SAFETY WARNING
Cables are insulated and sheathed with stable materials which may contain certain
toxic substances including lead. Insulation and sheathing materials should not be
chewed or ingested.
INSTALLATION
Cables must be installed in accordance with the requirements of Section 3
Selection and Installation of Wiring Systems in the latest issue of AS/NZS3000
or the appropriate ruling standard in the country of installation. Cables must also be
connected by a licensed electrician, as ruled in the state or country of installation.
In particular your attention is drawn to Section 1.7 of the Wiring Rules (AS/NZS3000)
Protection for Safety.
The requirements of AS/NZS3000.2000 (current edition) differ dramatically from
those in the 1991 edition of AS3000. While the intent to enforce safe design and
installation practices is the same, the new standard defines the requirements rather
than specifying solutions. Designers and installers can be assured the products
provided by Olex Cables meet the requirements of the relevant standards, but must
ensure appropriate selection of cables and components for any electrical installation.
HAZARDOUS AREAS
Installation of wiring and fittings for hazardous areas, e.g. flammable or explosive
gas, liquid, dust or solids must comply with Section 7.9 Hazardous Areas, of
AS/NZS3000, and other relevant Australian Standards for specific hazards and
occupancies.
TECHNICAL NOTE
PVC 90C THERMAL RATING
The current-carrying capacities for thermoplastic cables, including flexible cords
used as fixed wiring, insulated with V-90 and V-90HT PVC compounds have been
based on a conductor operating temperature of 75C because of the likelihood of
thermal deformation of these cable types in the temperature range 90 to 105C
(refer AS/NZS3008.1 Table 1 Note 2).
Olex Cables is a division of Australian Cables Pty Ltd. A.C.N. 087 542 863.
CONTENTS
Handbook 2000
ENVIROLEX
POWER CABLE
1 Core
1 Core
1 Core
2 & 3 Core
2 & 3 Core+Earth
2 & 3 Core+Earth
2 & 3 Core+Earth
4 Core+Earth
4 Core+Earth
2 & 3 Core+Earth
2 & 3 Core+Earth
4 Core+Earth
4 Core+Earth
5
6
7
8
9
10
11
12
13
14
15
16
17
COPPER CONTROL
Multicore+Earth
Multicore+Earth
PVC/PVC Circular
PVC/SWA/PVC Circular
18
19
NEUTRAL SCREENED
2, 3 & 4 Core
PVC/PVC Copper
20
AERIAL
1, 2, 3 & 4 Core
2, 3 & 4 Core
PVC Copper
XLPE Aluminium ABC
21
22
FLEXIBLE CORDS
Core Colours
2 Core, 2, 3 & 4 Core+Earth
2 Core, 2, 3 & 4 Core+Earth
1 Core
1 Core
2 Core
2 & 3 Core
Multicore
2, 3 & 4 Core+Earth
3 & 4 Core+Earth
Ordinary Duty
Heavy Duty
PVC
Silicone Rubber
PVC Figure 8
Light Duty
Heavy Duty
Flexolex Heavy Duty
Flexolex Heavy Duty Screened
23
24
25
26
26
26
26
27
28
29
CONTENTS
FLEXIBLE CABLES
1 Core
1 Core
Welding
VAROLEX
3 Core+3 Earths
PYROLEX FIRE RATED
1 Core
2, 3, 4 Core
30
31
32
XLPE/PVC Copper
33
ES110
Multicore D&W
34
35
COMMUNICATIONS CABLE
LAN
Category 3 16MHz
PVC Insulated Copper
Category 5 Standard
PVC Insulated Copper
Category 5 External
PVC Insulated Copper
Category 5e
PVC Insulated Copper
Category 5e External
PVC Insulated Copper
Proposed Category 6
DataTwist 350
Category 6
MediaTwist
Thin Ethernet
PVC Insulated Copper
100 Ohm Twinaxial
PVC Insulated Copper
78 Ohm Twinaxial
Blue Hose
FIBRE
Indoor/Outdoor Riser
Internal Light Duty Riser
Internal Heavy Duty Riser
External Single Tube
Construction
External Loose Tube
Single Mode & Multi Mode
External Armoured Loose Tube Cable
TELEPHONE CABLE
Internal
Underground External
External Jelly Filled
External Jelly Filled & Moisture Barrier
Aerial
Telstra Approved External
Jumper Wire
Jumper Wire
Category 5
36
37
38
39
39
40
40
41
41
42
42
42
43
44
44
45
46
47
48
49
50
51
51
52
53
53
CONTENTS
DATA CABLE
Audio Control
RS485 Screened Data
RS232 Screened Data
RS232 Screened Data
ISDN Foil or Braid 120 Ohm
SCSI Cables
Traffic Detector Cable
SECURITY CABLES
Multicore Circular
Flat (Figure 8)
MICROPHONE
Low Capacitance
Mid Capacitance
54
55
55
56
56
57
57
58
58
59
ACCESSORIES
ALCO Earth Tags
ALCO Locknuts
ALCO PVC Shrouds
Clipsal A4 Industrial Glands
Glands UA, UG, UFPR, G, WG, FLPW
60
60
61
61
6267
CURRENT RATINGS
Flexible Cords
PVC Aerial Cables
Flexible & Welding Cables
Single Phase
Single Phase
Three Phase
Three Phase
68
69
70
7172
7374
7576
7778
Copper
2 x 1 Core PVC, XLPE
2 Core PVC, XLPE
3 x 1 Core PVC, XLPE
3 & 4 Core PVC, XLPE
GENERAL
Cable Selection
Installation
Minimum Size of Copper Earthing Conductors
Maximum Operating Temperatures
D.C. Resistance
3 Phase Formulae
M.C.M. & A.W.G. Conductor Size Conversion
Bending Radii
Diameter to Cross-sectional Area
Number of Cables in Conduit
Cables in Conduit Space Factors
Pulling Tension
Abbreviations
7980
81
82
82
83
84
85
86
87
88
89
89
90
ENVIROLEX
Olex Envirolex cables are an extensive range of enhanced performance
cables for the construction industry engineered to dramatically reduce
environmental impact, particularly under fire conditions, while retaining
the excellent mechanical and electrical properties designed into Olex
cables. Olex uses a variety of inorganically filled polyolefin based
materials to engineer the cables in the Envirolex range to meet a wide
variety of end uses and performance requirements.
Advantages of Olex Envirolexcables
Conductor range up to 630mm2
Cable types from building wires to SWA, to multicore control
90C rated for superior thermal performance
Improved performance under fire conditions:
Flame retardant/self-extinguishing
Reduced acid, gas and smoke generation
Non-corrosive in fire situations
Reduced toxicity of fumes during fire
Halogen free (i.e. no chlorine, bromine etc.)
Lead free
No special termination or installation requirements
Made in accordance with Australian Standards
Envirolexcables have been tested according to and comply with the
requirements of the single and bunched flame tests (as applicable)
specified in AS1660.
Envirolexproducts include readily strippable cables for general
construction purposes as well as the tougher products commonly
found in cables with higher fire performance capability.
Envirolexmaterials are used as alternatives to all low voltage power
and control cables (refer tables on pages 5 to 23).
PVC INSULATED
POWER
N E WA R D
ND
STA
Nominal
insulation
thickness
mm
Nominal
overall
diameter
mm
AS / N
ZS
5000
Approximate
mass
Product
code
kg/100m
0.8
2.4
1.1
BAAP01AA001
0.8
2.7
1.7
BAAP02AA001
0.8
2.8
1.6
BAAP03AA001
0.8
3.1
2.1
BAAP05AA001
0.8
3.6
3.3
BAAP07AA001
1.0
4.5
5.3
BAAP09AA001
1.0
5.1
7.3
BAAP11AA001
1.0
6.0
12
BAAP13AA001
1.0
6.9
17
BAAP15AA001
1.2
8.4
26
BAAC17AA001
1.2
9.4
36
BAAC18AA001
1.4
10.9
48
BAAC19AA001
1.4
12.7
68
BAAC20AA001
1.6
14.6
91
BAAC22AA001
1.6
17.3
117
BAAP23AA001
1.8
18.8
145
BAAP24AA001
2.0
21.1
182
BAAP25AA001
2.2
24.1
238
BAAP26AA001
2.4
26.9
298
BAAP27AA001
2.6
30.6
377
BAAP28AA001
2.8
34.1
482
BAAP30AA001
2.8
37.8
615
BAAP32AA001
Single core PVC insulated copper earth conductor
0.6
2.7
1.8
AATP05AA001
0.7
3.4
3.2
AATP07AA001
POWER
PVC SDI
Nominal
Nominal
insulation
sheath
thickness thickness
mm
mm
0.6
0.6
0.7
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
Nominal Approximate
overall
mass
diameter
mm
kg/100m
3.9
4.2
4.9
5.9
6.4
7.8
9.0
10.6
12.2
13.8
15.5
17.7
20.4
22.1
24.5
27.8
30.8
34.7
38.4
42.2
2.7
3.2
4.8
7.1
9.4
14.7
20.8
31.3
43
56
77
103
133
161
201
262
326
411
521
659
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
AABP02AA001
AABP05AA001
AABP07AA001
AABP09AA001
AABP11AA001
AABP13AA001
AABP15AA001
AABC17AA001
BABC18AA001
BABC19AA001
BABC20AA001
BABC22AA001
BABP23AA001
BABP24AA001
BABP25AA001
BABP26AA001
BABP27AA001
BABP28AA001
BABP30AA001
BABP32AA001
XLPE INSULATED
POWER
Nom.
cond.
area
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Nom. Sheath
insul. thick.
thick.
mm
mm
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.2
Nominal
overall
diameter
mm
Cu
9.1
10.6
11.6
13.0
14.9
16.7
19.6
21.3
23.5
26.6
29.4
33.3
37.0
41.4
Al
9.1
10.8
12.8
13.7
15.0
17.7
18.5
20.6
22.4
25.1
27.7
31.1
34.7
39.5
Approximate
mass
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
kg/100m
Cu
21
30
40
52
73
97
123
152
189
246
306
386
491
635
Al
11
15
18
23
31
40
54.9
60
72
91
112
141
178
232
Cu
BDBP15
BDBC17
BDBC18
BDBC19
BDBC20
BDBC22
BDBP23
BDBP24
BDBP25
BDBP26
BDBP27
BDBP28
BDBP30
BDBP32
Al
BDBA15
BDBA17
BDBA18
BDBA19
BDBA20
BDBA22
BDBA23
BDBA24
BDBA25
BDBA26
BDBA27
BDBA28
BDBA30
BDBA32
POWER
PVC FLAT
Conductor
type
Nominal
earth
area
mm2
1.0
1.5
2.5
4
6
10
16
Solid
Strand
Strand
Strand
Strand
Strand
Strand
1.5
1.5
2.5
2.5
2.5
4
6
1.5
2.5
Strand
Strand
1.5
2.5
Nominal
overall
dimensions
mm
2C
6.44.1
7.14.4
8.75.3
10.56.3
11.56.8
14.38.3
16.69.6
3C
9.74.4
12.15.3
Approximate
mass
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
kg/100m
5.1
6.2
9.7
14.3
18.7
29.9
42.5
CACP02AA002
CACP05AA002
CACP07AA002
CACP09AA002
CACP11AA002
CACP13AA002
CACP15AA002
8.9
14.1
EACP05AA003
EACP07AA003
PVC FLAT
POWER
Nominal
earth
area
mm2
1.0
1.5
2.5
2.5
4
6
10
16
Solid
Strand
Solid
Strand
Strand
Strand
Strand
Strand
1.5
1.5
2.5
2.5
2.5
2.5
4
6
1.5
2.5
Strand
Strand
1.5
2.5
Nominal
Approximate
overall
mass
dimensions
mm
kg/100m
2C+E
9.04.2
9.74.4
11.85.2
12.15.3
13.96.3
14.86.8
18.58.3
21.319.6
3C+E
12.34.4
15.45.3
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
7.5
8.9
13.7
14.1
18.8
23.2
36.6
51.5
CNCP02AA002
CNCP05AA002
CNCP06AA002
CNCP07AA002
CNCP09AA002
CNCP11AA002
CNCP13AA002
CNCP15AA002
11.6
18.4
ENCP05AA003
ENCP07AA003
POWER
PVC CIRC
N E WA R D
ND
STA
10
Earth
conductor
area
mm2
1.5
2.5
4
6
10
16
25
35
50
1.5
2.5
2.5
2.5
4
6
6
10
16
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
Nominal
overall
diameter
mm
2C+E
9.4
10.9
12.3
13.3
16.0
17.7
20.5
22.5
25.6
3C+E
10.3
12.0
13.4
14.4
17.5
19.4
22.3
24.7
28.3
32.6
36.4
42.0
46.3
51.6
58.9
65.3
AS / N
ZS
5000
Approximate
mass
Product
code
kg/100m
13
17
22
28
48
65
80
107
139
CNHP05AA002
CNHP07AA002
CNHP09AA002
CNHP11AA002
DNHP13AA002
DNHP15AA002
DNHC17AA002
DNHC18AA002
DNHC19AA002
16
23
31
37
61
84
110
143
192
268
346
453
560
706
916
1153
ENHP05AA003
ENHP07AA003
ENHP09AA003
ENHP11AA003
FNHP13AA003
FNHP15AA003
FNHC17AA003
FNHC18AA003
FNHC19AA003
FNHC20AA003
FNHC22AA003
FNHP23AA003
FNHP24AA003
FNHP25AA003
FNHP26AA003
FNHP27AA003
Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
2C+E, 35mm2 and above, subject to minimum production run.
For insulation thickness refer to page 6.
