in Saudi Arabia and today is a leading international manufacturer of air conditioning systems and is No. 1 in the Middle East. Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55 countries in the Middle East, Europe, Africa and Asia. The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and service brands as well as a number of international brands under the OEM sales. The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima. The four SBUs are: 1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers. 2. Unitary & Applied Business Unit supporting Classic, Cooline, GE and OEM brands for commercial and industrial customers. 3. Zamil CoolCare providing engineering & project management services, HVAC maintenance, retrofit services and parts. 4. Geoclima srl is an independent business supporting other SBUs for their requirement of Chillers & Double skin AHUs. The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare Service direct their business operations from the corporate headquarters at Dammam, Saudi Arabia. Geoclima has its engineering & production departments located at Monfalcone, Italy and has a design center in Austria. All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at its best and achieve the corporate goals of maximizing customer satisfaction. Factories and Productions Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one speciality production facility in Italy operated by Geoclima. The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air Conditioning systems per year. Quality & Product Certificates The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification. Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization) Certificate for Room Air Conditioners. ZAC's products are also certified with: 1. CE (Council of European Community) 2. UL (Underwriters Laboratory) 3. Eurovent 4. DEMKO 5. ETL Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed bin Fahd Al Saud Award for Factory Safety. Our Products In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Concealed Units up to 5 tons, the Ducted Splits up to 30 tons, the Packaged Units up to 90 tons, the Single and Double Skin Air Handling Units up to 70,630 CFM and the Water Chillers up to 660 tons cooling capacity.
INDEX
Contents Page
Model decoding ........................................................................................................................................ 2 Standard specifications ......................................................................................................................... 3-7 Options & accessories ........................................................................................................................... 8-9 Physical data ..................................................................................................................................... 10-12 Selection procedure ............................................................................................................................... 13 Performance data .............................................................................................................................. 14-16 Electrical data .................................................................................................................................... 17-18 Dimensions ........................................................................................................................................ 19-23 Typical schematic wiring diagram ...................................................................................................... 24-30 Rigging instructions ................................................................................................................................ 31 Installation clearance .............................................................................................................................. 32 Mounting location ................................................................................................................................... 33 Load distribution ................................................................................................................................ 34-35 Installation instructions ........................................................................................................................... 36 Electrical ................................................................................................................................................. 37 System design ........................................................................................................................................ 37
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
MODEL DECODING
1, 2 & 3 BASIC 4, 5 & 6 NOMINAL COOLING CAPACITY (TONS)
020 025 031 035 040 045 050 060 070 080 090 110 130 140 150 190 F : 460-3-60
8 COMPRESSOR TYPE
10 CONDENSER COIL
CDX
CONDENSING UNIT
S : DUAL SCROLL
* **
A : STANDARD OPTIONS
A : ALUMINUM FIN B : COATED ALUMINUM FIN C : COPPER FIN D : ALUMINUM FIN WITH COIL GUARD E : COATED ALUMINUM FIN WITH COIL GUARD G : COPPER FIN WITH COIL GUARD M :ALUMINUM FIN WITH TG COATING N : COPPER FIN WITH TG COATING P: ALUMINUM FIN WITH TG COATING & COIL GUARD Q :COPPER FIN WITH TG COATING & COIL GUARD
K : FAN CYCLING & ADJUSTABLE HIGH & LOW PRESSURE SWITCHES V : VOLT FREE CONTACTS
***
****
C : COMPRESSOR CIRCUIT BREAKER P : PUMPDOWN SOLENOID VALVE B : K & V COMBO E : K & C COMBO G : K & P COMBO
**
*** +++
(LEAD COMPRESSOR) D : H + SPRING ISOLATOR K : Q + SPRING ISOLATOR B : L + SPRING ISOLATOR U : M + SPRING ISOLATOR
12 REFRIGERANT CHARGING
H : HOLDING CHARGE F : FULLY CHARGE
13 GENERAL OPTIONS
A : STANDARD OPTIONS
A : STANDARD OPTIONS C : NEMA 4X COATING FOR CONTROL BOX F : ADDITIONAL CORE FILTER DRYER S : ADDITIONAL SHUT-OFF VALVE T : THERMOSTAT K : F & S COMBO M : C & T COMBO L : F, S & T COMBO G : C, F & S COMBO B : C, F, S & T COMBO
M : REPLACEABLE CORE FILTER DRIER & SHUT-OFF VALVE P : PRESSURE GAUGES (SUCTION & DISCHARGE) O : PRESSURE GAUGES (SUCTION, DISCHARGE & OIL)
++
++++
H : HOT GAS BYPASS VALVE R : CONDENSER PRESSURE RELIEF VALVE J : M & P COMBO K : M & O COMBO N : M & H COMBO Q : M & R COMBO S : M, H & R COMBO T : M, H & P COMBO U : M, H & O COMBO V : A, H & R COMBO F : A, H & P COMBO G : A, H & O COMBO L : A, H, P & R COMBO B : M, H, O & R COMBO
NOTES:
* **
Dual scroll compressors are available up to models CDX070 only. Dual semi-hermetic compressors are available for models CDX035 - CDX190 only. (Single semi-hermetic compressors for models CDX020 - CDX031). Quadruple semi-hermetic compressors are available for models CDX110 - CDX190 only. A combination of volt free contact option: 1. Unit ON, 2. Individual compressor run & trip, 3. Unit trip indication. Standard options (for scroll compressors) contain sealed type filter drier, fixed low & high pressure switches. Standard options (for semi-hermetic compressors) contain replaceable filter drier, ball valve, sight glass, fixed low & high pressure switches, muffler and without spring isolators. Oil pressure gauge is applicable for semi-hermetic compressors only. Spring isolators includes vibration eliminator on suction & discharge lines. Optional thermostat is a 2 stage cool/2 stage heat and applicable for single or dual compressor models only. A loose sensor is included in the package for remote or duct temperature sensing option.
INTRODUCTION
The CDX series air cooled condensing units from Zamil Air Conditioners are designed to provide engineering excellence in comfort air conditioning and industrial cooling with a superior combination of energy saving, performance, application flexibility, ease of service & maintenance and ability to withstand extreme ambient temperatures. These units can be combined with a wide variety of evaporator coils and blower packages to provide quite and dependable comfort. These units can be installed on a roof tops or at ground level.
Scroll Compressor:
The scroll compressors are consists of two involutes or Archimedean spirals (Figure-1). One spiral is positioned inside the other to form a series of crescent-shaped pockets. During compression the upper spiral remains stationary and the lower one, being eccentrically mounted on the drive shaft, describes an orbital rather than a simple rotary motion.
Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. A refrigerant enters the outer openings as one of the spirals orbits.
The open passages are sealed off as gas is drawn into the spiral.
