The 2000 Handbook

A C B
POWER

DATA

PYROLEX

Official Cable Supplier of the 2000 Olympic Games

SAFETY WARNING
Cables are insulated and sheathed with stable materials which may contain certain
toxic substances including lead. Insulation and sheathing materials should not be
chewed or ingested.
INSTALLATION
Cables must be installed in accordance with the requirements of Section 3
Selection and Installation of Wiring Systems in the latest issue of AS/NZS3000
or the appropriate ruling standard in the country of installation. Cables must also be
connected by a licensed electrician, as ruled in the state or country of installation.
In particular your attention is drawn to Section 1.7 of the Wiring Rules (AS/NZS3000)
Protection for Safety.
The requirements of AS/NZS3000.2000 (current edition) differ dramatically from
those in the 1991 edition of AS3000. While the intent to enforce safe design and
installation practices is the same, the new standard defines the requirements rather
than specifying solutions. Designers and installers can be assured the products
provided by Olex Cables meet the requirements of the relevant standards, but must
ensure appropriate selection of cables and components for any electrical installation.
HAZARDOUS AREAS
Installation of wiring and fittings for hazardous areas, e.g. flammable or explosive
gas, liquid, dust or solids must comply with Section 7.9 Hazardous Areas, of
AS/NZS3000, and other relevant Australian Standards for specific hazards and
occupancies.

TECHNICAL NOTE
PVC 90C THERMAL RATING
The current-carrying capacities for thermoplastic cables, including flexible cords
used as fixed wiring, insulated with V-90 and V-90HT PVC compounds have been
based on a conductor operating temperature of 75C because of the likelihood of
thermal deformation of these cable types in the temperature range 90 to 105C
(refer AS/NZS3008.1 Table 1 Note 2).
Olex Cables is a division of Australian Cables Pty Ltd. A.C.N. 087 542 863.

CONTENTS
Handbook 2000
ENVIROLEX

POWER CABLE
1 Core
1 Core
1 Core
2 & 3 Core
2 & 3 Core+Earth
2 & 3 Core+Earth
2 & 3 Core+Earth
4 Core+Earth
4 Core+Earth
2 & 3 Core+Earth
2 & 3 Core+Earth
4 Core+Earth
4 Core+Earth

PVC Insulated Copper


PVC/PVC Copper
XLPE/PVC Copper & Aluminium
PVC/PVC Flat Copper
PVC/PVC Flat Copper
PVC/PVC Circular Copper
XLPE/PVC Circular Copper
PVC/PVC Circular Copper
XLPE/PVC Circular Copper
PVC/SWA/PVC Circular Copper
XLPE/SWA/PVC Circular Copper
PVC/SWA/PVC Circular Copper
XLPE/SWA/PVC Circular Copper

5
6
7
8
9
10
11
12
13
14
15
16
17

COPPER CONTROL
Multicore+Earth
Multicore+Earth

PVC/PVC Circular
PVC/SWA/PVC Circular

18
19

NEUTRAL SCREENED
2, 3 & 4 Core

PVC/PVC Copper

20

AERIAL
1, 2, 3 & 4 Core
2, 3 & 4 Core

PVC Copper
XLPE Aluminium ABC

21
22

FLEXIBLE CORDS
Core Colours
2 Core, 2, 3 & 4 Core+Earth
2 Core, 2, 3 & 4 Core+Earth
1 Core
1 Core
2 Core
2 & 3 Core
Multicore
2, 3 & 4 Core+Earth
3 & 4 Core+Earth

Ordinary Duty
Heavy Duty
PVC
Silicone Rubber
PVC Figure 8
Light Duty
Heavy Duty
Flexolex Heavy Duty
Flexolex Heavy Duty Screened

23
24
25
26
26
26
26
27
28
29

CONTENTS
FLEXIBLE CABLES
1 Core
1 Core
Welding
VAROLEX
3 Core+3 Earths
PYROLEX FIRE RATED
1 Core
2, 3, 4 Core

PVC/TPE Welding, Power & Switchboard


CPE Welding & Power
Current Ratings

30
31
32

XLPE/PVC Copper

33

ES110
Multicore D&W

34
35

INSTRUMENTATION CABLE DEKORON


Pairs
Pairs SWA

COMMUNICATIONS CABLE
LAN
Category 3 16MHz
PVC Insulated Copper
Category 5 Standard
PVC Insulated Copper
Category 5 External
PVC Insulated Copper
Category 5e
PVC Insulated Copper
Category 5e External
PVC Insulated Copper
Proposed Category 6
DataTwist 350
Category 6
MediaTwist
Thin Ethernet
PVC Insulated Copper
100 Ohm Twinaxial
PVC Insulated Copper
78 Ohm Twinaxial
Blue Hose
FIBRE
Indoor/Outdoor Riser
Internal Light Duty Riser
Internal Heavy Duty Riser
External Single Tube
Construction
External Loose Tube
Single Mode & Multi Mode
External Armoured Loose Tube Cable
TELEPHONE CABLE
Internal
Underground External
External Jelly Filled
External Jelly Filled & Moisture Barrier
Aerial
Telstra Approved External
Jumper Wire
Jumper Wire
Category 5

36
37

38
39
39
40
40
41
41
42
42
42
43
44
44
45
46
47
48
49
50
51
51
52
53
53

CONTENTS
DATA CABLE
Audio Control
RS485 Screened Data
RS232 Screened Data
RS232 Screened Data
ISDN Foil or Braid 120 Ohm
SCSI Cables
Traffic Detector Cable
SECURITY CABLES
Multicore Circular
Flat (Figure 8)
MICROPHONE

Low Capacitance
Mid Capacitance

54
55
55
56
56
57
57
58
58
59

ACCESSORIES
ALCO Earth Tags
ALCO Locknuts
ALCO PVC Shrouds
Clipsal A4 Industrial Glands
Glands UA, UG, UFPR, G, WG, FLPW

60
60
61
61
6267

CURRENT RATINGS
Flexible Cords
PVC Aerial Cables
Flexible & Welding Cables
Single Phase
Single Phase
Three Phase
Three Phase

68
69
70
7172
7374
7576
7778

Copper
2 x 1 Core PVC, XLPE
2 Core PVC, XLPE
3 x 1 Core PVC, XLPE
3 & 4 Core PVC, XLPE

GENERAL
Cable Selection
Installation
Minimum Size of Copper Earthing Conductors
Maximum Operating Temperatures
D.C. Resistance
3 Phase Formulae
M.C.M. & A.W.G. Conductor Size Conversion
Bending Radii
Diameter to Cross-sectional Area
Number of Cables in Conduit
Cables in Conduit Space Factors
Pulling Tension
Abbreviations

7980
81
82
82
83
84
85
86
87
88
89
89
90

ENVIROLEX
Olex Envirolex cables are an extensive range of enhanced performance
cables for the construction industry engineered to dramatically reduce
environmental impact, particularly under fire conditions, while retaining
the excellent mechanical and electrical properties designed into Olex
cables. Olex uses a variety of inorganically filled polyolefin based
materials to engineer the cables in the Envirolex range to meet a wide
variety of end uses and performance requirements.
Advantages of Olex Envirolexcables
 Conductor range up to 630mm2
 Cable types from building wires to SWA, to multicore control
 90C rated for superior thermal performance
 Improved performance under fire conditions:
Flame retardant/self-extinguishing
Reduced acid, gas and smoke generation
Non-corrosive in fire situations
Reduced toxicity of fumes during fire
 Halogen free (i.e. no chlorine, bromine etc.)
 Lead free
 No special termination or installation requirements
 Made in accordance with Australian Standards
Envirolexcables have been tested according to and comply with the
requirements of the single and bunched flame tests (as applicable)
specified in AS1660.
Envirolexproducts include readily strippable cables for general
construction purposes as well as the tougher products commonly
found in cables with higher fire performance capability.
Envirolexmaterials are used as alternatives to all low voltage power
and control cables (refer tables on pages 5 to 23).

Cables are available on request, subject to minimum production run.

PVC INSULATED

POWER
N E WA R D
ND
STA

Single core, 0.6/1kV PVC insulated,


unsheathed to AS/NZS5000.1,
Copper conductors, 90C.
Nominal
conductor
area
mm2
0.5
1.0
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1.5
2.5

Nominal
insulation
thickness
mm

Nominal
overall
diameter
mm

AS / N

ZS

5000

Approximate
mass

Product
code

kg/100m

0.8
2.4
1.1
BAAP01AA001
0.8
2.7
1.7
BAAP02AA001
0.8
2.8
1.6
BAAP03AA001
0.8
3.1
2.1
BAAP05AA001
0.8
3.6
3.3
BAAP07AA001
1.0
4.5
5.3
BAAP09AA001
1.0
5.1
7.3
BAAP11AA001
1.0
6.0
12
BAAP13AA001
1.0
6.9
17
BAAP15AA001
1.2
8.4
26
BAAC17AA001
1.2
9.4
36
BAAC18AA001
1.4
10.9
48
BAAC19AA001
1.4
12.7
68
BAAC20AA001
1.6
14.6
91
BAAC22AA001
1.6
17.3
117
BAAP23AA001
1.8
18.8
145
BAAP24AA001
2.0
21.1
182
BAAP25AA001
2.2
24.1
238
BAAP26AA001
2.4
26.9
298
BAAP27AA001
2.6
30.6
377
BAAP28AA001
2.8
34.1
482
BAAP30AA001
2.8
37.8
615
BAAP32AA001
Single core PVC insulated copper earth conductor
0.6
2.7
1.8
AATP05AA001
0.7
3.4
3.2
AATP07AA001

Note: Compacted conductor.


Other temperature grades subject to minimum production runs.

POWER

PVC SDI

Single core, PVC insulated, PVC sheathed


to AS/NZS5000, Copper conductors, 90C.
 1.0 to 25mm2 450/750V to AS/NZS5000.2
 35 to 630mm2 0.6/1kV to AS/NZS5000.1
Nominal
conductor
area
mm2
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Nominal
Nominal
insulation
sheath
thickness thickness
mm
mm
0.6
0.6
0.7
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8

Note: Compacted conductor.

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2

Nominal Approximate
overall
mass
diameter
mm
kg/100m
3.9
4.2
4.9
5.9
6.4
7.8
9.0
10.6
12.2
13.8
15.5
17.7
20.4
22.1
24.5
27.8
30.8
34.7
38.4
42.2

2.7
3.2
4.8
7.1
9.4
14.7
20.8
31.3
43
56
77
103
133
161
201
262
326
411
521
659

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

AABP02AA001
AABP05AA001
AABP07AA001
AABP09AA001
AABP11AA001
AABP13AA001
AABP15AA001
AABC17AA001
BABC18AA001
BABC19AA001
BABC20AA001
BABC22AA001
BABP23AA001
BABP24AA001
BABP25AA001
BABP26AA001
BABP27AA001
BABP28AA001
BABP30AA001
BABP32AA001

XLPE INSULATED

POWER

Single core, 0.6/1kV XLPE insulated,


PVC sheathed to AS/NZS5000.1,
Copper and Aluminium conductors, 90C.

Nom.
cond.
area
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Nom. Sheath
insul. thick.
thick.
mm
mm
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.2

Nominal
overall
diameter
mm
Cu
9.1
10.6
11.6
13.0
14.9
16.7
19.6
21.3
23.5
26.6
29.4
33.3
37.0
41.4

Al
9.1
10.8
12.8
13.7
15.0
17.7
18.5
20.6
22.4
25.1
27.7
31.1
34.7
39.5

Approximate
mass

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

kg/100m
Cu
21
30
40
52
73
97
123
152
189
246
306
386
491
635

Al
11
15
18
23
31
40
54.9
60
72
91
112
141
178
232

Cu
BDBP15
BDBC17
BDBC18
BDBC19
BDBC20
BDBC22
BDBP23
BDBP24
BDBP25
BDBP26
BDBP27
BDBP28
BDBP30
BDBP32

Al
BDBA15
BDBA17
BDBA18
BDBA19
BDBA20
BDBA22
BDBA23
BDBA24
BDBA25
BDBA26
BDBA27
BDBA28
BDBA30
BDBA32

Note: Compacted conductor.


Cu Copper conductors. Al Aluminium conductors.

POWER

PVC FLAT

2 & 3 core flat, 450/750V PVC insulated,


PVC sheathed to AS/NZS5000.2,
Copper conductors, 90C.
Nominal
conductor
area
mm2

Conductor
type

Nominal
earth
area
mm2

1.0
1.5
2.5
4
6
10
16

Solid
Strand
Strand
Strand
Strand
Strand
Strand

1.5
1.5
2.5
2.5
2.5
4
6

1.5
2.5

Strand
Strand

1.5
2.5

Nominal
overall
dimensions
mm

Note: For insulation thickness refer to page 6.

2C
6.44.1
7.14.4
8.75.3
10.56.3
11.56.8
14.38.3
16.69.6
3C
9.74.4
12.15.3

Approximate
mass

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

kg/100m
5.1
6.2
9.7
14.3
18.7
29.9
42.5

CACP02AA002
CACP05AA002
CACP07AA002
CACP09AA002
CACP11AA002
CACP13AA002
CACP15AA002

8.9
14.1

EACP05AA003
EACP07AA003

PVC FLAT

POWER

2 & 3 core+earth flat, 450/750V PVC


insulated, PVC sheathed to AS/NZS5000.2,
Copper conductors, 90C.
Nominal Conductor
conductor
type
area
2
mm

Nominal
earth
area
mm2

1.0
1.5
2.5
2.5
4
6
10
16

Solid
Strand
Solid
Strand
Strand
Strand
Strand
Strand

1.5
1.5
2.5
2.5
2.5
2.5
4
6

1.5
2.5

Strand
Strand

1.5
2.5

Nominal
Approximate
overall
mass
dimensions
mm
kg/100m
2C+E
9.04.2
9.74.4
11.85.2
12.15.3
13.96.3
14.86.8
18.58.3
21.319.6
3C+E
12.34.4
15.45.3

N E WA R D
ND
STA

AS / N

ZS

5000
Product
code

7.5
8.9
13.7
14.1
18.8
23.2
36.6
51.5

CNCP02AA002
CNCP05AA002
CNCP06AA002
CNCP07AA002
CNCP09AA002
CNCP11AA002
CNCP13AA002
CNCP15AA002

11.6
18.4

ENCP05AA003
ENCP07AA003

Note: For insulation thickness refer to page 6.

POWER

PVC CIRC
N E WA R D
ND
STA

2 & 3 core+earth, circular, PVC insulated,


PVC sheathed to AS/NZS5000,
Copper conductors, 90C.
 1.5 to 6mm2 450/750V to AS/NZS5000.2
 10 to 300mm2 0.6/1kV to AS/NZS5000.1
Nominal
conductor
area
mm2

10

Earth
conductor
area
mm2

1.5
2.5
4
6
10
16
25
35
50

1.5
2.5
2.5
2.5
4
6
6
10
16

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120

Nominal
overall
diameter
mm
2C+E
9.4
10.9
12.3
13.3
16.0
17.7
20.5
22.5
25.6
3C+E
10.3
12.0
13.4
14.4
17.5
19.4
22.3
24.7
28.3
32.6
36.4
42.0
46.3
51.6
58.9
65.3

AS / N

ZS

5000

Approximate
mass

Product
code

kg/100m
13
17
22
28
48
65
80
107
139

CNHP05AA002
CNHP07AA002
CNHP09AA002
CNHP11AA002
DNHP13AA002
DNHP15AA002
DNHC17AA002
DNHC18AA002
DNHC19AA002

16
23
31
37
61
84
110
143
192
268
346
453
560
706
916
1153

ENHP05AA003
ENHP07AA003
ENHP09AA003
ENHP11AA003
FNHP13AA003
FNHP15AA003
FNHC17AA003
FNHC18AA003
FNHC19AA003
FNHC20AA003
FNHC22AA003
FNHP23AA003
FNHP24AA003
FNHP25AA003
FNHP26AA003
FNHP27AA003

Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
2C+E, 35mm2 and above, subject to minimum production run.
For insulation thickness refer to page 6.

XLPE INSULATED

POWER
N E WA R D
ND
STA

2 & 3 core+earth, circular, 0.6/1kV XLPE


insulated, PVC sheathed to AS/NZS5000.1,
Copper conductors, 90C.

Nominal
conductor
area
mm2

Main
conductor
type

Sheath
thickness
mm

16
25
35
50
70
95
120

Strand
Compact
Compact
Compact
Compact
Compact
Strand

1.8
1.8
1.8
1.8
1.8
1.9
2.0

16
25
35
50
70
95
120
150
185
240
300

Strand
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand

1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.3
2.5
2.6
2.8

Nominal
overall
diameter
mm
2C+E
16.5
19.4
21.4
24.1
28.0
31.3
37.0
3C+E
18.0
21.0
23.3
26.3
31.0
34.1
40.1
44.2
49.8
56.3
62.5

AS / N

ZS

5000

Approximate
mass

Product
code

kg/100m
52
74
97
130
184
233
301

DTHP15AA002
DTHC17AA002
DTHC18AA002
DTHC19AA002
DTHC20AA002
DTHC22AA002
DTHP23AA002

68
100
132
178
253
321
422
521
661
857
1080

FTHP15AA003
FTHC17AA003
FTHC18AA003
FTHC19AA003
FTHC20AA003
FTHC22AA003
FTHP23AA003
FTHP24AA003
FTHP25AA003
FTHP26AA003
FTHP27AA003

Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted
For insulation thickness refer to page 7.
312 core (3 core+reduced neutral with or without earth) available on request
subject to minimum production runs.

11

POWER

PVC CIRC

4 core+earth, circular, PVC insulated,


PVC sheathed to AS/NZS5000,
Copper conductors, 90C.
 1.5 to 6mm2 450/750V to AS/NZS5000.2
 10 to 300mm2 0.6/1kV to AS/NZS5000.1
Nominal
conductor
area
mm2
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

Earth
conductor
area
mm2
1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120

Nominal
overall
diameter
mm
4C+E
11.0
12.9
14.5
15.7
19.1
21.3
24.6
27.3
32.9
38.1
42.3
48.7
53.8
60.2
69.5
77.8

N E WA R D
ND
STA

AS / N

5000

Approximate
mass

Product
code

kg/100m
18
27
37
46
75
105
138
182
249
349
451
591
734
908
1201
1502

GNHP05AA004
GNHP07AA004
GNHP09AA004
GNHP11AA004
HNHP13AA004
HNHP15AA004
HNHC17AA004
HNHC18AA004
HNHC19AA004
HNHC20AA004
HNHC22AA004
HNHP23AA004
HNHP24AA004
HNHP25AA004
HNHP26AA004
HNHP27AA004

Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
For insulation thickness refer to page 6.

12

ZS

XLPE INSULATED

POWER

4 core+earth, circular, 0.6/1kV XLPE


insulated, PVC sheathed to AS/NZS5000.1,
Copper conductors, 90C.