XLPE INSULATED
POWER
N E WA R D
ND
STA
Nominal
conductor
area
mm2
Main
conductor
type
Sheath
thickness
mm
16
25
35
50
70
95
120
Strand
Compact
Compact
Compact
Compact
Compact
Strand
1.8
1.8
1.8
1.8
1.8
1.9
2.0
16
25
35
50
70
95
120
150
185
240
300
Strand
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.3
2.5
2.6
2.8
Nominal
overall
diameter
mm
2C+E
16.5
19.4
21.4
24.1
28.0
31.3
37.0
3C+E
18.0
21.0
23.3
26.3
31.0
34.1
40.1
44.2
49.8
56.3
62.5
AS / N
ZS
5000
Approximate
mass
Product
code
kg/100m
52
74
97
130
184
233
301
DTHP15AA002
DTHC17AA002
DTHC18AA002
DTHC19AA002
DTHC20AA002
DTHC22AA002
DTHP23AA002
68
100
132
178
253
321
422
521
661
857
1080
FTHP15AA003
FTHC17AA003
FTHC18AA003
FTHC19AA003
FTHC20AA003
FTHC22AA003
FTHP23AA003
FTHP24AA003
FTHP25AA003
FTHP26AA003
FTHP27AA003
Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted
For insulation thickness refer to page 7.
312 core (3 core+reduced neutral with or without earth) available on request
subject to minimum production runs.
11
POWER
PVC CIRC
Earth
conductor
area
mm2
1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
Nominal
overall
diameter
mm
4C+E
11.0
12.9
14.5
15.7
19.1
21.3
24.6
27.3
32.9
38.1
42.3
48.7
53.8
60.2
69.5
77.8
N E WA R D
ND
STA
AS / N
5000
Approximate
mass
Product
code
kg/100m
18
27
37
46
75
105
138
182
249
349
451
591
734
908
1201
1502
GNHP05AA004
GNHP07AA004
GNHP09AA004
GNHP11AA004
HNHP13AA004
HNHP15AA004
HNHC17AA004
HNHC18AA004
HNHC19AA004
HNHC20AA004
HNHC22AA004
HNHP23AA004
HNHP24AA004
HNHP25AA004
HNHP26AA004
HNHP27AA004
Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
For insulation thickness refer to page 6.
12
ZS
XLPE INSULATED
POWER
Nominal
conductor
area
mm2
Main
conductor
type
16
25
35
50
70
95
120
150
185
240
300
Strand
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
N E WA R D
ND
STA
AS / N
5000
Sheath
Nominal Approximate
thickness overall
mass
diameter
mm
mm
kg/100m
1.8
1.8
1.8
1.9
2.0
2.2
2.3
2.5
2.7
2.9
3.1
4C+E
19.7
22.8
25.5
30.6
36.1
39.6
46.4
51.3
58.1
66.0
74.6
68
126
168
231
330
423
552
681
864
1117
1407
ZS
Product
code
HTHP15AA004
HTHC17AA004
HTHC18AA004
HTHC19AA004
HTHC20AA004
HTHC22AA004
HTHP23AA004
HTHP24AA004
HTHP25AA004
HTHP26AA004
HTHP27AA004
Note: Compacted conductor. Earth cores smaller than 25mm2 are not compacted.
For insulation thickness refer to page 7.
13
POWER
14
1.5
2.5
4
6
10
16
25
35
50
1.5
2.5
2.5
2.5
4
6
6
10
16
7.8
9.3
10.7
11.7
14.4
16.1
19.0
21.0
24.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
8.7
10.4
11.8
12.8
15.9
17.8
20.7
23.1
26.5
31.0
34.6
40.0
44.3
49.4
56.7
62.7
Nominal
dia. over
armour
mm
2C+E
9.7
11.2
13.2
14.3
16.9
18.6
22.2
24.2
27.2
3C+E
10.5
12.9
14.3
15.4
18.4
21.0
23.9
26.3
29.7
35.0
38.6
44.1
49.3
54.4
61.7
67.7
AS / N
ZS
5000
Nominal Approximate
overall
mass
diameter
mm
kg/100m
Product
code
13.3
14.8
16.8
17.9
20.5
22.3
25.8
27.8
30.9
34
43
59
67
95
116
150
181
230
CNMP05AA002
CNMP07AA002
CNMP09AA002
CNMP11AA002
DNMP13AA002
DNMP15AA002
DNMC17AA002
DNMC18AA002
DNMC19AA002
14.1
16.5
17.9
19.0
22.0
24.6
27.6
30.0
33.7
39.2
43.1
48.9
54.3
59.8
68.0
74.5
39
57
68
79
113
154
184
226
287
407
499
636
802
977
1230
1501
ENMP05AA003
ENMP07AA003
ENMP09AA003
ENMP11AA003
FNMP13AA003
FNMP15AA003
FNMC17AA003
FNMC18AA003
FNMC19AA003
FNMC20AA003
FNMC22AA003
FNMP23AA003
FNMP24AA003
FNMP25AA003
FNMP26AA003
FNMP27AA003
XLPE SWA
POWER
N E WA R D
ND
STA
Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm
2.5
4
6
10
16
25
35
50
70
95
120
16
25
35
50
70
95
120
150
185
240
300
2
2
2
4
6
6
10
16
25
25
35
9.3
10.3
11.3
13.2
14.9
17.8
19.8
22.5
26.4
29.9
35.4
6
6
10
16
25
25
35
50
70
95
120
16.4
19.4
21.7
24.7
29.6
32.0
38.2
42.4
47.6
54.3
60.1
Nominal
dia. over
armour
mm
2C+E
11.1
12.8
13.8
15.7
17.4
20.3
23.0
25.7
29.6
33.9
39.4
3C+E
18.9
22.6
24.9
27.9
33.6
36.0
42.3
47.4
52.6
59.3
65.1
AS / N
ZS
5000
Nominal Approximate
overall
mass
diameter
mm
kg/100m
Product
code
14.8
16.5
17.5
19.3
21.1
24.0
26.7
29.4
33.4
37.9
43.7
42
57
64
80
98
129
169
211
279
364
459
DTMP07AA002
DTMP09AA002
DTMP11AA002
DTMP13AA002
DTMP15AA002
DTMC17AA002
DTMC18AA002
DTMC19AA002
DTMC20AA002
DTMC22AA002
DTMP23AA002
22.5
26.2
28.6
31.8
37.8
40.5
46.9
52.5
57.9
65.0
71.7
118
171
212
267
387
467
596
750
916
1145
1406
FTMP15AA003
FTMC17AA003
FTMC18AA003
FTMC19AA003
FTMC20AA003
FTMC22AA003
FTMP23AA003
FTMP24AA003
FTMP25AA003
FTMP26AA003
FTMP27AA003
15
POWER
1.5
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
9.4
11.3
12.9
14.1
17.5
19.7
23.0
25.7
31.3
36.3
40.5
46.7
51.4
58.0
66.6
75.0
Nominal
dia. over
armour
mm
4C+E
11.3
13.9
15.4
16.7
20.7
22.9
26.2
28.9
35.3
40.3
45.5
51.7
56.4
63.0
71.6
82.1
14.9
17.5
19.0
20.3
24.4
26.5
29.9
32.7
39.5
44.7
50.4
56.9
61.9
69.4
78.4
88.9
43
63
78
91
145
181
221
276
390
511
672
849
1012
1227
1560
2009
ZS
5000
Nominal Approximate
overall
mass
diameter
mm
kg/100m
16
AS / N
Product
code
GNMP05AA004
GNMP07AA004
GNMP09AA004
GNMP11AA004
HNMP13AA004
HNMP15AA004
HNMC17AA004
HNMC18AA004
HNMC19AA004
HNMC20AA004
HNMC22AA004
HNMP23AA004
HNMP24AA004
HNMP25AA004
HNMP26AA004
HNMP27AA004
XLPE SWA
POWER
Nominal
Earth
Nominal
conductor conductor dia. over
area
area
bedding
mm2
mm2
mm
16
25
35
50
70
95
120
150
185
240
300
6
6
10
16
25
25
35
50
70
95
120
18.1
21.2
23.9
29.2
34.5
37.6
44.6
49.1
55.9
63.4
70.6
Nominal
dia. over
armour
mm
4C+E
21.3
24.4
27.1
33.2
38.5
41.6
49.6
54.1
60.9
68.4
76.9
Nominal
overall
diameter
mm
25.0
28.0
31.0
37.2
43.0
46.3
54.7
59.6
67.0
74.9
84.0
Approx.
mass
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
kg/100m
154
203
256
363
485
586
795
944
1164
1452
1900
HTMP15AA004
HTMC17AA004
HTMC18AA004
HTMC19AA004
HTMC20AA004
HTMC22AA004
HTMP23AA004
HTMP24AA004
HTMP25AA004
HTMP26AA004
HTMP27AA004
17
POWER
PVC CONTROL
Number
of cores
18
Nominal overall
diameter
mm
5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E
12.9
14.4
15.2
16.1
16.8
18.2
19.1
20.1
22.1
24.2
25.2
27.4
29.3
5+E
6+E
8+E
10+E
12+E
15+ E
16+E
20+E
25+E
30+E
36+E
40+E
50+E
14.5
14.8
17.2
18.2
19
20.6
21.7
22.8
25.2
27.7
28.9
31.5
33.8
Approximate
mass
kg/100m
1.5mm2 (7/0.50mm)
24
27
32
38
42
50
53
63
74
87
100
112
138
2.5mm2 (7/0.67mm)
33
35
46
56
61
71
77
91
109
128
150
168
203
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
BFAP05AA005
BFAP05AA006
BFAP05AA008
BFAP05AA010
BFAP05AA012
BFAP05AA015
BFAP05AA016
BFAP05AA020
BFAP05AA025
BFAP05AA030
BFAP05AA036
BFAP05AA040
BFAP05AA050
BFAP07AA005
BFAP07AA006
BFAP07AA008
BFAP07AA010
BFAP07AA012
BFAP07AA015
BFAP07AA016
BFAP07AA020
BFAP07AA025
BFAP07AA030
BFAP07AA036
BFAP07AA040
BFAP07AA050
POWER
Nominal
dia. over
bedding
mm
5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E
11.3
11.6
13.6
15.1
15.2
16.6
17.5
18.5
20.5
22.6
23.6
25.8
27.9
5+E
6+E
8+E
10+E
12+E
15+E
16+E
20+E
25+E
30+E
36+E
40+E
50+E
12.9
13.1
15.6
17.2
17.4
19
20.1
21.2
23.6
26.1
27.1
30.1
32.2
Nominal
dia. over
armour
mm
Nominal
overall
diameter
mm
1.5mm2 (7/0.50mm)
13.8
17.5
14.1
17.8
16.1
19.8
17.5
21.1
17.7
21.4
19.1
22.8
20.7
24.4
21.7
25.4
23.7
27.4
25.8
29.5
26.8
30.6
29
32.9
31.9
36.2
2.5mm2 (7/0.67mm)
15.4
19
15.6
19.3
18.1
21.8
20.4
24.1
20.6
24.3
22.2
25.9
23.3
26.9
24.4
28.1
26.8
30.7
29.3
33.1
30.3
34.4
34.1
38.4
36.2
40.6
Approx.
