Академический Документы
Профессиональный Документы
Культура Документы
2012
WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED KALYANI 132/33/11 KV SUB-STATION KALYANI TR. (O & M) SUB-DIVISION KALYANI, NADIA A REPORT ON KALYANI 132KV SUB-STATION & ITS INSTRUMENTS FOR MR. SIBASISH GHOSH ASSISTANT ENGINEER KALYANI TRANSMISSION (O & M) SUB-DIVISION WBSETCL BY STUDENT OF ELECTRICAL ENGINEERING JIS COLLEGE OF ENGINEERING
CONTENTS
SL. NO.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
TOPICS
PREFACE ACKNOWLEDGEMENT INTRODUCTION ELECTRIC SUBSTATION TRANSMISSION TOWER ELECTRICAL BUS SYSTEM CONDUCTORS INSULATORS CAPACITOR BANK BUS COUPLER CIRCUIT BREAKERS ARC IN CIRCUIT BREAKER LIGHTNING ARRESTORS TRANSFORMER INTRODUCTION OF INSULATING OIL BUCHHOLZ RELAY EARTHING TRANSFORMER CONTROL ROOM PLCC ELECTRICAL SWITCHGEAR ELECTRICAL PROTECTION RELAY BATTERY CONCLUSION BIBLIOGRAPHY
PAGE NO.
4 5 6 7-8 9-11 12-14 15 16-22 23 24 25-31 32-33 34 35-40 41-44 45-46 47-48 49 50 51 52 53 54 55
PREFACE
I have experienced vocational training in W.B.S.E.T.C.L. Kalyani sub-station from 25th June to 7th July, 2012. I am very grateful to all of the officers who gave warm reception & the valuable time for me. I have learnt many more things while doing training in sub-station which has helped me to enlarge my practical knowledge. By undergoing this training program I am able to relate my bookish knowledge with its practical application.
ACKNOWLEDGEMENT
Before going into the report, I would like to thank to the H.R.D. department of the W.B.S.E.T.C.L., Bidhyut Bhawan, Saltlake & Kalyani sub-station for providing me the opportunity to do the vocational training at their sub-station. I am highly thankful to Sri. Sibasish Ghosh (A.E.), Sri. Sadhan Ghosh (LNSS), Sri. Ashit Ghosh (A.E.) for their kind attention. I am also thankful to the other officers for sharing their valuable experiences & time with me during this training. In this training, I also got the opportunity to understand the status of export-import of in W.B.S.E.T.CL. & the overall view of the grid system. For this constant inspiration & active supervision from the very beginning of the training, I gratefully acknowledge their significant contribution to the successful completion of my training.
INTRODUCTION
Substation is a part of an electrical generation, transmission, & distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Electric power may flow through several substations between generating plant and consumer, and its voltage may change in several steps. Substations may be owned and operated by a transmission or generation electrical utility, or may be owned by a large industrial or commercial customer. Generally substations are un-attended, relying on SCADA for remote supervision and control. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. The word substation comes from the days before the distribution system became a grid. As central generation stations became larger, smaller generating plants were converted to distribution stations, receiving their energy supply from a larger plant instead of using their own generators. The first substations were connected to only one power station, where the generators were housed, and were subsidiaries of that power station.
ELECTRIC SUB-STATION
An Electric sub-station is an assembly of equipment in an electric power system through which electrical energy is passed for transmission, distribution, interconnection, transformation, conversion or switching.
TYPES OF SUB-STATION:
A. Transmission sub-station, B. Distribution sub-station, C. Collector sub-station,
A. Transmission sub-station:
transmission lines. The simplest case is where all transmission lines have the same voltage. In such cases, the substation contains high-voltage switches that allow lines to be connected or isolated for fault clearance or maintenance. A transmission station may have transformers to convert between two transmission voltages, voltage control/power factor correction devices such as capacitors, reactors or static VAr compensators and equipment such as phase shifting transformers to control power flow between two adjacent power systems.
transmission lines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is a number of feeders. Distribution voltages are typically medium voltage, between 2.4 kV and 33 kV depending on the size of the area served and the practices of the local utility.