Nominal
conductor
area
mm2

Main
conductor
type

16
25
35
50
70
95
120
150
185
240
300

Strand
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand

N E WA R D
ND
STA

AS / N

5000

Sheath
Nominal Approximate
thickness overall
mass
diameter
mm
mm
kg/100m
1.8
1.8
1.8
1.9
2.0
2.2
2.3
2.5
2.7
2.9
3.1

4C+E
19.7
22.8
25.5
30.6
36.1
39.6
46.4
51.3
58.1
66.0
74.6

68
126
168
231
330
423
552
681
864
1117
1407

ZS

Product
code

HTHP15AA004
HTHC17AA004
HTHC18AA004
HTHC19AA004
HTHC20AA004
HTHC22AA004
HTHP23AA004
HTHP24AA004
HTHP25AA004
HTHP26AA004
HTHP27AA004

Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
For insulation thickness refer to page 7.

13

POWER

PVC SWA CIRC


N E WA R D
ND
STA

2 & 3 core+earth, circular, PVC insulated,


PVC bedded, steel wire armoured,
PVC sheathed cable to AS/NZS5000,
Copper conductors, 90C.
 1.5 to 6mm2 450/750V to AS/NZS5000.2
 10 to 300mm2 0.6/1kV to AS/NZS5000.1
Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm

14

1.5
2.5
4
6
10
16
25
35
50

1.5
2.5
2.5
2.5
4
6
6
10
16

7.8
9.3
10.7
11.7
14.4
16.1
19.0
21.0
24.0

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120

8.7
10.4
11.8
12.8
15.9
17.8
20.7
23.1
26.5
31.0
34.6
40.0
44.3
49.4
56.7
62.7

Note: Compacted conductor.


For insulation thickness refer to page 6.

Nominal
dia. over
armour
mm
2C+E
9.7
11.2
13.2
14.3
16.9
18.6
22.2
24.2
27.2
3C+E
10.5
12.9
14.3
15.4
18.4
21.0
23.9
26.3
29.7
35.0
38.6
44.1
49.3
54.4
61.7
67.7

AS / N

ZS

5000

Nominal Approximate
overall
mass
diameter
mm
kg/100m

Product
code

13.3
14.8
16.8
17.9
20.5
22.3
25.8
27.8
30.9

34
43
59
67
95
116
150
181
230

CNMP05AA002
CNMP07AA002
CNMP09AA002
CNMP11AA002
DNMP13AA002
DNMP15AA002
DNMC17AA002
DNMC18AA002
DNMC19AA002

14.1
16.5
17.9
19.0
22.0
24.6
27.6
30.0
33.7
39.2
43.1
48.9
54.3
59.8
68.0
74.5

39
57
68
79
113
154
184
226
287
407
499
636
802
977
1230
1501

ENMP05AA003
ENMP07AA003
ENMP09AA003
ENMP11AA003
FNMP13AA003
FNMP15AA003
FNMC17AA003
FNMC18AA003
FNMC19AA003
FNMC20AA003
FNMC22AA003
FNMP23AA003
FNMP24AA003
FNMP25AA003
FNMP26AA003
FNMP27AA003

312 core (3 core+reduced neutral with or without earth)


available on request subject to minimum production runs.

XLPE SWA

POWER
N E WA R D
ND
STA

2 & 3 core+earth, circular, 0.6/1kV XLPE


insulated, PVC bedded, steel wire armoured,
PVC sheathed cable to AS/NZS5000.1,
Copper conductors, 90C.

Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm
2.5
4
6
10
16
25
35
50
70
95
120
16
25
35
50
70
95
120
150
185
240
300

2
2
2
4
6
6
10
16
25
25
35

9.3
10.3
11.3
13.2
14.9
17.8
19.8
22.5
26.4
29.9
35.4

6
6
10
16
25
25
35
50
70
95
120

16.4
19.4
21.7
24.7
29.6
32.0
38.2
42.4
47.6
54.3
60.1

Nominal
dia. over
armour
mm
2C+E
11.1
12.8
13.8
15.7
17.4
20.3
23.0
25.7
29.6
33.9
39.4
3C+E
18.9
22.6
24.9
27.9
33.6
36.0
42.3
47.4
52.6
59.3
65.1

AS / N

ZS

5000

Nominal Approximate
overall
mass
diameter
mm
kg/100m

Product
code

14.8
16.5
17.5
19.3
21.1
24.0
26.7
29.4
33.4
37.9
43.7

42
57
64
80
98
129
169
211
279
364
459

DTMP07AA002
DTMP09AA002
DTMP11AA002
DTMP13AA002
DTMP15AA002
DTMC17AA002
DTMC18AA002
DTMC19AA002
DTMC20AA002
DTMC22AA002
DTMP23AA002

22.5
26.2
28.6
31.8
37.8
40.5
46.9
52.5
57.9
65.0
71.7

118
171
212
267
387
467
596
750
916
1145
1406

FTMP15AA003
FTMC17AA003
FTMC18AA003
FTMC19AA003
FTMC20AA003
FTMC22AA003
FTMP23AA003
FTMP24AA003
FTMP25AA003
FTMP26AA003
FTMP27AA003

Note: Compacted conductor.


For insulation thickness refer to page 7.
312 core (3 core+reduced neutral with or without earth) available on request
subject to minimum production runs.

15

POWER

PVC SWA CIRC


N E WA R D
ND
STA

4 core+earth, circular, PVC insulated, PVC


bedded, steel wire armoured PVC sheathed
to AS/NZS5000, Copper conductors, 90C.
 1.5 to 6mm2 450/750V to AS/NZS5000.2
 10 to 300mm2 0.6/1kV to AS/NZS5000.1
Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120

9.4
11.3
12.9
14.1
17.5
19.7
23.0
25.7
31.3
36.3
40.5
46.7
51.4
58.0
66.6
75.0

Nominal
dia. over
armour
mm
4C+E
11.3
13.9
15.4
16.7
20.7
22.9
26.2
28.9
35.3
40.3
45.5
51.7
56.4
63.0
71.6
82.1

14.9
17.5
19.0
20.3
24.4
26.5
29.9
32.7
39.5
44.7
50.4
56.9
61.9
69.4
78.4
88.9

43
63
78
91
145
181
221
276
390
511
672
849
1012
1227
1560
2009

ZS

5000

Nominal Approximate
overall
mass
diameter
mm
kg/100m

Note: Compacted conductor.


For insulation thickness refer to page 6.
312 core (3 core+reduced neutral with or without earth) available on request
subject to minimum production runs.

16

AS / N

Product
code

GNMP05AA004
GNMP07AA004
GNMP09AA004
GNMP11AA004
HNMP13AA004
HNMP15AA004
HNMC17AA004
HNMC18AA004
HNMC19AA004
HNMC20AA004
HNMC22AA004
HNMP23AA004
HNMP24AA004
HNMP25AA004
HNMP26AA004
HNMP27AA004

XLPE SWA

POWER

4 core+earth, circular, 0.6/1kV XLPE


insulated, PVC bedded, steel wire armoured
PVC sheathed to AS/NZS5000.1,
Copper conductors, 90C.

Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm
16
25
35
50
70
95
120
150
185
240
300

6
6
10
16
25
25
35
50
70
95
120

18.1
21.2
23.9
29.2
34.5
37.6
44.6
49.1
55.9
63.4
70.6

Nominal
dia. over
armour
mm
4C+E
21.3
24.4
27.1
33.2
38.5
41.6
49.6
54.1
60.9
68.4
76.9

Nominal
overall
diameter
mm
25.0
28.0
31.0
37.2
43.0
46.3
54.7
59.6
67.0
74.9
84.0

Approx.
mass

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

kg/100m
154
203
256
363
485
586
795
944
1164
1452
1900

HTMP15AA004
HTMC17AA004
HTMC18AA004
HTMC19AA004
HTMC20AA004
HTMC22AA004
HTMP23AA004
HTMP24AA004
HTMP25AA004
HTMP26AA004
HTMP27AA004

Note: Compacted conductor.


For insulation thickness refer to page 7.
312 core (3 core+reduced neutral with or without earth) available on request
subject to minimum production runs.

17

POWER

PVC CONTROL

Multicore circular+earth, 0.6/1kV PVC


insulated, PVC sheathed to AS/NZS5000.1,
Copper conductors, 90C.

Number
of cores

18

Nominal overall
diameter
mm

5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E

12.9
14.4
15.2
16.1
16.8
18.2
19.1
20.1
22.1
24.2
25.2
27.4
29.3

5+E
6+E
8+E
10+E
12+E
15+ E
16+E
20+E
25+E
30+E
36+E
40+E
50+E

14.5
14.8
17.2
18.2
19
20.6
21.7
22.8
25.2
27.7
28.9
31.5
33.8

Approximate
mass
kg/100m

1.5mm2 (7/0.50mm)
24
27
32
38
42
50
53
63
74
87
100
112
138
2.5mm2 (7/0.67mm)
33
35
46
56
61
71
77
91
109
128
150
168
203

Note: For insulation thickness refer to page 5.

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

BFAP05AA005
BFAP05AA006
BFAP05AA008
BFAP05AA010
BFAP05AA012
BFAP05AA015
BFAP05AA016
BFAP05AA020
BFAP05AA025
BFAP05AA030
BFAP05AA036
BFAP05AA040
BFAP05AA050
BFAP07AA005
BFAP07AA006
BFAP07AA008
BFAP07AA010
BFAP07AA012
BFAP07AA015
BFAP07AA016
BFAP07AA020
BFAP07AA025
BFAP07AA030
BFAP07AA036
BFAP07AA040
BFAP07AA050

PVC SWA CONTROL

POWER

Multicore circular+earth, 0.6/1kV PVC


insulated, PVC bedded, steel wire armoured
PVC sheathed to AS/NZS5000.1,
Copper conductors 90C.
Number
of cores

Nominal
dia. over
bedding
mm

5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E

11.3
11.6
13.6
15.1
15.2
16.6
17.5
18.5
20.5
22.6
23.6
25.8
27.9

5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E

12.9
13.1
15.6
17.2
17.4
19
20.1
21.2
23.6
26.1
27.1
30.1
32.2

Nominal
dia. over
armour
mm

Nominal
overall
diameter
mm

1.5mm2 (7/0.50mm)
13.8
17.5
14.1
17.8
16.1
19.8
17.5
21.1
17.7
21.4
19.1
22.8
20.7
24.4
21.7
25.4
23.7
27.4
25.8
29.5
26.8
30.6
29
32.9
31.9
36.2
2.5mm2 (7/0.67mm)
15.4
19
15.6
19.3
18.1
21.8
20.4
24.1
20.6
24.3
22.2
25.9
23.3
26.9
24.4
28.1
26.8
30.7
29.3
33.1
30.3
34.4
34.1
38.4
36.2
40.6

Note: For insulation thickness refer to page 5.

Approx.
mass

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

kg/100m
60
62
75
87
89
100
119
131
151
170
188
208
266

BFCP05AA005
BFCP05AA006
BFCP05AA008
BFCP05AA010
BFCP05AA012
BFCP05AA015
BFCP05AA016
BFCP05AA020
BFCP05AA025
BFCP05AA030
BFCP05AA036
BFCP05AA040
BFCP05AA050

75
77
94
122
126
143
152
169
197
226
250
308
352

BFCP07AA005
BFCP07AA006
BFCP07AA008
BFCP07AA010
BFCP07AA012
BFCP07AA015
BFCP07AA016
BFCP07AA020
BFCP07AA025
BFCP07AA030
BFCP07AA036
BFCP07AA040
BFCP07AA050

19

POWER

NEUTRAL SCREEN

2, 3 & 4 conductor 0.6/1kV PVC insulated,


NEUTRAL SCREENED, PVC sheathed cable
to AS/NZS3155, Copper conductor, 90C.

4 conductor

3 conductor

2 conductor

Nominal
Nominal
conductor insulation
area
thickness
mm2
mm

20

Nominal
sheath
thickness
mm

6
10
16
25

1.2
1.2
1.2
1.4

1.8
1.8
1.8
2.0

6
10
16
25

1.2
1.2
1.2
1.4

1.8
1.8
1.8
1.8

6
10
16

1.0
1.0
1.0

1.8
1.8
1.8

6
10
16

1.0
1.0
1.0

1.8
1.8
1.8

6
10
16
25
35
50
70

1.0
1.0
1.0
1.2
1.2
1.4
1.4

1.8
1.8
1.8
1.8
1.9
2.0
2.0

6
10
16
25
35

1.0
1.0
1.0
1.2
1.2

1.8
1.8
1.8
1.8
1.8

Note: Compacted conductor.

Nominal Approximate
overall
mass
diameter
mm
kg/100m
Mains cable
10.4
11.6
13.2
15.5
Aerial cable
10.4
11.7
13.5
15.9
Mains cable
10.716.0
12.018.2
13.220.3
Aerial cable
10.816.1
12.018.3
13.420.8
Mains cable
16.6
18.1
20.7
23.9
26.6
30.5
35.3
Aerial cable
16.7
18.7
21.3
25.6
28.1

Product
code

21
31
44
70

BAGP11AA001
BAGP13AA001
BAGP15AA001
BAGC17AA001

22
31
45
68

BAGT11AA001
BAGT13AA001
BAGT15AA001
BAGT17AA001

33
47
65

DAEP11AA002
DAEP13AA002
DAEP15AA002

34
48
67

DAET11AA002
DAET13AA002
DAET15AA002

46
60
85
132
174
232
321

FAGP11AA003
FAGP13AA003
FAGP15AA003
FAGC17AA003
FAGC18AA003
FAGC19AA003
FAGC20AA003

45
62
87
139
174

FAGT11AA003
FAGT13AA003
FAGT15AA003
FAGT17AA003
FAGT18AA003

AERIAL

POWER
N E WA R D
ND
STA

0.6/1kV PVC insulated aerial cables


to AS/NZS5000.1, Hard Drawn
Copper conductors, 90C.
Nominal
conductor
area
mm2

No. & nom.


diameter
of wires
mm

Nominal
insulation
thickness
mm

6
10
16
25
35
50
70
95
120
150

7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.78
19/2.14
37/1.78
37/2.03
37/2.25

1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8

6
10
16

7/1.04
7/1.35
7/1.70

1.0
1.0
1.0

6
10
16

7/1.04
7/1.35
7/1.70

1.0
1.0
1.0

6
10
16
25

7/1.04
7/1.35
7/1.70
19/1.35

1.0
1.0
1.0
1.2

6
10
16
25

7/1.04
7/1.35
7/1.70
19/1.35

1.0
1.0
1.0
1.2

6
10
16
25

7/1.04
7/1.35
7/1.70
19/1.35

1.0
1.0
1.0
1.2

Nominal
overall
diameter
mm

Single core
5.1
6.1
7.1
9.2
10.1
11.7
13.5
15.7
17.4
19.4
2C Parallel
5.111.4
6.113.0
7.115.1
3C Parallel
5.117.2
6.120.0
7.123.2
2C Twisted
10.1
11.9
14.0
18.1
3C Twisted
10.9
12.9
15.1
19.5
4C Twisted
12.2
14.4
16.9
21.8

AS / N

ZS

5000

Approximate
mass

Product
code

kg/100m
8
12
18
29
37
50
70
95
121
149

BAAT11AA001
BAAT13AA001
BAAT15AA001
BAAT17AA001
BAAT18AA001
BAAT19AA001
BAAT20AA001
BAAT22AA001
BAAT23AA001
BAAT24AA001

15
23
35

DAAT11AA002
DAAT13AA002
DAAT15AA002

22
35
53

FAAT11AA003
FAAT13AA003
FAAT15AA003

15
23
35
59

DAFT11AA002
DAFT13AA002
DAFT15AA002
DAFT17AA002

22
35
53
89

FAFT11AA003
FAFT13AA003
FAFT15AA003
FAFT17AA003

30
47
71
118

HAFT11AA004
HAFT13AA004
HAFT15AA004
HAFT17AA004

21

POWER

AERIAL

2, 3 & 4 core aerial bundled cable 0.6/1kV XLPE insulated


compacted H9 Aluminium conductors, to AS3560, 90C.

22

Nominal
conductor
area

Nominal
insulation
thickness

Diameter
over
insulation

mm2

mm

mm

25
35
50
95

1.3
1.3
1.5
1.7

8.6
9.8
11.3
15.0

25
35
50
70

1.3
1.3
1.5
1.5

8.6
9.8
11.3
13.0

25
35
50
70
95
120
150

1.3
1.3
1.5
1.5
1.7
1.7
1.7

8.6
9.8
11.3
13.0
15.1
16.5
17.9

Diameter Approximate
over
mass
laid-up
cores
mm
kg/100m
2C
17.2
19.3
22.5
30.1
3C
18.7
21.0
24.3
27.7
4C
21.0
23.5
27.2
31.1
36.2
39.6
43.1

Product
code

20
25
34
64

XDAB17AA002
XDAB18AA002
XDAB19AA002
XDAB22AA002

29
37
51
70

XDAB17AA003
XDAB18AA003
XDAB19AA003
XDAB20AA003

39
50
67
93
128
157
189

XDAB17AA004
XDAB18AA004
XDAB19AA004
XDAB20AA004
XDAB22AA004
XDAB23AA004
XDAB24AA004

FLEXIBLE

POWER

CORE COLOURS
Colour sequences are valid for standard light ordinary
and heavy duty cords.
a) Preferred Core Colours As specified by AS/NZS3000
for cords not installed as fixed wiring.
2 Core
3 Core
4 Core
5 Core

Brown, Light Blue


Brown, Light Blue, Green/Yellow
Brown, Light Blue, White, Green/Yellow
Brown, Light Blue, Orange, White, Green/Yellow

Olex Colour Code


JJ
KA
DV
FS

Light blue is normally used as a neutral (where applicable).

b) Alternative Core Colours As recommended by


AS/NZS3191 for cords used in fixed applications. Purchase
of these cables may be subject to main order quantities.
2 Core
3 Core
4 Core

Red, Black
Red, Black, Green/Yellow
Red, White, Blue, Green/Yellow

Olex Colour Code


HF
TD
PF

Black may only be used as a neutral in fixed applications.

Note: The core colours are only recommended by AS/NZS3191.


Variations may be used for flexible or fixed application;
contact your local Olex office for further information.

23

POWER

FLEXIBLE

250/440V PVC insulated and sheathed ordinary duty


flexible cord to AS/NZS3191, 90C.
Nominal
conductor
area
mm2

Maximum
diameter
of wires
mm

Nominal
overall
diameter
mm

Approximate
mass

Product
code

kg/100m

2C
0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

6.3
6.6
7.6
9.4
10.5
2C+E
6.6
7.0
8.3
10.1
11.4
3C+E
7.2
7.8
9.2
11.0
12.4
4C+E
8.1
8.5
10.3
12.3
13.8

6
7
9
14
19

CAHR02AA002
CAHR03AA002
CAHR04AA002
CAHR05AA002
CAHR06AA002

7
8
11
17
24

EAHR02AA003
EAHR03AA003
EAHR04AA003
EAHR05AA003
EAHR06AA003

8
10
14
21
29

GAHR02AA004
GAHR03AA004
GAHR04AA004
GAHR05AA004
GAHR06AA004

10
12
17
26
36

APAR02AA005
APAR03AA005
APAR04AA005
APAR05AA005
APAR06AA005

Note: For core colour, flexible cords refer to page 23.


90C HT available on request subject to minimum production runs.