As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.
By the time the gas arrives at the center port, discharge pressure has been reached.
Actually, during operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction and discharge.
Refrigerant enters the compressor at the suction connection and flows around the motors housing and enters at the bottom side through the openings. Oil droplets separate from the refrigerant and fall into the oil sump. All suction refrigerant passes through the electrical motor, ensuring full motor cooling. After that the refrigerant enters the scroll elements.
Semi-hermetic Compressor:
These Semi hermetic reciprocating compressors are accessible hermetic type. Compressor and motor are enclosed in a hermetically sealed housing, with out shaft seal. The compressors are equipped with an oil sight glass through which the oil quantity and its conditions in the crankcase can be observed. These compressors can be disassembled in the field for service. Refrigerant-cooled motor compressors have an oil pressure lubrication system. This system is supplied by a positive displacement oil pump, working in either direction. It is protected by a screen and is made accessible for quick oil pressure checking by a Schrader check valve. The use of oil pressure control safeguards the lubrication system. These compressors can be provided with capacity control (optional). The use of unloading provides optimal part load capacities.
* * * * * * * * *
Compact unit design & excellent serviceability. High energy efficiency ratio (EER). Scroll and semi-hermetic reciprocating compressors. Independent refrigeration circuits. Integral sub cooling circuit provided to increase overall unit efficiency. Low noise condenser fans, direct drive with rolled form venturi design to eliminate airflow recycling. Condenser fan motors are totally enclosed air over type (TEAO) with class 'F' winding insulation. Microprocessor based controls. High safety standards with UL listed electrical components. Quality assurance according to ISO 9001: 2000. Guarantees high and constant product quality.
STANDARD SPECIFICATIONS
A. UNIT CASING & CONSTRUCTION
Unit casing shall be fabricated of heavy gauge (G-90) galvanized steel. Steel sheet panels are zinc coated and galvanized by the hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90 followed by backed on electrostatic polyester dry powder coat. Condensing unit consists of dual or quadruple refrigeration compressors, condenser coil, propeller fans, control wiring and interconnecting piping completely factory assembled. The whole unit is mounted on pressed steel or 'C' channel base rail with lifting holes. The unit is provided with an integral weather resistant control panel suitable for remote thermostat control, ready for field connection.
B. COMPRESSOR
Scroll compressors are used as standard & semi-hermetic reciprocating as an option for models CDX020-CDX070 and semi-hermetic reciprocating compressors are standard for models CDX080 - CDX190. All the compressors are conforming to ARI 540 standard. The compressors are equipped with internal motor protection, factory installed crankcase heaters and rubber vibration isolators for quiet and efficient operation. As an option, semi-hermetic compressor can be fixed on anti-vibration mounting (spring type) along with suction & discharge line vibration eliminators. Oil pressure control is provided on units with semi-hermetic compressor only. Each compressor has lock-out devices to protect it from short cycling when tripped by safety controls. Each compressor has separate condenser coil with safety controls. Sight glass and filter drier are standard for all models.
C. CONDENSER COILS
V & W-configurations condenser coils are of the enhanced louvered fin-and-tube type, constructed of seamless 3/8" dia. inner grooved copper tubes, mechanically bonded to aluminum fins for maximum heat transfer efficiency. As an option, corrugated copper fins or coated aluminum fins or other coated coils may be provided. The fins have full self spacing collars which completely cover each tube. The staggered tube design improves the thermal efficiency. End plates support sheets are heavy gauge galvanized steel with extruded collars for better tube support, formed to provide structural strength. Each coil is pressure tested in the factory at not less than 450 psi air pressure.
D. CONDENSER FANS
Condenser fans are constructed of die cast aluminum blades/hubs with direct driven motors. All fans are statically and dynamically balanced to operate at minimum noise and vibration. Fan blades are designed with appropriate pitch angle which result in maximum airflow through the condenser coil.
F. SERVICE VALVES
Both suction and liquid service valves are brass, back seating type with sweat connections. Valves are externally located so refrigerant piping connections can be made quickly and easily.
G. CONTROL PANEL
The control panel design is equivalent to NEMA-4 standard with hinged door for easy access ensuring dust and weatherproof construction. Internal power and control wiring is neatly routed, properly anchored and all wires are identified with cable markers as per NEC standard applicable to HVAC units. Major electrical devices used in the control panel are UL listed, which are reliable in operation at high ambient conditions for a long period.
6
H. MICROPROCESSOR CONTROLLER
These condensing units are provided with a microprocessor control board incorporating the following features:
BALANCE LOADING OF COMPRESSORS: The units electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor 1 can also be set to always lead. In this case, compressor 1 always starts first and stops last. (Selectable through dip switch setting on control board).
PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoids opening and compressor starting to equalize the pressure in the system necessary for compressor to startup. (Selectable through dip switch setting on control board).
COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load demand.
COMPRESSOR LOCK-OUT FUNCTION: If any of the units safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.
FAULT DIAGNOSTICS: In case of system fault, LEDs on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.
DIGITAL I/Os: The units control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.
SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential
order: supply fan condenser fan compressor; at a pre-determined timings.
K. CRANKCASE HEATERS
Each compressor has crankcase heater. The compressor crankcase heater is always on when the compressor is deenergized. This protects the system against refrigerant migration, oil dilution and potential compressor failure.
L. FILTER DRIER
Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil contaminating particles by the filter drier. Cartridge (sealed type) is standard for scroll compressor models and replaceable core filter drier is provided for semihermetic reciprocating compressor models.
M. SIGHT GLASS
Moisture indicating sight glass (supplied loose) to be installed in liquid line in the field. Easy to read color indicator shows moisture contents and provides a mean for checking the system refrigerant charge.
C. ADVANCE MICROPROCESSOR
Advance microprocessor control can be offered to achieve precise control and safety functions of the condensing units. Microprocessor is simple to use, push button keyboard allows to access the operating conditions, control set points and alarm history clearly displayed on a multi-line backed illuminated LCD panel. Also its compatible with building management system and adoptable to LON protocol.
H. CIRCUIT BREAKER
Protect against compressor & condenser fans branch circuit fault. When tripped (Manually or automatically), the breaker opens the power supply to the compressor and control circuit through auxiliary contacts.
I. PRESSURE GAUGES
Suction, discharge and oil (semi hermetic compressor only) pressure gauges.