mass
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
kg/100m
60
62
75
87
89
100
119
131
151
170
188
208
266
BFCP05AA005
BFCP05AA006
BFCP05AA008
BFCP05AA010
BFCP05AA012
BFCP05AA015
BFCP05AA016
BFCP05AA020
BFCP05AA025
BFCP05AA030
BFCP05AA036
BFCP05AA040
BFCP05AA050
75
77
94
122
126
143
152
169
197
226
250
308
352
BFCP07AA005
BFCP07AA006
BFCP07AA008
BFCP07AA010
BFCP07AA012
BFCP07AA015
BFCP07AA016
BFCP07AA020
BFCP07AA025
BFCP07AA030
BFCP07AA036
BFCP07AA040
BFCP07AA050
19
POWER
NEUTRAL SCREEN
4 conductor
3 conductor
2 conductor
Nominal
Nominal
conductor insulation
area
thickness
mm2
mm
20
Nominal
sheath
thickness
mm
6
10
16
25
1.2
1.2
1.2
1.4
1.8
1.8
1.8
2.0
6
10
16
25
1.2
1.2
1.2
1.4
1.8
1.8
1.8
1.8
6
10
16
1.0
1.0
1.0
1.8
1.8
1.8
6
10
16
1.0
1.0
1.0
1.8
1.8
1.8
6
10
16
25
35
50
70
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.8
1.8
1.8
1.8
1.9
2.0
2.0
6
10
16
25
35
1.0
1.0
1.0
1.2
1.2
1.8
1.8
1.8
1.8
1.8
Nominal Approximate
overall
mass
diameter
mm
kg/100m
Mains cable
10.4
11.6
13.2
15.5
Aerial cable
10.4
11.7
13.5
15.9
Mains cable
10.716.0
12.018.2
13.220.3
Aerial cable
10.816.1
12.018.3
13.420.8
Mains cable
16.6
18.1
20.7
23.9
26.6
30.5
35.3
Aerial cable
16.7
18.7
21.3
25.6
28.1
Product
code
21
31
44
70
BAGP11AA001
BAGP13AA001
BAGP15AA001
BAGC17AA001
22
31
45
68
BAGT11AA001
BAGT13AA001
BAGT15AA001
BAGT17AA001
33
47
65
DAEP11AA002
DAEP13AA002
DAEP15AA002
34
48
67
DAET11AA002
DAET13AA002
DAET15AA002
46
60
85
132
174
232
321
FAGP11AA003
FAGP13AA003
FAGP15AA003
FAGC17AA003
FAGC18AA003
FAGC19AA003
FAGC20AA003
45
62
87
139
174
FAGT11AA003
FAGT13AA003
FAGT15AA003
FAGT17AA003
FAGT18AA003
AERIAL
POWER
N E WA R D
ND
STA
Nominal
insulation
thickness
mm
6
10
16
25
35
50
70
95
120
150
7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.78
19/2.14
37/1.78
37/2.03
37/2.25
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
6
10
16
7/1.04
7/1.35
7/1.70
1.0
1.0
1.0
6
10
16
7/1.04
7/1.35
7/1.70
1.0
1.0
1.0
6
10
16
25
7/1.04
7/1.35
7/1.70
19/1.35
1.0
1.0
1.0
1.2
6
10
16
25
7/1.04
7/1.35
7/1.70
19/1.35
1.0
1.0
1.0
1.2
6
10
16
25
7/1.04
7/1.35
7/1.70
19/1.35
1.0
1.0
1.0
1.2
Nominal
overall
diameter
mm
Single core
5.1
6.1
7.1
9.2
10.1
11.7
13.5
15.7
17.4
19.4
2C Parallel
5.111.4
6.113.0
7.115.1
3C Parallel
5.117.2
6.120.0
7.123.2
2C Twisted
10.1
11.9
14.0
18.1
3C Twisted
10.9
12.9
15.1
19.5
4C Twisted
12.2
14.4
16.9
21.8
AS / N
ZS
5000
Approximate
mass
Product
code
kg/100m
8
12
18
29
37
50
70
95
121
149
BAAT11AA001
BAAT13AA001
BAAT15AA001
BAAT17AA001
BAAT18AA001
BAAT19AA001
BAAT20AA001
BAAT22AA001
BAAT23AA001
BAAT24AA001
15
23
35
DAAT11AA002
DAAT13AA002
DAAT15AA002
22
35
53
FAAT11AA003
FAAT13AA003
FAAT15AA003
15
23
35
59
DAFT11AA002
DAFT13AA002
DAFT15AA002
DAFT17AA002
22
35
53
89
FAFT11AA003
FAFT13AA003
FAFT15AA003
FAFT17AA003
30
47
71
118
HAFT11AA004
HAFT13AA004
HAFT15AA004
HAFT17AA004
21
POWER
AERIAL
22
Nominal
conductor
area
Nominal
insulation
thickness
Diameter
over
insulation
mm2
mm
mm
25
35
50
95
1.3
1.3
1.5
1.7
8.6
9.8
11.3
15.0
25
35
50
70
1.3
1.3
1.5
1.5
8.6
9.8
11.3
13.0
25
35
50
70
95
120
150
1.3
1.3
1.5
1.5
1.7
1.7
1.7
8.6
9.8
11.3
13.0
15.1
16.5
17.9
Diameter Approximate
over
mass
laid-up
cores
mm
kg/100m
2C
17.2
19.3
22.5
30.1
3C
18.7
21.0
24.3
27.7
4C
21.0
23.5
27.2
31.1
36.2
39.6
43.1
Product
code
20
25
34
64
XDAB17AA002
XDAB18AA002
XDAB19AA002
XDAB22AA002
29
37
51
70
XDAB17AA003
XDAB18AA003
XDAB19AA003
XDAB20AA003
39
50
67
93
128
157
189
XDAB17AA004
XDAB18AA004
XDAB19AA004
XDAB20AA004
XDAB22AA004
XDAB23AA004
XDAB24AA004
FLEXIBLE
POWER
CORE COLOURS
Colour sequences are valid for standard light ordinary
and heavy duty cords.
a) Preferred Core Colours As specified by AS/NZS3000
for cords not installed as fixed wiring.
2 Core
3 Core
4 Core
5 Core
Red, Black
Red, Black, Green/Yellow
Red, White, Blue, Green/Yellow
23
POWER
FLEXIBLE
Maximum
diameter
of wires
mm
Nominal
overall
diameter
mm
Approximate
mass
Product
code
kg/100m
2C
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
6.3
6.6
7.6
9.4
10.5
2C+E
6.6
7.0
8.3
10.1
11.4
3C+E
7.2
7.8
9.2
11.0
12.4
4C+E
8.1
8.5
10.3
12.3
13.8
6
7
9
14
19
CAHR02AA002
CAHR03AA002
CAHR04AA002
CAHR05AA002
CAHR06AA002
7
8
11
17
24
EAHR02AA003
EAHR03AA003
EAHR04AA003
EAHR05AA003
EAHR06AA003
8
10
14
21
29
GAHR02AA004
GAHR03AA004
GAHR04AA004
GAHR05AA004
GAHR06AA004
10
12
17
26
36
APAR02AA005
APAR03AA005
APAR04AA005
APAR05AA005
APAR06AA005
24
FLEXIBLE
POWER
Maximum
diameter
of wires
mm
Nominal
overall
diameter
mm
Approximate
mass
Product
code
kg/100m
2C
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
8.2
8.5
9.5
11.2
12.9
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
8.8
9.1
10.1
11.9
13.8
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
9.7
10.0
11.1
13.1
15.2
0.75
1.0
1.5
2.5
4
0.21
0.21
0.26
0.26
0.31
10.6
11.0
12.2
14.4
16.9
9
10
12
18
25
CBGR02AA002
CBGR03AA002
CBGR04AA002
CBGR05AA002
CBGR06AA002
10
12
15
22
30
EBGR02AA003
EBGR03AA003
EBGR04AA003
EBGR05AA003
EBGR06AA003
13
14
18
26
37
GBGR02AA004
GBGR03AA004
GBGR04AA004
GBGR05AA004
GBGR06AA004
15
17
22
32
46
BSBR02AA005
BSBR03AA005
BSBR04AA005
BSBR05AA005
BSBR06AA005
3C
4C
5C
25
POWER
FLEXIBLE
Maximum
diameter
of cores
mm
Nominal
overall
diameter
mm
Approximate
mass
Product
code
kg/100m
26
POWER
EW
N ARD
Multicore circular 0.6/1kV PVC insulated
ND
STA
ZS
and PVC sheathed heavy duty flexible
AS / N
control cable, with or without black neutral,
5000
white insulated, black numbered cores
including earth generally to AS/NZS5000.1, 90C.
Number
of cores
Nominal
overall
diameter
mm2
5
7
9
11
15
19
13.4
15.4
17.2
18.9
18.2
19.9
5
7
9
11
15
19
13.9
16.1
17.9
19.8
19.0
20.9
5
7
9
11
15
19
14.8
17.1
19.2
21.2
20.4
22.4
Approximate
mass
kg/100m
0.75mm2
22
28
34
41
43
51
1.0mm2
24
31
38
46
48
58
1.5mm2
29
36
46
54
58
70
Product
code
BFFR02AA005
BFFR02AA007
BFFR02AA009
BFFR02AA011
BFFR02AA015
BFFR02AA019
BFFR03AA005
BFFR03AA007
BFFR03AA009
BFFR03AA011
BFFR03AA015
BFFR03AA019
BFFR04AA005
BFFR04AA007
BFFR04AA009
BFFR04AA011
BFFR04AA015
BFFR04AA019
27
POWER
FLEXIBLE
0.21
0.21
0.26
0.26
0.31
0.8
0.8
0.8
0.9
1.0
1.5
2.5
4
6
10
16
25
0.26
0.26
0.31
0.31
0.41
0.41
0.41
0.8
0.9
1.0
1.0
1.2
1.2
1.4
1.5
2.5
4
6
10
16
25
35
0.26
0.26
0.31
0.31
0.41
0.41
0.41
0.41
0.8
0.9
1.0
1.0
1.2
1.2
1.4
1.4
2C+E
1.4
1.4
1.6
1.8
1.9
3C+E
1.7
1.9
2.0
2.2
3.4
3.6
4.0
4C+E
1.8
2.0
2.2
2.4
3.6
3.8
4.3
4.6
AS / N
ZS
5000
Product
code
8.8
9.1
10.1
12.0
13.9
11
12
15
22
31
RDER52AA003
RDER53AA003
RDER54AA003
RDER55AA003
RDER56AA003
11.2
13.2
15.3
17.9
24.4
27.4
32.9
19
27
39
55
97
135
204
RDER54AA004
RDER55AA004
RDER56AA004
RDHR57AA004
RDHR58AA004
RDHR59AA004
RDHR60AA004
12.3
14.5
17.0
19.9
26.8
30.2
36.4
40.6
23
33
48
68
118
164
251
322
RDER54AA005
RDER55AA005
RDER56AA005
RDHR57AA005
RDHR58AA005
RDHR59AA005
RDHR60AA005
RDHR61AA005
Note: Other sizes and conductor configurations are available upon request.
28
N E WA R D
ND
STA
FLEXIBLE
POWER
0.26
0.26
0.31
0.31
0.41
0.41
0.8
0.9
1.0
1.0
1.2
1.2
1.8
1.9
2.2
2.4
3.5
3.8
1.5
2.5
4
6
10
16
0.26
0.26
0.31
0.31
0.41
0.41
0.8
0.9
1.0
1.0
1.2
1.2
1.9
2.1
2.3
2.6
3.7
4.0
3C+E
9.7
11.3
13.2
15.3
19.2
21.8
4C+E
10.6
12.4
14.5
16.9
21.2
24.2
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
14.7
16.5
19.0
21.8
28.4
31.6
30
40
54
76
126
168
RDLR54AA004
RDLR55AA004
RDLR56AA004
RDXR57AA004
RDXR58AA004
RDXR59AA004
15.8
18.0
20.5
23.9
30.8
34.4
35
48
64
92
150
201
RDLR54AA005
RDLR55AA005
RDLR56AA005
RDXR57AA005
RDXR58AA005
RDXR59AA005
29
POWER
FLEXIBLE
6.2
7.4
9.1
10.2
12.2
14.1
16.3
17.9
19.6
12
17
26
35
50
70
95
117
132
BAAX01MN001
BAAX02MN001
BAAX03MN001
BAAX04MN001
BAAX05MN001
BAAX06MN001
BAAX07MN001
BAAX08MN001
BAAE88MN001
N E WA R D
ND
STA
AS / N
5000
Nominal Approximate
overall
mass
diameter
mm
kg/100m
TPSW*
9.1
10.2
12.0
13.1
15.1
16.9
19.4
20.9
22.8
16
23
33
42
59
79
107
130
155
ZS
Product
code
BABX01MN001
BABX02MN001
BABX03MN001
BABX04MN001
BABX05MN001
BABX06MN001
BABX07MN001
BABE87MN001
BABE88MN001
*Insulation thickness for TPSW cables is the same as that for TPS cables.
TPS: 0.6/1kV rated TPE insulated single core unprotected flexible copper cable for power and
switchboard applications. 90C HT rated to AS/NZS5000.1.
TPSW: 0.6/1kV rated TPE insulated and sheathed single core flexible copper cable for power,
welding and switchboard applications. 90C HT rated to AS/NZS5000.1 and AS/NZS1995.
TPS & TPSW are made with V90HT rated materials and are suitable for temperatures up to 105C
for limited periods (refer AS/NZS3008). These materials have enhanced UV protection characteristics
and enhanced fire resistance properties, hence the insulated and sheathed cables are excellent for
heavy duty welding applications.
30
FLEXIBLE
POWER
0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.51
0.51
0.51
0.51
Nominal
conductor
diameter
mm
4.5
5.0
6.5
7.8
9.6
11.8
13.7
15.3
16.5
19.2
22.9
Nominal Approximate
overall
mass
diameter
mm
kg/100m
8.9
9.4
10.9
12.2
14.4
16.9
19.4
21.3
23.0
26.3
30.2
16
22
32
43
60
83
108
136
167
210
266
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
RDWX01AA001
RDWX02AA001
RDWX03AA001
RDWX04AA001
RDWX05AA001
RDWX06AA001
RDWX07AA001
RDWX08AA001
RDWX09AA001
RDWX10AA001
RDWX11AA001
0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.31
Nominal
conductor
diameter
mm
2.3
2.3
2.3
2.4
2.4
2.6
2.8
2.9
Nominal Approximate
overall
mass
diameter
mm
kg/100m
10.0
11.3
12.4
14.2
16.0
18.2
20.2
21.9
22
32
41
57
78
105
130
158
Product
code
WDCX02AA001
WDCX03AA001
WDCX04AA001
WDCX05AA001
WDCX06AA001
WDCX07AA001
WDCE87AA001
WDCE88AA001
31
POWER
FLEXIBLE
Nominal
conductor
area
A
Maximum duty cycle %
Voltage
drop
mV/A.m
mm2
100
60
30
25
m/m
10
16
25
87
115
155
110
150
200
160
215
285
175
235
315
1.843
1.162
0.749
4.6
3.0
2.0
4.0
2.6
1.7
35
50
70
195
250
310
250
320
400
355
450
560
390
495
620
0.530
0.375
0.267
1.3
0.97
0.69
1.1
0.84
0.60
95
120
150
375
435
510
485
570
660
685
790
930
750
870
1020
0.198
0.153
0.123
0.54
0.44
0.37
0.47
0.38
0.32
185
240
570
680
740
880
1040
1240
1150
1360
0.097
0.076
0.32
0.28
0.28
0.24
32
Maximum D.C.