24

FLEXIBLE

POWER

0.6/1kV PVC insulated and PVC sheathed heavy duty


flexible cord to AS/NZS3191, 90C.
Nominal
conductor
area
mm2

Maximum
diameter
of wires
mm

Nominal
overall
diameter
mm

Approximate
mass

Product
code

kg/100m

2C
0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

8.2
8.5
9.5
11.2
12.9

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

8.8
9.1
10.1
11.9
13.8

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

9.7
10.0
11.1
13.1
15.2

0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

10.6
11.0
12.2
14.4
16.9

9
10
12
18
25

CBGR02AA002
CBGR03AA002
CBGR04AA002
CBGR05AA002
CBGR06AA002

10
12
15
22
30

EBGR02AA003
EBGR03AA003
EBGR04AA003
EBGR05AA003
EBGR06AA003

13
14
18
26
37

GBGR02AA004
GBGR03AA004
GBGR04AA004
GBGR05AA004
GBGR06AA004

15
17
22
32
46

BSBR02AA005
BSBR03AA005
BSBR04AA005
BSBR05AA005
BSBR06AA005

3C

4C

5C

Note: For core colour, flexible cords refer to page 23.


Conductor stranding may vary according to production method and relevant Standard.
90C HT available on request subject to minimum production runs.

25

POWER

FLEXIBLE

Other flexible cords to AS/NZS3191.


Nominal
conductor
area
mm2

Maximum
diameter
of cores
mm

Nominal
overall
diameter
mm

Approximate
mass

Product
code

kg/100m

Single core 0.6/1kV PVC insulated


flexible cord to AS/NZS3191, 90C
0.75
0.21
2.8
1.5
BAAR02AA001
1.0
0.21
3.0
1.7
BAAR03AA001
1.5
0.26
3.2
2
BAAR04AA001
2.5
0.26
3.7
3
BAAR05AA001
4
0.31
5.0
5.3
BAAR06AA001
Single core 0.6/1kV V90HT PVC insulated,
tinned copper flexible cord to AS/NZS3191, 90C HT
0.75
0.21
2.8
1.5
BAAR52AD001
1.0
0.21
3.0
1.7
BAAR53AD001
1.5
0.26
3.2
2.0
BAAR54AD001
2.5
0.26
3.7
3.0
BAAR55AD001
4
0.31
5.0
5.3
BAAR56AD001
Twin figure 8 250/250V PVC insulated
flexible cord to AS/NZS3191, 90C
0.75
0.21
3.15.9
2.3
CAAR02AA002
2 and 3 core 250/250V PVC insulated, PVC sheathed LIGHT duty
flexible cord to AS/NZS3191, 90C
0.75
0.21
5.7
5
CBER02AA002
0.75
0.21
5.8
6
EBER02AA003
2 core 250/250V PVC insulated, PVC sheathed LIGHT duty flat
flexible cord to AS/NZS3191, 90C
0.75
0.21
CBLR02AA002
Note: For core colour, flexible cords refer page 24.
2 core light duty flat cords supplied in red and white insulation,
red sheath for fire alarm wiring systems.

26

HEAVY DUTY FLEXIBLE

POWER
EW

N ARD
Multicore circular 0.6/1kV PVC insulated
ND
STA
ZS
and PVC sheathed heavy duty flexible
AS / N
control cable, with or without black neutral,
5000
white insulated, black numbered cores
including earth generally to AS/NZS5000.1, 90C.

Number
of cores

Nominal
overall
diameter
mm2

5
7
9
11
15
19

13.4
15.4
17.2
18.9
18.2
19.9

5
7
9
11
15
19

13.9
16.1
17.9
19.8
19.0
20.9

5
7
9
11
15
19

14.8
17.1
19.2
21.2
20.4
22.4

Approximate
mass
kg/100m
0.75mm2
22
28
34
41
43
51
1.0mm2
24
31
38
46
48
58
1.5mm2
29
36
46
54
58
70

Product
code

BFFR02AA005
BFFR02AA007
BFFR02AA009
BFFR02AA011
BFFR02AA015
BFFR02AA019
BFFR03AA005
BFFR03AA007
BFFR03AA009
BFFR03AA011
BFFR03AA015
BFFR03AA019
BFFR04AA005
BFFR04AA007
BFFR04AA009
BFFR04AA011
BFFR04AA015
BFFR04AA019

*Cables suitable for crane pendant and de-reeler applications.

27

POWER

FLEXIBLE

Flexolex HD; 0.6/1kV cords and cables


EPR insulated and CPE sheathed to
AS/NZS3191 (cords) and AS/NZS5000.1
(cables), tinned copper conductors, 90C.

Nominal Maximum Nominal Nominal Nominal Approximate


conductor diameter insulation sheath
overall
mass
area
of wires thickness thickness diameter
2
mm
mm
mm
mm
mm
kg/100m
0.75
1.0
1.5
2.5
4

0.21
0.21
0.26
0.26
0.31

0.8
0.8
0.8
0.9
1.0

1.5
2.5
4
6
10
16
25

0.26
0.26
0.31
0.31
0.41
0.41
0.41

0.8
0.9
1.0
1.0
1.2
1.2
1.4

1.5
2.5
4
6
10
16
25
35

0.26
0.26
0.31
0.31
0.41
0.41
0.41
0.41

0.8
0.9
1.0
1.0
1.2
1.2
1.4
1.4

2C+E
1.4
1.4
1.6
1.8
1.9
3C+E
1.7
1.9
2.0
2.2
3.4
3.6
4.0
4C+E
1.8
2.0
2.2
2.4
3.6
3.8
4.3
4.6

AS / N

ZS

5000

Product
code

8.8
9.1
10.1
12.0
13.9

11
12
15
22
31

RDER52AA003
RDER53AA003
RDER54AA003
RDER55AA003
RDER56AA003

11.2
13.2
15.3
17.9
24.4
27.4
32.9

19
27
39
55
97
135
204

RDER54AA004
RDER55AA004
RDER56AA004
RDHR57AA004
RDHR58AA004
RDHR59AA004
RDHR60AA004

12.3
14.5
17.0
19.9
26.8
30.2
36.4
40.6

23
33
48
68
118
164
251
322

RDER54AA005
RDER55AA005
RDER56AA005
RDHR57AA005
RDHR58AA005
RDHR59AA005
RDHR60AA005
RDHR61AA005

Note: Other sizes and conductor configurations are available upon request.

28

N E WA R D
ND
STA

FLEXIBLE

POWER

Flexolex HD Screened; 0.6/1kV cords and


cables EPR insulated, EPR bedded, tinned
copper wire braid screened, CPE sheathed
to AS/NZS3191 (cords) and AS/NZS5000.1
(cables), tinned copper conductors, 90C.
Nominal Maximum Nominal Nom. Nominal Nominal Approx.
cond. diameter insul. sheath dia.under overall
mass
area
of wires
thick. thick.
braid
diameter
2
mm
mm
mm
mm
mm
mm
kg/100m
1.5
2.5
4
6
10
16

0.26
0.26
0.31
0.31
0.41
0.41

0.8
0.9
1.0
1.0
1.2
1.2

1.8
1.9
2.2
2.4
3.5
3.8

1.5
2.5
4
6
10
16

0.26
0.26
0.31
0.31
0.41
0.41

0.8
0.9
1.0
1.0
1.2
1.2

1.9
2.1
2.3
2.6
3.7
4.0

3C+E
9.7
11.3
13.2
15.3
19.2
21.8
4C+E
10.6
12.4
14.5
16.9
21.2
24.2

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

14.7
16.5
19.0
21.8
28.4
31.6

30
40
54
76
126
168

RDLR54AA004
RDLR55AA004
RDLR56AA004
RDXR57AA004
RDXR58AA004
RDXR59AA004

15.8
18.0
20.5
23.9
30.8
34.4

35
48
64
92
150
201

RDLR54AA005
RDLR55AA005
RDLR56AA005
RDXR57AA005
RDXR58AA005
RDXR59AA005

Note: Other sizes are available upon request.

29

POWER

FLEXIBLE

1 core, 0.6/1kV TPE insulated cable


for welding, power and switchboard
applications to AS/NZS5000.1 and suitable
for 600V welding application to AS/NZS1995.
Nominal Nominal Approximate Product
insulation overall
mass
code
thickness diameter
mm
mm
kg/100m
TPS
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8

6.2
7.4
9.1
10.2
12.2
14.1
16.3
17.9
19.6

12
17
26
35
50
70
95
117
132

BAAX01MN001
BAAX02MN001
BAAX03MN001
BAAX04MN001
BAAX05MN001
BAAX06MN001
BAAX07MN001
BAAX08MN001
BAAE88MN001

N E WA R D
ND
STA

AS / N

5000

Nominal Approximate
overall
mass
diameter
mm
kg/100m
TPSW*
9.1
10.2
12.0
13.1
15.1
16.9
19.4
20.9
22.8

16
23
33
42
59
79
107
130
155

ZS

Product
code

BABX01MN001
BABX02MN001
BABX03MN001
BABX04MN001
BABX05MN001
BABX06MN001
BABX07MN001
BABE87MN001
BABE88MN001

*Insulation thickness for TPSW cables is the same as that for TPS cables.
TPS: 0.6/1kV rated TPE insulated single core unprotected flexible copper cable for power and
switchboard applications. 90C HT rated to AS/NZS5000.1.
TPSW: 0.6/1kV rated TPE insulated and sheathed single core flexible copper cable for power,
welding and switchboard applications. 90C HT rated to AS/NZS5000.1 and AS/NZS1995.
TPS & TPSW are made with V90HT rated materials and are suitable for temperatures up to 105C
for limited periods (refer AS/NZS3008). These materials have enhanced UV protection characteristics
and enhanced fire resistance properties, hence the insulated and sheathed cables are excellent for
heavy duty welding applications.

30

FLEXIBLE

POWER

1 core, 0.6/1kV CPE covered cable


for welding and power to AS/NZS1995
and AS/NZS5000.1, 90C.
Nominal Maximum
conductor diameter
area
of wires
mm2
mm
10
16
25
35
50
70
95
120
150
185
240

0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.51
0.51
0.51
0.51

Nominal
conductor
diameter
mm
4.5
5.0
6.5
7.8
9.6
11.8
13.7
15.3
16.5
19.2
22.9

Nominal Approximate
overall
mass
diameter
mm
kg/100m
8.9
9.4
10.9
12.2
14.4
16.9
19.4
21.3
23.0
26.3
30.2

16
22
32
43
60
83
108
136
167
210
266

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

RDWX01AA001
RDWX02AA001
RDWX03AA001
RDWX04AA001
RDWX05AA001
RDWX06AA001
RDWX07AA001
RDWX08AA001
RDWX09AA001
RDWX10AA001
RDWX11AA001

1 core, 600V PVC/TPE welding flex to AS/NZS1995, 90C.


Nominal Maximum
conductor diameter
area
of wires
mm2
mm
16
25
35
50
70
95
120
150

0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.31

Nominal
conductor
diameter
mm
2.3
2.3
2.3
2.4
2.4
2.6
2.8
2.9

Nominal Approximate
overall
mass
diameter
mm
kg/100m
10.0
11.3
12.4
14.2
16.0
18.2
20.2
21.9

22
32
41
57
78
105
130
158

Product
code

WDCX02AA001
WDCX03AA001
WDCX04AA001
WDCX05AA001
WDCX06AA001
WDCX07AA001
WDCE87AA001
WDCE88AA001

31

POWER

FLEXIBLE

Current carrying capacity, welding applications.

Nominal
conductor
area

A
Maximum duty cycle %

Voltage
drop
mV/A.m

mm2

100

60

30

25

m/m

10
16
25

87
115
155

110
150
200

160
215
285

175
235
315

1.843
1.162
0.749

4.6
3.0
2.0

4.0
2.6
1.7

35
50
70

195
250
310

250
320
400

355
450
560

390
495
620

0.530
0.375
0.267

1.3
0.97
0.69

1.1
0.84
0.60

95
120
150

375
435
510

485
570
660

685
790
930

750
870
1020

0.198
0.153
0.123

0.54
0.44
0.37

0.47
0.38
0.32

185
240

570
680

740
880

1040
1240

1150
1360

0.097
0.076

0.32
0.28

0.28
0.24

Note: For power current rating refer page 72.

32

Maximum D.C.
resistance
at 20C

1 phase

3 phase

VAROLEX

POWER

Fixed conductor variable speed drive cables.


0.6/1kV XLPE insulated, 3 core+3 earths,
PVC bedded, Copper tape screened,
PVC sheathed to AS/NZS5000.1,
Copper conductors, 90C.
Power cores

Combined Nominal diameter Approximate


earth size
mass
Conductor Insulation
over
overall
area
thickness
screen
mm2
mm
mm
mm
mm
kg/100m
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8

2.5*
4.5
4.5
4.5
7.5
12
18
30
30
48
48
75
75
105
150

10.7
12.7
13.9
14.9
16.9
19.4
22.2
25.4
28.6
31.6
38.1
41.8
46.5
52.7
59.2

14.4
16.4
17.6
18.6
20.6
23.1
25.9
29.1
32.3
35.3
41.8
45.6
50.6
56.9
63.8

33.1
41.8
49.2
62.1
86.3
123
163
215
281
367
464
581
703
914
1154

N E WA R D
ND
STA

AS / N

ZS

5000

Product
code

FTDP07AA003
FTDP09AA003
FTDP11AA003
FTDP13AA003
FTDP15AA003
FTDC17AA003
FTDC18AA003
FTDC19AA003
FTDC20AA003
FTDC22AA003
FTDP23AA003
FTDP24AA003
FTDP25AA003
FTDP26AA003
FTDP27AA003

*Split earth not feasible, therefore a single earth conductor is utilised.

33

PYROLEX

POWER

PYROLEXFIRE RATED SINGLE CORE ES110


Stranded Copper conductor, flame barrier tape layer,
0.6/1kV R-HF-110 insulated, HF-110-R sheathed
to AS/NZS5000.1, 110C.
Nominal
area

AS3013
rating

Insulation Sheath
mm
mm

mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

34

Thickness

WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W

1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8

1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2

Nominal Approximate Product


overall
mass
code
diameter
mm
kg/100m
10.5
11.5
13.4
14.2
15.8
17.6
19.9
21.6
23.8
26.2
29.4
32.6
36.2
39.8
43.9

20
26
40
49
64
86
114
142
174
216
279
389
443
553
699

PDEP13AA001
PDEP15AA001
PDEP17AA001
PDEP18AA001
PDEP19AA001
PDEP20AA001
PDEP22AA001
PDEP23AA001
PDEP24AA001
PDEP25AA001
PDEP26AA001
PDEP27AA001
PDEP28AA001
PDEP30AA001
PDEP32AA001

PYROLEX

POWER

PYROLEXFIRE RATED MULTICORE ES90


Stranded Copper conductor, flame barrier
tape layer, 0.6/1kV X-HF-90 XLPE insulated,
HFS-90-TP sheathed to AS/NZS5000.1, 90C.

N E WA R D
ND
STA

AS / N

ZS

5000

Number Nominal AS3013


Thickness
Nominal Approximate Product
of
area
rating
overall
mass
code
cores
Insulation Sheath diameter
2
mm
mm
mm
mm
kg/100m
2
2
2+E
2+E
2+E
2+E
2+E

1.5
2.5
1.5
2.5
4
6
10

WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W

0.7
0.7
0.7
0.7
0.7
0.7
0.7

1.8
1.8
1.8
1.8
1.8
1.8
1.8

11.0
12.2
11.7
12.5
13.5
14.6
16.1

15
20
18
23
28
30
50

PEGP05AA002
PEGP07AA002
PDGP05AA002
PDGP07AA002
PDGP09AA002
PDGP11AA002
PDGP13AA002

3
3
3+E
3+E
3+E
3+E
3+E
3+E
3+E
3+E

1.5
2.5
1.5
2.5
4
6
10
16
25
35

WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

11.5
12.7
12.5
13.7
14.7
16.0
17.8
21.0
23.0
25.6

17
22
20
27
33
40
57
82
114
149

PEGP05AA003
PEGP07AA003
PDGP05AA003
PDGP07AA003
PDGP09AA003
PDGP11AA003
PDGP13AA003
PDGP15AA003
PDGC17AA003
PDGC18AA003

4
4
4+E
4+E
4+E
4+E
4+E
4+E
4+E
4+E
4+E

1.5
2.5
1.5
2.5
4
6
10
16
25
35
50

WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W

0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9

12.8
13.8
13.6
15.1
16.4
17.3
19.5
23.1
25.5
28.4
32.8

20
26
25
33
41
50
71
105
145
191
255

PEGP05AA004
PEGP07AA004
PDGP05AA004
PDGP07AA004
PDGP09AA004
PDGP11AA004
PDGP13AA004
PDGP15AA004
PDGC17AA004
PDGC18AA004
PDGC19AA004

35

DEKORON

INSTRUMENTATION
Olex Dekoron instrumentation cable.
Number
& nominal
diameter
of wires
no/mm
7/0.30
7/0.50
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30

Number
of pairs

Nominal
overall
diameter

Approximate
mass

mm

kg/100m

Single pair screened


1
5.7
4.0
IEB183AA001
1
6.9
6.0
IEB184AA001
Overall screened pairs with drain wire
2
8.4
8
IEC183AA002
4
9.1
11
IEC183AA004
6
11.3
16
IEC183AA006
8
12.5
20
IEC183AA008
10
13.7
24
IEC183AA010
12
14.7
28
IEC183AA012
16
16.9
36
IEC183AA016
20
18.5
44
IEC183AA020
24
19.9
52
IEC183AA024
36
24.3
76
IEC183AA036
50
27.9
101
IEC183AA050
Individually and overall screened pairs with drain wire
2
8.7
9
IED183AA002
4
11.6
16
IED183AA004
6
13.5
21
IED183AA006
8
15.1
27
IED183AA008
10
16.3
33
IED183AA010
12
17.6
38
IED183AA012
16
19.7
48
IED183AA016
20
21.7
58
IED183AA020
24
24.1
71
IED183AA024
36
28.5
100
IED183AA036
50
33.1
134
IED183AA050

Note: A complete range of 7/0.50 pairs is available.

36

Product
code

DEKORON

INSTRUMENTATION

Olex Dekoron instrumentation cable.


Number
& nominal
diameter
of wires
no/mm
7/0.50
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.50
7/0.50
7/0.30
7/0.30
7/0.30
1/1.30
1/1.30
1/1.30
1/1.30

Number
of pairs
(or triples
where
applicable)

Nominal
overall
diameter

Approximate
mass

mm

kg/100m

Product
code

Single pair screened SWA


1
11.8
27.0
IEF184AA001
Overall screened pairs SWA
2
13.0
31
IEG183AA002
4
13.7
36
IEG183AA004
6
15.9
52
IEG183AA006
8
17.6
61
IEG183AA008
10
18.8
68
IEG183AA010
12
19.8
75
IEG183AA012
16
21.6
87
IEG183AA016
Individually & overall screened pairs SWA
2
13.3
33
IEH183AA002
4
16.3
53
IEH183AA004
6
18.6
66
IEH183AA006
8
20.3
76
IEH183AA008
10
21.0
82
IEH183AA010
Single triple screened
1
7.5
9.0
IGB184AA001
Single triple screened SWA
1
12.1
30.0
IGF184AA001
Overall screened triples with drain wire
4
11.3
17.0
IGC183AA004
6
13.1
22.0
IGC183AA006
12
17.7
41.0
IGC183AA012
Thermocouple extension wire, screened with drain wire
1
5.2
5.0
IKC971AA001
1
5.2
5.0
IKC972AA001
1
5.2
5.0
IKC973AA001
1
5.2
5.0
IKC974AA001

Note: Other pair and triple counts available.