STANDARD FEATURES/OPTIONS
DESCRIPTION Dual scroll compressor (for CDX020 - CDX070 only) Semi-hermetic compressor (for CDX020 - CDX070 only) Dual semi-hermetic compressor (for CDX080 - CDX090 only) Quadruple semi-hermetic compressor (for CDX110 & above) Capacity control for semi-hermetic compressor on lead compressor Compressor crankcase heaters Compressor circuit breakers Compressor overload protection Spring isolators with vibration eliminators for semi-hermetic compressor Compressor shut-off valves for scroll compressor Condenser fan motor, totally enclosed air-over type Condenser fan - direct drive, propeller type Condenser fan guard UVM (Under Voltage Monitor relay) Filter drier (sealed type) for scroll compressor units Filter drier (replaceable type) for semi-hermetic compressor units Sight glass (moisture indication) High/low pressure switch (fixed type) High/low pressure switch (adjustable type) Fan cycling (low ambient) Pump down solenoid valve Pressure relief valve Suction & discharge pressure gauges for scroll compressor Suction, discharge & oil pressure gauges for semi-hermetic compressor PIII controller Microsmart controller Coil guard Aluminum fins condenser coil Copper & coated fins condenser coil Thermo-guard coating on aluminum/copper coil Hot gas bypass Liquid line isolating valves Status indicator (Volt free contact) Discharge line muffler (for semi-hermetic compressor units) Thermostat controller (for 1 or 2 compressor models only) STANDARD FEATURES OPTION
PHYSICAL DATA
SCROLL COMPRESSORS
MODEL NUMBER NOMINAL CAPACITY , TONS* NUMBER OF REFRIGERATION CIRCUIT COMPRESSOR Type Oil per system (liters) Refrigerant Charge per system (oz)** CONDENSER FAN Type Qty. Diameter (inch) Nominal CFM Motor HP RPM CONDENSER COIL Type 2 30 15000 2 30 15000 2 32 22078 4 30 30000 400 470 580 760/580 3.25 3.25 4.14 4.67/4.14 CDX020 21.6 Dual CDX025 26.6 Dual CDX031 32.7 Dual CDX035 37.4 Dual CDX040 42.1 Dual Scroll 4.67 R-22 760 Propeller 4 30 30000 4 30 30000 4 30 30000 4 32 47796 4 32 50124 2 1100 900/760 900 1190/900 1190 5.91/4.67 5.91 6.3/5.91 6.3 CDX045 47.4 Dual CDX050 52.2 Dual CDX060 CDX070 59.2 Dual 65.6 Dual
1.5 1100 1.5 1100 2 1100 1.5 1100 1.5 1100 1.5 1100 1.5 1100 2 1100 Inner grooved tubes and enhanced fins
Tube DiaRowsFins per inch 3/8314 3/8414 3/8414 3/8214 3/8314 3/8314 3/8414 3/8314 3/8314 3/8414 3/8314 Total face area (Sq. ft.) HIGH PRESSURE SWITCH Open (PSIG) Close (PSIG) LOW PRESSURE SWITCH Open (PSIG) Close (PSIG) REFRIGERANT LINES+ Suction line size (OD), inch Liquid line size (OD), inch 30 36 36 60 60 72 72 75 88
450 10 450 10 450 10 450 10 450 10 450 10 450 10 450 10 450 10 360 15 360 15 360 15 360 15 360 15 360 15 360 15 360 15 360 15 25 5 50 5 1-3/8 5/8 25 5 50 5 1-3/8 5/8 25 5 50 5 1-3/8 5/8 25 5 50 5 1-5/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 2-1/8 7/8 25 5 50 5 21/8 7/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ 70.1/66.6/61.3 70.1/66.6/61.3 71.6/68.1/62.8 74/70.5/63.5 74.7/71.2/65.9 75.2/71.7/66.4 75.7/72.2/66.9 76.7/73.2/67.9 77.3/73.7/68.5 OPERATING WEIGHT, Kg.+++ 711 692 793 1100 1166 1299 1385 1482 1526
NOTES: * Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures. ** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping. + Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size. ++ Based on free field area at ARI conditions. Tolerance: 2dBA. +++ Values indicated are for standard unit with aluminum fin condenser coils.
10
PHYSICAL DATA
SEMI-HERMETIC RECIPROCATING COMPRESSORS (OPTIONAL)
MODEL NUMBER NOMINAL CAPACITY , TONS* NUMBER OF REFRIGERATION CIRCUIT COMPRESSOR Type Oil per system (liters) Refrigerant Charge per system (oz)** CONDENSER FAN Type Qty. Diameter (inch) Nominal CFM Motor HP RPM CONDENSER COIL Type 2 30 15000 2 32 23590 2 32 22078 4 30 30000 840 990 1180 660 4 4 4.3 CDX020 23.2 Single CDX025 27.5 Single CDX031 CDX035 32.8 Single 36.6 Dual CDX040 41.5 Dual CDX045 46.4 Dual CDX050 51 Dual CDX060 CDX070 60.5 Dual 65.4 Dual
Semi-hermetic reciprocating 3.6 4/3.6 R-22 840/660 Propeller 4 30 30000 4 30 30000 4 32 41684 4 32 46300 2 1100 4 32 50124 2 1100 840 990/840 1180/990 1180 4 4 4.3/4 4.3
2 1100 1.5 1100 1.5 1100 1.5 1100 2 1100 Inner grooved tubes and enhanced fins
Tube DiaRowsFins per inch 3/8414 3/8314 3/8414 3/8314 3/8414 3/8414 3/8414 3/8414 3/8314 3/8314 3/8314 3/8314 Total face area (Sq. ft.) HIGH PRESSURE SWITCH Open (PSIG) Close (PSIG) LOW PRESSURE SWITCH Open (PSIG) Close (PSIG) REFRIGERANT LINES+ Suction line size (OD), inch Liquid line size (OD), inch 30 36 36 60 60 60 60 75 88
450 10 450 10 450 10 450 10 450 10 450 10 450 10 360 15 360 15 360 15 360 15 360 15 360 15 360 15 25 5 50 5 2-1/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 1-5/8 7/8 25 5 50 5 2-1/8 7/8 25 5 50 5 2-1/8 7/8 25 5 50 5 2-1/8 7/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ 69.2/65.7/60.4 70.2/66.7/61.4 70.2/66.7/61.472.2/68.7/63.4 72.2/68.7/63.4 72.2/68.7/63.4 73.2/69.7/64.4 73.2/69.7/64.4 73.2/69.7/64.4 OPERATING WEIGHT, Kg.+++ 720 737 783 1149 1174 1191 1226 1270 1387
NOTES: * Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures. ** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping. + Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size. ++ Based on free field area at ARI conditions. Tolerance: 2dBA. +++ Values indicated are for standard unit with aluminum fin condenser coils.