resistance
at 20C
1 phase
3 phase
VAROLEX
POWER
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.5*
4.5
4.5
4.5
7.5
12
18
30
30
48
48
75
75
105
150
10.7
12.7
13.9
14.9
16.9
19.4
22.2
25.4
28.6
31.6
38.1
41.8
46.5
52.7
59.2
14.4
16.4
17.6
18.6
20.6
23.1
25.9
29.1
32.3
35.3
41.8
45.6
50.6
56.9
63.8
33.1
41.8
49.2
62.1
86.3
123
163
215
281
367
464
581
703
914
1154
N E WA R D
ND
STA
AS / N
ZS
5000
Product
code
FTDP07AA003
FTDP09AA003
FTDP11AA003
FTDP13AA003
FTDP15AA003
FTDC17AA003
FTDC18AA003
FTDC19AA003
FTDC20AA003
FTDC22AA003
FTDP23AA003
FTDP24AA003
FTDP25AA003
FTDP26AA003
FTDP27AA003
33
PYROLEX
POWER
AS3013
rating
Insulation Sheath
mm
mm
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
34
Thickness
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
20
26
40
49
64
86
114
142
174
216
279
389
443
553
699
PDEP13AA001
PDEP15AA001
PDEP17AA001
PDEP18AA001
PDEP19AA001
PDEP20AA001
PDEP22AA001
PDEP23AA001
PDEP24AA001
PDEP25AA001
PDEP26AA001
PDEP27AA001
PDEP28AA001
PDEP30AA001
PDEP32AA001
PYROLEX
POWER
N E WA R D
ND
STA
AS / N
ZS
5000
1.5
2.5
1.5
2.5
4
6
10
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
0.7
0.7
0.7
0.7
0.7
0.7
0.7
1.8
1.8
1.8
1.8
1.8
1.8
1.8
11.0
12.2
11.7
12.5
13.5
14.6
16.1
15
20
18
23
28
30
50
PEGP05AA002
PEGP07AA002
PDGP05AA002
PDGP07AA002
PDGP09AA002
PDGP11AA002
PDGP13AA002
3
3
3+E
3+E
3+E
3+E
3+E
3+E
3+E
3+E
1.5
2.5
1.5
2.5
4
6
10
16
25
35
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
11.5
12.7
12.5
13.7
14.7
16.0
17.8
21.0
23.0
25.6
17
22
20
27
33
40
57
82
114
149
PEGP05AA003
PEGP07AA003
PDGP05AA003
PDGP07AA003
PDGP09AA003
PDGP11AA003
PDGP13AA003
PDGP15AA003
PDGC17AA003
PDGC18AA003
4
4
4+E
4+E
4+E
4+E
4+E
4+E
4+E
4+E
4+E
1.5
2.5
1.5
2.5
4
6
10
16
25
35
50
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
WS52W
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
12.8
13.8
13.6
15.1
16.4
17.3
19.5
23.1
25.5
28.4
32.8
20
26
25
33
41
50
71
105
145
191
255
PEGP05AA004
PEGP07AA004
PDGP05AA004
PDGP07AA004
PDGP09AA004
PDGP11AA004
PDGP13AA004
PDGP15AA004
PDGC17AA004
PDGC18AA004
PDGC19AA004
35
DEKORON
INSTRUMENTATION
Olex Dekoron instrumentation cable.
Number
& nominal
diameter
of wires
no/mm
7/0.30
7/0.50
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
Number
of pairs
Nominal
overall
diameter
Approximate
mass
mm
kg/100m
36
Product
code
DEKORON
INSTRUMENTATION
Number
of pairs
(or triples
where
applicable)
Nominal
overall
diameter
Approximate
mass
mm
kg/100m
Product
code
JK
KX
SX
TX
37
COMMUNICATIONS
LAN
CATEGORY 3 16MHz
1/0.5mm (24 AWG) copper, S.R. PVC insulated,
twisted pairs, unshielded, grey PVC sheath.
Pairs
Pack
size
m
2
4
25
50
100
305 box
305 box
305 reel*
305 reel
600 reel
38
3.6
4.3
10.4
11.5
14.1
62.3
62.3
70
70
70
100
100
100
100
100
Product
code
J1227A1
J1229A2
JGAD06FG025
JGAD05FG050
JGAD06FG100
LAN
COMMUNICATIONS
Blue
Blue
Grey
Blue
Blue
Grey
Blue
*
305
500
305
305
305
305
305
500
N
N
N
N
Y
Y
N
N
Solid
Solid
Solid
Solid
Solid
Solid
Stranded
Stranded
0.20
0.20
0.20
0.23
0.28
0.28
0.19
0.19
5.4
5.4
5.4
14.0
6.4
6.4
5.6
5.6
Product
code
JVJDO6AA004BEDA
JVJD06AA004BED5
JVJD06AA004GYDA
J1864A0061000
J1624A006U1000
J1624RF2U1000
JWTP37DA004BEAA
JWTP37A5004xxAA
CATEGORY 5 EXTERNAL
1/0.5mm (24 AWG) copper, polyefin insulated, 4 unshielded
twisted pairs, ripcord, PVC sheath, black polyethylene
oversheath, for outdoor and underground applications.
Pack Std Nominal Nominal Maximum Maximum Maximum
size unit insulation O.D.
DCR capacitance capacitance
kg ea thickness
Ohms/ unbalanced unbalanced
m
mm
mm
100m
mm
pF/100m
1000 45.9
0.20
6.9
9.38
330
Product
code
JZZD061D006
39
COMMUNICATIONS
LAN
CATEGORY 5e
DATATWIST 5e, ENHANCED 5e 100MHz
1/0.5mm (24 AWG) copper or 7/0.20mm (24 AWG) copper,
polyefin insulated, unshielded twisted pairs, PVC sheath.
Maximum capacitance unbalanced (pF/m): 49.2.
Pairs
Solid/
stranded
conductor
Sheath
colour
Pack
size
4
4
4
4
Solid
Solid
Solid
Stranded
Blue
Blue
Grey
*
305 box
500 box
305 box
500 reel
Nominal Nominal
insulation O.D.
thickness
mm
mm
0.20
0.20
0.20
0.21
5.0
5.0
5.0
6.0
Product
code
J1583A006DA
J1583A006D5
J1583AF6HDA
JYJP37F6004
40
0.230
6.9
50pF
93.8
100
69% YM45092
LAN
COMMUNICATIONS
PROPOSED CATEGORY 6
DATATWIST 350
(High Performance with extra headroom) (350MHz)
1/0.5mm (24 AWG) copper or 7/0.20mm (24 AWG) tinned
copper, polyolefin insulated, unshielded twisted pairs,
ripcord, blue PVC sheath. Maximum capacitance
unbalanced (pF/100m): 66.
Pairs
Solid/
stranded
conductor
Pack
size
4
4
4
Solid
Solid
Stranded
305 box
500 reel
305 box
Nominal Nominal
insulated
O.D.
conductor
O.D. mm
mm
0.23
0.23
0.23
5.1
5.1
5.6
Product
code
J1700A006U1000
J1700A0061640
J1752A006U1000
CATEGORY 6
MediaTwist for Multimedia and all
shared sheath applications. Performs well
in excess of all proposed Category 6 requirements.
1/0.5mm (24 AWG) copper, polyolefin insulated, unshielded
twisted pairs, adjacent pairs bonded (see figure).
Pairs
Sheath
colour
Nominal insulated
conductor O.D. mm
Nominal
O.D. mm
Product
code
4
4
Blue
Grey
0.23
0.23
9.3 x 7.2
9.3 x 7.2
J1872A0061000
J1872AX661000
41
COMMUNICATIONS
LAN
THIN ETHERNET
19/0.20 (20 AWG) tinned copper, foam PE insulated,
Duobond II shield, 97% tinned copper braid, grey PVC sheath.
Pack
size
m
Nominal
O.D.
mm
Ohms
Nominal
velocity of
propagation
Nominal
capacitance
pF/m
Product
code
305 box
500 reel
4.7
4.7
50
50
80%
80%
83.3
83.3
J9907E4XU1000
J9907E4X1640
Nominal
O.D.
mm
Nominal
velocity of
propagation
Nominal
capacitance
pF/m
Product
code
305 reel
6.0
66%
50.9
J92070101000
42
Pack
size
m
Nominal
O.D.
mm
Nominal
velocity of
propagation
Nominal
capacitance
pF/m
Product
code
305 reel
305 box
6.2
6.2
66%
66%
64.60
64.60
J9463J221000
J9463J22U1000
FIBRE
COMMUNICATIONS
INDOOR/OUTDOOR RISER
Internal/external Multimode (62.5/125/250m) light
duty riser has individually buffered fibres (900m PVC)
surrounded by water swellable yarn reinforcement with an
external Flame Retardant Non-Corrosive (FRNC) Sheath.
Number
of
fibres
Nominal
O.D.
mm
Nominal
weight
kg/100m
4
6
8
12
4.8
5.3
5.3
7.0
1.7
2.1
2.2
3.5
Minimum bending
radius mm
No load
Full load
75
78
78
105
100
110
110
140
Product
code
NRBP62AA004
NRBP62AA006
NRBP62AA008
NRBP62AA012
Construction options:
1. Single mode.
2. Higher Pulling tension e.g. = 1000m.
3. Dual Jacket of PE & Halogen Free Sheath.
43
COMMUNICATIONS
FIBRE
Fibre
type
6
12
4
6
8
12
Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode
2.1
3.5
1.7
2.1
2.2
3.5
78
105
75
78
78
105
110
140
100
110
110
140
Product
code
NRAP10AA006
NRAP10AA012
NRAP62AA004
NRAP62AA006
NRAP62AA008
NRAP62AA012
44
Number
of
fibres
Nominal
O.D.
mm
Approximate
mass
kg/100m
6
12
9.8
12.2
0.8
1.1
Minimum bending
radius (mm)
No load
Full load
100
125
200
250
Construction options:
1. Multimode (62.5/125/250m) other sheath sizes 18 to 36 core.
2. Single mode (9/125/250m) 2 to 36 core.
3. Mixed fibre types.
4. Low Smoke Zero Halogen.
Product
code
NCAP62AA006
NCAP62AA012
FIBRE
COMMUNICATIONS
Fibre
type
Nominal
O.D.
mm
Maximum Att.
dB/km
850 1310 1551
nm nm nm
6
12
4
6
8
12
Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode
10.2
10.2
10.2
10.2
10.2
10.2
3.5
3.5
3.5
3.5
1.0
1.0
1.0
1.1
1.1
1.1
1.0
1.0
Product
code
Product
code
(nylon
oversheath)
NQCU10AA006
NQCU16AA012
NQCU62AA004
NQCU62AA006
NQCU62AA008
NQCU62AA012
NQDU10AA006
NQDU10AA012
NQDU62AA004
NQDU62AA006
NQDU62AA008
NQDU62AA012
Notes:
Minimum Bending Radius (mm) No load 85: Full load: 170.
Rated Tensile Strength: 150kg.
Maximum Crush resistance: 200kg/100mm.
Nominal Weight/km: PE sheath: 52. Nylon oversheath: 62.
Single mode 9/125/250m.
Multimode 62.5/125/250m.
45
COMMUNICATIONS
FIBRE
Fibre
type
6
8
12
18
24
36
6
8
12
18
24
36
Single mode
Single mode
Single mode
Single mode
Single mode
Single mode
Multi mode
Multi mode
Multi mode
Multi mode
Multi mode
Multi mode
Maximum Attentuation
dB/km
850 1310 1551
nm
nm
nm
3.5
3.5
3.5
3.5
3.5
3.5
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Product
code
Product
code
(nylon
oversheath)
NKCU10BA006
NKCU10BA008
NKCU10BA012
NKCU10BA018
NKCU10BA024
NKCU10BA036
NKCU62BA006
NKCU62BA008
NKCU62BA012
NKCU62BA018
NKCU62BA024
NKCU62BA036
NKDU10BA006
NKDU10BA008
NKDU10BA012
NKDU10BA018
NKDU10BA024
NKDU10BA036
NKDU62BA006
NKDU62BA008
NKDU62BA012
NKDU62BA018
NKDU62BA024
NKDU62BA036
Notes:
1. Single mode (9/125/250m). Multimode (62.5/125/250m).
2. Minimum Bending Radius (mm): No load 100, Full load 200.
3. Rated tensile strength: 200kg.
4. Maximum Crush Resistance: 200kg/100mm.
5. Nominal weight/km: PE sheath 85mm, nylon oversheath 99mm.
6. Nominal O.D. PE sheath 10.2mm, nylon oversheath 10.6mm.
46
FIBRE
COMMUNICATIONS
Nominal
O.D.
Aproximate
mass
mm
kg/100m
6
12
36
12.9
12.9
12.9
18.5
18.5
18.5
Maximum
Attenuation dB/km
850nm
1310nm
3.5
3.5
3.5
1.0
1.0
1.0
Product
code
NKGU62DA006
NKGU62DA012
NKGU62DA036
Notes:
1. Minimum Bending Radius (mm): No load 129, Full load 258.
2. Rated tensile strength: 275kg.
3. Maximum Crush Resistance: 448kg/100mm.
47
COMMUNICATIONS
TELEPHONE INT
INTERNAL
1/0.5mm PACW, PVC insulated, twisted pairs, PVC sheath.
Pairs
(1 Quad)
3
5
6
10
20
25
50
100
Nominal
conductor
diameter
mm
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
1.7
2.8
4.5
5.1
7.5
13.1
15.8
29.3
57.7
48
1000
300
300
300
300
300
300
300
300
Product
code
TLC590N3001
TLC590N3003
TJC590A5005
TJC590A5006
TJC590A9010
TJC590A9020
TJC590A9025
TJC590A9050
TJC590A9100
TELEPHONE EXT
COMMUNICATIONS
UNDERGROUND EXTERNAL
Plain Annealed Copper Wire (PACW), PE insulated,
twisted pairs, PE sheath.
Pairs
Nominal
sheath
thickness
mm
2
6
10
20
30
50
100
(1 Quad)
6
10
20
30
50
100
0.8
1.15
1.15
1.15
1.15
1.15
1.65
1.15
1.15
1.15
1.15
1.45
1.65
2.15
PE sheath
Product
code
Nominal Approx.
O.D.
mass
mm kg/100m
PE sheath with
nylon oversheath
Product Nominal Approx.
code
O.D.
mass
mm kg/100m
5.7
7.7
9.0
11.2
12.9
15.6
21.5
2.9
5.5
7.0
11.4
15.5
23.3
44.7
5.9
9.9
11.8
15.1
18.3
22.8
31.4
3.6
8.9
12.9
22.1
32.6
51.6
98.8
Pack size: 500m and 1000m drums. Other sizes available on application.