TRANSMISSION TOWER
The main supporting unit of overhead transmission line is transmission tower. Transmission towers have to carry the heavy transmission conductor at a sufficient safe height from ground. In addition to that all towers have to sustain all kinds of natural calamities. So transmission tower designing is an important engineering job where all three basic engineering concepts, civil, mechanical and electrical engineering concepts are equally applicable. Main parts of a transmission tower. A power transmission tower consists of the following parts, 1) Peak of transmission tower 2) Cross Arm of transmission tower 3) Boom of transmission tower 4) Cage of transmission tower 5) Transmission Tower Body 6) Leg of transmission tower 7) Stub/Anchor Bolt and Base plate assembly of transmission tower.
The portion above the top cross arm is called peak of transmission tower. Generally earth shield wire connected to the tip of this peak. Cross Arm of transmission tower: Cross arms of transmission tower hold the transmission conductor. The dimension of cross arm depends on the level of transmission voltage, configuration and minimum forming angle for stress distribution. Cage of transmission tower: The portion between tower body and peak is known as cage of transmission tower. This portion of the tower holds the cross arms. Transmission Tower Body: The portion from bottom cross arms up to the ground level is called transmission tower body. This portion of the tower plays a vital role for maintaining required ground clearance of the bottom conductor of the transmission line.
Minimum permissible ground clearance(H1), Maximum sag of the conductors (H2), Vertical spacing between top & bottom conductors (H3), Vertical clearance between ground wire and top conductors (H4),
11
As per the force applied by the conductor on the cross arms, the transmission towers can be categorized in another way. Tangent Suspension tower and it is generally A - type tower. Angle tower or tension tower or sometime it is called section tower. All B, C and D types of transmission towers come under this category. Apart from the above customized type of tower, the tower is designed to meet special usages listed below, These are called special type tower River Crossing Tower Railway/ Highway Crossing tower Transposition tower Based on numbers of circuits carried by a transmission tower, transportation can be classified as Single Circuit tower Double Circuit tower Multi Circuit tower.
12
Some very commonly used bus bar arrangement are discussed below
13
Single Bus System with Bus Sectionalizer: Some advantages are realized if a single bus bar is sectionalized with circuit breaker. If there are more than one incoming and the incoming sources and outgoing feeders are evenly distributed on the sections as shown in the figure, interruption of system can be reduced to a good extent.
14
15
CONDUCTORS
TYPES OF CONDUCTORS:
For 400 kV transmission line MOOSE wire is used. For 132 kV transmission line PANTHER wire is used. The diameter is 3mm. For 220 kV transmission line DEER wire is used. The diameter is 3.45mm. For 220kV transmission line ZEBRA wire is used. The diameter is 3.15mm. For 66 kV transmission line DOG wire is used.
16
ELECTRICAL INSULATOR
Electrical Insulator must be used in electrical system to prevent unwanted flow of electric current to the earth from its supporting points. Example: Porcelain insulator, glass insulator, polymer insulator.
PORCELAIN INSULATOR:
Porcelain in most commonly used material for over head insulator in present days. The porcelain is aluminium silicate. The aluminium silicate is mixed with plastic kaolin, feldspar and quartz to obtain final hard and glazed porcelain insulator material. The surface of the insulator should be glazed enough so that water should not be traced on it. Porcelain also should be free from porosity since porosity is the main cause of deterioration of its dielectric property. It must also be free from any impurity and air bubble inside the material which may affect the insulator properties.
17
GLASS INSULATOR:
Nowadays glass insulator has become popular in transmission and distribution system. Annealed tough glass is used for insulating purpose. Glass insulator has numbers of advantages over conventional porcelain insulator. Advantages of glass insulator: It has very high dielectric strength compared to porcelain. Its resistivity is also very high. It has low coefficient of thermal expansion. It has higher tensile strength compared to porcelain insulator. As it is transparent in nature it is not heated up in sunlight as porcelain. The impurities and air bubble can be easily detected inside the glass insulator body because of its transparency.
