TO YOUR LOAD AND DISTRIBUTION SYSTEMS. ENSURE IT IS SAFE TO DO SO. Select COMMANDS from the main menu display to obtain the Output Control screen. Press the Down button to set the cursor at OUTPUT ON, and press Enter; press Enter a second time to confirm. Refer to section for full details. The inverter is now supplying the load.

Issue 3 (01/03/98)

2-11

Chapter 2 - Operating Instructions


2.10 Removing Power
Follow the procedure in steps 1-4 above, and then follow the procedure below to isolate the UPS and LOAD totally from the power supply. Caution The following actions will remove power from the load. 5. Turn SW1 to O/P OFF to remove power from the LOAD completely. WARNING THE INPUT, BYPASS INPUT, AND UPS OUTPUT TERMINALS STILL CARRY LETHAL VOLTAGES. DO NOT REMOVE COVERS FROM THESE PARTS. ONLY COMPETENT PERSONNEL SHOULD REMOVE PANELS FASTENED WITH SCREWS. 6. Isolate the UPS from its external supplies by opening the input power isolator external to the UPS, and, in a split bypass system, the external bypass power isolator also. Refer to Section 2.7 - Applying Power to the UPS, on p.2-10 to restart the UPS from this state.

AP4300

2-12

Issue 3 (01/03/98)

Chapter 3 - Installation Instructions

These instructions are for use by competent personnel only.


3.1 Safety warnings 3.2
3.2.1

Installation Considerations
Introduction

WARNING Do not switch on electrical power to the UPS equipment or operate any of its switches before it has been commissioned by an authorised engineer. Failure to observe this condition will invalidate any implied warranty. WARNING - Battery hazards Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 380Vdc and is potentially lethal. Eye protection should be worn to prevent injury from accidental electrical arcs. If a battery leaks electrolyte, or is otherwise physically damaged, it should be placed in a container resistant to sulphuric acid and disposed of in accordance with local regulations. If electrolyte comes into contact with the skin the affected area should be washed immediately. WARNING THE UPS IS HEAVY AND IS FITTED WITH CASTORS TAKE CARE TO PREVENT MOVEMENT WHEN UNBOLTING THE EQUIPMENT FROM ITS SHIPPING PALLET. ENSURE SUFFICIENT PERSONNEL TRAINED IN MOVING HEAVY EQUIPMENT ARE AVAILABLE WHEN REMOVING THE UPS FROM ITS SHIPPING PALLET. REFER TO THE INSTRUCTIONS IN SECTION 3 - REMOVAL FROM SHIPPING PALLET. WARNING Take care that the UPS does not tip over when it is being moved. The position of its centre of gravity is shown in Fig.3-1. WARNING OPERATION OF THE CONTROL SWITCH (SW1) FROM THE UPS (ON) POSITION THROUGH TO THE OFF POSITION PASSES THROUGH BOTH THE TEST AND MAINT POSITIONS. THE INTERNAL MAINTENANCE BYPASS SYSTEM IS THEREFORE ACTIVATED DURING THIS OPERATION. IF THE UPS HAD PREVIOUSLY BEEN SWITCHED OFF BY EITHER THE LOCAL OUTPUT OFF SWITCH (SW2) OR BY A REMOTE STOP PUSHBUTTON SWITCH, TURNING THE CONTROL SWITCH (SW1) FROM THE UPS (ON) POSITION TO THE OFF POSITION WILL ACTIVATE THE INTERNAL BYPASS SYSTEM AND THEREFORE APPLY POWER SUPPLIES TO THE LOAD. IN ORDER TO AVOID ACCIDENTALLY APPLYING POWER SUPPLIES TO THE LOAD VIA THE INTERNAL BYPASS SYSTEM, ISOLATE THE POWER SUPPLIES TO THE BYPASS SYSTEM BEFORE TURNING THE CONTROL SWITCH (SW1) THROUGH THE TEST OR MAINT POSITIONS.

These installation instructions provide all the information needed for positioning the UPS (including environmental requirements), for fitting the batteries, and for connecting the input and output power cables. This equipment complies with the requirements of the EMC directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories. The external communication cabling assemblies must be of the shielded type. The shield must be grounded at the UPS end. 3.2.2 On Delivery The UPS can be supplied either with or without batteries installed. Battery installation instructions are given later in this chapter for use when the UPS is delivered without batteries. Carry out a thorough external inspection to verify that the UPS is complete and free of damage. Report any damage to the shipper immediately. Remove and store the packaging. 3.2.3 Environment The UPS may be installed in a computer room or other large office environment or in a general plant equipment room. It must be located in a cool, dry, dust-free environment with sufficient ventilation to keep its ambient temperature below 40oC (104oF). (Note: Operating in temperatures above 25oC (77oF) will reduce battery life). Its environment must also be free of excessive moisture (i.e. no water condensation), flammable vapours, chemical fumes or corrosive gasses or liquids. The specification, in Appendix A gives details of the UPS heat emission. If necessary, the room should be equipped with a ventilation system to assist cooling. A suitable air filtration system should be used for the incoming air where the UPS is to operate in a dirty environment. 3.2.4 Position The UPS is force-cooled with the aid of internal cooling fans. Cooling air enters from the back and from around the base of the

LOAD nn.n KVA O/P VOLTS nnn Vac UPS NORMAL NO ALARMS hh:mm:ss dd-mm-yy

ESC

LOAD nn.n KVA O/P VOLTS nnn Vac UPS NORMAL NO ALARMS hh:mm:ss dd-mm-yy

ESC

AP4300

AP4300

Figure 3-1 Position of the centre of gravity of the UPS cabinet complete with batteries.
Issue 3 (01/03/98)

3-1

Chapter 3 - Installation Instructions


3.3 Removal from Shipping Pallet

AP4300

100mm minimum gap

m 0m m 30 imu in ap mg

AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

1000 mm minimum access for fixed ins tallation

The UPS will be delivered on a pallet (Fig.3-3). It is secured to its pallet by means of three brackets. Two (three on 15/20kVA units) screws fasten the front of the UPS to a front bracket (Fig.3-4), and an anchor bolt screws up from beneath the pallet base board into each of two jacking feet brackets (Fig.3-5). There is one jacking foot on each side of, and towards the rear of the UPS. Two wood blocks bolted to the pallet, one in front of, and one behind the UPS, prevent movement of the UPS on the pallet. The 15/20kVA units also have side guide rails fitted.

Figure 3-2 Locating the UPS Jacking feet UPS, and is exhausted through a ventilation grill located at the top of the back panel; there must be a minimum gap of 300mm behind the equipment to allow adequate air flow. See figure 3-2. Maintenance requires unhindered access to the UPS right hand side, and you should allow for a clearance there of approximately 1000mm. To aid manoeuvrability on all models and for ventilation on the 15/20kVA models, a clearance of 100mm is required on the left hand side. Being mounted on castors, the UPS can be installed without side access provided its input and output power cables are held in suitably flexible conduits. The UPS can then be pulled forward to gain access for servicing. 3.2.5 Weight considerations With batteries fitted, the 7.5kVA and 10kVA models weigh 250kg, and the 15kVA and 20kVA models weigh 432kg. This will make it difficult to move the equipment over certain floor surfaces (e.g. carpet pile) with the batteries fitted. This should be taken into account when preparing for its installation, and when deciding whether or not to pull the UPS forward for servicing. If point loading forces must be considered, note that the weight of the UPS acts at six wheels and two jacking feet. 3.2.6 Extended battery option The UPS uses Valve regulated batteries which are housed internally. However if the installation includes an Extended Battery option, the additional batteries are contained in a separate battery cabinet which is attached to the left hand side of the main equipment. Batteries are fitted into this cabinet from the front, so it is only necessary to provide the 100mm clearance on the left as stated above for the UPS. Detailed installation instructions for the extended battery cabinet are provided with the fitting instructions supplied in the kit.

Jacking feet

Wood bolster Side guide rail pallet foot Figure 3-3 Rear view of UPS on its pallet

Removal Procedure WARNING ENSURE THE PALLET IS PLACED ON LEVEL GROUND BEFORE REMOVING THE UPS. 1. Remove the right hand front panel (Fig.3-6). 2. Undo the screws holding the front bracket to the UPS cabinet (Fig.3-4). WARNING THE FOLLOWING ACTIONS WILL PERMIT THE UPS TO MOVE ON THE PALLET, WHICH WILL TILT SO THAT THE UPS CAN ROLL OFF. THE UPS IS HEAVY (WEIGHT WITH BATTERIES OF 7.5 & 10KVA MODELS= 250KG, 15 & 20KVA MODELS= 432KG). YOU ARE ADVISED TO OBTAIN ASSISTANCE TO ENSURE IT IS KEPT UNDER CONTROL WHILE BEING MANOEUVRED OFF THE PALLET. 3. Undo the three wood screws fastening the rear wooden block to the top of the pallet base (on the 15/20 kVA units remove the six bolts), and remove the wood block (Fig. 3-7). 4. Undo the two bolts fastening the pallet feet to the pallet base (Fig. 3-7).

3-2

Issue 3 (01/03/98)

IOM Manual
Bracket screws

Chapter 3 - Installation Instructions

Front bracket

WARNING THE FOLLOWING ACTIONS WILL PERMIT THE UPS TO ROLL OFF THE PALLET UNDER ITS OWN WEIGHT WITH CONSIDERABLE MOMENTUM. TAKE CARE THAT THE UPS DOES NOT STRIKE ANY PART OF THE BODY AS IT MOVES. WHEN THE FRONT WHEELS, WHICH COME OFF THE PALLET LAST, ROLL OFF THE END OF THE PALLET, THE OTHER END MAY JUMP UPWARDS AND COULD CAUSE INJURY. DO NOT STAND BEHIND THIS END OF THE PALLET WHILE THE UPS ROLLS OFF. 6. Raise the two jacking feet as high as possible by rotating them anticlockwise. 7. Ensure that the wheels of the UPS are aligned so that it stays square to the pallet when it rolls off, and will not tilt sideways. Stop the UPS from moving by pushing it against the wooden block in front of the UPS, in the direction of the arrow in Fig.3-8. Remove the two rear feet and the wooden bolster assembly by knocking them away from beneath the pallet. Hold the UPS steady until the Figure 3-8 pallet has settled. It will balance in a level position because the centre of gravity of the UPS is located close to its centre line.

Figure 3-4 Detail of the front anchor bracket showing the position of the screws fastening the UPS to it wood screws Bolster bolt

Jacking foot

Anchor bolt

Figure 3-5 Detail of the jacking foot showing the position of the bolt anchoring the UPS to its pallet

5. Undo the two anchor bolts clamping the jacking feet to the pallet (Fig. 3-5). The heads of the anchor bolts are accessed from below the pallet base board. The UPS is now free to move on the pallet.

WARNING THE FOLLOWING ACTIONS WILL PERMIT THE UPS TO ROLL OFF THE PALLET RAPIDLY AND WITH CONSIDERABLE MOMENTUM IF IT IS NOT RESTRAINED. ENSURE NO EQUIPMENT IS IMMEDIATELY IN FRONT OF THE UPS, AND THAT ALL PERSONNEL ARE AWARE OF THE DANGER.
AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

8.

Stand at the side of the pallet and push the UPS gently backwards. The pallet will suddenly tilt (Fig. 3-9), and act as a ramp with a steep incline (30% approx.). The UPS will run down on to the floor. Restrain the UPS as it rolls down, to prevent it running off the pallet too rapidly.

Figure 3-6 Remove the right hand front panel by pushing upwards on its bottom edge.

Figure 3-7

Figure 3-9

Issue 3 (01/03/98)

3-3

Chapter 3 - Installation Instructions


3.4 Batteries

AP4300

3.4.1 Check Before you install the UPS check whether or not the unit has been shipped with batteries already fitted. If batteries are already fitted, their security must be checked visually; if they have not been fitted, they must be installed at this stage. WARNING HAZARDOUS VOLTAGE - BATTERY STRINGS CAN BE VERY DANGEROUS AND GREAT CARE SHOULD BE EXERCISED AT ALL TIMES. NOTE THE SAFETY WARNING ON BATTERY HAZARDS ON P.1 OF THIS CHAPTER. BATTERIES MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN. 3.4.2 Introduction

WARNING BEFORE PROCEEDING, ENSURE THAT THE BATTERY FUSES, FS1, FS2 AND, IN 15 & 20 KVA MODELS, FS3, HAVE BEEN REMOVED FROM THE BATTERY FUSE HOLDERS AND THAT THESE FUSE HOLDERS ARE OPEN. POSITIONS ARE SHOWN IN FIG.3-17. 2. The battery fuses are packaged separately in a polythene bag, located behind the power compartment cover plate (see Fig.3-20). Do not fit them at this stage but keep them for fitting later in these instructions.

AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

MAINT TEST

General Battery blocks are six-cell, valve regulated, lead acid batteries and are carried on seven trays, positioned one above the other in one or two columns on the left hand side of the cabinet, as shown in Figs 3-11 & 3-12. The top tray in a column carries two battery blocks, and the bottom six trays carry five battery blocks each, so that a single column is made up of a string of thirty-two battery blocks connected in series to give a nominal voltage of 384V. Battery blocks are secured in the trays with three captive bolts clamping a plastic bar over their tops, (Fig. 3-15), except in the top tray where there is only one bolt. 7.5kVA & 10kVA models A string of thirty-two battery blocks are installed in a single column on the left hand side of the cabinet, as shown in Fig.3-11 & 3-16. 15kVA & 20kVA models Two strings of thirty-two battery blocks are installed in two columns on the left hand side of the cabinet, as shown in Figs. 3-12 & 3-19. The battery strings in the two adjacent columns are connected in parallel to give the same nominal battery voltage of 384V. Fuses Fuses protect the battery from excessive currents when the UPS is operating. They are carried in switched fuse holders which are provided in both the positive, (FS2), and the negative, (FS1), battery lines. In the 15/20kVA models FS3 is added, which isolates the second string of batteries when fitted. (see fig.3-18). The fuse holders are opened when installing the UPS in order to isolate the battery. Fuse sizing The ratings for the battery fuses are shown in the specification. When replacing fuses ensure that correctly rated fuses are used. 3.4.3 Units shipped with batteries (For units shipped without batteries, follow steps 1 to 4 below to remove the front and side panels and battery fuses, and then go to the next section 3.4.4). Removal of UPS panels 1. Remove the front detachable panel by pushing up its bottom edge, (Fig. 3-6).