49
COMMUNICATIONS
TELEPHONE EXT
Nominal
sheath
thickness
mm
6
10
20
30
50
100
1.15
1.15
1.15
1.15
1.15
1.35
2
6
10
20
30
50
100
1.15
1.15
1.15
1.15
1.15
1.35
1.35
Product
code
PE sheath
Nominal Approx.
O.D.
mass
mm kg/100m
Product
code
Pack size: 500m and 1000m drums. Other sizes available on application.
50
Nylon jacket
Nominal Approx.
O.D.
mass
mm kg/100m
7.7
9.4
11.5
13.2
15.8
21.0
6.0
8.1
13.0
17.6
26.5
48.7
6.8
10.4
12.2
15.6
18.1
22.6
30.4
4.4
10.4
14.9
26.6
36.0
57.3
107.6
TELEPHONE EXT
COMMUNICATIONS
6
10
20
30
50
100
Nominal
sheath
thickness
mm
1.15
1.15
1.15
1.15
1.15
1.35
Product
code
PE sheath
Nominal Approx.
O.D.
mass
mm kg/100m
Product
code
Nylon jacket
Nominal Approx.
O.D.
mass
mm kg/100m
10.7
12.5
15.9
18.4
22.9
30.7
11.7
16.5
27.7
38.5
60.1
110.9
Pack size: 500m and 1000m drums. Other sizes available on application. Solid poly insulated.
AERIAL
0.64mm plain annealed copper wire, PE insulated, twisted
pair, tinned copper drain wire, PE sheath incorporating
a galvanised high tensile steel bearer wire in figure 8
construction.
Pairs
1
2
10
Size
Nominal
of bearer sheath thick.
mm
mm
1/1.25
1/1.25
1/2.50
Nominal
external dia.
mm
Approximate
mass
kg/100m
Product
code
TTA796IB001
TUA796IB002
TIA796IB010*
51
COMMUNICATIONS
TELEPHONE EXT
0.80
0.08
1.15
1.15
1.15
1.15
1.15
6
10
20
30
50
100
0.95
0.95
0.95
0.95
1.15
1.35
PE sheath
Product
code
Nominal Approx.
O.D.
mass
mm kg/100m
PE sheath
with nylon jacket
Product
Nominal Approx.
code
O.D.
mass
mm kg/100m
Pack size: 500m and 1000m drums, other sizes available on application.
52
5.7
6.3
9.8
12.3
13.6
16.2
21.3
2.9
4.5
9.2
14.0
19.5
29.0
51.0
10.7
13.0
15.9
18.4
22.9
30.7
11.7
16.5
27.7
38.5
60.1
110.9
TELEPHONE
COMMUNICATIONS
Nominal
O.D.
mm
Nominal
mass
kg/100m
Product
code
500
250
1.84
1.84
0.47
0.47
TJZ790A5717RWA5
TJZ790AA717RWA2
Pack
size
1
2
3
4
1.9
3.6
3.9
4.3
9.38
9.38
9.38
9.38
330
330
330
330
Product
code
J1721X000500
J1722X000500
J1723X000500
J1724X000500
53
COMMUNICATIONS
DATA CABLE
AUDIO CONTROL
7/0.25mm (22 AWG) tinned copper, polypropylene
insulated, twisted pairs, foil shield, 7/0.20 (24 AWG)
tinned copper drain wire, PVC jacket.
Pack
size
m
305 box
305 reel
500 reel
Nominal
Nominal
O.D.
velocity of
mm
propagation
4.3
4.3
4.3
66%
66%
66%
Nominal
pair capacitance
pF/500m
115*
115*
115*
203**
203**
203**
Product
code
J8723060U1000
J87230601000
J87230601640
54
DATA CABLE
COMMUNICATIONS
Nominal
O.D.
mm
Nominal pair
capacitance
pF/m
Product
code
1
2
5.9
8.6
12.8
12.8
J98410601000
J98420601000
Nominal
O.D.
mm
Nominal pair
capacitance
pF/m
Product
code
1
2
3
4
6
8
4.0
5.6
5.9
6.7
7.3
8.2
40
30
30
30
30
30
J95010601000
J95020601000
J95030601000
J59040601000
J95060601000
J95080601000
55
COMMUNICATIONS
DATA CABLE
Nominal insulation
thickness mm
Nominal
O.D. mm
Weight/
305m box
Product
code
1*
2
3
4
6
12.5
0.3
0.3
0.3
0.3
0.3
0.3
3.1
3.6
4.6
5.1
6.2
8.3
12.0
14.3
16.6
17.4
23.7
38.6
J1883A0081000*
JEIP87FG002GYA3
JEIP87FG003GYA3
JEIP87FG004GYA3
JEIP87FG006GYA3
JEIP87FG012GYA3
1
2
10
25
32
25
56
N/A
N/A
N/A
N/A
12.0
45
45
45
45
45
45
Product
code
JPMD06B1001
JPMD06B1002
JOCD56AA010
JOCD56AA025
JOCD56AA032
JOBD56AA025
DATA CABLE
COMMUNICATIONS
Pack
size
m
25
152
305
152
305
34
Nominal
capacitance
pF/m
Product
code
10.70
66%
45.9
98.4
J1401A
12.2
66%
45.9
98.4
J1403A
TRAFFIC DETECTOR
1.5mm2 stranded copper, PE insulated, twinned, jelly filled,
taped, PE sheathed, jelly coated, foil screened, with
7/0.25mm tinned copper drain wire, PVC sheath.
Number Nominal Nominal Charac- Mutual CapaciWater
of
insulation
O.D.
teristic capacitance
penecon- thickness
impedance tance unbalance* tration*
ductors
mm
mm
Ohms
nF/km
2
0.47
9.0
82100
6585
< 2%
Product
code
< 3% JTCD28A9002
57
COMMUNICATIONS
SECURITY CABLES
MULTICORE CIRCULAR
Copper conductor, PVC insulated, PVC sheath. Rated
50V AC/120V DC (not suitable for connection to mains).
Number
of
conductors
Nominal
insulation
thickness
Nominal
overall
diameter
Approximate
mass
mm
mm
kg/100m
4
6
0.25
0.25
4
6
0.45
0.45
7/0.20mm conductor
3.9
2
4.8
3
14/0.20mm conductor
5.4
4
6.4
6
Nominal
conductor
resistance
Ohms/km
@20C
Product
code
81.9
81.8
JSC.2xx4C*
JSC.2xx6C*
38.9
39.5
JSC.5xx4C*
JSC.4xx6C*
FLAT (FIGURE 8)
Copper conductor, PVC insulated only.
Number
of
conductors
58
Nominal
insulation
thickness
Nominal
diameter
Approximate
mass
mm
mm
kg/100m
0.45
0.8
7/0.20mm conductor
4.2 x 1.8
2
14/0.20mm conductor
5.8 x 2.9
3
Nominal
conductor
resistance
Ohms/km
@20C
Product
code
40.5
JSF.5
20.0
JSF.75
MICROPHONE
COMMUNICATIONS
Pack
size
m
Conductor
size
Nominal
O.D.
mm
Nominal
capacitance
pF/500m
Product
code
305 box
305 reel
5.6
5.6
79*
79*
144**
144**
J8760060U1000
J87600601000
4.5
4.5
79*
79*
154**
154**
J8761060U1000
J87610601000
305 box
305 reel
59
ACCESSORIES
GLANDS
Dim.B.
Dimension
B
mm
16
20
25
32
40
50
63
212
7.0
7.0
10.3
11.9
13.5
13.5
13.5
13.5
Dim.A.
Overall
length
mm
Between
centres
mm
55.0
55.5
69.0
90.0
108.0
126.0
141.0
150.0
34.0
34.9
41.3
54.0
63.5
76.2
84.1
95.3
Thickness Carton
quantity
mm
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
30
30
20
20
20
5
1
1
Product
code
ET16
ET20
ET25
ET32
ET40
ET50
ET63
ET75
ALCO LOCKNUTS
Nickel Plated (Unplated locknuts
use prefix U 16 to 63mm).
Mounting threading
diameter
mm
Dimension
across corner
mm
Carton
quantity
Product
code
2 26TPI
16
20
25
32
40
50
63
212 BSP
234 BSP
3 BSP
314 BSP
312 BSP
4 BSP
22
24
30
37
45
55
65
83
111
111
123
131
131
142
30
30
20
20
20
5
5
1
1
1
1
1
1
1
PLN12
PLN16
PLN20
PLN25
PLN32
PLN40
PLN50
PLN63
LN2.5
LN2.75
LN3
LN3.25
LN3.5
LN4
60
GLANDS
ACCESSORIES
Cable
Overall
Inside
Outside
Dimension A Dimension B Diameter C Diameter D
mm
mm
mm
mm
7.0
14.0
17.0
25.5
30.0
32.7
33.7
70
70
85
85
97
110
125
Dia.C.
Dim.A.
23
29
39
48
56
71
73
27
33
41
50
58
73
75
Dia.D.
Dim.B.
Carton
quantity
Product
code
50
40
20
20
5
5
5
SG1
SG2
SG3
SG4
SG5
SG6
SG7
Conductor size
mm2
Olex product
code
Clipsal product
code
20
25
25
25
25
32
32
32
40
50
50
50
63
63
75
75
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
FTDP05AA003
FTDP07AA003
FTDP09AA003
FTDP11AA003
FTDP13AA003
FTDP15AA003
FTDC17AA003
FTDC18AA003
FTDC19AA003
FTDC20AA003
FTDC22AA003
FTDP23AA003
FTDP24AA003
FTDP25AA003
FTDP26AA003
FTDP27AA003
A4 20
A4 25
A4 25
A4 25
A4 25
A4 32
A4 32
A4 32
A4 40
A4 50S
A4 50S
A4 50
A4 63S
A4 63
A4 75S
A4 75
61
ACCESSORIES
UA GLANDS
ALCO SERIES
UA GLANDS
Dia.A.
62
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
19
19
19
29
29
35
35
35
35
36
6.10
6.10
8.00
9.20
9.20
12.00
14.75
18.30
20.60
23.90
26.20
29.75
32.50
35.00
38.00
41.30
44.45
48.50
52.80
57.00
62.40
69.30
76.10
83.00
89.90
96.60
103.0
Dim.B.
Dim. B
Product
code
mm
16
16
16
16
18
18
18
19
19
20
20
25
25
29
29
29
29
30
30
43
35
35
35
48
48
48
48
UA12
UA16S
UA16
UA16L
UA20A
UA20B
UA20C
UA25A
UA25B
UA32A
UA32B
UA40A
UA40B
UA50A
UA50B
UA50C
UA50D
UA63A
UA63B
UA63C
UFPR250A
UFPR275A
UFPR300A
UFPR350A
UFPR350B
UFPR400A
UFPR400B
UG GLANDS
ACCESSORIES
ALCO SERIES
UG GLANDS
Dia.A.
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
9.90
11.90
13.00
14.70
15.90
17.50
19.00
20.60
22.20
23.80
25.80
27.00
28.60
30.20
31.80
Dim.B.
Dim. B
Product
code
mm
23.0
23.0
23.0
23.0
23.0
23.0
23.0
23.0
24.0
24.0
24.0
29.0
29.0
29.0
29.0
UG1B
UG1C
UG2A
UG2B
UG3A
UG3B
UG3C
UG3D
UG4A
UG4B
UG4C
UG5A
UG5B
UG5C
UG5D
63
ACCESSORIES
UFPR GLANDS
ALCO SERIES
UFPR GLANDS
Dia.A.
Dim.B.
64
12
12
13
15
18
18
20
20
29
29
29
29
29
29
35
35
35
35
36
6.2
9.1
12.0
14.5
18.2
21.9
25.6
29.8
34.2
39.1
44.0
48.7
55.5
62.4
69.3
76.1
83.0
89.9
96.6
9.1
12.0
14.5
18.2
21.9
25.6
29.8
34.2
39.1
44.0
48.7
55.5
62.4
69.3
76.1
83.0
89.9
96.6
103.0
25.3
27.5
30.2
36.0
41.6
45.9
49.8
55.0
72.1
72.1
87.6
87.6
97.4
105.0
113.0
127.0
127.0
143.0
143.0
17
17
17
21
22
22
22
22
34
34
35
35
35
35
35
48
48
48
48
1
1
2
3
4
4
5
5
6
7
15
15
15
10
5
5
3
3
2
2
2
2
1
1
1
1
1
1
1
UFPR20A
UFPR20B
UFPR20C
UFPR25A
UFPR32A
UFPR32B
UFPR40A
UFPR40B
UFPR50A
UFPR50B
UFPR63A
UFPR63B
UFPR250A
UFPR275A
UFPR300A
UFPR350A
UFPR350B
UFPR400A
UFPR400B
G GLANDS
ACCESSORIES
E
ALCO SERIES
G GLANDS
Dia.A.
Dia.B.
mm
16
20
20
25
25
32
32
40
50
50
63
212 BSP
212 BSP
10
10
10
10
10
10
10
15
15
15
19
19
19
Cable dimensions
Dia. A
Dia. B
obed
overall
mm
mm
7.2
11.0
13.8
16.3
18.8
22.8
26.5
32.8
38.5
44.5
56.3
60.4
66.7
10.8
17.0
20.0
22.5
26.0
30.0
34.0
41.5
49.0
55.5
68.3
73.0
79.4
SWA
diameter
Product
code
mm
Dim.
