Denite purpose contactors

De n co ite p nt ac urp to os rs e

Applications
Type DP contactors provide high performance with exibility and reliability, designed to match numerous applications including: Motors Power supplies Food service equipment Compressors Business machines Resistive heating Air conditioning Refrigeration equipment Welding

Features
Available as: 30A, 1, 2, 3 or 4 pole 40A, 2, 3 or 4 pole 60A, 3 pole Industry standard mounting plate provides easily accessible mounting holes Coil terminals are provided with #6-32 screws and (1) .250 quick connect or dual .250 quick connect terminals Exclusive hex, slotted, phillips #10-32 terminal screws for main terminals Coil is Class B (130 C) Insulation system with wide range of voltages and 50/60 Hz ratings Double E Magnet Assembly provides optimal performance with reduced power consumption Snap-in auxiliary switch with 1 SPDT or 2 SPDT contacts available as an option 1 NO & 1 NC auxiliary contact block with 600 VAC rating available as an option Base assembly is made from high arc-resistant plastic

Agency approvals
UL 508 Guide No. NLDX2, File # E227250 CE/Semko Certied EN60947-4-1:1991 IEC 947-4-1

Catalog number explanation

DP 30
Denite purpose Frame size 30 = 30A 40 = 40A 60 = 60A

3P

- 1

/B
Bulk pack quantities Coil voltage (See coil voltage selection chart) Power poles 1P = 1 NO 2P = 2 NO 3P = 3 NO 4P = 4 NO Contactor type C = Non-reversing

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

1.97
AC 1000 - 11/03

e os rp pu rs ite acto n t De con

30A, 40A & 60A

DP30C3P-F

DP40C4P-F

DP60C3P-F

30A, 40A & 60A


Locked rotor amps Full load amps Number of poles 240/ 277V Resistive amps Maximum HP 1 phase 600V 120V 240V 200/ 208V Maximum HP 3 phase 240/ 277V 480V 600V Bulk pack 1 Catalog number qty. Individual pack list price Bulk pack list price

480V

30 30 30 30 40 40 40 60

1 2 3 4 2 3 4 3

150 150 180 180 240 240 240 360

75 125 150 150 200 200 200 300

50 100 120 120 160 160 160 240

40 40 40 40 50 50 50 75

1 2 2 2 2 3 3 2

2 3 5 5 3 7.5 7.5 10

10 10 10 10 25

10 10 10 10 25

15 10 20 10 30

20 25 30

50 50 25 20 50 25 20 10

DP30C1P-F DP30C2P-F DP30C3P-F DP30C4P-F DP40C2P-F DP40C3P-F DP40C4P-F DP60C3P-F

$ 30 38 55 75 46 60 100 147

$ 27 34 50 68 42 54 90 140

Coil voltage selection chart


Voltage 24VAC 120VAC 208/240VAC 277VAC 480VAC 575VAC

Ordering bulk quantities


To order bulk package quantities add /B to the end of the catalog number. Example: For quantities of 25 of a 30A 3 pole contactor with 24VAC coil, the catalog number would be: DP30C3P-F/B 2 C 4 5

Sufx #

Coil voltage selection


All catalog numbers include a 24VAC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the rst digit after the dash in the catalog number.

Auxiliary contact blocks (3 pole only)


Description Catalog number 30A - 40A Catalog number 60A List price

NO or NC SPDT 1 NO & 1 NC

CADP40-10 CADP40-11

CADP60-10 CADP60-11

$ 10

Contact rating of 1 NO & 1 NC


120V 240V 480V 600V

Break Make Continous

A A A

3.0 30 10

1.5 15 10

.75 7.5 10

.6 6 10

Quick connect terminals on all auxiliary switches are .250 wide.