3. Remove the left hand front panel, (Fig. 3-10), by removing the screw (1) which clamps the flange on 2 its lower edge to the cabinet frame, and pulling 1 the bottom of the panel Figure 3-10 Removal of Left away from the cabinet (2). hand front panel. The panel is held at the top by means of a tab along its top edge which fits in a slot in the overhang of the top cover on the cabinet. The tab is released by allowing the panel to drop (3) when it is pulled away from the cabinet.
O/P OFF UPS

4. Remove the left hand side panel, by releasing three screws at the front and three on the back of the cabinet; refer to Figs.311 (7.5kVA & 10kVA models) & 3-12 (15kVA & 20kVA models).

Figure 3-11 Removal of left hand side panel.

Figure 3-12 15kVA & 20kVA models.Battery chamber access.Remove the left hand side panel by releasing three screws on the front and three on the back of the cabinet.

3-4

Issue 3 (01/03/98)

IOM Manual
Checks 5. Carry out the following checks: a) Check that each battery tray is seated securely on its rails with the six (three each side) tray guide tabs locating correctly on the cabinet rails and that the batteries on each tray are positioned as shown in Figs.3-15 & 3-16. Check that the battery vents are not obstructed by the clamping bar (Figs.3-15). Check that the interlinking cables are connected as shown in Figs.3-15 & 3-16.

Chapter 3 - Installation Instructions


3. Five battery blocks are fitted in the six lower trays, and two blocks are fitted in the top tray in each column (see Fig.3-16). Batteries are secured with three captive bolts clamping a plastic bar over their tops, (Fig.3-15), except for the top tray which uses one bolt. Fit the batteries as follows: Note: Before fitting each battery block, use a suitable voltmeter to check that the voltage between its terminals is between 12.5V and 13.0V. a) b) Push the clamp bolts through the square slots in the base of each tray, and locate each bolt head in its captive slot. Set the battery tray on the work area as shown in Fig.314, so that two clamp bolts are on the far side of the battery stop.

b) c)

6. Replace the left hand side panel and then the left hand front panel by reversing the procedures described in steps 3 & 4 above. 3.4.4 Units shipped without batteries.

Battery Installation The batteries must be installed before connecting power cables to the UPS. The recommended battery is a Yuasa NP11-12 or equivalent. Important Note: Check how many 12V battery blocks have been delivered. One string of thirty two is required for the 7.5 & 10kVA models; Normally two strings of thirty two are required for the 15 & 20kVA models. 1. Follow steps 1 to 4 described above to remove the front and side panels and battery fuses. 2. Remove the front horizontal strut(s) and two vertical retaining brackets in front of the column of battery trays (Fig.3-13) by removing the screws securing them. Note in the 15 & 20kVA models there is a second set of vertical brackets on the left hand side and three horizontal struts, which must also be removed. Remove the battery trays by sliding them forward from the front of the UPS. The battery cables, clamps and bolts are stowed in the trays. Carefully store the battery mounting hardware until required. Rail guides

Rail guides(back) Batterystop Clamp bolt

Rail guide(front)

Figure 3-14 Battery tray details and orientation.

c)

Fit the battery blocks on each tray with the terminals on the left hand side of the tray, as shown in Figs. 3-15 & 3-16. 7.5kVA & 10kVA models: Fit thirty-two battery blocks in seven trays to make up one column of battery blocks. Fit two battery blocks in the tray that will be fitted on the top level of the column of battery blocks, and five battery blocks in each of the six trays that will be fitted on the other levels (Fig.3-16). 15kVA & 20kVA models: Fit the first string of thirty two battery blocks into seven trays to make up one column of battery blocks. Fit two battery blocks in the tray that will be fitted on the top level of the column of battery blocks, and five battery blocks in each of the six trays that will be fitted on the other levels. Repeat this instruction for the second string.

d)

Figure 3-13 Release the battery trays by removing the screws holding the struts and retaining brackets in front of them; the screws holding the left hand brackets are hidden from view in the diagram. Note: There is a second pair of brackets in the 15kVA & 20kVA models, fastened similarly, in front of the left hand column.

Batteries are secured in the trays with three captive bolts clamping a plastic bar over their tops, (Fig.3-15), except in the top tray where only one bolt is used. Place the clamp bar over the top of the batteries in each tray, and ensure that each bolt feeds through its corresponding hole in the bar.

Note: The clamp bar must be positioned so that it runs between the middle and the right hand vents on each battery as shown in Fig.3-15.

Issue 3 (01/03/98)

3-5

Chapter 3 - Installation Instructions


e) Fit a flat washer, locking washer and a nut to the end of each bolt (Fig.3-15) and tighten down sufficiently to hold the batteries so that they cannot move in the tray (recommended torque loading is 2.5Nm).

AP4300
ties as indicated in fig.3-15. Leave the front end of the cable unconnected. 2. a) Refit the battery trays in the battery compartment and push them fully back on their rails; ensure that the tray guide tabs (Fig.3-14) are correctly located on the cabinet rails. Ensure the tray containing two battery blocks is fitted onto the top set of cabinet rails. Refit the vertical retaining brackets and front horizontal strut(s) shown in Fig.3-13.

62

recommended torque loading is 2.5Nm


62

Clamp bar
62

b)

interlinking cables cable tie

62

battery vent

3. Connect the cables between the battery sets in different trays: 7.5 & 10kVA models: Start with the bottom tray and connect the free end of the long interlinking cable, marked no.61, on each tray to the front (i.e. negative) terminal of the battery at the front of the tray immediately above in the same column. See Fig.3-16. Continue in this way until the trays on all the levels in the column have been connected. 15 & 20kVA models: Carry out the above procedure on the right hand column and then on the left hand column of battery trays. Battery string voltage checks - 15 & 20kVA models only When the battery blocks in each column have been connected up to form two battery strings, the voltage across each battery string must be checked before connecting them together. Measure the total voltage of each battery string with a voltmeter set on a DC range above 450V, as described below. 1. Measure and note the voltage of the battery string in the right hand column by placing the positive meter lead on the positive terminal (the rear terminal) of the rear battery on the top tray in the column, and then placing the negative meter lead on the negative terminal (the front terminal) of the front battery on the bottom tray in the same column. Refer to Fig.3-16 The total battery voltage should be between +384Vdc and +416Vdc.

61

Connection to next tray up Figure 3-15 Battery tray with battery blocks and clamp bar in position and interlinking cables connected (All models)

Battery cabling 1. Cable up the batteries in each tray as follows:

Important Note: The battery cables are fitted with Fast-on connectors. When connecting the cables to the batteries make sure that the battery tab fits correctly into the connector and not between the connector and its insulation. a) b) Connect the interlinking cables, marked no.62, between each of the batteries on each tray as shown in Fig.3-15. Fit a long interlinking cable, marked no.61, to the positive terminal of the battery at the rear of each tray use cable
A
+ + + 61

+ve Meter Probe

SW1
MAINT TEST

O/P OFF

UPS

FS3
61

Meter Terminals
-ve +ve

+ + + + -

FS3

FS1

FS2

CB1 CB2 CB3 CB4 CB5 CB6

61

FS1
BATTERY FUSES
BATTBATT+

BYPASS

INPUT

61

FS2

U V W N N N N U U V V WW E E E 3 3 3 3 4 2 1 2 1 2 1 2 1 1 2 3

61

61

-ve Meter Probe

Figure 3-16 Single battery string showing inter row connectors marked No. 61 and string positive and negative connections.

Figure 3-17 Detail of the 15 & 20kVA UPS showing the position of FS1, FS2 & FS3.
Issue 3 (01/03/98)

3-6

IOM Manual
2. Repeat step 1 above on the battery string in the left hand column. 3. If these checks are satisfactory, further connections to the batteries must be made before continuing with the voltage checks. Connection of the UPS cables to the battery string(s) (7.5 & 10kVA models only) WARNING ENSURE THE BATTERY FUSES FS1 AND FS2 ARE NOT FITTED AND THE FUSED SWITCHES ARE OPEN. 1. Push the connector on the free end of the red cable marked no.60 (labelled A in Fig.3-16) that enters from the slot in the top right hand corner of the cabinet on to the positive (rear) terminal of the rear battery on the top tray. 2. Connect the free end of the black cable marked no.59 (labelled B in Fig.3-16) that enters from the slot in the bottom right hand corner of the cabinet to the negative (front) terminal of the front battery on the bottom tray. 3. Refit the left hand side panel by reversing the procedure described in step 4 of para.3.4.3, (refer to Fig.3-11). This completes the battery connections. The total battery voltage must now be checked before continuing with the UPS installation. Turn to p.8 and follow the procedure given in the section: Total Battery Voltage Check. Connection of the UPS cables to the battery string(s) 15 & 20kVA models only: WARNING FUSEHOLDERS FS1, FS2 & FS3 MUST BE OPEN WITH THE FUSES REMOVED. DO NOT FIT ANY FUSES IN THEIR HOLDERS OR CLOSE ANY FUSE HOLDERS UNTIL INSTRUCTED. 1. Connect up the cables to the positive terminal of each battery string as shown in Fig.3-19, i.e.: b)

Chapter 3 - Installation Instructions


compartment from its top right hand corner and connect to cable no 55, using the connectors provided. Repeat the above operation on the left hand battery string, connecting cable marked no 67 to the battery and its other end to cable marked no 60.

2. Voltage Difference Check:


67 60 55 57 FS2 FS3

+ +

+ -

+ + -

+ -

+ + + + -

+ + + -

+ve meter probe Meter terminals


+ve -ve

-ve meter probe Figure 3-19 15 & 20kVA models only:Measuring the voltage difference between the two battery strings Note:- Fuses An additional battery fuse, FS3, is provided in the positive line between the two battery strings in the 15 & 20kVA units. The fuse protects the two battery strings from excessive currents flowing between them if they are unevenly discharged. Fig. 3-17 shows the position of the fuse-holders FS1, FS2 & FS3 . The block diagram in Fig.3-18 shows how they are connected to the two battery strings. Check the difference in voltage between the two battery strings with a voltmeter set on a DC range above 450V, as follows: a) Insert the fuse in fuse holder FS3 and close the fuse holder. Measure the voltage between the front (negative) terminals of the front battery block in the bottom tray in the left and the right hand columns. Refer to Fig.3-19. Open fuse holder FS3; remove and retain the fuse; leave the fuse-holder open.

59

58

55

57

right hand string

FS3
56

b)

65

64

67

60

FS1

Left hand string

c)
FS2

To converter SCR To Negative of d.c. bus Figure 3-18 Electrical block diagram of the main components in the battery circuit of the 15 & 20kVA models

a)

Push the connector at the end of the red cable marked no.55 onto the rear positive terminal of the rear battery on the top tray of the right hand string. Locate cable marked no 57 which enters the right hand battery

WARNING THE VOLTAGE READING SHOULD BE IDENTICAL TO THE DIFFERENCE IN THE READINGS NOTED EARLIER (BATTERY STRING VOLTAGE CHECKS) AND MUST NOT EXCEED 32V. IF THE VOLTAGE DIFFERENCE IS GREATER THAN 32V, THE BATTERIES HAVE BEEN CONNECTED INCORRECTLY. DISCONNECT THE BATTERY CABLES 55 TO 57 AND 60 TO 67, AND CORRECT THE BATTERY CABLING SO THAT A SATISFACTORY VOLTAGE INDICATION IS OBTAINED.

Issue 3 (01/03/98)

3-7

Chapter 3 - Installation Instructions


If the voltage difference checks are satisfactory, proceed to the next step to complete the connections to the batteries. 3. Final battery cable connections (15 & 20kVA models contd.) Connect up the cables to the negative terminal of each battery string as follows: WARNING FUSEHOLDERS FS1, FS2 & FS3 (FIG.3-17) MUST BE OPEN WITH THE FUSES REMOVED. a. Push the fast-on connector of the black cable marked no 58 onto the front negative terminal of the front battery on the bottom tray of the right hand string. Locate the black cable marked no 59 which enters the right hand battery compartment at its bottom right hand corner and connect it to cable marked no 58 using the connector provided. Repeat step a above on the left hand string using cable marked no 64 to the battery and its other end to cable marked no 65. Refit the left hand side panel (refer to Fig.3-12) by reversing the procedure described in step 4 of para.3.4.3.

AP4300
Measure the voltage between the upper screw terminals of the battery fuses FS1 (negative meter lead), and FS2 (positive meter lead); refer to Fig.3-21. The total battery voltage must be between 400Vdc and 416Vdc. WARNING ENSURE THAT THE METER INDICATES A POSITIVE VOLTAGE POLARITY. IF A NEGATIVE VOLTAGE IS INDICATED, DISCONNECT THE EXTENDED BATTERY CABINET CABLES FROM THE UPS, AND CORRECT THE EXTENDED BATTERY CABLING SO THAT A POSITIVE VOLTAGE INDICATION IS OBTAINED. 4. Replace the terminal block cover removed from the UPS in step 1 above. 5. Refit the left hand front panel by reversing the procedure described in step 3 of para.3.4.3, (Fig.3-10). This completes the Battery Installation procedure. Continue the UPS installation by going to Section 3-5 - Final Positioning.

b.

c.

Total Battery Voltage Check -All UPS models Check the total battery voltage with a suitable voltmeter as follows: 1. Remove the terminal block cover plate - see Fig.3-20 in order to gain access to the battery fuse holder terminals. 2. 15 & 20kVA models only - Insert a 30A fuse in fuse holder FS3 beside the battery compartment (Fig.3-17) and close it. 3. Set the voltmeter on a DC range above 450V.
BATTBATT+
BATTERY FUSES

MAINT

TEST

O/P OFF

UPS

SW1
FS1 FS2 CB1 CB2 CB3 CB4 CB5 CB6

BYPASS

INPUT

WARNING DO NOT FIT FUSES IN BATTERY FUSE-HOLDERS FS1 OR FS2. ENSURE THESE FUSE HOLDERS ARE LEFT OPEN.

U V W N N N U U V V WW E E E 3 3 3 3 2 1 2 1 2 1 2 1 1 2 3

+ve

-ve

Fused SwitchesFS1 & FS2(Battery Fuses)

AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

Figure 3-21 Terminals on the UPS on which the meter probes must be placed to measure the total battery voltage. Fused Switches (battery fuses) Circuit Breakers

AP4300

Power compartment cover plate


MAINT TEST

O/P OFF UPS

Main Terminal Block Gland Plate Cable Entry Aperture

Figure 3-20 UPS Power cable entry

3-8

Issue 3 (01/03/98)

IOM Manual
3.5 Final Positioning.

Chapter 3 - Installation Instructions


Important: If the intention is to install the UPS in a position where it will be moved away from nearby furniture etc. in order to gain access for servicing purposes, its power cables must be of sufficient length to permit this. When it is in its working position the surplus cable must be stowed safely beneath the equipment. 3.6.3 Input supply protection.