E SWA
exposed
mm
0.91.25
0.91.25
0.91.25
0.91.25
1.251.6
1.251.6
1.62.0
1.62.0
2.02.5
2.02.5
2.53.15
2.53.15
2.53.15
8.0
8.0
8.0
8.0
10.5
12.0
12.0
14.0
15.5
15.5
17.5
21.5
21.5
G164
G204
G206
G254
G256
G324
G326
G405
G503
G505
G636
G753
G755
65
ACCESSORIES
ALCO SERIES
WG GLANDS
WG GLANDS
Dia.A.
Dia.B.
Dim.C.
mm
16
14.00
16
14.00
20
14.00
20
14.00
20
14.00
20
14.00
25
14.00
25
14.00
32
14.00
32
14.00
40
15.00
40
15.00
40
15.00
50
15.00
50
15.00
50
15.00
50
15.00
63
19.00
63
19.00
63
19.00
212 BSP23.80
212 BSP23.80
212 BSP23.80
66
Dia. B
overall
mm
6.00
7.20
8.00
9.75
11.00
13.75
16.25
18.75
22.75
26.50
28.50
30.75
32.75
35.75
38.50
41.65
44.45
48.80
52.40
56.25
60.35
63.50
66.70
9.60
10.80
12.00
15.50
17.00
20.00
22.50
26.00
30.00
34.00
37.00
39.50
41.50
45.00
49.00
53.50
55.50
60.40
63.50
68.30
73.00
76.20
79.40
Armour
wires
mm
Dim.
C
mm
0.90
0.90
0.500.90
0.901.25
0.901.25
0.901.25
0.901.25
1.251.60
1.251.60
1.602.00
1.602.00
1.602.00
1.602.00
2.002.50
2.002.50
2.002.50
2.002.50
2.503.15
2.503.15
2.503.15
2.503.15
2.503.15
2.503.15
36.0
36.0
40.0
40.0
40.0
40.0
40.0
47.0
53.0
53.0
61.0
61.0
61.0
74.0
74.0
74.0
74.0
80.0
80.0
80.0
84.0
84.0
84.0
Length of Product
armour
code
to be
exposed
mm
8.00
8.00
8.00
8.00
8.00
8.00
8.00
10.50
12.00
12.00
14.00
14.00
14.00
15.50
15.50
15.50
15.50
17.50
17.50
17.50
23.00
23.00
23.00
WG162
WG164
WG202
WG203
WG204
WG206
WG254
WG256
WG324
WG326
WG403
WG404
WG405
WG502
WG503
WG504
WG505
WG634
WG635
WG636
WG753
WG754
WG755
FLPW GLANDS
ALCO SERIES
FLPW GLANDS
ACCESSORIES
Dia.B.
Dia.A.
Length
mm
mm
20
20
20
20
20
25
25
25
25
32
32
32
32
40
40
40
50
50
50
50
63
63
63
63
212 BSP
212 BSP
212 BSP
15.80
15.80
15.80
15.80
15.80
19.00
19.00
19.00
19.00
25.40
25.40
25.40
25.40
25.40
25.40
25.40
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
28.60
Max.
8.00
10.00
11.00
12.50
14.00
15.00
16.30
17.50
18.80
20.80
22.90
24.80
26.50
28.50
30.80
32.80
35.80
38.50
41.70
44.50
46.00
48.80
52.40
56.30
60.40
63.50
66.70
Dim.C.
Length of Product
armour
code
Dim. to be
C exposed
mm
mm
Dia. B
overall
mm
Armour
wire size
mm
12.00
15.50
17.00
20.00
20.00
22.50
22.50
26.00
26.00
30.00
30.00
34.00
34.00
37.00
39.50
41.50
45.00
49.00
53.50
55.50
57.20
60.40
63.60
68.30
73.00
76.20
79.40
0.500.90 53.0
0.901.25 54.0
0.901.25 54.0
0.901.25 54.0
0.901.25 54.0
0.901.25 56.0
0.901.25 56.0
1.251.60 56.0
1.251.60 56.0
1.251.60 65.0
1.251.60 65.0
1.602.00 65.0
1.602.00 65.0
1.602.00 73.0
1.602.00 73.0
1.602.00 73.0
2.002.50 90.0
2.002.50 90.0
2.002.50 90.0
2.002.50 90.0
2.002.50 97.0
2.503.15 97.0
2.503.15 97.0
2.503.15 97.0
2.503.15 102.0
2.503.15 102.0
2.503.15 102.0
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
13.5
13.5
13.5
13.5
15.5
15.5
15.5
17.0
17.0
17.0
17.0
19.0
19.0
19.0
19.0
23.0
23.0
23.0
FLPW202
FLPW203
FLPW204
FLPW205
FLPW206
FLPW253
FLPW254
FLPW255
FLPW256
FLPW323
FLPW324
FLPW325
FLPW326
FLPW403
FLPW404
FLPW405
FLPW502
FLPW503
FLPW504
FLPW505
FLPW633
FLPW634
FLPW635
FLPW636
FLPW753
FLPW754
FLPW755
67
CURRENT RATINGS
FLEXIBLE CORDS
3
7.5
10
15
20
25
T
38.20
25.40
19.10
13.00
7.82
4.85
Multicore
/km
P
39.00
26.00
19.50
13.30
7.98
4.95
68
T
40.10
26.70
20.00
13.70
8.21
5.09
Voltage drop
Single Three
phase phase
mV/A.m
64
47
32
18
13
55
41
28
16
11
COPPER AERIAL
CURRENT RATINGS
7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.78
19/2.14
37/1.78
37/2.03
37/2.25
37/2.52
1 core
insulated
conductors
still
air
35
48
65
88
105
130
165
200
235
265
310
1.0m/s
wind
70
96
125
165
205
240
305
360
425
475
540
2 and
3 core (a)
parallel webbed
3 and
4 core (b)
twisted
still
air
1.0m/s
wind
still
air
30
40
52
50
68
90
26
36
47
63
3
Phase
Voltage
Drop
1.0m/s at 50Hz
still mV/A.m
48
65
85
115
6.71
4.02
2.56
1.67
1.26
0.988
0.767
0.639
0.574
0.530
0.494
Note: The current carrying capacities are based on an air ambient temperature of 40C, a maximum
conductor temperature of 75C and exposure to direct sunlight having an intensity of 1000W/m2.
The values are based on the use of black PVC.
(a) Also for 2 conductor neutral screened aerial cable.
(b) Also for 3 and 4 conductor neutral screened aerial cable.
Under normal circumstances there will always be some air movement and the rating for 1.0m/s wind
is recommended.
General Note applies to all following current rating tables.
Reference should be made to AS/NZS3008.1 for the following derating factors for
(a) Grounded Circuits
(b) Cables fixed to underside of ceilings
(c) Cables on perforated or unperforated trays
(d) Ambient temperature and depth factors
69
CURRENT RATINGS
FLEXIBLES
FLEXIBLE CABLES
Nominal
conductor
area
Number
and nominal
diameter
of wires
mm2
no/mm
6
10
16
25
35
50
70
95
120
150
185
84/0.30
77/0.40
126/0.40
209/0.40
285/0.40
380/0.40
203/0.67
259/0.67
336/0.67
427/0.67
518/0.67
Single Phase
Protected
Exposed
from sun
to sun
Three Phase
Protected
Exposed
from sun
to sun
R-EP-90/
R-CPE-90
R-EP-90/
R-CPE-90
R-EP-90/
R-CPE-90
54
74
99
135
165
195
250
290
340
390
440
43
58
77
105
125
145
185
210
245
280
315
R-EP-90/
R-CPE-90
46
63
85
115
140
165
215
250
290
335
380
37
50
66
88
105
125
155
180
210
240
270
60
30
25
8
10
16
25
35
50
70
95
120
150
185
240
80
90
125
165
205
260
325
390
455
535
600
715
100
120
160
210
265
335
415
505
585
690
775
920
145
165
225
300
375
475
590
715
830
975
1095
1305
160
180
245
330
410
520
645
780
910
1070
1200
1430
Max D.C.
resistance
at 20C
(m/m)
1.843
1.162
0.749
0.530
0.375
0.267
0.198
0.153
0.123
0.097
0.076
Continuous
Heavy
Light industrial
Limited input
100%
60%
30%
25%
Duty cycle is defined as the ratio of the total time a cable carries a welding current, to the total time
that the welding supply is available, expressed as a percentage. The 100% duty cycle is based on a
cycle time to one hour, other duty cycles on a cycle time of five minutes.
70
71
96
120
145
185
230
270
305
355
425
495
580
670
790
68
92
115
140
175
215
250
285
330
395
455
530
620
730
Al
Cu
16
21
29
39
49
67
89
120
145
175
225
275
320
365
425
510
580
680
780
900
mm2 Cu
1 16
1.5 21
2.5 30
4 40
6 51
10 69
16 92
25 125
35 155
50 185
70 240
95 295
120 345
150 395
185 460
240 550
300 640
400 740
500 870
630 1010
Al
Spaced
from
surface
Cond. Spaced
size
Unenclosed
Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
310
360
430
495
580
670
770
55
75
93
115
145
180
210
240
280
335
385
455
530
630
Al
Cu
13
16
22
30
38
53
71
97
115
140
175
210
250
280
325
385
57
79
92
110
140
165
195
225
255
305
Al
Cu
10
13
18
24
31
42
57
79
92
110
140
165
195
225
255
300
95
125
145
175
215
255
295
330
375
435
490
560
640
740
Al
Cu
18
24
33
42
53
71
91
120
145
170
210
260
295
335
380
450
510
590
670
770
70
92
110
135
165
200
230
260
300
350
400
465
530
620
Al
Cu
21
27
37
48
60
79
100
135
160
190
235
285
320
360
415
480
560
630
730
830
4.68
2.95
2.14
1.582
1.100
0.804
0.644
0.535
0.439
0.352
0.300
0.256
0.226
0.202
Al
Single
phase
voltage
drop
mV/A.m
Cu
51.6
33.0
18.0
11.2
7.50
4.49
78 2.81
100 1.78
125 1.29
145 0.963
180 0.680
220 0.507
250 0.415
285 0.352
325 0.301
380 0.255
430 0.229
500 0.209
570 0.194
660 0.181
Al
Al Cu
24
31
43
56
71
94
28 120
37 160
46 190
225
275
330
380
425
480
560
630
710
800
900
Completely
surrounded
by thermal
insulation
Al Cu
6
8
12
16
20
27
45 36
62 48
72 59
87
110
130
155
175
200
235
Touching In conduit or
unenclosed partially
surrounded by
Conduit thermal
in air insulation
Enclosed
71
72
mm2 Cu
1
20
1.5 26
2.5 36
4
48
6
61
10
84
16 110
25 150
35 185
50 230
70 290
95 360
120 420
150 485
185 570
240 680
300 790
400 920
500 1080
630 1260
Al
87
115
145
175
225
280
330
375
440
530
610
720
850
1000
Cond. Spaced
size
Cu
20
25
36
47
60
82
110
145
175
215
275
340
395
450
520
620
720
840
970
1110
Al
84
110
135
165
210
260
305
350
405
485
560
660
770
900
Spaced
from
surface
Unenclosed
Cu
16
20
28
37
47
65
86
115
145
175
225
280
325
375
435
520
610
710
820
950
Al
67
91
110
135
175
215
255
290
340
410
475
560
660
770
Cu
16
20
28
37
47
65
86
115
145
175
220
260
310
350
400
475
Al
12
16
22
30
39
54
67
91
110
135
175
215
255
290
340
400
Cu
14
17
24
32
40
56
74
100
120
145
180
215
255
285
330
390
Al
11
13
19
25
32
44
58
81
94
115
140
170
200
230
260
310
Enclosed
Cu
8
10
14
19
24
32
43
58
72
Al
105
140
165
200
245
290
330
370
425
490
560
640
730
830
Buried
direct
Al
Cu
28
36
50
64
80
105
33 140
45 180
56 215
255
315
375
425
480
540
630
710
810
910
1030
Completely
surrounded
by thermal
insulation
Cu
21
27
37
48
60
80
105
135
160
195
240
290
335
375
435
510
580
670
760
890
Al
80
105
125
150
185
225
260
290
335
400
450
530
610
720
Cu
24
31
42
55
68
90
115
150
180
215
265
315
365
410
470
550
630
720
820
950
Al
89
115
140
165
205
245
285
320
365
425
490
560
650
750
CURRENT RATINGS
2 1 CORE XLPE
66
88
110
130
165
205
240
270
315
375
430
500
580
62
83
100
125
155
190
225
255
295
350
400
465
540
Al
Cu
14
18
26
34
44
60
80
105
130
160
200
250
290
330
375
445
510
590
670
Al
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cu
15
19
27
37
46
64
85
115
140
170
215
265
305
350
405
475
550
630
720
Touching
Cond. Spaced
size
Unenclosed
Cu
11
14
20
26
34
47
63
88
105
125
155
190
225
255
295
345
400
465
540
48
67
78
94
120
145
170
190
220
260
300
350
405
Al
Conduit
in air
round
cable
Cu
13
17
22
29
37
50
66
89
105
125
50
67
78
94
Al
Cu
10
13
18
24
31
43
57
79
92
110
140
165
195
220
255
300
345
405
465
44
62
72
87
110
130
155
175
200
240
275
320
370
Al
In conduit or
unenclosed partially
surrounded by
Conduit in air thermal
flat cable insulation
Enclosed
Cu
7
9
13
17
22
30
40
53
65
31
41
51
Al
Completely
surrounded
by thermal
insulation
Cu
22
28
40
52
65
87
115
145
180
210
260
310
355
400
450
520
590
660
740
88
115
140
165
200
240
275
310
350
405
460
530
600
Al
Cu
17
22
31
40
51
68
88
115
140
165
205
250
290
325
370
430
495
560
650
68
89
110
130
160
195
225
250
290
335
390
445
520
Al
Cu
51.6
33.0
18.0
11.2
7.50
4.46
2.81
1.78
1.28
0.951
0.673
0.498
0.405
0.342
0.290
0.243
0.215
0.194
0.180
4.66
2.93
2.13
1.57
1.10
0.798
0.638
0.528
0.431
0.343
0.290
0.245
0.215
Al
Single
phase
voltage
drop
mV/A.m
2 CORE PVC
CURRENT RATINGS
73
74
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cond.
