MSA FixedGasand FlameDetection Product Guide

Product Guide
TABLEOFCONTENTS
Section 1: Gas Monitors/ Sensors
Ultima X Series Gas Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7 Ultima X Series Sensor X-Change Program . . . . . . . . . . . . . . . . . . . . . . .8 Ultima XIR Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Ultima XL/XT Series Gas Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . .1011 Ultima XI Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Ultima MOS-5 Hydrogen Sulfide Sensor . . . . . . . . . . . . . . . . . . . . . .1314 UltraSonic EX-5 Gas Leak Detector . . . . . . . . . . . . . . . . . . . . . . . . . . .1516 Toxgard II Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Chemgard Series Infrared Gas Monitors . . . . . . . . . . . . . . . . . . . . . . . . . .18 MultiGard Gas Sampling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Ultima OPIR-5 Open Path Gas Detector . . . . . . . . . . . . . . . . . . . . . .2021 Chillgard RT Photoacoustic Infrared Refrigerant Monitor . . . . . . . . . .22 Chillgard LE Photoacoustic Infrared Refrigerant Monitor . . . . . . . . . .23 Chillgard LS Photoacoustic Infrared Refrigerant Monitor . . . . . . . . . .24 Chillgard LC Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Chillgard NH3 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Z Gard S Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Z Gard DS Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Z Gard COmbo Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

Section 3: Controllers
Suprema Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 Gasgard Family of Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 9010/9020 Controller Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40-41 ModCon 75 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 Z Gard CX Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 Z Gard C Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Z Gard C485 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45

Section 4: Fire and Gas Systems


Model 10K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48-49

Section 4: Custom Products & Accessories


MSA Custom Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52-53 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

Section 5: Calibration and Sensor Placement


Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56-57 Sensor Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58-59

Section 2: Flame Detectors


FlameGard 5 Series of Flame Detectors . . . . . . . . . . . . . . . . . . . . . . .3235

OurMission,YourSafety
MSAs mission is to ensure that men and women may work in safetyand that they, their families and their communities may live in health throughout the world. Our vision is to be the leading innovator and provider of quality safety and instrument products and services that protect and improve people's health, safety and the environment. Established in 1914, MSA is the world's leading manufacturer of safety products designed to protect people worldwide. Sophisticated safety products typically integrate any combination of electronics, mechanical systems and advanced materials to protect users against hazardous or life-threatening situations. With headquarters located in Pittsburgh, Pennsylvania, MSA employs approximately 4,500 associates. Our global manufacturing operations on five continents help protect lives in more than 140 countries.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
Product Market
GeneralIndustry combustible gas toxic gas oxygen flame HVAC Mechanical Rooms combustible gas toxic gas oxygen refrigerants Parking Garages combustible gas toxic gas oxygen oxygen refrigerants Public Transportation Facilities combustible gas toxic gas oxygen Oil,Gas&Petrochemical Process Areas combustible gas flame Analyzer Buildings combustible gas toxic gas oxygen Sulfur Recovery Unit toxic gas Tank Farm/ Spheres combustible gas flame Water&Wastewater Wet Wells combustible gas toxic gas oxygen Pumping Stations combustible gas toxic gas oxygen Digester Building combustible gas toxic gas oxygen UltimaX Series ZGard Series Chillgard Series ToxgardII Chemgard Multigard Ultima OPIR-5 FlameGard5

HowtoUseThisGuide
6 6 6 6 6 The table at left lists various monitoring applications within four markets: General Industry, HVAC, Water & Wastewater and Oil, Gas and Petrochemical, indicating the MSA products that are suitable for each. 1. Pick your market and application from the table at left. 2. Identify your products of interest. 3. Locate the product entries by using the Table of Contents p. 2. For more information on a product, or to obtain a datasheet, contact MSA Customer Service at 1-800-MSA-INST, or visit www.MSAnet.com and click on the Fixed Gas Detection icon.

6 6 6

6 6 6

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

6 6 6 6

6 6 6 6 6 6 6

Food Storage & Ammonia Refrigeration

6 6

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

6 6 6 6 6 6 6 6 6

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
MSA: The World Leader in Fixed Gas and Flame Detection
MSA oers a wide variety of permanent gas monitoring solutions to detect combustible gases, toxic gases, oxygen deficiency/enrichment. Our instruments reflect the latest developments in sensor and instrumentation design, using electrochemical, catalytic bead, ultrasonic, photoacoustic infrared and both point and open path infrared sensing technologies. We oer a wide range of systems to meet your facilitys monitoring needs: from a single sensor in a stand-alone application to a large-scale, completely computerized installation consisting of thousands of sensing points. MSA also designs custom systems that are tailored to fit unique monitoring requirements.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

MSAGAS MONITORS/SENSORS

MSA GAS MONITORS/SENSORS

sectionone

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

UltimaXSeriesGasMonitors

State-of-the-art detection for any gas need


Ultima X Series Gas Monitors, engineered using microprocessor-based technology for the detection of combustible and toxic gases and oxygen deficiency, provide HART Field Communications Protocol. HART protocol provides increased sensor data and convenient setup, calibration and diagnostics. It also enables existing wiring to be used, reducing installation costs. Features Patented sensor disconnect under power allows for sensor change-out without declassifying a hazardous area. Interchangeable smart sensors can be replaced in the field without the use of tools. The unit quickly recognizes the new sensor type and reconfigures alarm and relay settings to optimize the new sensor. State-of-the-art liquid crystal display conveniently alternates between sensor reading and gas type and features scrolling messaging, indicating ongoing diagnostic checks such as sensor "end-of-life" condition. World-class design features a single-board design for ultimate reliability and serviceability. The multiple-entry mounting enclosure has been designed to be separate from the electronics and sensor, allowing for problem-free installation and servicing. Onboard optional quick-check LEDs and 4 relay outputs allow for increased indication of alarm and fault conditions. 3Models: Ultima XE Monitor: Explosion-proof stainless steel gas detector with display Ultima XA Monitor: Water- and corrosionresistant, all-purpose, polycarbonate gas detector with display Ultima XIR Monitor: Explosion-proof stainless steel, infrared gas detector with display [Datasheet 07-2051]

UltimaX3 TechnologyfortheUltimaX SeriesGasMonitorsfeatures: Multi-sensing System can handle 93 sensors (up to 31 monitors with up to 3 sensors per monitor) Accepts any combination of electrochemical, catalytic and infrared sensors Scrolling display shows type and reading for all sensors Ultima X3 Monitor operates as a slave device on the network

Signal boost Each sensor can be observed remotely up to 3,000 ft. from the monitor Universal 85-256VAC or 7-30VDC power supply available at remote condulet ModBUS RTU Output Industry-standard format Provides an RS-485 half-duplex communication interface Integration into PLC/DCS systems

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
SENSORS
Specifications(forUltimaXE,UltimaXAandUltimaXIR) GasTypes XE, XA Combustibles, oxygen and toxics, XIR Combustibles; 0-100%LEL TemperatureRange -40C to +60C (-40F to +140F) (Typical-range for some gases may differ) Drift ZeroDrift XE, XA <5%/year, typical XIR 2%/year, typical SpanDrift XE, XA <10%/year, typical Noise <1% Full Scale Accuracy Repeatability XE, XA, XIR 1%Full Scale or 2ppm, typical Linearity XE, XA 2%Full Scale or 2ppm, (O2, CO) XIR 2%Full Scale (50% LEL) XE, XA 3%Full Scale (<50% LEL combustibles) XE, XA, XIR 5%Full Scale (>50% LEL combustibles) XE, XA 10%Full Scale or 2ppm, (non-CO toxics) ResponseTimes T20O2&toxics XE, XA <12 seconds (typically 6 seconds) T50O2&toxics XE, XA <30 seconds (typically 12 seconds) T50combust. XE, XA <8 seconds T90combust. XE, XA <30 seconds T90combust. XIR <2 seconds Humidity XE, XA 15%-95% RH, non-condensing XIR 0%-95% RH, non-condensing SensorLife Oxygen&Toxics XE, XA 2 years typical Combust. XE, XA 3 years typical Combust. XIR 5 years typical Warranty 1 year XE, XA; 2 years XIR; 10 yrs XIR, XI (IR source only) PowerInput XE, XA 7-30VDC (oxygen and toxics) XE, XA 7-30VDC @ 450mA maximum (combustibles) XIR 7-30VDC @ 750mA maximum (combustibles) WiringRequirements Combust. XE, XA, XIR 3-wire Oxygen&Toxics XE, XA 2-wire; no LEDs or relays Oxygen&Toxics XE, XA 3-wire; LEDs and/or relays SignalOutput XE, XA 4-20mA 2-wire current sink XE, XA, XIR 4-20mA 3-wire current source RelayContactRating 5amp @ 220 VAC; 5amp @ 30 VDC HousingEntries XE, XIR Four conduit entries, 3/4" NPT or 25mm XA One Entry Physical XE 316 Stainless Steel; 10.4lbs (4.7kg) 6.3"W x 3.9"D x 10.3"L (160 x 99 x 261mm) XA Polycarbonate; 1.5lbs (0.68kg) 5.1"W x 2.9"D x 9.4"L (130 x 76 x 239mm) XIR 316 Stainless Steel; 10.8lbs (4.9kg) 12.6"W x 3.9"D x 5.7"L (320 x 99 x 144mm) ApprovalRatings XE FM UL 1203 (Includes X3 CSA C22.2-30 Class I, Div. 1 & 2, Technology) Groups A, B, C, & D Class II, Div. 1, Groups F, G Class III CSA C22.2 No. 152 Class I, Div. 1, Groups A, B, C, & D XA Nema 4X rating XIR UL 1203 & CSA C22.2-30 Class I, Div. 1 & 2, Groups A, B, C, & D; Class II, Div.1, Groups E, F, & G; Class III CSA C22.2 No. 152 Class I, Div. 1 & 2, Groups B, C, & D XE & XIR EN 50018 Class I, Zone 1, Group IIC XE, XA, XIR CE Low Voltage Directive: 73/23/EEC, CE EMC Directive: 89/336/EEC (Not including X3 XE, XA, XIR SIL 2 certification or HART products)

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

UltimaXSeriesSensorX-ChangeProgram
Easily exchange sensors on demand
With the Ultima X Series Sensor X-change Program, you receive replacement calibrated sensor modules when they are needed, on demand. Sensors arrive prior to the Ultima X Gas Monitors scheduled calibration due date for easy installation and minimal downtime. Simply change out the old sensor with the new, perform a gas check, and the system is operational. HowtheProgramWorks 1. Replacement sensor modules are shipped at pre-determined intervals of 1, 2, 3, 6, and 12 months. Sign a program agreement for your choice of 1, 2, or 3 years. Some restrictions apply, contact your sales represent-ative for more information. 2. Receive a pre-calibrated sensor module plus complete calibration documentation in a returnable, pre-labeled container. 3. The shipping container, which identifies the sensor type, is used for return of the old sensor module. Benefits Eliminates the need to perform initial field calibrations Reduces overall maintenance time Greatly reduces calibration cylinder requirements Eliminates the need to dispose of sensor modules Assures that the installed sensor base has been factory-calibrated by trained MSA technicians prior to operation All Ultima X Smart Sensors, using catalytic bead and electrochemical technologies, are available through this program