11
PHYSICAL DATA
SEMI-HERMETIC RECIPROCATING COMPRESSORS
MODEL NUMBER NOMINAL CAPACITY , TONS* NUMBER OF REFRIGERATION CIRCUIT COMPRESSOR Type Oil per system (liters) Refrigerant Charge per system (oz)** CONDENSER FAN Type Qty. Diameter (inch) Nominal CFM Motor HP RPM CONDENSER COIL Type Tube DiaRowsFins per inch Total face area (Sq. ft.) HIGH PRESSURE SWITCH Open (PSIG) Close (PSIG) LOW PRESSURE SWITCH Open (PSIG) Close (PSIG) REFRIGERANT LINES+ Suction line size Dual (OD), inch Quadruple Liquid line size (OD), inch Dual Quadruple 3/8414 105 450 10 360 15 25 5 50 5 2-1/8 N.A. 1-1/8 N.A. 3/8414 100 450 10 360 15 25 5 50 5 2-1/8 N.A. 1-1/8 N.A. 4 32 50388 2 1100 6 32 63666 2 1100 6 32 69174 2 1100 1420 1710 980 7.4 7.4 CDX080 79 Dual CDX090 94 Dual CDX110 109 Quadruple CDX130 130 Quadruple CDX140 142 Quadruple CDX150 157 Quadruple CDX190 187 Quadruple
Semi-hermetic reciprocating 4 4.3 R-22 1170 Propeller 8 32 99096 2 1100 8 32 90280 2 1100 8 32 97896 2 1100 10 32 117390 2 1100 1280 1415 1685 4.7 7.4 7.4
Inner grooved tubes and enhanced fins 3/8414 120 450 10 360 15 25 5 50 5 N.A. 1-5/8 N.A. 7/8
75/71.5/66.2
73.3/69.8/64.5 75.1/71.6/66.3
1940
2275
2912
3164
3276
3792
4056
NOTES: * Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures. ** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping. + Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size. ++ Based on free field area at ARI conditions. Tolerance: 2dBA. +++ Values indicated are for standard unit with aluminum fin condenser coils.
12
SELECTION PROCEDURE
1. Enter performance tables at specified SST and desired ambient conditions to find gross capacity and power input. 2. HEAT REJECTION: Calculate condenser Total Heat Rejection Capacity as follows: HR = Unit cooling capacity + (3.41 x Total Unit Power Input, Watts). 3. HEAD PRESSURE: To determine head pressure (psig) use the following conversion table:
Condensing Temp. - 0F. (R-22) Head Pressure - PSIG. 100 195.9 110 226.4 120 259.9 130 296.9 140 337.3 150 381.6 160 429.8
13
1150F TC (MBH)
0
TC (MBH)
CDX020
230.4
CDX025
283.2
CDX031
373.1
CDX035
397.2
35 0F
CDX040
446.4
CDX045
520.0
CDX050
591.6
CDX060
645.6
CDX070
693.6
CDX020
250.8
CDX025
308.4
CDX031
390.0
CDX035
433.2
40 0F
CDX040
488.4
14
117 115 116 116 116 116 115 115 64.3 852.0 124 70.0 59.2 776.4 123 64.4 45.9 51.9 624.0 692.4 125 126 50.3 56.7 40.8 549.6 125 44.7 520.8 590.0 654.0 736.8 811.2 36.3 487.2 125 39.9 462.0 33.6 435.2 125 36.4 410.0 25.3 346.8 126 27.8 327.6 135 134 134 134 135 135 133 134 30.6 39.6 44.0 49.3 55.3 62.2 70.3 76.3
45 0F
CDX045 CDX050 CDX060 CDX070 CDX020 CDX025 CDX031 CDX035 CDX040 CDX045 CDX050 CDX060 CDX070 CDX020 307.2 382.0 434.4 489.6 555.6 614.4 694.8 768.0 144 143 144 144 144 145 142 143
555.6 618.0 692.4 759.6 273.6 336.0 416.3 471.6 531.6 598.0 661.2 748.8 829.2 297.6
111 112 110 111 114 114 113 114 114 114 114 112 113 117
43.4 48.7 56.0 60.9 20.4 24.8 32 35.5 39.7 44.5 49.9 57.7 63.2 20.9
526.8 585.6 658.8 724.8 259.2 319.2 395.4 448.8 505.2 568.0 626.4 710.4 787.2 282.0
121 121 120 120 124 124 122 123 123 123 124 121 122 126
47.7 53.6 61.2 67 22.5 27 35.2 38.8 43.6 49 54.8 62.6 68.2 23.0
498.0 552.0 624.0 688.8 244.8 302.4 371.7 424.8 477.6 537.6 591.6 668.4 739.2 266.4
131 131 129 130 133 133 131 132 132 133 133 131 131 135
52.5 59.0 67.3 73.4 24.9 30.0 38 43 48.1 54 60.0 67.5 72.6 25.4
466.8 520.0 588.0 651.6 230.4 284.4 345.4 398.4 448.8 505.2 556.8 622.8 682.8 249.6
140 141 139 140 142 142 140 142 142 142 142 140 140 144
57.9 65 74.1 81.4 27.4 33 41.9 47.6 53.3 59.2 66.0 72.3 76.5 28.0 33.9 43.1 48.6 54.6 61.0 68.4 76.8 83.2
434.4 484.8 552.0 613.2 214.8 265.2 316.6 372.0 417.6 471.6 520.8 573.6 620.4 232.8 285.6 352.0 405.6 458.4 519.6 574.8 652.8 723.6
150 150 148 149 152 152 150 151 151 151 152 149 149 154 154 152 153 153 153 154 152 152
63.9 70.9 81.9 91 30 36.7 45.7 52.6 59.0 65.2 72.5 77.1 80.0 30.8 37.4 46.9 53.7 60 67.2 75.0 84.0 90.9
CDX025
364.8
CDX031
457.8
CDX035
512.4
50 0F
CDX040
577.2
CDX045 CDX050
656.4 729.6
CDX060
814.8
CDX070
892.8
NOTE: In CDX035,CDX045 & CDX060, there is two different compressors in each unit. System 1 have 55% from total capacity.
LEGEND:
CT - Condensing Temperature
PI
1150F TC (MBH)
0
TC (MBH)
CDX020 CDX025
247 293
CDX031
352
CDX035
391
CDX040
443
CDX045
494
35 F
CDX050 CDX060
542 647
CDX110
1148
CDX130
1397
CDX140
1502
CDX150
1672
CDX190 CDX020
2003 271
CDX025 CDX031
322 356
CDX035
428
CDX040
485
CDX045
541
15
CDX050
595
40 F
CDX060
708
CDX070 CDX080
767 924
CDX090
1104
CDX110
1260
CDX130
1528
CDX140
1649
CDX150
1832
CDX190
2194
NOTE: In CDX040,CDX050 & CDX060, there is two different compressors in each unit. System 1 have 55% from total capacity.