7/0.50 SWA pairs and triples available.

JK
KX
SX
TX

37

COMMUNICATIONS

LAN

CATEGORY 3 16MHz
1/0.5mm (24 AWG) copper, S.R. PVC insulated,
twisted pairs, unshielded, grey PVC sheath.

Pairs

Pack
size
m

2
4
25
50
100

305 box
305 box
305 reel*
305 reel
600 reel

Nominal Nominal Nominal


Nominal
insulation O.D. capacitance impedance
thickness
mm
mm
pF/m
Ohm
0.18
0.18
0.18
0.13
0.13

Approvals UL, NEC, CEC.


*Also available in 1800m reels.

38

3.6
4.3
10.4
11.5
14.1

62.3
62.3
70
70
70

100
100
100
100
100

Product
code

J1227A1
J1229A2
JGAD06FG025
JGAD05FG050
JGAD06FG100

LAN

COMMUNICATIONS

CATEGORY 5 STANDARD (100MHz)


1/0.5mm (24 AWG) copper, or 7/0.20mm (24 AWG) tinned
copper, polyefin insulated, twisted pairs, PVC sheath.
Maximum capacitance unbalanced (pF/100m): 330.
Pairs Sheath Pack Screen Solid/
Nominal Nominal
colour size
Y/N
stranded insulation
O.D.
conductor thickness
m
mm
mm
4
4
4
25
4
4
4
4

Blue
Blue
Grey
Blue
Blue
Grey
Blue
*

305
500
305
305
305
305
305
500

N
N
N
N
Y
Y
N
N

Solid
Solid
Solid
Solid
Solid
Solid
Stranded
Stranded

0.20
0.20
0.20
0.23
0.28
0.28
0.19
0.19

5.4
5.4
5.4
14.0
6.4
6.4
5.6
5.6

Product
code

JVJDO6AA004BEDA
JVJD06AA004BED5
JVJD06AA004GYDA
J1864A0061000
J1624A006U1000
J1624RF2U1000
JWTP37DA004BEAA
JWTP37A5004xxAA

Approvals ACA, TIA/EIA, UL.


*Sheath colours available: blue, green, grey, red, white, and yellow.
**National Brand.

CATEGORY 5 EXTERNAL
1/0.5mm (24 AWG) copper, polyefin insulated, 4 unshielded
twisted pairs, ripcord, PVC sheath, black polyethylene
oversheath, for outdoor and underground applications.
Pack Std Nominal Nominal Maximum Maximum Maximum
size unit insulation O.D.
DCR capacitance capacitance
kg ea thickness
Ohms/ unbalanced unbalanced
m
mm
mm
100m
mm
pF/100m
1000 45.9

0.20

6.9

9.38

330

Product
code

JZZD061D006

Approvals UL, NEC, CEC.

39

COMMUNICATIONS

LAN

CATEGORY 5e
DATATWIST 5e, ENHANCED 5e 100MHz
1/0.5mm (24 AWG) copper or 7/0.20mm (24 AWG) copper,
polyefin insulated, unshielded twisted pairs, PVC sheath.
Maximum capacitance unbalanced (pF/m): 49.2.
Pairs

Solid/
stranded
conductor

Sheath
colour

Pack
size

4
4
4
4

Solid
Solid
Solid
Stranded

Blue
Blue
Grey
*

305 box
500 box
305 box
500 reel

Nominal Nominal
insulation O.D.
thickness
mm
mm
0.20
0.20
0.20
0.21

5.0
5.0
5.0
6.0

Product
code

J1583A006DA
J1583A006D5
J1583AF6HDA
JYJP37F6004

Available in blue, black, grey, green, red, white and yellow.


Approvals ACA, NEC, CEC, TIA/EIA, UL.
*Meets the return loss requirements specified in Addendum 5 of TIA/EIA 568A.

CATEGORY 5e (ENHANCED) EXTERNAL


1/0.5mm (24 AWG) copper, polyefin insulated, unshielded
twisted pairs each with adjoined singles, ripcord, PVC
sheath. Black oversheath to suit outdoor and underground
applications.
Pack Pairs Nominal Nominal Nominal Maximum Nominal Nominal Product
size
insulation O.D. capacitance
DCR Impedance velocity code
thickness
conductor
of
m
mm
mm
pF/m
Ohms/km Ohms propagation
305 box 4

40

0.230

6.9

50pF

93.8

100

69% YM45092

LAN

COMMUNICATIONS

PROPOSED CATEGORY 6
DATATWIST 350
(High Performance with extra headroom) (350MHz)
1/0.5mm (24 AWG) copper or 7/0.20mm (24 AWG) tinned
copper, polyolefin insulated, unshielded twisted pairs,
ripcord, blue PVC sheath. Maximum capacitance
unbalanced (pF/100m): 66.
Pairs

Solid/
stranded
conductor

Pack
size

4
4
4

Solid
Solid
Stranded

305 box
500 reel
305 box

Nominal Nominal
insulated
O.D.
conductor
O.D. mm
mm
0.23
0.23
0.23

5.1
5.1
5.6

Product
code

J1700A006U1000
J1700A0061640
J1752A006U1000

Approvals ACA, NEC, CEC, UL.

CATEGORY 6
MediaTwist for Multimedia and all
shared sheath applications. Performs well
in excess of all proposed Category 6 requirements.
1/0.5mm (24 AWG) copper, polyolefin insulated, unshielded
twisted pairs, adjacent pairs bonded (see figure).
Pairs

Sheath
colour

Nominal insulated
conductor O.D. mm

Nominal
O.D. mm

Product
code

4
4

Blue
Grey

0.23
0.23

9.3 x 7.2
9.3 x 7.2

J1872A0061000
J1872AX661000

41

COMMUNICATIONS

LAN

THIN ETHERNET
19/0.20 (20 AWG) tinned copper, foam PE insulated,
Duobond II shield, 97% tinned copper braid, grey PVC sheath.
Pack
size
m

Nominal
O.D.
mm

Ohms

Nominal
velocity of
propagation

Nominal
capacitance
pF/m

Product
code

305 box
500 reel

4.7
4.7

50
50

80%
80%

83.3
83.3

J9907E4XU1000
J9907E4X1640

100 Ohm TWINAXIAL


7/0.32 (20 AWG) 2 conductors, 1 tinned copper, 1 bare
copper, insulated, duofoil and 86% tinned copper braid,
black PVC sheath.
Pack
size
m

Nominal
O.D.
mm

Nominal
velocity of
propagation

Nominal
capacitance
pF/m

Product
code

305 reel

6.0

66%

50.9

J92070101000

78 Ohm TWINAXIAL (BLUE HOSE)


7/0.32mm (20 AWG) 2 conductors, tinned copper,
PE insulated, foil screen, tinned drain wire, 55% tinned
copper braid, blue PVC sheath.

42

Pack
size
m

Nominal
O.D.
mm

Nominal
velocity of
propagation

Nominal
capacitance
pF/m

Product
code

305 reel
305 box

6.2
6.2

66%
66%

64.60
64.60

J9463J221000
J9463J22U1000

FIBRE

COMMUNICATIONS

INDOOR/OUTDOOR RISER
Internal/external Multimode (62.5/125/250m) light
duty riser has individually buffered fibres (900m PVC)
surrounded by water swellable yarn reinforcement with an
external Flame Retardant Non-Corrosive (FRNC) Sheath.
Number
of
fibres

Nominal
O.D.
mm

Nominal
weight
kg/100m

4
6
8
12

4.8
5.3
5.3
7.0

1.7
2.1
2.2
3.5

Minimum bending
radius mm
No load
Full load
75
78
78
105

100
110
110
140

Product
code
NRBP62AA004
NRBP62AA006
NRBP62AA008
NRBP62AA012

Construction options:
1. Single mode.
2. Higher Pulling tension e.g. = 1000m.
3. Dual Jacket of PE & Halogen Free Sheath.

43

COMMUNICATIONS

FIBRE

INTERNAL LIGHT DUTY RISER CABLE


Individually buffered optical fibres surrounded by yarn
reinforcement, flame retardant, PVC Sheath. Fibre element
diameter 0.9mm.
Number
of
fibres

Fibre
type

6
12
4
6
8
12

Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode

Nominal Approximate Minimum bending


radius (mm)
O.D.
mass
mm
kg/100m No load Full load
5.3
7.0
4.8
5.3
5.3
7.0

2.1
3.5
1.7
2.1
2.2
3.5

78
105
75
78
78
105

110
140
100
110
110
140

Product
code
NRAP10AA006
NRAP10AA012
NRAP62AA004
NRAP62AA006
NRAP62AA008
NRAP62AA012

Note: Single mode 9/125/250m.


Multi mode 62.5/125/250m.
Construction options:
1. Heavy Duty Yarn for higher pulling tension.
2. Dual sheath: PE & Low Smoke Zero Halogen materials.

INTERNAL HEAVY DUTY RISER


Single element multimode (62.5/125/250m) fibres
stranded around a tension member, taped, PVC sheath.

44

Number
of
fibres

Nominal
O.D.
mm

Approximate
mass
kg/100m

6
12

9.8
12.2

0.8
1.1

Minimum bending
radius (mm)
No load
Full load
100
125

200
250

Construction options:
1. Multimode (62.5/125/250m) other sheath sizes 18 to 36 core.
2. Single mode (9/125/250m) 2 to 36 core.
3. Mixed fibre types.
4. Low Smoke Zero Halogen.

Product
code
NCAP62AA006
NCAP62AA012

FIBRE

COMMUNICATIONS

EXTERNAL SINGLE TUBE


Construction
Single mode (9/125/250m) or Multi-mode
(62.5/125/250m).
The optical fibres are contained in a jelly filled loose tube,
with external strength members, PE sheath, with or
without nylon jacket.
Number
of
fibres

Fibre
type

Nominal
O.D.
mm

Maximum Att.
dB/km
850 1310 1551
nm nm nm

6
12
4
6
8
12

Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode

10.2
10.2
10.2
10.2
10.2
10.2

3.5
3.5
3.5
3.5

1.0
1.0
1.0
1.1
1.1
1.1

1.0
1.0

Product
code

Product
code
(nylon
oversheath)

NQCU10AA006
NQCU16AA012
NQCU62AA004
NQCU62AA006
NQCU62AA008
NQCU62AA012

NQDU10AA006
NQDU10AA012
NQDU62AA004
NQDU62AA006
NQDU62AA008
NQDU62AA012

Notes:
Minimum Bending Radius (mm) No load 85: Full load: 170.
Rated Tensile Strength: 150kg.
Maximum Crush resistance: 200kg/100mm.
Nominal Weight/km: PE sheath: 52. Nylon oversheath: 62.
Single mode 9/125/250m.
Multimode 62.5/125/250m.

45

COMMUNICATIONS

FIBRE

EXTERNAL LOOSE TUBE


Single Mode: 10/125 single mode fibres in jelly filled
2.35mm loose tubes, laid up around central strength
member, PE sheath.
Multi Mode: 62.5/125 multi mode fibres, in 2.35mm jelly
filled loose tubes, laid up around central strength member,
PE sheath. Both Single mode and Multi mode type available
with or without nylon oversheath.
Number
of
fibres

Fibre
type

6
8
12
18
24
36
6
8
12
18
24
36

Single mode
Single mode
Single mode
Single mode
Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode
Multi mode
Multi mode

Maximum Attentuation
dB/km
850 1310 1551
nm
nm
nm

3.5
3.5
3.5
3.5
3.5
3.5

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

1.0
1.0
1.0
1.0
1.0
1.0

Product
code

Product
code
(nylon
oversheath)

NKCU10BA006
NKCU10BA008
NKCU10BA012
NKCU10BA018
NKCU10BA024
NKCU10BA036
NKCU62BA006
NKCU62BA008
NKCU62BA012
NKCU62BA018
NKCU62BA024
NKCU62BA036

NKDU10BA006
NKDU10BA008
NKDU10BA012
NKDU10BA018
NKDU10BA024
NKDU10BA036
NKDU62BA006
NKDU62BA008
NKDU62BA012
NKDU62BA018
NKDU62BA024
NKDU62BA036

Notes:
1. Single mode (9/125/250m). Multimode (62.5/125/250m).
2. Minimum Bending Radius (mm): No load 100, Full load 200.
3. Rated tensile strength: 200kg.
4. Maximum Crush Resistance: 200kg/100mm.
5. Nominal weight/km: PE sheath 85mm, nylon oversheath 99mm.
6. Nominal O.D. PE sheath 10.2mm, nylon oversheath 10.6mm.

46

FIBRE

COMMUNICATIONS

EXTERNAL ARMOURED LOOSE TUBE


Multi-mode (62.5/125/250m) fibres, in jelly filled loose
tubes, laid up around central strength member, water
swellable taped, yarn reinforced, corrugated steel tape
armour, PE sheath.
Number
of
fibres

Nominal
O.D.

Aproximate
mass

mm

kg/100m

6
12
36

12.9
12.9
12.9

18.5
18.5
18.5

Maximum
Attenuation dB/km
850nm

1310nm

3.5
3.5
3.5

1.0
1.0
1.0

Product
code

NKGU62DA006
NKGU62DA012
NKGU62DA036

Notes:
1. Minimum Bending Radius (mm): No load 129, Full load 258.
2. Rated tensile strength: 275kg.
3. Maximum Crush Resistance: 448kg/100mm.

47

COMMUNICATIONS

TELEPHONE INT

INTERNAL
1/0.5mm PACW, PVC insulated, twisted pairs, PVC sheath.

Pairs

(1 Quad)
3
5
6
10
20
25
50
100

Nominal
conductor
diameter
mm
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

Nominal Approximate Capacitance


overall
mass
pair to pair
diameter
at 1kHz
mm
kg/100m
pF/500m
3.3
4.5
5.4
6.1
7.3
9.5
10.5
14.0
19.5

1.7
2.8
4.5
5.1
7.5
13.1
15.8
29.3
57.7

Note: 1 Quad and 3 pair available in 305m box.


5 and 6 pair available in 200 and 500 metre reels.
10 and above available in 500 and 100 metre reels.

48

1000
300
300
300
300
300
300
300
300

Product
code

TLC590N3001
TLC590N3003
TJC590A5005
TJC590A5006
TJC590A9010
TJC590A9020
TJC590A9025
TJC590A9050
TJC590A9100

TELEPHONE EXT

COMMUNICATIONS

UNDERGROUND EXTERNAL
Plain Annealed Copper Wire (PACW), PE insulated,
twisted pairs, PE sheath.
Pairs

Nominal
sheath
thickness
mm

2
6
10
20
30
50
100
(1 Quad)
6
10
20
30
50
100

0.8
1.15
1.15
1.15
1.15
1.15
1.65
1.15
1.15
1.15
1.15
1.45
1.65
2.15

PE sheath
Product
code

Nominal Approx.
O.D.
mass
mm kg/100m

PE sheath with
nylon oversheath
Product Nominal Approx.
code
O.D.
mass
mm kg/100m

0.4mm diameter conductor


TEP794FPB02
4.9
2.2 TEP794FNB02
TAP794PP006
6.7
4.0 TAP794PN006
TAP794PP010
8.0
5.6 TAP794PN010
TAP794PP020 10.2
9.7 TAP794PN020
TAP794PP030 11.9
13.5 TAP794PN030
TAP794PP050 14.6
20.8 TAP794PN050
TAP794PP100 20.5
41.3 TAP794PN100
0.64mm diameter conductor
TUP796PP002
5.1
2.9 TUP796PN002
TAP796PP006
8.9
7.4 TAP796PN006
TAP796PP010 10.8
11.0 TAP796PN010
TAP796PP020 14.1
19.8 TAP796PN020
TAP796PP030 17.3
29.7 TAP796PN030
TAP796PP050 22.8
47.9 TAP796PN050
TAP796PP100 30.4
94.0 TAP796PN100

5.7
7.7
9.0
11.2
12.9
15.6
21.5

2.9
5.5
7.0
11.4
15.5
23.3
44.7

5.9
9.9
11.8
15.1
18.3
22.8
31.4

3.6
8.9
12.9
22.1
32.6
51.6
98.8

Pack size: 500m and 1000m drums. Other sizes available on application.

49

COMMUNICATIONS

TELEPHONE EXT

EXTERNAL JELLY FILLED


Plain annealed copper wire (PACW), cellular PE insulated,
twisted pairs, high temperature jelly, paper tape wrap,
PE sheath, with or without nylon oversheath.
Pairs

Nominal
sheath
thickness
mm

6
10
20
30
50
100

1.15
1.15
1.15
1.15
1.15
1.35

2
6
10
20
30
50
100

1.15
1.15
1.15
1.15
1.15
1.35
1.35

Product
code

PE sheath
Nominal Approx.
O.D.
mass
mm kg/100m

Product
code

0.4mm diameter conductor


TDP794FP006
6.7
4.4 TDP794FN006
TDP794FP010
8.4
6.7 TDP794FN010
TDP794FP020 10.5
11.2 TDP794FN020
TDP794FP030 12.2
15.6 TDP794FN030
TDP794FP050 14.8
24.1 TDP794FN050
TDP794FP100 20.0
45.5 TDP794FN100
0.64mm diameter conductor
TBP796FP002
6.0
3.6 TBP796FN002
TDP796FP006
9.4
8.8 TDP796FN006
TDP796FP010 11.2
13.2 TDP796FN010
TDP796FP020 14.6
25.5 TDP796FN020
TDP796FP030 17.1
33.2 TDP796FN030
TDP796FP050 21.6
53.7 TDP796FN050
TDP796FP100 29.4
102.8 TDP796FN100

Pack size: 500m and 1000m drums. Other sizes available on application.

50

Nylon jacket
Nominal Approx.
O.D.
mass
mm kg/100m
7.7
9.4
11.5
13.2
15.8
21.0

6.0
8.1
13.0
17.6
26.5
48.7

6.8
10.4
12.2
15.6
18.1
22.6
30.4

4.4
10.4
14.9
26.6
36.0
57.3
107.6

TELEPHONE EXT

COMMUNICATIONS

EXTERNAL JELLY FILLED & MOISTURE BARRIER


PACW, cellular PE insulated, twisted pair, high temperature
jelly, taped, Al laminate moisture barrier bonded to the PE
sheath, with or without Nylon oversheath.
Pairs

6
10
20
30
50
100

Nominal
sheath
thickness
mm
1.15
1.15
1.15
1.15
1.15
1.35

Product
code

PE sheath
Nominal Approx.
O.D.
mass
mm kg/100m

Product
code

Nylon jacket
Nominal Approx.
O.D.
mass
mm kg/100m

0.64mm diameter conductor


TDB796FP006
9.7
10.1 TDB796FN006
TDB796FP010 11.5
14.5 TDB796FN010
TDB796FP020 14.9
28.5 TDB796FN020
TDB796FP030 17.4
35.6 TDB796FN030
TDB796FP050 21.9
56.9 TDB796FN050
TDB796FP100 29.7
106.1 TDB796FN100

10.7
12.5
15.9
18.4
22.9
30.7

11.7
16.5
27.7
38.5
60.1
110.9

Pack size: 500m and 1000m drums. Other sizes available on application. Solid poly insulated.