[Datasheet 07-2142]

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
UltimaXIRGasMonitor
Infrared technology with display for combustible gas detection
The Ultima XIR Gas Monitor is a microprocessorbased, infrared point gas detector for continuous monitoring of combustible gases and vapors. Designed around a rugged, 316 stainless steel enclosure, the monitor operates with dualwavelength, heated-optics technology, providing definitive compensation for temperature, humidity and aging eects. The IR technology oers excellent long-term stability, eliminates the need for frequent calibrations and reduces the overall cost of ownership. Reliability DuraSource technology oers improved IR sensor life Extremely fast speed of response Designed without a sintered disk for optimum performance in the harsh, oshore environment Operates over extended temperature ranges Immune to poisoning Operates in high-gas and low-oxygen environments Fail to safety operation EaseofUse 4-20mA, HART and ModBus (X3 output) LCD display with scrolling messaging Single-board design for ultimate reliability and easy, no-tool servicing Optional "quick-check" LEDs for increased product visibility No-gas calibration. A zero adjustment is all that is required for full calibration Flexibility Field-selectable algorithms for a variety of hydrocarbon-based gases Optional field-programmable relays feature three alarm levels and one fault Durability 316 stainless steel explosion-proof, multiple-entry-mounting enclosure No moving parts, jumpers, switches or pots Sensor life not reduced by exposure to gas

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Combustible gases & vapors; 0-100% LEL -40C to +60C (-40F to +140F) 5% Full Scale/year 1% Full Scale 3% Full Scale (50% LEL) 5% Full Scale (>50% LEL) ResponseTime(withoutthesensorguard) T90 <2 sec. Humidity 0%-95% RH, non-condensing SensorWarranty 10 years for IR source PowerInput 7-30VDC, 5 watts WiringRequirements 3-wire SignalOutput 4-20mA 3-wire current source RelayContactRating 5amp @ 230VAC; 5amp @ 30VDC ConduitEntries Four entries, 3/4" NPT Physical 316 stainless steel; 10.8 lbs. (4.9 kg) 12.6W x 3.9D x 5.7L (320 x 99 x 144mm) ApprovalRatings cFMus, cULus, CSA Class I, Div. 1 and 2, Groups B, C, & D Class II, Div. 1, Groups E, F, & G Class III ANSI/ISA 12.13.01 CSA C22.2 No. 152 Combustible Gas Performance CE EMC Directive: 89/336/EEC CE ATEX Directive: 94/9/EC II 2G EEx d IIc T5 (Tamb -40C to +60C) TYPE 4X, IP 66 SIL 2 Certification [Datasheet 07-2054]

Specifications GasTypesandRanges TemperatureRange Stability Repeatability Accuracy

M S A Cu s to m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

UltimaXL/XTSeriesGasMonitors
Ultima XL/XT Series Gas Monitors oer an aordable choice in combustible gas, toxic gas and oxygen-deficiency detection and monitoring while retaining key features of MSAs Ultima X Series Gas Monitors. HART Field Commun-ications Protocol running over 4-20mA output provides convenient setup, calibration, and diagnostics. The handheld HART communicator, controller or laptop provides a display, while local calibration employs LEDS and push-buttons. 3Models: Ultima XL Monitor: Explosion-proof stainless steel 316 stainless steel Multiple-entry mounting enclosure Intrinsically safe HART port Ultima XT Monitor: Water- and corrosionresistant, all-purpose, polycarbonate Nema 4X rating Light-weight (Only 1.75 lbs) HART port Ultima XL IR Combustible Gas Monitor: Explosion-proof stainless steel, infrared gas detector 316 stainless steel Multiple-entry mounting enclosure Intrinsically safe HART port Fast response time Operation based on dual-wavelength, heated-optics technology, providing definitive compensation for temperature, humidity, and aging eects IR technology oers excellent long-term stability, eliminating the need for frequent calibrations A sintered-disk-free design for optimum performance in harsh environments No-gas calibration, a zero adjustment is all that is required for full calibration IP66 rated

Economical continuous gas monitors with HART Field Communications Protocol

Features Sensor disconnect-under-power without declassifying a hazardous area Interchangeable smart sensors; no reconfiguration required One circuit board for increased reliability and easier serviceability Calibrate, set up or perform diagnostics with HART from any point along the 4-20mA line Easy installation with two-piece field wiring connectors Asset management using HART interface Adjustable full-scale range

CalibrationOptions: Internal push-button and LEDs provide local intrusive calibration Compatible with handheld communicator, host DCS or laptop

[Datasheet 07-2157]

10

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
SENSORS
Specifications(forUltimaXL,UltimaXTandUltimaXLIR) GasTypes XL, XT Combustibles, oxygen and toxics XLIR Combustibles; 0-100%LEL TemperatureRange -40C to +60C (-40F to +140F) (Typical-range for some gases may dier) Drift Zero Drift XL, XT <5%/year, typical XLIR 2%/year, typical Span Drift XL, XT <10%/year, typical Noise <1% Full Scale Accuracy Repeatability XL, XT, XLIR 1%Full Scale or 2ppm, typical Linearity XL, XT 2%Full Scale or 2ppm, (O2, CO) XLIR 2%Full Scale (50% LEL) XL, XT 3%Full Scale (<50% LEL combustibles) XL, XT, XLIR 5%Full Scale (>50% LEL combustibles) XL, XT 10%Full Scale or 2ppm, (non-CO toxics) ResponseTimes T20 O2 & toxics XL, XT <12 seconds (typically 6 seconds) T50 O2 & toxics XL, XT <30 seconds (typically 12 seconds) T50 combust. XL, XT <10 seconds T90 combust. XL, XT <30 seconds T90 combust. XLIR <2 seconds Humidity XL, XT 15%-95% RH, non-condensing XLIR 0%-95% RH, non-condensing SensorLife Oxygen & Toxics XL, XT 2 years typical Combust. XL, XT 3 years typical Combust. XLIR 5 years typical Warranty 1 year XL, XT; 2 years XLIR; 10 years XLIR (IR source only) PowerInput XL, XT 8-30VDC (oxygen and toxics) XL, XT 8-30VDC @ 450mA maximum (combustibles) XLIR 8-30VDC @ 750mA maximum (combustibles) WiringRequirements Combust. XL, XT, XLIR 3-wire; LEDs and no relays Oxygen & Toxics XL, XT 3-wire; LEDs and no relays SignalOutput XL, XT, XLIR 4-20mA 3-wire current source, HART HousingEntries XL, XLIR Three conduit entries, 3/4" NPT or 25mm XT Two entries Physical XL 316 Stainless Steel; 7.7lbs (3.5kg) 7.1"W x 4.1"D x 8.8"L (180 x 103 x 224mm) XT Polycarbonate; 1.75lbs (0.79kg) 6.2"W x 3.0"D x 9.4"L (157 x 76 x 239mm) XLIR 316 Stainless Steel; 8.0lbs (3.6kg) 11.4"W x 4.1"D x 6.3"L (288 x 104 x 159mm) ApprovalRatings XL USA/Canada Class I, Div. 1 & 2, Groups A, B, C, & D Class I, Zone 1 & 2, Groups IIC, IIB & IIA, T6 Type 4X, IP 66 Europe II 2G, 3G, EEx d nA [ib] IIC T6, IP 66 International IEC EX scheme, Ex d nA [ib] IIC T6, IP 66

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

11

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

UltimaXIGasMonitor

Infrared technology for combustible gas detection


The Ultima XI Gas Monitor is a digital signal processor-based, infrared point gas detector for continuous monitoring of combustible gases and vapors. Designed around a rugged 316 stainless steel enclosure, the ULTIMA XI Monitor is a completely self-contained, explosion-proof unit that is dependable in harsh environments. Dual wavelength-heated optics technology, provides definitive compensation for temperature, humidity and aging eects. The IR technology oers excellent long-term stability, eliminates the need for frequent calibrations and reduces overall cost of ownership. Reliability DuraSource technology oers improved IR sensor life Extremely fast speed of response Designed without a sintered disk for optimum performance in the harsh, oshore environment Operates over extended temperature ranges Immune to poisoning Operates in high-gas and low-oxygen environments Fail to safety operation EaseofUse No-gas calibration. A zero adjustment is all that is required for full calibration Durability 316 stainless steel explosion-proof enclosure Sensor life not reduced by exposure to gas Specifications GasTypesandRanges TemperatureRange Stability Repeatability Accuracy

[07-2074]

C1-C7 hydrocarbons; 0-100% LEL -40C to +60C (-40F to +140F) 2% Full Scale/year 1% Full Scale 3% Full Scale (50% LEL) 5% Full Scale (>50% LEL) ResponseTimes (withoutthesensorguard) T90 <2 sec. Humidity 0%-95% RH, non-condensing SensorWarranty 10 years for IR source PowerInput 7-30VDC, 5 watts CurrentDraw 200mA maximum @ 24VDC WiringRequirements 3-wire SignalOutput 4-20mA 3-wire current source ConduitEntries One entry, 3/4" NPT (19.05mm) with optional condulet Physical 316 stainless steel Weight 6 lbs. (2.7kg) Dimensions 2.5 dia. x 8 long (64 x 203mm) ApprovalRatings cFMus, cULus, CSA Class I, Div. 1, Groups B, C, & D Class II, Div. 1, Groups E, F, & G Class III ANSI/ISA 12.13.01 CSA C22.2 No. 152 Combustible Gas Performance CE EMC Directive: 89/336/EEC CE ATEX Directive: 94/9/EC II 2G EEx d IIc T5 (Tamb -40C to +60C) TYPE 4X, IP 66

12

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
UltimaMOS-5IntelligentHydrogenSulfideSensor
Suitable for use in SIL 3 systems and approved by FM and CSA, the Ultima MOS-5 Sensor detects PPM levels of hydrogen sulfide (H2S), providing status indication and alarm outputs. Features include one-person calibration, event logging via HART, wireless capability, and four operating modes. With its high tolerance for a broad range of temperatures, humidity levels, and shortterm high H2S concentrations, the Ultima MOS-5 Gas Sensor is ideal for use in oil and gas applications, chemical plants and a variety of other important industrial applications. HighlightsoftheUltimaMOS-5Sensor include: Robust construction which has been proven in the most extreme environments Precise and reliable MOS sensor is highly selective; unaected by many gases commonly present in plant environments User self-calibration: simply activate a magnetic switch and apply gas - No special tools or area declassification is required Lower use of H2S calibration gas and personnel time required to perform routine maintenance saves time and money Suitable for use in SIL 3 systems and approved by FM and CSA Functions within a wide range of ambient temperatures and high humidity 2-year product warranty including the long life MOS sensor

