FEEDER PROTECTION RELAY

CROMPTON GREAVES LIMITED

CROMPTON GREAVES LIMITED


MV Switchgear Division (S2) A-3 MIDC, Ambad, Nashik 422 010 T: +91- 2382271-75, 2301104 Fax: +91-0253-2381247

Operating Manual For Feeder Protection Relay

CROMPTON GREAVES LIMITED

REVISION HISTORY
Revision 00 Type AEGIS Date 01-12-2011 Checked By NS Approved By GPB

Note: The features mentioned may not be a part of standard product. Product development is a continuous process. Consequently the data indicated is subject to change without prior notice.

CROMPTON GREAVES LIMITED

Dear Customer, Please accept our thanks for giving us the privilege to serve you by choosing a CG make Feeder Protection Relay. If this is your first CG Protection Relay, we hope it is the beginning of a long relationship which delivers value to your organization. If you already own and use a CG product, we are doubly honored by your decision of continuing this relationship. It is our constant endeavor to partner you for the growth and success of your business. This philosophy is reflected in our Mission statement Smart Solutions. Strong Relationships. Please do give us feedback to help us realize our Mission.

CROMPTON GREAVES LIMITED

CROMPTON GREAVES LIMITED

IMPORTANT
This manual contains information concerning the Operation of the AEGIS Series Feeder Protection Relay for the Switchgear Systems. All relevant parts of the manual should be read prior to commencing installation. The Relay must be commissioned by an engineer approved by the manufacturer (or his agent) before being put into service. Failure to observe this condition will invalidate any implied warranty. The AEGIS Series Feeder Protection Relay has been designed for Industrial use only. If you encounter any problem with the procedures contained in this manual you should seek immediate assistance from Crompton Greaves Limited, Sales Office from whom the equipment was purchased. Alternatively contact the Crompton Greaves Limited Customer Service & Support department at the address shown below: Crompton Greaves Limited MV Switchgear Division (S2) A-3 MIDC, Ambad, Nashik 422 010 , India Phone : (00 91 253) 2382271-75 2301104 Fax : (00 91 253) 2381247

Crompton Greaves Limited pursues a policy of continual product development and reserves the right to change the equipment without notice.
@ Copyright 2011 by Crompton Greaves Ltd. Unauthorized reproduction prohibited All rights reserved

CROMPTON GREAVES LIMITED

Disclaimer
The information in this document is subject to change without notice and should not be interpreted as assurance by CG. CG assumes no responsibility for any errors that may appear in this document.
@ Copyright 2010 by Crompton Greaves Ltd. Unauthorized reproduction prohibited All rights reserved

CROMPTON GREAVES LIMITED

Table Of Contents
1. General 1.1. Relay Features 1.2. User Interface 1.3. Health & Safety 1.3.1. Installing, Commissioning & Servicing 1.3.2. Decommissioning & Disposal 1.3.3. General Considerations 1.3.4. Handling of Electronic Equipment 1.3.5. Storage 2. Local Panel User Interface 2.1. Relay Front Panel 2.1.1. LED Indications 2.1.2. LCD Display 2.1.3. Keypad 2.1.4. Communication Port 2.1.5. Flowchart for Menu Navigation 3. Relay Settings 3.1. 3.2. 3.3. 3.4. 3.5. 3.6. 3.7. Device Info View Password Accessing Error Status View Measurements View Harmonics View Configuration Settings Non Directional Overcurrent Protection 3.7.1. IDMT Settings 3.7.2. Highset Settings 3.8. Non Directional Earth Fault Protection 3.8.1. IDMT Settings 3.8.2. Highset Settings 3.9. Directional Overcurrent Protection 3.9.1. IDMT Settings 3.9.2. Highset Settings 3.9.3. Directional Settings 3.10. Directional Earth Fault Protection 3.10.1. IDMT Settings 3.10.2. Highset Settings 3.10.3. Directional Settings 1 1 2 2 3 4 5 5 6 7 7 8 9 10 10 10 16 16 16 17 18 20 21 22 22 22 24 24 25 26 26 26 26 29 29 29 29

CROMPTON GREAVES LIMITED

3.11. Overvoltage Protection 3.11.1. IDMT Settings 3.11.2. Highset Settings 3.12. Undervoltage Protection 3.12.1. IDMT Settings 3.12.2. Highset Settings 3.13. Neutral Voltage Displacement Protection 3.14. Broken Conductor Protection 3.15. Cold Load Pick up & Inrush Current Protection 3.16. CT Supervision 3.17. VT Fuse Failure protection 3.18. Negative Phase Sequence Over Current Protection 3.19. Communication Settings 3.20. Binary Input & Binary Output Settings 3.21. Fault Records 3.22. Fault Records Overview 3.23. Disturbance Recorder 4. Technical Data 4.1. Connections 4.1.1. Measuring Circuitry 4.1.2. Auxiliary Voltage 4.1.3. Binary Inputs 4.1.4. Binary Outputs 4.1.5. Local Serial Communication Port 4.1.6. Remote Control Connections 4.2. Test & Environmental Conditions 4.2.1. Type Test 4.2.2. Casing 4.2.3. Package 4.3. Protection Stages 4.3.1. Non Direction Current Protection Stage 4.3.2. Directional Current Protection Stage 4.3.3. Voltage Protection Stage 4.4. Circuit Breaker Failure Protection 4.5. Supporting Functions 4.6. Transformer Supervision 5. Connections 5.1. Rear Port Connections 5.2. Wiring Diagram 6. Dimensions

31 31 32 33 33 34 35 37 38 40 41 43 44 45 46 47 48 49 49 49 49 50 50 50 50 51 51 52 52 53 53 55 57 58 59 60 61 61 64 65

CROMPTON GREAVES LIMITED

7. Curves 7.1. 7.2. 7.3. 7.4. Standard IDMT Characteristic of Overcurrent Standard Characteristic of Overvoltage Standard Characteristic of Undervoltage Standard Characteristic of Negative Phase Sequence Overcurrent

66 66 72 72 72 73 74 81

8. Ordering Information 9. Customer Settings 10. Notes

CROMPTON GREAVES LIMITED

List of Figures
1. Figure 2.1-1 Front panel of feeder protection relay 2. Figure 2.1.1-1 LED indicators of feeder protection relay 3. Figure 2.1.2-1.LCD display of feeder protection relay 4. Figure 2.1.3-1 Keypad of feeder protection relay 5. Figure 2.1.5-1 Principle of the menu structure & navigation 6. Figure 3.1-1 Device info view 7. Figure 3.2-1 Password accessing 8. Figure 3.3-1 Error status view 9. Figure 3.4-1 Measurements view 10. Figure 3.4-2 Graphical representation of 3 phase system 11. Figure 3.4-3 Zoom view of measurement window 12. Figure 3.5-1 Example of harmonics view 13. Figure 3.6-1 Configuration settings 14. Figure 3.7-1 Non directional overcurrent settings 15. Figure 3.8-1 Non directional earth fault settings 16. Figure 3.9-1 Directional overcurrent settings 17. Figure 3.10-1 Directional earth fault settings 18. Figure 3.11-1 Overvoltage protection settings 19. Figure 3.12-1 Undervoltage protection settings 20. Figure 3.13-1 NDR protection settings 21. Figure 3.14-1 Broken conductor settings 22. Figure 3.15-1 Inrush protection settings 23. Figure 3.16-1 CT supervision settings 24. Figure 3.17-1 Logical diagram for VTFF 25. Figure 3.17-2 VTFF settings 26. Figure 3.18-1 Negative phase sequence over current settings 27. Figure 3.19-1 Communication settings 28. Figure 3.20-1 Binary inputs & outputs settings 29. Figure 3.21-1 Fault records view 30. Figure 3.22-1 Fault records overview 31. Figure 3.23-1 Disturbance recorder 32. Figure 5.1-1 Rear view of feeder protection relay 33. Figure 5.2-1 Wiring diagram for feeder protection relay (AE001) 34. Figure 6-1 Dimensions 35. Figure 7.1-1 IEC VI & SI curves characteristics 36. Figure 7.1-2 IEC EI & LTI curves characteristics 37. Figure 7.1-3 IEEE EI & VI curves characteristics 38. Figure 7.1-4 IEEE SI curves characteristics 39. Figure 7.1-5 RI & RD curves characteristics 7 8 9 10 11 16 16 17 18 19 19 20 21 23 24 28 30 31 33 35 37 39 40 41 42 43 44 45 46 47 48 61 64 65 67 68 69 70 71

CROMPTON GREAVES LIMITED

ABBREVIATIONS AND SYMBOLS


ANSI AWG BI BO BR.C CBFP COMM CONF CT CTSV D-EF D-OC DR DT EF ESD FL-R FWD HRMN I2> IDMT IEC IEEE INFO INRH KVA KVAR KW LCD LED MESR NDR NV OC OV PF PROT REV SCADA THD USB UV VT VTFF American National Standards Institute American Wire Gauge Binary Input Binary Output Broken Conductor Circuit Breaker Failure Protection Communication Configuration Current Transformer Current Transformer Supervision Directional Earth Fault Directional Over Current Disturbance Recorder Definite Time Earth Fault Electrostatic Discharge Fault Record Forward Harmonics Negative Phase sequence over current Inverse Definite Minimal Time International Electrotechnical Commission Institute of Electrical and Electronics Engineers Information Inrush Current Kilo Volt Ampere Kilo Volt Ampere Reactive Kilo Watt Liquid Crystal Display Light Emitting Diode Measurements Neutral Voltage Displacements No Volt Over Current Over Voltage Power Factor Protection Reverse Supervisory Control and Data Acquisition Total Harmonic Distortion Universal Serial Bus Under Voltage Voltage Transformer Voltage Transformer Fuse Failure

CROMPTON GREAVES LIMITED

1.