18
POLYMER INSULATOR:
In a polymer insulator has two parts, one is glass fiber reinforced epoxy resin rod shaped core and other is silicone rubber or EPDM (Ethylene Propylene Diene Monomer) made weather sheds. Rod shaped core is covered by weather sheds. Weather sheds protect the insulator core from outside environment. As it is made of two parts, core and weather sheds, polymer insulator is also called composite insulator. The rod shaped core is fixed with Hop dip galvanized cast steel made end fittings in both sides. Advantages of polymer insulator: It is very light weight compared to porcelain and glass insulator. As the composite insulator is flexible the chance of breakage becomes minimum. Because of lighter in weight and smaller in size, this insulator has lower installation cost. It has higher tensile strength compared to porcelain insulator. Disadvantages of polymer insulator: Moisture may enter in the core if there is any unwanted gap between core and weather sheds. This may cause electrical failure of the insulator. Over crimping in end fittings may result to cracks in the core which leads to mechanical failure of polymer insulator.
Types of Insulator:
There are mainly three types of insulator used as overhead insulator likewise
19
PIN INSULATOR:
Pin Insulator is earliest developed overhead insulator, but still popularly used in power network up to 33KV system. Pin type insulator can be one part, two parts or three parts type, depending upon application voltage. In 11KV system we generally use one part type insulator where whole pin insulator is one piece of properly shaped porcelain or glass. As the leakage path of insulator is through its surface, it is desirable to increase the vertical length of the insulator surface area for lengthening leakage path. In order to obtain lengthy leakage path, one, two or more rain sheds or petticoats are provided on the insulator body. In addition to that rain shed or petticoats on an insulator serve another purpose. These rain sheds or petticoats are so designed, that during raining the outer surface of the rain shed becomes wet but the inner surface remains dry and non-conductive. So there will be discontinuations of conducting path through the wet pin insulator surface.
20
2. To keep the inner side of the insulator dry, the rain sheds are made in order that these rain sheds should not disturb the voltage distribution they are so designed that their subsurface at right angle to the electromagnetic lines of force.
POST INSULATOR:
Post insulator is more or less similar to Pin insulator but former is suitable for higher voltage application. Post insulator has higher numbers of petticoats and has greater height. This type of insulator can be mounted on supporting structure horizontally as well as vertically. The insulator is made of one piece of porcelain but has fixing clamp arrangement are in both top and bottom end. The main differences between pin insulator and post insulator are: SL. NO. 1 2 3 PIN INSULATOR It is generally used up to 33KV system. It is single stag. Two insulators cannot be fixed together for higher voltage application. Metallic fixing arrangement provided only on bottom end of the insulator. POST INSULATOR It is suitable for lower voltage and also for higher voltage. It can be single stag as well as multiple stags. Two or more insulators can be fixed together one above other for higher voltage application. Metallic fixing arrangement provided on both top and bottom ends of the insulator.
SUSPENSION INSULATOR:
In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size, weight of the insulator become more. Handling and replacing bigger size single unit insulator are quite difficult task. For overcoming these difficulties, suspension insulator was developed. In suspension insulator numbers of insulators are connected in series to form a string and the line conductor is carried by the bottom most insulator. Each insulator of a suspension string is called disc insulator because of their disc like shape
21
22
STRAIN INSULATOR:
When suspension string is used to sustain extraordinary tensile load of conductor it is referred as string insulator. When there is a dead end or there is a sharp corner in transmission line, the line has to sustain a great tensile load of conductor or strain. A strain insulator must have considerable mechanical strength as well as the necessary electrical insulating properties.
Rated System Voltage 33KV Number of disc insulator used in strain type tension insulator string Number of disc insulator used in suspension insulator string 3
3 5 9 15
4 8 14
There are other two types of insulator for low voltage application. Those are i.Stay Insulator ii. Shackle Insulator.
STAY INSULATOR:
For low voltage lines, the stays are to be insulated from ground at a height. The insulator used in the stay wire is called as the stay insulator and is usually of porcelain and is so designed that in case of breakage of the insulator the guy-wire will not fall to the ground.
SHACKLE INSULATOR:
The shackle insulator or spool insulator is usually used in low voltage distribution network. It can be used both in horizontal and vertical position.