AERIAL
0.64mm plain annealed copper wire, PE insulated, twisted
pair, tinned copper drain wire, PE sheath incorporating
a galvanised high tensile steel bearer wire in figure 8
construction.
Pairs

1
2
10

Size
Nominal
of bearer sheath thick.
mm
mm
1/1.25
1/1.25
1/2.50

Nominal
external dia.
mm

Approximate
mass
kg/100m

0.64mm diameter conductor


1.15
5.4 x 3.8
2.6
1.25
6.7 x 3.8
3.2
1.15
17.0 x 11.2
16.9

Product
code

TTA796IB001
TUA796IB002
TIA796IB010*

*Includes aluminium foil screen over the twisted pair.


These cables are not power cables or for direct connection of equipment to mains power supplies.

51

COMMUNICATIONS

TELEPHONE EXT

TELSTRA APPROVED EXTERNAL


Plain annealed copper wire, cellular PE insulated, twisted
pair, high temperature jelly filled, taped, PE sheath.
Alternate construction, aluminium laminate moisture
barrier bonded to the PE sheath, nylon oversheath.
Pairs Nominal
sheath
thickness
mm
2
5
10
20
30
50
100

0.80
0.08
1.15
1.15
1.15
1.15
1.15

6
10
20
30
50
100

0.95
0.95
0.95
0.95
1.15
1.35

PE sheath
Product
code

Nominal Approx.
O.D.
mass
mm kg/100m

PE sheath
with nylon jacket
Product
Nominal Approx.
code
O.D.
mass
mm kg/100m

0.4mm diameter conductor


TEP794FPB02
4.9
2.2 TEP794FNB02
TFP794FPB05
5.6
3.8 TFP794FNB02
TDB794FPB10
8.8
7.8 TDB794FNB10
TDB794FPB20 11.3
12.0 TDB794FNB20
TDB794FPB30 12.6
17.5 TDB794FNB30
TDB794FPB50 15.2
26.5 TDB794FNB50
TDB794FPB00 20.3
48.0 TDB794FNB00
0.64mm diameter conductor
TDB796FPB06
9.7
10.1 TDB796FNB06
TDB796FPB10 12.0
14.5 TDB796FNB10
TDB796FPB20 14.6
25.5 TDB796FNB20
TDB796FPB30 17.4
35.6 TDB796FNB30
TDB796FPB50 21.9
56.7 TDB796FNB50
TDB796FPB00 27.7 106.1 TDB796FNB00

Pack size: 500m and 1000m drums, other sizes available on application.

52

5.7
6.3
9.8
12.3
13.6
16.2
21.3

2.9
4.5
9.2
14.0
19.5
29.0
51.0

10.7
13.0
15.9
18.4
22.9
30.7

11.7
16.5
27.7
38.5
60.1
110.9

TELEPHONE

COMMUNICATIONS

TELEPHONE JUMPER WIRE (CROSS-CONNECT)


1/0.5mm (24 AWG) copper conductor, PVC insulated,
twisted pair.
Pack
size
m

Nominal
O.D.
mm

Nominal
mass
kg/100m

Product
code

500
250

1.84
1.84

0.47
0.47

TJZ790A5717RWA5
TJZ790AA717RWA2

CATEGORY 5 JUMPER WIRE (CROSS CONNECT)


1/0.5mm (24 AWG) copper, polyolefin insulated,
twisted pairs, adjoined singles.
Pairs

Pack
size

1
2
3
4

30.5 & 152


30.5 & 152
30.5 & 152
30.5 & 152

Nominal Nominal Maximum Maximum


insulation
O.D.
DCR
capacitance
thickness
Ohms/ unbalanced
mm
mm
100m
pF/100m
0.20
0.20
0.20
0.20

1.9
3.6
3.9
4.3

9.38
9.38
9.38
9.38

330
330
330
330

Product
code

J1721X000500
J1722X000500
J1723X000500
J1724X000500

Approvals: UL, NEC, CEC.

53

COMMUNICATIONS

DATA CABLE

AUDIO CONTROL
7/0.25mm (22 AWG) tinned copper, polypropylene
insulated, twisted pairs, foil shield, 7/0.20 (24 AWG)
tinned copper drain wire, PVC jacket.

Pack
size
m
305 box
305 reel
500 reel

Nominal
Nominal
O.D.
velocity of
mm
propagation
4.3
4.3
4.3

66%
66%
66%

Nominal
pair capacitance
pF/500m
115*
115*
115*

203**
203**
203**

Product
code
J8723060U1000
J87230601000
J87230601640

*Capacitance between conductors.


**Capacitance between one conductor and other conductors connected to shield.
Notes: Pair 1: black and red. Pair 2: green and white.

54

DATA CABLE

COMMUNICATIONS

RS485 SCREENED (LOW CAPACITANCE)


7/0.20 (24 AWG) tinned copper conductors, PE insulated,
twisted pairs, foil screened, 7/0.20 (24 AWG) tinned
copper drain wire, overall tinned copper braid shield (90%
coverage), PVC sheath. Nominal Impedance: 120 Ohms.
Pairs

Nominal
O.D.
mm

Nominal pair
capacitance
pF/m

Product
code

1
2

5.9
8.6

12.8
12.8

J98410601000
J98420601000

RS232 SCREENED DATA


RS232 paired, 7/0.20mm (24 AWG) tinned copper
conductors, PVC insulated, twisted pairs, foil screened,
7/0.20 (24 AWG) drain wire, PVC jacket.
Nominal Impedance 75 Ohms.
Pairs

Nominal
O.D.
mm

Nominal pair
capacitance
pF/m

Product
code

1
2
3
4
6
8

4.0
5.6
5.9
6.7
7.3
8.2

40
30
30
30
30
30

J95010601000
J95020601000
J95030601000
J59040601000
J95060601000
J95080601000

55

COMMUNICATIONS

DATA CABLE

RS232 SCREENED DATA (MID CAPACITANCE)


7/0.20mm (24 AWG) Copper, PE insulated, twisted pairs,
foil screened, 7/0.20mm (24 AWG) tinned copper drain
wire, grey PVC sheath. Nominal Capacitance pF/m: 100.
Rating 300V.
Pairs

Nominal insulation
thickness mm

Nominal
O.D. mm

Weight/
305m box

Product
code

1*
2
3
4
6
12.5

0.3
0.3
0.3
0.3
0.3
0.3

3.1
3.6
4.6
5.1
6.2
8.3

12.0
14.3
16.6
17.4
23.7
38.6

J1883A0081000*
JEIP87FG002GYA3
JEIP87FG003GYA3
JEIP87FG004GYA3
JEIP87FG006GYA3
JEIP87FG012GYA3

*1 pair has tinned copper and polypropylene insulated conductors.

ISDN FOIL OR BRAID 120 Ohm


1/0.5mm (24 AWG) Tinned annealed copper.
Dual insulation of polyolefin foam and non-halogenated
fire retardant skin, twisted pairs, polyolefin wrapped,
tinned copper wire braid or foil screen with 1/0.5mm
tinned copper drain wire, PVC sheath.
Pairs

1
2
10
25
32
25

56

Nominal insulation Nominal


thickness
O.D. braid
mm
mm
0.40
0.40
0.26
0.26
0.26
0.26

N/A
N/A
N/A

N/A
12.0

Minimum quantities apply for other sizes.

Nominal Nominal pair


O.D. foil capacitance
mm
nF/km
4.4
5.7
8.3
11.8
13.5

45
45
45
45
45
45

Product
code
JPMD06B1001
JPMD06B1002
JOCD56AA010
JOCD56AA025
JOCD56AA032
JOBD56AA025

DATA CABLE

COMMUNICATIONS

SCSI (Small Computer System Interface)


Tinned copper, 7/0.13mm (28 AWG) flame retardant
polyolefin insulated, twisted pairs. Polypropylene buffer
layer, foil screen, tinned copper braid shield (85% cover).
Light Grey PVC sheath.
Pairs

Pack
size
m

25

152
305
152
305

34

Standard Nominal Nominal


unit
O.D. velocity of
kg each
mm propagation
24
47
33
64

Nominal
capacitance
pF/m

Product
code

10.70

66%

45.9

98.4

J1401A

12.2

66%

45.9

98.4

J1403A

*Capacitance between conductors.


**Capacitance between one conductor and other conductors connected to shield.
Note: 1. Differential mode impedance: 120 Ohms.
2. Single end mode termination impedance: 80 Ohms.
Approvals: UL, NEC, CEC.

TRAFFIC DETECTOR
1.5mm2 stranded copper, PE insulated, twinned, jelly filled,
taped, PE sheathed, jelly coated, foil screened, with
7/0.25mm tinned copper drain wire, PVC sheath.
Number Nominal Nominal Charac- Mutual CapaciWater
of
insulation
O.D.
teristic capacitance
penecon- thickness
impedance tance unbalance* tration*
ductors
mm
mm
Ohms
nF/km
2

0.47

9.0

82100

6585

< 2%

Product
code

< 3% JTCD28A9002

*Capacitance unbalance and water penetration to AS2276.21986.

57

COMMUNICATIONS

SECURITY CABLES

MULTICORE CIRCULAR
Copper conductor, PVC insulated, PVC sheath. Rated
50V AC/120V DC (not suitable for connection to mains).
Number
of
conductors

Nominal
insulation
thickness

Nominal
overall
diameter

Approximate
mass

mm

mm

kg/100m

4
6

0.25
0.25

4
6

0.45
0.45

7/0.20mm conductor
3.9
2
4.8
3
14/0.20mm conductor
5.4
4
6.4
6

*xx Sheath colour: BN Brown


GY Grey
WT White

Nominal
conductor
resistance
Ohms/km
@20C

Product
code

81.9
81.8

JSC.2xx4C*
JSC.2xx6C*

38.9
39.5

JSC.5xx4C*
JSC.4xx6C*

Pack size: 1 100m spool


B 305m spool
5 500m spool

Notes: Insulation colours 4 core Red, black, white, blue.


6 core Red, black, white, blue, green, yellow.

FLAT (FIGURE 8)
Copper conductor, PVC insulated only.
Number
of
conductors

58

Nominal
insulation
thickness

Nominal
diameter

Approximate
mass

mm

mm

kg/100m

0.45

0.8

7/0.20mm conductor
4.2 x 1.8
2
14/0.20mm conductor
5.8 x 2.9
3

Nominal
conductor
resistance
Ohms/km
@20C

Product
code

40.5

JSF.5

20.0

JSF.75

Notes: JSF.5: available in 5 colours. Rated voltage 50V AC/120V DC (ELV).


Not suitable for connection to mains.
JSF.75: available in 16 colour combinations. Rated voltage 250/250V.
Both Flat figure 8 cables available in 100m and 500m spools.

MICROPHONE

COMMUNICATIONS

Tinned Copper, PE insulated, twisted pair, foil shield,


tinned Copper drain wire, PVC jacket. Rating 300V 60C.

Pack
size
m

Conductor
size

Nominal
O.D.
mm

Nominal
capacitance
pF/500m

Product
code

305 box
305 reel

16/0.25 (18 AWG)


16/0.25 (18 AWG)

5.6
5.6

79*
79*

144**
144**

J8760060U1000
J87600601000

4.5
4.5

79*
79*

154**
154**

J8761060U1000
J87610601000

Note: 7/0.32 (20 AWG) Drain Wire

305 box
305 reel

7/0.25 (22 AWG)


7/0.25 (22 AWG)

Note: 7/0.25 (22 AWG) Drain Wire


*Capacitance between conductors.
**Capacitance between one conductor and other conductors connected to shield.

59

ACCESSORIES

GLANDS
Dim.B.

ALCO EARTH TAGS


Nickel Plated.
Mounting
Dim.A
mm

Dimension
B
mm

16
20
25
32
40
50
63
212

7.0
7.0
10.3
11.9
13.5
13.5
13.5
13.5

Dim.A.

Overall
length
mm

Between
centres
mm

55.0
55.5
69.0
90.0
108.0
126.0
141.0
150.0

34.0
34.9
41.3
54.0
63.5
76.2
84.1
95.3

Thickness Carton
quantity
mm
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

30
30
20
20
20
5
1
1

Product
code
ET16
ET20
ET25
ET32
ET40
ET50
ET63
ET75

ALCO LOCKNUTS
Nickel Plated (Unplated locknuts
use prefix U 16 to 63mm).
Mounting threading
diameter
mm

Dimension
across corner
mm

Carton
quantity

Product
code

2 26TPI
16
20
25
32
40
50
63
212 BSP
234 BSP
3 BSP
314 BSP
312 BSP
4 BSP

22
24
30
37
45
55
65
83
111
111
123
131
131
142

30
30
20
20
20
5
5
1
1
1
1
1
1
1

PLN12
PLN16
PLN20
PLN25
PLN32
PLN40
PLN50
PLN63
LN2.5
LN2.75
LN3
LN3.25
LN3.5
LN4

60

GLANDS

ACCESSORIES

ALCO PVC SHROUDS


Orange (Black also
available: add B suffix).

Cable
Overall
Inside
Outside
Dimension A Dimension B Diameter C Diameter D
mm
mm
mm
mm
7.0
14.0
17.0
25.5
30.0
32.7
33.7

70
70
85
85
97
110
125

Dia.C.

Dim.A.

23
29
39
48
56
71
73

27
33
41
50
58
73
75

Dia.D.

Dim.B.

Carton
quantity

Product
code

50
40
20
20
5
5
5

SG1
SG2
SG3
SG4
SG5
SG6
SG7

CLIPSAL A4 INDUSTRIAL GLANDS


TO SUIT OLEX VAROLEX CABLE
Thread size
metric

Conductor size
mm2

Olex product
code

Clipsal product
code

20
25
25
25
25
32
32
32
40
50
50
50
63
63
75
75

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

FTDP05AA003
FTDP07AA003
FTDP09AA003
FTDP11AA003
FTDP13AA003
FTDP15AA003
FTDC17AA003
FTDC18AA003
FTDC19AA003
FTDC20AA003
FTDC22AA003
FTDP23AA003
FTDP24AA003
FTDP25AA003
FTDP26AA003
FTDP27AA003

A4 20
A4 25
A4 25
A4 25
A4 25
A4 32
A4 32
A4 32
A4 40
A4 50S
A4 50S
A4 50
A4 63S
A4 63
A4 75S
A4 75

61

ACCESSORIES

UA GLANDS

ALCO SERIES
UA GLANDS

Dia.A.

Economical gland suitable for use with


unarmoured circular constructed cables.
Mounting thread
Diameter
Length
mm
mm
2 BSP
16
16
16
20
20
20
25
25
32
32
40
40
50
50
50
50
63
63
63
2.5 BSP
2.75 BSP
3 BSP
3.5 BSP
3.5 BSP
4 BSP
4 BSP
1

62

10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
19
19
19
29
29
35
35
35
35
36

Cable dimensions Dia. A


Minimum
Maximum
mm
mm
0.00
0.00
6.10
7.90
5.70
9.20
12.00
14.75
18.30
20.60
23.90
26.20
29.75
32.50
35.00
38.00
41.30
44.45
48.50
52.80
55.50
62.40
69.30
76.10
83.00
89.90
96.60

Note: UA12 Gland is supplied complete with locknut.

6.10
6.10
8.00
9.20
9.20
12.00
14.75
18.30
20.60
23.90
26.20
29.75
32.50
35.00
38.00
41.30
44.45
48.50
52.80
57.00
62.40
69.30
76.10
83.00
89.90
96.60
103.0

Dim.B.

Dim. B

Product
code

mm
16
16
16
16
18
18
18
19
19
20
20
25
25
29
29
29
29
30
30
43
35
35
35
48
48
48
48

UA12
UA16S
UA16
UA16L
UA20A
UA20B
UA20C
UA25A
UA25B
UA32A
UA32B
UA40A
UA40B
UA50A
UA50B
UA50C
UA50D
UA63A
UA63B
UA63C
UFPR250A
UFPR275A
UFPR300A
UFPR350A
UFPR350B
UFPR400A
UFPR400B

UG GLANDS

ACCESSORIES

ALCO SERIES
UG GLANDS

Dia.A.

Premium gland suitable for use with


unarmoured circular constructed cables.
Mounting thread
Diameter
Length
mm
mm
20
20
20
20
25
25
25
25
32
32
32
40
40
40
40

10
10
10
10
10
10
10
10
10
10
10
15
15
15
15

Cable dimensions Dia. A


Minimum
Maximum
mm
mm
8.30
9.90
11.90
13.00
14.70
15.90
17.50
19.00
20.60
22.20
23.80
25.80
27.00
28.60
30.20

9.90
11.90
13.00
14.70
15.90
17.50
19.00
20.60
22.20
23.80
25.80
27.00
28.60
30.20
31.80

Dim.B.
Dim. B

Product
code

mm
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
24.0
24.0
24.0
29.0
29.0
29.0
29.0

UG1B
UG1C
UG2A
UG2B
UG3A
UG3B
UG3C
UG3D
UG4A
UG4B
UG4C
UG5A
UG5B
UG5C
UG5D

63

ACCESSORIES

UFPR GLANDS

ALCO SERIES
UFPR GLANDS

Dia.A.

Flameproof and weatherproof


gland suitable for use with
unarmoured circular constructed cables.

Dim.B.

Mounting thread Cable dimensions Dimension Dimension SG Carton Product


Diameter A
across
B
shroud qty
code
Diameter Length Minimum Maximum corner
mm
mm
mm
mm
mm
mm
20
20
20
25
32
32
40
40
50
50
63
63
2.5 BSP
2.75 BSP
3 BSP
3.5 BSP
3.5 BSP
4 BSP
4 BSP

64

12
12
13
15
18
18
20
20
29
29
29
29
29
29
35
35
35
35
36

6.2
9.1
12.0
14.5
18.2
21.9
25.6
29.8
34.2
39.1
44.0
48.7
55.5
62.4
69.3
76.1
83.0
89.9
96.6

9.1
12.0
14.5
18.2
21.9
25.6
29.8
34.2
39.1
44.0
48.7
55.5
62.4
69.3
76.1
83.0
89.9
96.6
103.0

25.3
27.5
30.2
36.0
41.6
45.9
49.8
55.0
72.1
72.1
87.6
87.6
97.4
105.0
113.0
127.0
127.0
143.0
143.0

17
17
17
21
22
22
22
22
34
34
35
35
35
35
35
48
48
48
48

1
1
2
3
4
4
5
5
6
7

15
15
15
10
5
5
3
3
2
2
2
2
1
1
1
1
1
1
1

UFPR20A
UFPR20B
UFPR20C
UFPR25A
UFPR32A
UFPR32B
UFPR40A
UFPR40B
UFPR50A
UFPR50B
UFPR63A
UFPR63B
UFPR250A
UFPR275A
UFPR300A
UFPR350A
UFPR350B
UFPR400A
UFPR400B

G GLANDS

ACCESSORIES
E

ALCO SERIES
G GLANDS
Dia.A.

Dia.B.