GENERAL
The first part of the publication contains general description & operating instructions of AEGIS Series Feeder Protection Relay. It also includes instructions for parameterization and configuration of the Relay.

1.1.

RELAY FEATURES

The comprehensive protection functions of the relay make it ideal for utility & industrial power distribution applications. The relay features following protection functions:
ANSI No.
50/51 51,51N 67 67N 27 59 59N 46 50BF 46BC 68 51V 32 40 79 60CTS 74TCS

FUNCTION NAME
Instantaneous and Inverse time phase over current protection Instantaneous and Inverse time Earth fault protection Directional Instantaneous and Inverse time phase over current protection Directional Instantaneous and Inverse time Earth fault protection Instantaneous and Inverse time phase under voltage protection Instantaneous and Inverse time phase over voltage protection Neutral Displacement Protection Phase unbalance Protection Circuit Breaker failure Protection Broken conductor detection Protection Cold load Pickup & Inrush Voltage Controlled Over Current* Reverse Power Protection* Loss of Excitation* Auto Reclose* CT Supervision PTFF Supervision Trip Circuit Supervision Three Phase Current Neutral current Sequence Components of Currents Sequence Components of voltages Phase to earth, Phase to Phase Voltage Phase Angle Power factor Active Power Reactive Power Apparent Power Energy Measurement* 2nd to 15th harmonic and THD of Currents 2nd to 15th harmonic and THD of Voltages Phasor diagram of Voltages Phasor diagram of Currents Frequency Actual RMS value of Currents Actual RMS value of Voltages IEC 60870-5-103 Modbus IEC61850 DNP3.0

MEASUREMENTS & MONITORING FUNCTIONS

PROTECTION FUNCTIONS

55

CROMPTON GREAVES LIMITED

COMMUNICATION FUNCTIONS

PAGE

1.2. USER INTERFACE


The relay can be configured in two ways We can operate the relay locally by the key pad on the front panel By using the front USB on the relay through PC

1.3. HEALTH & SAFETY


The information in the Safety Section of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition. It is assumed that everyone who will be associated with the equipment will be familiar with the contents of that Safety Section, or this Safety Guide. When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the equipment must be isolated. Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and Servicing. For this reason only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected; are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorised to energize and de-energize equipment and to isolate, ground, and label it; are trained in the care and use of safety apparatus in accordance with safety Engineering practices; are trained in emergency procedures (first aid). The operating manual for the equipment gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization.

CROMPTON GREAVES LIMITED

PAGE

1.3.1. INSTALLING,COMMISSIONING & SERVICING


Equipment connection Personnel undertaking installation, commissioning or servicing work for this equipment should be aware of the correct working procedures to ensure safety. The equipment documentation should be consulted before installing, commissioning or servicing the equipment. Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated. Any disassembly of the equipment may expose parts at hazardous voltage, also electronic parts may be damaged if suitable electrostatic voltage discharge (ESD) precautions are not taken. If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards. Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used. The equipment must be connected in accordance with the appropriate connection diagram. Equipment use If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Removal of equipment front panel/cover Removal of the equipment front panel/cover may expose hazardous live parts which must not be touched until the electrical power is removed. Equipment operations conditions The equipment should be operated within the specified electrical and environmental limits.

CROMPTON GREAVES LIMITED

PAGE

Current Transformer Circuits Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to personnel and could damage insulation. Generally, for safety, the secondary of the line CT must be shorted before opening any connections to it. For most equipment with ring-terminal connections, the threaded terminal block for current transformer termination has automatic CT shorting on removal of the module. Therefore external shorting of the CTs may not be required; the equipment documentation should be checked to see if this applies. For equipment with pin-terminal connections, the threaded terminal block for current transformer termination does NOT have automatic CT shorting on removal of the module. Insulation & Dielectric Strength Testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected. Insertion of modules & PCB cards Modules and PCB cards must not be inserted into or withdrawn from the equipment whilst it is energised, since this may result in damage. Cleaning The equipment may be cleaned using a lint free cloth dampened with clean water, when no connections are energised.

1.3.2. DECOMMISSIONING AND DISPOSAL


Decommissioning: The supply input (auxiliary) for the equipment may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the equipment (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning. Disposal: It is recommended that incineration and disposal to water courses is avoided. The equipment should be disposed of in a safe manner.

CROMPTON GREAVES LIMITED

PAGE

1.3.3. GENERAL CONSIDERATIONS


Receipt of relays Protective relays, although generally of robust construction, require careful treatment prior to installation on site. Upon receipt, relays should be examined immediately to ensure no damage has been sustained in transit. If damage has been sustained during transit a claim should be made to the transport contractor and Crompton Greaves Ltd. should be promptly notified. Electrostatic discharge The relays use components that are sensitive to electrostatic discharges. The electronic circuits are well protected by the metal case and the internal module should not be withdrawn unnecessarily. When handling the module outside its case, care should be taken to avoid contact with components and electrical connections. If removed from the case for storage, the module should be placed in an electrically conducting antistatic bag. There are no setting adjustments within the module and it is advised that it is not unnecessarily disassembled. Although the printed circuit boards are plugged together, the connectors are a Manufacturing aid and not intended for frequent dismantling; in fact considerable effort may be required to separate them. Touching the printed circuit board should be avoided, since complementary metal oxide semiconductors (CMOS) are used, which can be damaged by static electricity discharged from the body.

1.3.4. HANDLING OF ELECTRONIC EQUIPMENT


A persons normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced. The electronic circuits are completely safe from electrostatic discharge when housed in the case. Do not expose them to risk of damage by withdrawing modules unnecessarily. Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured. Before removing a module, ensure that you are at the same electrostatic potential as the equipment by touching the case. Handle the module by its front plate, frame or edges of the printed circuit board. Avoid touching the electronic components, printed circuit track or connectors. Do not pass the module to another person without first ensuring you are both at the same electrostatic potential. Shaking hands achieves equipotential.

CROMPTON GREAVES LIMITED

PAGE

Place the module on an antistatic surface, or on a conducting surface which is at the same potential as yourself. Store or transport the module in a conductive bag. If you are making measurements on the internal electronic circuitry of equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist straps should have a resistance to ground between 500k 10M. If a wrist strap is not available you should maintain regular contact with the case to prevent a build-up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible.

1.3.5. STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a place free from dust and moisture in their original cartons. Where de-humidifier bags have been included in the packing they should be retained. The action of the dehumidifier crystals will be impaired if the bag has been exposed to ambient conditions and may be restored by gently heating the bag for about an hour, prior to replacing it in the carton. Dust which collects on a carton may, on subsequent unpacking, find its way into the relay; in damp conditions the carton and packing may become impregnated with moisture and the dehumidifier will lose its efficiency. Storage temperature: 25C to +70C.

CROMPTON GREAVES LIMITED

PAGE

2. LOCAL PANEL USER INTERFACE


2.1. RELAY FRONT PANEL
The below figure 2.1-1 shows, as an example, the front panel of the AEGIS Series Feeder Protection Relay and the location of the user interface elements for the local control of Relay.

Figure 2.1-1.Front Panel of Feeder Protection Relay

1. 2. 3. 4. 5.

LED Indicators 160x160 LCD Display Keypad USB Communication for PC Model Number

CROMPTON GREAVES LIMITED

PAGE

2.1.1. LED INDICATORS


This Relay provided with 16 LED Indicators:
Power Alarm Trip Error

Figure 2.1.1-1.LED Indicators of Feeder Protection Relay

LED Indicator Power Alarm

Trip

Error

Meaning Auxiliary power has been switched on Indicates that any one of the Protection or Monitoring function has been picked up due to fault Indicates that Protection, Monitoring functions has been operated due to faults which are in the enabled condition. Indicates the internal faults of the Relay Configurable LEDs for the indication of Alarm & Trip signals of the Protection & Monitoring functions.

Remarks Normal operation state Fault indication of the Protection and Monitoring functions Refer fault record for type of faults For the particular error in the Relay refer section 3.3 We can set the LED operations as self or hand resets while the operation of Protection and Monitoring elements in the BI/BO menu.

12 LEDS

Resetting the Operated LEDs/Output Relays: All the LEDs, Output Relays can be configured by using the menus in the BI/BO window. 1. If any protection function is operated and LEDs/Output Relays are Hand Reset, then acknowledgement or Resetting is done by pressing the Esc( ) key in the keypad 2. We can activate or deactivate the LEDs/Output Relays by using the external Binary Input.

CROMPTON GREAVES LIMITED

PAGE

2.1.2. LCD DISPLAY


AEGIS Feeder Relay is having the display 160*160 Graphical display. The purpose of this display is to show the configuration and parameterization values of the relay.

Figure 2.1.2-1.LCD Display of Feeder Protection Relay

Menu navigation and pointers


Use the arrow keys UP ( ) and DOWN ( ) to move up and down in the main Menu, that is on the left side of the display, the active main menu option is indicated with a cursor. The options in the main menu are abbreviations Ex: INFO (Information) After any selection in the Main Menu, the possible navigating directions are indicated on the top of the Display window by arrows (,) The complete description of the selected menu is indicated on the top of Display window(Ex: Information)

Backlight control
The display backlit is automatically switched OFF after 1 minute when left idle. It can be switched on by pressing any key.

