Академический Документы
Профессиональный Документы
Культура Документы
January, 2008
1. Wires applied either helically, as a braid or serving; or longitudinally with corrugations 2. Helically applied tape, not overlapped 3. Helically applied flat tape, overlapped 4. Corrugated tape, longitudinally applied 5. Tubular sheath
Meaning of Symbols:
A B b dis dm ds I w n L t M
= = = = = = = = = = = =
Effective cross-sectional area, shield or sheath Tape overlap (mils) (usually 375) Thickness of tape (mils) Diameter over semiconducting insulation shields (mils) Mean diameter of shield or sheath (mils) Diameter of wires (mils) Short circuit current (amperes) Width of tape (mils) Number of serving or braid wires or tapes Overlap of tape (percent) Short circuit duration (seconds) 0.058 for 5-15kV cables 0.060 for 25-46kV cables
SPEC F150
January, 2008
10
0.1
0.058 . A I = _______ t
A= Effective cross-sectional area (circular mils) t= Short circuit duration (seconds) I= Short circuit current (amperes) Temperature excursion range 100C200C
0.01
10
100
SPEC F150
January, 2008
10
0.1
0.060 . A I = _______ t
A= Effective cross-sectional area (circular mils) t= Short circuit duration (seconds) I= Short circuit current (amperes) Temperature excursion range 95C200C
0.01
10
100