23
CAPACITOR BANK
A capacitor bank is a grouping of several identical capacitors interconnected in parallel or in series with one another. These groups of capacitors are typically used to correct or counteract undesirable characteristics, such as power factor lag or phase shifts inherent in alternating current (AC) electrical power supplies. Capacitor banks may also be used in direct current (DC) power supplies to increase stored energy and improve the ripple current capacity of the power supply. Single capacitors are electrical or electronic components which store electrical energy. Capacitors consist of two conductors that are separated by an insulating material or dielectric. When an electrical current is passed through the conductor pair, a static electric field develops in the dielectric which represents the stored energy. Unlike batteries, this stored energy is not maintained indefinitely, as the dielectric allows for a certain amount of current leakage which results in the gradual dissipation of the stored energy. The energy storing characteristic of capacitors is known as capacitance and is expressed or measured by the unit farads. These characteristics also allow capacitors to be used in a group or capacitor bank to absorb and correct AC power supply faults. The use of a capacitor bank to correct AC power supply anomalies is typically found in heavy industrial environments that feature working loads made up of electric motors and transformers. This type of working load is problematic from a power supply perspective as electric motors and transformers represent inductive loads, which cause a phenomenon known as phase shift or power factor lag in the power supply. The use of a capacitor bank in the power supply system effectively cancels out or counteracts these phase shift issues, making the power supply far more efficient and cost effective. The installation of a capacitor bank is also one of the cheapest methods of correcting power lag problems and maintaining a power factor capacitor bank is simple and cost effective. One thing that should always be kept in mind when working with any capacitor or capacitor bank is the fact that the stored energy, if incorrectly discharged, can cause serious burns or electric shocks.
24
BUS COUPLER
Bus coupler is a device which is used to switch from one bus to the other without any interruption in power supply and without creating hazardous arcs. It is achieved with the help of circuit breaker and isolators. Bus coupler configurations are available as non-terminated or internally terminated. If two or more non-terminated couplers are used on a bus, then the couplers at each end of the bus must be terminated externally with 78 ohm terminators on the unused bus connections of the end couplers. Alternately, internally single terminated couplers (with or without the non-functional bus connectors) can be supplied. Even if only one non-terminated coupler acts as the bus because all devices (bus controller, remote terminals, etc.) are connected to the couplers stubs, the external bus connections of the coupler must be terminated. A dual-terminated coupler (with or without nonfunctional bus connectors) can be employed where the coupler acts as the bus without other couplers. COMPONENTS OF BUS COUPLER: Main bus isolator Current transformer Circuit breaker Line isolator Supporting insulator Potential transformer
25
CIRCUIT BREAKERS
Electrical Circuit Breaker is a switching device which can be operated manually as well as automatically for controlling and protection of electrical power system respectively. TYPES OF CIRCUIT BREAKER: According different criteria there are different types of circuit breaker. According to their arc quenching media the circuit breaker can be divided as
SF6 CIRCUIT BREAKER VACCUM CIRCUIT BREAKER OIL CIRCUIT BREAKER GAS CIRCUIT BREAKER
SF6 CIRCUIT BREAKER: A circuit breaker in which the current carrying contacts operate in Sulphur Hexafluoride or SF6 gas is known as an SF6 Circuit Breaker. SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has high affinity of absorbing free electron. Whenever a free electron collides with the SF6 gas molecule, it is absorbed by that gas molecule and forms a negative ion. The attachment of electron with SF6 gas molecules may occur in tow different ways, 1) SF6 +e=SF6 2) SF6 + e = SF5 - + F
These negative ions obviously much heavier than a free electron and therefore over all mobility of the charged particle in the SF6 gas is much less as compared other common gases. We know that mobility of charged particle is majorly responsible for conducting current through a gas. WORKING OF SF6 CIRCUIT BREAKER: The working of SF6 circuit Breaker of first generation was quite simple it is some extent similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a high pressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is released through the arc and collected to relatively low pressure reservoir and then it pumped back to the high pressure reservoir for reutilize.
26
The working of SF6 circuit breaker is little bit different in modern time. Innovation of puffer type design makes operation of SF6 circuit breaker much easier. In buffer type design, the arc energy is utilized to develop pressure in the arcing chamber for arc quenching.