CROMPTON GREAVES LIMITED

PAGE

2.1.3. KEYPAD
You can navigate the menu and set the required parameter values using the key pad and directions indicated on the top of the display. Key pad is composed of four arrow keys for navigation UP ( ), down ( ), Left ( ), Right ( ) , ESC ( ), ENTER ( ) keys and CLOSE ( I ), TRIP ( O ) keys for the control of breaker
1

Figure 2.1.3-1.Keypad of Feeder Protection Relay

1. 2. 3. 4. 5. 6.

UP/DOWN Keys to navigate in Main Menu, to Increase/Decrease Numerical Values and for Enable/Disable operations. RIGHT/LEFT Keys to navigate in Sub-menu. ESC Key to cancel the current selection and to reset the output relays/LED. ENTER Key for edit & save the changed value. CLOSE key is to close the breaker from the relay. TRP key is to trip the breaker from the relay.

2.1.4. COMMUNICATION PORT


The Front port of the relay is a standard USB port provided for interfacing with PC. This port is used for relay configuration, downloading fault, event and disturbance records. The rear port is either a, Standard RS-485 port Ethernet port This port is used for communication with standard SCADA master/client softwares.

2.1.5. FLOWCHART FOR MENU NAVIGATING


All the menu functions are based on the main menu/sub menu structure: 1. Use the arrow keys UP and DOWN to move up and down in the main menu. 2. To move to a sub menu, repeatedly push the RIGHT, LEFT key until the requested submenu is shown as per the Indicated Arrows on the top of Display window 3. To move up and down in the Submenu use the UP and DOWN 4. At the any time to edit the value use the ENTER key, to increase or decrease the any parameter value use UP and DOWN keys. Use the enter key for confirmations. 5. To cancel the settings at any time press the Esc key. 6. At any time to return to main Menu Press the Esc key.
CROMPTON GREAVES LIMITED

PAGE

10

Figure 2.1.5-1. Principles of the menu structure and navigation in the menus

CROMPTON GREAVES LIMITED

PAGE

11

Main Menu: Menu structure of AEGIS Feeder Relay as shown in the below table, it describes the total parameters available in the sub menus.
Description of Parameters Relay Description, Model No. and Serial No. Setting Password and Default load password Internal faults in the Relay indication Measured Values for the System Currents & Voltages Power Calculation for the phase wise Indication of Date and Time Representation of System Voltages and Currents in Graphical Display Graphical representation of the Harmonics in the Bar-Graph format & the Calculation of THD(%) by the Phase wise for the both Currents & Voltages Last 10 faults can be stored by the Relay. Fault description shows the Fault No, Date & time, Magnitudes and Phase angles of the Fault Currents and Voltages. Contains features for enabling/disabling , Pre & Post fault conditions, sample rate & trigger options for DR Primary and Secondary Settings for the CT,VT Breaker control settings i.e. Close and trip No. of Parameters in Submenus

Main Menu

INFO

Information Password Error


Currents Primary Voltages Primary(L-N) Currents Secondary Voltages Secondary(L-N) Voltages Secondary(L-L) True RMS power L1 True RMS power L2 True RMS power L3 Date & Time Currents & Voltages Harmonics IL1 Harmonics IL2 Harmonics IL3 Harmonics UL1 Harmonics UL2 Harmonics UL3 Fault Recorder

Submenus

2 2 19
5 5 7 7 3 6 6 6 2

MESR

HRMN

22

FL-R

DR

Disturbance Recorder CT/VT Setting Configuration

4 6 2

CONF

CROMPTON GREAVES LIMITED

PAGE

12

3I> OC settings

3I>> OC Settings

4 2 2 2

OC
Breaker failure Settings LED & S/W BI Settings for the OC LED & S/W BI Settings for the Breaker failure

We can set the all the Parameters for the Over Current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT. We can set the all the Parameters for the Instantaneous Over Current element by this Menu i.e. Setting, Curve, DT, RST DT. This Setting allows the user to use the Relay as a Breaker back up relay You can set LEDs & output Relays for the indication of Over Current elements. You can set LEDs & output Relays for the Breaker failure element.

Io> E/F settings

EF

Io>> E/F Settings

LED & S/W BI Settings for the OC Directional 3I> Settings

2 1 1

D-OC

Directional 3I>> Settings

LED & S/W BI Settings for the Directional over Current element Directional Io> Settings

D-EF

Directional Io>> Settings

LED & S/W BI Settings for the Directional Earth fault Current

We can set the all the Parameters for the Earth fault Current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT. We can set the all the Parameters for the Instantaneous Earth fault current element by this Menu i.e. Setting, Curve, DT, RST DT. You can set LEDs & output Relays for the indication of Earth fault Current elements. We can set the all the Parameters for the directional over current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT, Directional angle, Polarization We can set the all the Parameters for the Instantaneous directional over current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT You can set LEDs & output Relays for the indication of Directional over current elements. We can set the all the Parameters for the directional Earth fault Current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT, Directional angle, Polarization We can set the all the Parameters for the Instantaneous directional Earth fault current element by this Menu i.e. Setting, TMS, Curve, DT, RST DT You can set LEDs & output Relays for the indication of Directional over current elements.

CROMPTON GREAVES LIMITED

Description of Parameters

No. of Parameters in Submenus

Main Menu

Submenus

PAGE

13

3U> OV settings

3U>> OV Settings OV LED & S/W BI Settings for the Over Voltage element 3U> UV settings

We can set the all the Parameters for the Over voltage element by this Menu i.e. Setting, TMS, Curve, DT, RST DT. We can set the all the Parameters for the Instantaneous Over Voltage current element by this Menu i.e. Setting, Curve, DT, RST DT. You can set LEDs & output Relays for the indication of Over Voltage elements. We can set the all the Parameters for the under voltage element by this Menu i.e. Setting, TMS, Curve, DT, RST DT. We can set the all the Parameters for the Instantaneous under Voltage element by this Menu i.e. Setting, Curve, DT, RST DT. You can set LEDs & output Relays for the indication of Over Voltage elements. We can set the all the Parameters for the NDR element by this Menu i.e. Setting, Curve, DT, RST DT. You can set LEDs & output Relays for the indication of NDR element.

3U>> UV Settings UV LED & S/W BI Settings for the under Voltage element NDR Settings NDR LED & S/W BI Settings for the NDR element

CROMPTON GREAVES LIMITED

Description of Parameters

No. of Parameters in Submenus

Main Menu

Submenus

PAGE

14

Broken conductor Settings BR.C LED & S/W BI Settings for the Broken conductor element Inrush Current Settings for the 2nd & 5th Harmonic Blocking CT Supervision Settings LED & S/W BI Settings for the CTSV element VT Supervision Settings LED & S/W BI Settings for the VTFF element Negative phase sequence over current Settings LED & S/W BI Settings for the I2> element Communication Settings

No. of Parameters in Submenus

11

INRUSH

5 2 5 2 6

CTSV

VTFF

I2>

COMM

BI-O

BI-BO Settings

We can set the all the Parameters for the Broken element by this Menu i.e. Setting, DT, RST DT. You can set LEDs & output Relays for the indication of Broken conductor element. This setting allows the user to set the parameters to block 2nd & 5th Harmonic blocking This setting allows the user to set CT Supervision parameters settings You can set LEDs & output Relays for the indication of CTSV element. This setting allows the user to set VT Supervision parameters settings You can set LEDs & output Relays for the indication of VTFF element. We can set the all the Parameters for the I2> element by this Menu i.e. Setting, Curve, DT, RST DT You can set LEDs & output Relays for the indication of I2> element. This menu allows the user to set type of Protocol ,Baud rate, Parity, Relay address, Period, Scaling etc. This Menu allows the user to set the External BIs, LED, Output Relays Configuration, Out puts Operation, Binary Input action on the Protection parameters. For the complete description refer section 3.20

CROMPTON GREAVES LIMITED

Description of Parameters

Main Menu

Submenus

PAGE

15

3. RELAY SETTINGS:
The Relay has different setting windows as shown in figures below. The Relay Setup is password protected for changing any parameter. The purpose of password is to prevent accidental change of configurations, parameters or settings. The password for entering Relay configuration setting window is 0002.

3.1. DEVICE INFO VIEW:


As you POWER ON the relay INFORMATION window will appear on the screen. It will give the information about the Relays Type, Version, Model number & Serial number. Below figure 3.1-1 gives the complete idea about this menu.

Figure 3.1-1. Device info view

3.2. PASSWORD ACCESSING


The navigation described below is to set the password for changing the relay configuration as shown in figure 3.2-1.

Figure 3.2-1. Password Accessing

Enter the password needed for the desired level: the password contains four digits. The digits are entered from left to right one by one by first moving to the position of the digit using the RIGHT key and then setting the desired digit value using the UP key & to save the password push the ENTER key. Please note that the relay password is 0002.

CROMPTON GREAVES LIMITED

PAGE

16

3.3. ERROR STATUS VIEW


This window is used to determine the type of internal error generated in the relay. The errors can be Calibration Error, Memory Error, Protection function or Monitoring function related error. Whenever the relay encounters a particular type of error, the ERROR LED glows, and the corresponding status Ok/Not Ok value is indicated in error window To navigate the Error window follow procedure described below in figure 3.3-1.

Figure 3.3-1. Error Status View

CROMPTON GREAVES LIMITED

PAGE

17

3.4. MEASUREMENT VIEW


This menu displays measured values of system Primary, Secondary voltages and currents, Line to Neutral, Line to Line voltages, Sequence components of currents & voltages along with Date and Time. It also displays Phase wise power parameters of KW, KVAR, KVA, Power factor and system frequency.

Figure 3.4-1.Measurement View

CROMPTON GREAVES LIMITED

PAGE

18

The Last window in the measurement menu displays vector representation of 3 phase system Voltages and Currents along with residual voltage & current as shown in below figure 3.4-2.