LEGEND:
CT - Condensing Temperature
PI
1150F TC (MBH)
0
TC (MBH)
CDX020 CDX025
295 352
CDX031
391
CDX035
468
CDX040
530
CDX045
592
45 F
CDX050 CDX060
650 773
CDX110
1379
CDX130
1663
CDX140
1805
CDX150
2003
CDX190 CDX020
2394 322
CDX025 CDX031
383 427
CDX035
510
CDX040
577
CDX045
643
16
CDX050
708
50 0F
CDX060
841
CDX070 CDX080
907 1103
CDX090
1313
CDX110
1505
CDX130
1806
CDX140
1968
CDX150
2184
CDX190
2604
NOTE: In CDX040,CDX050 & CDX060, there is two different compressors in each unit. System 1 have 55% from total capacity.
LEGEND:
CT - Condensing Temperature
PI
MODEL NUMBER
SUPPLY VOLTAGE
Min.
CDX020
CDX025
CDX031
CDX035
CDX040
CDX045
CDX050
17
CDX060
CDX070
Nominal (V-Ph-Hz) 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 105.3 58.74 48.6 116.78 60.76 49.5 137.8 93.55 68.95 180.15 103.35 80.6 204.75 106.45 86.4 220 123.7 96.95 232 137.33 104.75 238.6 138.68 115.08 245 140.08 122.38 140 80 70 160 80 70 190 130 90 260 140 110 280 150 120 320 190 140 320 190 140 340 190 170 340 190 170 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 240 380 460 240 380 480 240 380 480 240 380 480 240 380 480 240 380 480 240 380 480 240 380 480 240 380 480 RLA (each) 42 23.5 19.2 47.1 24.4 19.6 56.8 39 27.8 81.4/56.8 42.1/39 33.6/27.8 81.4 42.1 33.6 93.6/81.4 55.7/42.1 41.4/33.6 93.6 55.7 41.4 100/93.6 57.1/55.7 48.7/41.4 100 57.1 48.7 LRA (each) 30 18 13.1 30 18 13.1 16 9.5 11.1 30 18 13.1 30 18 13.1 30 18 13.1 30 18 13.1 16 9.5 11.1 16 9.5 11.1 CB (Qty.) 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 LRA (each) 239 145 125 245 145 125 425 239 187 505/425 280/239 225/187 505 280 225 605/505 353/280 272/225 605 353 272 605/599 358/353 310/272 599 358 310 FLA (each) 5.4 2.93 2.7 5.4 2.93 2.7 5 2.9 3.2 5.4 2.93 2.7 5.4 2.93 2.7 5.4 2.93 2.7 5.4 2.93 2.7 5 2.9 3.2 5 2.9 3.2 Total Watts 90 90 90 90 90 90 90 90 90 120/90 120/90 120/90 120 120 120 150/120 150/120 150/120 150 150 150 150 150 150 150 150 150 OUTPUT POWER 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 Total Amps 0.38 0.24 0.19 0.38 0.24 0.19 0.38 0.24 0.19 0.50/0.38 0.32/0.24 0.25/0.19 0.50 0.32 0.25 0.63/.50 0.39/0.32 0.31/0.25 0.63 0.39 0.31 0.63 0.39 0.31 0.63 0.39 0.31
187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414
LEGEND:
MCA
RLA
LRA
FLA
CB
- Circuit Breaker
MODEL NUMBER
SUPPLY VOLTAGE
Min.
CDX020
CDX025
CDX031
CDX035
CDX040
CDX045
CDX050
18
599.3 330.05 281.03 679 438.28 372.85 820 530 450 730 400 340 4 4 4 4 4 4 131.6 72.2 60.1 148 96.3 80.2 611 332 292 803 436 383 8 8 8 10 10 10 RLA - Rated Load Amps 5 2.9 3.2 5 2.9 3.2 MOCP - Maximum Over Current Protection
CDX060
CDX070
CDX080
CDX090
CDX110
CDX130
CDX140
105.8 57.8 48.78 120 66.05 56.65 160.29 88.18 75.03 157.59 86.3 72.9 177.04 96.8 81.78 192.6 105.2 88.88 206 113.45 97.75 258.29 142.18 121.63 290.52 159.88 136.33 316.1 174.05 148.03 363 234.08 199.65 404 222.25 190.05 550.98 303.28 258.93 470.1 287.98 240.65 16 9.5 11.1 16 9.5 11.1 2 2 2 2 2 2 LRA - Locked Rotor Amps 4 4 4 6 6 6 240 240 240 240 240 240 FLA - Full Load Amps 200 200 200 200 200 200 0.84 0.84 0.84 0.84 0.84 0.84 CB - Circuit Breaker
180 100 80 200 110 90 280 150 130 210 120 100 250 130 110 260 140 120 290 160 130 370 200 170 410 220 190 440 240 200 510 330 280 490 270 230 670 370 310 570 350 290
1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4
RLA (each) 76 41.6 34.7 88 48.2 40.2 120.23 65.9 54.9 60.44 33.2 27.6 76/60.44 41.6/33.2 34.7/27.6 76 41.6 34.7 88/76 48.2/41.6 40.2/34.7 120.23/88 65.9/48.2 54.9/40.2 120.23 65.9 54.9 131.6 72.2 60.1 148 96.3 80.2 88 48.2 40.2 120.23 65.9 54.9 101.2 62.3 50.6 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 6 6 6 6 6 6 8 8 8 8 8 8 LRA (each) 30 18 13.1 16 9.5 11.1 16 9.5 11.1 30 18 13.1 30 18 13.1 30 18 13.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 16 9.5 11.1 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 CB (Qty.) 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4
LRA (each) 419 228 200 447 243 213 611 332 292 374 203 178 419/374 228/203 200/178 419 228 200 447/419 243/228 213/200 611/447 332/243 292/213 611 332 292 611 332 292 803 436 383 447 243 213 611 332 292 600 333 262 FLA (each) 5.4 2.9 2.7 5 2.9 3.2 5 2.9 3.2 5.4 2.9 2.7 5.4 2.9 2.7 5.4 2.9 2.7 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 5 2.9 3.2 Total Watts 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 200 200 200 200 200 200 100 100 100 100 100 100 200 200 200 Total Amps 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.42 0.84 0.84 0.84 0.84 0.84 0.84 0.42 0.42 0.42 0.42 0.42 0.42 0.84 0.84 0.84
OUTPUT POWER 1.5 1.5 1.5 2 2 2 2 2 2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
CDX150
CDX190
Nominal (V-Ph-Hz) 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506
187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414
DIMENSIONS
CDX 020 & CDX 025
CDX 031
19
DIMENSIONS
CDX 035, CDX 040, CDX 045 & CDX 050
20
DIMENSIONS
CDX 080
CDX 090
21
DIMENSIONS
CDX 110
22
DIMENSIONS
CDX 190
23
HVTB L1 L2 L3
PLEASE REFER TO SHEET 2 OF 2 FOR CONDENSER FAN MOTOR POWER CONNECTIONS.
