Академический Документы
Профессиональный Документы
Культура Документы
Acceptance Testing,
Commissioning and Maintenance Manual
IMPORTANT
The information contained herein is general in nature and not intended for
specific application purposes. It does not relieve the user of responsibility
to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make
changes at any time without notice or obligations. Should a conflict arise
between the general information contained in this publication and the contents of drawings or supplementary material, or both, the latter shall take
precedence.
QUALIFIED PERSON
For the purposes of this manual, a qualified person is one who is familiar
with the installation, construction, or operation of the equipment and the
hazards involved. In addition, this person has the following qualifications:
(a) is trained and authorized to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as
rubber gloves, hard hat, safety glasses or face shields, flash clothing,
etc., in accordance with established safety procedures.
(c) is trained in rendering first aid.
NOTE
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information
be desired or should particular problems arise which are not covered sufficiently for the purchasers purposes,
the matter should be referred to the local sales office.
The contents of the instruction manual shall not become part of or modify any prior or existing agreement,
commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between parties is the sole warranty of Siemens. Any statements contained herein do not
create new warranties or modify the existing warranty.
7UT51 v3
Contents
Table of Figures ....................................................................................................................................................... 6
Table of Tables ......................................................................................................................................................... 7
Introduction .............................................................................................................................................................. 8
Definition of Terms .................................................................................................................................................. 8
Understanding the Siemens 7UT51 Numerical Protective Relay...................................................................... 10
Suggested Test Equipment................................................................................................................................... 13
Siemens 7UT51 Relay Pre-Energization Checklist ............................................................................................. 14
Setting and Programming the Siemens 7UT51 Relay ........................................................................................ 15
Front Panel ........................................................................................................................................................... 15
PC......................................................................................................................................................................... 15
Configuration Menu .......................................................................................................................................... 15
Marshalling Menu ............................................................................................................................................. 15
Settings Menu ................................................................................................................................................... 15
Additional Protective Functions ........................................................................................................................ 15
Important Notes about Transformers ................................................................................................................... 16
Regulated Transformer..................................................................................................................................... 16
FOA Transformers ............................................................................................................................................ 16
Accessing Data ...................................................................................................................................................... 17
Matching or Adaptation Factors ........................................................................................................................... 17
Operational Annunciations (Event Log) Address Block 5100 .............................................................................. 19
Network-Disturbance Annunciations (Fault Logs)................................................................................................ 19
Operational Measured Values.............................................................................................................................. 20
Waveform Data..................................................................................................................................................... 21
Acceptance Testing ............................................................................................................................................... 22
7UT51 Electrical Testing ...................................................................................................................................... 22
Acceptance Testing .......................................................................................................................................... 22
Installation Testing............................................................................................................................................ 22
Testing for In-Service Setting Changes............................................................................................................ 22
Evaluation Testing ............................................................................................................................................ 22
Automated Testing............................................................................................................................................ 22
Acceptance Test Equipment............................................................................................................................. 22
Important Notes about the Procedure .............................................................................................................. 23
Transformer Differential Protection ...................................................................................................................... 25
Test 1. Minimum Pickup of 87: Address 1603............................................................................................... 26
Remaining Tests of the Differential Protection ................................................................................................. 26
Test 2. Time Delay of 87 Tripping: Address 1625......................................................................................... 26
Test 3. Trip Dropout after Reset of 87: Address 1627 .................................................................................. 28
Test 4. Pickup of 87hs: Address 1604 .......................................................................................................... 29
Test 5. Time Delay of 87hs Trip: Address 1626............................................................................................ 30
Test 6. Trip Dropout after Reset of 87hs: Address 1627 .............................................................................. 32
Test 7. Second Harmonic Restraint Per-Phase: Address 1611.................................................................... 33
Test 8. Nth Harmonic Restraint Per-Phase: Addresses 1613 and 1614 ...................................................... 34
Test 9. Differential Current Stopping Nth Harmonic Restraint: Address 1616.............................................. 34
Test 10. Cross-Blocking, Nth Harmonic, Minimum Pickup: Address 1615 ..................................................... 34
PRCM-1108A-0199
7UT51 v3
Test 11. Cross-Blocking, Second Harmonic, Minimum Pickup: Address 1612................................................ 35
Test 12. Cross-Blocking, Second Harmonic, Time Delay: Address 1612 ....................................................... 35
Test 13. Cross-Blocking, Nth Harmonic, Time Delay: Address 1615.............................................................. 36
Notes about Simulating Through-Faults and Testing the 87 Slopes ................................................................ 37
Three-Winding Transformers ............................................................................................................................... 46
Test 14. Through-Fault Security, Metering Validation ..................................................................................... 46
Notes about Slope 1, Slope 2, and Through-Fault Restraint Area. .................................................................. 47
Test 15. Slope 1 (Lower Slope): Address 1606............................................................................................... 48
Test 16. Slope 2 (Upper Slope): Addresses 1607 and 1608........................................................................... 48
Test 17. Minimum Current for Through-Fault Restraint Area: Address 1618................................................... 49
Comments about Through-Fault Restraint Area Slope and
Maximum Duration of Through-Fault CT-Saturation
Restraint: Address 1617.................................................................................................................... 50
Test 18. Status Control - Differential Elements: Discrete Inputs,
Address 1601 .................................................................................................................................... 51
Thermal Overload Protection ............................................................................................................................... 53
Notes about Testing 49-1 And 49-2.................................................................................................................. 53
Settings for Trip Relays, Signal Relays, and LEDs All 49 Tests ................................................................... 53
Test 19. Warning, Overload Current:
Address 2405 (49-1) and 2505 (49-2)............................................................................................... 54
Notes about 49 Trip Times and Alarm Times ................................................................................................... 54
Test 20. Warning, Temperature: Addresses 2404, 2403
and 2402 (49-1) ; Addresses 2504, 2503, and 2502 (49-2).............................................................. 55
Test 21. 49 Tripping: Addresses 2402 and 2403 (49-1),
2502 and 2503 (49-2)........................................................................................................................ 56
Test 22. Status Control of 49 Elements: Discrete Inputs or
Addresses 2401 and 2501 ................................................................................................................ 56
External Trip Functions ........................................................................................................................................ 58
Optional Programming for All External Trip Function Tests ............................................................................. 58
7UT51 Test Connections for All External Trip Function Tests ......................................................................... 58
Test 23. External Trips, Function Test and Trip-Time Delay:
Addresses 3002 (Trip 1) and 3102 (Trip 2)....................................................................................... 59
Test 24. Status Control of External Trips: Discrete Inputs,
Address 3001 (Trip 1) and Address 3101 (Trip 2) ............................................................................ 60
Test 25. Trip Dropout Time of External Trips:
Addresses 3003 (Trip 1) and 3103 (Trip 2)....................................................................................... 61
Test 26. Verification of Other Discrete Input Functions ................................................................................... 61
Time Overcurrent Backup Protection 50/51 And 50hs......................................................................................... 62
Notes about Testing Overcurrent Protection .................................................................................................... 62
Test 27. Pickup and Dropout of 50/51: Address 2112 or 2114 ....................................................................... 62
Test 28. Time Delay of 51 Tripping: Address 2115 ......................................................................................... 63
Test 29. Time Delay of 50 Tripping: Address 2113 ......................................................................................... 64
Test 30. Manual Close Controlling 50/51 Tripping Delay: Address 2121........................................................ 65
Test 31. Status Control of 50/51: Discrete Inputs or Address 2101 ................................................................ 66
Test 32. Trip Dropout after Reset of 50/51: Address 2118.............................................................................. 67
Notes about Testing 50hs................................................................................................................................. 68
Test 33. Pickup and Dropout of 50hs: Address 2103...................................................................................... 68
Test 34. Time Delay of 50hs Tripping: Address 2104 ..................................................................................... 69
Test 35. Manual Close Controlling 50hs Tripping Delay: Address 2121 ......................................................... 71
Test 36. Status Control of 50hs: Discrete Inputs or Address 2101 ................................................................. 71
Test 37. Trip Dropout after Reset of 50hs: Address 2118............................................................................... 72
Tank Leakage Protection ..................................................................................................................................... 73
Notes about Testing Tank Leakage Protection ................................................................................................ 73
Test 38. Pickup and Dropout of Tank Leakage Protection:
Address 2703 or 2704, and Address 2709 ....................................................................................... 73
Test 39. Time Delay of Tank Leakage Protection Tripping: Address 2725...................................................... 74
PRCM-1108A-0199
7UT51 v3
Test 40. Status Control of 64t: Discrete Inputs or Address 2701 .................................................................... 75
Test 41. Trip Dropout after Reset of 64t: Address 2727.................................................................................. 76
Restricted Ground-Fault Protection...................................................................................................................... 77
Notes about Testing 87n................................................................................................................................... 77
Test 42. Pickup and Dropout of 87n: Address 1903......................................................................................... 77
Test 43. Time Delay of 87n Tripping: Address 1925 ........................................................................................ 78
Test 44. Status Control of 87n: Discrete Inputs or Address 1901 ................................................................... 79
Test 45 Trip Dropout After Reset of 87n: Address 1927 ................................................................................. 79
Test 46. Second Harmonic Restraint of 87n: Addresses 1910 and 1911 ....................................................... 80
Test 47. Differential Current Stopping 2nd Harmonic
Restraint of 87n: Addresses 1910 and 1912..................................................................................... 81
Notes about Testing the Extended Tripping
Area of 87n - Critical Angle for Restraint .......................................................................................... 82
Test 48. 87n Security for External Faults and Critical Angle for
Restraint: Address 1904.................................................................................................................... 84
Setting Verification after Electrical Testing........................................................................................................... 86
Control Wire, CT, and Relay Installation ............................................................................................................. 87
Primary Equipment Check.................................................................................................................................... 87
Electrical Drawings Wire Check ........................................................................................................................... 87
CT Installation....................................................................................................................................................... 87
Interposing Transformers ..................................................................................................................................... 87
Relay Installation .................................................................................................................................................. 87
Commissioning Tests............................................................................................................................................ 89
Physical Inspection............................................................................................................................................... 89
Installation Test Procedures................................................................................................................................. 89
Operational Checks.............................................................................................................................................. 89
Energizing the Transformer.................................................................................................................................. 90
In-Service Readings ............................................................................................................................................. 90
Operational Measured Values.............................................................................................................................. 90
Measured Test Currents....................................................................................................................................... 90
Waveform Capture during Test Fault Record Address 4900 ............................................................................ 90
Installation of 7UT51 Relay in Existing Circuit ..................................................................................................... 91
Output Connections.............................................................................................................................................. 91