Standard gland suitable for indoor use with armoured


circular cables in general areas.
Mounting thread
Diameter
Length
mm

mm

16
20
20
25
25
32
32
40
50
50
63
212 BSP
212 BSP

10
10
10
10
10
10
10
15
15
15
19
19
19

Cable dimensions
Dia. A
Dia. B
obed
overall
mm
mm
7.2
11.0
13.8
16.3
18.8
22.8
26.5
32.8
38.5
44.5
56.3
60.4
66.7

10.8
17.0
20.0
22.5
26.0
30.0
34.0
41.5
49.0
55.5
68.3
73.0
79.4

SWA
diameter

Product
code

mm

Dim.
E SWA
exposed
mm

0.91.25
0.91.25
0.91.25
0.91.25
1.251.6
1.251.6
1.62.0
1.62.0
2.02.5
2.02.5
2.53.15
2.53.15
2.53.15

8.0
8.0
8.0
8.0
10.5
12.0
12.0
14.0
15.5
15.5
17.5
21.5
21.5

G164
G204
G206
G254
G256
G324
G326
G405
G503
G505
G636
G753
G755

65

ACCESSORIES
ALCO SERIES
WG GLANDS

WG GLANDS

Dia.A.

Dia.B.

Dim.C.

Weatherproof gland suitable for


use with armoured circular cables in general areas.
Mounting thread
Diameter Length
mm

mm

16
14.00
16
14.00
20
14.00
20
14.00
20
14.00
20
14.00
25
14.00
25
14.00
32
14.00
32
14.00
40
15.00
40
15.00
40
15.00
50
15.00
50
15.00
50
15.00
50
15.00
63
19.00
63
19.00
63
19.00
212 BSP23.80
212 BSP23.80
212 BSP23.80

66

Cable acceptance detail


Dia. A
obed
mm

Dia. B
overall
mm

6.00
7.20
8.00
9.75
11.00
13.75
16.25
18.75
22.75
26.50
28.50
30.75
32.75
35.75
38.50
41.65
44.45
48.80
52.40
56.25
60.35
63.50
66.70

9.60
10.80
12.00
15.50
17.00
20.00
22.50
26.00
30.00
34.00
37.00
39.50
41.50
45.00
49.00
53.50
55.50
60.40
63.50
68.30
73.00
76.20
79.40

Armour
wires
mm

Dim.
C
mm

0.90
0.90
0.500.90
0.901.25
0.901.25
0.901.25
0.901.25
1.251.60
1.251.60
1.602.00
1.602.00
1.602.00
1.602.00
2.002.50
2.002.50
2.002.50
2.002.50
2.503.15
2.503.15
2.503.15
2.503.15
2.503.15
2.503.15

36.0
36.0
40.0
40.0
40.0
40.0
40.0
47.0
53.0
53.0
61.0
61.0
61.0
74.0
74.0
74.0
74.0
80.0
80.0
80.0
84.0
84.0
84.0

Length of Product
armour
code
to be
exposed
mm
8.00
8.00
8.00
8.00
8.00
8.00
8.00
10.50
12.00
12.00
14.00
14.00
14.00
15.50
15.50
15.50
15.50
17.50
17.50
17.50
23.00
23.00
23.00

WG162
WG164
WG202
WG203
WG204
WG206
WG254
WG256
WG324
WG326
WG403
WG404
WG405
WG502
WG503
WG504
WG505
WG634
WG635
WG636
WG753
WG754
WG755

FLPW GLANDS
ALCO SERIES
FLPW GLANDS

ACCESSORIES
Dia.B.

Dia.A.

Flameproof and weatherproof gland suitable


for use with armoured circular cables in flameproof areas.
Mounting thread
Diameter

Length

mm

mm

20
20
20
20
20
25
25
25
25
32
32
32
32
40
40
40
50
50
50
50
63
63
63
63
212 BSP
212 BSP
212 BSP

15.80
15.80
15.80
15.80
15.80
19.00
19.00
19.00
19.00
25.40
25.40
25.40
25.40
25.40
25.40
25.40
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60

Cable acceptance detail


Dia. A
obed
mm
Min.
6.00
7.90
9.20
10.60
12.60
13.40
14.60
15.90
17.10
18.40
20.40
22.40
24.40
26.10
28.10
30.40
32.40
35.40
38.10
41.30
44.10
45.60
48.40
52.00
55.90
60.00
63.10

Max.
8.00
10.00
11.00
12.50
14.00
15.00
16.30
17.50
18.80
20.80
22.90
24.80
26.50
28.50
30.80
32.80
35.80
38.50
41.70
44.50
46.00
48.80
52.40
56.30
60.40
63.50
66.70

Dim.C.

Length of Product
armour
code
Dim. to be
C exposed
mm
mm

Dia. B
overall
mm

Armour
wire size
mm

12.00
15.50
17.00
20.00
20.00
22.50
22.50
26.00
26.00
30.00
30.00
34.00
34.00
37.00
39.50
41.50
45.00
49.00
53.50
55.50
57.20
60.40
63.60
68.30
73.00
76.20
79.40

0.500.90 53.0
0.901.25 54.0
0.901.25 54.0
0.901.25 54.0
0.901.25 54.0
0.901.25 56.0
0.901.25 56.0
1.251.60 56.0
1.251.60 56.0
1.251.60 65.0
1.251.60 65.0
1.602.00 65.0
1.602.00 65.0
1.602.00 73.0
1.602.00 73.0
1.602.00 73.0
2.002.50 90.0
2.002.50 90.0
2.002.50 90.0
2.002.50 90.0
2.002.50 97.0
2.503.15 97.0
2.503.15 97.0
2.503.15 97.0
2.503.15 102.0
2.503.15 102.0
2.503.15 102.0

11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
13.5
13.5
13.5
13.5
15.5
15.5
15.5
17.0
17.0
17.0
17.0
19.0
19.0
19.0
19.0
23.0
23.0
23.0

FLPW202
FLPW203
FLPW204
FLPW205
FLPW206
FLPW253
FLPW254
FLPW255
FLPW256
FLPW323
FLPW324
FLPW325
FLPW326
FLPW403
FLPW404
FLPW405
FLPW502
FLPW503
FLPW504
FLPW505
FLPW633
FLPW634
FLPW635
FLPW636
FLPW753
FLPW754
FLPW755

67

CURRENT RATINGS

FLEXIBLE CORDS

ELECTRICAL DATA & CURRENT RATINGS


In accordance with wiring regulation AS/NZS3000.
Nominal Current
conductor carrying
area
capacity
mm2
A
0.5
0.75
1.0
1.5
2.5
4.0

3
7.5
10
15
20
25

Maximum D.C. resistance at 20C


Single core
/km
P
37.10
24.70
18.50
12.70
7.60
4.71

T
38.20
25.40
19.10
13.00
7.82
4.85

Multicore
/km
P
39.00
26.00
19.50
13.30
7.98
4.95

Where a flexible cord is wound on a drum, multiply current


carrying capacities by the following factor:
Number of layers: 1
2
3
4
Derating factor: 0.85 0.65 0.45 0.35

68

T
40.10
26.70
20.00
13.70
8.21
5.09

Voltage drop
Single Three
phase phase
mV/A.m

64
47
32
18
13

55
41
28
16
11

COPPER AERIAL

CURRENT RATINGS

PVC AERIAL CABLES


CURRENT CARRYING CAPACITY COPPER CONDUCTOR
Nominal Number
conductor and
area
nominal
diameter
of wires
mm2
no/mm
6
10
16
25
35
50
70
95
120
150
185

7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.78
19/2.14
37/1.78
37/2.03
37/2.25
37/2.52

1 core
insulated
conductors
still
air
35
48
65
88
105
130
165
200
235
265
310

1.0m/s
wind
70
96
125
165
205
240
305
360
425
475
540

2 and
3 core (a)
parallel webbed

3 and
4 core (b)
twisted

still
air

1.0m/s
wind

still
air

30
40
52

50
68
90

26
36
47
63

3
Phase
Voltage
Drop
1.0m/s at 50Hz
still mV/A.m
48
65
85
115

6.71
4.02
2.56
1.67
1.26
0.988
0.767
0.639
0.574
0.530
0.494

Note: The current carrying capacities are based on an air ambient temperature of 40C, a maximum
conductor temperature of 75C and exposure to direct sunlight having an intensity of 1000W/m2.
The values are based on the use of black PVC.
(a) Also for 2 conductor neutral screened aerial cable.
(b) Also for 3 and 4 conductor neutral screened aerial cable.
Under normal circumstances there will always be some air movement and the rating for 1.0m/s wind
is recommended.
General Note applies to all following current rating tables.
Reference should be made to AS/NZS3008.1 for the following derating factors for
(a) Grounded Circuits
(b) Cables fixed to underside of ceilings
(c) Cables on perforated or unperforated trays
(d) Ambient temperature and depth factors

69

CURRENT RATINGS

FLEXIBLES

FLEXIBLE CABLES
Nominal
conductor
area

Number
and nominal
diameter
of wires

mm2

no/mm

6
10
16
25
35
50
70
95
120
150
185

84/0.30
77/0.40
126/0.40
209/0.40
285/0.40
380/0.40
203/0.67
259/0.67
336/0.67
427/0.67
518/0.67

Single Phase
Protected
Exposed
from sun
to sun

Three Phase
Protected
Exposed
from sun
to sun

R-EP-90/
R-CPE-90

R-EP-90/
R-CPE-90

R-EP-90/
R-CPE-90

54
74
99
135
165
195
250
290
340
390
440

43
58
77
105
125
145
185
210
245
280
315

R-EP-90/
R-CPE-90

46
63
85
115
140
165
215
250
290
335
380

37
50
66
88
105
125
155
180
210
240
270

WELDING CABLES CURRENT RATINGS ELECTRICAL DATA


Nominal
conductor
area
(mm2)

Maximum duty cycle (%)


100

60

30

25

8
10
16
25
35
50
70
95
120
150
185
240

80
90
125
165
205
260
325
390
455
535
600
715

100
120
160
210
265
335
415
505
585
690
775
920

145
165
225
300
375
475
590
715
830
975
1095
1305

160
180
245
330
410
520
645
780
910
1070
1200
1430

Max D.C.
resistance
at 20C
(m/m)
1.843
1.162
0.749
0.530
0.375
0.267
0.198
0.153
0.123
0.097
0.076

Duty Cycle AS1966


Cycle

Continuous
Heavy
Light industrial
Limited input

100%
60%
30%
25%

Duty cycle is defined as the ratio of the total time a cable carries a welding current, to the total time
that the welding supply is available, expressed as a percentage. The 100% duty cycle is based on a
cycle time to one hour, other duty cycles on a cycle time of five minutes.

70

Power Cable Application


Welding Cables comply with the requirements of 0.6/1kV single core unsheathed power cables in
AS/NZS5000.1 and are therefore suitable for use in a variety of applications where flexible power
connections are required.

71
96
120
145
185
230
270
305
355
425
495
580
670
790

68
92
115
140
175
215
250
285
330
395
455
530
620
730

Al

Cu
16
21
29
39
49
67
89
120
145
175
225
275
320
365
425
510
580
680
780
900

mm2 Cu
1 16
1.5 21
2.5 30
4 40
6 51
10 69
16 92
25 125
35 155
50 185
70 240
95 295
120 345
150 395
185 460
240 550
300 640
400 740
500 870
630 1010

Al

Spaced
from
surface

Cond. Spaced
size

Unenclosed

Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
310
360
430
495
580
670
770

55
75
93
115
145
180
210
240
280
335
385
455
530
630

Al

Cu
13
16
22
30
38
53
71
97
115
140
175
210
250
280
325
385

57
79
92
110
140
165
195
225
255
305

Al

Cu
10
13
18
24
31
42
57
79
92
110
140
165
195
225
255
300

95
125
145
175
215
255
295
330
375
435
490
560
640
740

Al

Cu
18
24
33
42
53
71
91
120
145
170
210
260
295
335
380
450
510
590
670
770
70
92
110
135
165
200
230
260
300
350
400
465
530
620

Al

Cu
21
27
37
48
60
79
100
135
160
190
235
285
320
360
415
480
560
630
730
830

4.68
2.95
2.14
1.582
1.100
0.804
0.644
0.535
0.439
0.352
0.300
0.256
0.226
0.202

Al

Single
phase
voltage
drop
mV/A.m

Cu
51.6
33.0
18.0
11.2
7.50
4.49
78 2.81
100 1.78
125 1.29
145 0.963
180 0.680
220 0.507
250 0.415
285 0.352
325 0.301
380 0.255
430 0.229
500 0.209
570 0.194
660 0.181

Al

Buried direct Underground ducts

Al Cu
24
31
43
56
71
94
28 120
37 160
46 190
225
275
330
380
425
480
560
630
710
800
900

Completely
surrounded
by thermal
insulation

Al Cu
6
8
12
16
20
27
45 36
62 48
72 59
87
110
130
155
175
200
235



Touching In conduit or
unenclosed partially
surrounded by
Conduit thermal
in air insulation

Enclosed

CURRENT CARRYING CAPACITY A

21 CORE PVC


CURRENT RATINGS

SINGLE PHASE CURRENT RATINGS


Two single core V90 PVC or PVC/PVC 0.6/1kV cables.

71

72

mm2 Cu
1
20
1.5 26
2.5 36
4
48
6
61
10
84
16 110
25 150
35 185
50 230
70 290
95 360
120 420
150 485
185 570
240 680
300 790
400 920
500 1080
630 1260

Al

87
115
145
175
225
280
330
375
440
530
610
720
850
1000

Cond. Spaced
size

Cu
20
25
36
47
60
82
110
145
175
215
275
340
395
450
520
620
720
840
970
1110

Al

84
110
135
165
210
260
305
350
405
485
560
660
770
900

Spaced
from
surface

Unenclosed

Cu
16
20
28
37
47
65
86
115
145
175
225
280
325
375
435
520
610
710
820
950

Al

67
91
110
135
175
215
255
290
340
410
475
560
660
770

Cu
16
20
28
37
47
65
86
115
145
175
220
260
310
350
400
475

Al
12
16
22
30
39
54
67
91
110
135
175
215
255
290
340
400

Cu
14
17
24
32
40
56
74
100
120
145
180
215
255
285
330
390

Al
11
13
19
25
32
44
58
81
94
115
140
170
200
230
260
310

Touching In non-metallic wiring


unenclosed partially
Non-metallic surrounded
wiring en- by thermal
closure in air insulation

Enclosed

Cu
8
10
14
19
24
32
43
58
72

Al

105
140
165
200
245
290
330
370
425
490
560
640
730
830

Buried
direct

Al
Cu

28

36

50

64

80
105
33 140
45 180
56 215
255
315
375
425
480
540
630
710
810
910
1030

Completely
surrounded
by thermal
insulation

CURRENT CARRYING CAPACITY A

Cu
21
27
37
48
60
80
105
135
160
195
240
290
335
375
435
510
580
670
760
890

Al

80
105
125
150
185
225
260
290
335
400
450
530
610
720

Cu
24
31
42
55
68
90
115
150
180
215
265
315
365
410
470
550
630
720
820
950

Al

89
115
140
165
205
245
285
320
365
425
490
560
650
750

Underground nonmetallic wiring enclosure

CURRENT RATINGS
2 1 CORE XLPE

SINGLE PHASE CURRENT RATINGS


Two single core XLPE/PVC 90 0.6/1kV cables.

66
88
110
130
165
205
240
270
315
375
430
500
580

62
83
100
125
155
190
225
255
295
350
400
465
540

Al

Cu
14
18
26
34
44
60
80
105
130
160
200
250
290
330
375
445
510
590
670

Al

mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

Cu
15
19
27
37
46
64
85
115
140
170
215
265
305
350
405
475
550
630
720

Touching

Cond. Spaced
size

Unenclosed

Cu
11
14
20
26
34
47
63
88
105
125
155
190
225
255
295
345
400
465
540

48
67
78
94
120
145
170
190
220
260
300
350
405

Al

Conduit
in air
round
cable

Cu
13
17
22
29
37
50
66
89
105
125

50
67
78
94

Al

Cu
10
13
18
24
31
43
57
79
92
110
140
165
195
220
255
300
345
405
465
44
62
72
87
110
130
155
175
200
240
275
320
370

Al

In conduit or
unenclosed partially
surrounded by
Conduit in air thermal
flat cable insulation

Enclosed

Cu
7
9
13
17
22
30
40
53
65

31
41
51

Al

Completely
surrounded
by thermal
insulation

CURRENT CARRYING CAPACITY A

Cu
22
28
40
52
65
87
115
145
180
210
260
310
355
400
450
520
590
660
740
88
115
140
165
200
240
275
310
350
405
460
530
600

Al

Cu
17
22
31
40
51
68
88
115
140
165
205
250
290
325
370
430
495
560
650
68
89
110
130
160
195
225
250
290
335
390
445
520

Al

Buried direct U/ground ducts

Cu
51.6
33.0
18.0
11.2
7.50
4.46
2.81
1.78
1.28
0.951
0.673
0.498
0.405
0.342
0.290
0.243
0.215
0.194
0.180

4.66
2.93
2.13
1.57
1.10
0.798
0.638
0.528
0.431
0.343
0.290
0.245
0.215

Al

Single
phase
voltage
drop
mV/A.m

2 CORE PVC
CURRENT RATINGS

SINGLE PHASE CURRENT RATINGS


Two core V90 PVC PVC 0.6/1kV cables.

73

74

mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

Cond.
size

Cu
18
24
34
45
57
78
105
140
175
210
270
330
385
440
510
600
690
800
920

Al

81
110
135
165
210
255
300
340
395
470
540
640
730

Spaced

Cu
17
22
31
42
53
73
97
130
160
195
250
310
360
410
475
560
640
750
850

Al

75
100
125
155
195
240
280
320
370
440
510
590
680

Touching

Unenclosed

Cu
13
17
24
33
42
59
79
110
130
160
200
240
285
325
375
445
520
600
770

Al
10
13
18
24
32
44
60
84
99
120
155
185
220
250
290
350
405
475
620

Cu
14
17
24
32
41
56
74
105
120
145
180
215
255
285
330
390
450
520
620

Al
11
14
18
25
32
44
58
81
94
115
140
170
200
230
265
310
355
415
495

In non-metallic wiring
unenclosed partially
surrounded
Non-metallic
by thermal
wiring
enclosure in air insulation

Enclosed

Cu
9
11
16
21
27
36
49
66
81

Al

38
51
63

Completely
surrounded
by thermal
insulation

CURRENT CARRYING CAPACITY A

Cu
26
33
46
60
75
100
130
170
205
245
300
360
410
460
520
600
680
770
860

Al

100
130
160
190
235
280
320
355
405
470
530
610
690

Buried
direct

Cu
20
25
35
46
57
77
100
130
160
190
235
285
325
375
425
500
570
650
750

Al

78
100
120
145
180
220
255
290
330
390
450
520
600

Underground
non-metallic
wiring enclosure

CURRENT RATINGS
2 CORE XLPE

SINGLE PHASE CURRENT RATINGS


Two core XLPE/PVC 90 0.6/1kV cables.

