Вы находитесь на странице: 1из 2

Pressure testing of Coil Tubing PCE

Weekly Full BOP Test This test will be carried out every seventh day that the CTU unit is in operation, AND before any stimulation or clean out operation. 1. Rig up temporary pipework (TPW) from the pump unit to KWV. Ensure there is a check valve between the TPW and the KWV. Ensure the TPW is secured by restraining wire. 2. Stab on the BOP and function test all rams. 3. Flush the coil with water to the cellar until clean returns. 4. Before stabbing on the injector head, inspect the BHA and remove and inspect the check valves. Check the overall condition of the BHA. 5. Open up the Lo-torque valve at the T piece at the wellhead and flush the surface lines with water to the cellar until clean returns. 6. Test surface lines. Close the KWV and pressure test the surface lines to 5000 psi, observe for any leaks. 7. Test Xmas tree valves. Close the UMV, SWV and WV, open the KWV. Test Xmass-tree and WV to 3500psi. Monitor pressure drop-off. Grease and cycle valves if required. 8. Stab on injector. 9. Test Blind Rams. Close blind rams, open SWV and pressure test against blind rams to 3500psi via the KWV 10. Run in BHA to below pipe rams. 11. Test check valves. Close the slip rams around the coil and energize the stripper. Apply 1000 psi via the KWV to the riser. Open the coil tubing reel inlet valve or monitor a gauge at the real inlet valve and observe for any leaks through BHA-check valves. If a leak occurs, remove the injector, change out the check valves and re-test. 12. Test stripper & connections. With the stripper still closed, pressure up via coil to 3500 psi to pressure test the connections between the tree cap and the stripper. 13. Test Pipe rams Close the pipe rams. Open the Lo-torque valve on the BOPs kill line. Pressure test via the coil tubing to 5000 psi

Observe for leaks thro the BOP kill line that may indicate the pipe rams are not holding pressure. 14. Bleed off the pressure via the KWV and open the pipe rams. Close the BOP lotorque valve. 15. Purge the reel if necessary. BOP function test, Stripper test & BHA check-valves test. This test will be carried out on every rig up. 1. Rig up temporary pipe-work (TPW) from the pump unit to KWV. Ensure there is a check valve between the TPW and the KWV. Ensure the TPW is secured by restraining wire. 2. Stab on the BOP and function test all rams. 3. Open up the Lo-torque valve at the T piece at the wellhead and flush the surface lines with water to the cellar until clean returns. 4. Test surface lines. Close the KWV and pressure test the surface lines to 5000 psi, observe for any leaks. 5. Test Xmas tree valves. Close the UMV, SWV and WV, open the KWV. Test Xmass-tree and WV to 3500psi. monitor pressure drop-off. Grease and cycle valves if required. 6. Flush the coil with water until clean returns. 7. Before stabbing-on the injector head, inspect the BHA and remove and inspect the check valves. Check the overall condition of the BHA. 8. Stab the injector onto the riser/BOPs 9. Test check valves. Close the slip rams around the coil and energize the stripper. Apply 1000 psi via the KWV to the riser. Open the coil tubing reel inlet valve or monitor a gauge at the real inlet valve and observe for any leaks through BHA-check valves. If a leak occurs, remove the injector, change out the check valves and re-test. 10. Test stripper and connections. With the stripper still closed, pressure up via coil to 3500 psi to pressure test the connections between the tree cap and the stripper. 11. Bleed off pressure, purge the reel if required.

Вам также может понравиться