Putting the Relay into Operation .......................................................................................................................... 92
Routine Testing of System.................................................................................................................................... 93
Relay Integrity....................................................................................................................................................... 93
Operational Measured Values.............................................................................................................................. 93
Input Integrity........................................................................................................................................................ 93
Output Integrity ..................................................................................................................................................... 93
Validate Metering.................................................................................................................................................. 93
Measured Test Currents....................................................................................................................................... 93
Waveform ............................................................................................................................................................. 94
Putting the Relay into Operation .......................................................................................................................... 94
Fault Data and Analysis Tools.............................................................................................................................. 95
Front Panel Alarms............................................................................................................................................... 95
Fault Analysis Data............................................................................................................................................... 95
PC......................................................................................................................................................................... 95
Saving/Archiving Fault Data ................................................................................................................................. 96
Resetting/Clearing Buffers and Targets ............................................................................................................... 96
Address Index ........................................................................................................................................................ 97
PRCM-1108A-0199
7UT51 v3
Table of Figures
Figure 1: Control of a Protection Function ............................................................................................................ 10
Figure 2: Discrete Signal Inputs ............................................................................................................................ 11
Figure 3: Signal Contacts ...................................................................................................................................... 12
Figure 4: Trip Contacts.......................................................................................................................................... 12
Figure 5: LED Targets ........................................................................................................................................... 12
Figure 6: Example Configuration Menu................................................................................................................. 16
Figure 7: Matching/Adaptation Factor Relay Front Display................................................................................... 17
Figure 8: Measured Current Tests ........................................................................................................................ 19
Figure 9: Operational Annunciations and Fault Log.............................................................................................. 19
Figure 10: Waveform Capture Example.................................................................................................................. 21
Figure 11: Test 1 Connection Diagram ................................................................................................................... 26
Figure 12: Test 2 Connection Diagram ................................................................................................................... 27
Figure 13: Test 3 Connection Diagram ................................................................................................................... 28
Figure 14: Connection Diagram .............................................................................................................................. 29
Figure 15: Test 5 Connection Diagram ................................................................................................................... 30
Figure 16: Test 6 Connection Diagram ................................................................................................................... 32
Figure 17: Test 7 Connection Diagram ................................................................................................................... 33
Figure 18: Test 10 Connection Diagram ................................................................................................................. 34
Figure 19: Test 12 Connection Diagram ................................................................................................................. 35
Figure 20: Dy1 Transformer, ................................................................................................................................... 38
Figure 21: Test Connections for Dy1 Transformer with a-Phase-Ground Through-Fault...................................... 39
Figure 22: Test Connections for Yd11 transformer with a-Phase-Ground Through-Fault, Io-Elimination .............. 42
Figure 23: Yd11 Transformer a-Phase-Ground Fault .............................................................................................. 44
Figure 24: Test Connect for a Yd11 Transformer, with
an a-Phase-Ground Through-Fault, Io-Correction................................................................................. 45
Figure 25: Differential Characteristics ..................................................................................................................... 47
Figure 26: Test Connections for Testing 49-1 and 49-2.......................................................................................... 53
Figure 27: Tests 23-25 Connection Diagram .......................................................................................................... 58
Figure 28: Test 27 Connection Diagram ................................................................................................................. 62
Figure 29: Test 28 Connection Diagram ................................................................................................................. 63
Figure 30: Test 29 Connections Diagram ............................................................................................................... 64
Figure 31: Test 32 Connection Diagram ................................................................................................................. 67
Figure 32: Test 33 Connection Diagram ................................................................................................................. 68
Figure 33: Test 34 Connection Diagram ................................................................................................................. 69
Figure 34: Test 37 Connection Diagram ................................................................................................................. 72
Figure 35: Test 38 Connection Diagram ................................................................................................................. 73
Figure 36: Test 39 Connection Diagram ................................................................................................................. 74
Figure 37: Test 41 Connection Diagram ................................................................................................................. 76
Figure 38: Test 42 Connection Diagram ................................................................................................................. 77
Figure 39: Test 46 Connection Diagram ................................................................................................................. 80
Figure 40: Test 47 Connection Diagram ................................................................................................................. 81
Figure 41: Test 48 Connection Diagram ................................................................................................................. 84
Figure 42: Two-Winding, Delta-Wye Transformer................................................................................................... 88
Figure 43: Three Winding, Delta-Wye-Delta Transformer ....................................................................................... 88
Figure 44: WinDIGSI Metering Data Screen........................................................................................................... 90
Figure 45: Waveform Capture of Normal Line Current ........................................................................................... 91
Figure 46: Example of Fault Data............................................................................................................................ 95
PRCM-1108A-0199
7UT51 v3
Table of Tables
Table 1:
Table 2:
Table 3:
Table 4:
Table 5:
Table 6:
Table 7:
Measured Values..................................................................................................................................... 20
Currents Limitations................................................................................................................................. 23
Default Settings for Some of the Signal Relays:...................................................................................... 24
Default Settings for Some of the LEDs:................................................................................................... 25
Default Settings for the LCD after a Fault................................................................................................ 25
Correction Factor for 87-Itrip(Wx)............................................................................................................ 25
Source 1 Current- Connections, Delta-Grounded
Wye Transformers (Dyz).......................................................................................................................... 39
Table 8: Equations of Winding 2 Currents for IREST and IDIFF,
and Relationship of Restraint Currents for Phase-Ground, Through-Faults. .......................................... 40
Table 9: Source 2 Current- Connections, Delta-Grounded Wye Transformers (Ydz)........................................... 42
Table 10: Equations of Winding 2 Currents for IREST and IDIFF, and
Relationship of Restraint Currents for Phase-Ground, Through-Faults. ................................................. 43
Table 11: Maximum for 87N Tripping with
3I0* = 3I0** = [2 X Address 1903 X INRGFWx or IOBJRGF] and
k-Values for Address 1904 ..................................................................................................................... 84
Table 12: Maximum for 87N Tripping with
3I0* = 3I0** = [3 X Address 1903 X INRGFWx or IOBJRGF] and
k-Values for Address 1904 ..................................................................................................................... 84
PRCM-1108A-0199
7UT51 v3
Introduction
This manual is to be used in conjunction with the
Siemens 7UT51 v3 Protective Relay Instruction
Manual. Prior to working with this relay, it is
recommended that the instruction manual be read
and understood. The relay has many powerful
features that should be understood before any
settings are applied, tests performed, or installation
made.
This handbook describes manual acceptance
testing, installation, commissioning, and
maintenance of a Siemens 7UT513 V3 Protective
Definition of Terms
Adaptation Factor See Matching Factors
CT Current Transformer
CTR Current Transformer Turns Ratio
where:
PRCM-1108A-0199
7UT51 v3
Star-point The common point or the non-polarity
connection of a Y connected transformer.
SWITCH-OFF The switch-off of a function means
that the protective function has been established as
Enabled; however, the function is turned Off.
PRCM-1108A-0199
7UT51 v3
Understanding the Siemens 7UT51
Numerical Protective Relay
The following diagrams are intended to further
enhance the understanding of the Siemens 7UT51
by giving a visual representation of the relay
functions. It is also important to understand these
ENABLED /
DISABLED
Protection
Function
On
Off
PC
Display
SCAD
B11
B13
t
B12
t
Block
Control of a Protection Function
The protective function must first be set as Enabled.
Once made Enabled, the protective function can be turned Off
or On via the relay front panel, remote interface, PC, or discrete
input.
If the protective function is Enabled and On, the trip function
can be blocked; however the relay will still function normally and
record events accordingly.
10
PRCM-1108A-0199
7UT51 v3
Signal
Circuit
Go LO to HI
when rise above
19V
INPUT
Go LO to HI when
rise above 65V
Internal
Event(s)
Event 1
Event 2
:
:
Event 10
Discrete-Signal
Inputs
Each discrete-signal
input is actuated by
voltage in a signalcircuit. Each input
controls up to 20
events. Each event is
configured to occur
either when the
discrete input is
actuated (HI), or
when it ceases to be
actuated (LO).
PRCM-1108A-0199
11
7UT51 v3
Signal Contacts
This diagram illustrates
the functions of the
signal contacts. Each
signal contact is
controlled by up to 20
events and is used to
sound alarms for
operators or to signal
other protection
devices.
Event 1
Event 2
:
:
Event 20
Trip Contacts
Event 1
Event 2
:
:
Event 20
LED Targets
Event 1
Event 2
:
:
Event 20
12
PRCM-1108A-0199
7UT51 v3
Suggested Test Equipment
The following equipment is suggested to perform the
acceptance and commissioning tests for the
transformer differential scheme. Further detail on the
equipment specifications required for acceptance
testing is given in the Acceptance Testing section of
this document.
PRCM-1108A-0199
13
7UT51 v3
Siemens 7UT51 Relay Pre-Energization
Checklist
14
PRCM-1108A-0199
7UT51 v3
Setting and Programming the Siemens 7UT51 Relay
Have the Relay Setting Sheets (included in the
Siemens 7UT51 Relay Instruction Manual)
completely filled out with the required settings.
If the meaning of the required parameter is not clear,
it is usually best to leave it at the factory setting.
Front Panel
(See Relay Front Panel View in the Siemens 7UT51
Instruction Manual.)
If the parameter address is known, then direct
addressing is possible on the front panel of relay.
This is achieved by depressing the Direct Access
key, followed by the four-digit address, and then
pressing the Enter key.
If the parameter address is not known, paging by
means of the arrow keys on the front panel of the
relay is possible.
To change the content of a memory address, the
address must be selected and the relay must be
placed in Password mode.
PC
The programming of the relay with a PC and
WinDIGSI software is straight forward since it is
Windows based; however, consult the Siemens
WinDIGSI Users Manual for detailed instructions if
necessary.
When using the PC to set the parameters, it is best
to enter the data as you scroll through the screens
rather than programming for particular functions.
The following parameters must be entered to enable
the relay to respond accurately (with the desired
alarms, measurements, and event information) in an
87-transformer differential scheme:
Configuration Menu
(See Figure 6)
7100
7200
7400
7800
Marshalling Menu
The relay will remain in password mode until you
save the settings.
Note: You may be required to save a setting
change before the relay will allow you to
program parameters related to that setting.
This will also required a re-entry of the
password.
If you are changing a selection from a list, press No
until the option you want is displayed, then press
Yes.
If you are changing an entered value, after entering
the appropriate address, enter the new value, then
press the Enter key.
The setting procedure can be ended at any time by
the key combination of F and Enter.
6100
6200
6300
6400
Settings Menu
1100
1400
1600
2900
PRCM-1108A-0199
15
7UT51 v3
Transformer Tank Protection
Address Block 2700
The relay must first be Enabled in Device Options
menu, Address 7827 Transformer Tank Protection.
Settings can then be made for this protective
function in the Settings menu, Address Block 2700.
External Trip Functions
Address Block 3000 and 3100
The relay must first be Enabled in Device Options
menu, Address 7830 and 7831 State of External Trip
Functions. Settings can then be made for this
protective function in the Settings menu, Address
Block 3000 and 3100.
Important Notes about Transformers
Regulated Transformer
If a transformer winding is regulated, then the actual
rated voltage of the winding is not used as Vn. The
average current of the regulated range should be
used.
Figure 6: Example Configuration Menu
FOA Transformers
16
PRCM-1108A-0199
7UT51 v3
Accessing Data
The Siemens 7UT51 relay is microprocessor
controlled, it can monitor, record, and store input
and output data. This data is available through the
LEDs and LCD display on the relay and can also be
accessed via a PC with WinDIGSI software or a
SCADA system. Using the WinDIGSI software, the
currents can be monitored, event logs can be read,
tested performed, and the oscillograms can be
viewed for fault analysis.
PRCM-1108A-0199
17
7UT51 v3
Line Phase Angle Relations
(Figure 8)
The phase angle relations are displayed in Address
4121 after the test has been performed. Symbols
W1, W2, W3*, WA*, WB* for the winding of the
transformer on the relay LCD (such as I1, I2, I3 in
WinDIGSI). Symbols Ia, Ib, and Ic for the phase on
the relay LCD (PhA, PhB, and PhC in WinDIGSI).
The phase angle differences are displayed in 30
increments; small deviations up to 10 are
tolerated. When the measured angle is outside of
this tolerance range, the display shows inval. The
angle differences are defined for clockwise phase
rotation. The angle differences of the three currents
of side 1, 2, and 3 should be as follows:
18
PRCM-1108A-0199
7UT51 v3
mode be definitely finished once the tests have been
completed.
Access Address 4800 Commission Test Stop.
Page to Address 4801 Test Stop?
Enter Yes key.
PRCM-1108A-0199
19
7UT51 v3
Operational Measured Values
Address Block 5700
Measured values are system data collected and
calculated by the relay. The relay can display
measured values on the front panel LCD, or export
them to a PC. The display of measured values is
updated every 1 to 5 seconds.
Address Block 5700 will display winding current as a
percentage of the rated current and winding current
in amps. See Figure 10 for a list of all operational
measured values.
Address Block 5900 will display Temperature rise of
each thermal overload function (49-1 and 49-2)
separately for each phase, or for all three phases
combined.
20
Address
5701
5702
5703
Description
Current in winding or side 1 for
phases A, B, and C as a
percentage of the rated
current.
Current in winding or side 2 for
phases A, B, and C as a
percentage of the rated
current.
Current in winding or side 2 for
phases A, B, and C as a
percentage of the rated
current.