IL3 IL1

UL3 UL1

IL2

UL2

Figure 3.4-2. Graphical representation of 3 Phase System

If you left the measurement window idle for 5 sec you can observe the larger view than the default one as shown in the figure 3.4-3.

Figure 3.4-3. Zoom view of measurement window

CROMPTON GREAVES LIMITED

PAGE

19

3.5. HARMONICS VIEW (HRMN)


This menu indicates the 1st to 15th harmonics in the bar graph manner to understand the system conditions by phase wise for the both currents and voltages along with the THD % (Total harmonic Distortion). Harmonics: IL1 THD = 7.020 % 5.000 I

11

13

15

Freq
Figure 3.5-1. Example of harmonic view

CROMPTON GREAVES LIMITED

PAGE

20

3.6. CONFIGURATION (CONF)


Configuration Menu allows the user to set the System parameters like CT, VT Primary, Secondary ratios, system frequency and the setting group for the protection parameters.

Figure 3.6-1. Configuration Settings

Permissible Values: CT PRIM: 020A - 2000A (In steps of 1A) CT SEC: 1A/5A VT PRIM: 3.3kV, 6.6kV, 11.00kV, 17.50kV, 22.00kV, 33.00kV VT SEC: 100V 120V (In steps of 1V) SYS FRQ: 50Hz/60Hz SETTING GROUP: 1, 2, 3, 4

CROMPTON GREAVES LIMITED

PAGE

21

3.7. NON DIRECTIONAL OVER CURRENT PROTECTION (51) (OC):


Over current protection is used against the short circuit faults and the heavy over loads. This protection measures the fundamental frequency components of the phase currents. The protection is sensitive for the highest of the three phase currents. Whenever this value exceeds the user pick up setting of a particular stage, that stage starts picking up and Alarm signal is generated. If the fault situation persists for longer than the estimated trip time configured in the relay, a trip signal is issued. Breaker failure Protection (50BF): After protection function generates a trip command, it is expected that the circuit breaker opens and/or the fault current drops below the pre-defined normal level. If not, then additional trip command will be generated for all back up circuit breakers to clear the fault.

3.7.1. IDMT SETTINGS:


Three phase time over current protection includes definite time and IDMT characteristics as per IEC and IEEE standards. Permissible Values: 3I> PROT: Enable/Disable 3I>SET: 5% -400% (In steps of 1%) 3I>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE SI3 RI, RD 3I>TMS: IEC Curves: 0.02 - 2(In steps of 0.01) IEEE, RI & RD: 1.000-100.0 (In steps of 0.1) 3I>RST DT: 0.10S 50.0S (In steps of 100ms) 3I>DT: INST & 0.100S-600.0S (In steps of 100ms)

3.7.2. HIGHSET SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristic of variable time operation with respect to the fault current. Permissible Values: 3I>>PROT: Enable/Disable 3I>>SET: 50% -4000% (In steps of 1%) 3I>>DT: INST & 0.100S-600.0S (In steps of 100ms) 3I>>RST DT: 0.10S 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

22

CROMPTON GREAVES LIMITED 8 9


10 11

Figure 3.7-1. Non Directional Over Current Settings

PAGE

23

3.8. NON DIRECTIONAL EARTH FAULT PROTECTION (51N) (EF):


The Non directional earth fault function is sensitive to the fundamental frequency component of the residual current 3I0. Whenever this value exceeds the user pick up setting of a particular stage, that stage starts picking up and Alarm signal is generated. If the fault situation persists for longer than the estimated trip time configured in the relay, a trip signal is issued.

10

Figure 3.8-1. Non Directional Earth Fault Settings

3.8.1. IDMT SETTINGS


Three phase time over current protection includes definite time and IDMT characteristics as per IEC and IEEE standards. Permissible Values: Io> PROT: Enable/Disable Io>SET: 5% -400% (In steps of 1%) Io>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE SI3 RI, RD Io>TMS: IEC Curves: 0.02 - 2(In steps of 0.01) IEEE, RI & RD: 1.000-100.0 (In steps of 0.1) Io>RST DT: 0.10S 50.0S (In steps of 100ms) Io>DT: INST & 0.100S-600.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

24

3.8.2. HIGHSET SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristics of variable time operation with respect to the fault current. Permissible Values: Io>>PROT: Enable/Disable Io>>SET: 50% -4000% (In steps of 1%) Io>>DT: INST & 0.100S-600.0S (In steps of 100ms) Io>>RST DT: 0.10S 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

25

3.9. DIRECTIONAL OVER CURRENT PROTECTION (67) (D-OC):


If the fault current can flow in both directions through a relay location, it is necessary to add directionality to over current relays to obtain the exact fault finding. For example parallel feeders and Ring main systems. In order to give directionality to over current element there should be a suitable reference or Polarization angle. System voltages should be taken as a reference because under fault conditions also there is no change in the Reference angle. Under system fault conditions fault current vector will generally lags its nominal phase voltage by an angle. To achieve the maximum sensitivity for the currents directional element should be act in required region; this can be achieved by directional angle of the relay. The stages are sensitive to the amplitude of the highest fundamental frequency current of the three measured phase currents.

3.9.1. IDMT SETTINGS


Three phase time over current protection includes definite time and IDMT characteristics as per IEC and IEEE standards. Permissible Values: 3I> PROT: Enable/Disable 3I>SET: 005% -400% (In steps of 1%) 3I>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE SI3 RI, RD 3I>TMS: IEC Curves: 0.02 - 2(In steps of 0.01) IEEE RI & RD: 1.000-100.0 (In steps of 0.1) RST DT: 0.10S 50.0S (In steps of 100ms) 3I>DT: INST & 0.100S-600.0S (In steps of 100ms)

3.9.2. HIGHSET SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristics of variable time operation with respect to the fault current. Permissible Values: 3I>>PROT: Enable/Disable 3I>>SET: 050% -4000% (In steps of 1%) 3I>>DT: INST & 0.100S-600.0S (In steps of 100ms) RST DT: 0.10S 50.0S (In steps of 100ms)

3.9.3. DIRECTIONAL SETTINGS


Permissible Values: DIR ANG: 180 to -180 (In steps of 1) Polarization TYPE: PH-N, PH-PH, CROSS

CROMPTON GREAVES LIMITED

PAGE

26

POLARIZATION : PH-N Operating region is forward IL1: Va FWD IL2: Vb FWD IL3: Vc FWD Operating region is Reverse IL1: Va REV IL2: Vb REV IL3: Vc REV

In the PH-N polarization we can assign the reference parameters as per our requirement w.r.t phase wise currents. e.g. IL1: Va FWD can be set as IL1: Vb FWD or IL1: Vc FWD POLARIZATION : PH-PH Operating region is forward IL1: Vab FWD IL2: Vbc FWD IL3: Vca FWD Operating region is Reverse IL1: Vab REV IL2: Vbc REV IL3: Vca REV

In the PH-PH polarization we can assign the reference parameters as per our requirement w.r.t phase wise currents. e.g. IL1: Vab REV can be set as IL1: Vbc REV or IL1: Vca REV POLARIZATION: CROSS Operating region is forward IL1: Vbc FWD IL2: Vca FWD IL3: Vab FWD Operating region is Reverse IL1: Vbc REV IL2: Vca REV IL3: Vab REV

In the case of CROSS Polarization we can change only operating regions for the directional element. e.g. IL1: Vbc FWD can be set as IL1: Vbc REV only.

CROMPTON GREAVES LIMITED

PAGE

27

CROMPTON GREAVES LIMITED


10 11 12

Figure 3.9-1. Directional Over Current Settings

PAGE

28

3.10.

DIRECTIONAL EARTH FAULT PROTECTION (67N) (DEF):

The directional earth fault elements are available with independently settable two stages. In the case of Earth fault directional elements are internally polarized by Zero sequence voltage (Uo), Neutral voltage (ULo) and also Reactive and capacitive components which are useful in the case of Compensated networks & Un-earthed networks. Whenever the size of current and reference parameter and the phase angle between them fulfils the pickup Criteria, that stage starts picking up and Alarm signal is generated. If the fault situation persists for longer than the estimated trip time configured in the relay, a trip signal is issued.

3.10.1. IDMT SETTINGS


Permissible Values: Io> PROT: Enable/Disable Io>SET: 005% -400% (In steps of 1%) Io>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE SI3 RI, RD Io>TMS: IEC Curves: 0.02 - 2(In steps of 0.01) IEEE RI & RD: 1.000-100.0 (In steps of 0.1) RST DT: 0.10S 50.0S (In steps of 100ms) Io>DT: INST & 0.100S-600.0S (In steps of 100ms)

3.10.2. HIGHEST SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristics of variable time operation with respect to the fault current. Permissible Values: Io>>PROT: Enable/Disable Io>>SET: 050% -2000% (In steps of 1%) Io>>DT: INST & 0.100S-600.0S (In steps of 100ms) Io>>RST DT: 0.10S 50.0S (In steps of 100ms)

3.10.3. DIRECTIONAL SETTINGS


Permissible Values: Io DIR ANG: 180 to -180 (In steps of 1) Io Pol TYPE: Vn-In, Vo-Io, I Sin , Icos F/R Dir: FWD,REV

CROMPTON GREAVES LIMITED

PAGE

29

CROMPTON GREAVES LIMITED 9 9 9

Figure 3.10-1. Directional Earth Fault Settings

PAGE

30

3.11.