size
Cu
18
24
34
45
57
78
105
140
175
210
270
330
385
440
510
600
690
800
920
Al
81
110
135
165
210
255
300
340
395
470
540
640
730
Spaced
Cu
17
22
31
42
53
73
97
130
160
195
250
310
360
410
475
560
640
750
850
Al
75
100
125
155
195
240
280
320
370
440
510
590
680
Touching
Unenclosed
Cu
13
17
24
33
42
59
79
110
130
160
200
240
285
325
375
445
520
600
770
Al
10
13
18
24
32
44
60
84
99
120
155
185
220
250
290
350
405
475
620
Cu
14
17
24
32
41
56
74
105
120
145
180
215
255
285
330
390
450
520
620
Al
11
14
18
25
32
44
58
81
94
115
140
170
200
230
265
310
355
415
495
In non-metallic wiring
unenclosed partially
surrounded
Non-metallic
by thermal
wiring
enclosure in air insulation
Enclosed
Cu
9
11
16
21
27
36
49
66
81
Al
38
51
63
Completely
surrounded
by thermal
insulation
Cu
26
33
46
60
75
100
130
170
205
245
300
360
410
460
520
600
680
770
860
Al
100
130
160
190
235
280
320
355
405
470
530
610
690
Buried
direct
Cu
20
25
35
46
57
77
100
130
160
190
235
285
325
375
425
500
570
650
750
Al
78
100
120
145
180
220
255
290
330
390
450
520
600
Underground
non-metallic
wiring enclosure
CURRENT RATINGS
2 CORE XLPE
Cu
14
17
25
33
42
56
77
105
125
155
195
245
285
330
385
455
530
610
710
820
Al
59
80
99
120
155
190
225
255
300
355
415
485
570
670
Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
310
355
425
490
570
660
760
Al Cu
11
14
20
26
34
47
55 62
75 87
93 100
115 125
145 155
180 185
210 220
240 250
280 285
330 340
385 390
455 455
530 530
630 620
Al Cu
10
12
17
23
29
39
48 52
68 72
79 84
95 100
120 125
145 150
170 175
195 200
220 230
265 270
305 310
355 360
410 415
480 485
Al Cu
6
8
12
16
20
27
40 36
56 48
65 59
79
99
120
140
160
180
215
250
290
335
390
Al Cu
21
27
37
49
61
81
28 105
37 135
46 160
190
235
280
315
355
400
465
520
590
670
750
Al
61
80
97
115
145
175
200
230
260
305
350
405
465
540
Cu
19
25
34
44
54
72
92
120
145
170
210
255
290
320
370
430
495
560
650
730
Cu
44.7
28.6
15.6
9.71
6.49
3.86
71 2.43
92 1.54
110 1.12
130 0.834
165 0.589
195 0.439
225 0.359
255 0.305
290 0.261
335 0.221
385 0.198
490 0.181
510 0.168
580 0.157
Al
Al
Cu
44.7
28.6
15.6
9.71
6.49
3.86
4.05 2.43
2.55 1.55
1.85 1.12
1.37 0.84
0.952 0.597
0.696 0.449
0.558 0.371
0.463 0.319
0.380 0.277
0.305 0.240
0.260 0.219
0.222 0.202
0.196 0.191
0.175 0.181
Al
68
93
115
140
180
225
260
300
345
415
485
570
660
790
Al Cu
16
20
28
37
46
61
81 80
105 105
125 125
145 150
180 185
215 225
245 260
275 290
310 335
365 390
410 450
470 510
540 590
620 660
Underground
ducts
mm2 Cu
1 16
1.5 20
2.5 29
4 38
6 49
10 67
16 89
25 120
35 150
50 180
70 230
95 285
120 335
150 385
185 445
240 540
300 620
400 730
500 850
630 990
Buried
direct
Three phase
voltage drop
mV/A.m
Enclosed
Unenclosed
Al
4.05
2.55
1.85
1.37
0.956
0.702
0.565
0.472
0.391
0.319
0.276
0.240
0.216
0.197
75
76
Enclosed
mm2 Cu
1 19
1.5 25
2.5 35
4 46
6 59
10 81
16 110
25 145
35 180
50 220
70 280
95 350
120 410
150 470
185 550
240 660
300 770
400 900
5001050
6301230
Al Cu Al
16
21
30
40
50
69
84 92 71
115 125 97
140 155 120
170 190 145
220 240 185
270 300 230
320 350 270
365 405 315
425 470 365
510 560 440
600 650 510
700 760 600
830 870 700
9801010 820
Cu
16
20
28
37
47
65
86
115
145
175
225
280
325
375
435
520
600
700
810
940
Al Cu
14
18
25
33
42
58
67 78
91 110
110 125
135 155
175 190
215 230
255 270
290 310
340 355
405 420
470 485
560 560
650 650
770 760
Al Cu
10
12
17
28
36
50
64 66
90 92
105 105
125 130
160 160
195 195
230 225
260 255
300 295
360 350
415 400
485 465
560 540
660 630
Al Cu
8
10
14
19
24
32
53 43
73 58
85 72
100
130
155
180
205
235
275
320
370
425
500
Al Cu
24
31
42
55
68
91
33 115
45 150
56 180
215
260
315
365
400
450
520
590
670
750
840
Underground
ducts
Al Cu Al Cu Al Cu
18
22
46.8
23
28
30.0
32
39
16.4
41
50
10.2
52
62
6.81
69
81
4.05
96 89 69 105 80 2.55
115 115 90 135 105 1.62
140 140 110 160 125 1.17
165 170 130 195 150 0.872
205 210 165 235 185 0.615
245 250 195 280 220 0.457
275 290 225 325 255 0.373
310 330 255 365 280 0.316
350 375 290 420 325 0.269
410 440 345 485 380 0.227
465 510 400 560 435 0.202
530 580 455 640 500 0.183
600 670 540 720 570 0.170
690 760 620 830 660 0.159
Buried
direct
Unenclosed
Cu
46.8
30.0
16.4
10.2
6.81
4.05
4.25 2.55
2.67 1.62
1.94 1.18
1.43 0.878
0.997 0.623
0.727 0.467
0.582 0.385
0.482 0.330
0.394 0.285
0.314 0.245
0.266 0.222
0.226 0.205
0.197 0.193
0.177 0.182
Al
Three phase
voltage drop
mV/A.m
4.25
2.67
1.94
1.44
1.00
0.733
0.589
0.491
0.404
0.327
0.281
0.243
0.216
0.198
Al
CURRENT RATINGS
31 CORE XLPE
56
75
93
115
145
180
205
235
275
325
375
440
500
53
71
87
105
135
165
195
220
255
305
345
405
460
Al
Cu
12
15
22
29
37
51
68
91
110
135
170
215
245
280
325
385
440
500
570
Al
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cu
13
16
23
31
40
54
72
97
120
145
185
230
265
305
350
410
470
540
620
Touching
Cond. Spaced
size
Unenclosed
Cu
10
13
18
24
31
42
56
79
92
110
140
165
195
225
260
305
43
60
70
84
105
125
150
170
195
230
Al
Cu
12
15
20
26
34
46
60
83
92
110
46
63
70
84
Al
Cu
10
12
17
22
29
39
52
72
84
100
125
150
175
200
230
270
40
56
65
79
99
120
140
160
180
215
Al
Conduit In conduit or
in air unenclosed partially
round surrounded by
cable
Conduit in air thermal
flat cable insulation
Enclosed
Cu
6
8
11
15
19
25
34
46
56
26
35
43
Al
Completely
surrounded
by thermal
insulation
Cu
19
24
34
44
55
74
96
125
150
180
220
265
300
335
380
440
495
560
620
75
97
115
140
170
205
235
265
300
345
390
450
500
Al
Cu
15
19
26
34
43
57
74
96
115
140
175
210
240
270
310
370
415
480
540
58
75
91
110
135
165
190
210
245
290
325
385
435
Al
Cu
44.7
28.6
15.6
9.71
6.49
3.86
2.43
1.54
1.11
0.829
0.583
0.431
0.351
0.296
0.251
0.210
0.186
0.168
0.156
4.04
2.54
1.84
1.36
0.948
0.691
0.552
0.457
0.373
0.297
0.251
0.212
0.186
Al
Three
phase
voltage
drop
mV/A.m
77
78
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cond.
size
Cu
16
20
28
38
48
66
88
120
145
180
230
285
330
375
435
520
590
680
780
Al
68
93
115
140
180
220
255
295
340
405
465
550
630
Spaced
Cu
14
19
26
35
45
62
83
110
135
170
215
265
305
350
405
480
550
630
720
Al
64
86
105
130
165
205
240
270
315
375
430
500
580
Touching
Unenclosed
Cu
12
16
22
29
38
53
70
98
115
140
175
210
250
280
325
385
54
76
89
110
135
165
195
220
255
305
Al
Cu
12
16
21
28
36
50
66
92
105
130
160
195
225
255
295
350
53
73
85
100
130
155
180
205
235
275
Al
In conduit or unenclosed
partially surrounded by
thermal
Conduit insulation
in air
Enclosed
Cu
6
8
11
15
19
25
34
46
56
26
35
43
Al
Completely
surrounded
by thermal
insulation
75
97
115
140
170
205
235
265
300
345
390
450
500
Al
Buried direct
Cu
19
24
34
44
55
74
96
125
150
180
220
265
300
335
380
440
495
560
620
Cu
15
19
26
34
43
57
74
96
115
140
175
210
240
270
310
370
415
480
540
58
75
91
110
135
165
190
210
245
290
325
385
435
Al
U/ground ducts
Cu
46.8
30.0
16.4
10.2
6.80
4.05
2.55
1.61
1.17
0.868
0.609
0.450
0.366
0.307
0.259
0.216
0.190
0.171
0.158
4.24
2.67
1.93
1.43
0.993
0.723
0.577
0.476
0.388
0.307
0.258
0.216
0.189
Al
Three
phase
voltage
drop
mV/A.m
CURRENT RATINGS
3 & 4 CORE XLPE
GENERAL
CABLE SELECTION
The size and type of cable required for a given application should be
selected according to the following criteria:
1. Current carrying capacity and voltage drop
Conductor sizes are nominated by the Wiring Rules (AS/NZS3000)
for the wiring of socket outlets and lighting circuits in domestic and
commercial buildings.
For other types of installations:
a) The cable must be capable of carrying the maximum continuous load
of the circuit, with due regard for the insulating material and conditions
of installation.
b) The voltage drop from the consumers terminals to any point in the
installation must not exceed 5% of the nominal system voltage.
Simplified tables of current ratings and voltage drops for commonly used
cables are given on pages 68 to 78.
In large installations where current ratings are critical, attention is drawn
to the comprehensive tables given in AS/NZS3008.1.1:1998.
2. Installation conditions
Olex cables are available for aerial, underground and submarine
installations as well as in conduit, on racks or trays in air.
Special constructions available include:
Brass or copper taped or nylon sheathed cables for resistance
to termite and marine borer.
Steel wire or tape armoured for areas where there is a high risk
of mechanical damage.
Pyrolex fire performance low smoke halogen free cables for emergency power and lighting and other purposes in areas of high fire risk.
Lead alloy sheathing as a barrier to moisture or hydrocarbons.
Envirolex cables with low smoke emission and no halogen
for environmentally sensitive areas.
Flexolex cables for flexible applications and where flexibility provides
advantages during installation.
79
GENERAL
3. Cable insulating and sheathing materials
Standard Olex cables are available in a number of materials, including
the following:
Olex PVC (Polyvinyl Chloride) insulated and sheathed cables are the
economic choice for general wiring. They are resistant to occasional
contact with most oils and solvents, clean and easy to handle and
coloured to assist phase identification. PVC is suitable for operating
temperatures up to 90C and 90HT, subject to the requirements
of AS/NZS3000.
PVC is inherently resistant to ultraviolet radiation and although some
colours may fade the material will not significantly degrade due to the
effects of sunlight and weather, maintaining its physical integrity if not
physically abused.
Care should be taken where cables are subjected to extremes of
temperature or contact with crude petroleum, caustic materials
or aromatic solvents.
80
Olex synthetic rubber (EPR/CPE) insulated and sheathed cables are more
flexible and have better resistance to oils and solvents than PVC.
Olex EPR (Ethylene Propylene Rubber), while not oil resistant, has
excellent dielectric properties and high voltage grades are available for
cables up to 33kV. In addition, EPR is halogen free and therefore does
not emit toxic or corrosive by-products when burnt.
Olex CPE (Chlorinated Polyethylene) is an excellent flexible insulation
and heavy duty sheathing material. Although having lower insulation
resistance than EPR it is suitable for low voltage cable insulation and
is used as such in welding cables because of its oil resistance.
For special purposes a sheath of Olex EA (Ethylene Acrylic) material
can be provided subject to special order. This material is halogen free,
extremely flame retardant and has better oil resistance than CPE.
EPR/EA cables can safely be used in plenum air ducts and other
applications where high flame retardance and freedom from acid gas
emission is required. EPR, CPE and EA are all suitable for continuous
operation up to 90C.
GENERAL
In all cases, cables must be installed in compliance with
the safety requirements of AS/NZS3000.
Particular attention should be paid to the following:
Current carrying capacities of cables depend on the temperature of the
air or ground in which they are installed and the degree to which heat
can escape. Except for a group of single core cables carrying the phase
currents of a circuit, cables should be spaced to allow heat to escape.