Additional current inputs when
used and assigned as a
percentage of the rated
current. (7UT513 only)
Current in winding or side 1 for
phases A, B, and C in amps
W2 Ia(%)
W2 Ib(%)
W2 Ic(%)
5704
5705
5706
W3 Ia(%)
W3 Ib(%)
W3 Ic(%)
5707
5708
5709
IA(%)
IB(%)
5710
5711
W1 Ia
W1 Ib
W1 Ic
W2 Ia
W2 Ib
W2 Ic
W3 Ia
W3 Ib
W3 Ic
IA
IB
5721
5722
5723
5724
5725
5726
5727
5728
5729
5730
5731
1/trp
1/trpA
1/trpB
1/trpC
2/trp
2/trpA
2/trpB
2/trpC
5911
5912
5913
5914
5921
5922
5923
5924
PRCM-1108A-0199
7UT51 v3
Waveform Data
The relay can simultaneously capture data for all
current inputs and up to four user-defined functions
that report the status of discrete-signal inputs. The
data must be downloaded to a PC for analysis and
storage.
The data storage parameters can be programmed in
Address Block 7400. Data storage can also be
initiated via a discrete input or by the operator via the
front panel of the relay or a PC. The configuration
parameters required for this function to operate are
as follows:
Options
Type of Graph
(Prim., Sec., or
Normalized)
DIGRA
Display
Analog Curves
From this point several choices are
given to display and analyze the data.
Choose Device.
PRCM-1108A-0199
21
7UT51 v3
Acceptance Testing
7UT51 Electrical Testing
The purpose of this section is to provide a procedure
for acceptance testing and installation testing a
7UT51. The procedure is for manual testing,
although the document could be used as a
foundation for automated test plans. Simple
adaptations allow the procedure to also be used for
testing after an in-service setting change. The
procedure can be easily adapted for evaluation and
familiarization with a 7UT51.
For this document, acceptance testing is testing a
user performs to become satisfied that a 7UT51 is
functioning properly. Installation testing is done by a
user to verify that the 7UT51 will perform correctly
within a specific application. For many users,
acceptance testing and installation testing are the
same.
It is important to note that routine testing is covered
in another section.
The degree of testing needed for acceptance testing
and installation testing is dependent upon the users
philosophies. There is sufficient detail to guide the
user in adapting the procedure to the users
satisfaction.
Acceptance Testing
Installation Testing
Perform only the tests required to check the settings
and control to be used in the specific field
application. Complete testing of the discrete inputs,
signal contacts, and trip contacts is recommended
using this procedure. This will reduce field
22
PRCM-1108A-0199
7UT51 v3
Continuous
Current
Rating
I 20 AMPS
1 AMP
I 4 AMPS
4 AMPS < I 20
AMPS
10-Second
Current Rating
PRCM-1108A-0199
23
7UT51 v3
Verification of the programming of trip relays and
signals relays is especially important during
installation testing. The user may have to add
tests to the procedure to verify each output relay is
operating as intended.
The relay and target default settings of interest in
this procedure are given below. They apply for a
7UT513. The programming also applies to a
7UT512 except this protective system has trip
relays 1 and 2, signal relays 1-4, and LEDs 1-6.
Table 3:
Default Settings for Some of the
Signal Relays:
Address
6201
Signal
Relay
1
6202
6203
6206
24
6207
6208
6209
6210
10
6211
11
Default Programming
(Events)
0511 General trip of the
relay
5671 87-Diff protection:
General trip
2451 BU
Overcurrent+G/F :
General Trip
1571 49-TRIP by
thermal O/L protection 1
1621 49-TRIP by
thermal O/L protection 2
1566 49-Thermal O/L
prot. 1: Thermal warning
1616 49-Thermal O/L
prot. 2: Thermal warning
5821 Restricted ground
fault: General TRIP
5921 Transformer tank
prot.: General TRIP
0391 Warning stage
from Buchholz
protection
0392 Tripping stage
from Buchholz
protection
PRCM-1108A-0199
7UT51 v3
Table 4: Default Settings for Some
of the LEDs:
Address
6301
LED
1
6302
6303
6304
6307
6308
6309
6310
10
6311
11
6312
12
Default Programming
(Events)
0511 General trip of the
Relay m
5691 87-Diff protection:
Trip m
5692 87HS-Diff protection:
Trip m
2451 BU Overcurrent+G/F
: General Trip m
5821 Restricted groundfault: General TRIP m
5921 Transformer tank
prot.: General TRIP m
1571 49-TRIP by thermal
O/L protection 1 m
1621 49-TRIP by thermal
O/L protection 2 m
0391 >Warning stage from
Buchholz prot. m
0392 >Tripping stage from
Buchholz prot. m
Address
7107
Top
7108
Bottom
Default Programming
0543 Protection
function(s) pickup
0544 Protective Trip
Type of Fault
3-Phase
2-Phase
1-Phase
with
I0
2
Elimination
1-Phase
without I0
3
Elimination
Winding 1
(A,B,C)
Reference
Winding
Winding 2
(a,b,c) or
Winding 3
(a,b,c)
Even Number
Vector Group
1
Winding 2
(a,b,c) or
Winding 3
(a,b,c)
Odd Number
1
Vector Group
1.0
1.0
1.0
1.0
1.0
0.866
1.5
1.5
1.732
1.0
1.0
1.732
Notes:
1. Vector Group settings are Address 1121 for
Winding 2, and Address 1141 for Winding 3.
For this table, 0 is considered even.
2. Use this row if the I0Process setting for the
tested winding is I0 Elimination. The settings
are Address 1106 for Winding 1, Address 1126
for Winding 2, and Address 1146 for Winding 3.
3. Use this row if the I0Process setting for the
tested winding is either Without or
I0 CORRECTION. The settings are Address
1106 for Winding 1, Address 1126 for Winding 2,
and Address 1146 for Winding 3.
In tests 1-3 current is injected in one phase at any
time; therefore, use the rows for 1-phase faults. The
other fault types are given if the user wishes to
expand the tests.
PRCM-1108A-0199
25
7UT51 v3
Test 1. Minimum Pickup of 87: Address 1603
Expected Results:
I1
7UT51 Relay
IA
Trip
Contact 1
Contact
Monitor
IB
W1
W2
IC
Ia
Ib
Ic
Ia
Ib
Ic
W3
(7UT513
only)
26
PRCM-1108A-0199
7UT51 v3
Option 2:
Test Equipment
I
1
1.
2.
3.
4.
5.
6.
7.
8.
9.
7UT51 Relay
Connect to one
phase of one
winding
with lowest
87-Itrip (Wx)
IA
IB
Trip
Contact 1
W1
I
C
START I1 ON
Timer
Option 2
STOP
Ia
I
b
I
c
STOP
W2
Trip
Contact 2
I
a
Connection
Option 2
5A1
5A2
START
Timer
Option 1
I
b W3
(7UT513
I
c only)
Option 1:
1. Program Trip Relay 1 for 5691 87-Diff
protection: Trip. (The default setting is
sufficient.)
2. Program Trip Relay 2 for 5621 87-Differential
unit pickup.
3.
4.
5.
6.
7.
8.
PRCM-1108A-0199
Option 1:
The value read from the timer is the direct, tested
value for Address 1625. The value should be within
the larger of +/- 3% or +/-13 ms of Address 1625.
Operations of the contacts, LEDs, and LCD should
be consistent with those in the Test 1, with
consideration given to the changing of the
programming for Trip Relays 1 and 2.
27
7UT51 v3
Option 2:
87-Itrip (Wx)
Timer
START I1 OFF
STOP
7UT51 Relay
Connect to one
phase of one
winding with
lowest
I1
IA
Trip
Contact 1
IB
W1
IC
Ia
Ib
W2
Ic
Ia
Ib
Ic
W3
(7UT513
only)
28
PRCM-1108A-0199
7UT51 v3
Notes about Testing the Differential High-Set
Element: Address 1604
Tests pertaining to the high-set element (87HS) are
likely to require high currents.
Note: Do not to exceed the current limitations of the
7UT51 previously mentioned in this
procedure.
The pickup current of 87HS depends on the winding
into which current is injected.
I1
7UT51 Relay
Connect to one
phase of one
winding with
lowest
87HS - Itrip
(Wx)
IA
Trip
Contact 1
IB
W1
Contact
Monitor
IC
Ia
Ib
W2
Ic
Ia
Ib
Ic
W3
(7UT513
only)
Address 1603
3. If 87HS-Itrip(Wx) is 20 amps or less (4 amps or
less for a 7UT51 with a 1 amp rating), perform
tests 4, 5, and 6. Otherwise, perform only tests
5 and 6.
If the 87HS pickup current is less than 20 amps, a
precise pickup level is determined in Test 4. If the
pickup current is greater than 20 amps, the test for a
precise pickup is foregone, and a test current of 1.2
X 87HS-Itrip(Wx) is used for verification of pickup in
tests 5 and 6.
Tests for 87HS may cause other elements to
operate, such as those of the Overcurrent Backup
Protection or the Thermal Overload Protection. If
this occurs, the other elements can be temporarily
turned Off (Address 2101 for Overcurrent Protection
and Address 2401 or Address 2501 for Thermal
Overload Protection). If elements are turned Off,
they should remain Off until the tests for the
differential protection are completed. Some later 87
tests could also operate these other elements.
Note: Be sure to turn back on any affected
elements, after the 87/87HS tests are
completed.
PRCM-1108A-0199
Recommended Option:
Set Address 1625 = +* (infinite) seconds. This
setting will permit verification that 87HS tripping
operates contacts that are programmed for both 87
and 87HS tripping. Otherwise, 87 tripping will occur
before 87HS tripping in the test below.
1. Program Trip Relay 1 to include 5692 87HS-Diff
protection: Trip. (The default setting includes
this.)
2. Turn On the current and slowly increase the
current until 87HS trips, as indicated by the
LEDs or contacts.
3. Turn Off the current and reset targets.
4. Set Address 1625 for the desired setting if a
change was made.
Note: Regardless of the setting of Address 1625,
the contact of Trip Relay 1 will not reset in
the above test until 87 drops out. The
dropout of 87 is tested above; therefore, not
repeated here.
29
7UT51 v3
Expected Results:
Pickup Current
The pickup current at contact closure should be
within +/- 5% of the calculated 87HS-Itrip(Wx).
Contacts, LEDs, and LCD
For the default settings with Address 1625 = infinite
seconds, all trip contacts should close, signal relays
1 and 2 should operate, and LEDs 1 and 3 should
light when 87HS trips. When the current is turned
Off, the contacts should open, the LCD should
display 87Diff GenFlt and 87DiffGenTrip, and the
LEDs remain latched. With Address 1625 equal to
another setting, the same target and contact
operations should occur, except LED 2 should also
light and latch.
7UT51 Relay
Connect to one
phase of one
winding
with lowest
87-trip (Wx)
IA
Trip
Contact 1
IB W1
IC
Timer
Option 2
START 1I ON
STOP
Ia
Ib
Trip
Contact 2
W2
Ic
Connection
Option 2
Ia
W3
Ib (7UT513
only)
Ic
STOP
5A1
5A2
START
Timer
Option 1
30
PRCM-1108A-0199
7UT51 v3
Option 1:
1. If 87HS-Itrip(Wx) > 16.5 amps,
change Address 1604 so that 87HS-Itrip(Wx)
16.5 amps. The new setting is determined by:
New Address 1604
[16.5 X Existing Address 1604]
Existing 87HS-Itrip(Wx)
Option 2:
1. If 87HS-Itrip(Wx) > 16.5 amps,
change Address 1604 so that 87HS-Itrip(Wx)
16.5 amps. The new setting is determined by:
New Address 1604
[16.5 X Existing Address 1604]
Existing 87HS-Itrip(Wx)
PRCM-1108A-0199
Option 2:
The pickup times from Step 13 (1626 = 0.00
seconds) must be subtracted from the pickup time
of Step 15 (1626 = desired setting) to obtain the
tested value for Address 1626. The accuracy of
Address 1626, with the timer accuracy included, is
the larger of +/- 3% or +/- 10 ms. The pickup
31
7UT51 v3
timespread of 87HS (without delay) plus contact
must be considered.
Test Equipment
7UT51 Relay
Connect to one
phase of one
winding with
lowest
I1
IA
Trip
Contact 1
W1
IC
START I1 OFF
STOP
Ib
W2
Expected Results:
Ia
Ib
Ic
Ia
Ic
W3
(7UT513
only)
32
IB
87-Itrip (Wx)
Timer
PRCM-1108A-0199
7UT51 v3
Address 1627, including the timer accuracy, is the
larger of +/- 3% or +/- 10 ms. The dropout
timespread of 87HS (without delay) plus contact
must be considered.