Here the breaker is filled with SF6 gas at rated pressure. There are two fixed contact fitted with a specific contact gap. A sliding cylinder bridges these to fixed contacts. The cylinder can axially slide upward and downward along the contacts. There is one stationary piston inside the cylinder which is fixed with other stationary parts of the breaker, in such a way that it can not change its position during the movement of the cylinder. As the piston is fixed and cylinder is movable or sliding, the internal volume of the cylinder changes when the cylinder slides. During opening of the breaker the cylinder moves downwards against position of the fixed piston hence the volume inside the cylinder is reduced which produces compressed SF6 gas inside the cylinder. The cylinder has numbers of side vents which were blocked by upper fixed contact body during closed position. As the cylinder move further downwards, these vent openings cross the upper fixed contact, and become unblocked and then compressed SF6 gas inside the cylinder will come out through this vents in high speed towards the arc and passes through the axial hole of the both fixed contacts. The arc is quenched during this flow of SF6 gas. During closing of the breaker, the sliding cylinder moves upwards and as the position of piston remains at fixed height, the volume of the cylinder increases which introduces low pressure inside the cylinder compared to the surrounding. Due to this pressure difference SF6 gas from surrounding will try to enter in the cylinder. The higher pressure gas will come through the axial hole of both fixed contact and enters into cylinder via vent and during this flow; the gas will quench the arc.
27
28
separated hence there is no question of re-vaporization of contact surface, for next cycle of current. That means, the arc cannot be reestablished again. In this way vacuum circuit breaker prevents the reestablishment of arc by producing high dielectric strength in the contact gap after current zero.
There are two types of arc shapes. For interrupting current up to 10kA, the arc remains diffused and the form of vapour discharge and cover the entire contact surface. Above 10kA the diffused arc is constricted considerably by its own magnetic field and it contracts. The phenomenon gives rise over heating of contact at its center. In order to prevent this, the design of the contacts should be such that the arc does not remain stationary but keeps travelling by its own magnetic field. Specially designed contact shape of vacuum circuit breaker make the constricted stationary arc travel along the surface of the contacts, thereby causing minimum and uniform contact erosion.
29
forms an excessively fast growing gas bubble around the arc. It is found that the mixture of gases occupies a volume about one thousand times that of the oil decomposed. From this figure we can assume how fast the gas bubble around the arc will grow in size. If this growing gas bubble around the arc is compressed by any means then rate of de ionization process of ionized gaseous media in between the contacts will accelerate which rapidly increase the dielectric strength between the contacts and consequently the arc will be quenched at zero crossing of the current cycle. This is the basic operation of oil circuit breaker. In addition to that cooling effect of hydrogen gas surround the arc path also helps, the quick arc quenching in oil circuit breaker.
Bulk Oil Circuit Breaker is such types of circuit breakers where oil is used as arc quenching media as well as insulating media between current carrying contacts and earthed parts of the breaker. The oil used here is same as transformer insulating oil.
Minimum Oil Circuit Breaker:
These types of circuit breakers utilize oil as the interrupting media. However, unlike bulk oil circuit breaker, a minimum oil circuit breaker places the interrupting unit in insulating chamber at live potential. The insulating oil is available only in interrupting chamber. The features of designing MOCB are to reduce requirement of oil, and hence these breaker are called minimum oil circuit breaker.
30
reestablishment of arcing after current zero by creating a situation where in the contact gap will withstand the system recovery voltage. The air circuit breaker does the same but in different manner. For interrupting arc it creates an arc voltage in excess of the supply voltage. Arc voltage is defined as the minimum voltage required maintaining the arc. This circuit breaker increases the arc voltage by mainly three different ways. It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma is decreased, the mobility of the particle in arc plasma is reduced; hence more voltage gradient is required to maintain the arc. It may increase the arc voltage by lengthening the arc path. As the length of arc path is increased, the resistance of the path is increased, and hence to maintain the same arc current more voltage is required to be applied across the arc path. That means arc voltage is increased. Splitting up the arc into a number of series arcs also increases the arc voltage.