Cu
14
17
25
33
42
56
77
105
125
155
195
245
285
330
385
455
530
610
710
820

Al

59
80
99
120
155
190
225
255
300
355
415
485
570
670

Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
310
355
425
490
570
660
760

Al Cu
11
14
20
26
34
47
55 62
75 87
93 100
115 125
145 155
180 185
210 220
240 250
280 285
330 340
385 390
455 455
530 530
630 620

Al Cu
10
12
17
23
29
39
48 52
68 72
79 84
95 100
120 125
145 150
170 175
195 200
220 230
265 270
305 310
355 360
410 415
480 485

Al Cu
6
8
12
16
20
27
40 36
56 48
65 59
79
99
120
140
160
180
215
250
290
335
390

Al Cu
21
27
37
49
61
81
28 105
37 135
46 160
190
235
280
315
355
400
465
520
590
670
750

Al

61
80
97
115
145
175
200
230
260
305
350
405
465
540

Cu
19
25
34
44
54
72
92
120
145
170
210
255
290
320
370
430
495
560
650
730

Cu
44.7
28.6
15.6
9.71
6.49
3.86
71 2.43
92 1.54
110 1.12
130 0.834
165 0.589
195 0.439
225 0.359
255 0.305
290 0.261
335 0.221
385 0.198
490 0.181
510 0.168
580 0.157

Al

Al
Cu

44.7

28.6

15.6

9.71

6.49

3.86
4.05 2.43
2.55 1.55
1.85 1.12
1.37 0.84
0.952 0.597
0.696 0.449
0.558 0.371
0.463 0.319
0.380 0.277
0.305 0.240
0.260 0.219
0.222 0.202
0.196 0.191
0.175 0.181

Al

68
93
115
140
180
225
260
300
345
415
485
570
660
790

Al Cu
16
20
28
37
46
61
81 80
105 105
125 125
145 150
180 185
215 225
245 260
275 290
310 335
365 390
410 450
470 510
540 590
620 660

Underground
ducts

mm2 Cu
1 16
1.5 20
2.5 29
4 38
6 49
10 67
16 89
25 120
35 150
50 180
70 230
95 285
120 335
150 385
185 445
240 540
300 620
400 730
500 850
630 990

Buried
direct
Three phase
voltage drop
mV/A.m

Enclosed

CURRENT CARRYING CAPACITY A

Cond. Spaced Spaced Touching In conduit or un- Completely


size
from
enclosed partially surrounded
surface
by thermal
surrounded by
thermal
Conduit
insulation
in air

Unenclosed

Al

4.05
2.55
1.85
1.37
0.956
0.702
0.565
0.472
0.391
0.319
0.276
0.240
0.216
0.197

31 CORE PVC


CURRENT RATINGS

THREE PHASE CURRENT RATINGS


Three single core V90 PVC or PVC/PVC 0.6/1kV cables.

75

76

Enclosed

mm2 Cu
1 19
1.5 25
2.5 35
4 46
6 59
10 81
16 110
25 145
35 180
50 220
70 280
95 350
120 410
150 470
185 550
240 660
300 770
400 900
5001050
6301230

Al Cu Al
16
21
30
40
50
69
84 92 71
115 125 97
140 155 120
170 190 145
220 240 185
270 300 230
320 350 270
365 405 315
425 470 365
510 560 440
600 650 510
700 760 600
830 870 700
9801010 820

Cu
16
20
28
37
47
65
86
115
145
175
225
280
325
375
435
520
600
700
810
940

Al Cu
14
18
25
33
42
58
67 78
91 110
110 125
135 155
175 190
215 230
255 270
290 310
340 355
405 420
470 485
560 560
650 650
770 760

Al Cu
10
12
17
28
36
50
64 66
90 92
105 105
125 130
160 160
195 195
230 225
260 255
300 295
360 350
415 400
485 465
560 540
660 630

Al Cu
8
10
14
19
24
32
53 43
73 58
85 72
100
130
155
180
205
235
275
320
370
425
500

Al Cu
24
31
42
55
68
91
33 115
45 150
56 180
215
260
315
365
400
450
520
590
670
750
840

Underground
ducts

Al Cu Al Cu Al Cu
18
22
46.8
23
28
30.0
32
39
16.4
41
50
10.2
52
62
6.81
69
81
4.05
96 89 69 105 80 2.55
115 115 90 135 105 1.62
140 140 110 160 125 1.17
165 170 130 195 150 0.872
205 210 165 235 185 0.615
245 250 195 280 220 0.457
275 290 225 325 255 0.373
310 330 255 365 280 0.316
350 375 290 420 325 0.269
410 440 345 485 380 0.227
465 510 400 560 435 0.202
530 580 455 640 500 0.183
600 670 540 720 570 0.170
690 760 620 830 660 0.159

Buried
direct

CURRENT CARRYING CAPACITY A

Cond. Spaced Spaced Touching In conduit or un- Completely


size
from
enclosed partially surrounded
surface
by thermal
surrounded by
thermal
Conduit
insulation
in air

Unenclosed

Cu
46.8
30.0
16.4
10.2
6.81
4.05
4.25 2.55
2.67 1.62
1.94 1.18
1.43 0.878
0.997 0.623
0.727 0.467
0.582 0.385
0.482 0.330
0.394 0.285
0.314 0.245
0.266 0.222
0.226 0.205
0.197 0.193
0.177 0.182

Al

Three phase
voltage drop
mV/A.m

4.25
2.67
1.94
1.44
1.00
0.733
0.589
0.491
0.404
0.327
0.281
0.243
0.216
0.198

Al

CURRENT RATINGS
31 CORE XLPE

THREE PHASE CURRENT RATINGS


Three single core XLPE/PVC 90 0.6/1kV cables.

56
75
93
115
145
180
205
235
275
325
375
440
500

53
71
87
105
135
165
195
220
255
305
345
405
460

Al

Cu
12
15
22
29
37
51
68
91
110
135
170
215
245
280
325
385
440
500
570

Al

mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
305
350
410
470
540
620

Touching

Cond. Spaced
size

Unenclosed

Cu
10
13
18
24
31
42
56
79
92
110
140
165
195
225
260
305

43
60
70
84
105
125
150
170
195
230

Al

Cu
12
15
20
26
34
46
60
83
92
110

46
63
70
84

Al

Cu
10
12
17
22
29
39
52
72
84
100
125
150
175
200
230
270

40
56
65
79
99
120
140
160
180
215

Al

Conduit In conduit or
in air unenclosed partially
round surrounded by
cable
Conduit in air thermal
flat cable insulation

Enclosed

Cu
6
8
11
15
19
25
34
46
56

26
35
43

Al

Completely
surrounded
by thermal
insulation

CURRENT CARRYING CAPACITY A

Cu
19
24
34
44
55
74
96
125
150
180
220
265
300
335
380
440
495
560
620
75
97
115
140
170
205
235
265
300
345
390
450
500

Al

Cu
15
19
26
34
43
57
74
96
115
140
175
210
240
270
310
370
415
480
540
58
75
91
110
135
165
190
210
245
290
325
385
435

Al

Buried direct U/ground ducts

Cu
44.7
28.6
15.6
9.71
6.49
3.86
2.43
1.54
1.11
0.829
0.583
0.431
0.351
0.296
0.251
0.210
0.186
0.168
0.156

4.04
2.54
1.84
1.36
0.948
0.691
0.552
0.457
0.373
0.297
0.251
0.212
0.186

Al

Three
phase
voltage
drop
mV/A.m

3 & 4 CORE PVC


CURRENT RATINGS

THREE PHASE CURRENT RATINGS


Three and four core V90 PVC/PVC 0.6/1kV cables.

77

78

mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

Cond.
size

Cu
16
20
28
38
48
66
88
120
145
180
230
285
330
375
435
520
590
680
780

Al

68
93
115
140
180
220
255
295
340
405
465
550
630

Spaced

Cu
14
19
26
35
45
62
83
110
135
170
215
265
305
350
405
480
550
630
720

Al

64
86
105
130
165
205
240
270
315
375
430
500
580

Touching

Unenclosed

Cu
12
16
22
29
38
53
70
98
115
140
175
210
250
280
325
385

54
76
89
110
135
165
195
220
255
305

Al

Cu
12
16
21
28
36
50
66
92
105
130
160
195
225
255
295
350

53
73
85
100
130
155
180
205
235
275

Al

In conduit or unenclosed
partially surrounded by
thermal
Conduit insulation
in air

Enclosed

Cu
6
8
11
15
19
25
34
46
56

26
35
43

Al

Completely
surrounded
by thermal
insulation

75
97
115
140
170
205
235
265
300
345
390
450
500

Al

Buried direct

Cu
19
24
34
44
55
74
96
125
150
180
220
265
300
335
380
440
495
560
620

CURRENT CARRYING CAPACITY A

Cu
15
19
26
34
43
57
74
96
115
140
175
210
240
270
310
370
415
480
540
58
75
91
110
135
165
190
210
245
290
325
385
435

Al

U/ground ducts

Cu
46.8
30.0
16.4
10.2
6.80
4.05
2.55
1.61
1.17
0.868
0.609
0.450
0.366
0.307
0.259
0.216
0.190
0.171
0.158

4.24
2.67
1.93
1.43
0.993
0.723
0.577
0.476
0.388
0.307
0.258
0.216
0.189

Al

Three
phase
voltage
drop
mV/A.m

CURRENT RATINGS
3 & 4 CORE XLPE

THREE PHASE CURRENT RATINGS


Three and four core XLPE/PVC 90 0.6/1kV cables.

GENERAL
CABLE SELECTION
The size and type of cable required for a given application should be
selected according to the following criteria:
1. Current carrying capacity and voltage drop
Conductor sizes are nominated by the Wiring Rules (AS/NZS3000)
for the wiring of socket outlets and lighting circuits in domestic and
commercial buildings.
For other types of installations:
a) The cable must be capable of carrying the maximum continuous load
of the circuit, with due regard for the insulating material and conditions
of installation.
b) The voltage drop from the consumers terminals to any point in the
installation must not exceed 5% of the nominal system voltage.
Simplified tables of current ratings and voltage drops for commonly used
cables are given on pages 68 to 78.
In large installations where current ratings are critical, attention is drawn
to the comprehensive tables given in AS/NZS3008.1.1:1998.
2. Installation conditions
Olex cables are available for aerial, underground and submarine
installations as well as in conduit, on racks or trays in air.
Special constructions available include:
 Brass or copper taped or nylon sheathed cables for resistance
to termite and marine borer.
 Steel wire or tape armoured for areas where there is a high risk
of mechanical damage.
 Pyrolex fire performance low smoke halogen free cables for emergency power and lighting and other purposes in areas of high fire risk.
 Lead alloy sheathing as a barrier to moisture or hydrocarbons.
 Envirolex cables with low smoke emission and no halogen
for environmentally sensitive areas.
 Flexolex cables for flexible applications and where flexibility provides
advantages during installation.

79

GENERAL
3. Cable insulating and sheathing materials
Standard Olex cables are available in a number of materials, including
the following:
 Olex PVC (Polyvinyl Chloride) insulated and sheathed cables are the
economic choice for general wiring. They are resistant to occasional
contact with most oils and solvents, clean and easy to handle and
coloured to assist phase identification. PVC is suitable for operating
temperatures up to 90C and 90HT, subject to the requirements
of AS/NZS3000.
PVC is inherently resistant to ultraviolet radiation and although some
colours may fade the material will not significantly degrade due to the
effects of sunlight and weather, maintaining its physical integrity if not
physically abused.
Care should be taken where cables are subjected to extremes of
temperature or contact with crude petroleum, caustic materials
or aromatic solvents.

80

 Olex synthetic rubber (EPR/CPE) insulated and sheathed cables are more
flexible and have better resistance to oils and solvents than PVC.
Olex EPR (Ethylene Propylene Rubber), while not oil resistant, has
excellent dielectric properties and high voltage grades are available for
cables up to 33kV. In addition, EPR is halogen free and therefore does
not emit toxic or corrosive by-products when burnt.
Olex CPE (Chlorinated Polyethylene) is an excellent flexible insulation
and heavy duty sheathing material. Although having lower insulation
resistance than EPR it is suitable for low voltage cable insulation and
is used as such in welding cables because of its oil resistance.
For special purposes a sheath of Olex EA (Ethylene Acrylic) material
can be provided subject to special order. This material is halogen free,
extremely flame retardant and has better oil resistance than CPE.
EPR/EA cables can safely be used in plenum air ducts and other
applications where high flame retardance and freedom from acid gas
emission is required. EPR, CPE and EA are all suitable for continuous
operation up to 90C.

GENERAL
In all cases, cables must be installed in compliance with
the safety requirements of AS/NZS3000.
Particular attention should be paid to the following:
 Current carrying capacities of cables depend on the temperature of the
air or ground in which they are installed and the degree to which heat
can escape. Except for a group of single core cables carrying the phase
currents of a circuit, cables should be spaced to allow heat to escape.
 Wherever cables are installed in close proximity, especially in the
ground, or enclosed in such a way as to restrict heat loss, their current
carrying capacities must be reduced using a derating factor appropriate
to the situation.
 For minimum voltage drop single core cables carrying the phase
currents of a single circuit should be installed as closely as possible
together, to minimise inductive reactance. The preferred formation for
three phase conductors is a trefoil or cloverleaf pattern although flat
formation may also be used. Sheaths should be in contact with one
another in either case.
A single core cable generates an alternating magnetic field around itself
which can cause large increases in voltage drop and power loss due to
transformer effect when ferrous metal (iron and steel) is allowed to
encircle the cable. Steel racking or ladder will not cause trouble, but the
following must be observed:
 Steel wire or tape armour is never used on a single core cable for AC use.
 Where three single phase cables pass through a steel bulkhead all must
pass through the same hole. Where glanding is required it is usual to
cut out a panel and replace this with a non-ferrous (metal or plastic)
plate in which the three or four glands are mounted.

81

GENERAL
Minimum size of Copper earthing conductors.
Nominal area
ACTIVE conductors
mm2

For COPPER
active conductors
mm2

1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

For ALUMINIUM
active conductors
mm2

1.0*
1.5*
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
120
120
120

2.5
2.5
4
6
6
10
10
16
25
25
35
50
70
95
95
120

*Refer Wiring Rules. AS/NZS3000 regarding 1.5 earthing conductors.

Maximum operating temperatures for various types


of cable insulants.
Type
Thermoplastic (PVC)

Elastomer

82

V75
V90
V90-HT
R-EP-90
R-CPE-90
R-S-150

Polyethylene Low Density


Cross linked polyethylene (XLPE)
PILC 0.6/1kV
*V90-HT PVC may be operated up to 105C for restricted periods only.

C
75
90
90*
90
90
150
75
90
80

GENERAL
Conductor resistances for insulated cables for
fixed installations. Solid, stranded conductors;
also refer to AS1125.
Nominal
conductor
area

Conductor
type

Copper

mm2
0.5
1.0*
1.0
1.5*
1.5
2.5*
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Single Core or Multicore


Maximum DC resistance at 20C//km
Tinned

Solid
Solid
Stranded
Solid
Stranded
Solid
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded

36.7
18.2
21.6
12.2
13.8
7.35
7.56
4.70
3.11
1.84
1.16
0.734
0.529
0.391
0.270
0.201
0.154
0.126
0.100
0.0762
0.0607
0.0475
0.0369
0.0286

Aluminium
Plain
36.0
18.1
21.2
12.1
13.6
7.28
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.199
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

1.91
1.20
0.867
0.641
0.443
0.329
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

*Single strand conductors only (solid).

83

GENERAL
Useful 3 phase formulae

kW = kVA  pf
kW =

hp  746
1000  Eff

kW =

Line Amps  Line Volts  1.732  pf


1000

kVA =

kW
pf

kVA =

hp  746
1000  Eff  pf

kVA =

Line Amps  Line Volts  1.732


1000

Line Amps =

kW  1000
Line Volts  1.732  pf

Line Amps =

kVA  1000
Line Volts  1.732

Line Amps =

hp  746
Line Volts  1.732  Eff  pf

kW  1000  Eff
Horsepower
=
(hp) = 746

84

hp =

kVA  1000  Eff  pf


746

hp =

Line Amps  Line Volts  1.732  Eff  pf


746

GENERAL
American conductor sizes M.C.M. & A.W.G. conversion
to mm2.
M.C.M.

mm2

M.C.M.

mm2

1300
1200
1100
1000
950
900
850
800
750
700

659
608
557
507
481
456
431
405
380
355

650
600
550
500
450
400
350
300
250
200

329
304
279
253
228
203
177
152
127
101

Note: The American term mil refers to a milli-inch (1/1000) NOT a millimetre.
A Circular Mil. (C.M.) is the area of a circle 1 mil in diameter.
The term M.C.M. refers to an area of 1000 Circular Mils.
1.0mm2 is approximately 2000 Circular Mils.

A.W.G.

Diameter
mm

mm2

A.W.G.

Diameter
mm

mm2

0000
000
00
0
2
4
6
8

11.68
10.40
9.27
8.25
6.54
5.19
4.12
3.25

107.3
85.0
67.4
53.5
33.6
21.2
13.3
8.4

10
12
14
16
18
20
22
24

2.59
2.05
1.63
1.29
1.02
0.81
0.64
0.51

5.3
3.3
2.1
1.3
0.8
0.5
0.3
0.2

Note: The American Wire Gauge (AWG) was originally known as the Brown & Sharp (B&S) Gauge
and both terms are synonymous.
Note: The gauge number can apply to a single wire or to a standard or bunched conductor.
The cross-sectional areas given apply to single wire only.
Note: The larger gauges are sometimes written using a number to denote the number of zeroes,
e.g. 0 gauge can be written 1/0 and 000 as 3/0.

85

GENERAL
Cable minimum installed bending radii.
Type
Fixed wiring

Flexible Cords

Voltage

PVC or Elastomer or XLPE


(1) Single and Multicore
(a) Overall diameter to & including 25mm
(b) Overall diameter over 25mm
(2) Multicore SWA
(3) Solid Aluminium
PVC or Elastomer

Flexible Cables
Lead Sheath
Paper Insulated

PVC or Elastomer
PVC or Elastomer
Single
Multicore
Single Core
Multicore
Single Core
Multicore
Trailing
Elastomer
(1) Single and Multicore
(2) Single and Multicore
Welding
PVC or Elastomer
Nylon Covered All Cables
HDPE Sheathed All Cables

0.6/1kV
0.6/1kV
0.6/1kV
0.6/1kV
250/440V
0.6/1kV
0.6/1kV
0.6/1kV
Up to 11kV
Up to 11kV
22kV
22kV
33kV
33kV

Factor

4
6
12
8
4
4
4
12
12
15
18
15
20
18

1.1kV
6
3.3kV & above 12
0.6/1kV
6
20
15

Factor  cable overall diameter = minimum internal bending radius.