OVER VOLTAGE PROTECTION (59) (OV):

Over Voltage conditions generally related to loss of load conditions. Under load shedding conditions, supply voltage will increase in the magnitude. This situation would normally rectify by the voltage regulating equipments such as AVRs or On Load Tap changers. However failure of this equipments to bring back the system to normal condition, this would create over voltage which should be identified with the Over voltage protection element otherwise system insulation life will decrease.

10

11

12

13

Figure 3.11-1. Over Voltage Protection Settings

3.11.1. IDMT SETTINGS:


The IDMT Stage of AEGIS Feeder Protection Relay consists of variable Characteristics i.e. Curve1, Curve2, Curve3, Curve4 and DT for the Relay operation Permissible Values: 3U> PROT: Enable/Disable 3U>SET: 105% -170% (In steps of 1%) 3U>Curve: Curve1, Curve2, Curve3, Curve4 and DT 3U>TMS: 0.02 - 2(In steps of 0.01) 3U>RST DT: 0.10S 50.0S (In steps of 100ms) 3U>DT: INST & 0.100S-600.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

31

3.11.2. HIGHSET SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristics of variable time operation with respect to the fault voltage. Permissible Values: 3U>>PROT: Enable/Disable 3U>>SET: 150% -200% (In steps of 1%) 3U>DT: INST & 0.100S-600.0S (In steps of 100ms) 3U>RST DT: 0.10S 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

32

3.12.

UNDER VOLTAGE PROTECTION (27) (UV):

Voltage regulating equipments such as AVRs and On Load Tap changers should take action in maintaining the healthy voltage in the system. If those voltage regulating equipments are unsuccessful to bring back the system to healthy condition, then tripping signal will be issued by the under voltage element with assigned delay. The proportion by which voltage decreases depends on the type of fault and location of the relay with respect to the fault point. Even dead bus setting can also be configured through the NV PROT element.

11

12

13

14

Figure 3.12-1. Under Voltage Protection Settings

3.12.1. IDMT SETTINGS:


The IDMT Stage of AEGIS Feeder Protection Relay consists of variable Characteristics i.e. Curve1, Curve2, Curve3, Curve4 and DT for the Relay operation Permissible Values: 3U< PROT: Enable/Disable 3U<SET: 45% -90% (In steps of 1%) 3U<Curve: Curve1, Curve2 and DT 3U<TMS: 0.02 2.00 (In steps of 0.01) NV PROT: Enable/Disable
CROMPTON GREAVES LIMITED

PAGE

33

NV VOLT: 003% 020% (In steps of 1%) 3U<RST DT: 0.10S 50.0S (In steps of 100ms) 3U<DT: INST & 0.100S-600.0S (In steps of 100ms)

3.12.2. HIGHSET SETTINGS


The Highset Stage of AEGIS Feeder Protection Relay having DT Characteristics of variable time operation with respect to the fault voltage. Permissible Values: 3U<<PROT: Enable/Disable 3U<<SET: 25% -50% (In steps of 1%) 3U<<DT: INST & 0.100S-600.0S (In steps of 100ms) 3U<<RST DT: 0.10S 50.0S (In steps of 100ms) NV PROT: Enable/Disable NO Volt: 003% - 020%

CROMPTON GREAVES LIMITED

PAGE

34

3.13.

NDR PROTECTION (59N) (NDR):

On a healthy three phase power system, the addition of the each of the three phases to earth voltages is zero nominally, as these results from the vector addition of the three balanced vectors displaced by 120.When an earth fault occurs this balance will be disturbed and residual voltage is produced. This can be measured by Residual voltage measuring element .This condition causes a rise in the neutral voltage with respect to earth, which is commonly referred to as a Neutral Voltage Displacement Voltage Setting applied to the protection elements is dependent on the magnitude of the residual voltage that is expected to occur during the fault conditions. There are two ways for calculating the neutral voltage displacement described below. 3VO: The zero sequence voltage is calculated internally from the phase voltages. OPEN DELTA: The zero sequence voltage is measured with open delta voltage.

12

13

14

Figure 3.13-1. NDR Protection Settings

AEGIS Feeder Protection Relay consists of variable Characteristics i.e.Curve1, Curve2, Curve3, Curve4 and DT for the Relay operation.

CROMPTON GREAVES LIMITED

PAGE

35

Permissible Values: PROT: Enable/Disable TYPE: OPEN DELTA/3VO SET: 005% -030% (In steps of 1%) CURVE: Curve1, Curve2, Curve3, Curve4 and DT TMS: 0.02 2.00 (In steps of 0.01) RST DT: 0.10S 50.0S (In steps of 100ms) DT: INST & 0.100S-600.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

36

3.14.

BROKEN CONDUCTOR PROTECTION (46BC):

The most of the faults in the power system are shunt type of faults, due to this kind of faults there is appreciable amount of current will increase and are easily detectable in most applications. Another type of unbalanced system condition is the series or open circuit fault .This fault can arise from broken conductor, mal operation of single phase switchgear, or the operation of fuses. Open circuit faults should not produce over current to sense, however they will produce unbalance components of currents (Negative sequence over current) which can be identified. But at light load conditions I2 may close to the full load steady state unbalance arising from CT errors, load unbalance etc. By taking the ratio of I2/I1, we can achieve the better efficiency because ratio is constant with the variations of load current.

13

14

15

Figure 3.14-1. Broken Conductor Protection Settings

The Broken conductor Stage of AEGIS Feeder Protection Relay consists of definite time Characteristics for the Relay operation Permissible Values: BC PROT: Enable/Disable BC SET: 020% - 100% (In steps of 1%) BC DT: INST & 0.100S - 600.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

37

BC RST DT: 0.10S - 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

38

3.15.

COLD LOAD PICK-UP & INRUSH CURRENT PROTECTION (68)

Cold load pick-up A situation is regarded as cold load when all the three phase currents have been less than a given idle value and then at least one of the currents exceeds a given pick-up level within 80 ms. In such case the cold load detection signal is activated for a given time. Application for cold load detection Right after closing a circuit breaker a given amount of overload can be allowed for a given limited time to take care of concurrent thermostat controlled loads. Cold load pick-up function does this for example by selecting a more coarse setting group for over-current stage(s). It is also possible to use the cold load detection signal to block any set of protection Stages for a given time. Inrush current detection Inrush current detection is quite similar with the cold load detection but it does also include a condition for 2nd & 5th harmonic relative content of the currents. When all phase currents have been less than a given idle value and then at least one of them exceeds a given pick-up level within 80 ms and the ratio 2nd harmonic ratio to fundamental frequency, If2/If1, AND/OR the ratio 5th harmonic ratio to fundamental frequency, If5/If1 of at least one phase exceeds the given setting, the inrush detection signal is activated. By setting the parameter for If2/If1 & If5/If1 to zero, the inrush signal will behave equally with the cold load pick-up signal. Application for inrush current detection The inrush current of transformers usually exceeds the pick-up setting of sensitive overcurrent stages and contains a lot of even harmonics. Right after closing a circuit breaker the pickup and tripping of sensitive overcurrent stages can be avoided by selecting a more coarse setting group for the appropriate over-current stage with inrush detect signal.

CROMPTON GREAVES LIMITED

PAGE

39

14

15

16

Figure 3.15-1. Inrush Protection Settings

Permissible Values: 3I2f>PROT: Enable/Disable LOW SET: 005% - 100% (In steps of 1%) (It depends on the value of HIGH SET i.e. we cant set LOW SET above HIGH SET) HIGH SET: 005% - 100% (In steps of 1%) (It depends on the value of LOW SET i.e. we cant set HIGH SET below LOW SET) DT: INST & 0.10 1.00 (In steps of 100ms) If2/If1: 000% - 100% (In steps of 1%) If5/If1: 000% - 100% (In steps of 1%) If2 AND/OR If5 I>PROT: Enable/Disable I>>PROT: Enable/Disable I>PROT: Enable/Disable I>>PROT: Enable/Disable

CROMPTON GREAVES LIMITED

PAGE

40

3.16.

CT SUPERVISION (CTSV)(60CTS)

Current transformer supervision is provided to detect loss of phase CT signals and inhibit the operation of current dependent protection elements. The CT supervisor function measures phase currents. If one of the three phase currents drops below Imin< setting, while another phase current is exceeding the Imax> setting, the function will issue an alarm after the operation delay has elapsed.

15

16

17

Figure 3.16-1. CT Supervision Settings

Permissible Values: PROT: Enable/Disable Imax: 000% - 1000% (In steps of 1%) (It depends on the value of Imin i.e. we cant set Imax below Imin) Imin: 000% - 1000% (In steps of 1%) (It depends on the value of Imax i.e. we cant set Imin above Imax) DT: INST & 0.100S-600.0S (In steps of 100ms) RST DT: 0.10S 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

41

3.17.

VT FUSE FAILURE PROTECTION (VTFF):

Voltage transformer supervision is provided to detect loss of one, two or three VT signals, providing indication and inhibition of voltage dependent protection elements. The VT fuse failure supervision detects failures between the voltage measurement circuit and the Relay. The failures are detected by the delta voltage and delta current algorithm. Upon the detection of fuse failure supervision function based on the time of operation relay will operate. The VTFF function measures the three phase voltages and currents. The negative sequence voltage U2 and the negative sequence current I2 are calculated. If U2 exceed the U2> setting and at the same time, I2 is less than the I2< setting, the function will issue an alarm after the operation delay has elapsed. Logical diagram for the VT Fuse fail as represented in the below figure.