CC1 OLR1
T2A
COMP 1 ATB
T3A
UVM CONNECTION
L1 L2 L3
F1
L1 SEE VFC PLEASE REFER CONNECTION (SHEET 2 OF 2) FAN MOTOR CONTROL CONNECTION, TO (SHEET 2 OF 2) FR1
L2 UVM-1 8
L3
UVM
TO ATB
TO ATB
TO PDS1 CC1
TO ATB 1A
(REMOVE JP1)
41A
4A
3A
OUTFAN2
OUTFAN1
HEATER2
NEUTRAL
HEATER1
COMP2
INFAN
COMP1
LVTB ( NOTE 7)
R C G Y1 JP
24Vac
X2
X1
P2
P1
R C G Y1 Y2 W1 W2 STG1 COOLING
R C Y1
LIVE
ECB
SQMBO4 ( P III )
Y2 W1 W2
ON/OFF
PRI
FUSE
P3_##
(ON/OFF)
21A 27A
OLR1-1 24A
HPS1
P
SEC
22A 23A
LPS1
P
TO POWER SUPPLY L1 L2 L3
TO POWER SUPPLY L1 L2 L3
TO POWER SUPPLY L1 L2 L3
LVTB ( NOTE 8)
24Vac
R C G
R C G Y1 W1 W2
CB L1C L2C L3C CB11 71B 72B 71A 72A 73A 73B CB12
Y1 Y2 W1 W2
BMC HC2 68 69 70 OLR TO ATB (in cond. unit) TO ECB (in cond. unit) INFAN HTR1 HTR2 CONTROLS 230Vac
HC1
T1H
T2H
T3H
T1F
T2F
T3F
14 29 30
BMC
19
OLR-1 AFS
HC2
28
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
24
LEGEND AHU AFS AR ATB BM BMC CC CCA CB C. HTR COMP ECB F FCS FM FMC FMCA FR HC HPS HVTB JP L1 L2 L3 LPS LUG NTB OLR OPS P PDS
2
FMC2
FMC1
FMC2
FM1
FM2
FM1 FM2 FM1 T.O.P FM2 T.O.P
ECB
13A 13B
FMC1 FMC2
12A
11A
13A
13B
FMC1 FMC2
ATB 2
12B
11B
10B FCS2
P
OPTIONAL CONNECTIONS
COMP. WITH CB CONNECTION
TO HVTB L1 L2 L3 1
AIR HANDLING UNIT AIR FLOW SWITCH AUXILIARY RELAY AUXILIARY TERMINAL BLOCK BLOWER MOTOR BLOWER MOTOR CONTACTOR COMPRESSOR CONTACTOR CC AUXILIARY CONTACT CIRCUIT BREAKER CRANKCASE HEATER COMPRESSOR ELECTRONIC CONTROL BOARD FUSE FAN CYCLING SWITCH FAN MOTOR (CONDENSER) FAN MOTOR CONTACTOR FMC AUXILIARY CONTACT FAULT RELAY HEATER CONTACTOR HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK JUMPER LINE 1 LINE 2 LINE 3 LOW PRESSURE SWITCH LUG GROUND NEUTRAL TERMINAL BLOCK OVER LOAD RELAY OIL PRESSURE SWITCH PRESSURE PUMP DOWN SOLENOID DIP SWITCH (IN ECB) SOLID STATE PROTECTION SYSTEM FM THERMAL OVERLOAD PROTECTION COMP. UNLOADER SOLENOID UNDER VOLTAGE MONITOR FIELD WIRING TERMINAL BLOCK OR TERMINATION POINT SPLICE-CLOSED END
101 36B
101
100
102
35B
100
35A
36A
37A
CC1A-1B
100A
C.HTR1
CB1
37B 45
102
L1A
L2A
L3A
43
44
24A
S SSPS TOP UL
T1A
T2A
T3A
COMP 1
(SEE NOTE 5)
(REMOVE JP3)
FR1-2A CC1A-2A
TRANS TRANSFORER
56 58
55 2 COMP1 ON
UVM
28A
5A
NC
UL1
___
CB1A-1A 3A
8A
CC1
LPS5
C P
NO
NC
COMP2
COMP1
ECB
NOTE UL3 CONNECTION APPLICALBLE FOR COMP WITH 3 STEPS CAPACITY UNLOADING.
17 31A AR8
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY. 3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 5. COMPRESSOR IS PROVIDED WITH SSPS OR INTERNAL LINE BREAK THERMAL OVERLOAD PROTECTION. 6. IF PDS IS FACTORY INSTALLED, PLEASE READ BROKEN LINES AS CONTINUOUS LINES. 7. USE SHIELDED TYPE CABLE, #18 AWG (MIN.) FOR LVTB FIELD WIRING. GROUND CONNECT AT BOTH ENDS. 8. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
7E
AR8-1
7F
HGS
P2
P1
ECB
( NOTE 6)
CLOSE (PSIG)
50 5 45 55 360 15 290 15
note: Set dip switch #3 according to unit's option (pump down or no pump down)
25
5A
LPS5NO
C P NC
5A AR8-1
6D
AR9-1
6C
HGS
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
26
TRANS TRANSFORER
___
CONDENSER FAN MOTOR POWER, CONTROL CONNECTIONS : WITH STANDARD AND FAN CYCLING OPTION
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY. 3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL.
CB6
CB7
CB8
100
101
102
103
104
105
107
108
FMC6
FM1
FM3
FM2
FM4
FM5
FM6
TO ECB1 OUTFAN 1
12A
FM1 T.O.P
13A
FMC1 2 FMC5 2
TO ECB1 OUTFAN 2
12B
FM2 T.O.P
13B
FMC2 2 FMC6 2
12E FMC1A-1
FM5 T.O.P
13E
12F FMC2A-1
FM6 T.O.P
5. COMPRESSORS ARE PROVIDED WITH SSPS OR INTERNAL LINE BREAK THERMAL OVERLOAD PROTECTION. 6. IF PDS IS FACTORY INSTALLED, PLEASE READ BROKEN LINES AS CONTINUOUS LINES. 7. USE SHIELDED TYPE CABLE, #18 AWG (MIN.) FOR LVTB FIELD WIRING. GROUND CONNECT AT BOTH ENDS.