1. Wheel the UPS near to its final position but leave adequate room around it for work. 2. The brackets (2 off) which secure the UPS to its shipping pallet also serve as jacking feet to prevent the UPS from moving once it is in position. Important: The jacking feet support a large proportion of the equipment weight when the feet are screwed down tightly. 3. Move the UPS to its final position and screw down both jacking feet as far as possible. Important: If the installation was shipped with batteries fitted and includes an extended' battery option or remote' battery option these should be connected at this point following the appropriate instructions supplied with these options.

WARNING THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED PROTECTION. A WARNING LABEL MUST BE FITTED TO ALL PRIMARY POWER ISOLATORS STATING: ISOLATE UNINTERRUPTIBLE POWER SUPPLY BEFORE WORKING ON THIS CIRCUIT All supplies to the UPS must be provided with three phase power isolators, each of which can break all its supply lines to the UPS simultaneously; a split bypass system will require two isolators. The isolator(s) must be located within two metres of the UPS. Note: The UPS internal input and bypass circuit breakers are type C (IEC 898). The overload characteristics of the input isolators supplying these circuit breakers must be selected accordingly. Refer to table 3-1 in order to choose site supply fuses, circuit breakers and power isolators appropriate to the UPS current ratings. On start-up the UPS will take a half cycle inrush current of 7 to 8 times the rated current. This must be taken into account when selecting the overload protection device at the input mains supply distribution point. To avoid random tripping on start-up, we recommend that the input mains supply is protected with an MCB capable of withstanding this initial inrush. (An MCB specified as being either TYPE 4 (British Standard) or rated to CURVE D (IEC 898) is suitable for this purpose.)

3.6
3.6.1

Connecting the UPS Power Cables


General introduction

Power cables connect to screw terminals on a terminal block which is located behind the power compartment front cover plate see Fig.3-20. They enter the UPS at the front, from beneath, and pass through a gland plate which covers an aperture in the cabinet floor. Cables used for all input and output distribution should enter the UPS via flexible metal conduit which must be terminated at the gland-plate on the UPS. The gland-plate must first be removed and drilled to suit the glands or bushes for the cables. Ensure that the glands are sized so that they hold the cables securely. If the intention is to run the cables to the UPS above the floor, instead of from below, then the cable must be carried in a flexible metal conduit, and a suitable 60 or 90 elbow must be used where the cable enters the UPS. A block diagram of the electrical circuit is shown in Fig.3-29. 3.6.2 Cable sizing consideration The UPS must be installed in compliance with local regulations. Before cabling-up, careful consideration must be given to selecting the appropriate size power cables and input circuit protection device see table 3-1 below. Note: The maximum cable size that can be connected to the UPS power terminal blocks is 10mm Input / Output cables The UPS requires a 380V/415V three phase input supply and produces a 380V/415V three phase output. The input, output and bypass cables are all rated the same. Bypass cables The bypass supply can either be connected to the UPS input supply (common bypass) or it can be linked to a separate three phase power source (split bypass). Figures 3-25 to 3-28 show these configurations. Neutral cables It is important to size the neutral cable according to the type of load connected. Some loads can give a neutral current equal to twice the line current.

Table 3-1 - Power Cable & Fuse Current Ratings Model Rating
Max input current @ 380V (-15%) (including battery charging*) Maximum bypass current @ 220V (-15%) Rating for circuit breaker on supply to input terminals (& to bypass terminals in split bypass system): Note: Circuit Breaker type C (or slower) is recommended.

7.5 kVA
16A

10 kVA
20A

14A 18A minimum 25A maximum 32A

Table 3-1a - Power Cable & Fuse Current Ratings Model Rating 15 20 kVA kVA

Max input current @ 380V (-15%) (including 32A 40A battery charging*) Maximum bypass current @ 220V (-15%) 28A 36A Rating for circuit breaker on supply to input minimum 50A terminals (& to bypass terminals in split bypass maximum 63A system): Note: Circuit Breaker type C (or slower) is recommended.

Issue 3 (01/03/98)

3-9

Chapter 3 - Installation Instructions


3.7 Terminal connection points

AP4300

Caution This equipment is fitted with RFI suppression filters. Earth leakage exceeds 3.5mA but is less than 200mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCCD devices. Note also that the earth leakage currents of the load will be carried by this RCCB or RCCD. WARNING HIGH LEAKAGE CURRENT - EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY THIS EQUIPMENT MUST BE EARTHED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES. 3.6.4 Output Protection

Fig. 3-22 shows the position of the power cable connection terminals behind the power compartment cover plate which must first be removed. The input and bypass cables are connected directly to the terminal block. Note that the terminal blocks for the input phases (U1, V1, W1), and bypass phases (U2, V2, W2), are fitted with bridging links which are removed when the UPS is supplied with a separate bypass supply. Use the procedures described below for connecting power cables to both the 10 and the 20 kVA units. WARNING THE BRIDGING LINK FITTED ACROSS THE NEUTRAL TERMINAL BLOCKS N1, N2 & N3 ON 10 KVA UNITS (FIG.3-24) AND ACROSS N1 & N2, AND N3 & N4 ON 20KVA UNITS (FIG.3-26) MUST NOT BE REMOVED ON A COMMON BYPASS SYSTEM SEE FIGURE 3-23.

Caution Where the load consists of a number of loads, care must be exercised that the correct type of rating of protection is used. Ensure that individual loads are protected and that the correct discrimination is maintained between different load elements.

MAINT

TEST

Fused Switches (Battery Fuses) Bypass Circuit Breakers

O/P OFF

UPS

SW1
FS1 FS2

CB1 CB2 CB3 CB4 CB5 CB6

BATTBATT+

BATTERY FUSES

BYPASS

INPUT

Input Circuit Breakers Earth Connection Terminals Common Bypass Links

U V W N N N U U V V WW E E E 3 3 3 3 2 1 2 1 2 1 2 1 1 2 3

Extended Battery Connectors

Power Connection Terminal Block

Neutral Bridging Link

Figure 3-22 Detail showing power cable connection terminals, fuse locations and circuit breakers accessed after removing the front panel. Key to terminal labels Input Supply U1, V1, W1, N1 Bypass Supply U2, V2, W2, N2 Output U3, V3, W3, N3 Earth E1, E2, E3 Note: The terminal arrangements for the 20kVA unit include an extra neutral terminal - N4 (see Fig.3-26).

3-10

Issue 3 (01/03/98)

IOM Manual
Neutral linking Figure 3-23 shows various input alternatives and the arrangement of the bypass links and specifically the neutral link. The upper row of drawings show the 7.5/10kVA configurations and the lower row shows the 15/20kVA configurations. The UPS power train does not require a neutral input, however, it is essential that the bypass has a neutral as this is used not only when the system is in bypass but as a reference by the UPS power train. The linking should be arranged as follows:Figure A Shows a standard common bypass system with a 4 wire and earth input supply - all links should be fitted. Figure B Shows a Split bypass system with a 3 wire and earth input supply to the UPS power train and a 4 wire and earth input supply to the bypass - the U, V & W links should be removed; the neutral link can be left in position. Figure C Shows a split bypass system with a 4 wire and earth input supply to the UPS power train and a 3 wire and earth input supply to the bypass - the U, V & W links should be removed; it is essential that the neutral links are left in position Figure D Shows a split bypass system with a 4 wire and earth input supply to the UPS power train and a 4 wire and earth input supply to the bypass - the U, V & W links should be removed; The neutral link between N1 and N2 should also be removed, on the 7.5/10kVA unit this would involve removing the three terminal link and removing with cutters the N1/N2 link and then refitting the link onto N2 and N3 terminals.
7,5/10 kVA
N3
N2 U2 V2 W2 N1

Chapter 3 - Installation Instructions


Connections to Extended and Remote battery cabinets The black and the red connectors on the leads from the external battery cabinet must be connected to their corresponding connectors on the leads from the terminals directly below the battery fuses, labelled - and + in figs.3-24 & 3-26 i.e. black to black and red to red. The Extended Battery cabinet contains fuses in both its positive and negative output lines. They are held in the same type of fuse holders as those used in the UPS FS1 and FS2 positions. This provides protection and enables the Extended Batteries to be isolated independently from the internal batteries for servicing etc. The terminal for the negative connection from the Extended/Remote battery is connected directly to the UPS internal DC busbar negative rail. The terminal for the positive connection from the Extended/Remote battery is connected through FS2, and is therefore connected to the UPS internal DC busbar positive rail via FS2. FS2 therefore carries both the internal and extended or remote battery currents. The batteries are connected in this way for safety reasons; when the UPS battery fuse holders (FS1/FS2) are opened, the positive terminals of both the internal and extended/remote batteries are disconnected from the DC busbar. Full fitting instructions are provided with the option pack. The UPS internal batteries are protected by fuses FS1 & FS2. The optional Extended battery units by its own fuses FS1 and FS2, a Remote battery must be equipped with equivalent fuses to protect the external batteries. Where a Remote Battery option is used, an isolator and overload protection device must be located as close to the batteries as possible.

N3

Bypass 4 wire and earth input UPS 3 wire and earth input

N2 U2 V2 W2 N1 U1 V1 W1

4 wire and earth input

U1 V1 W1

Common Bypass Links

A
N3

B
N3

Bypass 3 wire and earth input UPS 4 wire and earth input

N2 U2 V2 W2 N1 U1 V1 W1

Bypass 4 wire and earth input UPS 4 wire and earth input
15/20 kVA

N2 U2 V2 W2 N1 U1 V1 W1

B L A C K
L6

U V W N N N U U V V WW E E E 3 3 3 3 2 1 2 1 2 1 2 1 1 2 3Power Connection

N3 N4
N2 U2 V2 W2 N1 U1 V1 W1
L6

N3 N4

- +E D

Terminals

Bypass 4 wire and earth input UPS 3 wire and earth input

N2 U2 V2 W2 N1 U1 V1 W1

To Extended/Remote Battery Connections Figure 3-24 Terminals for extended battery connections

4 wire and earth input

A
N3 N4
L6

B
N3 N4
L6

Bypass 3 wire and earth input UPS 4 wire and earth input

N2 U2 V2 W2 N1 U1 V1 W1

Bypass 4 wire and earth input UPS 4 wire and earth input
D

N2 U2 V2 W2 N1 U1 V1 W1

Figure 3-23 Bridging links for common and split bypass with three and four wire inputs.

Issue 3 (01/03/98)

3-11

Chapter 3 - Installation Instructions


3.8 Procedure for connecting the UPS to the power supply
Power Connection Terminals

AP4300
Earth Terminals
U V W N N N N U U V V WW E E E 3 3 3 3 4 2 1 2 1 2 1 2 1 1 2 3

WARNING BEFORE PROCEEDING WITH CABLING-UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE DISTRIBUTION PANEL ISOLATORS THAT CONNECT MAINS POWER TO THE UPS. VERIFY THAT THESE ISOLATORS ARE OPEN, AND THAT ALL NECESSARY SAFETY MEASURES TO PREVENT THEIR CLOSURE HAVE BEEN TAKEN. ENSURE THAT THE MAIN ROTARY SWITCH, SW1, IS SET AT OFF. BEFORE CONNECTING THE SUPPLY CABLES TO THE UPS, A PERMANENT SIGN MUST BE PLACED AT THE ISOLATOR FROM WHICH THE CABLES ARE RUN, STATING THAT THE ISOLATOR IS SUPPLYING A UPS. IT IS IMPORTANT THAT THIS ISOLATOR IS ONLY OPERATED WITH THE AUTHORITY OF THE UPS USER. 3.8.1 Common input/bypass supply system This procedure should be followed if the same power source is used for both the UPS input and the bypass supply. Use it for both the 10 and the 20kVA units. 1. Ensure that the fuse holders FS1 & FS2, and circuit breakers CB1 to CB6 are open. 2. Remove the power compartment front cover plate see Fig.3-20. 3. Connect the input earth to one of the main earth terminals (E1, E2, E3) shown in figs. 3-25/26. The output earth wires must also be connected to one of these earth terminals. 4. Connect the output cables to the UPS output terminals U3, V3, W3, and N3 on 10kVA units (Fig.3-25); an additional neutral link is provided on 20kVA units (Fig.3-26). Be sure to observe the correct phase rotation. 5. Connect the input cables from the supply distribution panel to the UPS input terminals U1, V1, W1, N1 shown in figs.325/26. Be sure to observe the correct phase rotation. Replace the terminal block cover plate and all panels removed earlier.

BATTBATT+

Common Bypass Links


U VWN N N U V W

3 phase output and neutral to load

3 phase input supply and neutral

Figure 3-26 Power cable connections - 20kVA unit in common bypass configuration

3.8.2 Split input/bypass supply This procedure should be followed if the UPS input and bypass input are supplied from different three phase supplies. Use it for both the 10 and the 20 kVA units. 1. Ensure that the fuse holders FS1 & FS2, and circuit breakers CB1 to CB6 are open. 2. Remove the power compartment front cover plate see Fig.3-20. 3. Remove the U1/U2, V1/V2, W1/W2 links as shown in figs. 3-27 & 28. Leave the bridging links fitted to the earth terminal blocks (E1, E2 & E3) and the neutral terminal blocks refer to figure 3-23. 4. Connect the input earth to one of the main earth terminals (E1, E2, E3) shown in figs. 3-27/28. The output earth wires must also be connected to an earth terminal. Common bypass links removed from U, V, W terminals Earth Terminals

Neutral Bridging Link refer to figure 3-23.

BATTBATT+

BATTBATT+

Earth Terminals

U V W N N N U U V V WW E E E 3 3 3 3 2 1 2 1 2 1 2 1 1 2 3

U V W N N N U U V V WW E E E 3 3 3 3 2 1 2 1 2 1 2 1 1 2 3

Earth Bridging Link

Power Connection Terminals

U VWN 3 phase output and neutral to load

N U V W 3 phase input supply and neutral

Common Bypass Links

Power Connection Terminals

W 3 phase input V supply U U VWN 3 phase output and neutral to load


3phase bypass supply & neutral

Figure 3-25 Power cable connections - 10kVA unit in common bypass configuration

W V U N Figure 3-27 Power cable connections - 10kVA unit in split bypass configuration

3-12

Issue 3 (01/03/98)

IOM Manual
5. Connect the output cables to the UPS output terminals U3, V3, W3, and N3 on 10kVA units (Fig.3-27); an additional neutral link is provided on 20kVA units (Fig.3-28). Be sure to observe the correct phase rotation. 6. Connect the bypass cables from the supply distribution panel to the UPS bypass terminals U2, V2, W2 & N2 as shown in figs.3-27/28. Be sure to observe the correct phase rotation. 7. Connect the input cables from the supply distribution panel to the UPS input terminals U1, V1, W1 & N1 as shown in figs. 3-27/28. Be sure to observe the correct phase rotation. Replace the terminal block cover plate and all panels removed earlier. Common bypass links removed from U, V, W terminals Earth Terminals Earth Bridging Link

Chapter 3 - Installation Instructions


3.10 Electrical Details

3.10.1 Introduction The main components in the UPS are shown in the block diagram of the circuit in Fig.3-29. The converter, battery charger, inverter and static switch are controlled by the microcontroller.