31
This was working principle of air circuit breaker now we will discuss in details the operation of air circuit breaker in practice. The air circuit breaker, operated within the voltage level 1KV, does not require any arc control device. Mainly for heavy fault current on low voltages (low voltage level above 1 KV) air circuit breakers with appropriate arc control device, are good choice. These breakers normally have two pairs of contacts. The main pair of contacts carries the current at normal load and these contacts are made of copper. The additional pair is the arcing contact and is made of carbon. When circuit breaker is being opened, the main contacts open first and during opening of main contacts the arcing contacts are still in touch with each other. As the current gets, a parallel low resistive path through the arcing contact during opening of main contacts, there will not be any arcing in the main contact. The arcing is only initiated when finally the arcing contacts are separated. The each of the arc contacts is fitted with an arc runner which helps, the arc discharge to move upward due to both thermal and electromagnetic effects as shown in the figure. As the arc is driven upward it enters in the arc chute, consisting of splitters. The arc in chute will become colder, lengthen and split hence arc voltage becomes much larger than system voltage at the time of operation of air circuit breaker, and therefore the arc is quenched finally during the current zero.
32
Definition of arc:
During opening of current carrying contacts in a circuit breaker the medium in between opening contacts become highly ionized through which the interrupting current gets low resistive path and continues to flow through this path even the contacts are physically separated. During the flowing of current from one contact to other the path becomes so heated that it glows. This is called arc.
33
Deionization of gas:
If all the cause of ionization of gas are removed from an ionized gas it rapidly come back to its neutral state by recombination of the positive and negative charges. The process of recombination of positive and negative charges is known as deionization process. In deionization by diffusion, the negative ions or electrons and positive ions move to the walls under the influence of concentration gradients and thus completing the process of recombination.
34
35
TRANSFORMER
Electrical Power Transformer is a static device which transforms electrical energy from one circuit to another without any direct electrical connection and with the help of mutual induction between to windings. It transforms power from one circuit to another without changing its frequency but may be in different voltage level.
36
The above mentioned form of transformer is theoretically possible but not practically, because in open air very tiny portion of the flux of the first winding will link with second so the current flows through the closed circuit of latter, will be so small that it may be difficult to measure. The rate of change of flux linkage depends upon the amount of linked flux, with the second winding. So it desired to be linked almost all flux of primary winding, to the secondary winding. This is effectively and efficiently done by placing one low reluctance path common to both the winding. This low reluctance path is core of transformer, through which maximum number of flux produced by the primary is passed through and linked with the secondary winding. This is most basic theory of transformer.
37
38
Let us take flux as reference. EMF Es and Ep lags behind the flux by 90o. The magnitude of the passers Es and Ep are proportional to secondary and primary turns. The excitation current Io which is made up of two components Im and Iw. The secondary current Io lags behind the secondary induced emf Es by an angle s. The secondary current is now transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The total current flows through the primary Ip is then vector sum of KT Is and Io.
39
40
terminals. this Ep is equal to primary induced emf. This primary emf will transform to the secondary winding by mutual induction and transformed emf is Es. Again this Es will be dropped by secondary winding resistance and reactance, and resultant will actually appear across the burden terminals and it is denoted as Vs So if system voltage is Vp, ideally Vp/KT should be the secondary voltage of PT, but in reality actual secondary voltage of PT is Vs.
41
2. Chemical Parameter - Water Content, Acidity, Sludge Content. 3. Physical Parameters - Inter Facial Tension, Viscosity, Flash Point, Pour Point.
42
43
More clearly, the leakage current through an insulation does have two component one is capacitive or reactive and other one is resistive or active. Again it is clear from above diagram, value of which is also known as loss angle, is smaller, means resistive component of the current IR is smaller which indicates high resistive property of the insulating material. High resistive insulation is good insulator. Hence it is desirable to have loss angle as small as possible. So we should try to keep the value of tan as small as possible. High value of this tan is an indication of presence of contaminants in transformer oil. Hence there is a clear relationship between tan and resistivity of insulating oil. If resistivity of the insulating oil is decreased, the value of tandelta increases and vice versa. So both resistivity test and tan delta test of transformer oil are not normally required for same piece of insulator or insulating oil. In one sentence it can be said that, tan is measure of imperfection of dielectric nature of insulation materials like oil.
