Compressors
SC18GH
R134a
Blue stripe Approvals
104G
Application
Application Evaporating temperature range C HBP 50Hz: -15 to 20 60Hz: -15 to 15 Condensing temperature max. C 50Hz: 70 60Hz: 60 / 70 short-term Voltage range V/Hz 198 - 254 /50 198 - 254 /60 Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C 43C CSR 43 F2 F2 F2
Yellow background
DANFOSS COMPRESSORS
Approval mark
S O F1 F2 = Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary
Design
Displacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm
3
16
19 9.7
127 101.6 35
1460 13.7
kg
Motor
Motor size LRA (rated after 4 sec. UL984) HST Cut-in current HST watt A A 550 21.8 21.8 3.5/12.1 EN 60335-2-34, UL984/CSA-C22.2
B1
E
B A B2
Dimensions
B B1 B2 Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 213 193 110
37 37
Height
mm
219
255
55
8.2 0.09 80
107 107 115
8258
August 2002
CG.44.G2.02
55 63
6.2 0.09
63
10.2 0.09
151
70 150
8292-8
8292-4
8861
watt
20 2389
a3
a2 e
Capacity (ASHRAE)
Evap. temp in C SC18GH, 50Hz SC18GH, 60Hz -15 600 707 -10 790 921 -5 1021 1181 0 1298 1495 5 1626 1869 7.2 1788 2054 10 2011 2310 15 2461 2825
watt
20 2982
c
8227
Power consumption
Evap. temp in C SC18GH, 50Hz SC18GH, 60Hz -15 404 449 -10 452 511 -5 503 577 0 554 643 5 605 708 7.2 626 736 10 651 770 15 692 826
watt
20 724
Current consumption
Evap. temp in C SC18GH, 50Hz SC18GH, 60Hz -15 2.44 2.14 -10 2.66 2.45 -5 2.86 2.75 0 3.06 3.05 5 3.26 3.35 7.2 3.34 3.48 10 3.45 3.65 15 3.63 3.94
A
20 3.80
b
Start winding
5 2
e a2
Bleeder resistance
W/W
20 3.30
COP (ASHRAE)
Evap. temp in C SC18GH, 50Hz SC18GH, 60Hz -15 1.48 1.57 -10 1.75 1.80 -5 2.03 2.05 0 2.34 2.33 5 2.69 2.64 7.2 2.86 2.79
ASHRAE 55C 32C 32C
W/W
10 3.09 3.00 15 3.56 3.42 20 4.12
M
a3
Fan
Thermostat
Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature 50Hz: Fan cooling F2, 220V 60Hz: Fan cooling F2, 220V
Accessories
Devices Starting device Cover Starting relay Starting capacitor 80 F Run capacitor Cord relief Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Fig. a3 b a2 c e d SC18GH 117-7038 (470 mm cable length) 117-7039 (550 mm cable length) 103N2008 Components of starting device 103N1004 118-1917 118-1918 118-1919
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
CG.44.G2.02
August 2002