Motor current table, Amperes (approx.)


kW

86

Power Single phase Three phase


hp
240V
415VkW

0.37
0.55
0.75
1.1
1.5
1.8
2.2
4

0.5
0.75
1
1.5
2
2.5
3
5

2.2
3.2
4.3
6.5
8.6
10.8
13.0
21.6

0.7
1.1
1.4
2.2
2.9
3.6
4.3
7.2

Power
Single phase Three phase
kW
hp
240V
415VkW
5.5
7.5
9.3
11
15
18.5
22

7.5
10
12.5
15
20
25
30

32.4

10.8
14.4
18.0
21.6
28.8
36.0
43.2

GENERAL
Recommended maximum number of thermoplastic insulated
unsheathed single core 0.6/1kV Copper or Aluminium cables
permitted in metallic and non-metallic conduit or pipe.
Nominal
area
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Nominal size of conduit (mm)


16 20 20 25 25 32 32 40 40 50 50 63 63 65 80
LD LD HD LD HD LD HD LD HD LD HD LD HD HD HD
7 11 10 20 17 34
5 9 8 15 13 27
4 7 6 12 10 20
2 4 4 7 6 13
1 3 3 6 5 10
1 2 2 4 4 7
1 1 1 3 3 5
1 1 1 1 3
1 1 1 1 2
1 1 1
1 1 1
1
1
1





31
24
18
11
9
7
5
3
2
1
1
1
1

56
43
33
20
17
12
9
5
4
3
2
1
1
1
1
1

51
40
30
19
15
11
8
5
4
3
2
1
1
1
1

90
69
52
33
27
19
14
9
7
5
4
3
2
1
1
1
1
1

84 148 137
65 114 106
49 86 80
30 54 50
25 44 41
18 31 29
13 23 22
8 14 13
6 11 11
5 9 8
4 7 6
3 5 5
2 4 4
1 3 3
1 2 2
1 1 1
1 1 1
1 1
1 1
1 1




76 106
62 87
44 61
33 46
20 28
16 23
12 17
9 13
7 10
6 8
5 6
4 5
2 4
2 3
1 2
1 1
1 1

Notes:
1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or
with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of
PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn
into the conduit.
2. One earth wire of appropriate size, as determined by the requirements of AS/NZS3000, may be
inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables.

87

GENERAL
Recommended maximum number of thermoplastic insulated
and sheathed single core Copper or Aluminium cables
permitted in metallic and non-metallic conduit or pipe.
 1.0 to 25mm2 450/750V to AS/NZS5000.2
 35 to 630mm2 0.6/1kV to AS/NZS5000.1
Nominal
area
mm2
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

88

Nominal size of conduit (mm)


20
HD

25
HD

32
HD

40
HD

50
HD

63
HD

65
HD

80
HD

100
HD

150
HD

7
7
5
3
3
1
1
1

15
7
7
5
4
3
2
1
1

27
23
17
10
8
6
4
3
1
1
1

43
37
27
19
16
10
7
5
2
1
1
1
1

61
45
31
26
17
12
9
4
3
2
1
1
1
1
1

51
43
29
21
16
6
5
4
3
2
1
1
1
1
1

44
33
23
9
7
6
4
4
3
2
1
1
1
1
1

33
13
10
8
6
5
4
3
3
2
1
1
1

17
13
10
9
7
6
5
4
3
2
1

20
17
14
11
9
7
6
5
4

Notes:
1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or
with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of
PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn
into the conduit.
2. One earth wire of appropriate size, as determined by the requirements of AS/NZS3000, may be
inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables.

GENERAL
Cables in conduit and pipe space factors.
One cable in conduit or pipe
Two cables in conduit or pipe
Three or more in conduit or pipe

50%
33%
40%

Note: The above values should not be exceeded.

Maximum safe pulling tension.


Conductor
area
mm2
1.5
2.5
4
6
10
16

Maximum tension
kN per conductor
Copper
Aluminium
0.11
0.18
0.28
0.42
0.70
1.12

0.08
0.13
0.20
0.30
0.50
0.80

Conductor
area
mm2
25
35
50
70
95

Maximum tension
kN per conductor
Copper
Aluminium
1.75
2.45
3.50
4.90
6.65

1.25
1.75
2.50
3.50
4.75

(1kN = 102kgf)

89

ABBREVIATIONS

A.m
ABC
AC
Al
AS
C
C
CPE
CSA
CSP

90

Ampere metre
aerial bundled cable
alternating current
Aluminium
Australian Standard
core
degree Celsius
Chlorinated Polyethylene
cross-sectional area
Chlorosulphinated
Polyethylene
Cu
Copper
dB
Decibel
DC
direct current
E
earth
EA
Ethylene Acrylic
Eff
efficiency
ELV
Extra Low Voltage
EPR
Ethylene Propylene Rubber
HD
hard drawn
H.D.
heavy duty
HFS-90-TP halogen free sheath
90C thermoplastic
HF-110-R halogen free
110C rubber (sheath)
hp
horsepower
HR
heat resistant
HRC
high rupture capacity
ISDN
Integrated Services
Digital Network
kg
kilogram
kN
kilonewton
kV
kilovolt
kVA
kilovoltamp
kW
kilowatt

LAN
L.D.
mm
MM
nF/km
OD
O.D.
PACW
PE
pf
pF/m
PILC

local area network


light duty
millimetre
Multi mode (Fibre)
nanofarad/kilometre
outside diameter
ordinary duty
plain annealed copper wire
Polyethylene
power factor
picofarad/metre
paper insulated
lead covered
PVC
Polyvinyl Chloride
R-CPE-90 rubber Chlorinated
Polyethylene 90C
R-EP-90
rubber Ethylene Propylene
90C
R-HF-110 rubber halogen free
110C (insulation)
SM
Single Mode (Fibre)
SWA
steel wire armoured
TACW
tinned annealed copper wire
TPW
thermoplastic welding
TPS
thermoplastic switchboard
TPSW
thermoplastic
welding/switchboard
UTP
unshielded twisted pairs
V
volt
V75
75C rated PVC
V90
90C rated PVC
V90HT
90C rated PVC
105C for restricted periods
X-HF-90
XLPE halogen free 90C
XLPE
cross-linked Polyethylene

AUSLEC BRANCHES

New South Wales


124 Adderley Street, Auburn NSW 2144
Phone: (02) 9748 0295
29 Forge Street, Blacktown NSW 2148
Phone: (02) 9622 3777
15 Thirteenth St, Cobar NSW 2835
Phone: (02) 6836 3611
42 Kareena Road, Miranda NSW 2228
Phone: (02) 9525 5099
19 Market Street, Muswellbrook NSW 2333
Phone: (02) 6541 1733
Unit 5, 176180 March Street, Orange NSW 2800
Phone: (02) 6362 4944
96 Batt Street, Penrith NSW 2750
Phone: (02) 4731 5744
43 Mentmore Ave, Rosebery NSW 2018
Phone: (02) 9662 2211
Units 24, 2 Drummond St, Coniston NSW 2521
Phone: (02) 4229 3411
Northern Territory
7 Albatross Street, Winnellie NT 0821
Phone: (08) 8984 4077
Queensland
Cnr Commercial Rd & Leopold St
Fortitude Valley Qld 4006
Phone: (07) 3854 1661
63 Lord Street, Gladstone Qld 4680
Phone: (07) 4972 3133
48 Barkly Highway, Mt Isa Qld 4825
Phone: (07) 4743 5544
Units 2 & 3, 241 Evans Road, Salisbury Qld 4107
Phone: (07) 3272 7355
1719 Madden Street, Aikenvale Qld 4814
Phone: (07) 4779 7955
South Australia
9 Ritana Road, Mt Gambier SA 5290
Phone: (08) 8725 6722

7882 Hardys Road, Torrensville SA 5031


Phone: (08) 8352 6866
8 Cook Street, Whyalla SA 5608
Phone: (08) 8645 9177
Tasmania
20 Wellington Street, Burnie South Tas 7320
Phone: (03) 6431 4366
250260 Murray Street, Hobart Tas 7000
Phone: (03) 6234 2133
Victoria
7 Dawson Street, Ballarat Vic 3350
Phone: (03) 5331 3966
Unit 3, 37 Princes Highway, Doveton Vic 3177
Phone: (03) 9791 7600
283285 Thompsons Road, Geelong Vic 3215
Phone: (03) 5278 1822
1/14 Fitzgerald Road, Laverton North Vic 3026
Phone: (03) 9369 5515
9 Osburn Street, Wodonga Vic 3690
Phone: (02) 6024 2877
Unit 3, 260 Hyde Street, Yarraville Vic 3013
Phone: (03) 9689 5900
Western Australia
172 Boulder Road, Boulder WA 6432
Phone: (08) 9021 3877
5 Halifax Drive, Bunbury WA 6230
Phone: (08) 9725 4133
211 Bannister Road, Canningvale WA 6155
Phone: (08) 9455 1344
220 Lester Avenue, Geraldton WA 6530
Phone: (08) 9921 2444
Lot 1415 Crane Circle, Karratha WA 6714
Phone: (08) 9185 1922
Unit 7, 18 Kewdale Rd, Kewdale WA 6106
Phone: (08) 9451 3433
Lot 1421 Hardies Street, Port Hedland WA 6721
Phone: (08) 9173 3288

91

LAWRENCE & HANSON BRANCHES

Australian Capital Territory


Fyshwick
Phone: (02) 6280 5532
Mitchell
Phone: (02) 6242 9655

92

New South Wales


Albury
Alexandria
Artarmon
Ballina
Bathurst
Berkeley Vale
Brookvale
Campbelltown
Cardiff
Castle Hill
Coffs Harbour
Condell Park
Dubbo
Erina
Gosford
Goulburn
Griffith
Homebush
Hornsby
Hurstville
Inverell
Lakemba
Leichhardt
Lismore
Liverpool
Newcastle
Nowra
Orange
Pambula
Parramatta
Peakhurst
Pyrmont
Rydalmere
Ryde
Seven Hills

Phone: (02) 6041 5055


Phone: (02) 9318 0755
Phone: (02) 9439 3066
Phone: (02) 6686 4955
Phone: (02) 6331 5966
Phone: (02) 4389 1434
Phone: (02) 9938 5288
Phone: (02) 4625 4599
Phone: (02) 4954 5288
Phone: (02) 9634 1322
Phone: (02) 6651 2611
Phone: (02) 9709 2577
Phone: (02) 6882 3188
Phone: (02) 4365 4822
Phone: (02) 4325 0517
Phone: (02) 4822 2377
Phone: (02) 6962 3911
Phone: (02) 9736 3500
Phone: (02) 9476 5666
Phone: (02) 9588 1166
Phone: (02) 6722 3311
Phone: (02) 9740 5622
Phone: (02) 9566 2091
Phone: (02) 6621 2756
Phone: (02) 9601 3488
Phone: (02) 4926 1499
Phone: (02) 4421 7077
Phone: (02) 6362 1888
Phone: (02) 6495 6088
Phone: (02) 9890 7855
Phone: (02) 9534 2099
Phone: (02) 9552 4299
Phone: (02) 9684 1755
Phone: (02) 9808 3555
Phone: (02) 9624 5600

Smithfield
St Marys
Tamworth
Wagga Wagga
Warilla
Windsor
Wollongong

Phone: (02) 9604 7811


Phone: (02) 9623 0099
Phone: (02) 6766 5511
Phone: (02) 6921 4224
Phone: (02) 4296 9166
Phone: (02) 4577 5300
Phone: (02) 4229 3088

Northern Territory
Alice Springs
Phone: (08) 8952 2878
Darwin
Phone: (08) 8984 3900
Katherine
Phone: (08) 8972 2033
Palmerston
Phone: (08) 8932 1511
Queensland
Ayr
Beenleigh
Browns Plains
Bundaberg
Caboolture
Cairns
Capalaba
Coorbaroo
Currumbin
Emerald
Geebung
Gympie
Hervey Bay
Ipswich
Lawnton
Mackay
Mansfield
Maroochydore
Milton
Nambour
Nerang
Noosa
Redcliffe
Rockhampton
Rocklea
Slacks Creek

Phone: (07) 4783 5833


Phone: (07) 3287 2822
Phone: (07) 3800 1069
Phone: (07) 4153 1699
Phone: (07) 5498 6188
Phone: (07) 4053 6055
Phone: (07) 3245 4133
Phone: (07) 3397 9322
Phone: (07) 5534 1766
Phone: (07) 4982 4144
Phone: (07) 3265 4011
Phone: (07) 5482 8377
Phone: (07) 4128 2099
Phone: (07) 3281 2211
Phone: (07) 3205 4344
Phone: (07) 4957 7311
Phone: (07) 3343 2155
Phone: (07) 5443 2633
Phone: (07) 3369 3899
Phone: (07) 5441 1011
Phone: (07) 5527 3511
Phone: (07) 5449 7666
Phone: (07) 3284 4171
Phone: (07) 4927 2066
Phone: (07) 3848 4433
Phone: (07) 3208 7555

LAWRENCE & HANSON BRANCHES

Southport
Sumner Park
Surfers Paradise
Toowoomba
Townsville

Phone: (07) 5532 8166


Phone: (07) 3376 4488
Phone: (07) 5570 2911
Phone: (O7) 4632 3022
Phone: (07) 4775 5866

South Australia
Berri
Blair Athol
Clovelly Park
Glynde
Holden Hill
Kilkenny
Kurralta Park
Lonsdale
Mount Barker
Mount Gambier
Naracoorte
Nuriootpa
Port Adelaide
Port Lincoln
Port Pirie
Salisbury South

Phone: (08) 8582 1900


Phone: (08) 8269 1811
Phone: (08) 8277 9844
Phone: (08) 8337 8177
Phone: (08) 8369 1416
Phone: (08) 8268 7755
Phone: (08) 8297 4566
Phone: (08) 8384 1555
Phone: (08) 8391 2899
Phone: (08) 8725 9244
Phone: (08) 8762 2899
Phone: (08) 8562 3388
Phone: (08) 8341 2744
Phone: (08) 8682 2633
Phone: (08) 8632 3411
Phone: (08) 8281 7022

Tasmania
Devonport
Hobart
Launceston

Phone: (03) 6424 1152


Phone: (03) 6234 2666
Phone: (03) 6331 4955

Victoria
Airport West
Ballarat
Bayswater
Bendigo
Berwick
Brunswick
Coburg
Dandenong
Fawkner
Frankston
Geelong

Phone: (03) 9338 6266


Phone: (03) 5332 1871
Phone: (03) 9729 0388
Phone: (03) 5443 1611
Phone: (03) 9769 9055
Phone: (03) 9387 1244
Phone: (03) 9354 4533
Phone: (03) 9793 4166
Phone: (03) 9357 2933
Phone: (03) 9776 9755
Phone: (03) 5222 3899

Hoppers Crossing Phone: (03) 9742 5911


Horsham
Phone: (03) 5382 2388
Lilydale
Phone: (03) 9739 5500
Mildura
Phone: (03) 5022 1044
Moorabbin
Phone: (03) 9555 8511
Mornington
Phone: (03) 5977 0100
Morwell
Phone: (03) 5134 4028
Mulgrave
Phone: (03) 9560 3100
Nunawading
Phone: (03) 9873 5922
Portland
Phone: (03) 5523 4133
Preston
Phone: (03) 9480 5588
Richmond
Phone: (03) 9428 4345
Ringwood
Phone: (03) 9879 1111
Sale
Phone: (03) 5144 7944
Scoresby
Phone: (03) 9764 1277
Shepparton
Phone: (03) 5821 4922
South Melbourne Phone: (03) 9697 1599
Sunshine
Phone: (03) 9312 5111
Swan Hill
Phone: (03) 5032 3292
Thomastown
Phone: (03) 9464 0664
Traralgon
Phone: (03) 5174 8655
Wangaratta
Phone: (03) 5722 1033
Warrnambool
Phone: (03) 5562 1233
Western Australia
Albany
Phone: (08) 9841 6566
Balcatta
Phone: (08) 9240 2429
Busselton
Phone: (08) 9752 1211
Embleton
Phone: (08) 9272 5344
Joondalup
Phone: (08) 9300 3266
Kelmscott
Phone: (08) 9495 1800
Kenwick
Phone: (08) 9459 8122
Malaga
Phone: (08) 9249 6644
Mandurah
Phone: (08) 9581 9286
Midland
Phone: (08) 9250 1366
Myaree
Phone: (08) 9330 1244
Osborne Park
Phone: (08) 9446 5400
Rockingham
Phone: (08) 9592 1588
Wanneroo
Phone: (08) 9409 1000
Welshpool
Phone: (08) 9351 8955

93

OLEX CABLES SALES OFFICES

HEAD OFFICE
207 Sunshine Road, Tottenham Vic. 3012
Phone 03 9281 4444 Fax 03 9314 0383
For more information on the complete Olex Cables range, see www.olexcables.com.au
New South Wales
STATE OFFICE 8 South Street, Rydalmere NSW 2116
Phone 02 8845 6111 Fax 02 8845 6150
NEWCASTLE Suite 9, 115 Darby Street, Newcastle NSW 2300
Phone 02 4929 3977 Fax 02 4929 3975
Queensland
STATE OFFICE 541 Bilsen Road, Geebung Qld 4034
Phone 07 3259 2600 Fax 07 3259 2606
TOWNSVILLE 16 Leyland Street, Townsville Qld 4810
Phone 07 4779 0322 Fax 07 4779 7201
Victoria and Tasmania
STATE OFFICE 11 Newcastle Road, Bayswater Vic. 3153
Phone 03 9237 8188 Fax 03 9729 8144
South Australia
STATE OFFICE 539 South Road, Regency Park SA 5010
Phone 08 8268 3266 Fax 08 8347 0879
Western Australia
STATE OFFICE 503 Abernethy Road, Kewdale WA 6105
Phone 08 9353 1122 Fax 08 9353 2688
Australian Capital Territory
STATE OFFICE Suite 8, 29 Townsville Street, Fyshwick ACT 2609
Phone 02 6280 8130 Fax 02 6280 8135
Northern Territory

94

STATE OFFICE 84 Smith Street, Darwin NT 0800


Phone 08 8981 0252 Fax 08 8941 1306

OLEX CABLES SALES OFFICES

MANUFACTURING LOCATIONS
Tottenham
207 Sunshine Road, Tottenham Vic. 3012
Lilydale
55 Main Street, Lilydale Vic. 3140
Wetherill Park
29 Davis Road, Wetherill Park NSW 2164
INTERNATIONAL SALES OFFICES
Head Office
Olex Cables, 207 Sunshine Road, Tottenham Vic. 3012 Australia
Phone 61 3 9281 4444 Fax 61 3 9314 0383
New Zealand
Olex Cables (NZ), Paraite Road, Bell Block, New Plymouth, New Zealand
Phone 64 6 755 3799 Fax 64 6 755 3790
Singapore
No 6 Loyang Way 1 #02-02, Singapore 508707
Phone 65 546 2788 Fax 65 546 2766
Malaysia
Lot T1, Centrepoint, Lebuh Bandar Utama, Bandar Utama 47800,
Petaling Jaya, Malaysia
Phone 60 3 710 4901 Fax 60 3 710 4910
China
Room 57119, Building 7#, Xiyuan Hotel, Beijing China 100044
Phone 86 10 6831 8549, 86 10 6835 1019, 86 10 6831 3388 ext. 57119, 57120
Fax 86 10 6832 1963

95

Olex Cables has taken every precaution to ensure that the information contained in this
booklet is in line with requirements of the appropriate Australian Standards and correct
electrical practice. However, we accept no liability of any kind with respect to the
information presented here.
Note: Current-carrying capacity tables stated in this handbook are based on
AS/NZS3008.1, Electrical Installations Selection of Cables. Part 1: Cables for alternating
voltages up to and including 0.6/1kV.

96

All information is subject to change without notice.

E D
MINING

OPTICAL FIBRE

Head Office & International Sales


207 Sunshine Road Tottenham Victoria 3012
Telephone 03 9281 4444 Facsimile 03 9314 0383

www.olexcables.com.au
Disegno OLC3342 Printed in Australia 6/2000.