(E & E ) Elective: DESIGN OF ELECTRICAL MACHINES- (ELE 310C)


ASSIGNMENT # 1 ASSIGNMENT DATE: 01 02 2012 LAST DATE FOR SUBMISSION: 12 02 2012

Note: Part A is mandatory for all students. Part B shall be answered by the students as indicated PART A Common to all students 1. A 1000 KVA, 6600/440 V, 50 Hz, 3 phase, delta/star, core type oil immersed natural cooled transformer has the following design data: Centre to centre distance of adjacent limbs = 47 cm; Outer diameter of HV winding = 44 cm; Height of frame = 124 cm; Core loss = 3.7 KW; Full load copper loss = 10.5 KW; Average temperature rise of oil should not exceed 350 C; Specific heat dissipation from tank walls = 6 W/m2 and 6.5 W/m2 due to radiation and convection respectively; Assume that convection is improved by 35% due to tubes. 2. Design a suitable tank and no. of tubes required. A 300 KVA, 6600/400 V, 50 Hz, 3 phase, delta/star, core type transformer has the following design data: Outer diameter of HV winding = 36 cm; Inner diameter of HV winding = 29 cm; Cross section of HV conductors = 5.4 mm2; Outer diameter of LV winding = 26 cm; Inner diameter of LV winding = 22 cm; Cross section of LV conductors = 170 mm 2; Length of coils = 50 cm; Voltage per turn = 8; Resistivity of conductors = 2 -cm. Calculate full load copper loss and % voltage regulation at full load 0.8 pf lagging. 3. A 15 MVA, 33/6.6 KV, 50 Hz, 3 phase, star/delta, core type transformer has the following design data: Net area of each limb = 15 cm2; Net area of each yoke = 18 cm2; Mean length of flux path = 2.3 m per limb and 1.6 m per yoke; No. of turns of HV winding = 450; Calculate the no load current. Use the following data of transformer steel: Bmax (Wb/m2) MMF (AT/m) Iron loss (Watts/Kg) 0.9 130 0.8 1.0 200 1.3 1.2 420 1.9 1.3 660 2.4

..Please turn over

Page 1 of 2

PART B Applicable to students as indicated 4. Give complete design of transformer which should include core and yoke design, winding design, tank design and performance calculations like no load current, winding resistance and leakage reactance, core and copper loss efficiency and regulation at full load, 0.8 pf lagging. Highlight final designed data and performance details in tabular form. (Necessary information for the design can be obtained from any Electrical Machine Design text book) a) 1500 KVA, 33/11 KV, 3 phase, 50 Hz star/delta core type transformer A section students b) 750 KVA, 6600/400 V, delta/star, three phase, 50 Hz core type transformer B section students c) 5 KVA, 11000/440 V, 3 phase, 50 Hz delta/star core type transformer with 5% tapping C section students (R. Nos 48 to 140) d) 1 KVA, 230/110 V, single phase, 50 Hz shell type transformer C section students (R. Nos 176 to 199)

Page 2 of 2

Вам также может понравиться