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

A microprocessor-based transmitter designed for use with a Metal Oxide Semiconductor (MOS) sensor

Features Intelligent Sensor Detection ranges (0-20 ppm, 0-50 ppm and 0-100 ppm) enable a wide range of applications 4-20mA output is the industry standard for remote alarm and fault indication HART and ModBus communication provide complete status and control capability in the control room Warning, Alarm & Fault Relays provide local alarm capability Remaining Sensor Life Indication reduces downtime by providing an estimate of remaining sensor life Calibration, Calibration Check, and Set-up Modes simplify operation and maintenance Event logging stores fault, gas check, calibration, and alarm event history

H2S Sensor & Accessories Solid-state operation functions in the harshest environments High selectivityit does not respond to hydrocarbonsenables low false alarm risk It is unaected by over-range exposure, which reduces the need for sensor replacement Robust mechanical design is vibration and shock resistant Resistance to high humidity and a wide range of ambient temperatures makes the sensor suitable for worldwide use Specific sensors meet ISA-92.0.01 performance standard

[Datasheets 07-8103 and 07-8105]

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

13

Product Guide
System Specifications Environmental Specifications OperatingTemperatureRange Electronics -40F to 167F (-40C to 75C) Std.Sensor(FM) -40F to 167F (-40C to 75C) Std.Sensor(ATEX) -40F to 158F (-40C to 70C) StorageTemperatureRange OperatingHumidityRange Mechanical Specifications Length Height Calibration, calibration check, setup, operating Width Weight MountingHoles Electrical Specifications InputPower RelayRatings(optional) 24 VDC nominal, 20 to 36 VDC 350 mA max. 8A @ 250 VAC / 8A @ 30 VDC res. max. (3x) SPDT - Warning, Alarm & Fault 0-20 mA (650 Ohms max. load) Malfunction 0 mA** Gas Check/Cal 1.5 mA*** Setup mode 1.5 mA*** Zero reading 4 mA+0.2 mA 0-100% scale 4-20 mA Over-range 20-22 mA Complies with EN50270, EN61000-3-2, EN61000-3-3 Three-digit LED display with gas concentration, Warn and Alarm LEDs, calibration prompts, fault codes, and setup options ModBus RTU, suitable for linking up to 128 units or up to 247 units with repeaters 2400, 4800, 9600, or 19200 BPS HART 6, HART Device Description Language available. AMSAware Available with ELPRO Technologies wireless devices Calibration error, sensor heater error, low DC supply, EEPROM, EPROM, setup error, gas check time exceeded, switch input error, internal errors 3-wire shielded cable. Max. distance between Ultima MOS-5 Sensor and power source or remote sensor @ 24 VDC nominal (20 Ohm loop): 14 AWG - 2240 ft. (824 m) Max. distance for analog output (600 Ohms max): 14 AWG - 8000 ft. (2400 m) 6.4 inches (161mm) 3.4 inches (86mm) 4.1 inches (104mm) 5.5 lbs. (2.5 kg) 5.0 inches (127mm) (center to center) -58F to 185F (-50C to 85C) 5% to 100% RH, non-condensing

SENSORS

SensorType SensorLife Repeatability ResponseTime Measuring Ranges Modes

Continuous diusion, adsorption type Metal Oxide Semiconductor (MOS) 3 to 5 years typical 2 ppm or 10% of the applied gas, whichever is greater T50: 5-10 seconds (nominal) of full scale with full scale gas applied. 0-20 ppm, 0-50 ppm, 0-100 ppm

Electrical Classification CSA/FM Class I, Division 1, Groups B, C & D; Class I, Zone 1 IIB+H2, T6. Type 4X (Tamb = -40C to +60C) ATEX EEx d IIB+H2, T5 II2G, IP66 (Tamb = -40C to +70C) Warranty Approvals Two years ATEX, CSA, FM, CE Marking, HART registered, SIL 2 and 3 suitable*, FM certified to IEC 61508 MOS5-10011 0-100 ppm H2S, 4-20 mA output, w/o relays or ModBus; FM, CSA & ATEX approvals

AnalogSignal

Standard PartNumber

RFI/EMIProtection StatusIndicators

H2S Sensor Specifications Type Metal Oxide Semiconductor (MOS)

RS-485Output(optional) With wire screen flame arrestor: T50 10 seconds ResponseTime With sintered stainless steel flame arrestor: T50 30 seconds On application of full scale gas according to ANSI/ISA-92.0.01 Temperature Range CSA -40F to +167F (-40C to +75C) FM -40F to +140F (-40C to +60C) Life Electrical Classification Warranty 3 - 5 years Class I, Div. 1, Groups B, C, and D; Ex d IIC Two years CableRequirements BaudRate HART(optional) WirelessCommunication FaultsMonitored

* Use in typical environments has a lower safety rating than in clean environments ** Under HART, current values can be either 3.5 mA or 1.25 mA, depending on user selection *** Under HART, current value can be either 3.5 mA or 1.5 mA, depending on user selection

14

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
UltraSonicEX-5GasLeakDetector
The UltraSonic EX-5 Gas Leak Detector responds to the ultrasound generated from gas releases in open, well-ventilated areas, where traditional methods of detection may be unsuitable or dependent on ventilation. Because the UltraSonic EX-5 Detector responds to the source of a gas release rather than the dispersed gas, it is unaected by changing wind directions, gas dilution, and the direction of the gas leak. With its wide coverage radius, a single unit can monitor a relatively large area. The UltraSonic EX-5 Detector is immune to many false signals and can be configured to filter short timescale ultrasonic noise that can produce nuisance alarms. Frequencies below 25 kHz are removed by a high pass filter, eectively eliminating interference from audible and low frequency ultrasonic noise. At the same time, setting the alarm trigger level above the ultrasonic background noise ensures immunity to other noise sources. The result is a reliable method of detection, able to monitor environments with high levels of ultrasound such as turbine rooms and compressor stations. The UltraSonic EX-5Detector also features the Senssonic patented self-test for full failsafe operation. This self-test checks the electrical integrity of the device and microphone every 15 minutes and ensures that the detector is operational at all times. In addition to a 4-20 mA output, the UltraSonic EX-5 Detector is available with ModBus or HART to enable asset management and process improvement.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Detects airborne leaks from high-pressure gas systems

Features Advanced high precision stainless steel microphone enables instant detection of pressurized gas leaks Senssonic integrated acoustic self-test provides full failsafe operation HART and ModBus communication options provide complete status and control capability in the control room Stainless steel 316L explosion-proof housing for corrosion resistance in harsh environments

One-person check and calibration with traceable portable test unit delivers high reliability and trouble-free maintenance Three-digit LED display shows actual sound pressure level and alarm indication Event logging stores fault, sound check, calibration, and alarm event history (requires HART communication)

[Datasheet 07-8303]

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

15

Product Guide
System Specifications Environmental Specifications OperatingTemperatureRange OperatingHumidityRange Mechanical Specifications Housing Dimensions Weight ConduitEntries MountingHoles Electrical Specifications InputPower 15 36 VDC, 250 mA max. 0 mA 1 mA 3 mA 4-20 mA Start up, other errors* Pulsed acoustic error* Unit inhibit* 58 dB 104 dB Stainless steel 316L 7.99 x 7.99 x 7.91 in (203 x 203 x 201 mm) 16.5 lbs (7.5 kg) M20 x 1.5 or 3/4" NPT 2x mounting screws M8 x 19 max -40 F to 140 F (-40C to 60C) 10 to 95% RH

SENSORS

DetectorType

Ultrasonic (acoustic) gas leak detector

Detector 25 kHz 70 kHz FrequencyRange DynamicRange 58 104 dB

TestSound 40 3 kHz SourceFrequency TestSound Pressure 100 dB, 60 mm from sound source 150 PSI for methane. Lower pressures are possible with lighter gases (e.g., hydrogen). Use of heavier gases results in reduced coverage. Very low noise areas (<58 dB) 43-65' radius at leak rate = .22 lb/s (0.1 kg/s) 130' + at leak rates 2.2 lb/s (1.0 kg/s) Detector Coverage(ref. methane): Low noise areas (< 68 dB) 30-39' radius at leak rate = .22 lb/s (0.1 kg/s) High noise areas (< 78 dB) 16-26' radius at leak rate = .22 lb/s (0.1 kg/s) Electrical Classification CSA/FM

Pressure Requirements

AnalogSignal

RelayRatings(optional)

8 A @ 250 VAC / 8 A @ 30 VDC res. max. Relay 1: Error/fault indication Relay 2: Indication of trigger level ModBus RTU, suitable for linking up to 247 units with repeaters 2400, 4800, 9600, or 19200 BPS HART 6, HART Device Descriptor available, AMSaware support Complies with EN61010-1 and EN61000-6-2 Max. cable length between UltraSonic EX-5 and power source @ 24 VDC (20 ohm) 14 AWG 5,928 ft (1,809 m)

RS-485Output(optional) BaudRate HART(optional) RFI/EMIProtection

Class I, Div 1 & 2, Groups B, C, D; Class II/III, Div 1 & 2, Groups E, F, & G; Type 4X (Tamb= -40C to +60C) Ex d ia IIB+H2 T6 Gb Ex tb IIIC T85C Db; IP66 T3C (Tamb= -40C to +60C) < 1 s (speed of sound) Two years FM, CSA, ATEX, IECEx, CE Marking, HART registered, SIL 3 suitable Portable test and calibration unit, wind screen, sun shield, mounting bracket UEX5-5111 4-20 mA source output, ModBus and HART, 3/4" NPT, screw terminals

CableRequirements

ATEX/IECEx

* With HART, current values are 1.25 mA. Specifications subject to change without notice.

ResponseTime Warranty Approvals

Accessories

Standard PartNumber

16

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ToxgardIIGasMonitor
Simplicity/EaseofUse Large, four-digit LED display Large LED alarm indicators Internal relay contacts for FAULT, CAUTION, WARNING and ALARM Failsafe fault relay output Diagnostics that appear on the display Audible alarm 4 to 20 mA output Automatic calibration Replace Sensor indication when sensor nears its end-of-life Real-time clock for time and date stamping of events Logging of minimum, maximum and average gas concentrations over predetermined time intervals Selectable lock-out of output signals during calibration to inhibit alarms and control actions Digital, multi-drop communication Externally-mounted plug-in sensor is easily replaced Remote sensor enables sensors and transmitters to be separated for installations where access to the sensor may be dicult Some UL Class I, Div 2 approvals apply Flexibility Can be used as a transportable gas monitor with its optional internal battery Three levels of alarm Optional integral pump for sample draw systems Durability Housed in a rugged, metal NEMA 4X enclosure, or standard steel version Sensorgard protects sensor from dirt and water and acts as a bae in windy environments

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Versatile monitor for combustible gas, toxic gas or oxygen deficiency detection
Specifications GasTypes TemperatureRange Toxicsandoxygen Combustibles ZeroDrift SpanDrift Noise Accuracy Repeatability Linearity Combustibles; oxygen; toxics -20 to +50C -4 to +122F
(Range on some models may differ.)

