Вы находитесь на странице: 1из 8

Reference Fire Protection Systems Information Release Date

FM 4.32 Rev 0 January 2005

H60 Steel Bulkhead


Fire towards EITHER side
Profile Wrap System
Accompanies Method Statement FM-MS 01 PW

Product Application Requirements

FireMaster 607 Blanket 76mm of 128 kg/m Blanket applied in two layers on the bulkhead plate each of 38mm. 50mm of 128 kg/m Blanket is applied over the stiffeners in two layers of 25mm. CD welded pins 3mm diameter 90mm long on main bulkhead plate and 70mm on stiffeners. 9.7 kg/m (applied to flat area) FM CAD04-4.32 Lloyds Register

Anchoring

Weight System Drawing Reference System Features Certification

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Drawing FMCAD04-4.32 H60 Steel Bulkhead Fire Towards EITHER Side


Firemaster Blanket 38 mm x 128 kg/m

Plan View of Anchor Pattern

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

Fire Protection Systems Information

Detail 'A'
Firemaster Blanket 25 mm x 128 kg/m

50 mm from edge

Detail 'A'
330 mm 330 mm

Joint

Reference

Release Date

200 mm

50 mm from edge

Typically 300 mm

100 mm

FM4.32 Rev 0

January 2005

Chicken mesh

Fire EITHER side Fire EITHER side

www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684

Reference Fire Protection Systems Information Release Date

FM 4.33 Rev 0 January 2005

H60 Steel Bulkhead


Fire towards EITHER side
Profile Wrap System
Accompanies Method Statement FM-MS 01 PW

Product Application Requirements

FireMaster 607 Blanket 100mm of 96 kg/m Blanket applied in two layers of 50mm thickness on the bulkhead plate and over the stiffeners. Lining can be compressed to 88mm on installation. CD welded pins 3mm diameter 100mm long minimum for 88mm lining or 120mm for 100mm thick lining. 9.6 kg/m (applied to flat area) FM CAD05-4.33 Fire tested on 4mm thick bulkhead plate. Lining can be compressed to 88mm on installation to save space without invalidating the Type Approval. Good thermal and acoustic insulation with minimal weight contribution. DNV

Anchoring

Weight System Drawing Reference System Features

Certification

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Reference Fire Protection Systems Information Release Date

FM4.33 Rev 0 January 2005

Drawing FMCAD05-04.33 H60 Steel Bulkhead Fire Towards EITHER Side


240mm 240mm 100mm

Blanket width 610 compressed to 580mm

100

Detail 'A'

Chicken mesh covering to blanket

350mm max

FireMaster 607 Blanket 50mm x 96 kg/m

Fire EITHER side

Detail 'A'
Chickken Wire Mesh FireMaster 607 Blanket 50mm x 96 kg/m packed into stiffener

Anchor 50mm from blanket edge

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Reference Fire Protection Systems Information Release Date

FM 4.34 Rev 0 January 2005

H60 Steel Deck


Profile Wrap System
Accompanies Method Statement FM-MS 01 PW

Product Application Requirements

FireMaster 607 Blanket 50mm of 128 kg/m Blanket applied in two 25mm thick layers over deck plate and stiffeners. CD welded pins 3mm diameter 70mm long. 6.4 kg/m (applied to flat area) FM CAD04-4.34 No packing of stiffener web No anchors required on stiffeners No chicken mesh required Can also be used on bulkheads when fire risk is towards the INSULATED SIDE only Lloyds Register

Anchoring Weight System Drawing Reference System Features

Certification

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Reference Fire Protection Systems Information Release Date

FM4.34 Rev 0 January 2005

Drawing FMCAD04-4.34 H60 Steel Deck


Detail 'A'
50 mm from blanket edge 50 mm from blanket edge

Joint

50 mm x 128 kg/m3 Firemaster Blanket

100 mm

Stiffener Detail 'A'

240 mm

240 mm

100 mm

Plan View of Anchor Pattern

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

Blanket width 610 mm compressed to 580 mm


100 mm
phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Reference Fire Protection Systems Information Release Date

FM 4.35 Rev 0 January 2005

H60 Steel Deck


Profile Wrap System
Accompanies Method Statement FM-MS 01 PW

Product Application Requirements

FireMaster 607 Blanket 76mm of 96 kg/m Blanket applied in two 38mm thick layers over deck plate and stiffeners. CD welded pins 3mm diameter 90mm long. 7.3 kg/m (applied to flat area) FM CAD05-4.35 No packing of stiffener web No anchors required on stiffeners No chicken mesh required Good comfort insulation value with low weight contribution DNV

Anchoring Weight System Drawing Reference System Features

Certification

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk

Reference Fire Protection Systems Information Release Date

FM4.35 Rev 0 January 2005

Drawing FMCAD05-4.35 H60 Steel Deck


First Layer Second Layer

Anchor 50mm from blanket edge

38mm x 96 kg/m FireMaster 607 Blanket

350mm max
Second Layer Joint

100mm

First Layer joint is offset from Second layer joint

350mm max

Thermal Ceramics Europe Tebay Rd Bromborough Wirral. CH62 3PH England.

100mm

350mm max

phone: +44 (0) 151 334 4030 fax : +44 (0) 151 334 1684 www.thermalceramics.com www.thermal-ceramics-firemaster.co.uk