Figure 3.17-1. Logical Diagram for VTFF

CROMPTON GREAVES LIMITED

PAGE

42

16

18 17

Figure 3.17-2. VTFF Settings

Permissible Values: PROT: Enable/Disable I2< SET:005% - 200% (In steps of 1%) U2> SET: 001% - 170% (In steps of 1%) DT: INST & 0.100S-600.0S (In steps of 100ms) RST DT: 0.10S 50.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

43

3.18.

NEGATIVE PHASE SEQUENCE OVER CURRENT PROTECTION (I2>) (46)

Any unbalance fault condition will produce Negative phase sequence current of some magnitude. This could not be identified by the traditional phase over current as well as the residual over current protection techniques. This could be achieved by the Negative phase sequence over current protection element. Thus, a negative sequence element can operate for both Phase and earth faults. This kind of protection will give greater sensitivity compared over current and earth fault protection elements. Both definite time and inverse time characteristics are available.

17

18 19

Figure 3.18-1. Negative Phase sequence Overcurrent Settings

Permissible Values: I2> PROT: Enable/Disable SET: 001% - 050% (In steps of 1%) CURVE: DT,IEC SI1, IEC SI3, IEC VI, IEC EI, IEC LTI, IEEE SI3, IEEE EI, IEEE VI, CURVE1 & CURVE2 TMS: 0.02 2.00 (In steps of 0.01) K: 1.000 100.0 (In steps of 0.1) K1: 0.90 1.20 (In steps of 0.1)
CROMPTON GREAVES LIMITED

PAGE

44

RST DT: 0.10S 50.0S (In steps of 100ms) DT: INST & 0.100S-600.0S (In steps of 100ms)

CROMPTON GREAVES LIMITED

PAGE

45

3.19.

COMMUNICATION SETTINGS:

The rear port of the relay can be configured for various settings as listed below:

18

19

Figure 3.19-1. Communication Settings

Permissible Values: PROTOCOL: MODBUS, IEC 103, CG VIEW, IEC 61850 BAUDRATE: 2400, 4800, 9600, 19200, 38400, 57600 PARITY: NONE, EVEN, ODD RLY ADRS: 000-254 (In steps of 001) PERIOD: 000S 060S (In steps of 001) SCALING: 1.2X, 2.4X

CROMPTON GREAVES LIMITED

PAGE

46

3.20.

BINARY INPUT & BINARY OUTPUT SETTINGS:

Relay having multiple Binary inputs & Binary outputs. The configuration allows to program or assign any relay output for any fault Pick-up and trip condition. The relay outputs can be configured on Digital Inputs.

20

21

Figure 3.20-1. Binary Inputs & Outputs Settings

CROMPTON GREAVES LIMITED

PAGE

47

3.21.

FAULT RECORD (FL-R)

Aegis Feeder Protection Relay stores the latest 10 faults occurred in the system. Follow the below procedure to view the fault records.

13

14

15

Figure 3.21-1. Fault Records View


CROMPTON GREAVES LIMITED

PAGE

48

3.22.

FAULT RECORD OVERVIEW

Aegis Feeder Protection Relay stores the latest 10 faults occurred in the system. Follow the below procedure to view the fault records.

Fault Number Date & Time on which Fault Occurred


4

Fault Currents Fault Voltages Phase angle, Polarization type & Polarizing voltage for IL1 when fault occured Phase angle, Polarization type & Polarizing voltage for IL2 when fault occured Phase angle, Polarization type & Polarizing voltage for IL3 when fault occured Phase angle, Polarization type & for ILo when fault occured
6

Fault type

Figure 3.22-1. Fault Records Overview


CROMPTON GREAVES LIMITED

PAGE

49

3.23.

DISTURANCE RECORDER (DR)

The disturbance recorder can be used to record all the measured signals, that is, currents, voltages and the status information of digital inputs (DI) and digital outputs (DO) in oscillographic manner. The recorder can be triggered by any start or trip signal from any protection stage or by a digital input. The triggering signal is selected in the output matrix (vertical signal DR). The recording can also be triggered manually. All recordings are time stamped. The disturbance records can be down loaded & viewed in Aegis relay configuration software.

Figure 3.23-1. Disturbance Recorder

Permissible Values: DIST. REC: ENABLE/DISABLE PRE-FAULT: 000% - 100% (In steps of 1%) SAMPLE: 8/Cycle, 16/Cycle, 32/Cycle DR TRGR: YES/NO

CROMPTON GREAVES LIMITED

PAGE

50

4.
4.1. 4.1.1.

TECHNICAL DATA
CONNECTIONS
MEASURING CIRCUITARY 1A/5A (Configurable) 5% to 4000% of CT Secondary 2xIn (Continuously) 20xIn (for 3 seconds) <0.3VA@1A <0.5VA@5A Maximum wire dimensions: 6mm 63.5Vac (L-N) 5% to 200% of VT Secondary 2xUn (Continuously) <0.15VA@70VAC <0.3VA@120VAC Maximum wire dimensions: 2.5mm (12-28AWG) 50Hz/60Hz

Rated phase Current (In) - Current measuring range - Thermal withstand

- Burden

- Terminal Block Rated Voltage (Un) - Voltage measuring range - Voltage withstand - Burden

- Terminal Block Rated Frequency - Frequency measuring range

4.1.2.

AUXILIARY VOLTAGE 18-52VDC <10W Maximum wire dimensions: 2.5mm (12-28AWG) 75-250VDC <10W Maximum wire dimensions: 2.5mm (12-28AWG)

Rated Voltage Power Consumption Terminal Block

CROMPTON GREAVES LIMITED

PAGE

51

4.1.3.

BINARY INPUTS 4 Similar to the Auxiliary supply of relay Maximum wire dimensions: 2.5mm (12-28AWG)

Number of Inputs External Operating voltage Terminal Block

4.1.4.

BINARY OUTPUTS 8 Ag-Alloy + gold plating (standard) 8A@250VAC, 5A@30VDC 8A 250VAC, 30VDC 2000VA, 150W 10mA, 5VDC

Number of outputs Normal Contact Contact Material Rated Switching Current Rated Carry Current Max. Switching Voltage Max. Switching Capacity Min. Permissible Load Heavy Duty Trip Contact Contact Material Rated Switching Current Rated Carry Current Max. Switching Voltage Max. Switching Capacity Min. Permissible Load Terminal Block

Ag-Alloy 16A@250VAC, 16A@30VDC 16A 380VAC, 125VDC 4000VA, 480W 100mA, 5VDC Maximum wire dimensions: 2.5mm (12-28AWG)

4.1.5.

LOCAL SERIAL COMMUNICATION PORT 1 on front panel USB CG PROPERIETARY

Number of ports Electrical connection Protocol

4.1.6.

REMOTE CONTROL CONNECTIONS 2 RS-485 Ethernet 10 Base-T 2400 - 57600 2400 - 57600 Refer ordering information section 8

Number of ports Electrical connection Data transfer rate Protocol

CROMPTON GREAVES LIMITED

PAGE

52

4.2. 4.2.1.

TEST & ENVIROMENTAL CONDITIONS


TYPE TEST IEC 60255-22-4 (Edition-2008) IEC 60255-22-1 (2nd Edition-2005) IEC 60255-5 (2nd Edition-2000) IEC 60255-25 (1st Edition-2000) IEC 60255-22-3 (Edition-2007) IEC 60255-25 (1st Edition-2000) IEC 60255-22-6 (1st Edition-2001) IEC 60255-22-2 (3.0 Edition-2008) IEC 60255-22-5 (Edition 2008) IEC 61000-4-8 (Edition-2009) IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-2 IEC 60255-21-2 IEC 60529 Ed.2.1:2001

Electrical Fast Transient Test High Frequency Disturbance Test Impulse Voltage Test Radiated Emission Test Radiation Susceptibility Test Conducted Emission Test Conducted Susceptibility Test Electrostatic Discharge Test Surge Immunity Test Power Frequency Magnetic Field Test Vibration Endurance Test (Class1) Shock Response Test (Class1) Shock Withstand Test (Class1) Bump Test (Class 1) Seismic Test Ingress Protection Test IP:5X Test (Ingress of Dust for Enclosure CAT 2) IP:X4 Test (Splashing of Water for Enclosure) Insulation Resistance Test Dielectric Test Relay Characteristics,Performance & Accuracy Test Operating (pickup) Value & Reset (Dropout) Value Test Pick up Test for High Fault Operating characteristics Test (IDMT Timing Test) Rated Burden Test VA Burden for Auxiliary Power Supply VA Burden on Current Transformers VA Burden on Voltage Transformers Thermal Requirement Test Mechanical Endurance Test Contact Performance Test Making Capacity Test AC Resistive Load DC Resistive Load Breaking Capacity Test AC Resistive Load AC Inductive Load DC Resistive Load Short Time Capacity Test

IEC 60255-27:2005 Cl.10.5.3.3 IEC 60255-27:2005 Cl.10.5.3.2 IEC 60255-12:1980 IEC 60255-3:1989

IEC 60255-1:2009 Cl.6.10

IEC 60255-27:2005 Cl.No.7.2 IEC 60255-1:2009 Cl.6.11 IEC 60255-1:2009 Cl.6.11 IEC 60255-1:2009 Cl.6.11

IEC 60255-1:2009 Cl.6.11

IEC 60255-1:2009 Cl.6.11

CROMPTON GREAVES LIMITED

PAGE

53

AC Resistive Load DC Resistive Load Effect of Interruption to DC Auxiliary Energizing Quantity Alternating Component (Ripple) in DC Auxiliary Energizing Quanity Climatic/Environmental Test Damp Heat Cyclic Test Dry Heat Test Cold Test Damp Heat,Steady State Test Communication Protocol Conformance Test

IEC 60255-11:2008 IEC 60255-11:2008

IEC 60068-2-30 IEC 60068-2-2 IEC 60068-2-1 IEC 60068-2-78 IEC 61850

4.2.2.