Key to labels in Fig.3-29


A B C D E F Input Filter 3-phase rectifier (into 580V bus) Resonant Circuit & Switches HF Transformer (T1) 1-Phase Rectifier (into 800V bus) 3-phase Inverter G H J K L M Output Filter Battery Charger Battery String 2nd Battery string (15/20kVA units only) Static Switch Input links

Neutral Bridging Link refer to figure 3-23.


BATTBATT+

U V W N N N N U U V V WW E E E 3 3 3 3 4 2 1 2 1 2 1 2 1 1 2 3

Power Connection Terminals

W 3 phase input V supply U U VWN N 3 phase output and neutral to load

W 3phase bypass V supply & U neutral N Figure 3-28 Power cable connections - 20kVA unit in split bypass configuration

3.9

Commissioning

Now that the unit has been correctly installed it must be commissioned by a Liebert approved engineer. He will validate the installation work and install site information into the UPS microcontroller memory. This information is required to substantiate and validate any subsequent warranty claims that might be made. Refer to the Commissioning Manual.

Issue 3 (01/03/98)

3-13

3-14
Maintenance Bypass
S1-A S1-B S1-E
N2

Chapter 3 - Installation Instructions

CB1
U2

Static Bypass

L
L6

BypassSupply Figure 3-29 Electrical block diagram InputSupply

CB2
V2 W2

CB3

M
U1 V1

Remove links for Split Bypass system


CB4

I/P Over voltage Cut-out Relay

Main Control Switch SW1


S1-C

N4 N3
U3

Output

CB5 CB6
W1 N1

C DE

F
Inverter Output Cutout Relay

S1-D
V3

S1-G
W3

15/20kVA units only 2nd battery string

FS3

FS1

FS2

H
AP4300 INITIALISING PLEASE WAIT...

ESC

AP4300

K
Output offSwitch SW2

J
MICROCONTROLLER BOARD INTERFACE

OPTIONS

Issue 3 (01/03/98)

Remote Stop Option

AP4300

Chapter 4 - Options and Features

4.1

Introduction

4.2
4.2.1

Standard Features
Auto-restart Inhibit

A number of options and features are available on the AP4300 series UPS; these are listed below.

Auto-restart Inhibit (feature). Common Bypass Links (feature). Remote Stop (option). Hot Standby Configuration (feature). RS232 Interface and External Relay Board (feature). RS232 Compatible Software (SiteNet) (option). SNMP Interface (option). Remote Alarm Monitor (option). Extended Battery (option). Remote Battery (option). Input Filter (option). Isolation Transformer (option). Bypass Enclosure (option). Output Distribution Module (option). Frequency Changer (Option).
All options are supplied complete with installation and operator instructions.

The UPS has an Auto-restart facility fitted as standard. If this capability is not required, the commissioning engineer will inhibit it by setting a parameter during commissioning. 4.2.2 Common Bypass Links The input terminals to the rectifier are separate from the static bypass line terminals, so that different power supplies can be used for the two inputs. This arrangement is referred to as split bypass. An alternative arrangement, referred to as common bypass, where the corresponding phases on these two sets of input terminals are connected by means of links, is used where only one power supply is available. The UPS is supplied with the common bypass links fitted. The connecting links for the common bypass must be removed during installation if a split bypass arrangement is required - refer to the Chapter 3. 4.2.3 Remote stop A remote stop circuit can be connected to an RJ12 connector on the inner panel behind the right hand detachable (lift-off) panel on the front of the UPS. The remote stop kit consists of a 10 metre length cable with a RJ12 connector on one end and a junction box for connection to the users normally closed switch on the other end. When selected open the switch provides a remote output OFF control. 4.2.4 Hot Standby Configuration The AP4300 can be used in a HOT STANDBY to provide increased security for the load. One UPS is connected in the Common input/Bypass Configuration, and is used to supply a second unit which is connected in a split bypass configuration.

Unit 1 (Common Input/Bypass Configuration) (see 3.8.1)

E N L1 L2 L3

Unit 2 (Split Bypass Configuration) (see 3.8.2)

E N

LOAD
L1 L2 L3

Figure 4-1 Hot Standby Configuration

Issue 3 (01/03/98)

4-1

Chapter 4 - Options and Features


4.3
4.3.1

AP4300
Connectors The AP4300 communication board is fitted with two 25 way female D type connectors as shown in Figs. 4-2 & 4-4. The top connector is labelled COMM'S; the lower connector is labelled RELAY. The DB25 socket labelled RELAY connects only to a set of relay contacts on the board. The DB25 socket labelled COMM'S connects to a second set of relay contacts, to lines carrying the direct action signals and also to the RS232D serial interface as shown in figure 4-3.
25 Way D' Type Connector PL1
15 N.C. N.O. N.C. N.O. TxD RxD GND 24 18 16 17 10 11 9 2

Remote Control/ Communications Facilities


RS232 Interface and External Relay Board

Introduction The COMMUNICATIONS BOARD is fitted as standard and provides two sets of volt free relay contacts, an interface for a set of direct action signals conforming to RS232D voltage levels, and a local RS232D serial port. The local RS232D serial port permits signals about the state of the UPS to be transmitted to a wide range of computers, which can then transmit control signals back to the UPS when required. The computers may be located close to the UPS or remotely. Communication with computers over short distances is achieved by connecting them directly to the RS232 interface. Communication with remotely located computers, i.e. over greater distances, requires the use of a modem and telephone line. Note: When employing the communications features of the AP4300, SiteNet software and cable kits are available for use with most operating systems. When using the communications connector, only Liebert software and connecting cables should be used. If using other than Liebert cable or software, only terminals 2, 3 and 7 (send, receive, ground) should be connected. Use of the other terminals may change the operational state of the UPS or cause a shutdown. Communications with the UPS is not guaranteed with unauthorised software and cables. Note: Any connection to a telecommunications network must be via an approved modem complying with clause 6 of BS EN 60950:1994 or BS EN 41003:1997. The relay contacts on the COMMUNICATIONS board permit the status of the UPS and major UPS alarms to be transmitted to other devices such as an external alarm panel located remote to the unit, or to the power supply monitoring features of the *IBM AS400 computer systems, *Novell, *UNIX or other common operating systems. * Registered Trade Marks

25 Way 'D' Type Connector PL3 UPS ON ON BYPASS ON BATTERY COMMON


15 24 18 N.C. 16 N.O. 17 10 N.C. 11 N.O. 9

LOW BATTERY COMMON

Transmit data (from external system)

3 Receive data (to external system) 7

0 volt for use with Serial data lines and RS232 compatible lines

21 LOW BATTERY Outputs 13 POWER FAIL

Inputs

19 INVERTER SHUTDOWN HIGH 12 INVERTER SHUTDOWN LOW 14 ON/OFF (High/Low)

RS232 level control signals

Figure 4-3 DB25 Connectors Comms (PL1) and Relay (PL3) Output Communication Lines.

Remote Stop Connection PL1 Comms. Connector


PL1

The outputs from the relay contact closures permit information about the state of the UPS to be sent, via a cable, to external indicating panels etc. The relays are operated by the following UPS states: On UPS On battery On bypass Low battery The RS232D direct action signals are used by the UPS to indicate to an attached system when the UPS state changes; and by the attached system to control the UPS. The relay contacts and interface signals are assigned to the connector pins as set out in figure 4-3 and the table below: Cable Termination The DB25 connector on the UPS end of the cable must be a right angle outlet as shown in Fig.4-4. The front cover of the UPS cannot be fitted correctly if a straight-out connector is used.

PL3

PL3 Relay Connector

Figure 4-2 Location of the communications assembly in the UPS

4-2

Issue 3 (01/03/98)

IOM Manual
DB25 Pin Definition: The pin out for both DB25 connectors is shown below.

Chapter 4 - Options and Features


The function of the relay contact connections are listed below:

Relay Contact Pin No. Signal name COMMS Connector PL1


Not Used TXD RXD Not Used Not Used Not Used Signal Common Not Used Low Battery Relay common

Direction
On UPS Relay On Bypass Relay On Battery Relay

Normal State
NO NO NO

Function
Contact is closed when the UPS is operational Contact closes when the UPS activates the static bypass Contact is closed when the UPS is using power from its internal batteries (utility has failed) Contact is opened when the UPS is deriving power from its internal batteries (utility has failed) Contact closes when the battery voltage reaches a given threshold, and indicates a limited time period before the UPS shuts down. Contact opens when the battery voltage reaches a given threshold, and indicates a limited time period before the UPS shuts down. A common connection for the ON UPS, ON BATTERY and ON BYPASS relays. A common connection for the LOW BATTERY relay. This connection is separate from the Relays Common to maintain compatibility with the UPStation GX interface.

RELAY Connector PL3


Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Low Battery Relay common From UPS From UPS To UPS From UPS To UPS From UPS

1 2 3 4 5 6 7 8 9

On Battery Relay

NC

Low Battery Relay

NO

Low Battery Relay

10 Low Battery Relay NC Low Battery Relay NC 11 Low Battery Relay NO Low Battery Relay NO 12 Shutdown, Active Low Not Used 13 Power Fail (Active High) 14 ON/OFF (High/Low) 15 On UPS Relay NO 17 Relays Common 18 On Battery Relay NC 20 Not Used 21 Low Battery (Active High) 22 Not Used 23 Not Used 24 On Bypass Relay NO 25 Not Used Relays Not Used Not Used On UPS Relay NO

NC

Relays Common

Low Battery Relay common

16 On Battery Relay NO On Battery Relay NO From UPS Relays Common On Battery Relay NC From UPS To UPS

19 Shutdown, Active High Not Used Not Used Not Used Not Used Not Used

Direct Action signals(RS232D interface) From UPS The direct action signals are used by the UPS to indicate a change of state to a connected system (monitoring signals), and by the system to control the UPS (control signals). The signal excursions will conform to the RS232D standard; i.e. a high is a voltage level between +3 and +15 volts and a low is a voltage level between -3 and -15 volts. Description of the Monitoring & Control signals Monitoring signals (i.e. sent by the UPS to an external system) Power Fail (Active High - pin 13) This output is normally held at an RS232 low level and is set to an RS232 high level if the utility supply fails. Low Battery (Active High - pin 21) This output is normally held at an RS232 low level and is set to an RS232 high level if the battery voltage drops to a pre-set voltage level. This indicates a limited time before the UPS shuts down. Control signals (i.e. sent to the UPS by an external system): ON/OFF (High/Low - pin 14) An RS232 high level signal on this pin will turn the UPS on (if it is off), and an RS232 low level signal will turn the UPS off (if it is on). If the UPS is ON and the interface cable is disconnected the UPS will remain ON. If the UPS is OFF and the interface cable is disconnected the UPS will remain OFF.

On Bypass Relay NO From UPS Not Used

The relays provide volt free contact closures for connection to AS400 minicomputers and/or connection to Novell networks. Contact ratings: 1A at 30Vdc 0.5A at 125Vdc 0.3A at 110Vac. Four relays are used, each having a double pole change-over contact. They are energised by changes in the state of the UPS as shown below; the signals are used by the systems shown in brackets: ON UPS (AS400 Interface) ON BYPASS (AS400 Interface) ON BATTERY (AS400 and NOVELL interface) LOW BATTERY (AS400 and NOVELL interface)

Issue 3 (01/03/98)

4-3

Chapter 4 - Options and Features


Shutdown (Active High - pin 19) An RS232 high level on this input causes the UPS to shutdown. The utility must have failed and the signal must be present for 2 seconds. Disconnecting the interface cable will not cause the UPS to shut down. Shutdown (Active Low - pin 12) An RS232 low level on this input causes the UPS to shutdown. The utility must have failed and the signal must be present for 2 seconds. Disconnecting the Interface cable will not cause the UPS to shut down. Note: The two shutdown signals are logically OR'd within the UPS; either one of these must be present for 2 seconds before they shutdown the UPS. The conditions for the shutdown are set by the user on the UPS control panel and can be selected from: a) b) Shutdown the UPS if the utility has failed and the UPS is on battery. Shutdown the UPS whatever its condition. Cable connection Procedure

AP4300

Preparation

Caution The load will not be protected from an input power supply failure during the following procedure. 1. 2. Remove the lift off perforated cover from the front of the UPS cabinet. Follow the procedure To Put the Load on Maintenance Bypass given in the Operator Manual to isolate the internal components of the UPS, while continuing to supply the load with power. Ensure that all the circuit breakers (CB1 - CB6) and battery fuse holders (FS1, FS2) are open.

3.

Cable connection
4.

Action a is the default. Signal Common A common reference for all active interface signals.

Remote communications The TxD transmit data signal (from external system) to pin 2 The RxD receive data signal (to external system) to pin 3 The signal common signal - common reference for all interface signals to pin 7. Serial Communications To provide a straight forward connection to an attached system the above signals will be arranged to configure the interface so that the UPS behaves as a DCE (Data Communications Equipment). If the attached system employs a 25 way D type connector, then us connections:UPS System 2 2 3 3

Insert the 25-way D-type connector at the end of the cable into the socket marked RELAY or COMMS (as appropriate) on the communications option board. Run the cable down to the bottom of the cabinet so that it will leave the UPS from beneath the front lift off cover and connect it to the external communication equipment. Use the Cold Start Procedure given in chapter 2 to start up the UPS. Replace the lift off perforated cover removed earlier from the front of the UPS cabinet in step 1 above.

5.

6. 7.

7 7 If the attached system employs a 9 way D type connector, then use connections:UPS System 2 3 3 2 7 5 The serial communication employs propriety protocol.

Recommended Right-angle DB25 cable connectors

Figure 4-4 The communications option assembly (cables and connectors not included)

4-4

Issue 3 (01/03/98)

IOM Manual
4.3.2 SNMP Interface 4.3.3

Chapter 4 - Options and Features


Interface Software

An SNMP interface is available to allow the UPS to be used with network systems. The AP4300 Ethernet SNMP option is equipped with two 25 way female D type connectors, one RJ12 connector and one RJ45 connector. The RJ12 connector, labelled SETUP, provides a serial (RS232) interface to the SNMP board and is used to set up the SNMP board parameters. The RJ45 connector, labelled NETWORK, provides a twisted pair interface to the network. The DB25 connectors are labelled COMM'S and RELAY, the action of the relays in the RELAY connector duplicates the action of the relays in the COMM'S connector, the COMM'S connector also contains all the relevant interface signals, as described below. Relay Section The relay section provides volt free contact closures which are necessary for connection to AS400 minicomputers and/or connection to Novell networks. To fulfil all the necessary requirements four relays are used, each having a double pole change-over contact. These relays will convey information on: ON UPS (AS400 Interface) ON BATTERY (AS400 and NOVELL interface) LOW BATTERY (AS400 and NOVELL interface) ON BYPASS (AS400 Interface) Control/Monitoring signal section The direct action signals are used by the UPS to signal change of state and by the attached system to control the UPS. The signal functions are: POWER FAIL (from UPS, active high) LOW BATTERY (from UPS, active high) SHUTDOWN (ACTIVE HIGH) (to UPS) SHUTDOWN (ACTIVE LOW) (to UPS) ON/OFF (to UPS, high/low) The signal excursions will conform to the RS232D standard, i.e. a high is a voltage level between +3 and +15 volts and a low is a voltage level between -3 and -15 volts.