-40 to +90C -40 to +194F <5%/Yr., typically <10%/Yr., typically Less than 1% FS 1% FS or 2 ppm 2% FS (Combustible; O2; CO) 10% FS or 2 ppm (others)

StepChangeResponse T20O2 andtoxics < 12 sec. (Typ. 6 sec.) T50O2 andtoxics < 30 sec. (Typ. 12 sec.) T50Combustibles < 8 sec. T90Combustibles < 20 sec. Humidity 0-95% RH, non-condensing SensorLife Combustibles 3 years typically ToxicsandO2 2 years typically Fullreplacementwarranty 1 year HazardousAreaRating General Purpose, XP Remote Sensor Assembly can be installed in Class I, Div I areas. PowerInput 110-220 VAC power input SignalOutput 4-20mA 2-wire current source Digital See Bulletin 1600-08 InternalRelays Fault, Caution, Warning, Alarm InternalRelayContactRating 5 amp @ 125 VAC; 5 amp @ 30 VDC BatteryBackUp Batterytype 12V lead acid Batteryoperatingtime No options; minimal alarm activity: ToxicsandO2 up to 24 hr. Combustibles up to 10 hr. Full options; depending on alarm activity: E-chem: 1-4 hrs Combustibles: 0.5-2 hr. Physical Enclosure 10W x 12H x 5D Weight 13 lbs.

[Datasheet 07-0949] M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

17

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Chemgard SeriesInfraredGasMonitors

Precise photoacoustic IR monitoring of a variety of industrial gases


such as hydrocarbons, solvents, alcohols, alkanes and toxics
The Chemgard Series of Gas Monitors provide low-cost, high-performance monitoring that is extremely stable and highly selective to the gas of interest. Detectability is as low as 0.01 ppm for certain applications, and the unit can operate for months with virtually no zero drift. The monitors are UL 2075-approved. Simplicity/EaseofUse Direct-reading display shows actual gas value, alarms and diagnostic messages Data logging provides access to datestamped information on key events including gas readings, alarms and fault conditions. Data is accessible through the front panel display or the RS-232 port. Easy to install, operate and maintain Easy-to-read display showing gas concentration(s) and alarms Three alarm levels with relay output All user functions configurable through front panel Three system alarm levels with relays Normally energized trouble and alarm relays for failsafe operation Flexibility Variety of output ranges 3 enclosure styles: explosion-proof, NEMA 4, or rack-mounted Can be expanded to monitor up to 8 locations simply by adding the multipoint sequencer option Operates over a wide temperature range Can be installed in numerous environments and configurations Monitor one, four or eight sampling points per instrument Discreet relays expandable up to 3 per sample line (separate enclosure)

Specifications Performance characteristics subject to change, depending on gas to be monitored and full-scale range For0-1000ppmrange Accuracy Linearity Sensitivity Resolution Reproducibility Response Operating Temperature TemperatureEffect RelativeHumidity Sampleflowrate Maximumtotal tubinglength Operatingpower requirements Alarmrelays Approvals PhysicalEnclosure NEMA4 Dimensions Weight 19RackMount Dimensions Weight ExplosionProof(XP) Dimensions Weight 0-100 ppm 2 ppm; 100-1000 ppm 10% reading 0-100 ppm linear, 100-1000 2% of full scale 2 ppm 1 ppm 2 ppm over 12 months at specified operating conditions Updated reading every 7 seconds 0-50 C, 32-122 F 0.3% per C of reading 0-99% non-condensing- no effect on reading 1.5 liter/minute 150 feet with 1/8 ID; 500 feet with 3/16 ID 120 VAC 10% at 0.56 Amps, or 240 VAC; 10% at 0.3 Amps 3 relays @ 8 Amps resistive UL 2075 for many configurations 18H x 16W x 7D 40 lbs. 7H x 17-5/8W x 15-1/4D 19 lbs. 19-1/8H x 19-1/8W x 9-1/2D 100 lbs.

Note: Specifications for other ranges dependent on application. Consult factory.

[Datasheet 07-2033]

18

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
MultiGard GasSamplingSystem
The MultiGard Sampling System draws gas samples from remote locations and delivers them to customer-selectable internal analyzers. Maintenance and calibration are simplified because all maintenance is performed at a single location. Modular construction allows simple installation and maintenance Easy setup via front touchscreen panel display Auto-standardization Common or discrete alarm and fault relays Gas flow failure indication Flexible sample point order Options include relays and readouts Sensing technology options include electrochemical, catalytic bead and both photoacoustic and nondispersive infrared Eciency Ecient, cost eective gas detection method Gas samples are sequentially delivered to internal analyzers Timesharing between multiple locations provides significant cost savings Includes up to 4 analyzers, reducing floor space and eliminating multiple systems and duplicate tubing. Reliability Reliability is enhanced through use of a single set of analyzers All calibrations completed at the MultiGard System analyzer(s), with no need to enter the monitored area Manual or auto-standardization of sensors or analyzers when desired Adaptability MultiGard System adapts to provide optimum time for a given analyzer Each location can have a dierent sample transport time [Datasheet 07-0603]

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Simple, ecient, cost-eective gas detection


Critical sampling points can be sampled more frequently Ethernet capable (IP addressable) to be viewed and controlled via computer A dual-sequencer system can be used, in which up to two analyzers are dedicated to each half of the sampling points

Specifications Enclosure Area classification: General purpose for non-hazardous areas enclosure rating: 8/16 point NEMA 12 24/32 point NEMA 12 Dual 8 point NEMA 1 Dual 16 point NEMA 1 Dimensionsin.(mm)(nominal) 8/16/dual 8 24" (609.6) W x 30" (762) H x 12" (304.8) D, weight 125 lbs. (56.7 kg) 24/32/dual 16 30" (762) W x 30" (762) H x 12" (304.8) D, weight 150 lbs. (68 kg) OperatorInterface Type integrated color TFT touch-screen display Size 8/16 point - 6" diagonal (optional 10.5" diagonal) 24/32/dual 8/dual 16 - 10.5" diagonal PowerRequirements 5 amp @ 115 VAC, 60 Hz, single sequencer systems 10 amp @ 115 VAC, 60 Hz, dual sequencer systems Electrical entry through gasketed gland plate Outputs Two levels of alarm Common alarms: Form C contacts (SPDT), 8 amp, 250 VAC optional user-configurable Discrete alarms: Form C contacts (SPDT), 10 amp, 250 VAC optional user-configurable solid state outputs: 100 mA @ 24 VDC, sinking FlowSystem Scheme Look ahead bypass connections: 1/8 NPT sample line tubing: 500 max. w/0.250 OD tubing, longer lengths possible with external pump Sample line flow rate (0.175 ID tubing): 20 SCFH (10 lpm) typical, no-load 10 SCFH (5 lpm) typical, full load Temperature Operating 32 - 95 F (0 - 35 C) Non-operating: 14 - 140 F (-10 - 60C) Sample: 0 - 140 F (-17 - 60 C) Humidity 30 to 85% RH non-condensing
Analyzers are not reflected in above specifications

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

19

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

UltimaOPIR-5OpenPathGasDetector

An open path IR gas detector that provides continuous monitoring of combustible hydrocarbon gas concentrations
The Ultima OPIR-5 System consists of an IR source and receiver which continuously monitor for methane in both the 0 to 5000 ppmmeter and 0 to 5 LELmeter range. A 0 to 2000 ppmmeter and 0 to 1 LELmeter range is also available for monitoring propane. The Ultima OPIR-5 Detector provides two 4 to 20 mA analog signals proportional to each of the above ranges, in addition to a digital display and relay contacts. The Ultima OPIR-5 Detector is easily aligned using the digital display and adjustable mounting arms, therefore it does not require any bulky setup equipment (e.g. digital volt meters, handheld alignment aids). The Ultima OPIR-5 Detectors sensitivity can be checked by placing a test gas film in front of the receiver. The Ultima OPIR-5 Detector is calibrated at the factory and needs no further calibration. It also requires little maintenance except for a periodic visual inspection, test gas film check, and cleaning of the windows to assure dependable performance. Sensor data and status information from the receiver can be transmitted up to 9,000 feet to any industrial analog to digital (A/D) converter for use in multipoint computer-based monitoring. [Datasheet 07-8202]

Features Dual detection range enables sensitivity to both small (ppmmeter) and large (LELmeter) gas leaks Performance approved for use in harsh environments Single detection beam improves accuracy and reduces drift Up to 150 meter path length

Multiple communication outputs (HART, ModBus, AMS Support) provide complete status and control capability in the control room Unitized display for ease of operation and reduced cost Automatic gain control compensates for dirty optics, rain and fog

20

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
System Specifications SensorType Ranges Methane 0 to 5000 ppmmeter 0 to 5 LELmeter Propane 0 to 2000 ppmmeter 0 to 1 LELmeter PathLength LELmeter: 5-30 m, 20-100 m, 50-150 m ppmmeter: 5-30 m, 20-100 m, 80-150 m T90 < 3 s < +5% < +5% of full scale for each scale or +10% of applied gas, whichever is greater Class I, Div 1 & 2, Groups B, C & D; Class II, Div 1 & 2, Groups E, F & G Class III; Type 4X Class I, Zone 1, IIB+H2 II 2 G D, Ex d IIB+H2 T4 Gb Ex tb IIIC T135C Db, IP66/67 (T =-55C to +65C)
amb amb

Environmental Specifications OperatingTemperatureRange -67F to +149F (-55C to +65C) OperatingHumidityRange Mechanical Specifications Housing Source 316 stainless steel 5.3 dia. x 12.4 length (135 mm dia. x 315 mm length) 5.3 dia. x 12.4 length (135 mm dia. x 315 mm length) NPT (standard) M25 (optional) 0-95% RH, non-condensing

SENSORS

Infrared absorption detects hydrocarbon gases over an open path

Receiver ConduitEntries(2) Electrical Specifications

ResponseTime Repeatability Linearity Classification

InputPower

20 to 36 VDC range 24 VDC @ 12 W (max.) source 24 VDC @ 10 W (max.) receiver (w/relays) 24 VDC @ 5 W (max.) receiver (no relays, heater off) Consult factory for lower power consumption options for other configurations 700 Ohm load max. 0-5000ppmmeter 0 mA* Startup/Fault 1.5 mA* Test Gas/Setup 2 mA* Beam Block 4-20mA** 0-5000 ppmm 4-12 mA*** 0-5000 ppmm 12-20 mA*** 21.7 mA Over-range 0-5LELmeter Startup/Fault Test Gas/Setup Beam Block 0-5 LELm 0-5 LELm Over-range

DualAnalogSignals

HazLoc T3C (T =-60C to +75C); Performance T4 (T =-55C to +65C) Verified


amb

RelayRatings RS-485Output BaudRate HART RFI/EMIProtection

8 A @ 250 VAC / 8 A @ 30 VDC res. max. Four (4) SPDT - Fault, ppm Warning, LEL Warning and Alarm ModBus RTU with block and single data transfer modes 2400, 4800, 9600, 19200 or 38400 BPS HART 6, HART Device Description available. AMS Device Management Support Complies with EN 61000-6-4 and EN 50270 For cable resistance of 3 ohms/1,000 ft, max. distance between OPIR-5 and power source @ 24VDC: - 14 AWG - 1,330 ft (405 m) - receiver - 14 AWG - 1,040 ft (317 m) - source. For 16 AWG cable with cable resistance of 5 ohms/1,000 ft, max. distance for analog output (100 ohms max.): - 10,000 ft (3,048 m).