For the default settings, all trip contacts should
close, signal relays 1 and 2 should operate, and
LEDs 1 and 3 should light when 87HS trips. When
the current is turned Off, the contacts should reset,
the LEDs should remain latched, and the LCD
should display 87Diff GenFlt and 87DiffGenTrip.
I1
(60 Hz)
IA
Trip
Contact 1
IB
W1
Contact
Monitor
Ia
Ib
Expected Results:
IC
I2
(N x
60Hz)
7UT51 Relay
Connect to one
phase of one
winding
with lowest
87-Itrip ( Wx )
W2
Ic
W3 (7UT513 only)
not shown
PRCM-1108A-0199
33
7UT51 v3
th
Expected Results:
Expected Results:
th
%N Harmonic Restraint =
Test Equipment
th
7UT51 Relay
IA
I1
(60 Hz)
Trip Contact 1
Contact
Monitor
IB
W1
IC
Ia
2
(N x 60Hz)
Ib
W2
Ic
W3 (7UT513 only)
not shown
th
34
PRCM-1108A-0199
7UT51 v3
Expected Results:
Expected Results:
th
th
%N Harmonic Restraint =
th
Test Equipment
I1
Trip Contact 1
IB
(60 Hz)
IC
I2
(N x 60Hz)
Start I1 ON
STOP
Ia
Example
connections for
W1. Use
winding with the
lowest 87-Itrip
(Wx)
Ib
Ic
W3 (7UT513)
not shown
Timer
PRCM-1108A-0199
35
7UT51 v3
winding, and 120 Hz current injected into one of the
phases that has the 60 Hz current.
Connect the 7UT51 as shown in Figure 19. Any
winding can be selected for current injection. To
minimize current requirements, choose the winding
that has the lowest 87-Itrip(Wx). This is typically
Winding 1 (high voltage side of the transformer). For
clarity, Figure 19 is drawn with the current
connections to W1. Adapt if necessary.
1. Set Address 1612 = 0 cycle.
2. Set Address 1625 = 0.00 seconds.
3. Set the 60 Hz current (Source 1) for a solid
pickup of 87. Usually a value of [2 X 87-Itrip(Wx)]
is a good choice. Avoid operation of 87HS or
exceeding the continuous current rating of the
7UT51.
4. Set the Source 2 current frequency to 120 Hz,
and the magnitude equal to the magnitude of the
Source 1 current.
5. Set the timer to start on the application of 60 Hz
current (Source 1), and stop on the closure of
the contact.
6. Turn On Source 1 only.
7. Record the tripping time of 87 and contact, and
turn off Source 1.
8. Repeat steps 6 and 7 two times to obtain a
timespread of the tripping of 87 and contact.
9. Set Address 1612 = desired setting.
10. Simultaneously apply both Source 1 and Source
2 currents.
11. Record the value from the timer, which now
includes Address 1612.
12. Turn Off both currents, and reset the LEDs and
LCD.
13. Reset Address 1625 to the desired value.
Expected Results:
The pickup times from step 8 must be subtracted
from the pickup time from Step 11 (1612 = desired
setting) to obtain the tested value for Address 1612.
The accuracy of Address 1612 is +/- 1.02 cycles
(timer accuracy included). The pickup timespread of
87 plus contact must be considered in the result.
The pickup timespread of 87 plus contact can add
errors and uncertainty to the results. If the user is
not satisfied with the calculated values for Address
1612, the Network Disturbances option in the
WinDIGSI software can be useful.
36
PRCM-1108A-0199
7UT51 v3
8. Record the tripping time of 87 and contact and
turn Off Source 1.
Expected Results:
The pickup times from Step 9 must be subtracted
from the pickup time from Step 12 (1615 = desired
setting) to obtain the tested value for Address 1615.
The accuracy of Address 1615 is +/- 1.02 cycles
(timer accuracy included). The pickup timespread of
87 plus contact must be considered in the result.
The pickup timespread of 87 plus contact can add
errors and uncertainty to the results. If the user is
not satisfied with the calculated values for Address
1615, the Network Disturbances option in the
WinDIGSI software can be useful.
Obtain dialog with the 7UT51. Click on
Annunciation, then Annunciations Edit. Select
Network Disturbances, and Display. Display an
event associated with the testing. The coming of
events 5641 and 5642 should be seen. Then the
going of Event 5641 (cross-blocking of Ph A ceases)
should be seen at the same time of the coming of
events 5621 and 5691 (87 tripping). Subtract the
coming time of Event 5641 from the going time of
Event 5641 to obtain Address 1615.
The LEDs, LCD, and contact operations should be
the same as those for Test 1. The delay between
current application and tripping may be noticeable,
depending on the desired setting of Address 1615.
Note:
PRCM-1108A-0199
37
7UT51 v3
For all three cases, the fault simulated is an
external, phase-ground fault on the wye-side of the
transformer. This is the simplest fault to simulate
using two test-current sources.
Consider the common, ANSI connected, delta
grounded wye transformer shown in Figure 20. Let
currents be defined as flowing into the transformer
(both sides). For an a-phase-ground fault resulting
in a current of 1.0 per unit through the transformer
winding to the fault, IA = -IC. Also, IA = 0.58 per unit
or (1/1.732) per unit for Ia = -1.0 per unit. If the fault
is on b-phase, with Ib = -1.0 per unit, then IB = -IA =
(1/1.732) per unit. If the fault is on c-phase, with Ic =
-1.0 per unit, then IC = -IB = (1/1.732) per unit.
These current relationships that result for phaseground faults on the wye side are used in the tests
below.
1.0 p.u.
0.58 p.u.
A
0.58 p.u.
0.58 p.u.
b
38
PRCM-1108A-0199
7UT51 v3
Test Equipment
7UT51 Relay
IA
I1
Trip Contact 1
Contact
Monitor
IB
IC
Ia
I2
Note polarity of
test sources.
Ib
Ic
Dy3
Ia*, Ib*, Ic*, Ia, Ib, and Ic are similar except they
apply for Winding 2.
Dy5
Dy7
Dy9
Dy11
PRCM-1108A-0199
39
7UT51 v3
Winding 1, the connection of the transformer
Winding 2, and the processing of the zero-sequence
currents.
Knowledge of the equations for the I** is not
essential for the tests below; however, the equations
do allow the user to understand better the operation
of the 7UT51. The equations also allow the
procedure to be adapted easier if the user is testing
the 7UT51 for applications other than the three
cases mentioned above. Consult the instruction
book or Siemens to obtain the equations.
For Dyz transformers, the equations for I** are given
immediately below and in Table 8. The table also
provides the metering values to expect when
simulating a phase-ground, through-fault on the
Winding 2 side.
Table 8:
Equations of Winding 2 Currents for
IREST and IDIFF, and Relationship of Restraint
Currents for Phase-Ground, Through-Faults.
Transf.
Type
Dy1
Dy3
Dy5
Dy7
Dy9
Dy11
40
Relationship of
Restraint Currents
for Phase-Ground,
Through-Faults on
W2 Terminals. ( )
Denotes Faulted
Phase
Winding 2 Currents
for IREST and IDIFF in
per unit of INsecW2
(a)IA** + Ia** =
IC** + Ic**
(b)IB** + Ib** =
IA** + Ia**
(c)IC** + Ic** =
IB** + Ib**
Ia**=(0.577)[Ia Ib]
(a)IB** + Ib** =
IC** + Ic**
(b)IC** + Ic** =
IA** + Ia**
(c)IA** + Ia** =
IB** + Ib**
Ia**=(0.577)[-Ib + Ic]
(a)IB** + Ib** =
IA** + Ia**
(b)IC** + Ic** =
IB** + Ib**
(c)IA** + Ia** =
IC** + Ic**
Ia**=(0.577)[-Ia + Ic]
(a)IC** + Ic** =
IA** + Ia**
(b)IA** + Ia** =
IB** + Ib**
(c)IB** + Ib** =
IC** + Ic**
Ia**=(0.577)[-Ia + Ib]
(a)IC** + Ic** =
IB** + Ib**
(b)IA** + Ia** =
IC** + Ic**
(c)IB** + Ib** =
IA** + Ia**
Ia**=(0.577)[Ib Ic]
(a)IA** + Ia** =
IB** + Ib**
(b)IB** + Ib** =
IC** + Ic**
(c)IC** + Ic** =
IA** + Ia**
Ia**=(0.577)[Ia Ic]
Ib**=(0.577)[Ib Ic]
Ic**= (0.577)[-Ia + Ic]
Ib**=(0.577)[Ia Ic]
Ic**=(0.577)[-Ia + Ib]
Ib**=(0.577)[Ia Ib]
Ic**=(0.577)[Ib Ic]
Ib**=(0.577)[-Ib + Ic]
Ic**=(0.577)[Ia Ic]
Ib**=(0.577)[-Ia + Ic]
Ic**=(0.577)[Ia Ib]
Ib**=(0.577)[-Ia + Ib]
Ic**=(0.577)[-Ib + Ic]
PRCM-1108A-0199
7UT51 v3
Notice for the common Dy1 transformer, with an aphase-ground through-fault (Figure 20), IC = -IA, IB
= 0, and Ib = Ic = 0
IA** = IA = 0.577 per unit
IB** = 0
IC** = -IA = -0.577 per unit
Ia** = (-0.577)(Ia) = - 0.577 per unit
Ib** = 0
Ic** = (-0.577)(-Ia) = 0.577 per unit
Currents Ia** and Ic** have a negative factor
because Ia flows out terminal Ia*.
IAREST = ICREST = 0.577 per unit + -0.577 per
unit = 1.154 per unit
IBREST = 0 per unit + 0 per unit = 0 per unit
IADIFF = ICDIFF = 0.577 per unit + (-0.577 per unit)
= 0 per unit
ICDIFF = 0 p.u. + 0 p.u. = 0 p.u.
PRCM-1108A-0199
41
7UT51 v3
Case 2: Delta-Grounded Wye Transformers, Wye
is Reference Winding (Wdz), Zero
Sequence Current Elimination
(Address 1106 = I0 elimination)
7UT51 Connections:
Figure 22 shows the connections for a Yd11
transformer, with an A-phase-ground fault simulated.
Notice the wye winding current applies to Winding 1.
Source 1 is still associated with Winding 1. The
connections for all Ydz transformers and all phaseground faults are below.
Test Equipment
I1
Yd1
Yd3
7UT51 Relay
IA
Trip Contact 1
Contact
Monitor
Yd5
IB
IC
I2
Note polarity of
test sources.
Ia
Yd7
Ib
Ic
Yd9
Yd11
42
PRCM-1108A-0199
7UT51 v3
The winding currents are phasors! The
positive direction for a winding current in this case 2
is into the polarity terminals IA*, IB*, and IC*
(terminals 3A1, 2A1, and 1A1).
Yd7
Transf.
Type
Yd1
Yd3
Yd5
Relationship of
Restraint Currents
for Phase-Ground,
Through-Faults on
W2 Terminals. ( )
Denotes Faulted
Phase
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
PRCM-1108A-0199
Yd11
Winding 2 Currents
for IREST and IDIFF in
per unit of INsecW2
Ia** =
(0.577)[Ia Ib]
Ib** =
(0.577)[Ib Ic]
Ic** =
(0.577)[-Ia + Ic]
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
(A) IAREST =
(2)IBREST = (2)
ICREST
(B) IBREST =
(2)IAREST = (2)ICREST
(C) ICREST =
(2)IAREST = (2)IBREST
Ia** =
(0.577)[-Ia + Ib]
Ib** =
(0.577)[-Ib + Ic]
Ic** =
(0.577)[Ia Ic]
Ia** =
(0.577)[Ib Ic]
Ib** =
(0.577)[-Ia + Ic]
Ic** =
(0.577)[Ia Ib]
Ia** =
(0.577)[Ia Ic]
Ib** =
(0.577)[-Ia + Ib]
Ic** =
(0.577)[-Ib + Ic]
Ia** =
(0.577)[-Ib + Ic]
Ib** =
(0.577)[Ia Ic]
Ic** =
(0.577)[-Ia + Ib]
Ia** =
(0.577)[-Ia + Ic]
Ib** =
(0.577)[Ia Ib]
Ic** =
(0.577)[Ib Ic]
43
7UT51 v3
1.0 p.u.
0.58 p.u.
a
0.58 p.u.