Both SiteNet 1 and SiteNet 2 are available for all major operating platforms. Please contact your dealer for further information. SiteNet 1 - (Shutdown Management) SiteNet 1 prevents unexpected server shutdowns by automatically monitoring UPS activity and closing down protected devices if the input power supply remains off or the battery back-up becomes low. Connection is via a proprietary cable that runs between the UPS and serial port on the server. When the input supply fails SiteNet 1 notifies the users that the protected equipment is running on battery power, providing an on-screen count down of the time remaining. If the input power supply returns the shutdown sequence ends and the users are notified. SiteNet 1 can be programmed to dial out on a modem and notify upon defined events such as input power failure. SiteNet 1 also offers real time monitoring of power events so you can monitor and analyse recent and past power history. SiteNet 2 -Power Surveillance and shutdown SiteNet 2 provides ongoing monitoring and control, via a two way graphical interface, between network servers and the systems UPS. Under normal conditions. SiteNet 2 provides real-time monitoring of power flow and critical power data such as voltage and battery temperature. The UPS status can be displayed in three different formats: system animation, power flow and metering. The Event Manager allows you to customise the monitoring events and pre-program responses to power problems. SiteNet 2 can, for example be programmed to broadcast multiple user alerts, and provide a countdown timer so users can complete back-ups and disconnect from the server before the automatic shutdown occurs. The software can also dial a pager to alert network administrators, shut down the server, and log events. All this can be accomplished from a single location. This capability includes scheduled on/off control, the initiation of diagnostic routines, or down loading power event history for analysis. These routines can be performed with a user command, or executed automatically according to a pre-set schedule. SiteNet SNMP Manager SiteNet SNMP Manager is a snap-in application for your network management software. SNMP Manager seamlessly incorporates the Liebert UPS with your existing network management system to provide user friendly screens to monitor and control power. SiteNet SNMP Manager gives you everything you need to oversee network power with ease and precision.

Issue 3 (01/03/98)

4-5

Chapter 4 - Options and Features


4.3.4 Remote Alarm Monitor The Remote Alarm Monitor (RAM) offers the following features: 1. Up to eight alarm/status indications 2. Each indicator can be selected to be red, amber or green. 3. Each indication can be accompanied by an audible warning. 4. Each indication can be electronically latched (indication remains even if the condition changes). 5. Audio alarm silence push button both local and remote. 6. Alarm indication test/reset push button both local and remote. 7. Ability to change alarm legend and company logo labels. 8. Operates from 220V - 240V a.c. 9. Battery back-up option. The unit normally includes individual alarms for: UPS ON UPS ON BATTERY LOW BATTERY UPS ON BYPASS UPS ALARM CONDITION. Plus 3 Spare ALARM positions The system is provided in an enclosure for wall mounting and comes complete with installation instructions.
mm

AP4300

150

UP AC LO

SO

IL FA TT BA

Y ER S

200mm

B ON

AS YP E E E

AR SP AR SP AR SP A SP

Weight 1.2 kg
M AR E ALENC SIL

RE

MP ET LA ES T/R ES

75m

Figure 4-5 Remote Alarm Monitor

4-6

Issue 3 (01/03/98)

IOM Manual
4.4 Extended Battery Options

Chapter 4 - Options and Features


RFI ( EMC ) CONSIDERATIONS To reduce the risk of radio frequency interference to other parts of the installation external batteries and associated wiring should be shielded. The shielding for the battery can be either a steel cabinet or a rack cladded with steel panels wherever practical. Whichever is used, all panels should be bonded together and to earth for safety. In addition to the safety earth a separate earth conductor from the battery enclosure to the UPS should be fitted to provide the lowest impedance path possible to RFI noise. Wiring should be shielded by conduit , trunking or the cabling used must be screened. Where these recommendations are not implemented a minimum radius of 10 metres to any sensitive electronic equipment is recommended. Safety Labelling Warning labels should be fixed to the UPS to warn of an external battery, unless by its placement it is obvious to the personnel working on the UPS where isolation is available. The external battery enclosure must have a label on the outside to warn the Fire Authorities that lead-acid batteries are contained within and also advise the voltage level inside the enclosure. VENTILATION Adequate ventilation of battery enclosures must be provided to disperse any build up of gases vented by the battery. Weight Ensure that the battery installation weight does not exceed loading capacity of the floor.

The Extended Battery option is a separate cabinet containing further batteries that can be connected to the UPS to increase its total battery capacity and therefore the system autonomy time. 4.4.1 Extended Battery The battery cabinet for this option is of the same height and depth as the UPS, and is attached to the left hand side of the UPS. Up to 4 battery cabinets can be connected to the AP4310 UPS and upto 8 battery cabinets to the AP4320 UPS. The extra batteries can increase the autonomy time by up to approximately 1 hour. The battery cabinet can contain either one 11Ah set of batteries or two 11Ah sets of batteries

Weights (kg)
Empty Battery Cabinet Cabinet with one 11Ah set Cabinet with two 11Ahr sets 70 200 330

Dimensions (mm)
Width Height Depth 4.4.2 Remote Battery 386 1100 663

This option is similar to the extended battery option, but in this case the additional battery capacity is much larger, taking the autonomy time up to approximately 8 hours. Due to the size of the additional batteries they are housed in a much larger cabinet (or on a special battery rack) which is located away from the UPS. Due to the numerous battery configurations available for this option it is not possible to cover every installation possibility in this manual, please consult your dealer for advice. The following points should be taken into consideration when planning your installation. Battery Isolation And Protection External batteries must be fused in both positive and negative lines as close to the battery terminals as practical. Fuses shall have a voltage rating suitable for operation at 440V, the d.c. level of the battery. A suitable off load isolator must be fitted at the battery end to allow isolation by the service engineer . Where fuses can be safely withdrawn, they may act as the means of isolation. Fused isolators or circuit breakers may also be used. The cable rating between the battery and UPS shall be sized to give a maximum volt drop of 2V at currents stated in table below, irrespective of the battery autonomy time for the application.

Model Max. battery current

7,5kVA 10kVA 15kVA 19A 25A 37,5

20kVA 50A

Issue 3 (01/03/98)

4-7

Chapter 4 - Options and Features


4.5
4.5.1

AP4300
4.5.3 Filter &Transformer

Power Options
Input Harmonic Filter

Specification Inrush current

Introduction The optional input harmonic filter can be added to the UPS to improve the UPS power factor and reduce the amount of electrical noise reflected back into the input three phase supply. The filter which is free standing and clipped onto the left hand side of the UPS is contained in a cabinet whose styling, colour and size matches that of the 4300 UPS. The cabinet is designed such that it can contain either the Input Filter or the Isolation Transformer or both the filter and transformer. Specification Input voltage range: Frequency : Supply Impedance : (including cables) Supply voltage distortion : Input power factor : Input current harmonics Filter protection 4.5.2

400V + 20% -15% 3ph. 3 wire and earth. 50Hz. or 60Hz. 10%. 5% (at UPS rated load).

Operating Ambient : Temperature Storage & Transportation : Relative Humidity : Max. operating altitude above sea-level : without derating Ventilation :

Will not exceed 10 times the nominal full load peak current for 10ms. 0 to +40oC Continuously rated. -25oC to +70oC. 95% non - condensing.

1000m. 1% load derating for each 100m above 1000m up to 3000m. Natural air cooling cabinet requires 150mm free space at the rear of unit.

Dimensions:

Option
<1,5% (at zero load). 0,98 (at rated load) 0.8 (at zero UPS load). <10% Thd (at rated load and with the input supply stated above). 3 phase circuit breaker in the trap. Filter Transformer

Width (mm)
550 550 550

Depth (mm)
650 650 650

Height (mm)
1100 1100 1100

Weight (kg)
70 255 320

: :

Both

Isolation Transformer

Introduction The Isolation transformer is designed for use on electrical systems of the IT (Impdance Terre) type. The Isolation transformer is double wound with a ratio of 1:1. The output winding is star connected to re-establish ground. Connection DY11. Specification Input voltage range: Frequency : Output regulation : Neutral current Crest factor : :

4.5.4 External Bypass Enclosure The Bypass cabinet allows the user to completely remove the UPS from the system, whilst still maintaining power supplies to the load equipment. The Change-over switch is a make before break type and can be key operated. (i.e. A key fitted in the UPS Main Switch S1 can not be removed until the switch is selected to internal Maintenance bypass. Once removed the key can be inserted into the change-over switch to allow operation.)

400V 20% 3ph. 3 wire and earth. 50Hz. or 60Hz. 10%. <2% zero to full load under all conditions. 200% of full line current. 3 : 1 (Maximum) .

External Bypass System Enclosure Input isolator Change-over switch Output to Load

UPS disconnect Sockets Internal Bypass Line Static Switch

UPS Main Switch S1 Figure 4-6 Simple line diagram of External Bypass System

4-8

Issue 3 (01/03/98)

IOM Manual
4.5.5 Distribution Cabinet 4.5.6

Chapter 4 - Options and Features


Frequency Changer

The Distribution Cabinet permits several loads to be connected by means of output sockets on the rear of the cabinet. The Distribution Cabinet is fitted on the left hand side of the UPS cabinet and is available in either a no Break neutral or Break neutral configuration. The basic cabinet (A and D Series) contains an input cable, main circuit breaker, pre-drilled cable landing plate for bottom cable exit, and a 16 pole panel board without output circuit breakers. (the user to fit own circuit breakers and to directly connect the output cables as required). In addition to the above, the C & F series cabinet contains two 16A three phase, neutral and ground and six 16A single phase, neutral and ground CEE17 type industrial output sockets. Each output is protected with circuit breakers which are accessed through a panel on the left hand side of the cabinet. Where required cabinets can be supplied with various combinations of the above configurations.

The AP4300 can be used as a frequency changer. The standard 50Hz. unit can be converted to allow 60Hz. input and give 50Hz. output. The 60Hz. unit can be converted to allow 50Hz. input and give 60 Hz. output. The following instructions are for converting the AP4300 into a frequency changer. Warning THIS WORK MUST ONLY BE CARRIED OUT BY A LIEBERT AUTHORISED SERVICE ENGINEER. HIGH VOLTAGES ARE PRESENT WITHIN THIS UNIT, ENSURE THAT THE APPROPRIATE PRECAUTIONS AS DETAILED IN YOUR MANUAL HAVE BEEN TAKEN BEFORE ANY COVERS ARE REMOVED.

For conversion to 50Hz. INPUT and 60Hz. OUTPUT use For conversion to 60Hz. INPUT and 50Hz. OUTPUT use
standard 50Hz. Unit. Installation Instructions 1. Gain access to the UPS Microcontoller Board following the instructions contained in the AP4300 Service Manual. standard 60Hz. Unit.

Distribution Cabinet

0034PA SMRALA O yy:mm:dd SPU N LAMRON m:hh ss:m

0034PA

2. Refer to figure 4-8 and ensure the link between pins 3 and 4 of LK6 is fitted. 3. Ensure that the correct firmware processor is fitted for the output frequency required. 50 Hz. Output = Part number 02117670. 60 Hz. Output = Part number 02117671. 4. Remove the common bypass links from the main input terminal block. Remove links as follows: Link between U1 and U2; V1 and V2; W1 and W2.

Circuit Breaker Access

AP4320 UPS

Note: Do not remove the Neutral links. When connecting the UPS to the input power supply, ensure connections are made to the input terminals U1, V1 and W1. 5. Refit the Display Panel.

Figure 4-7 Distribution cabinet fitted to an AP4320

6. Start the UPS normally as instructed in your IOM manual. 7. Refit the front cover. The UPS should now be operating as a frequency changer.The bypass facility is no longer available.

Issue 3 (01/03/98)

4-9

Chapter 4 - Options and Features

AP4300

Microcontroller firmware

Figure 4-8 AP4300 Micro controller board

4-10

Issue 3 (01/03/98)

Chapter 5 - Troubleshooting

5.1

Introduction
Table 5.1 - Alarm sound identification
Alarm Type 1 2 3 4 5.2.2 Description of Sound Priority

WARNING UNDER FAILURE CONDITIONS, THE UPS WILL AUTOMATICALLY TRANSFER TO THE INTERNAL BYPASS SYSTEM. POWER SUPPLIES TO THE LOAD WILL BE MAINTAINED EVEN WHEN THE UPS IS INDICATING OUTPUT OFF. THE UPS STATUS ON THE CONTROL & DISPLAY PANEL REFERS TO THE OUTPUT OF THE STATIC INVERTER RATHER THAN THE COMPLETE UPS. ALWAYS CHECK FOR A VOLTAGE AT THE OUTPUT TERMINALS BEFORE ATTEMPTING TO SERVICE THE UPS OR THE LOAD. Problems indicated on the UPS can be divided into two groups: 1. External faults: i.e. abnormalities in the conditions in which the UPS operates, and which the user can usually resolve: e.g. input power supply failure, ambient temperature too high. 2. Internal Faults: i.e. defects which develop within the UPS itself, and which need specialist attention. The highly integrated design of the AP4300 UPS prevents the user from curing internal faults. As soon as any abnormal conditions or faults are detected, the UPS automatically takes action, if necessary, to protect the load and/or the UPS itself; at the same time it triggers alarm signals on the operator display panel. The horn sounds and/or LEDs switch to indicate the nature and urgency of the alarm. Text messages indicate the nature of the fault on the default screen when this is displayed on the LCD Display Panel. Charts at the end of this chapter enable the user to interpret these messages, and so identify which problems can be resolved by the user and which require attention from a UPS specialist. The UPS microcontroller board contains a battery-backed memory which keeps a record ( Event History) of previous alarms. This is for service personnel to use when establishing the original cause of a fault. WARNING SOME OF THE INSTRUCTIONS CONTAINED IN THE CHARTS AT THE END OF THIS CHAPTER INVOLVE CHECKING INTERNAL FUSES. THIS SHOULD BE UNDERTAKEN (AFTER THE EQUIPMENT HAS BEEN SHUT DOWN) BY COMPETENT PERSONNEL ONLY WHO ARE FAMILIAR WITH THE LAY-OUT AND OPERATION OF THE EQUIPMENT AND FULLY CONVERSANT WITH THE AREAS OF POTENTIAL HAZARD.