Calibration Modes Accessories Warranty Approvals

No calibration required. Field background zero adjustment provided Setup, alignment, test gas, run Test gas films, mounting arm, mounting base, scope, attenuation plate Two years CSA, FM, ATEX, IEC Ex, CE Marking. SIL-3 suitable. HART-registered. OPIR5-1-1-1-1-1-2-1-1-1-1 Methane, dual 0-20 mA, dual ModBus, relays, mounting arm, 20-100 m path length, NPT

SampleCableDistances

WirelessCommunication DigitalDisplay

Available with ELPRO Technologies wireless devices LED indication of scale displayed; two digit, seven segment (auto range change)

Standard Configuration

HART units can be configured to never output current less than 3.5 mA if the host equipment is incapable of working below this level. ** 0 to 2000 ppmmeter and 0 to 1 LELmeter on propane unit. *** Using optional split range.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

21

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

ChillgardRTPhotoacousticInfraredRefrigerantMonitor
The industry stadard for refrigerant leak detection monitors
The Chillgard RT Photoacoustic Infrared Refrigerant Monitor provides economical, lowlevel monitoring of refrigerant gases used in most refriger-ation systems or chillers. By detecting leaks early enough to prevent a major loss of refrigerant gas, the monitor reduces operating costs. Chillagrd RT Monitors meet the requirements of ANSI/ASHRAE 15. SensorTechnology The Chillgard RT Monitor utilizes very stable and highly selective photoacoustic infrared (IR) technology to sense refrigerant gases at levels as low as 1 part-per million. Can operate for months with virtually no zero drift Inherent stability eliminates the need for autozeroing techniques that take the monitor o-line at regular intervals, leaving the area unprotected Fresh air sampling line or on-line scrubber is not required High immunity to interferents such as cleaning agents and solvents Unaected by changes in humidity Operates over a wide temperature range Detects single or multiple refrigerants Expandability SimplybyaddingtheMultipointSequencer, theChillgardRTRefrigerantMonitorcan beexpandedtomonitorupto8locations, resultingin: More cost-eective monitoring, especially when monitoring large areas or multiple locations or chillers The fastest possible response to any leak or spill Fresh sample pumped from locations up to 500 feet for each sample Simplicity/EaseofUse Easy to install, operate and maintain. Four frontpanel keys configure the entire system. Front panel displays all alarm and trouble messages. If a trouble condition occurs, the message is clearly shown on the display and the type of trouble is indicated. 2-line x 20-character vacuum fluorescent display shows alarm indications, monitored location and actual gas concentration Three alarm levels with relay outputs for each level Password protection
Specifications Performance Stability

Linearity Response Operatingtemperature Temperatureeffect Relativehumidity Sampleflowrate Maximumtotaltubinglength Operating Powerrequirements Alarmrelays Audibleoutput Analogoutput Serialoutput Maximumsignalload Sampletubingconnections Flowswitch Performance,MultipointSequencer Maximum sampled points: Eight (8) Maximum sample tubing length: Physical EnclosureType Dimensions Weight Approvals

0-50 ppm 1 ppm; (ammonia 2 ppm; ) 51-1000 ppm 10% reading 0-50 ppm 1 ppm, (ammonia 2 ppm) 51-1000 10% of reading Updated instrument reading every 7 seconds 0-50C, 32-122F 0.3% per C of reading 0-95% non-condensing, no effect on reading 0.75 liter/minute 150 ft. with 1/8" ID; 500 ft. with 3/16" ID 120 VAC 10% at 0.56 Amps, or 240 VAC 10% at 0.3 Amps 3 relays @ 8 Amps resistive Sonic Alert 75 db standard 0-10V, and 4-20mA isolated sourcing RS-232 0-10V into 2kOhms, or 4-20mA into 1kOhms 1/4 w/ 1/8ID or 3/16 ID Activates at flow < 0.5 liter/min.

150 ft. ea. standard 500 ft. optional (1/4 OD, 3/16 ID Tubing) Designed as NEMA 4 18 H x 16 W x 7 D 45 lb. UL2075

[Datasheet 07-2016]

22

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ChillgardLERefrigerantMonitor
The Chillgard LE Photoacoustic Infrared Refrigerant Monitor provides fast, reliable and economical low-level monitoring of refrigerant gases used in most refrigerant systems or chillers, including R123, R 134A, R 11, R12 and R22. The full scale range of the unit is 0-1,000 ppm with the capability of measuring a refrigerant leak as low as 20 ppm, well below the established threshold limit values. The units standard 4-20mA output can be connected directly to any existing Building Automation System (BAS) or other controller. The 4-20mA output can be used to provide indication of a leak prior to a worker entering the room containing the refrigerant gas. With the integral display, status LEDs and optional strobe, workers have a visual indication of the refrigerant level in their work area. Sample draw units can be mounted inside or outside of the room, providing detailed information such as gas level and alarm status before a worker enters. [Datasheet 07-0008]

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Refrigerant sensor and control module in one enclosure


Single point diusion or 4- point pumped models Complies with ANSI/ASHRAE 15-2001 UL approval Photoacoustic Infrared (PIR) sensing technology No moving parts in diusion model Water- and corrosion-resistant plastic enclosure 24 VAC/DC or 110/220 VAC power Five LEDs indicating power, fault and 3 levels of alarm Digital Signal Processing Standard outputs: 4-20mA & RS-485

Specifications Single-pointDiffusionModel OperatingRange 0-1000 ppm MinimumDetectability 20 ppm Linearity 0-100 ppm linear, 100-1000 ppm 5% of reading Warm-uptime 10 minutes Responsetime 50% of a step change in less than 60 seconds Operatingtemperatures 0 to 40 C (32 to 104 F) Non-operatingtemperatures -40 to 60 C (-40 to 140 F) Temperatureeffect <4%/10 C Relativehumidity 0 to 99% OperatingPowerOptions 24 VAC/DC standard, 110/220 VAC optional Analogoutput 4 to 20 mA Physical 14.7 high x 11.2 wide x 5 deep Weight 9.5 lbs. Warranty 2 years

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

23

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

ChillgardLSRefrigerantMonitor
Flexible, reliable gas monitor
The Chillgard LS Refrigerant Monitor detects the five most commonly used refrigerant gases (R-11, R-12, R-22, R-123 and R-134a). Standard features include five LED's to indicate power, alarm and fault conditions, 4-20 mA output and RS-485 ModBus output for communication to the Chillgard LC Control Module. The Chillgard LS Refrigerant Monitor sensor module meets the requirements of ASHRAE 15 for detection below the TLV for refrigerant gases. Available in either single-point diusion (no pump needed) or 4-point pumped version for remote sampling Works as either a stand-alone unit or in conjunction with the Chillgard LC Control Module Full scale range of 0-1,000 ppm with the capability of measuring as low as 20 ppm Fast reliable detection for low level leaks prevents a major loss of costly refrigerant gas Integral status LEDs and optional strobe provide visual indication of refrigerant level SimplicityandUpgradeability Designed for easy installation, operation and maintenance No moving parts in the diusion version simplifying maintenance and repair [Datasheet 07-2042] SensorTechnology Utilizes very stable and highly selective photoacoustic infrared (PIR) technology Can operate for months with virtually no zero drift Inherent stability eliminates the need for auto-zeroing techniques that take the monitor o-line at regular intervals Fresh air sampling line or on-line scrubber is not required

Specifications Single-pointDiffusionModel OperatingRange MinimumDetectability Linearity Warm-uptime Responsetime Operatingtemperatures Non-operatingtemperatures Temperatureeffect Relativehumidity Operatingpoweroptions Analogoutput Physical Weight

0-1000 ppm 20 ppm 0-100 ppm linear, 100-1000 ppm 5% of reading 10 minutes 50% of a step change in less than 60 seconds 0 to 40 C (32 to 104 F) -40 to 60 C (-40 to 140 F) <4%/10 C 0 to 99% 24 VAC/DC, 110/220 VAC optional 4 to 20 mA 7.1 high x 10 wide x 4.25 deep 5.5 lbs.