0.58 p.u.
B
IBREST = ICREST =
(1/3) per unit + -(1/3) per unit =
(2/3) per unit = (1/2)IAREST
IADIFF = -(2/3) per unit + (2/3) per unit) =
0 per unit
IBDIFF = ICDIFF =
(1/3) per unit + (-1)(1/3)per unit =
0 per unit
44
7UT51 Connections:
Figure 24 shows the connections for a Yd11
transformer, with an A-phase-ground fault simulated.
Notice the wye winding current applies to Winding 1.
Source 1 is still associated with Winding 1. The
connections for all Ydz transformers and all phaseground faults are discussed below.
PRCM-1108A-0199
7UT51 v3
Test Equipment
7UT51 Relay
IA
I1
IB
Trip
Contact 1
Contact
Monitor
W1
IC
I2
Ia
Ib
W2
Ic
1D1
1D2
INb
2D1
2D2
INa
PRCM-1108A-0199
45
7UT51 v3
The conclusion concerning test currents for case 2
also results for Case 3.
I1 = [M X 1.5 X INsecW1] at 0
I2 = [(M X 1.5) X (0.577 X INsecW2 )] =
[M X 0.866 X INsecW2] at 0
Three-Winding Transformers
A 7UT513 protecting three winding transformers can
be adequately tested by considering two windings at
a time, and testing them like a two-winding
transformer. Test the reference winding and
Winding 2. Then test the reference winding and
Winding 3. These two tests will verify the 87
algorithm and the constants being used to form IDIFF
and IREST. Testing Winding 2 and Winding 3 is not
necessary.
Transformers Other Than Dyz and Ydz with the
above Assumptions
If the transformer being protected has different
winding connections or CT connections, determine
the current flows to the 7UT51 for the simplest fault,
with the transformer connected to a power system in
the simplest way. If the equations for I** are
available, they can be used in an analysis, similar to
those above, to predict the test currents needed to
obtain a desired restraint current. If the equations
are not available, the metering from the WinDIGSI
software can be used to obtain the desired restraint
current. Remember always to increase the currents
on different sides of the transformer by the same
factor.
46
PRCM-1108A-0199
7UT51 v3
I1
I2
87HS Pickup
(1604)
IR
ES
T
16
08
ID
IF
F
7UT51
6
5
po
in
t
(b
as
e
Operate Area
Non-Operate Area
Sl
op
e
3
2
1
Slope
06)
1 (16
0
0
4
5
6
7
8
9
10
Restraining Current, IREST ( in multiples of In )
11
PRCM-1108A-0199
47
7UT51 v3
The intersection of Slope 1 and Slope 2 is the value
of IREST at which Slope 2 begins to control 87 tripping
(Slope 2 > Slope 1). The intersection is found using
the equation:
Slope 1 =
2 1/2
2 1/2
[A + B ]
2xM
Expected Results:
The calculated Slope 1 should be within +/- 10% of
Address 1606.
Contact and target operations should be the same
as Test 1, or any test with 87 tripping.
48
2 1/2
PRCM-1108A-0199
7UT51 v3
Slope 2 =
2 1/2
[A + B ]
2xM
Expected Results:
The calculated Slope 2 should be within +/- 10% of
Address 1608.
Contact and target operations should be the same
as test 1, or any test with 87 tripping.
Test 17. Minimum Current for Through-Fault
Restraint Area: Address 1618
PRCM-1108A-0199
49
7UT51 v3
29. Set Addresses 1618 and 1625 to the original
values.
30. Program LED 4 for the original settings.
Expected Results:
The result of Step 17 is the tested value for Address
1618. To calculate the tested value:
Case 1:
Source 1 Current + Source 2 Current
INsecW1
1.732 X INsecW2
(in. per unit)
Case 2 or 3:
Source 1 Current + Source2 Current
1.5 X INsecW1
0.866 X INsecW2
(in. per unit)
Manual testing of the maximum duration of throughfault restraint is very complicated; therefore, a test
for Address 1617 is not included. The feature can
be tested with automated-test equipment. A
description of one possible automated-test is given
in the next paragraph for users wishing to test
Address 1617.
Program an LED, with memory, for events 5651,
5652, and 5653. The LED will indicate pickup of the
through-fault restraint. Program a trip relay for 5691,
87 tripping. Connect the 7UT51 as in test 17. Set
up a fault which maps above either Slope 1 or Slope
2, but not within [85% to 100%] of the IDIFF = IREST
line or above 87HS pickup. The fault currents
should be within the continuous current rating of the
7UT51. Set a timer to start on the application of the
fault, and stop on the closure of the trip contact.
Apply the fault, and record the tripping time of 87.
Repeat the fault a couple of times to obtain a range
of tripping times of 87 for the specific fault. Then,
set-up a two-stage fault event. For Stage 1,
simulate a through-fault that maps into the throughfault restraint area. Set the currents for about 120%
of the minimum values needed to enter the throughfault restraint area (120% of the results from Test
17). This ensures the through-fault restraint will pick
up. The duration of Stage 1 should be 2 cycles or
more. The only concern for the Stage 1 duration is
the current limits of the 7UT51. Stage 2 is the
aforementioned fault. Set the timer to start at the
beginning of stage 2, and stop when the trip contact
closes. The duration of Stage 2 should be Address
1617 plus 10 cycles. Apply the event. Be sure the
LED lights. Record the tripping time of 87.
Address 1617 is the setting of a timer that is armed
when the through-fault restraint picks up. The timer
begins to expire when the differential operating point
leaves the through-fault restraint area. Tripping of
87 is inhibited until the timer expires.
The tripping time of 87, determined before the twostage event, must be subtracted from the tripping
time recorded during the event, to obtain the tested
50
PRCM-1108A-0199
7UT51 v3
value for Address 1617. The accuracy of Address
1617 is +/- 1.02 cycles (timer accuracy included).
The pickup timespread of 87 must be considered.
PRCM-1108A-0199
51
7UT51 v3
52
PRCM-1108A-0199
7UT51 v3
Thermal Overload Protection
(49-1 and 49-2)
Test Equipment
IA
I1
or
I1
Timer
IB
IC
Start I1
On
Ia
Ib
Stop
Ic
Example
Connections
7UT51 Relay
Only
Signal
Contact 1
8B1
7B1
W1
49-1
Signal
Contact 2 8B2
7B2
W2
49-2 Trip
Contact 1 5B1
5B2
Contact
Monitor
Ia
Ib
Ic
W3
(7UT513
only)
PRCM-1108A-0199
53
7UT51 v3
Signal Relay 1 = 1565 49-Thermal O/L prot.1:
Current warning
= 1615 49-Thermal O/L prot.2: Current warning
OR
OR
or
Expected Results:
The 49-1 current warning should occur within +/3% of [Address 2405 X INsecWx] or [Address 2405 X
IObjsec]. This applies for 49-2 also, using Address
2505.
The 49 warning should dropout at a current between
[95% and 99%] of the actual current at pickup.
For the default settings and the changes made,
LED 4 should light and the contact of Signal Relay 1
should close when the 49 current warning occurs.
At dropout, the LED should go out and the contact
54
PRCM-1108A-0199
7UT51 v3
current for the tests below is 20 amps (4 amps for a
7UT51 rated for 1 amp). Using this current,
calculate 49 Ttrip now. Also estimate 49 Twarn.
PRCM-1108A-0199
55
7UT51 v3
Test 21. 49 Tripping: Addresses 2402 and
2403 (49-1), 2502 and 2503 (49-2)
Expected Results
The trip time should occur within the larger of +/12% or +/- 2 seconds of the calculated 49-1 Ttrip
or 49-2 Ttrip.
After several seconds of the current application (the
actual time is not important), LED 4 should light and
the contact of Signal Relay 1 should close. The
warning should occur at about the same time as in
test 20 if the same test current is used. LED 3 and
Signal Relay 2 should operate. At tripping, with the
default settings and the changes made, all of the trip
contacts should close, contacts of Signal Relays 1,
2, 6 and 7 should be toggled, and LEDs 1, 2, 3, 4,
and 9 (49-1) or 10 (49-2) should be lit. When the
current is turned Off, the contact of Signal Relay 1
should open and LED 4 should go out. After some
time perhaps minutes the trip contacts should
open, Signal Relay 6 should reset, and LED 2
should go out (the 7UT51 is still calculating
temperature with the current off). Later, LED 3
should go out and Signal Relays 2 and 7 should
reset. The other LEDs have memory. The LCD
should display 49 O/L1 PU and 49 O/L1 TRIP, or
49 O/L2 PU and 49 O/L2 TRIP, after LED 2 goes
out (49 trip resets).
56
PRCM-1108A-0199
7UT51 v3
If Event 1553 is initially blocking 49-1, and then the
input state is changed while current is still present
above [Address 2402 X INsecWx (or IObjsec)], 49-1
should begin to time-out at the instant of the input
transition. The element should trip if the current is
present long enough, but the trip time may not be
within the specifications given for Test 21. The trip
time from input transition may be longer than the
specification.
If Event 1553 occurs while 49-1 is timing out, but not
tripped, the element should be immediately blocked
at the event occurrence. Any LEDs or signal relays
that operate before the event should immediately
reset when the event occurs. The coming of Event
1553 after a 49-1 trip should do nothing initially. The
7UT51 should remain in a trip state until 49-1
tripping drops out. Then the event should cause the
immediate going of Event 1566 (thermal warning
LED 3). Without Event 1553, Event 1566 would stay
active for a long time until the calculated
temperature fell below 99% of the thermal alarm
pickup value.
Address 2501 = Off and an input causing the
coming of Event 1603 >49-BLOCK thermal O/L
protection 2 should have similar effects. Either
should effectively render 49-2 non-existent. The
action described in the two paragraphs immediately
above should apply for Event 1603 and 49-2.
Address 2401 = Block Tripping and an input
causing the coming of Event 1555 >49-BLOCK trip
of thermal O/L prot 1, before a 49-1 trip, should
have similar effects. Either should prevent Event
1571 from operating trip relays. All of the 49-1
events (including Event 1571) should be uninhibited
in operating LEDs and Signal Relays. The LCD
should show 49 O/L1 PU after the going of Event
1571 (LED 2).
If Event 1555 blocks 49-1 tripping, and then the
input changes to cause the going of Event 1555
while the calculated temperature is still above the
trip threshold (LED 2 is lit), the trip relays should
remain blocked. The LCD should display 49 O/L1
PU after LED 2 goes out.
Applying Event 1555 while 49-1 is timing out, but not
tripped, should have the same effect as applying the
event before 49-1 begins to time out.
PRCM-1108A-0199
57
7UT51 v3
Reset 7UT51 for Desired Settings
Program Trip Relay 1, Signal Relays 1 and 2, and
LED 2, 3, and 4 for the desired settings. If 49
warning or trip times were decreased for testing
purposes, reset Addresses 2403 and 2503 to the
original settings. Be sure Addresses 2401 and 2501
have the proper settings. Reset any other
addresses changed for testing purposes.
External Trip Functions
(External trips 1 and 2) and
Other Discrete Input Functions
These two External Trip functions are independent.
The existence of External Trip Function 1 is
determined by Address 7830. The status of the
function is determined by Address 3001. The
function is operational when Address 7830 =
Existent and Address 3001 is any setting other than
Off. A discrete input must be programmed for Event
4526 >External Trip 1.
I
C
I
a
I
b
Current
I
c
Inputs
I
a'
I
b'
I
c'
I
Na
I
Nb
Switc
h
3A1
3A2
2A1
2A2
1A1
1A2
3B1
3B2
2B1
2B2
1B1
1B2
3D1
3D2
2C1
2C2
1C1
1C2
2D1
2D2
1D1
1D2
+ 8A2
- 8A1
Trip
T1
Contact T2
Outputs
T3
D1
+ 8A4
D2
- 8A3
+ 8D2
D3 Discrete
- 8D1
+ 8D4
Inputs
D4
- 8D3
+ 7D2
D5
- 7D1
+ 4B1 DC
Power
- 4B2
DC
Supply
Gnd
Communications
In
Gnd 4A2
6A2
6A1
6A3
Contact
Monitor
Stop
Start
Timer
Signal
Contact
Outputs
Relay
Status S5
Outputs
Communications
Out
RX 4A1
5B1
5B2
5B3
5B4
5A1
5A2
5A3
5A4
6D1
6D2
6D3
6D4
5D1
5D2
5D3
5D4
6B1
8B1 S1
7B1
6B2
8B2 S2
7B2
6B3
8B3 S3
7B3
6B4
8B4 S4
7B4
4D1
4D2 S6
4D3
4D4 S7
4C1
3C1 S8
4C2
4C4 S9
3C3
3C2 S10
3C4
7D3
7D4 S11
4A3 TX
RS-232 Wire
4A4 Gnd
Or
F-SMA 4A1
RX
Fiber Optic
4A2 F-SMA
TX
58
PRCM-1108A-0199
7UT51 v3
PRCM-1108A-0199
59
7UT51 v3
60
PRCM-1108A-0199
7UT51 v3
Expected Results
The value from the timer in step 9 is the direct,
tested value for Address 3003 or Address 3103.
