Академический Документы
Профессиональный Документы
Культура Документы
Subject: Schneider Modbus RTU to Zelio 2 SR3 using GP-Pro PBIII AN# 1137 Rev A Date: 08/20/2005 Name: Bjorn den Dunnen Page: 1/8
Description: This application note shows how to set up a Modbus RTU connection between a Pro-face GP, GLC or ST using the Schneider Modbus RTU 1:n comm. driver in GP-Pro PBIII and Zelio SR3 system using the SR3-MBU01BD communication module.
Within the scope of this application note the terms ST, GP and GLC can be read as applying to any ST-400, ST-403, GP-2000/1 and GLC-2000 series hardware without exceptions unless noted otherwise. Contents 1) Cable Diagrams (ST-400 or GP/GLC-2000 Series to 1 Zelio 2 SR3-MBU01BD) 2) Communication Settings 3) Addressing 4) Error Codes 5) Disclaimer 1) Cable Diagrams Cable Diagram 1: ST-400 or ST-403.
2) Communication Settings 1) Make sure you are using GP-Pro PBIII v7.x C-Package 03 (for details see Help, About) 2) In the Project Manager select Schneider Electric. and Schneider Modbus RTU 1:n comm.
Note: Baud Rate and Parity Bit can be changed as long as the settings match.
About the address offset Modbus addressing is offset by 1: to read address 10h (16d) use N_400017 Reading / Writing an Integer value (assuming 1 PLC, Node number 1) Zelio 20h (32d) = 1_400033 Reading / Writing 1 bit in an Integer value (assuming 1 PLC, Node number 1) Zelio Run/Stop = 1_40004900 Below is a simplified view of the Zelio Soft 2 FBD editor showing the JnXT1 input form the GP/ST to the Zelio and the OnXT1 output from the Zelio to the GP/ST. (note that your are not required to send the data from the input directly to the output, the data flow below is used to illustrate the relation of J and O)
* NOTE: the Zelio Soft 2 v2.4 English manual states that the O1XT1 O4XT1 addresses can be found in addresses 0000h 0003h. Instead use the addresses shown in the table above.