4-pointPumpedModel Same as above except for the following Minimumsampleflowrate 0.75 liters/min. Maximumtotaltubinglength 300 ft. Physical 14.7 high x 11.2 wide x 5 deep Weight 9.5 lbs. Warranty 2 years

24

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ChillgardLCControlModule
Microprocessor-based controller
The MSA Chillgard LC Control Module can communicate with up to eight sample points from Chillgard LS Refrigerant Monitors over an RS-485 communication line. The Chillgard LC Module remotely displays gas concentration, alarm status, calibration and fault diagnostics for the LS Monitors. Expandable: Configurable with up to 8 LS sensor module points of detection Easy to use: 20-position LCD display with 4-button keypad 3 LEDsPOWER, FAULT and ALARMgive a quick visual indication of monitor status 4 internal relays: FAULT and 3 ALARM levels [Datasheet 07-0009] Beacon option 85 db piezo horn; with 100 db option Analog outputs: 0-10 V and 4-20 mA Serial output: RS-232 with datalogging and RS-485 modbus Water- and corrosion-resistant enclosure Four power options: - 24 VDC output powers remote "L" Series sensor module up to 100 ft. - 24 VAC output option powers up to 5 remote "L" Series sensor modules - 110 VAC 50/60 Hz 220 VAC 50/60 Hz 2-year warranty

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

25

SENSORS

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

ChillgardNH3GasMonitor
Simplicity/EaseofUse Single-board design for ultimate reliability and serviceability Interchangeable Smart Sensors - precalibrated sensor modules are ready for installation out of the box. Sensors can be replaced in the field without the use of tools Integral display and status LEDs provide visual indication of the ammonia level in an area State-of-the-art display liquid crystal display (LCD) conveniently alternates between sensor reading and gas type and features scrolling messaging, indicating ongoing diagnostic checks such as sensor "end-of-life" condition Onboard LEDs and relays - optional "quick-check" LEDs and four relay outputs allow for increased indication of alarm and fault conditions. Quickcheck LEDs, viewable from afar, indicate NORMAL (green) and ALERT (red) status conditions Simple and flexible installation and operation Easy-to-follow calibration instructions displayed on monitor No need to open the enclosure during set-up and calibration when using accessory calibrator or controller

Provides fast, reliable detection of low-level ammonia leaks


Flexibility Standard 4-20mA output can be connected directly to any existing Building Automation System or other controller to provide workers with indication of a leak prior to entering the room Durability Water- and corrosion-resistant NEMA 4X enclosure

[Datasheet 07-2096]

Specifications: Range TemperatureRange Drift Zero Drift Span Drift Noise Accuracy Repeatability Linearity ResponseTimes T20 T50 Humidity SensorLife PowerInput WiringRequirements SignalOutput RelayContactRating Physical ApprovalRatings

0-1000 ppm -40C to +40C (-40F to +104F) <5%/year, typical <10%/year, typical <1% full scale 10 ppm, typical 10 ppm <6 seconds <12 seconds 15%-95% RH, non-condensing 2 years, typical 1 year warranty 7-30 VDC Internal heater option for operation down to -40C, -40F 2-wire - no heater or relays; 3-wire - with heater or relays 4-20mA 5 amp @ 220 VAC; 5 amp @ 30 VDC Polycarbonate; 1.5 lbs (0.68 kg) 5.1"W x 2.9"D x 9.4"L (130 x 76 x 239 mm) Nema 4X rating

26

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ZGardSSensor
Economical, reliable detection of carbon monoxide, nitrogen dioxide or refrigerants
Simplicity/EaseofUse Green OK LED sensor status indicates that the device is operating properly Two sensor output options: 4-20mA analog output or RS-485 digital signal Jumpers drive the output to percentages of full-scale. Useful for testing remote devices, which may be connected to sensor output. Flexibility Z Gard S Sensor with RS-485 digital output is specifically designed to operate with any Z Gard C 485 Controller, operating as a system Solid state and electrochemical sensor options Z Gard S Sensor with 4-20mA can be installed as a stand-alone sensor typicallyintegrated with the Z Gard C Controller or common commercial equipment including PLC, DCS, or building automation systems [Datasheet 07-2148] Durability Standard housing is 4 x 4 tamperresistant commercial electrical box constructed of PVC with _ PVC conduit opening. Sensor and electronics are housed in a steel cover plate that mounts to the box with four screws.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

Specifications SolidStateSensor
DetectionRange Sensor Accuracy Humidity Temperature Operating: Storage: Specified through ATO (Assemble To Order) Matrix for CO, refrigerants and ammonia Metal oxide sensing element 5%, full scale (FS) at 50% relative humidity 0 - 95% RH 0 to 40C (32 to 104F) -10 to 50C (14 to 122F)

ElectrochemicalSensor
DetectionRange Carbon monoxide Nitrogen dioxide Sensors Accuracy Humidity Temperature Operating: Storage: Standard- 0-100 ppm Optional- 0-200 ppm Standard- 0-10 ppm Plug-in, electrochemical sensing elements 5%, full scale (FS) 0 - 95% RH 0 to 40C (32 to 104F) -10 to 50C (14 to 122F) Factory-calibrated. Sensors can also be field-calibrated. Plastic double-gang connection box Metal front plate secures the sensor and the circuit board 5.5 H x 5.5" W x 2.2" D ENTELA (to CSA Standards)

AllZGardSensors
Calibration StandardEnclosure Dimensions Certification OperatingPower 24 VAC or DC 24 VAC SignalOutput

ZGardS4-20mASensors
100mA used with MSA Z Gard Controllers or commercial DCS and PLC devices 100mA used with commercial DCS and PLC devices 4-20mA analog, 3-wire, point-to-point connection 24 VDC, 100mA used with MSA Z-Gard C Controllers RS-485, 4-wire network connection Network Address jumpers, 1 to 127

ZGardSRS-485Sensors
OperatingPower SignalOutput FunctionSelection

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

27

Product Guide
SENSORS

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

ZGardDSSensor

Economical, reliable detection of carbon monoxide and nitrogen dioxide


Simplicity/EaseofUse Two sensors in one enclosure provide dual gas detection Green OK LED sensor status indicates that the device is operating properly Two sensor output options: an addressable RS-485 digital signal or separate 4-20mA analog outputs for the two gases Jumpers drive the output to percentages of full-scale. Useful for testing remote devices, which may be connected to sensor output Housing includes separate fieldreplaceable electrochemical sensors for carbon monoxide and nitrogen dioxide [Datasheet 07-2149] Flexibility Z Gard DS Sensor with RS-485 digital output is specifically designed to operate with any Z Gard C 485 Controller, operating as a system Z Gard DS Sensor with 4-20mA outputs can be installed as a standalone sensor typically integrated with the Z Gard C Controller or common commercial equipment including PLC, DCS or building automation systems Durability Plastic NEMA 4X enclosure

Specifications ZGardDSSensor DetectionRange Carbon monoxide Standard- 0-100 ppm Nitrogen dioxide Standard- 0-10 ppm Sensors Plug-in, electrochemical sensing elements Accuracy 5%, full scale (FS) Humidity 0 - 95% RH Temperature Operating 0 to 40C (32 to 104F) Storage -10 to 50C (14 to 122F) AllZGardDSSensors Calibration Factory-calibrated. Sensors can also be field-calibrated. StandardEnclosure Plastic enclosure Dimensions 10.5 W x 8.5" L x 4.5" D Certification ENTELA (to CSA Standards) ZGardDS4-20mASensors OperatingPower 24 VAC or DC 100mA used with MSA Z Gard Controllers or commercial DCS and PLC devices 24 VAC 100mA used with commercial DCS and PLC devices SignalOutputs 4-20mA analog, 3-wire, point-to-point connection ZGardDSRS-485Sensors OperatingPower 24 VDC, 100mA used with MSA Z-Gard C Controllers SignalOutput RS-485, 4-wire network connection FunctionSelection Network Address jumpers, 1 to 127

28

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ZGardCOmboGasMonitor
Gas alarm monitor with integrated solid-state carbon monoxide sensor
Simplicity/EaseofUse Economical and reliable Onboard solid-state (MOS) carbon monoxide sensor 100 and 200 ppm full scale ranges available Local audio/visual alarm status indication Relay contact outputs can be employed to interface with air handling equipment to control the vehicle exhaust emissions or general air quality inside buildings All relays are factory-configured to be normally de-energized. All relays will return to their inactive state once the condition is cleared Alarm relay can be made in the activated position even after alarm is cleared Pushbutton to silence an audible alarm or to reset the latching alarm relay Sensor status feature provides an indication if either integral sensor or any other remote sensor fails to communicate properly 4-20mA output proportional to the calibrated operating range Optional LED readout with auto-ranging available, which will display internal sensors gas concentration level Expandability Can also act as a master panel, managing up to 7 additional remote gas sensors connected to the monitors RS-485 network port

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

SENSORS

[Datasheet 07-2088]

110 VAC, 50/60 Hz at 0.5 amps 220 VAC, 50/60 Hz at 0.25 amps or 24 VDC at 1.5 amps DigitalSignalPort RS-485, 4-wire serial network for remote sensor connections Optional4-20mAOutputExhibits the highest reading derived from all associated sensors OptionalDigitalReadout 4-digit LED display. First digits for channel number and three digits for concentration readings StatusDisplay Common LED for Power, Warning, Alarm and Sensor Status RelayContacts All relays can be selected as normally-energized or de-energized. The alarm relay can also be selected as latching or non-latching Relays 1-Warning SPDT, 1-Alarm SPDT and 1-Sensor Fail SPDT 10 amps 1/8 H.P., 125 VAC 6 amps 1/8 H.P., 277 VAC 5 amps 30 VDC Warning&AlarmSet-Points Field-adjustable and factory-set at 25 ppm and 50 ppm CO TimeDelays 5 minutes ON delay for alarm and 5 minutes OFF delay for warning or selected with NO delay action AudibleDevice 93 dB at 0.3 meters with solid ON or user-selected variable option Temperature Operating 0 to 40C (32 to 104F) Storage -10 to 50C (14 to 122F) Pushbutton Alarm reset and audible device silence feature Enclosure Standard Metal NEMA 1 Optional Fiberglass NEMA 4 Dimensions 8.25 H (210 mm) x 8.25 W (210 mm) x 4.0 D (102 mm) Certification CSA Certificate of Compliance No. LR51078-5

Specifications PowerRequirements Standard Optional

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

29

sectiontwo
MSAFLAMEDETECTORS

MSA FLAME DETECTORS

Product Guide
FlameGard5SeriesofFlameDetectors
Therearefourproductsinthisseries: FlameGard 5 MSIR Multi-Spectral Infrared Flame Detector Combines a precision multi-spectral infrared sensing array with highly intelligent neural network processors for high accuracy through superior false alarm immunity. FlameGard 5 UV/IR Flame Detector Uses ultraviolet and infrared technologies for flame detection. FlameGard 5 UV/IR-H2 Flame Detector Uses ultraviolet and infrared technologies to detect hydrogen fires. FlameGard 5 Test Lamp Provides an easy way to verify the functionality of any of the FlameGard 5 Detectors. FeaturesthatsettheFlameGard5 Seriesapartfromsimilarproductsin themarketinclude: Multi-spectral infrared sensing array (FlameGard 5 MSIR Detector) with highly intelligent neural network processors provides high accuracy through superior false alarm immunity Wide field of view SIL 3-suitable products Continuous Optical Path Monitoring (COPM) checks optical path integrity and electronic circuitry once every minute MSA FlameGard 5 Flame Detectors are ideal for use in chemical plants, aircraft hangers, gas turbines, hydrogen storage and test facilities, and numerous applications in the oil, gas and petrochemical industry, including drilling and production platforms, LNG/LPG processing and storage facilities, refineries and many other applications.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Uses advanced infrared and ultraviolet flame detection technologies to provide superior flame detection

FLAME

FlameGard5TestLampSpecfications
System Specifications OutputSpectrum ChargingTime ChargerInput ChargerOutput Classification Warranty Approvals Standard PartNumbers Broadband emissions in UV, visible and IR spectra 3.5 hours max. 110-240VAC, 50/60 Hz, 1.5A 24 VDC @ 2.1A Class I, Zone I, T4 (110C) Ex d IIB + H2 Two years CSA, ATEX, CE marking 5TL-02 FlameGard 5 MSIR Test Lamp 5TL-12 FlameGard 5 UVIR Test Lamp Includes power supply adapter Environmental Specifications OperatingTemperature Range 5F to +122F (-15C to +50C) 0-90% 3% RH, non-condensing