Contact rating of SPDT


Voltage Current rating

125VAC 120VAC 250VAC 125VDC 250VDC

10A, 1/3 HP 4A on lamp load 10A, 1/3 HP .5A .25A

1 Must be ordered in standard pack quantities as shown. Add sufx /B to the catalog number.

1.98
AC 1000 - 11/03

Discount schedule DP

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Technical data 30A 60A 1, 2, 3, & 4 Pole


30A 40A 1 & 2 pole
Coil technical data DP30C1P DP30, DP40C2P

De n co ite p nt ac urp to os rs e

Nominal coil voltage Maximum pickup volts Drop-out volts range Nominal inrush VA Nominal inrush VA Nominal sealed VA Nominal sealed VA Nominal DC resistance
Other specications

50 Hz 60 Hz 50 Hz 60 Hz Ohms

24 18 6 15 31 28 6 5 17.5

120 88 20 70 31 28 6 5 450

208/240 177 40 170 35 32 7 6 1800

277 221 50 165 31 28 6 5 2252

24 18 6 15 22 20 5.5 4.5 13

120 88 20 70 22 20 5.5 4.5 275

208/240 177 40 140 22 20 5.5 4.5 1056

277 221 50 165 22 20 5.5 4.5 1772

DP30C1P

DP30, DP40C2P

Line and load terminals Wire size AWG min max Tightening torque (recommended) Coil termination Quick connects .250 std. 1 1.5 pole Quick connects .250 std. 2 pole Covers Insulation system

# 10 32 screw 1 16 82 25 in. lbs. Dual .250 QC (2) Quad Dual or quad Optional 130 C Class B

Box lug 1 14 4 Cu/Al 40 in. lbs Dual .250 QC (2) Quad Dual or quad Standard 130 C Class B

30A- 60A 3 pole


Coil technical data DP30, DP40C3P DP60C3P

Nominal coil voltage Maximum pickup volts Drop-out volts range Nominal inrush VA Nominal inrush VA Nominal sealed VA Nominal sealed VA Nominal DC resistance
Other specications

50 Hz 60 Hz 50 Hz 60 Hz Ohms

24 18 6 15 65 60 7.5 6 6.6

120 88 20 70 65 60 7.5 6 165


DP30C3P

208/240 177 40 140 65 60 7.5 6 660

277 220 65 185 65 60 7.5 6 880

480 384 150 270 65 60 7.5 6 1320

24 18 6 15 140 132 20 14 2.4

120 93 20 70 140 132 20 14 45

208/240 177 40 135 140 132 20 14 180

277 235 50 180 140 132 20 14 280


DP60C3P

480 374 150 286 140 132 20 14 852

DP40C3P

Line and load terminals Wire size AWG min max Tightening torque (recommended) Quick connects: power terminals Coil terminals Covers Insulation system

# 10 32 Screw 1 16 8 2 25 in. lbs Dual.250 QC Dual .250 QC (2) Optional 130 C Class B

Box lug 1 14 7 Cu/Al 40 in.lbs Dual.250 QC Dual .250 QC (2) Standard 130 C Class B

Box lug 1 14 2 Cu/Al 50 in. lbs Dual.250 QC #6 35 screw & .250 QC (2) Standard 130 C Class B

30A 40A 4 Pole


Coil technical data DP30, DP40C4P

Nominal coil voltage Maximum pickup volts Drop-out volts range Nominal inrush VA Nominal inrush VA Nominal sealed VA Nominal sealed VA Nominal DC resistance
Other specications

50 Hz 60 Hz 50 Hz 60 Hz Ohms

24 19.2 6 15 68 60 14 9 5
DP30C4P

120 88 20 70 68 60 14 9 148 # 10 32 screw 1 16 8 2 22 in. lbs Dual .250 QC Dual .250 QC (2) Optional 130 C Class B

208/240 177 40 140 58 55 11 9.5 550

277 220 65 185 58 52 11 9.5 750


DP40C4P

480 384 150 270 48 52 11 9 2100

Line and load terminals Wire size AWG Min Max Tightening torque (recommended) Quick connects: power terminals Coil terminals Covers Insulation system

Box Lug 14 4 Cu/AL 40 in. lbs Dual .250 QC Dual .250 QC (2) Standard 130 C Class B

1 See page 1.82 to 1.85 for description and approximate dimensions. 2 Stranding must be split for #8 wire.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

1.99
AC 1000 - 11/03

ABB Inc. 1206 Hatton Road Wichita Falls, TX 76302 Telephone 888-385-1221; 940-397-7000 Fax 940-397-7085 http://www.abb-control.com

Publication AC1000 No. 1SXU 001 000 C0201 Printed in USA, November 2003