44
45
BUCHHOLZ RELAY
Construction of Buchholz Relay:
Buchholz Relay in transformer is an oil container housed the connecting pipe from main tank to conservator tank. It has mainly two elements. The upper element consists of a float. The float is attached to a hinge in such a way that it can move up and down depending upon the oil level in the Buchholz Relay Container. One mercury switch is fixed on the float. The alignment of mercury switch hence depends upon the position of the float. The lower element consists of a baffle plate and mercury switch. This plate is fitted on a hinge just in front of the inlet (main tank side) of Buchholz Relay in transformer in such a way that when oil enters in the relay from that inlet in high pressure the alignment of the baffle plate along with the mercury switch attached to it, will change. In addition to these main elements a Buchholz Relay has gas release pockets on top. The electrical leads from both mercury switches are taken out through a molded terminal block.
46
47
EARTHING TRANSFORMER
If the earthing transformer on the Delta Side is outsides the Zone of protection the Earth Fault(E/F)in the delta system outside Current Transformer(CT) locations would produce current distributions as shown which circulate within the differential CT secondaries and is kept out of operating coils. Zig-Zag or inter connected star grounding transformer has normal magnetising impedance of high value but for E/F, currents flow in windings of the same - core in such a manner that the ampere turn cancel and hence offer lower impedance. In cases where the neutral point of three phase system is not accessible like the system connected to the delta connected side of a electrical power transformer, an artificial neutral point may be created with help of a zigzag connected earthing transformer. This is a core type transformer with three limbs. Every phase winding in zigzag connection is divided into two equal halves. One half of which is wound on one limb and other half is wound on another limb of the core of transformer. 1st half of Red phase winding is wound on the 1st limb of the core and 2nd half of same Red phase is wound on 3rd limb. 1st half of Yellow phase winding is wound on the 2nd limb of the core and 2nd half of same Yellow phase is wound on 1st limb. 1st half of Blue phase winding is wound on the 3rd limb of the core and 2nd half of same Blue phase is wound on 2nd limb. End point of all three windings ultimately connected together and forms a common neutral point. Now if any fault occurs at any of the phases in delta connected system, the zero sequence fault current has close path of circulating through earth as shown in the figure. In normal condition of the system, the voltage across the winding of the earthing transformer is 1/3 times of rated per phase voltage of the system. But when single line to ground fault occurs on any phase of the system, as shown in the figure, zero sequence component of the earth fault current flows in the earth and returns to the electrical power system by way of earth star point of the earthing transformer. It gets divided equally in all the three phases. Hence, as shown in the figure, the currents in the two different halves of two windings in the same limb of the core flow in opposite directions. And therefore the magnetic flux set up by these two currents will oppose and neutralize each other. As there is no increase in flux due to fault current, there is no extra d/dt means no extra voltage induced across the winding and
48
no choking effect occurs to impede the flow of fault current. So it can be concluded like that, the zigzag type earthing or grounding transformer maintains the rated supply voltage at normal current as well as when a solid single line to ground fault current flows through it. The rated voltage of an erthing or grounding transformer is the line to line voltage on which it is intended to be used. Current rating of this transformer is the maximum neutral current in Amperes that the transformer is designed to carry in fault condition for a specific time. Generally the time interval, for which transformer designed to carry the maximum fault current through it safely, is taken as 30 second.
49
CONTROL ROOM
Control room is the controlling unit of the whole substation.
CONTROL PANEL:
In the facial of the control panel there are few meters attached for measuring power, voltage, current etc.
COMMUNICATION ROOM:
The work of PLCC is controlled and manipulated in communication room. As human voice frequency is low so it is amplified to high level by amplifier, also there are various types of filters, capacitors and rectifiers to get crystal communication.