Rising Pitch for 0.5s, at 1s intervals Red Alert Two tones (high-low) for 0.25s each, at 1s Urgent intervals Single tone for 0.5s, at 1s intervals Problem Single tone for 0.5s, at 10s intervals Low LED Indications

The meanings, and the colour of each of the LEDs on the operator panel shown in fig.5-1 are summarised in the table below. If the UPS input power supply is available (and within specification) and the UPS is operating normally, only green LEDs should be lit, as described in Chapter 1 - General Description. LED1 (input supply available) and LED3 (load on inverter) indicate correct operation on the module mimic; the number of green LEDs lit on the autonomy bar indicates the state of charge of the battery; and the number of green LEDs illuminated on the percentage load bar depends on the load on the most heavily loaded phase. After the detection of an alarm condition, LEDs switch on or off, or flash on/off, according to the nature of the fault as shown in the table below.

Meaning of the Operator Panel Indicator LEDs (refer to fig.5-1) Key


1 2 3 4 5 6 7

LED
Input Supply Static Switch Inverter Battery Status Overload Indicator Charger Fault Alarm

Colour Normal State


Green Amber Green Amber Amber Amber Red on off on off off off off

Indication when ON
Input Power supply present. Load is on bypass. Load is on UPS. Battery is discharging, UPS on battery. Output has exceeded 100% of full load. Charger is faulty (LED flashes). A condition requiring urgent attention has developed (LED flashes). State of charge of battery; this LED will be on while battery capacity is above 10%. It flashes when capacity falls below 10%.

5.2
5.2.1

Alarm indications
Audible Alarm Horn

The horn will make one of five different sounds, according to the urgency of the alarm. The pattern of the audible signals is described in table 5- below. All follow the same basic pattern; i.e. an on period of 0.5secs at intervals of either 1s or 10s, depending on the urgency of the alarm. The audible warning can be cancelled immediately by pressing the horn cancel button (except when the UPS is running On Battery - see Section 2.6.2 - Input Supply Failure On Load). The LED continues to indicate until the fault clears.

Low Battery Indicator

Green

on

Issue 3 (01/03/98)

5-1

Chapter 5 - Troubleshooting
5.2.3 Messages in the LCD Text Window When the UPS is operating normally the message shown on the display panel in fig.5-1, appears in the Default Screen. The top line gives the UPS model n; the third line displays the UPS operational status; and the fourth line normally shows the date and time. The action taken will be one of the following: General fault Emergency transfer to inverter Fatal error Tests aborted

AP4300

Emergency transfer to bypass Emergency shutdown

The ERROR PAGE, is a screen which permits a service engineer to analyse the internal state of the UPS, and to identify the active alarm. Follow the procedure given in Chapter 6 - Maintenance for displaying the Information Screen: ERROR PAGE UPS STATUS EVENT HISTORY

AP4300 UPS NORMAL NO ALARMS dd-mm-yy hh:mm:ss

ESC

Select the Error Page. The nature of the information on each of the lower three lines is summarised below: line 2: line 3: line 4: UPS Status Action taken by the UPS (error message) Reason/fault description.

Figure 5-1 Position of the LEDs on the operator panel that indicate alarms or provide status information. When an alarm is triggered, status messages and/or an error message will be shown on the default screen. If this screen is not on the display when an alarm is indicated, press ESC repeatedly to show the Default Screen. Status messages: Status messages are shown on the third line of the screen, as indicated above. When an operator action, an environmental change, or a UPS problem changes the state of the UPS, the new status is indicated by a message on this line as shown in the example below: AP4310 UPS ON BYPASS 14-02-95 14:35:00 If UP or DOWN pushbutton symbols, or both: appear between the time and date, as shown above, then there are two or more status messages. Use the UP/DOWN pushbuttons to scroll through these messages. Refer to para 5.3 Troubleshooting Procedure for help. The Error Message: If the UPS takes action in response to a fault developing, then the top line on the default screen changes to display an error message, which shows what action has been taken by the UPS (e.g. emergency shutdown). The second line of the screen tells the operator to select the error page for more information. The third line continues to display status messages; e.g.:EMERG SHUTDOWN NN REFER TO ERROR PAGE UPS OUTPUT OFF DD-MM-YY HH:MM:SS

Refer to para 5.3 Troubleshooting Procedure for help with the action to take according to the reason/fault description on line 4. When there are no problems, the error page appears as shown below: ERROR PAGE NORMAL NO REPORT NO MESSAGES Event History: The event history screen is accessed from the information screen (see Chapter 6 - Maintenance). It permits details of the circumstances of previous fault (i.e. conditions which generate an error message) to be obtained. Up to 100 events can be stored. The format of the information obtained is shown below: DD-MM-YY HH:MM:SS #XX STATE NORMAL BAT TEMP SENS FAULT In each case, if UP/DOWN pushbutton symbols: appear between the time and date, as shown above, then there are two or more events recorded. Use the UP/DOWN pushbuttons to scroll through them; XX denotes the number of the event, in the chronological sequence of the events, on the display. The UPS status is indicated in text on line 3. The reason/fault for the UPS action (i.e. the error message) is presented as text on line 4.

5-2

Issue 3 (01/03/98)

IOM Manual
Notes: 1. The Tests aborted error message appears only if an alarm condition is detected during the start-up test. The instruction line then shows to which position switch SW1 must be turned: TESTS ABORTED NN TURN SW1 TO MAINT ON MAINTENANCE B/P DD-MM-YY HH:MM:SS 2. If a fault occurred during start-up, or communications between the microcontroller and the UPS have failed during normal operation the following alarm message appears on the display: AP4300 INT FAILURE FFNN CALL FOR SERVICE 44-1793 553355 The user cannot correct this fault and the UPS supplier must be called. Whether or not the 'phone no. to call and other details are displayed during start-up depends on how far initialisation had progressed before the fault was detected. If a communications fault triggered the alarm then the LCD display may freeze, since communications may be inoperative, but the UPS will continue to operate.

Chapter 5 - Troubleshooting
5.3
5.3.1

Troubleshooting Procedure
Fault Records

When a UPS fault occurs, first observe and record the UPS Status parameter values, i.e. the present values of the UPS bypass & output voltage and current and other electrical parameters. Refer to Chapter 6 - Maintenance for details of the procedure. Details of any loads being started or shed at the time that the fault occurred should also be recorded. 5.3.2 Alarm Interpretation and Corrective action The right hand column of the charts on the next five pages shows how the messages that appear on the default screen should be interpreted, and also provides information on what action to take. Status messages are listed in alphabetical order in Table 5.2 Interpretation of Status Messages; if several status messages are active and you are unable to identify the reason, then seek immediate assistance. Interpretations of Error Messages are given in Tables 5.3 & 5.4-; if you are unsure as to how to undertake the actions detailed, or, as in most cases, you are advised to seek qualified assistance, contact the site engineer, or the UPS supplier for further advice. WARNING UNDER NO CIRCUMSTANCES SHOULD YOU REMOVE THE UPS COVER PANELS OTHER THAN THE FRONT LIFT-OFF COVER. THIS EQUIPMENT CONTAINS POTENTIALLY LETHAL VOLTAGES EVEN WHEN IT IS DISCONNECTED FROM THE INPUT SUPPLY. Caution If a problem cannot be resolved by taking the actions given, then fully trained assistance should be sought immediately. Do not under any circumstances make internal circuit adjustments or interfere with the circuit boards in any way. WARNING IF THE NOMINAL SET INPUT SUPPLY VOLTAGE EXCEEDS 120% THE UPS WILL SHUT DOWN OPERATION. DO NOT SWITCH TO MAINTENANCE BYPASS OR YOU MAY CAUSE CONNECTED EQUIPMENT TO BE DAMAGED.

Issue 3 (01/03/98)

5-3

Chapter 5 - Troubleshooting
5.4 Troubleshooting Charts

AP4300

WARNING THE ACTIONS DESCRIBED SHOULD BE CARRIED OUT BY COMPETENT PERSONNEL. REMEMBER THAT THE UPS EQUIPMENT CONTAINS POTENTIALLY LETHAL VOLTAGES EVEN WHEN DISCONNECTED FROM ITS INPUT POWER SUPPLY. DO NOT UNDERTAKE ANY ACTION NOT DESCRIBED

Table 5.2 - Interpretation of Status Messages Status Message


AMBIENT TOO HOT

Interpretation & Actions


Ambient temperature has exceeded its preset limit. This is a warning that the ambient temperature is getting too high. If it continues to rise the UPS will transfer to bypass, if available, and shut down if not. 1. Check that UPS room ventilation system is operating correctly. 2. Check there is no obstruction of the inlet and outlet grills of the UPS and that there is sufficient clearance around the unit. 3. Seek qualified assistance if no cause can be identified.

BATTERY CHARGE FAULT There is a problem with the battery charger. The batteries may be charging at the wrong voltage, and possibly not at all. On battery operation after an input supply failure is still possible, but the batteries will not be recharged when the input supply returns. Autonomy time will therefore not return to normal. Seek qualified assistance. BATTERY ON TEST BATTERY TOO HOT A battery test, initiated at the UPS control panel, is in progress. Battery temp is above recommended maximum for correct operation. Whilst in this state, the battery charger will not operate. Check battery ventilation system is operating correctly. The battery voltage is greater than the set limit, probably because a faulty battery was fitted when a battery string was replaced. Check the voltages on each tray/battery block and replace any found defective.

BATTERY VOLTS HIGH

BATTERY VOLTS TOO LOW This alarm will usually appear when the UPS is operating on batteries under an input supply failure condition. It warns that the end of battery autonomy time is near (i.e. is less than 10% of nominal). NB: At the end of the autonomy time the load will transfer to the bypass supply if available; i.e. with a split bypass system, in which case LED2 will be off. If the bypass supply is not available (e.g. with a common bypass system) LED2 will be flashing. Shut down your load in a controlled manner because power to the load will soon be lost. CONVERTER HEATSINK TOO HOT The temperature of the converter heat sink has risen above its warning value. If the temperature continues to rise, the UPS will transfer to bypass, if available and shut down if not. 1. Ensure unrestricted airflow around the unit - e.g. no blocked ventilation grills. 2. Check fan operation. 3. Check for AMBIENT OVERHEAT alarm indication and reduce ambient temperature if necessary. 4. Reduce the UPS load if excessive. 5. If (1) to (4) are satisfactory seek qualified assistance. May appear when servicing the UPS. For use only by service engineers. The inverter has developed a fault and transferred the load to bypass. 1. Observe any other alarms (e.g. excessive load or overtemperature) and take necessary actions. 2. Seek qualified assistance if no problems are found. A fault has occurred while the load was on bypass which transferred the load to the inverter. 1. Observe any other alarms and take necessary actions. 2. Seek qualified assistance. Battery voltage has fallen below an acceptable minimum value. The alarm usually appears when the UPS has been operating on batteries under a input power failure condition and indicates that the battery autonomy time has ended. The load will have transferred to the bypass supply (if available - i.e. a split bypass system). Otherwise, (common bypass system) the UPS will have shut down and power to the load will have been lost. Alternatively, it may be because of a battery fuse failure or a charger fault. 1. Check battery fuses FS1 and FS2 - refer to paragraph 5.5. 2. If fuses have failed, or there is a charger fault, seek qualified assistance.

DIAGNOSTIC LINK ON EMERGENCY TRANSFER TO BYPASS EMERGENCY TRANSFER TO INVERTER END OF DISCHARGE

INVERTER HEATSINK TOO The temperature of the inverter heat sink has risen above its warning value. If the temperature HOT continues to rise, the UPS will transfer to bypass, if available and shut down if not. Carry out the checks given above for converter heatsink too hot (table 5.2).

5-4

Issue 3 (01/03/98)

IOM Manual

Chapter 5 - Troubleshooting
Table 5.2 - Interpretation of Status Messages - contd.

Status Message
LOCALLY STOPPED

Interpretation & Actions


SW2 on the back of the UPS has been pressed and consequently the UPS output has been switched off. Switch the output on when required, if it is safe to do so; follow the operating instructions in chapter 2. The load is too large for the UPS to supply for an indefinite period. The time for which the UPS can support the overload will depend on the magnitude of the overload - the greater the overload, the shorter the time interval. If this time is exceeded, a transfer to bypass will be performed if the bypass is available. If it is not, the unit will shut down. Refer to the Output Overload Ability information given under Output Data in the AP4300 Series Specification at the end of this manual. 1. Check for an overload and shed any excess load. 2. If load is not indicated as being excessive, or the indications persist, seek qualified assistance. The output voltage has become too high due to an inverter fault, and has exceeded the permitted level. The load will transfer to bypass if the condition persists. Seek assistance if condition persists. A short circuit fault exists on one or more of the output lines. 1. Correct the short circuit. 2. If no short circuit is found on the output lines, seek qualified assistance. The phase sequence of the supply on the power cables connected to the bypass line is incorrect. This fault should only appear either when first starting up after installation, or after repairs to the bypass power source when phases have been reconnected incorrectly after a cable break. Disconnect power from the bypass line and correct the wiring. Your local service agent's representative must be present when first starting up your UPS system. Either missing or low input power supply and battery discharged. Check the input supply voltage and if this is found to be correct then seek qualified assistance. The remote STOP button (option) has been pressed and consequently the UPS output has been switched off: 1. Determine if remote stop has really been operated. 2. Check continuity of remote stop line. Battery is discharging -e.g. because the input power supply is absent and the battery has taken over. The five autonomy LEDs switch off progressively from the right as the time remaining before battery shutdown reduces. 1. Check that the input supply is present. 2. Check the UPS input circuit breakers (CB4, CB5 & CB6) - refer to paragraph 5.5. 3. If (1) and (2) are satisfactory then seek assistance. The load has been transferred to the bypass supply due to a fault or status malfunction: Note: The UPS will periodically transfer to bypass to check the integrity of the static bypass circuitry. It should remain in this state for a maximum of 6 seconds after which a re-transfer to inverter will take place. Observe other indications (e.g. excessive load or overtemperature) and take appropriate actions. The UPS is active but its output has been switched OFF using one of the methods described in chapter 2. 1. Check if the UPS output has been turned OFF - e.g. from a remote location. If it has, find out the reason and then turn it on when it is safe to do so. Refer to the operating instructions in chapter 2. If the output does not switch on, turn SW1 back to MAINT and restart the UPS. Refer to the operating instructions in chapter 2. 2. If the above actions do not overcome the problem, seek qualified assistance. Temperature of one or more of the UPS internal sensors has reached its fail level. The UPS will transfer to bypass immediately, if the bypass supply is available. 1. Check if there are any other status messages indicating excessive temperature by scrolling through them on the default screen. 2. Carry out the checks given above for converter heatsink too hot (table 5.2).