Wherever cables are installed in close proximity, especially in the
ground, or enclosed in such a way as to restrict heat loss, their current
carrying capacities must be reduced using a derating factor appropriate
to the situation.
For minimum voltage drop single core cables carrying the phase
currents of a single circuit should be installed as closely as possible
together, to minimise inductive reactance. The preferred formation for
three phase conductors is a trefoil or cloverleaf pattern although flat
formation may also be used. Sheaths should be in contact with one
another in either case.
A single core cable generates an alternating magnetic field around itself
which can cause large increases in voltage drop and power loss due to
transformer effect when ferrous metal (iron and steel) is allowed to
encircle the cable. Steel racking or ladder will not cause trouble, but the
following must be observed:
Steel wire or tape armour is never used on a single core cable for AC use.
Where three single phase cables pass through a steel bulkhead all must
pass through the same hole. Where glanding is required it is usual to
cut out a panel and replace this with a non-ferrous (metal or plastic)
plate in which the three or four glands are mounted.
81
GENERAL
Minimum size of Copper earthing conductors.
Nominal area
ACTIVE conductors
mm2
For COPPER
active conductors
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
For ALUMINIUM
active conductors
mm2
1.0*
1.5*
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120
120
120
120
2.5
2.5
4
6
6
10
10
16
25
25
35
50
70
95
95
120
Elastomer
82
V75
V90
V90-HT
R-EP-90
R-CPE-90
R-S-150
C
75
90
90*
90
90
150
75
90
80
GENERAL
Conductor resistances for insulated cables for
fixed installations. Solid, stranded conductors;
also refer to AS1125.
Nominal
conductor
area
Conductor
type
Copper
mm2
0.5
1.0*
1.0
1.5*
1.5
2.5*
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Solid
Solid
Stranded
Solid
Stranded
Solid
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
Stranded
36.7
18.2
21.6
12.2
13.8
7.35
7.56
4.70
3.11
1.84
1.16
0.734
0.529
0.391
0.270
0.201
0.154
0.126
0.100
0.0762
0.0607
0.0475
0.0369
0.0286
Aluminium
Plain
36.0
18.1
21.2
12.1
13.6
7.28
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.199
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
1.91
1.20
0.867
0.641
0.443
0.329
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
83
GENERAL
Useful 3 phase formulae
kW = kVA pf
kW =
hp 746
1000 Eff
kW =
kVA =
kW
pf
kVA =
hp 746
1000 Eff pf
kVA =
Line Amps =
kW 1000
Line Volts 1.732 pf
Line Amps =
kVA 1000
Line Volts 1.732
Line Amps =
hp 746
Line Volts 1.732 Eff pf
kW 1000 Eff
Horsepower
=
(hp) = 746
84
hp =
hp =
GENERAL
American conductor sizes M.C.M. & A.W.G. conversion
to mm2.
M.C.M.
mm2
M.C.M.
mm2
1300
1200
1100
1000
950
900
850
800
750
700
659
608
557
507
481
456
431
405
380
355
650
600
550
500
450
400
350
300
250
200
329
304
279
253
228
203
177
152
127
101
Note: The American term mil refers to a milli-inch (1/1000) NOT a millimetre.
A Circular Mil. (C.M.) is the area of a circle 1 mil in diameter.
The term M.C.M. refers to an area of 1000 Circular Mils.
1.0mm2 is approximately 2000 Circular Mils.
A.W.G.
Diameter
mm
mm2
A.W.G.
Diameter
mm
mm2
0000
000
00
0
2
4
6
8
11.68
10.40
9.27
8.25
6.54
5.19
4.12
3.25
107.3
85.0
67.4
53.5
33.6
21.2
13.3
8.4
10
12
14
16
18
20
22
24
2.59
2.05
1.63
1.29
1.02
0.81
0.64
0.51
5.3
3.3
2.1
1.3
0.8
0.5
0.3
0.2
Note: The American Wire Gauge (AWG) was originally known as the Brown & Sharp (B&S) Gauge
and both terms are synonymous.
Note: The gauge number can apply to a single wire or to a standard or bunched conductor.
The cross-sectional areas given apply to single wire only.
Note: The larger gauges are sometimes written using a number to denote the number of zeroes,
e.g. 0 gauge can be written 1/0 and 000 as 3/0.
85
GENERAL
Cable minimum installed bending radii.
Type
Fixed wiring
Flexible Cords
Voltage
Flexible Cables
Lead Sheath
Paper Insulated
PVC or Elastomer
PVC or Elastomer
Single
Multicore
Single Core
Multicore
Single Core
Multicore
Trailing
Elastomer
(1) Single and Multicore
(2) Single and Multicore
Welding
PVC or Elastomer
Nylon Covered All Cables
HDPE Sheathed All Cables
0.6/1kV
0.6/1kV
0.6/1kV
0.6/1kV
250/440V
0.6/1kV
0.6/1kV
0.6/1kV
Up to 11kV
Up to 11kV
22kV
22kV
33kV
33kV
Factor
4
6
12
8
4
4
4
12
12
15
18
15
20
18
1.1kV
6
3.3kV & above 12
0.6/1kV
6
20
15
86
0.37
0.55
0.75
1.1
1.5
1.8
2.2
4
0.5
0.75
1
1.5
2
2.5
3
5
2.2
3.2
4.3
6.5
8.6
10.8
13.0
21.6
0.7
1.1
1.4
2.2
2.9
3.6
4.3
7.2
Power
Single phase Three phase
kW
hp
240V
415VkW
5.5
7.5
9.3
11
15
18.5
22
7.5
10
12.5
15
20
25
30
32.4
10.8
14.4
18.0
21.6
28.8
36.0
43.2
GENERAL
Recommended maximum number of thermoplastic insulated
unsheathed single core 0.6/1kV Copper or Aluminium cables
permitted in metallic and non-metallic conduit or pipe.
Nominal
area
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
31
24
18
11
9
7
5
3
2
1
1
1
1
56
43
33
20
17
12
9
5
4
3
2
1
1
1
1
1
51
40
30
19
15
11
8
5
4
3
2
1
1
1
1
90
69
52
33
27
19
14
9
7
5
4
3
2
1
1
1
1
1
84 148 137
65 114 106
49 86 80
30 54 50
25 44 41
18 31 29
13 23 22
8 14 13
6 11 11
5 9 8
4 7 6
3 5 5
2 4 4
1 3 3
1 2 2
1 1 1
1 1 1
1 1
1 1
1 1
76 106
62 87
44 61
33 46
20 28
16 23
12 17
9 13
7 10
6 8
5 6
4 5
2 4
2 3
1 2
1 1
1 1
Notes:
1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or
with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of
PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn
into the conduit.
2. One earth wire of appropriate size, as determined by the requirements of AS/NZS3000, may be
inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables.
87
GENERAL
Recommended maximum number of thermoplastic insulated
and sheathed single core Copper or Aluminium cables
permitted in metallic and non-metallic conduit or pipe.
1.0 to 25mm2 450/750V to AS/NZS5000.2
35 to 630mm2 0.6/1kV to AS/NZS5000.1
Nominal
area
mm2
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
88
25
HD
32
HD
40
HD
50
HD
63
HD
65
HD
80
HD
100
HD
150
HD
7
7
5
3
3
1
1
1
15
7
7
5
4
3
2
1
1
27
23
17
10
8
6
4
3
1
1
1
43
37
27
19
16
10
7
5
2
1
1
1
1
61
45
31
26
17
12
9
4
3
2
1
1
1
1
1
51
43
29
21
16
6
5
4
3
2
1
1
1
1
1
44
33
23
9
7
6
4
4
3
2
1
1
1
1
1
33
13
10
8
6
5
4
3
3
2
1
1
1
17
13
10
9
7
6
5
4
3
2
1
20
17
14
11
9
7
6
5
4
Notes:
1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or
with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of
PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn
into the conduit.
2. One earth wire of appropriate size, as determined by the requirements of AS/NZS3000, may be
inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables.
GENERAL
Cables in conduit and pipe space factors.
One cable in conduit or pipe
Two cables in conduit or pipe
Three or more in conduit or pipe
50%
33%
40%
Maximum tension
kN per conductor
Copper
Aluminium
0.11
0.18
0.28
0.42
0.70
1.12
0.08
0.13
0.20
0.30
0.50
0.80
Conductor
area
mm2
25
35
50
70
95
Maximum tension
kN per conductor
Copper
Aluminium
1.75
2.45
3.50
4.90
6.65
1.25
1.75
2.50
3.50
4.75
(1kN = 102kgf)
89
ABBREVIATIONS
A.m
ABC
AC
Al
AS
C
C
CPE
CSA
CSP
90
Ampere metre
aerial bundled cable
alternating current
Aluminium
Australian Standard
core
degree Celsius
Chlorinated Polyethylene
cross-sectional area
Chlorosulphinated
Polyethylene
Cu
Copper
dB
Decibel
DC
direct current
E
earth
EA
Ethylene Acrylic
Eff
efficiency
ELV
Extra Low Voltage
EPR
Ethylene Propylene Rubber
HD
hard drawn
H.D.
heavy duty
HFS-90-TP halogen free sheath
90C thermoplastic
HF-110-R halogen free
110C rubber (sheath)
hp
horsepower
HR
heat resistant
HRC
high rupture capacity
ISDN
Integrated Services
Digital Network
kg
kilogram
kN
kilonewton
kV
kilovolt
kVA
kilovoltamp
kW
kilowatt
LAN
L.D.
mm
MM
nF/km
OD
O.D.
PACW
PE
pf
pF/m
PILC
AUSLEC BRANCHES
91
92
Smithfield
St Marys
Tamworth
Wagga Wagga
Warilla
Windsor
Wollongong
Northern Territory
Alice Springs
Phone: (08) 8952 2878
Darwin
Phone: (08) 8984 3900
Katherine
Phone: (08) 8972 2033
Palmerston
Phone: (08) 8932 1511
Queensland
Ayr
Beenleigh
Browns Plains
Bundaberg
Caboolture
Cairns
Capalaba
Coorbaroo
Currumbin
Emerald
Geebung
Gympie
Hervey Bay
Ipswich
Lawnton
Mackay
Mansfield
Maroochydore
Milton
Nambour
Nerang
Noosa
Redcliffe
Rockhampton
Rocklea
Slacks Creek
Southport
Sumner Park
Surfers Paradise
Toowoomba
Townsville
South Australia
Berri
Blair Athol
Clovelly Park
Glynde
Holden Hill
Kilkenny
Kurralta Park
Lonsdale
Mount Barker
Mount Gambier
Naracoorte
Nuriootpa
Port Adelaide
Port Lincoln
Port Pirie
Salisbury South
Tasmania
Devonport
Hobart
Launceston
Victoria
Airport West
Ballarat
Bayswater
Bendigo
Berwick
Brunswick
Coburg
Dandenong
Fawkner
Frankston
Geelong
93
HEAD OFFICE
207 Sunshine Road, Tottenham Vic. 3012
Phone 03 9281 4444 Fax 03 9314 0383
For more information on the complete Olex Cables range, see www.olexcables.com.au
New South Wales
STATE OFFICE 8 South Street, Rydalmere NSW 2116
Phone 02 8845 6111 Fax 02 8845 6150
NEWCASTLE Suite 9, 115 Darby Street, Newcastle NSW 2300
Phone 02 4929 3977 Fax 02 4929 3975
Queensland
STATE OFFICE 541 Bilsen Road, Geebung Qld 4034
Phone 07 3259 2600 Fax 07 3259 2606
TOWNSVILLE 16 Leyland Street, Townsville Qld 4810
Phone 07 4779 0322 Fax 07 4779 7201
Victoria and Tasmania
STATE OFFICE 11 Newcastle Road, Bayswater Vic. 3153
Phone 03 9237 8188 Fax 03 9729 8144
South Australia
STATE OFFICE 539 South Road, Regency Park SA 5010
Phone 08 8268 3266 Fax 08 8347 0879
Western Australia
STATE OFFICE 503 Abernethy Road, Kewdale WA 6105
Phone 08 9353 1122 Fax 08 9353 2688
Australian Capital Territory
STATE OFFICE Suite 8, 29 Townsville Street, Fyshwick ACT 2609
Phone 02 6280 8130 Fax 02 6280 8135
Northern Territory
94
MANUFACTURING LOCATIONS
Tottenham
207 Sunshine Road, Tottenham Vic. 3012
Lilydale
55 Main Street, Lilydale Vic. 3140
Wetherill Park
29 Davis Road, Wetherill Park NSW 2164
INTERNATIONAL SALES OFFICES
Head Office
Olex Cables, 207 Sunshine Road, Tottenham Vic. 3012 Australia
Phone 61 3 9281 4444 Fax 61 3 9314 0383
New Zealand
Olex Cables (NZ), Paraite Road, Bell Block, New Plymouth, New Zealand
Phone 64 6 755 3799 Fax 64 6 755 3790
Singapore
No 6 Loyang Way 1 #02-02, Singapore 508707
Phone 65 546 2788 Fax 65 546 2766
Malaysia
Lot T1, Centrepoint, Lebuh Bandar Utama, Bandar Utama 47800,
Petaling Jaya, Malaysia
Phone 60 3 710 4901 Fax 60 3 710 4910
China
Room 57119, Building 7#, Xiyuan Hotel, Beijing China 100044
Phone 86 10 6831 8549, 86 10 6835 1019, 86 10 6831 3388 ext. 57119, 57120
Fax 86 10 6832 1963
95
Olex Cables has taken every precaution to ensure that the information contained in this
booklet is in line with requirements of the appropriate Australian Standards and correct
electrical practice. However, we accept no liability of any kind with respect to the
information presented here.
Note: Current-carrying capacity tables stated in this handbook are based on
AS/NZS3008.1, Electrical Installations Selection of Cables. Part 1: Cables for alternating
voltages up to and including 0.6/1kV.