CASING IP54 188.58 x 199.18 x 228.40 mm 0.8mm CRCA MS 750 gm

Degree of protection (IEC 60529) Dimensions (W x H x D) Material Weight

4.2.3.

PACKAGE 188.58 x 199.18 x 228.40 4.8 kg

Dimensions (W x H x D) Weight (Terminal, Package and Manual)

CROMPTON GREAVES LIMITED

PAGE

54

4.3. 4.3.1.

PROTECTION STAGES NON DIRECTIONAL CURRENT PROTECTION STAGE

NON DIRECTIONAL OVERCURRENT STAGE I> (50/51) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range IDMT Function : Delay Curve Family Curve Type Time Multiplier (TMS) Inaccuracy : Operating time at definite time function Operating time at IDMT function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 5% - 400% (DT), IEC, IEEE, RI & RD IEC SI1, IEC SI3, IEC EI, IEC VI, IEC LTI, IEEE EI, IEEE VI, IEEE SI3, RI, RD For IEC: 0.02-2 (step 0.01) For IEEE, RI & RD: 1-100 (step 0.1) 1% or 30 ms 5% or at least 30 ms

NON DIRECTIONAL OVERCURRENT STAGE I>> (50/51) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 50% - 4000% 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

55

NON DIRECTIONAL EARTH FAULT STAGE Io> (50N/51N) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range IDMT Function : Delay Curve Family Curve Type Time Multiplier (TMS) 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 5% - 400% (DT), IEC, IEEE, RI & RD IEC SI1, IEC SI3, IEC EI, IEC VI, IEC LTI, IEEE EI, IEEE VI, IEEE SI3, RI, RD For IEC: 0.02-2 (step 0.01) For IEEE, RI & RD: 1-100 (step 0.1) 1% or 30 ms 5% or at least 30 ms

Inaccuracy : Operating time at definite time function Operating time at IDMT function

NON DIRECTIONAL EARTH FAULT STAGE Io>> (50N/51N) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 50% - 2000% 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

56

NEGATIVE PHASE SEQUENCE OVERCURRENT PROTECTION STAGE I2> (46) Setting Range IDMT Function : Delay Curve Family Curve Type Time Multiplier (TMS) 1% - 50% (DT), IEC, IEEE IEC SI1, IEC SI3, IEC EI, IEC VI, IEC LTI, IEEE EI, IEEE VI, IEEE SI3, Curve1,Curve2 For IEC: 0.02-2 (step 0.01) For IEEE : 1-100 (step 0.1) For Curve1 & Curve2 : 1-50 (step 0.1) 0.90 - 1.20 (step 0.1) 5% or 30 ms 7.5% or 30 ms DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s)

Time Multiplier (K1) Inaccuracy : Operating time at Definite time function Operating time at IDMT function Definite Time Function Operating Time Reset DT Function Operating Time

4.3.2.

DIRECTIONAL CURRENT PROTECTION STAGE

DIRECTIONAL OVERCURRENT STAGE I> (67) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Base Angle Setting Range Operation Angle IDMT Function : Delay Curve Family Curve Type Time Multiplier (TMS) 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 5% - 400% -180 to +179 89 (DT), IEC, IEEE, RI & RD IEC SI1, IEC SI3, IEC EI, IEC VI, IEC LTI, IEEE EI, IEEE VI, IEEE SI3, RI, RD For IEC: 0.02-2 (step 0.01) For IEEE, RI & RD: 1-100 (step 0.1) 1% or 30 ms 5% or at least 30 ms 1

Inaccuracy : Operating time at definite time function Operating time at IDMT function Angle

CROMPTON GREAVES LIMITED

PAGE

57

DIRECTIONAL OVER CURRENT STAGE I>> (67) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 50% - 4000% 1% or 30 ms

DIRECTIONAL EARHT FAULT STAGE Io> (67N) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Base Angle Setting Range Operation Angle IDMT Function : Delay Curve Family Curve Type Time Mulitiplier (TMS) 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 5% - 400% -180 to +179 89 (DT), IEC, IEEE, RI & RD IEC SI1, IEC SI3, IEC EI, IEC VI, IEC LTI, IEEE EI, IEEE VI, IEEE SI3, RI, RD For IEC: 0.02-2 (step 0.01) For IEEE, RI & RD: 1-100 (step 0.1) 1% or 30 ms 5% or at least 30 ms 1

Inaccuracy : Operating time at definite time function Operating time at IDMT function Angle

DIRECTIONAL EARHT FAULT STAGE Io>> (67N) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 50% - 2000% 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

58

4.3.3.

VOLTAGE PROTECTION STAGE

OVER VOLTAGE PROTECTION STAGE 3U> (59) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range IDMT Function : Curve Type Time Mulitiplier (TMS) Inaccuracy : Operating time at definite time function Operating time at IDMT function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 105% - 170% Curve1, Curve2, Curve3, Curve4 0.02-2 (step 0.01) 1% or 30 ms 5% or at least 30 ms

OVER VOLTAGE PROTECTION STAGE 3U>> (59) Pick Up Current Drop out Current Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function 4% above Set Value 10% below Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 150% - 200% 1% or 30 ms

UNDER VOLTAGE PROTECTION STAGE 3U< (27) Pick Up Voltage Drop out Voltage Definite Time Function Operating Time Reset DT Function Operating Time Setting Range IDMT Function : Curve Type Time Multiplier (TMS) Inaccuracy : Operating time at definite time function Operating time at IDMT function 10% below Set Value 4% above Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 45% - 90% Curve1, Curve2 0.02-2 (step 0.01) 1% or 30 ms 5% or at least 30 ms

CROMPTON GREAVES LIMITED

PAGE

59

UNDER VOLTAGE PROTECTION STAGE 3U<< (27) Pick Up Voltage Drop out Voltage Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function NDR PROTECTION STAGE NDR (59N) Pick Up Voltage Drop out Voltage NDR Type Definite Time Function Operating Time Reset DT Function Operating Time Setting Range IDMT Function : Curve Type Time Multiplier (TMS) Inaccuracy : Operating time at definite time function Operating time at IDMT function 10% above Set Value 4% below Set Value 3Vo ; Open Delta DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 5% - 30% Curve1, Curve2, Curve3, Curve4 0.02-2 (step 0.01) 1% or 30 ms 5% or at least 30 ms 10% below Set Value 4% above Set Value DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 25% - 50% 1% or 30 ms

4.4.

CIRCUIT-BREAKER FAILURE PROTECTION

CIRCUIT BREAKER FAILURE PROTECTION (50BF) Definite Time Function Operating Time Inaccuracy : Operating time at definite time function DT 0 - 600s (step 0.1s) 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

60

4.5.

SUPPORTING FUNCTIONS

BROKEN CONDUCTOR PROTECTION STAGE I2/I1 (46BC) Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Inaccuracy : Operating time at definite time function INRUSH CURRENT DETECTION (68) Definite Time Function Operating Time Setting Range LOW SET HIGH SET If2/If1 If5/If1 Inaccuracy : Operating time at definite time function DISTURBANCE RECORDER (DR) Sample Rate Pre fault Triggering Rate Disturbance Trigger 8/Cycle, 16/Cycle, 32/Cycle 000% - 100% (step 1%) YES/NO DT 0 - 600s (step 0.1s) 005%-100% * *Depends upon HIGH SET 005%-100% * *Depends upon LOW SET 000% - 100% (step 1%) 000% - 100% (step 1%) 1% or 30 ms DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 20% - 100% 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

61

4.6.

TRANSFORMER SUPERVISION

CURRENT TRANSFORMER SUPERVISION (60CTS) Definite Time Function Operating Time Reset DT Function Operating Time Setting Range Imax Imin Inaccuracy : Operating time at definite time function DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 000% - 1000% (step 1%)* 000% - 1000% (step 1%)* 1% or 30 ms *Depends upon Imin *Depends upon Imax

VOLTAGE TRANSFORMER FUSE FAILURE (VTFF) Definite Time Function Operating Time Reset DT Function Operating Time Setting Range I2<SET U2>SET Inaccuracy : Operating time at definite time function DT 0 - 600s (step 0.1s) Reset DT 0 - 50s (step 0.1s) 005% - 200% (step 1%) 001% - 170% (step 1%) 1% or 30 ms

CROMPTON GREAVES LIMITED

PAGE

62

5.
5.1.