2
13F
** 1 **
12C FMC5A-1
FM3 T.O.P
13C
FMC3 2
** 1 **
12D FMC6A-1
FM4 T.O.P
13D
FMC4 2
FMC1A-1
FMC2A-1
FMC5A-1
P
11B
12D
FM4 T.O.P
13D
FMC4
FMC6A-1
8. COOLING OUTPUT SIGNAL FROM CONTROLLER SHOULD FOLLOW THE SEQUENCE: ON SEQUENCE - Y1 FIRST, THEN Y2. OFF SEQUENCE - Y2 FIRST, THEN Y1. 9. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
27
L1A
L2A
L3A
L1B
L2B
L3B
L1C
L2C
L3C
L1D
L2D
CB1
CB2
CB3
CB4
UVM CONNECTION
L1 L2 L3 COMP 1 COMP 2 COMP 3 COMP 4
L1 L2 L3 1 UVM-1 8 TO ATB 1
UVM
COMP. 2: COMP. 3:
1 1 1
TO ATB 1A
(REMOVE JP1)
COMP. 4:
TO HVTB L1
TO NTB N ATB
C.HTR1
ATB 1 JP1 1A JP2 1B PDS2 SEE VFC CONNECTION (sheet 1 of 2) TO ATB SEE FM CONNECTION TO TO (sheet 1 of 3) FR2 FR1 PDS1
C.HTR2
C.HTR3
C.HTR4
41B
41A
4B
4A
3B
OUTFAN2
OUTFAN1
HEATER2
NEUTRAL
HEATER1
3A
COMP2
INFAN
COMP1
TB1
X2
X1
P2
P1
R C G Y1
JP
15 17 31A 31B
R C
G
Y1
Y1 Y2
Y3 Y4
LIVE
ECB1
SQMBO4 ( P III )
Y2 W1 W2
ON/OFF
YR3 YR4
Y2
31C 31D Y3 Y4
PRI
FUSE
P3_##
(ON/OFF)
OLR1-1 24A OLR2-1 24B JP4 25B JP6 26B JP3 25A JP5 26A
HPS1
P
HPS2
P
LPS1
P
SEC
LPS2
P
TO FR4
TO FR3
(NOTE 5)
41D
41C
4D
4C
3D
3C
OUTFAN2
OUTFAN1
HEATER2
NEUTRAL
HEATER1
COMP2
INFAN
COMP1
X2
X1
P2
P1
R C G Y1 JP
15B
31C 31D
L1/MP/L
LIVE
ECB2
SQMBO4 ( P III )
Y2 W1 W2
ON/OFF
PRI
FUSE
P3_##
(ON/OFF)
OLR3-1 24C OLR4-1 24D JP8 25D JP10 26D JP7 25C JP9 26C
HPS3
P
HPS4
P
L1/MP/L
(REMOVE JP8)
LPS3
P
SEC
LPS4
P
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
28
CDX110
L1 L2 L3 L1 L2 L3 L1 L2 L3
CB6
CB7
12E FMC1A-1
FM5 T.O.P
13E
12F
FM6 T.O.P
13F
100
101
102
103
104
105
FMC6
** 1 **
12C FMC5A-1
FM3 T.O.P
106
107
108
1 **
12D FMC6A-1
FM4 T.O.P
13D
FMC4 2
FM1
FM3
FM2
FM4
FM5
FM6 1
13C
FM3 T.O.P
11B
P
FMC6A-1 10D
13D
FMC4 2
FCS4
P
11D
CONTROL PANEL
CDX130~150
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
CB9
FMC1
FMC2
FMC3
FMC4
13A
12C
12C
FMC1
13B
12D
12D
FMC2 2
FM5 T.O.P
13E
12G
FM7 T.O.P
12H
FMC3 2
FM6 T.O.P
13F
12H
FM8 T.O.P
12H
FMC2 2
35H
36H
35G
36G
37G
35E
36E
37E
35F
36F
35C
36C
37C
35D
36D
37D
35A
36A
37A
35B
36B
37B
37F
FM1
FM3
FM2
FM4
FM5
FM7
FM6
FM8
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS : WITH FAN CYCLING OPTION
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
37H
CDX130~150
8-FAN MOTOR LAYOUT
CB9
CONTROL PANEL
TO ECB1 OUTFAN 1 12A FM1 T.O.P 13A FMC1 2 FMC3 2 FMC7 2 FMC5 2 TO ECB2 OUTFAN 2 TO ECB2 OUTFAN 1 12B FM2 T.O.P 13B FMC2 2 FMC4 2 FMC8 2 FMC6 2 10A TO ECB1 OUTFAN 2 FCS1 11A 12C
P
CB6
CB7
CB8
100
101
102
103
104
105
106
107
108
109
110
111
FM3 T.O.P
13C
10B
FM4 T.O.P
13D
12G
FM5 T.O.P
13G
12H
FM6 T.O.P
13H
FM1
FM3
FM2
FM4
FM5
FM7
FM6
FM8
10C FCS3 11C 12E
P
FM7 T.O.P
13E
10D
FM8 T.O.P
13F
L1 L2 L3
L1 L2 L3
L1 L2 L3
L1 L2 L3
L1 L2 L3
L1 L2 L3
CDX190
10-FAN MOTOR LAYOUT
CB10
CONTROL PANEL
TO ECB1 OUTFAN 1 12A TO ECB1 OUTFAN 2 2 TO ECB2 OUTFAN 2 2 12H 12B
FMC1
FMC2
FMC3
FMC4
FMC5
FMC6
FM1 T.O.P
13A
12C
FM3 T.O.P
12C
FMC1
FM2 T.O.P
13B
12D
FM4 T.O.P
12D
FMC2 2
FM7 T.O.P
13G
12I
FM9 T.O.P
13I
FMC3
FM8 T.O.P
13H
12J
FM10 T.O.P
12J
FMC4 2
35F
36F
35H
36H
35G 36G
37G
37H
35E
36E
35C
36C
37C
35D
36D
37D
35A
36A
37A
35B
36B
37B
37E
36J
35J
37J
35I
36I
37I
37F
FMC1A-1
FM1
FM3
FM2
FM4
FM7
FM9
FM8
FM10
FM5
FM6
** 1
FMC3A-1
12E
FM5 T.O.P
** ** 1
12F FMC4A-1
FM6 T.O.P
13F
FMC6 2
**
**
13E
13F
11B
P
11D
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
29
LEGEND AHU AFS AR ATB BM BMC CC CCA CB C. HTR COMP ECB F FCS FM FMC FMCA FR HC HPS HVTB JP L1 L2 L3 LPS LUG NTB OLR OPS P PDS S AIR HANDLING UNIT AIR FLOW SWITCH AUXILIARY RELAY AUXILIARY TERMINAL BLOCK BLOWER MOTOR BLOWER MOTOR CONTACTOR COMPRESSOR CONTACTOR CC AUXILIARY CONTACT CIRCUIT BREAKER CRANKCASE HEATER COMPRESSOR ELECTRONIC CONTROL BOARD FUSE FAN CYCLING SWITCH FAN MOTOR (CONDENSER) FAN MOTOR CONTACTOR FMC AUXILIARY CONTACT FAULT RELAY HEATER CONTACTOR HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK JUMPER LINE 1 LINE 2 LINE 3 LOW PRESSURE SWITCH LUG GROUND NEUTRAL TERMINAL BLOCK OVER LOAD RELAY OIL PRESSURE SWITCH PRESSURE PUMP DOWN SOLENOID DIP SWITCH (IN ECB) SOLID STATE PROTECTION SYSTEM FM THERMAL OVERLOAD PROTECTION COMP. UNLOADER SOLENOID UNDER VOLTAGE MONITOR FIELD WIRING TERMINAL BLOCK OR TERMINATION POINT SPLICE-CLOSED END
AR1
FR1-2A
45
46
55 COMP1 ON
56
58
65 COMP3 ON
66
68
FR2-2A
43
60 COMP2 ON
61
63
70
73
COMP2 TRIP
5A
NC
UL1
LPS9 NO 6A
P NC
UL5
31B
17A
COMP 2
TO ATB 28B
28B
LPS6 NO
C
5B
P NC
UL2
LPS5 NO
C
6E
P NC
AR8-1
6D
AR9-1
6C
HGS
LPS10 NO
C
6B
P NC
UL6
5A AR8-1
6D
AR9-1
6C
HGS
COMP 3
TO ATB 28C
28C
LPS7
C P
NO
5C
NC
UL3
LPS11 NO
C
NOTE: COMP1 SHOULD ALWAYS BE LEAD COMPRESSOR. DIP SWITCH S2 SHOULD ALWAYS BE SET TO "ON" POSITION.