OUTPUT OVERLOAD

OUTPUT HIGH FAIL

OUTPUT SHORT CIRCUIT

PHASE ROTATION ERROR

PRIMARY DC BUS LOW WARNING REMOTELY STOPPED

UPS ON BATTERY

UPS ON BYPASS

UPS OUTPUT OFF

UPS OVERTEMPERATURE

Issue 3 (01/03/98)

5-5

Chapter 5 - Troubleshooting
Table 5.3 - Interpretation of Error Messages Status Message
BYPASS SCR SHORT CCT

AP4300

Interpretation & Actions


Internal power component problem. 1. Transfer the load to the maintenance bypass following the appropriate operating instructions. 2. Seek qualified assistance immediately. Internal power component problem. 1. Leave the UPS running. Do not operate SW1 or SW2 under any circumstances as this will power down the load. 2. Seek qualified assistance immediately. The input supply is low and the battery is not supporting the primary DC Bus, so the voltage on the primary DC Bus has fallen below its fail level. 1. Check the state of the input, the input circuit breakers and battery fuses refer to paragraph 5.5. 2. If these are OK then seek qualified assistance. Also see status message [UPS ON BATTERY] in table 5.2 for other possible messages. The input supply voltage on one or more of the INPUT terminals is too high (i.e. greater than 120%). 1. Problem could be due to genuine high input supply voltage, or surge(most likely if it corrects itself). Check if voltage is above 120% of nominal on the input supply. 2. If this alarm occurs during initial start-up check that the voltage is correctly set for the local working voltage. (see installation instructions). 3. If neither of the above then seek qualified assistance. Note warning on page 5-4. While on bypass for whatever reason, the UPS has detected that the bypass volts on one or more of the phases has fallen below its fail level. The UPS will have performed an emergency transfer to inverter, if available, or shut down if not. 1. Could be due to genuine low voltage on the bypass supply 2. Check if the bypass circuit breakers: CB1, CB2 & CB3 have tripped open, - refer to paragraph 5.5. 3. If neither of the above then seek qualified assistance. While on bypass for whatever reason, the UPS has detected that the bypass volts on one or more of the phases has risen above its fail level. The UPS will have performed an emergency transfer to inverter, if available, or shut down if not. Could be due to genuine high bypass. Check if voltage is above 120% of nominal on the bypass supply. If it is not, seek assistance.. Refer to this message in table 5.2. Refer to this message in table 5.2. Output voltage has fallen below the allowed minimum on one or more phases. Either an internal voltage regulation problem exists or there has been a sudden increase in load. Load will transfer to bypass if condition persists. Seek assistance if the load is not excessive and cannot be transferred back to the inverter. Refer to the message OUTPUT SHORT CIRCUIT in table 5.2. Load current on one or more output phases has exceeded the permitted level for too long. The UPS has transferred the load to the bypass. 1. Shed excess load 2.If load is not indicated as being excessive seek qualified assistance. Automatic tests (SW1 in TEST position) cannot proceed due to one or more of the bypass phases being absent. 1. Check bypass supply voltage and circuit breakers. 2. Seek assistance if all three phases are present. Battery has reached end of discharge, following a input supply failure. UPS will have shutdown, (in a common bypass system), or transferred to bypass (split bypass system). An attempt has been made to start the UPS with the rotary switch SW1 set at UPS without autorestart enabled. The UPS has detected DC on the output of one or more phases. The UPS will have transferred the load to the bypass. Seek qualified assistance. Refer to BYPASS SCR OPEN CCT above. Refer to UPS OVERTEMPERATURE in table 5.2. One of the input phases is not supplying power, probably because a fuse has failed in the supply. Check that all input supply fuses are OK, all input circuit breakers are closed and connections to all input terminals are tight.

BYPASS SCR OPEN CCT

INPUT LOW FAIL

INPUT HIGH FAIL

BYPASS LO FAIL

BYPASS HI FAIL

PHASE ROT. ERROR OUTPUT HI FAIL OUTPUT LO FAIL

OUTPUT SHORT CIRCUIT O'LOAD TIMEOUT

WAITING FOR BYPASS

END OF DISCHARGE SW1 IN WRONG POS. DC OFFSET TIMEOUT

BP SCR OPEN CCT (2) * * * * HI TEMP FAIL EOD (IP MISSING)

5-6

Issue 3 (01/03/98)

IOM Manual

Chapter 5 - Troubleshooting

Table 5.4 - Interpretation of Error Messages

Error Message
AMB TEMP SENS FAULT BATTERY CHRG. FAULT BATTERY NOT CHARGING BAT TEMP SENS FAULT COMMS FAILURE (CAN) COMMS FAILURE (422) CONTROL PWR OFF FAIL CONV. FEEDBACK ERROR CONVERTER NOT OK CONV TEMP SENS FAULT DC2 MIDPOINT HI FAIL EMERG BYPASS FIRING INTERFACE RESET INV TEMP SENS FAULT MAG TEMP SENS FAULT NO OUTPUT VOLTS NVRAM RELOADED OUTPUT SHORT CCT. SEC. DC BUS HIGH FAIL SEC. DC BUS LOW FAIL SETUP DATA ERROR SETUP DATA RELOADED TOO MANY CONV. RST. VCE SAT FAIL

Interpretation & Actions

SELECT SWITCH 1 TO THE MAINTENANCE BYPASS POSITION AND SEEK QUALIFIED ASSISTANCE FOR ALL THESE ERROR MESSAGES

Issue 3 (01/03/98)

5-7

Chapter 5 - Troubleshooting
5.5 Checking the input and bypass circuit breakers, and battery fuses

AP4300

5.5.2 Circuit breaker check The switch levers of any circuit breakers which have tripped open due to an excessive current passing through them will be in the A number of alarms may be triggered by a circuit breaker opening or down position. a fuse failure; e.g: Battery volts too low, UPS on battery & Bypass Before closing any tripped circuit breakers, ensure that it is safe IP volts low. to do so. Circuit breakers and fuses are accessible after removing the lift-off right hand front panel. The positions of the fused switches (FS1-FS2) which carry the battery fuses and the circuit breakers for the bypass supply (CB1-CB3) and the input power supply (CB4-CB6), are shown in fig.5-2. MAINT TEST
AP4300 UPS NORMAL NO ALARMS hh:mm:ss dd:mm:yy

AP4300

WARNING ONLY PERSONNEL WHO ARE TRAINED AND DEEMED COMPETENT SHOULD CHECK FUSES OR OPERATE CIRCUIT BREAKERS. TRANSFER THE LOAD TO THE MAINTENANCE BYPASS SUPPLY BEFORE CARRYING OUT A FUSE CONTINUITY CHECK. 5.5.1 Battery fuse check Open the fuse holders of the fuses in question and extract the fuses from the holder. Check the continuity of the fuses with a suitable meter, and replace any fuses found to be defective. Caution Ensure any defective fuses are replaced by fuses of the same TYPE and RATING (i.e. 30A) as the fuse being removed. Never increase the fuse rating.

OFF (0)
MAINT TEST O/P OFF UPS

UPS

SW1
FS1 FS2 CB1 CB2 CB3 CB4 CB5 CB6

BATTERY BYPASS FUSES

INPUT

Figure 5-2 Input and bypass circuit breaker and battery fuse holder locations

5-8

Issue 3 (01/03/98)

Chapter 6 - Maintenance

6.1
6.1.1

Routine Maintenance Checks by the Operator


Introduction

The UPS uses solid state components with the only moving parts being the cooling fans, switches and relays, so it is essentially maintenance free. However the checks in this chapter will help to maintain the reliability of the UPS module and battery. We recommend an annual service of the unit by an engineer approved by the manufacturer, preferably under a service contract. Scheduled maintenance requirements, beyond ensuring that the UPS remains cool and clean, are minimal. However, a well documented program of regular inspection will help to ensure optimum performance and also help to detect certain minor problems before they develop into a major fault. 6.1.2 Checks at weekly intervals 1. Ensure that the ventilation space around the base and the back of the UPS is not obstructed. 2. Check the function of all the LEDs and pushbuttons on the panel by carrying out a Front Panel Test. Press each pushbutton in turn for two seconds. All the LEDs should switch on and the audible alarm should sound with each pushbutton. Cancel the alarm and record the result. If the default screen is on the display when a test is made, the top line of the screen will indicate the UPS type in the following format: AP43XX NN.N ii/oo b NO ALARMS 10:15:00

5. Voltage on the primary and secondary DC bus. Ambient and battery temperatures, temperatures on the inverter & converter heatsinks (& on the converter magnetics in 20kVA units). State of the converter, charger & inverter. UPS status parameters The values of the status parameters are displayed on the LCD panel by selecting options from the windows reached via the main menu & status windows, (see the menu map in fig.6-1). If any of the values differ greatly from those previously logged, for no apparent reason, seek advice from your Distributor or Service Agent. From the default window, press ENTER to display the main menu window: STATUS COMMANDS SETUP MAINTENANCE The cursor will be aligned with STATUS. Press ENTER to select the status window. The menu of UPS status categories is displayed: OUTPUT BYPASS BATTERY INTERNAL Output parameters

Select OUTPUT by pressing ENTER to display the first of a set of six screens which can be displayed in rotation by pressing ENTER successively. Press ESC to return to the STATUS screen. These screens display, in sequence: XX = chassis type (XX=10 or 20) OUTPUT VOLTS (L-N) NN.N = UPS output rating. OUTPUT VOLTS (L-L) ii = input frequency OUTPUT LOAD (kVA) on each of the phases L1, L2, L3 oo = output frequency OUTPUT LOAD (kW) b = battery presence (i.e. +b=battery fitted; - b=battery OUTPUT CURRENT not fitted, e.g. when the UPS is used as a line INVERTER OUTPUT FREQUENCY. conditioner). The inverter output frequency screen also carries a message stating whether the UPS output and bypass supplies are 6.1.3 Checks at monthly intervals synchronised. In addition to the weekly checks, use the procedure following to check and record the present values of the UPS status parameters Bypass Return to the status window and select BYPASS to display the as listed: bypass supply voltage and frequency levels: 1. Output voltage and frequency on each phase.

UPS NORMAL 25-09-95

2. Output current & output load (kW & kVA) on each phase. Note: If the output currents differ significantly from the values previously logged then, if possible, record the size, type and location of any load connected to (or removed from) the UPS since the previous inspection. 3. Bypass supply voltage on each phase, and the frequency. 4. Battery float charge voltage and capacity.

BYPASS L1 L2 240 240 FREQUENCY (HZ)

L3 240 50.1

Issue 3 (01/03/98)

6-1

Chapter 6 - Maintenance

AP4300

TESTS ABORTED NN TURN SW1 TO MAINT ON MAINTENANCE B/P 14-02-94 14:35:00

FAULT

SWITCH ON AT MAIN ISOLATOR


INITIALISATION TESTS OK AP4300 INITIALISING PLEASE WAIT . . .

CLOSE BATTERY FUSES

UPS NORMAL NO ALARMS 14-02-94 14:35:00

TESTS PASSED TURN SW1 TO UPS ON MAINTENANCE B/P 14-02-94 14:35:00

START UP TESTS OK

AP4300 TURN SW1 TO TEST UPS OUTPUT OFF 14-02-94 14:35:00

STATUS COMMANDS SETUP MAINTENANCE

OUTPUT VOLTS L-N L2 L1 L3 240 240 240

OUTPUT VOLTS L-L L1-2 L2-3 L3-1 400 400 400

OUTPUT BYPASS BATTERY INTERNAL

OUTPUT FREQUENCY FREQUENCY(Hz) 50.0 SYNCHRONISED

OUTPUT CURRENT AMPS L1 L2 L3 1.4 1.5 1.4

OUTPUT POWER KW L1 L2 L3 0.88 089 0.88 TOTAL 2.65 KW

OUTPUT POWER KVA L1 L2 L3 0.87 0.87 0.87 TOTAL 2.61 KVA

BATTERY INFORMATION VOLTS CAP% CHARGER 420 100 ON TIME 00:41:24 DC BUS TEMPERATURES INFORMATION

BYPASS L1 L2 L3 240 240 240 FREQUENCY (HZ) 50.0 DC BUS VOLTS PRIMARY SECONDARY 400 800 TO RETURN

OUTPUT CONTROL OUTPUT OFF OUTPUT ON

CONV 40 38 INV MAG 42

BAT 23 AMB 24

ERROR PAGE (status) (UPS action) (message/fault) UPS STATUS CONVERTER ON INVERTER ON BATTERY CHARGER ON 14-02-94 14:35:00 #XX NORMAL NO REPORT NO MESSAGE

OUTPUT CONTROL TIMED OP CONTROL SHUTDOWN CONDITION BATTERY TEST

TIMED OP CONTROL DELAYED OP ON DELAYED OP OFF CANCEL OR DELAY SHUTDOWN CONDITION ON BATTERY AT ANY TIME

ERROR PAGE UPS STATUS EVENT HISTORY

BATTERY TEST TEST BATTERY LAST TEST RESULT

COMMUNICATION FAULT AT ANY TIME

SET DATE AND TIME SELECT LANGUAGE

SELECT SET ADJUST CANCEL DD-MM-YY HH:MM:SS 00 - 00 - 00 00 : 00 : 00 ENGLISH ESPANOL FRANCAIS DEUTSCH ITALIANO

SET SELECT ADJUST CANCEL ENTER PASSWORD ****

AP4310 FATAL ERROR CALL FOR SERVICE 01793 553355

Figure 6-1 Map of the displays on the LCD screen accessible by the operator

6-2

Issue 3 (01/03/98)

IOM Manual
Battery parameters Selecting BATTERY from the status window displays the battery voltage, capacity, and autonomy time at the current load, and the charger status: BATTERY INFORMATION VOLTS CAP % CHARGER 420 100 ON TIME 00:41:24 Internal parameters Select INTERNAL from the status window to display further options: DC BUS TEMPERATURES INFORMATION 6.1.4 Annual checks

Chapter 6 - Maintenance

1. Carry out the monthly checks given above. 2. Carry out a battery test as follows: From the default window, press ENTER to display the main menu window. Select COMMANDS. and press ENTER: OUTPUT CONTROL TIMED OP CONTROL SHUTDOWN CONDITION BATTERY TEST Select BATTERY TEST and press ENTER: BATTERY TEST TEST BATTERY LAST TEST RESULT

Select DC BUS to show the voltage levels on the two DC buses: DC BUS VOLTS PRIMARY SECONDARY 400 800 TO RETURN Select TEMPERATURES to display the battery (BAT) and ambient (AMB) temperatures, and the temperatures on the converter (CONV) and inverter (INV) heatsinks, and, on 20kVA units only, the converter magnetics (MAG): CONV 40 INV 38 MAG 42 BAT 23 AMB 24

The cursor points at TEST BATTERY. Press ENTER to start the battery test. If the battery is satisfactory, the word: PASS appears on the screen.