The tested value should be within the larger of +/3% or +/- 13 ms of Address 3003 or Address 3103.
Operations of the contacts and targets should be
consistent with test 23.
Reset 7UT51 for Desired Settings
Program Trip Relay 1 and 2, Signal Relays 1, 2, and
3, LEDs 2, 3, and 4, and Discrete Input 1 for the
desired settings. Reset any other addresses
changed during testing to the original settings.
PRCM-1108A-0199
61
7UT51 v3
Time Overcurrent Backup Protection
50/51 and 50HS
Overcurrent protection is existent and operational
when settings other than Disabled and Off are
selected for Addresses 7821 and 2101, respectively.
Notes about Testing Overcurrent Protection
The overcurrent backup protection consists of two
elements: 50/51 and 50HS. The 50/51 element can
be either a 50 or a 51. Both 50 and 50HS can have
no intentional delay, a definite time trip delay, or an
infinite delay (trip defeated). The 51 can have
various inverse time characteristics with selectable
time dials, or an infinite delay.
Test Equipment
I1
Connect to
one phase
of winding
associated
with
50/51/50HS
IA
IB
62
W1
8B1
Contact
Monitor
(optional)
IC
Ia
Ib
W2
Ic
Ia
Ib
Signal
Contact 1 7B1
Ic
W3
(7UT513
only)
PRCM-1108A-0199
7UT51 v3
Expected Results:
Pickup Current and Dropout Current
The pickup current at LED 4 illumination should be
within +/- 10% of:
[Address 2112] X [INsecWx or IObjsec] if Address
2111 is Definite Time
[Address 2114] X [INsecWx or IObjsec] if Address
2111 is an inverse option.
The dropout current when LED 4 turns off should be
greater than or equal to 93% of the tested pickup
current.
Contacts, LEDs, and LCD
For the default settings and recommended change,
only LED 4 should light if 51 is being tested. The
LCD should show Back Gen. Flt when 51 drops out.
Depending on the time delay for 50, LEDs and
contacts programmed for 50 tripping may transition
during the test. If a trip occurs, the second line of
the LCD should indicate BU Gen.Trip.
7UT51 Relay
Connect to
one phase
of winding
associated
with
I1
50/51/50HS
IB
Trip
Contact 1
W1
Timer
IC
where:
Ia
START I1 ON
STOP
IA
Ib
W2
Ic
Ia
Ib
Ic
B = [ M 1]
PRCM-1108A-0199
63
7UT51 v3
Test Equipment
Address
2111
Moderately
Inverse
Very
Inverse
Extremely
Inverse
7UT51 Relay
Connect to one
phase of winding
Associated with
I
A
50/51/50HS
Trip
Contact 1 5B1
W1
5B2
W2
5A1
I
C
0.02
0.054196
0.09328
START I
STOP
ON
Timer
Option 2
I
a
I
b
START
5A2
2.0
19.138
I
c
0.48258
Timer
Option 1
I
a
2.0
28.2785
0.12173
Connection
I
b
Option 2
I
c
STOP
Trip
Contact 2
W3
(7UT513
only)
64
PRCM-1108A-0199
7UT51 v3
Option 2:
1. Program Trip Relay 1 to include 2451 BU
Overcurrent+G/F : General Trip. (The default
setting includes this signal.)
2. Set the current source magnitude for a value
that will provide a solid pickup of 50, based on
the results from Test 27. Twice the pickup of 50
is a good value for the test current.
Note: Be certain not to pickup 50HS. Temporarily
increase the pickup of 50HS (Address 2103),
if necessary.
3. Set the timer to start on the application of
current, and stop on the closure of the Trip
Relay 1 contact.
4. If Address 2113 is infinite (+*), continue to
Step 5. Otherwise, skip to step 8.
5. Suddenly apply the current.
6. Verify the timer does not stop, and no other
contacts or LEDs programmed for the tripping of
50 to operate. (Action from the pickup of 50 is
proper.)
7. Turn Off the current, and reset the LEDs and
LCD if applicable. End of test.
8. Set Address 2113 = 0.00 seconds.
9. Suddenly apply the current.
10. Record the pickup time of 50 plus the output
contact.
11. Repeat steps 9 and 10 two or more times, to
obtain a pickup timespread for 50 and contact.
12. If Address 2113 = 0.00 seconds is the desired
setting, end of test. Reset the LEDs and LCD,
but keep the connections and test-set settings
for Test 30. Otherwise, continue.
13. Set Address 2113 for the desired value.
14. Repeat steps 9-10. The recorded time now
includes Address 2113.
15. Turn the current Off, reset the LEDs and LCD,
but keep the connections and testset settings for
tests 30 and 31.
Expected Results:
Option 1:
The value read from the timer is the direct, tested
value for Address 2113. The value should be within
the larger of +/- 3% or +/- 13 ms of Address 2113.
PRCM-1108A-0199
65
7UT51 v3
1. Energize (or de-energize if appropriate) the
discrete input to cause the coming of Event
0356 > Manual close command.
Address 2111 Set for 51
2. Repeat Test 28.
3. Record the trip time of 51.
4. If the timer does not turn Off the current upon
sensing contact closure, switch the state of the
discrete input to cause the going of Event 0356.
Note the response of the 7UT51. End the test.
If the timer turns Off the current, continue.
5. Remove the timer sensing.
6. Apply the current to Cause 51 tripping.
7. Switch the state of the discrete input to cause
the going of Event 0356.
9.
66
PRCM-1108A-0199
7UT51 v3
non-existent. If the event is then de-activated
(going) while current is still present, 50/51 should trip
and provide LEDs and outputs in the normal fashion.
Address 2101 = Block Tripping and an input causing
the coming of Event 2304 >Block trip signal of
backup O/C, applied before a 50/51 trip, should
have similar effects. Either should prevent trip
contacts from operating for all 50/51 events except
Event 2411, described below. The events below
should be free to operate signal relays or LEDs.
Event 2411 Backup O/C+G/F: General fault
detected
Event 2412 BU O/C : Fault detection PhA (if
current in phase A exceeds p.u.)
Event 2413 BU O/C : Fault detection PhB (if
current in phase B exceeds p.u.)
Test Equipment
7UT513 Relay
Connect to one
phase of
winding
associated with
50/51/50HS
I1
START I1 OFF
PRCM-1108A-0199
IB
Trip
Contact 1
W1
IC
IA
STOP
Ia
Timer
Ib
W2
Ic
Ia
Ib
Ic
W3
(7UT513
only)
67
7UT51 v3
4. Set the current source for a magnitude that will
provide a trip of 50/51. The value used in tests
28 or 29 is good. Be sure to trip only 50/51.
Set the pickup of 50HS (Address 2103) higher, if
necessary.
5. Apply the current until 50/51 trips.
6. Turn Off the current.
7. Record the trip dropout value given by the timer.
8. If the desired setting of Address 2118 = 0.00
seconds, go to Step 12. Otherwise, go to the
next step.
9. Repeat steps 5-7 two or more times to
determine a timespread for the dropout time of
50/51 plus contact.
10. Set Address 2118 for the desired setting.
Test Equipment
Expected Results:
With Address 2118 = 0.00 seconds, the dropout
time of 50 or 51, plus the contact, should be 50 ms
+/- 13 ms, with a current of twice the pickup value
dropping suddenly to 0 A after 50/51 trips.
The dropout times from Step 9 (2118 = 0.00
seconds) must be subtracted from the dropout time
of Step 11 (2118 = desired setting) to obtain the
tested value for Address 2118. The accuracy of
Address 2118, including the timer accuracy, is the
larger of +/- 3% or +/- 10 ms. The dropout
timespread of 50/51 (without delay) plus contact
must be considered. The spread is typically wider
when the pickup of 50/51 is less than 0.5 amp.
Contact and target operations should be the same
as in tests 28 or 29.
Notes about Testing 50HS
Depending on the application, a high current may be
required to pickup 50HS.
Note: Do not exceed the current limitations of the
7UT51, given at the beginning of this
document.
If the 50HS pickup current is less than 20 amps (4
amps for a 7UT51 rated for 1 amp), a precise
I1
Connect to
one phase
of winding
associated
with
50/51/50HS
IA
IB
Signal
Contact 1 7B1
W1
8B1
Contact
Monitor
(optional)
IC
Ia
Ib
W2
Ic
Ia
Ib
Ic
W3
(7UT513
only)
68
PRCM-1108A-0199
7UT51 v3
2. Slowly raise the current until LED 4 lights.
Record the pickup current.
3. Slowly reduce the current until the LED 4 light
extinguishes. Record the current at dropout.
Also note LCD indications. Turn Off the current.
Test Equipment
7UT51 Relay
Connect to one
phase of winding
Associated with
50/51/50HS
START I1 ON
STOP
Timer
Option 2
Trip
Contact 1 5B1
W1
5B2
W2
5A1
5A2
I
a
I
b
I
c
I
B
I
C
I
A
START
Timer
Option 1
I
a
Connection
Option 2
I
b
I
c
STOP
Trip
Contact 2
W3
(7UT513
only)
PRCM-1108A-0199
69
7UT51 v3
6. Suddenly apply the current.
7. Record the value from the timer. This is the
tested value for Address 2104. If Address 2104
is infinite (+*) seconds, the timer should not
stop.
8. Turn Off the current, reset the LEDs and LCD.
9. Program Trip Relays 1 and 2 for the original,
intended settings.
Option 2:
1. The pickup of 50HS = Address 2103 X
[INsecWx or IObjsec]. If the pickup is greater
than 16.5 amps, change Address 2103 so that
the 50HS picks up at 16.5 amps or less.
2. Program Trip Relay 1 to include 2451 BU
Overcurrent+G/F : General Trip. (The default
setting includes this signal.)
3. Set the current source magnitude for 20 amps
(4 amps for a 7UT51 rated for 1 amp).
Note: Be sure 50/51 pickup is greater than 20 amps.
4. Set the timer to start on the application of
current, and stop on the closure of the Trip
Relay 1 contact.
5. If Address 2104 is infinite (+*) seconds,
continue to Step 6. Otherwise, skip to Step 9.
6. Suddenly apply the current.
7. Verify the timer does not stop, and no other
contacts or LEDs programmed for the tripping of
50HS operate. (Action from the pickup of 50HS
is proper.)
8. Turn Off the current and reset the LEDs and
LCD if applicable. Keep the connections, testset settings, and 7UT51 settings if Test 35 is to
be done. Otherwise, program Trip Relay 1 for
the intended settings. End of test.
9. Set Address 2104 = 0.00 seconds.
10. Suddenly apply the current.
11. Record the pickup time of 50HS plus the output
contact.
12. Repeat steps 10 and 11 two or more times, to
obtain a pickup timespread for 50HS and
contact.
13. If Address 2104 = 0.00 seconds is the desired
setting, end of test. Turn Off the current and
reset the LEDs and LCD. Keep the connections,
test-set settings, and 7UT51 settings for Test 35.
Otherwise, continue.
70
PRCM-1108A-0199
7UT51 v3
For the default settings, LEDs 1 and 4 should light
when 50HS trips. Depending on Address 2104, the
time lag between application of current and 50HS
tripping can be noticeable. All trip contacts and
contacts associated with Signal Relays 1 and 3
should toggle when 50HS trips. When the current is
Off, the LCD should show Back Gen. Flt and BU
Gen.Trip.
Test 35. Manual Close Controlling
50HS Tripping Delay: Address 2121
7.