OperatingHumidity Range
Mechanical Specifications Length Diameter Weight

13 inches (330 mm) 5 inches (127 mm) 7.9 lbs (3.5 kg)

32

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
FlameGard5MSIRMulti-spectralInfraredFlameDetectorSpecfications
System Specifications SpectralRange 2 - 5 microns (IR) Environmental Specifications Operating/Storage TemperatureRange OperatingHumidityRange < 10 s 5-15 ft. (1.5-4.6 m) depending on rod Mechanical Specifications Housing Height Diameter 100 @ 100 ft; 90 @ 210 ft. Weight Mounting CableEntry Electrical Specifications InputPower AnalogSignal FaultMode TestMode COPMFault ReadyMode WARNMode ALARMMode RelayContactRating RFI/EMIProtection 20-36 VDC 24 VDC @ 150 mA (3.6 W) 316 stainless steel 4.3 inches (109 mm) 5.4 inches (137 mm) base 3.5 inches (89 mm) optical housing 7.9 lbs. (3.6 kg) Stainless steel mounting bracket 2 x 3/4 inch NPT -40F to +176F (-40C to +80C) 0% to 95% RH, non-condensing MaximumRange 230 ft. (70 m)* Typical ResponseTime Minimum ArcWelding Immunity Distance Maximum FieldofView

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

FLAME

* 1 sq. ft. n-heptane fire using high sensitivity. This is a nominal value and dierent results may arise depending on the source of each fire. Maximum field of view is the angle at which FlameGard 5 MSIR Detector can detect flame at 50% of maximum specified range.

Accessories

Test Lamp, Mounting Bracket Class I, Div. 1, Groups B, C, D; Class II, Div. 1, Groups E, F, G; Class III II 2GD Ex d IIC T5 Gb Ex tb IIIC T100C Db Two years CSA, FM, ULC, ATEX, IECEx & CE Marking. HART registered SIL 3 suitable FM certified to IEC 61508.

SelectableOptions

Classification

RS-485Output BaudRate HART StatusIndicators FaultMonitoring

Warranty

0-20 mA (600 Ohms maximum) 0 mA to 0.2 mA 1.5 mA, 0.2 mA 2 mA, 0.2 mA 4.3 mA, 0.2 mA 16 mA, 0.2 mA 20 mA, 0.2 mA 8A @ 250 VAC, 8A @ 30 VDC resistive maximum Complies with EN6100-6-4: 2001 and EN50130-4: 1995+A2: 2003 Sensitivity: High, Medium or Low Alarm Time Delay: up to 14 seconds with dip switches and up to 30 seconds with ModBus Warn & Alarm Relays: Latching/Non-latching Energized/De-energized ModBus RTU, suitable for linking up to 128 units and 247 units with repeaters 2400, 4800, 9600, 19200, or 38400 bit/s HART 6, HART Device Description Two LEDs with status and fault cues RAM, EPROM and EEPROM checksum errors, optics failure/ blockage and low supply voltage 3-wire shielded cable minimum configuration. Maximum distance between Flamegard 5 MSIR and power source or remote sensor @ 24 VDC nominal (20 Ohm loop): 14 AWG - 4,500 ft (1,370 m) Max. distance for analog output (250 Ohms max): 14 AWG - 9,000 ft. (2,750 m) 5MSIR-1013110 Dual ModBus, no relays, 0 - 20 mA, high sensitivity, 10-second delay 71370-1 mounting bracket

Approvals

CableRequirements

StandardPartNumbers

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

33

Product Guide
FlameGard5UV/IRFlameDetectorSpecfications
System Specifications WaveLengths FieldofView 185 to 260 nm (UV) 4.35 microns (IR) 120 max. conical Approved performance specifications 50 feet (15.2m) distance for a 1 sq. ft (0.092m2) heptane fire Environmental Specifications OperatingTemperatureRange StorageTemperatureRange OperatingHumidityRange Mechanical Specifications Housing Length Diameter Weight Mounting CableEntry Electrical Specifications InputPower Warranty Two years AnalogSignal Approvals CSA, FM, ATEX, IECEx, HART registered, SIL 3 suitable, FM approved to IEC 61508 5 UVIR - 1513111 FlameGard 5 UVIR Flame Detector Single ModBus, Aluminum, 0-20mA Output, Relays, Aluminum Housing Mounting bracket, test lamp DipSwitchSelectableOptions FaultMode COPMFault ReadySignal IRSignal UVSignal WARNSignal ALARMSignal RelayContactRating 20-36 VDC 24 VDC @ 150 mA max. (3.4 W max.) 0 20 mA (600 Ohms maximum) 0 0.2 mA* 2 mA, 0.2 mA** 4.05 mA, 0.05 mA Aluminum (stainless steel optional) 5.5 inches (140 mm) 6 inches (152 mm) 5 lbs (2.3 kg) aluminum 16 lbs (7.3 kg) stainless steel 3/4 NPT (2 ports) 2 x 3/4" NPT or 2 x 25 mm ISO or 2 x 20 mm ISO or 2 x 13.5 PG -40F to +185F (-40C to +85C) -40F to +185F (-40C to +85C) 0% to 100% RH, non-condensing

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Sensitivity

FLAME

TypicalResponse < 3sec @ 50 ft. Time MinimumSensor 500 ms ResponseTime Class I, Div 1 & 2, Groups B, C & D Class II, Div 1 & 2, Groups E, F& G Class III, Type 4X, Ex d IIC, T5, IP66

Classification

Standard PartNumber

8 mA, +0.2 mA 20 mA, 0.2 mA 8A @ 250 VAC, 8A @ 30 VDC resistive maximum Complies with EN6100-6-4: 2001 and EN50130-4: 1995+A2: 2003 8A 250 VAC, 8A @ 30 VDC resistive (North America) 8A @ 30 VDC resistive (Europe) Sensitivity: 100%, 75%, 50% Alarm Time Delay: 2, 4, 8 or 10 seconds Warn & Alarm Relays: Latching/Non-latching Energized/De-energized ModBus RTU, suitable for linking up to 128 units or up to 247 units with repeaters. Optional Dual ModBus. 2400, 4800, 9600, or 19200 BPS HART 6, HART Device Description Language available. AMS-aware Available with ELPRO Technologies wireless devices Complies with EN 50130-4, EN 61000-6-4 Max. distance between detector and power source @ 24 VDC nominal (20 Ohm loop), 14 AWG 4500 ft (1370 m) Terminal Blocks 14-22 AWG 2 LEDs with status, fault and alarm indication Memory checksum, reset line shorted, optics failure / blockage, internal voltages, and low supply voltage

Accessories

RS-485Output BaudRate HART(optional) WirelessCommunication RFI/EMIProtection CableRequirements StatusIndicator FaultsMonitored

* Under HART, current values can be either 3.5 mA or 1.25 mA, depending on user selection ** Under HART, current value can be either 3.5 mA or 2.0 mA,depending on user selection

34

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
FlameGard5UV/IR-H2FlameDetectorSpecfications
System Specifications SpectralRange FieldofView Typical ResponseTime Accessories 2.7 to 3.2 microns (IR)) 120 horizontal < 3 sec @ 15 ft Swivel elbow union, mounting bracket, test lamp Class I, Div 1 & 2, Groups B, C & D Class II, Div 1 & 2, Groups E, F & G Class III, Type 4X, Ex d IIC, T5, IP66 Two years CSA, ATEX, IECEx HART registered 5,914,489 5 UVIR - 1513311 Single ModBus, relays, hydrogen, 100% sensitivity, 4 second delay, aluminum housing Environmental Specifications OperatingTemperatureRange -40F to +185F (-40C to +85C)) StorageTemperatureRange OperatingHumidityRange Mechanical Specifications Housing Length Diameter Weight Mounting CableEntry Electrical Specifications InputPower AnalogSignal FaultMode COPMFault ReadySignal IRSignal UVSignal WARNSignal ALARMSignal RelayContactRating 20-36 VDC 24 VDC @ 150 mA max. (3.4 W max.) 0 20 mA (600 Ohms maximum) 0 0.2 mA* 2 mA, 0.2 mA** 4.05 mA, 0.05 mA Aluminum (stainless steel optional) 5.5 inches (140 mm) -58F to +185F (-50C to +85C) 0% to 100% RH, non-condensing

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

FLAME

6 inches (152 mm) 5 lbs (2.3 kg) aluminum 16 lbs (7.3 kg) stainless steel 3/4 NPT (2 ports) 2 x 3/4" NPT or 2 x 25 mm ISO or 2 x 20 mm ISO or 2 x 13.5 PG

Classification

Warranty Approvals PatentNumber

Standard PartNumber

8 mA, 0.2 mA 12 mA, 0.2 mA 16 mA, 0.2 mA 20 mA, 0.2 mA 8A 250 VAC, 8A @ 30 VDC resistive (North America)

Sensitivity: 100%, 75%, 50% Alarm Time Delay: 2, 4, 8 or 10 seconds DipSwitchSelectableOptions Warn & Alarm Relays: Latching/Non-latching Energized/De-energized RS-485Output BaudRate HART(optional) RFI/EMIProtection CableRequirements StatusIndicator FaultsMonitored ModBus RTU, suitable for linking up to 128 units or up to 247 units with repeaters. Optional Dual ModBus. 2400, 4800, 9600, or 19200 BPS HART 6, HART Device Description Language available. AMS-aware Complies with EN 50130-4, EN 61000-6-4 Max. distance between detector and power source @ 24 VDC nominal (20 Ohm loop), 14 AWG 4500 ft (1370 m) Terminal Blocks 14-22 AWG 2 LEDs with status, fault and alarm indication Memory checksum, reset line shorted, optics failure / blockage, internal voltages, and low supply voltage

* Under HART, current values can be either 3.5 mA or 1.25 mA, depending on user selection ** Under HART, current value can be either 3.5 mA or 2.0 mA, depending on user selection

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

35

sectionthree
MSACONTROLLERS

MSA CONTROLLERS

Product Guide
Suprema ControlSystem
The Suprema Systems modular redundancy design brings flexibility to virtually any fire or gas monitoring system. Designed around industrial 19 rack standards, the Suprema System oers signal processing for up-to 256 inputs and will provide up-to 512 relay and 4-20mA outputs. The Suprema System is compatible with all of the MSA fire and gas products; including the Ultima X Series Gas Monitors, the SafEye Open Path Gas Detection System and the FlameGard 5 Flame Detector. In addition, the Suprema System accommodates a variety of thirdparty devices such as 4-20 mA output sensors and heat and smoke sensors. The Suprema Control Systems modular, intelligent safety system is field configurable and provides a distributed bus technology ensuring fail-safe internal data transfer. Simplicity/EaseofUse System and signal status LEDs User-friendly graphical user interface (GUI) Simple system operation with graphic display, text readouts, cursor keys and function keys Battery connections for emergency power operation (24V) Space-saving compact modular design Easy installation with plug-in ribbon cables Simple mouse-click configuration for voting, alarm grouping and multiple task activations Minimal cost of ownership Receives 4-20mA output sensors; 2-wire and 3-wire Receives switched output sensors (smoke, fire, heat) Internal power supply (150W, 85-265 VAC) Interfaces to external Modbus and Profibus protocols