50
51
ELECTRICAL SWITCHGEAR
A switchgear or electrical switchgear is a generic term which includes all the switching devices associated with mainly power system protection. It also includes all devices associated with control, metering and regulating of electrical power system. Assembly of such devices in a logical manner forms a switchgear. This is very basic definition of switchgear. We all familiar with low voltage switches and re-wirable fuses in our home. The switch is used to manually open and close the electrical circuit in our home and electrical fuse is used to protect our household electrical circuit from over current and short circuit faults. In same way every electrical circuit including high voltage electrical power system needs switching and protective devices. But in high voltage and extra high voltage system, this switching and protective scheme becomes complicated one for high fault current interruption in safe and secure way. In addition to that from commercial point of view every electrical power system needs measuring, control and regulating arrangement. Collectively the whole system is called Switchgear and Protection of power system. The electrical switchgear has been developing in various forms. Switchgear protection plays a vital role in modern power system network, right from generation through transmission to distribution end. The current interruption device or switching device is called circuit breaker in Switchgear protection system. The circuit breaker can be operated manually as when required and it is also operated during over current and short circuit or any other faults in the system by sensing the abnormality of system. The circuit breaker senses the faulty condition of system through protection relay and this relay is again actuated by faulty signal normally comes from current transformer or voltage transformer. A switchgear has to perform the function of carrying, making and breaking the normal load current like a switch and it has to perform the function of clearing the fault in addition to that it also has provision of metering and regulating the various parameters of electrical power system. Thus the circuit breaker includes circuit breaker, current transformer, voltage transformer, protection relay, measuring instrument, electrical switch, electrical fuse, miniature circuit breaker, lightening arrestor or surge arrestor, isolator and other associated equipment.
52
Types of Relays:
Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism. Based on operation mechanism protection relay can be categorized as Electro Magnetic relay, Static relay and Mechanical relay. Actually relay is nothing but a combination of one or more open or closed contacts. These all or some specific contacts the relay change their state when actuating parameters are applied to the relay. That means open contacts become closed and closed contacts become open. In electromagnetic relay these closing and opening of relay contacts are done by electromagnetic action of a solenoid. In mechanical relay these closing and opening of relay contacts are done by mechanical displacement of different gear level system. In static relay it is mainly done by semiconductor switches like thyristor. In digital relay on and off state can be referred as 1 and 0 state. Based on actuating parameter the protection relay can be categorized as
53
BATTERY
Function of battery in sub-station:
It is an arrangement of number of cells to supply dc voltage to the control panel. There are three sets of batteries in this substation 2V 15 batteries for 11kV control panel. YKP-7 supply 10 Amp-hr. 2.3V 108 batteries for 33 kV & 132 kV control panel. YKP-17 supply 200 Amphr. These are all electrolytic type batteries connected in series. 48V battery for PLCC panel. These are all dry cell type battery.
Battery charger:
It is used for charging the batteries. Specifications: Model = BC Rating = 229V, 24+24 A Ac Input = 415V, 30 Amp, 50 Hz, 3 Phase DC Output = 24.7V, 24A
54
CONCLUSION
This training report has primarily been prepared on the basis of the vocational training session underwent at the West Bengal State Electricity Transmission Company Limited. The training underwent at the West Bengal State Electricity Company Transmission Limited (WBSETCL) was an eye opener for us. It provided us with the opportunity to observe various important aspects of the functioning of a substation. We became acquainted with the duties of the Assistant Engineer in-charge of a transmission substation as well as that of the Station Manager, or the Assistant Engineer in charge of a Group Electric Supply Office. I wished if I had the scope and opportunity to work in the above designation. Ill be able to dispense off with the duties efficiently Working with Electrical department enhanced my major understanding In addition, I gained a good experience in term of self confidence, real life working situation, interactions among people in the same field and working with others with different professional background. I had an interest in understanding basic engineering work and practicing what has been learnt in the class. Also, the training was an opportunity for me to increase my human relation both socially and professionally.
55
BIBLIOGRAPHY
The books & websites which served as a source of information for us are listed below:BOOKS: 1) 2) 3) 4) 5) 6) 7) Electrical Power Systems Ashfaq Hussain Switchgear & Protection U.V.Bakeshi Principles Of Power System Mr. V.K. Mehta A Course in Electrical and Electronics Measurements & InstrumentationA.K.Sawhney Basic electrical Thereja Electrical power system Subir Roy Electrical and Electronics Measurements & Instrumentation P. Purkait & B. Biswash.