8.
9.
10.
11.
12.
Expected Results:
When Event 0356 is active and current exceeds the
pickup of 50HS, the element should trip without
delay, other than inherent delay. Once tripped,
50HS should reset only after the current decreases
below the element dropout level. A change in state
of the discrete input causing Event 0356 should not
PRCM-1108A-0199
71
7UT51 v3
below should be free to operate signal relays or
LEDs.
Event 2411 Back-up O/C+G/F: General fault
detected
Event 2421 BU 50HS Phase highset OC fault det.
Event 2441 BU 50HS Highset O/C time expired
(with or without time delay)
Event 2451 BU Overcurrent+G/F : General Trip
7UT513 Relay
Connect to one
phase of
winding
associated with
50/51/50HS
I1
IA
IB
Trip
Contact 1
W1
IC
START I1 OFF
Ia
Timer
STOP
Ib
W2
Ic
Ia
Ib
Ic
W3
(7UT513
only)
72
PRCM-1108A-0199
7UT51 v3
8. Record the trip dropout value given by the timer.
9. If the desired setting of Address 2118 = 0.00
seconds, go to Step 13. Otherwise, go to the
next step.
10. Repeat steps 6-8 two or more times to
determine a timespread for the dropout time of
50HS plus contact.
14. Set Address 2118 for the desired setting.
15. Repeat steps 6-8.
16. Set Address 2103 for the original, desired
setting.
17. Program the Trip Relays for the original, desired
settings.
Expected Results:
With Address 2118 = 0.00 seconds, the dropout
time of 50HS, plus the contact, should be 50 ms +/13 ms, with a current of [1.2 X pickup value]
dropping suddenly to 0 A after 50HS trips.
The dropout times from step 10 (2118 = 0.00
seconds) must be subtracted from the dropout time
of step 12 (2118 = desired setting) to obtain the
tested value for Address 2118. The accuracy of
Address 2118, including the timer accuracy, is the
larger of +/- 3% or +/- 10 ms. The dropout
timespread of 50HS (without delay) plus contact
must be considered.
For the default settings, LEDs 1 and 4 should light
when 50HS trips. All trip contacts and contacts
associated with signal relays 1 and 3 should toggle
when 50HS trips. The contacts should remain
tripped until the dropout timer expires. When 50HS
drops out, the LCD should display Back Gen. Flt
and BU Gen.Trip.
Note: Set all Settings Pertaining to 50/51 to the
Desired Values
Tank Leakage Protection
The tests for tank leakage protection (64T) apply
only to a 7UT513 fitted with the 64T option.
The protection is existent and operational when
settings other than Nonexistent and Off are
selected for Addresses 7827 and 2701, respectively.
Notes about Testing Tank Leakage Protection
To make 64T existent, one of two settings are
selected for Address 7827. There are important
differences between the two settings.
PRCM-1108A-0199
7UT513 Relay
IA
I1
IB
Trip
Contact 1
W1
or
Contact
Monitor
IC
I1
Ia
Ib
Address 7827
= Sensitive
CTB, connect
I1 to INb
Address 7827
= Insensitive
CTA, connect
I1 to INa
W2
Ic
W3 not
shown
1D1
1D2
INb
2D1
2D2
INa
73
7UT51 v3
Test Equipment
7UT513 Relay
IA
I1
IB
or
I1
W1
IC
Ia
START I 1 ON
Trip
Contact 1
STOP
STOP
Ib
W2
5A1
5A2
Timer
Option 2
Ic
START
Trip
Contact 2
W3 not shown
1D1
Connection
1D2
INb
Option 2
2D1
2D2
INa
Address 7827 =
Sensitive CTB,
connect I1 to INb
Timer
Option 1
Address 7827 =
Insensitive CTA,
connect I1 to INa
Option 1:
74
PRCM-1108A-0199
7UT51 v3
results from Test 38. Current equal to twice the
pickup value is good.
4. If Address 2725 is infinite (+*) seconds,
continue to Step 5. Otherwise, skip to Step 8.
5. Suddenly apply the current.
6. Verify the timer does not stop, and no other
contacts or LEDs programmed for the tripping of
64T operate. (Action from the pickup of 64T is
proper.)
7. Turn Off the current, and reset the LEDs and
LCD, if applicable. Keep the testset connections
and 7UT513 settings if Test 40 is to be done.
End of test.
8. Set Address 2725 = 0.00 seconds.
9. Suddenly apply the current.
10. Record the pickup time of 64T plus the output
contact.
11. Repeat steps 9 and 10 two or more times, to
obtain a pickup timespread for 64T plus contact.
12. If Address 2725 = 0.00 seconds is the desired
setting, end of test. Keep the connections,
testset settings, and 7UT513 settings if Test 40
is to be done. Otherwise, continue.
13. Set Address 2725 for the desired value.
14. Repeat steps 9-10. The recorded time now
includes Address 2725.
15. Reset the LEDs and LCD.
16. Keep the connections, test-set settings, and
7UT513 settings if Test 40 is to be done.
Otherwise, program Trip Relay 1 for the original,
intended setting.
Expected Results:
Option 2:
With Address 2725 = 0.00 seconds, the results
indicate the inherent tripping time of 64T. Expect
times in the range of 20 to 30 ms at 2 times pickup.
The pickup times from Step 11 (2725 = 0.00
seconds) must be subtracted from the pickup time
of Step 14 (2725 = desired setting) to obtain the
tested value for Address 2725. The accuracy of
Address 2725, with the timer accuracy included, is
the larger of +/- 3% or +/- 10 ms. The pickup
timespread of 64T (without delay) plus contact must
be considered.
The pickup timespread of 64T plus contact can add
errors and uncertainty to the results. If the user is
not satisfied with the calculated value for Address
2725, the Network Disturbances option in the
WinDIGSI software can be useful.
Obtain dialog with the 7UT513. Click on
Annunciation, then Annunciations Edit. Select
Network Disturbances, and Display. Display an
event associated with the testing. Subtract the time
for Event 5916 (64T pickup) from the time for Event
5921 (64T General Trip) to get the delay in tripping
caused by Address 2725.
Operations of the contacts, LEDs, and LCD should
be consistent with those in Test 38, with
consideration given to the programming for Trip
Relay 1. Depending on Address 2725, the delay
between the application of current and 64T tripping
may be noticeable.
Option 1:
The value read from the timer is the direct, tested
value for Address 2725. The value should be within
the larger of +/- 3% or +/- 13 ms of Address 2725.
Operations of the contacts, LEDs, and LCD should
be consistent with those in test 38, with
consideration given to the programming for Trip
Relays 1 and 2. Depending on Address 2725, the
delay between the application of current and 64T
tripping may be noticeable.
PRCM-1108A-0199
75
7UT51 v3
5903 is activated, the event should have no effect.
The 7UT513 should remain in a tripped state with all
contacts, LEDs, and the LCD reflecting the 64T trip.
If (1) the event is first activated, (2) current above
the pickup of 64T is applied, and then (3) the event
is deactivated with the current still present, 64T
should trip and provide outputs, LEDs, and an LCD
display in the normal fashion.
Address 2701 = Block Tripping and an input causing
the coming of Event 5905 >BLOCK transformer
tank prot trip signal, applied before a 64T trip,
should have similar effects. Either should prevent
Event 5921 Transformer tank prot.: General TRIP
from operating trip relays. Events 5916, 5917, and
5921 should be uninhibited in operating LEDs and
signal relays. For the default settings, the LCD
should read TankGen FAULT.
If Event 5921 is blocked from operating a trip relay
because of Event 5905, and then Event 5905 is
released, Event 5921 should remain blocked.
Applying Event 5905 after 64T has tripped should do
nothing. The event should be ignored.
7UT513 Relay
IA
I1
IB
Trip
Contact 1 5B1
5B2
W1
or
IC
I1
Timer
Ia
START I1
OFF
STOP
Ib
W2
Ic
Address 7827 =
Sensitive CTB,
connect I1 to INb
Address 7827 =
Insensitive CTA,
connect I1 to INa
1D1
1D2
2D1
2D2
W3 not
shown
INb
INa
76
PRCM-1108A-0199
7UT51 v3
Restricted Ground Fault Protection
The tests for restricted ground fault protection (87N)
apply only to a 7UT513 fitted with the 87N option.
Test Equipment
7UT513 Relay
IA
I1
Trip
Contact 1
5B1
5B2
IB
PRCM-1108A-0199
W1
or
I1
Timer
Ia
Ib
W2
Connect I1 to
INb if Address
7807 (CTB) is
associated
with 87N.
W3 not
shown
Connect I1 to
INa if Address
7806 (CTA) is
associated
with 87N.
Ic
* I1 ON for
testing
Address
1925
*I1 OFF for
testing
Address
1927
1D1
1D2
INb
2D1
2D2
5B3
5B4
IC
START *
STOP
Contact
Monitor
INa
77
7UT51 v3
out. Record the current at dropout. Record
changes of contacts, LEDs, and the LCD.
3. Turn Off the current. Reset the LEDs and LCD.
Note: Keep the 7UT513 connections for tests 43-45.
Expected Results:
78
Expected Results:
With Address 1925 = 0.00 seconds, the results
indicate the inherent tripping time of 87N. Expect
times in the range of [35 to 45] ms at 2 times pickup.
The pickup times from Step 10 (1925 = 0.00
seconds) must be subtracted from the pickup time
of Step 13 (1925 = desired setting) to obtain the
tested value for Address 1925. The accuracy of
Address 1925, with the timer accuracy included, is
the larger of +/- 3% or +/- 10 ms. The pickup
timespread of 87N (without delay) plus contact must
be considered, though the spread should be tight at
two times pickup.
The pickup timespread of 87N plus contact can add
errors and uncertainty to the results. If the user is
not satisfied with the calculated value for Address
1925, the =Network Disturbances option in the
WinDIGSI software can be useful.
Obtain dialog with the 7UT513. Click on
Annunciation, then Annunciations Edit. Select
Network Disturbances, and Display. Display an
event associated with the testing. Subtract the time
for Event 5816 Restricted gnd fault: Pickup from
PRCM-1108A-0199
7UT51 v3
the time for Event 5821 Restricted ground fault:
General Trip to get the delay in tripping caused by
Address 1925.
PRCM-1108A-0199
79
7UT51 v3
timespread of 87N (without delay) plus contact must
be considered.
7UT513 Relay
IA
I1
(60Hz)
IB
Trip
Contact 1
or
Connect I1 to Inb
Ib
W2
if Address 7807
(CTB) is
associated with
87N.
W3 not
shown
Connect I1 to INa
if Address 7806
(CTA) is
associated with
87N.
Ic
1D1
1D2
INb
2D1
2D2
INa
80
Ia
(120Hz) I2
Connect I2 to one
phase of winding
associated with 87N.
Connect I2 polarity to
phase input polarity.
Contact
Monitor
5B3
5B4
IC
I1
(60Hz)
5B1
5B2
W1
% 2 Restr. =
([120 Hz current from Step 7] X [87N Phase CT
Primary Rating] X 100%)
PRCM-1108A-0199
7UT51 v3
ND
Option 2:
Option 1:
Use the same 7UT513 connections as in Test 46
(Figure 39).
1. Set the 60 Hz Source 1 current for about [0.8 X
INRGFWx X Address 1912] or [0.8 X IOBJRGF X
Address 1912].
2. Set the Source 2 current frequency for 120 Hz.
3. Set the Source 2 current magnitude so that the
nd
percentage of 2 harmonic current, when the
Source 1 current reaches [INRGFWx X Address
1912] or [IOBJRGF X Address 1912], is much
greater than the minimum restraint level
(Address 1911). If I2 is the magnitude of the
Source 2 current and I1 the magnitude of the
Source 1 current, then:
I2 >>
I1
X [87N Ground CT Primary Rating]
X [Address 1911, Decimal Format]
87N Phase CT Primary Rating
PRCM-1108A-0199
Test Equipment
7UT513 Relay
I2
(120Hz)
IA
Trip
Contact 1
IB
W1
or
IC
I1
5B1
5B2
Contact
Monitor
5B3
5B4
Ia
(60Hz)
Ib
Example
Connections
only. Assumes
CTA and
winding 2 are
associated with
87N.