Select INFORMATION to gain access to windows from which information on the past and present state of the UPS can be obtained: ERROR PAGE UPS STATUS EVENT HISTORY

Select UPS STATUS to show the state of the three major blocks of the UPS: UPS STATUS CONVERTER ON INVERTER ON BATTERY CHARGER ON The ERROR PAGE & EVENT HISTORY windows are used when an alarm has been triggered, and enable the cause of the alarm, and the events leading up to it, to be analysed. Refer to Section 5.2.3 in Chapter 5 - Troubleshooting.

Issue 3 (01/03/98)

6-3

Chapter 6 - Maintenance
6.2 Annual Maintenance Checks by Service Engineer
Batteries

AP4300

6.2.1 Introduction These checks entail working inside the UPS, and should be undertaken only by a Liebert trained engineer who is familiar with the UPS operation and lay-out, and who is aware of the potential hazards. SAFETY PRECAUTIONS When working on the UPS remember that it will contain live voltages at ALL TIMES unless it has been isolated from the external input power supply, and the internal batteries (and external batteries, if fitted) have been disconnected. It is essential that the safety and precautionary notes contained throughout this manual are read and fully understood before touching any UPS internal component part. The service engineer would complete the following checks: UPS Carry out a thorough visual examination of the UPS power components and sub-assemblies, paying particular attention to the following: Electrolytic capacitors Check for signs of leakage, buckling etc. Magnetic components Check for signs of overheating, security of fixture and signs of cracking in ferrite components. Cables and connections Check all cables for chafing, fraying or signs of overheating. Also check that all cable connections are tight and all printed circuit board connectors are secure. Printed circuit boards Check the cleanliness and integrity of the circuit boards and replace if any signs of deterioration are found. Caution A lithium battery powered chip (part no.02101065) is carried on the interface board. If this board is replaced, either dispose of the chip in accordance with the manufacturer's instructions, or else contact your local distributor for disposal instructions. DO NOT DISPOSE OF THE CHIP THROUGH THE DOMESTIC REFUSE SERVICE.

WARNING - BATTERY HAZARDS SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT. WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 380VDC AND IS POTENTIALLY LETHAL. IT MAY BE NECESSARY TO DISCONNECT THE INTER-TRAY LINKS IN ORDER TO GAIN FULL ACCESS TO THE BATTERY TRAYS. DO THIS WITH EXTREME CAUTION. EYE PROTECTION SHOULD BE WORN TO PREVENT INJURY FROM ACCIDENTAL ELECTRICAL ARCS. IF A BATTERY LEAKS ELECTROLYTE, OR IS OTHERWISE PHYSICALLY DAMAGED, IT SHOULD BE PLACED IN A CONTAINER RESISTANT TO SULPHURIC ACID AND DISPOSED OF IN ACCORDANCE WITH LOCAL REGULATIONS. IF ELECTROLYTE COMES INTO CONTACT WITH THE SKIN, THE AFFECTED AREA SHOULD BE WASHED IMMEDIATELY. Check the batteries carefully, paying particular attention to the following: General condition Examine the battery cases for signs of deformation, cracks or general physical deterioration. Battery block voltage Check the voltage of each battery block with a meter. This should be greater than 12.6 volts d.c. Cables and connections Examine the cables for signs of deterioration and ensure that all connections are securely fastened. General If necessary, thoroughly clean inside the UPS using a vacuum cleaner. Re-assemble the UPS, and start it up following the procedures in Chapter 2 - Operating Instructions. If possible, check the battery autonomy time by turning the UPS input supply OFF while the UPS is on-load. Ensure that the UPS operates on battery correctly and check that the available battery autonomy time meets the specification. Refer to the procedure in Chapter 2 - Operating Instructions. Turn the UPS input supply ON again as soon as these checks have been made.

6-4

Issue 3 (01/03/98)

Chapter 7 - Liebert Warranty

LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the purchaser): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanship under normal use, service and maintenance FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert Dealer/Retailer. THE FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO OTHER WARRANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to consumer products acquired by individuals and used for personal, family, or household purposes (as distinguished from industrial or other purposes). Local laws may not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may have other rights which vary according to local law. Certain repairs or services are the responsibility of the purchaser and the purchaser is expected to pay for them. This warranty does not extend either to products with removed or altered serial numbers or to any losses or damages due to an act of god or source external to the product, misuse, accident, abuse, neglect, negligence, unauthorised modification, alteration, or repair, use beyond rated capacity, or improper installation, maintenance, application or use, including without limitation, use in a manner contrary to the accompanying instructions or applicable codes. The battery must be recharged every four (4) to six (6) months when not in use. The warranty will be invalidated unless the UPS has been commissioned by Liebert CS&S or an engineer who has been trained on the product in an approved Liebert Training Centre. Warranty does not apply to consumable parts such as lamps and fuses. Warranty of batteries only applies to batteries that have been sold by Liebert and installed as an integral part of the UPS system. If the UPS fails to conform with the above warranty within the stated period, Liebert will repair or replace the UPS, at Liebert's option. Replacement parts will only carry the benefit of the unexpired portion of the main equipment warranty. Purchaser to make warranty claim, should on first instance contact the Dealer/Retailer from whom the unit was purchased, supplying the model type, rating and serial number along with a fault description.

LIFE SUPPORT APPLICATIONS


Due to the diversity of applications and considerations to be applied in each case, Liebert does not recommend or knowingly sell its products for such use. The responsibilty for risk assessment and management in applications where the malfunction or failure of the UPS could be reasonably be expected to give rise to risk of human life shall be the sole responsibility of the purchaser. Liebert accepts no liability for consequential harm in such applications.

Issue 3 (01/03/98)

7-1

Chapter 7 - Liebert Warranty

AP4300

7-2

Issue 3 (01/03/98)

AP4300 Series UPS Specification

INPUT DATA
Input line voltage (nominal) Continuous input voltage Operational range Input bypass voltage line and neutral Tolerance Input kVA at maximum rated load including battery charging Power factor at rated kW load Max input power at rated kW load including battery charging Nominal input current at rated kW load, including battery charging (i.e. @ 400V supply) Max input current at rated kW load, including battery charging (i.e. @ 320V supply) Nominal Input frequency Max permissible input frequency variation for synchronised operation Conducted and radiated EMC levels Compliant safety standards Compliant immunity standards

UNITS
V ac V ac V ac kVA kW A A Hz Hz -

AP4307

AP4310

AP4315

AP4320

400V 3 Phase 320V to 480V* 400V 3 Phase (programmable to 380 or 415V) default: 10% (programmable to 15%) 8,1 0.95 7,7 11,7 14,5 9,8 15,0 18,6 50 or 60 5 EN 55022 A EN 50091-1 15,2 23,4 29,0 10,4 16 0.95 20 30 37,2 21

(
AP4307
32

EN 50082-1 IEC 801 Parts 2, 3, 4 & 5.

)
AP4320

Note 1: Unless otherwise specified all voltage and current values stated in this specification are rms. *Note2: Below 320V 2% unit will transfer to battery Above 480V 2% unit will transfer to battery

INTERMEDIATE DC CIRCUIT DATA


Number of valve regulated lead acid batteries (12V) Type of battery (recommended) Nominal battery float voltage @ 20oC End of battery discharge voltage Battery capacity (default)** Battery autonomy time (Typical) Maximum charging current Battery fuse rating (FS1 & FS2) and (FS3)

UNITS
-

AP4310

AP4315

2 x 32

Yuasa NP 11-12 (or equivalent) Vdc Vdc Ahr mins. A mean A 17 2.8 30 (Bussman KLM-30A 500Vd.c.) 11 14 17 5.6 50 (Bussman FWP-50A14F 700Vd.c.) 437 0.5% 320 1% 2 x 11 14

**Note 3: Battery Capacity Battery performance depends on the ambient battery temperature. Capacity and autonomy times are quoted for a new battery operating at 20C. Battery capacity is increased by 1% for every 1C increase in temperature up to 25C. If a battery is used at a temperature above 25C, its life is reduced; consequently its capacity and UPS autonomy time will reduce more rapidly over a period of time. Battery float voltage is compensated (by 3mV per C per cell).

Issue 3 (01/03/98)

8-1

AP4300 Series UPS Specification


OUTPUT DATA
Output voltage Nominal

AP4300
UNITS
Vac

AP4307

AP4310

AP4315

AP4320

3 Phase - 400V adjustable 361V to 436V 1 Phase - 230V adjustable 200V - 250V 1 1 2 <3,0 120 1 120

Output voltage regulation Voltage Balance (L-N, L-L) Balanced Load 100% unbalanced load Output voltage distortion with 100% linear load Phase Balance Balanced Load 100% unbalanced load Output frequency Output frequency tolerance while synchronised to input mains supply Maximum rated output kVA (balanced load) Maximum rated output power (balanced load) Nominal UPS efficiency at 100% linear load, not including battery charging Output overload ability (for kW and for kVA) (load will transfer to static bypass if times are exceeded)

% %

Hz Hz kVA kW % % 7,5 6 88 10 8 89

50 or 60 5 15 12 87 20 16 89

up to110% continuous 125% for 10 mins 150% for 60 seconds 200% for 5 seconds 45 14 20 18 28 40 90 36

Inverter output peak current limit (max. transient) Continuous Bypass rating Internal overload protection on static bypass (Type C circuit breaker)

A pk A A

MECHANICAL CHARACTERISTICS
Dimensions: Width Height Depth

UNITS
mm kg kg m /hr C m kW dBA 3

AP4307

AP4310

AP4315

AP4320

427 1100 682 122 250 RAL 7035/7038 4 fans IP22 130 0 to +40 1000 1,2 <54 1,3 2,3

657 1100 682 176 432

Weight (without batteries) Weight (with batteries) Colour Ventilation - internal fans Enclosure Airflow Operating temperature (range) Max altitude for full rating Nominal heat dissipation (fully charged battery) Acoustic noise level for rated load at 1 metre Relative Humidity

6 fans

325

2,6 58

0-90% non-condensing

This equipment is manufactured by Liebert Swindon Limited, Elgin Drive, Swindon, Wilts SN2 6DX, United Kingdom Telephone: +44 (0) 1793 553355 Fax: +44 (0) 1793 553400 a BS EN ISO9001:1994 registered company.

8-2

Issue 3 (01/03/98)

Parameter Settings for the AP4300

This table permits a record to be kept of any changes made to the software default settings during commissioning.The commissioning engineer will enter the values of any changed parameters and sign where indicated.

Parameter Max
OUTPUT VOLTS HIGH FAIL NOMINAL VOLTS LOW WARN LOW FAIL BYPASS VOLTS HIGH FAIL HIGH WARN LOW WARN LOW FAIL PRIMARY DC BUS (DC Volts) HIGH FAIL HIGH WARN LOW WARN LOW FAIL SECONDARY DC BUS (DC Volts) HIGH FAIL HIGH WARN LOW WARN LOW FAIL BATTERY VOLTAGES HIGH FAIL HIGH WARN NOM FLOAT NOMINAL LOW WARN LOW FAIL EOD VOLTS 488 468 462 427 391 330 340 840 840 760 740 705 705 400 300 276 264 216 204 264 250 216 204

Range Min Default

Setting New Setting

231 200 198 187

253 230 207 195

253 242 198 187

265 253 207 195

645 619 320 300

660 650 390 300

820 820 740 660

840 820 760 700

431 413 408 377 328 290 300

460 441 437 402 350 310 320

Issue 3 (01/03/98)

8-3

Parameter Settings for the AP4300

AP4300

Parameter Max
BATTERY CAPACITY (Ampere Hours) CAPACITY BATTERY WARNING TIME (Seconds) LOW BAT WARN TIME TEMPERATURES (Deg C) FAIL INVERTER CONVERTER BATTERY AMBIENT PHASE LOCKED LOOP (PLL) OP frequency (Hz x 10) - fixed by firmware installed FREQUENCY Capture Range (Hz x 10) CAPTURE RG Lock Range on Inverter (Hz x 10) LOCK (INV) Lock Range on Bypass (Hz x 10) LOCK (BYP) Slew Rate (Hz per sec x 10) SLEW In Phase Range (msec) IN LOCK MISCALLANEOUS DUMMY SHUTDOWN ALLOWED LAST OP STATE AUTORESTART 1 0 200 20 50 50 50 75 65 70 40 40 1800 240

Range Min Default

Setting New Setting

12

60

300

55 50 50 30 30

65 55 55 35 30

500

20

25

50

10

120

120

(not used) 0 1 0 1

Note: Parameter settings which are not normally changed are indicated by a tint in the corresponding cell in the New Setting column.

UPS MODEL....................................................................Name:......................................................................................................

SER. NO...........................................................................Signature............................................................Date..............................

8-4

Issue 3 (01/03/98)

Keeping Business in Business

TM

Series AP4300 UPS AP4300 Three Phase 7.5 to 20 kVA 50 or 60Hz.

The Company Behind The Products


With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics Environmental systems close-control air conditioning from 1.5 to 600 tons. Power conditioning and UPS with power ranges from 400 VA to more than 1000 kVA. Integrated systems that provide both environmental and power protection in a single, flexible package. Monitoring and control - on-site or remote - from systems of any size or location Service and support, through more than 100 service centres around the world and a 24 hour Customer Response Centre

+ + + + +

Liebert Corporation
Globe Park, Marlow, Buckinghamshire SL7 1YG United Kingdom Tel: +44 (0) 1628 403200 Fax: +44 (0) 1628 403203

Liebert Franais
124 Avenue Gallini, 93170 Bagnolet, France Tl: +33 (0) 1 43 60 0177 Fax: +33 (0) 1 43 60 7007

Liebert GmbH
Liebigstrae 9, D-85551 Kirchheim, B.Mnchen, Deutschland Tel: +49 (0) 89 991 9220 Fax: +49 (0) 89 904 3151

Liebert BV
Bosstraat 96, Postbus 9100, 6070 AC Swalmen, Netherland Tel: +31 (0) 475 504050 Fax: +31 (0) 475 502876

Liebert Sice
Via G Rossini 6, 20098 San Giuliano Milanese, Milano, Italia Tel: +39 (0) 2 982501 Fax: +39 (0) 9844633

Liebert Web Site


While every precaution has been taken to ensure accuracy and completeness in this manual, Liebert Corporation assumes no responsibility and disclaim all liability for damages resulting from use of this information or for any errors or omissions. 1997 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners.

http:/www.liebert.com

Вам также может понравиться