HINDUSTAN PETROLEUM CORPORATION LIMITED

TERMINAL / DEPOT AUTOMATION PROJECT

SPECIFICATION FOR MASS FLOW METERS Make Model Line Size Qty Service Flow Range Velocity Over range Type : : : : : : : : : As per approved vendor list W&M type approved, Vendor to Specify Refer BOQ Black Oil FO, LDO Up to max 1200 LPM Pipeline velocity Max 2 m/s 130% of max flow Microprocessor based Coriolis mass flow and density transmitter for custody transfer application Remote mounted SS 316 L To be sized by vendor Flow (Mass & Volume), Density SS 304 fully welded/ Aluminium

Transmitter type Wetted parts Tube size (sensor) Service Transmitter Body Material Process connection End connection Material Reducer & expander Matching flanges Mounting accessories Accuracy Mass 145 | 5 1 1

: : : : :

: :

RF, ANSI # 150 B16.5 SS 316

: : : : :

As per requirement Required Required

+/- 0.05%

HINDUSTAN PETROLEUM CORPORATION LIMITED


TERMINAL / DEPOT AUTOMATION PROJECT Volume Density Linearity Repeatability Local display & data to be shown on GUI +/- 0.05% +/-0.5 Kg/Cum +/- 0.15 % of the reading +/- 0.02% of flow rate & +/0.0002gm/cc for density 2 line, 16 characters, scroll touch screen Data to be displayed Volume flow (compensated) Mass flow Temperature, Density @ 15 Deg C Density @ ambient temperature Required for volume & Density (local & remote) as per relevant API & ASTM tables.

: : : :

Temperature Compensated output

Electrical Connection Power supply Power consumption Output

: : : : Vendor to specify Vendor to specify 1 nos. of 4 20mA with HART API MPMS Chapter11.1 for density, 1 no. frequency output/ 4-20 mA for mass flow rate 1 No RS 485 Modbus output configurable. RTD input for external temperature sensor To individual Batch Controllers Class 1, Div II, Group II A& B Weatherproof to IP67 & Explosion proof

Input Connectivity Area classification Housing Protection

: : : :

146 | 5 1 1

HINDUSTAN PETROLEUM CORPORATION LIMITED


TERMINAL / DEPOT AUTOMATION PROJECT Approval Calibration : : PESO & CMRI, W&M At FCRI or any other NABL approved lab acceptable to W&M. Lab Calibration is must for all the Meters including Master Meter before installation. Subsequently, yearly calibration at Lab or as & when required by W&M for the Master Meter W&M

Stamping
NOTE : 1. Density

is required to be transmitted to JDE at the time of truck loading andonly density of product flowing through the meter shall be considered. 2. Pressure drop across the metering assembly should not exceed 1 Kg/Sq Cm over the entire flow range

147 | 5 1 1