W2
Ic
W3 not
shown
1D1
1D2
1Nb
2D1
2D2
1Na
81
7UT51 v3
positive direction the test current is doubled in
forming the differential current.)
3. Be sure current Source 2 is connected to a
different phase than current Source 1.
4. Set the Source 2 current frequency for 120 Hz.
5. Set the Source 2 current magnitude equal to 18
amps.
Option 2:
82
PRCM-1108A-0199
7UT51 v3
3I0* [k X ISTAB] [Address 1903 X INRGFWx] or
[Address 1903 X IOBJRGF] (2)
PRCM-1108A-0199
83
7UT51 v3
Table 11: Maximum for 87N tripping
with 3I0* = 3I0** = [2 X Address 1903 X
INRGFWx or IOBJRGF] and
k-Values for Address 1904
Address
1904
Value of k
associated with
Address 1904
Maximum
for 87N Trip
130
1.03372
109.7
120
1.36603
104.9
110
2.03603
100.0
100
4.05657
95.0
90
90.0
Value of k
Associated with
Address 1904
1.03372
Maximum
for 87N Trip
1.36603
109.9
110
2.03603
103.3
100
4.05657
96.7
90
90.0
IA
Trip
Contact 1
or
IB
W1
I1
IC
I1
116.4
120
7UT513 Relay
5B1
5B2
Contact
Monitor
5B3
5B4
Ia
I2
Connect I2 to
one phase of
winding
associated with
87N. Connect
I2 polarity to
phase input
polarity.
Ib
W2
Ic
1D1
1D2
2D1
2D2
W3 not
shown
INb
INa
Connect I1 to INb
if Address 7807
(CTB) is
associated with
87N.
Connect I1 to INa
if Address 7806
(CTA) is
associated with
87N.
84
PRCM-1108A-0199
7UT51 v3
Security for External Faults:
Magnitude =
([Current-Source 1 Magnitude] X [87N Ground CT
Primary Rating])
(87N Phase CT Primary Rating)
PRCM-1108A-0199
85
7UT51 v3
Program Trip Relay 1 for the desired, in-service
settings.
Setting Verification after Electrical Testing
Although instructions are given throughout the
procedure to reset addresses or programming back
to the original, desired values after the tests, a
complete down-loading of all of the intended 7UT51
settings is recommended when the electrical tests
have finished. This will prevent unintended settings
when the 7UT51 is placed in-service. Alternatively,
a thorough check of the settings should be made
after the electrical tests have been completed and
before the 7UT51 is placed in-service.
86
PRCM-1108A-0199
7UT51 v3
Control Wire, CT, and Relay Installation
PRCM-1108A-0199
87
7UT51 v3
Primary
A
C
I
I
3A1
2A1
1A2
3B1
3B2
1B1
3A1
3A2
2A1
2A2
1A1
1A2
3B1
3B2
2B1
2B2
1B1
1B2
a '
3D1
3D2
b '
c '
2A2
2B2
I
3A2
1A1
2B1
Primary
B
C
1B2
Secondary
7U T 51 R ela y
Secondary
a'
b'
Tertiary
2C1
2C2
1C1
1C2
c'
7U T513
88
PRCM-1108A-0199
7UT51 v3
Commissioning Tests
Operational Checks
Operational checks are performed after wire
checking is complete.
Physical Inspection
Inspect all cables, junction boxes, circuit breakers,
etc., for proper wiring, shorting type terminal blocks
at proper locations, tight connections (screw heads
must be tight against wire). Check that shorting
screws are removed from CT blocks that will be in
service. Inspect boxes, switches, and relays for any
material such as wires, screws, lugs, or tags that
could short or ground the circuit. Visually wire-check
all current circuits.
Check auxiliary switches for connections, wipe, and
adjustment per manufacturer's instructions,
particularly the operating relation with respect to
main blade make and break.
After the acceptance tests have been completed and
the relay is installed with the permanent settings
applied and tested, the commissioning tests and
checks can be performed.
Installation Test Procedures
For test procedures, refer to the Acceptance Testing
section and perform only the tests required to check
the settings and control to be used in the specific
field application. Prior to installation, complete
testing of the discrete inputs, signal contacts, and
trip contacts is recommended. This will reduce the
operational checking of the transformer protection to
simply checking the CT connections, 7UT51 input
connections, and wiring of the output contacts.
PRCM-1108A-0199
89
7UT51 v3
Energizing the Transformer
90
PRCM-1108A-0199
7UT51 v3
Note:
PRCM-1108A-0199
91
7UT51 v3
Using WinDIGSI, deleting the operational buffer
is founder under:
92
PRCM-1108A-0199
7UT51 v3
Routine Testing of System
Input Integrity
The inputs can be periodically checked by
performing the following:
Block tripping.
Relay Integrity
Routine checks of the relay characteristics or pickup
values are not necessary, as they form part of the
continuously supervised firmware programs.
The relay is self-monitored and problems within the
relay are automatically annunciated. If a problem
within the relay is detected, the relay will block itself
and the red LED Blocked light will be lit and LCD
will read Equipment Fault.
Output Integrity
During an outage, one method available to check
the outputs is to program one input for external trip
and program all outputs (signal and trip) for external
trips up to ten (10) at a time. Then trip the
perspective devices. This test would check the
outputs and operational wiring out to the controlled
device.
Validate Metering
PRCM-1108A-0199
93
7UT51 v3
During normal operation or through-fault testing, the
value of differential current should be negligible
against the magnitude of the line currents. The
stabilizing (restraint) value should be approximately
twice the test or line current value.
Waveform
94
PRCM-1108A-0199
7UT51 v3
Fault Data and Analysis Tools
Front Panel Alarms
Addresses 7107 and 7108 can be set to Display
Information on the latest fault event. Once the
message is acknowledged with the Reset key or via
remote reset, the selected display for Addresses
7105 and 7106 will appear.
The LEDs will be lit depending on how they were
marshalled in Address block 6300 (assuming the
corresponding function is Enabled and On).
Remote warnings will also be initiated if utilized.
Fault Analysis Data
The sources available to analyze a fault event are as
follows.
Address 5100 - the Event Log which contains the
50 most recent event messages, both operational
and fault messages, with older messages
overwritten by newer messages.
Address 5200 The Last Fault information (see
Note)
nd
rd
PRCM-1108A-0199
PC
The PC can communicate directly with the relay by
entering the Dialog menu and choosing the Dialog
mode with the protection device Direct. Data may
also be accessed via a modem or SCADA system.
Consult the WinDIGSI Instruction Manual or the
WinDIGSI Users Manual for detailed instructions.
The recorded waveform fault data can be viewed
and analyzed by exporting (download) to a PC.
Data for up to three faults is stored in the relay;
however, the PC memory can store many. This data
can give valuable information on the simultaneously
captured data for all current inputs and up to four
user-defined functions that report the status of
discrete-signal inputs.
95
7UT51 v3
The fault data is accessed by entering the Fault
menu. From the Fault menu:
96
PRCM-1108A-0199
7UT51 v3
Address Index
1000
1100 ................................................ 8, 22, 37
1102 .......................................................... 17
1104 .................................. 17, 22, 43, 76, 87
1105 .................................................... 17, 36
1106 .................................. 24, 36, 37, 39, 41
1107 .............................................. 43, 47, 76
1108 .......................................................... 42
1121 .................................................... 17, 24
1124 .............................................. 17, 22, 76
1125 .................................................... 17, 36
1126 .......................................................... 24
1127 .......................................................... 76
1141 .......................................................... 24
1144 .................................................... 22, 76
1146 .......................................................... 24
1147 .......................................................... 76
1401 .......................................................... 76
1402 .................................................... 22, 76
1601 ...................... 20, 24, 48, 49, 50, 60, 76
1603 ............................ 24, 27, 32, 44, 45, 54
1604 .......... 25, 26, 27, 28, 29, 30, 31, 45, 55
1606 .......................................................... 45
1607 .................................................... 44, 45
1608 .................................................... 45, 46
1611 .............................................. 31, 33, 90
1612 .............................................. 33, 34, 90
1613 .............................................. 32, 33, 35
1614 .................................................... 32, 33
1615 ............................ 32, 33, 34, 35, 50, 51
1616 .................................. 23, 32, 33, 50, 51
1617 .............................................. 47, 48, 55
1618 .................................................... 46, 47
162525, 26, 27, 28, 29, 30, 31, 34, 35, 46, 47, 48
1626 .............................................. 28, 29, 30
1627 ........................................ 26, 27, 30, 31
1900 .......................................................... 14
1901 .............................................. 76, 77, 78
1903 ........................................ 76, 77, 82, 83
1904 .............................................. 82, 83, 84
1910 .................................................... 79, 80
1911 .............................................. 79, 80, 81
1912 .................................................... 80, 81
1925 .............................................. 76, 77, 78
1927 .............................................. 76, 78, 79
2000
5000
2100 .......................................................... 15
2101 ...................... 27, 50, 60, 64, 65, 67, 70
2103 ...................... 61, 62, 63, 66, 67, 68, 71
2104 .................................. 61, 67, 68, 69, 70
2111 ........................................ 60, 61, 62, 64
2112 .................................................... 60, 61
PRCM-1108A-0199
3000
3000 .......................................................... 15
3001 ........................................ 56, 57, 58, 59
3002 .............................................. 57, 58, 59
3003 .......................................................... 59
4000
4100 .................................................... 16, 84
4101 ............................ 16, 43, 44, 89, 90, 92
4121 .................................................... 16, 17
4141 .................................................... 16, 17
4161 .................................................... 17, 44
4181 .................................................... 17, 84
4800 ........................................ 17, 18, 44, 91
4801 .............................................. 18, 44, 84
4900 ........................................ 20, 89, 90, 93
4901 .............................................. 20, 90, 93
97
7UT51 v3
Address Index (Continued)
5706 .......................................................... 19
5708 .......................................................... 19
5709 .......................................................... 19
5710 .......................................................... 19
5711 .......................................................... 19
5721 .......................................................... 19
5722 .......................................................... 19
5723 .......................................................... 19
5724 .......................................................... 19
5725 .......................................................... 19
5726 .......................................................... 19
5727 .......................................................... 19
5728 .......................................................... 19
5729 .......................................................... 19
5730 .......................................................... 19
5731 .......................................................... 19
5900 .............................................. 19, 89, 92
5911 .......................................................... 19
5912 .......................................................... 19
5913 .......................................................... 19
5914 .......................................................... 19
5921 ............................ 19, 23, 72, 73, 74, 75
5922 .......................................................... 19
5923 .......................................................... 19
5924 .......................................................... 19
6000
6201 .......................................................... 23
6202 .......................................................... 23
6203 .......................................................... 23
6206 .......................................................... 23
6207 .......................................................... 23
6208 .......................................................... 23
6209 .......................................................... 23
6210 .......................................................... 23
6211 .......................................................... 23
6300 .................................................... 14, 94
6301 .......................................................... 23
6302 .......................................................... 23
6303 .......................................................... 23
6304 .......................................................... 23
98
5707 .......................................................... 19
6307 .......................................................... 23
6308 .......................................................... 23
6309 .......................................................... 23
6310 .......................................................... 23
6311 .......................................................... 23
6312 .......................................................... 23
6401 .......................................................... 23
6405 .......................................................... 23
7000
7100 .................................................... 14, 16
7105 .............................................. 16, 91, 94
7106 .............................................. 16, 91, 94
7107 .............................................. 16, 23, 94
7108 .............................................. 16, 23, 94
7110 .......................................................... 16
7200 .......................................................... 14
7221 .......................................................... 93
7222 .......................................................... 93
7400 .......................................................... 20
7402 .................................................... 20, 89
7411 .......................................................... 20
7431 .......................................................... 20
7432 .......................................................... 20
7800 .............................................. 35, 91, 93
7806 ......................17, 42, 76, 77, 78, 79, 83
7807 ......................17, 42, 76, 77, 78, 79, 83
7816 .......................................................... 24
7819 .................................. 14, 76, 77, 78, 79
7821 .................................................... 15, 60
7824 .................................................... 15, 50
7825 .................................................... 15, 50
7827 ........................................ 15, 72, 73, 75
7830 .................................................... 15, 56
7831 .................................................... 15, 56
8000
8300 .......................................................... 93
8301 .......................................................... 93
PRCM-1108A-0199