CONNECTIONS
REAR PANEL CONNECTIONS

Figure 5.1-1. Rear View of Feeder Protection Relay

TERMINAL DETAILS (X1)


X1

NO.
5 6 7 8 9 10 11 12

SYMBOL IL1 IL1 IL2 IL2 IL3 IL3 ILo ILo

DESCRIPTION Rph Current Input (1A/5A)

5 6 7 8 9 10 11 12

Yph Current Input (1A/5A)

Bph Current Input (1A/5A)

Eph Current Input (1A/5A)

CROMPTON GREAVES LIMITED

PAGE

63

CROMPTON GREAVES LIMITED

PAGE

64

TERMINAL DETAILS (X2)


X2

13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

NO. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

SYMBOL P (BO8) NO (BO8) P (BO7) NO (BO7) P (BO6) NO (BO6) P (BO5) NO (BO5) NC VT1 VT1 VT2 VT2 VT3 VT3 VT4 VT4 NC + NC EARTH

DESCRIPTION Binary Output Contact 8 Binary Output Contact 7 Binary Output Contact 6 Binary Output Contact 5 Not Connected Rph Voltage Input UL1 Yph Voltage Input UL2 Bph Voltage Input UL3 NDR Voltage Input ULo Not Connected Auxiliary DC Input Not Connected Earth

CROMPTON GREAVES LIMITED

PAGE

65

TERMINAL DETAILS (X3)


X3

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56

NO. 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56

SYMBOL P (BO1) NO (BO1) NC (BO1) P (BO2) NO (BO2) NC (BO2) P (BO3) NO (BO3) P (BO4) NO (BO4) + (BI1) - (BI1) + (BI2) - (BI2) + (BI3) - (BI3) + (BI4) - (BI4) NC A B GND

DESCRIPTION Binary Output Contact 1 (Heavy Duty) Binary Output Contact 2 (Heavy Duty) Binary Output Contact 3 Binary Output Contact 4 Binary Input 1 Binary Input 2 Binary Input 3 Binary input 4 Not Connected RS-485 Port

CROMPTON GREAVES LIMITED

PAGE

66

5.2. WIRING DIAGRAM (AE001)

Figure 5.2-1. Wiring Diagram for Feeder Protection Relay (AE001)

CROMPTON GREAVES LIMITED

PAGE

67

6. DIMENSIONS

Figure 6-1. Dimensions

CROMPTON GREAVES LIMITED

PAGE

68

7. CURVES
7.1. STANDARD IDMT CHARACTERISTICS OF OVER CURRENT
Relay Characteristics IEC SI3 (Standard Inverse 3) IEC SI1 (Standard Inverse 1) IEC VI (Very Inverse) IEC EI (Extremely Inverse) IEC LTI (Long Time Inverse) IEEE VI (Very Inverse) IEEE EI (Extremely Inverse) IEEE SI3 (Standard Inverse) Equation (IEC /IEEE)

RI

RD

CROMPTON GREAVES LIMITED

PAGE

69

Various characteristics IEC Curves for the Over Current protection as shown in below figure:

IEC - Very Inverse-time characteristic

IEC- Standard Inverse-time characteristic

Figure 7.1-1.IEC VI & SI Curves Characteristics

CROMPTON GREAVES LIMITED

PAGE

70

IEC - Extremely Inverse-time characteristic

IEC - Long Time Inverse-time characteristic

Figure 7.1-2.IEC EI & LTI Curves Characteristics

CROMPTON GREAVES LIMITED

PAGE

71

Various characteristics IEEE Curves for the Over Current protection as shown in below figure:

IEEE - Extremely Inverse-time characteristic

IEEE - Very Inverse-time characteristic

Figure 7.1-3.IEEE EI & VI Curves Characteristics

CROMPTON GREAVES LIMITED

PAGE

72

IEEE Standard Inverse-time characteristic Figure 7.1-4.IEEE SI Curve Characteristics

CROMPTON GREAVES LIMITED

PAGE

73

Various characteristics RI & RD Curves for the Over Current protection as shown in below figure:

RI-type characteristic

RD-type characteristic

Figure 7.1-5.RI & RD Curves Characteristics

CROMPTON GREAVES LIMITED

PAGE

74

7.2. STANDARD CHARACTERISTIC FOR OVERVOLTAGE & NDR


Relay Characteristics Curve 1 Equation

Curve 2

Curve 3

Curve 4

7.3. STANDARD CHARACTERISTIC FOR UNDERVOLTAGE

Characteristic Curve 1

Equation

Curve 2

7.4. STANDARD CHARACTERISTIC FOR NEGATIVE PHASE SEQUENCE


OVERCURRENT (I2>) Relay Characteristics Curve 1 Equation

Curve 2

CROMPTON GREAVES LIMITED

PAGE

75

8. ORDERING INFORMATION
AEGIS PROTECTION FUNCTION
Three Phase O/C & E/F (50/51/50N/51N) Three Phase Directional O/C & E/F (67/67N) Three Phase O/V, U/V & NDR (27,59,59N) Negative Phase Sequence (46) Cold load Pick up & Inrush CBFP (50BF) , Broken Conductor (46BC) VTFF (97) & CT Supervision (60CTS) Model A+ Following functions=Model B Reverse Power (32) Loss of Excitation (40) Voltage Controlled Over Current (51V) Energy KWH,KVAH,KVARH Auto Reclose (79)

COMMUNICATION
IEC 60870-5-103 on RS-485 MODBUS RTU on RS-485 IEC 60870-5-103 on Fiber Optic DNP3 on RS485 Modbus TCP/IP on Ethernet RJ45 IEC61850 on Ethernet RJ45 IEC61850 on Fiber optic IEC61850 ON RJ45 + IEC103 on RS485 IEC61850 ON Fiber Optic + IEC103 on Fiber Optic 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2

DIGITAL INPUTS & DIGITAL OUTPUTS


4DI + 8DO 8DI + 12DO 10DI + 10DO 12DI + 8DO 4DI + 16DO Reserved Reserved Reserved Reserved

AUXILIARY POWER SUPPLY


18-52VDC 75-250VDC

CROMPTON GREAVES LIMITED

PAGE

76

9. CUSTOMER SETTINGS
MODEL NO: SERIAL NO: CONFIGURATION SETTINGS: (CONF) PARAMETER CT PRIM : CT SEC : VT PRIM : VT SEC : SYS FRQ : SETTING GROUP : NON DIRECTIONAL OC IDMT SETTINGS: 3I> PARAMETER 3I> PROT : 3I>SET : 3I>Curve : 3I>TMS : 3I>RST DT : 3I>DT : NON DIRECTIONAL OC HIGHSET SETTINGS: 3I>> PARAMETER 3I>>PROT: 3I>>SET : 3I>>DT : 3I>>RST DT : CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

77

NON DIRECTIONAL EF IDMT SETTINGS: Io> PARAMETER Io> PROT : Io>SET : Io>Curve : Io>TMS : Io>RST DT : Io>DT : NON DIRECTIONAL EF HIGHSET SETTINGS: Io>> PARAMETER Io>>PROT: Io>>SET : Io>>DT : Io>>RST DT : DIRECTIONAL OC IDMT SETTINGS: 3I> PARAMETER 3I> PROT : 3I>SET : 3I>Curve : 3I>TMS : RST DT : 3I>DT : DIRECTIONAL OC HIGHSET SETTINGS: 3I>> PARAMETER 3I>>PROT: 3I>>SET : 3I>>DT : RSTDT : CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

78

DIRECTIONAL SETTINGS (POLARIZATION): PARAMETER DIR ANG : Pol Type : IL1 : IL2 : IL3 : DIRECTIONAL EF IDMT SETTINGS: Io> PARAMETER Io> PROT : Io>SET : Io>Curve : Io>TMS : Io>RST DT : Io>DT : DIRECTIONAL EF HIGHSET SETTINGS: Io>> PARAMETER Io>>PROT: Io>>SET : Io>>DT : Io>>RST DT : DIRECTIONAL SETTINGS (POLARIZATION): PARAMETER Io DIR ANG : Io Pol Type : F/R DIR : CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

79

OV IDMT SETTINGS: 3U> PARAMETER 3U> PROT : 3U>SET : 3U>Curve : 3U>TMS : 3U>RST DT : 3U>DT : OV HIGHSET SETTINGS: 3U>> PARAMETER 3U>>PROT: 3U>>SET : 3U>>DT : 3U>>RST DT : UV IDMT SETTINGS: 3U< PARAMETER 3U< PROT : 3U<SET : 3U<Curve : 3U<TMS : NV PROT : NV VOLT : 3U<RST DT : 3U<DT : CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

80

UV HIGHSET SETTINGS: 3U<< PARAMETER 3U<<PROT: 3U<<SET : 3U<<DT : 3U<<RST DT : NV PROT : NV VOLT : NDR SETTINGS: NDR PARAMETER PROT: TYPE : SET : CURVE : TMS : RST DT : DT: BROKEN CONDUCTOR SETTINGS: (I2/I1>) PARAMETER BC PROT : SET : BC DT : BC RST DT: CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

81

INRUSH SETTINGS: (3I2f>) PARAMETER 3I2f>PROT: LOW SET : HIGH SET : DT : If2/If1 : If5/If1 : If2 AND/OR If5 : I>PROT : I>>PROT : I>PROT : I>>PROT : CT SUPERVISION SETTINGS: (CTSV) PARAMETER PROT : Imax : Imin : DT : RST DT : VT FUSE FAILURE SETTINGS: (VTFF) PARAMETER PROT : I2<SET : U2>SET : DT : RST DT : CUSTOMER SETTINGS CUSTOMER SETTINGS CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

82

NEGATIVE PHASE SEQUENCE OC PROTECTION SETTINGS: (I2>) PARAMETER I2>PROT : SET : CURVE : TMS : K1 : RST DT : DT : CUSTOMER SETTINGS

COMMUNICATION SETTINGS: (COMM) PARAMETER PROTOCOL : BAUDRATE : PARITY : RLY ADRS : PERIOD : SCALING : CUSTOMER SETTINGS

CROMPTON GREAVES LIMITED

PAGE

83

10. NOTES

CROMPTON GREAVES LIMITED

PAGE

84

Crompton Greaves Ltd.


Power Systems: M. V. Switchgear Division (S2) A-3, MIDC, Ambad, Nasik - 422010. India. Tel.: +91 253 2382271 to 75 Email: mv.switchgear@cgglobal.com Registered Office CG House, 6th Floor, Dr.Annie Besant Road, Worli, Mumbai-400 030 Visit us at: www.cgglobal.com Doc. No. : AEGIS-F-A-00

CROMPTON GREAVES LIMITED

PAGE

CROMPTON GREAVES LIMITED

PAGE