6C
P NC
UL7
COMP 4
TO ATB 28D
28B
LPS8 NO 5B
P NC
UL4
LPS12 NO
C
6B
UL8
NC P NOTE UL3 & UL 4 CONNECTION APPLICALBLE FOR COMP WITH 3 STEPS CAPACITY UNLOADING.
SSPS TOP UL
2 26A
2 26D
COMP 2 CC2A-1A
COMP 4
240
2 26B
CC4A-1A
240
2 26D
___
25B
25C
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY. 3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 5. COMPRESSOR MOTORS ARE PROVIDED WITH SSPS OR INTERNAL LINE BREAK THERMAL OVERLOAD PROTECTION. 6. USE DISCONNECT TAB + OR SPLICE ONLY WHERE EVER REQUIRED FOR EXTENSION OF ORIGINAL WIRE. 7. AT COMP. LOCKOUT CONDITION (FAULT), VOLTAGE ACROSS TERMINAL X1, X2 OF ECB & ATB #2 IS 230VAC. ALSO, COMP. LOCKOUT LIGHT (RED) IS ON. 8. USE SHIELDED TYPE CABLE, #18 AWG (MIN.) FOR LVTB FIELD WIRING. GROUND CONNECT AT BOTH ENDS.
CB L1C L2C L3C BMC HC2 68 69 T1H T2H T3H 70 OLR CB11 71B 72B 71A 72A 73A 73B CB12
TB1 (ECB)
(REMOVE JUMPER JP)
LVTB ( NOTE 8)
R C G Y1 Y2 Y3
R C G Y1 Y2
24Vac
YR3 YR3
Y4 W1 W2 W1 W2
TO ATB (in cond. unit) TO ECB (in cond. unit) INFAN HTR1 HTR2
CONTROLS 230Vac
14 29 30
BMC
19
OLR-1 AFS
HC2
28
9. COOLING OUTPUT SIGNAL FROM CONTROLLER SHOULD FOLLOW THE SEQUENCE: ON SEQUENCE - Y1 FIRST, THEN Y2. OFF SEQUENCE - Y2 FIRST, THEN Y1. 10.NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
30
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS Hook rigging sling thru holes in base rail, as shown below. Holes in base rail are centered around the unit center of gravity. Center of gravity is not unit center line. Ensure center of gravity aligns with the main lifting point before lifting. Use spreader bar when rigging, to prevent the slings from damaging the unit. CAUTION All panels should be in place when rigging. Care must be taken to avoid damage to the coils during handling. Insert packing material between coils & slings as necessary.
LIFT
LIFT
31
INSTALLATION CLEARANCE
WALL
MODEL NUMBER
CDX020 - CDX031 1500 1500 1500 1500 1500 CDX035 - CDX050 1500 1500 2000 1500 1500 CDX060 - CDX190 2000 2000 3000 2000 2000
E
FIGURE - 2 CORNER WALL NOTE: 1. All dimensions are in mm. 2. If unit is installed in special pit, please observe the same tolerance for walls. Pit height should not exceed the unit height.
32
MOUNTING LOCATION
MODELS: CDX020 - CDX031
MODELS: CDX090
MODELS: CDX110
34
MODEL: CDX090
MODEL: CDX110
35
INSTALLATION
STEP-1: Check equipment and job site
Unpack unit and move to final location taking care not to damage the unit. Remove screws holding the unit to wooden pallet and after removing wooden pallet, refix the screws.
Sweat connection
Use refrigerant grade piping. Service valves are closed from factory when shipped and ready for brazing. After wrapping the service valve with a wet cloth, the piping set can be brazed to service valve using either silver rod or silfos rod brazing material. When brazing completed, refrigerant piping and indoor coil are now ready for leak testing. This check should also include all field and factory brazed joints. Warning: Relieve all pressure before refrigerant system repair or final unit disposal to avoid personal injury or death. Use service ports and open all valves.
36
ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements. Caution: Operation of the unit on improper power supply will result in damage to the unit. Note: Use copper wires of proper rating for all field wiring. Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death. B) Ground & power wires Connect power wires to terminal block per wiring diagram. Connect ground wire to the ground lug inside the control box. C) Control wiring between outdoor & indoor unit Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring).
STEP 2: START-UP
1) Energize crankcase heater for a minimum of 12 hours prior to the system start-up. To energize crankcase heater only, set thermostat to OFF position and close electrical disconnect switch to the outdoor unit. 2) Fully open liquid/suction service valves. 3) Close electrical disconnect switch to energize the system. 4) Set room thermostat to desired temperature.
SYSTEM DESIGN
THESE CONDENSING UNIT SYSTEM HAS BEEN DESIGNED BASED ON THE FOLLOWING: Intended for outdoor installation with free air intake and discharge. Minimum outdoor operating air temperature during cooling with low ambient operation option is 550F. Maximum outdoor operating air temperature during cooling is 1300F.
37