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Modular flexibility for individual solutions


Flexibility Optional electrically-isolated analog outputs Available in redundant system versions Flexible planning with integrated modules Straightforward system expansion Durability ATEX approval TUV approved SIL3 rating (IEC61508) [Datasheet 07-2068]

CONTROLLERS

Specifications Operating TemperatureRange 23 to 131 F (-5 to 55 C) Power(optional) 85 265 VAC, 50/60 Hz, 150W Humidity 0 95% RH noncondensing Relays Relayoutputs (230V, 3A) Switched outputsas open-collectordriver (24V, 0.3A) KeyFeatures SystemLEDstatusindicator Green (power), Orange (fail and inhibit) SignalLEDstatusindicator Red (four levels of alarm), Orange (fail) Signal processing for up to 64 inputs in one 19 rack Hot swap replacement Operating voltage range 18-32V Key switch or password for secure access control Key operated switch for relay inhibit 2 x RS-232 electrically isolated interfaces for data transfer to PC/laptop/printer

38

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
GasgardFamilyofProducts
The MSA Gasgard family of products includes the Gasgard1 and Gasgard XL Monitors. Designed to work with any 2- or 3-wire 4-20 mA input signal, these monitors oer expanded features and options, selectable through user-friendly software. Each monitor uses microprocessor-based technology and provides eective and reliable monitoring of toxic and combustible gases as well as for oxygen deficiency. Each monitors measuring range includes PPM, % LEL and % Volume. Features Each channel has: - 4 levels of alarm with LED indicator and failsafe relay output for each alarm level - Fault alarm with LED indicator and failsafe relay output - Individual digital LED display and electronics - 4-20 mA output signal Selectable measuring range Audible alarm Easy-to-program alarm levels User-selectable relay contact positions Power ON/Ready LED Configurable external reset switch or flow failure fault status [Datasheet 07-2032] MSAGasgard1Specifications TemperatureRange Operating 0 C to +50 C Storage -20 C to +70 C PowerSupply RelayContacts Enclosure Dimensions CaseWeight Approvals 115/230VAC +/- 10%, 50/60 Hz, 24 VDC 2 Amps, 250 VAC 3 Amps, 30 VDC General Purpose wall mount 6.5" (H) x 10" (W) x 2.75" (D) (160 x 249 x 70 mm) 6.5 lbs. CE

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Versatile, compact, cost-eective gas monitors


GasgardXLController The GasGard XL Controller oers reliability in a compact, durable, wall-mounted housing constructed of fire-retardant ABS plastic. The large and clear multilanguage LCD display provides real-time target gas readings and events, oers full system diagnosis, and is supported by individual LEDs per channel with common relays and internal buzzer. The GasGard XL Controller can be easily configured to accept up to eight remote gas sensors, depending upon the number of individual plug-in input cards installed. With two alarm levels per channel, the GasGard XL Controller operates in conjunction with MSAs remote gas sensors (combustible, toxic, or oxygen 4 20 mA). Ideal MSAGasgardXLSpecifications for use with MSA Ultima X Series Gas Temp: Monitors, FlameGard 5 Flame Detectors, and Operating -10 C to +50 C Storage -20 C to +75 C SafEye Open Path Gas Detection Systems, this controllers ergonomic design allows for PowerSupply 85 VAC256 VAC ecient wiring and installation. 50/60 Hz, 24 VDC nominal range Features 18 32 VDC Fully configurable via USB or RS485 Modbus Relay 5 amps @ 30 VDC connection or 250 VAC Event log upload through isolated Ethernet Enclosure NEMA 4X flame RS 485 or USB retardant grade Multi-language display selectable via UL-94-0 ABS plastic controller menu Dimensions 11 (H) x 20 (W) x 5 (D) Expandable up to 8 independent channels CaseWeight 11 lbs. to 17.6 lbs. using plug-in boards (with battery) Dedicated keys make all functions accessible Approvals cCSAus, UL/CSA 61010-1 from the front panel CSA 22.2 No.152 and Common relay board for Alarm Level 1 and 2, ISA 12.13 Horn 1 and 2, or Failure ATEX 94/9/EC Large graphic display with intuitive icons; all EN 50270 (EMC) channels shown at a glance EN 50402 EN 61010-1 Internal buzzer 85 dB (Low Voltage Directive) EN 61779-1 [Datasheet 0720-06] EN 61779-4

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

39

CONTROLLERS

Product Guide
9010/9020ControllerUnits
Flexible options for reliable system control
9010/9020 Controller Units operate with a complete range of gas sensors and transmitters including toxic, combustible and oxygen sensors. They oer maximum flexibility to work in conjunction with a variety of remote sensors to provide reliable gas detection for a wide range of industries and applications. Advanced design includes SMD components throughout. The 9010 LCD operates with one independent sensor (single-channel) while the 9020 LCD operates with two independent sensors (dual-channel) per control module, oering considerable cost savings while maintaining high reliability and performance. Modular design combined with dual-channel capability allows for many configurations to meet most applications. Simplicity/EaseofUse Simple 3-key operation for configuration, calibration and routine operation Selectable unit of measure (LEL, LELm, ppm, % Vol, g/m3 or blank) Flexible options for 1 to 20 channels Enhanced system reliability through individual terminal blocks for each module Adjustable calibration timer for calibration reminders Leading-edge SMD components and over range function 4-20 mA current loop accepted with no control unit calibration required Control Modules with independent LCD display specific to each channel Error and failure display warnings of any operational anomalies An RS-485 interactive serial interface for printer connection

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

CONTROLLERS

Flexibility Each Control Module features: - An independent AC/DC power supply transformer for increased system reliability - Two (SPDT) relays with change-over contacts for verification of Warning and Alarm conditions (common to both channels in the 9020 version) Full internal diagnostics and inherent reliability minimize false alarms and unexpected down-time Customized transmission protocol ModBus RTU can be used for serial bus data transmission such as system configuration, gas concentration, alarm and failure events, alarm inhibit and reset The LCD can power the remote sensors (by constant current or voltage), enhancing the versatility of the system. These user-friendly, configurable Control Modules adjust through code access with no tools required.

Large, 4-digit, 7- segment, back-lit LCD and bright LED provide gas concentration, alarm status, measurement units, flags indicating status, and settings such as calibration interval, time-out function, alarm ON delay and alarm inhibit When operating in connection with toxic sensors, the 9010/20 LCD can be set to alarm when relevant STEL and TWA values are exceeded Remote sensors are factory-set to 2-or 3-wire connection, depending on the specific application. Durability Four enclosure options: NEMA 4X plastic, metal or stainless steel; and explosionproof metal

[Datasheet 07-2111]

40

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
Specifications Powersupply 115/230V 15% 50/60 Hz, 24 VDC + 15%-20% Powerconsumption Mod. 9010 Mod. 9020 12 W transformer 9W 10.5 W AC supply 25 W transformer 15 W 17 W DC supply 24 VDC nominal 4W 6W Sensorsupply Constantcurrent 5-500 mA Constantvoltage 3-24 VDC Sensorconnectionmodes 2 or 3 wires Connectionterminals for wires up to 2.5 mm2 (14 gauge wire) Inputsignals 10-200 mV; 4-20 mA Outputsignals Analog(normal) 0-20/4-20 mA (selectable) isolated Analog(fault) 0/2/4/20 mA/frozen (selectable) Serialinterface RS-485 Alarmlevels 3 (Caution - Warning - Alarm) Alarmratings Viarelaycontacts(SPDT) 5 A @ 24 VDC/250 VAC* *resistive load Alarmhandling Reset latching/non-latching ONdelay 0-9999 seconds adjustable Automatic with specific access code Manual with specific access code Electronicspeedofresponse <0.5 sec. for 100% full scale Spanandzerodrift <0.5% full scale Repeatability 1% full scale Operatingtemperature -10C (+14F) to +40C (+104F) Storagetemperature -20C (-4F) to +75C (+167F) Humidity 90% R.H. non-condensing Vibrations unaected within 10 to 55 Hz, 0.15 mm bandwidth LCDdisplay back-lit liquid crystal display; 4-digit, 7 segments Opticalalarms bright LEDs Warm-upandself-diagnosistime 20 sec/channel Time-outsetting 2-6 min., adjustable Defaultandconfigurationdata stored in non-volatile memory Protections AC/DC automatic switching in case of AC power failure through electronic switch Accidentaltampering by specific access codes and password Softwareself-diagnosis by watch-dog and check-sum Approvals complies with UL/CSA 61010-1 per MET

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

41

CONTROLLERS

Product Guide
ModCon75Controller
MSA's ModCon75 Controller is designed for use with your Ultima X Gas Monitor with X3 Technology, enabling selfconfiguration and saving time and money. This new, economical choice is suitable for all industrial, municipal, oil, gas, petrochemical and HVAC applications. Compact unit allows for remote control of many features ModBUS RTU input and ModBUS-overEthernet interface capability Self-configuring to Ultima X Gas Monitors with X3 Technology View and control of up to 25 Ultima X Gas Monitors with X3 Technology (75 total sensors) All pertinent data displays on main data screen 12/24 VDC power supply Panel input power is 12/24 VDC; wall-mount power is 115 VAC. Seven-year battery backup provides memory and real-time clock Logs up to 2000 events Nine zone control relays Password-protected cUL listed (panel only) [Datasheet 07-2129]

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Pre-programmed, self-configuring controller for monitoring up to 25 Ultima X Gas Monitors with X3 Technology

CONTROLLERS

Specifications PanelMount Weight Dimensions Enclosuretype Maximumnumber ofsensors Frontpanel Mountingprovisions WallMount Weight Dimensions Enclosuretype Maximumnumber ofsensors Mountingprovisions GraphicalDisplayScreen Type IlluminationBacklight DisplayResolution HMIDisplays BatteryBackup Environmental Temperature Humidity

3 lbs. 6.1H x 10.24W x 2.8D none 75 is IP65/NEMA 4X (when mounted) installation designed for panel mount 18 lbs 17.3H x 15.3W x 6.7D NEMA 4X fiberglass enclosure with panel mount display and controls 75 (25 transmitter heads with a maximum of 75 sensors) 4 mounting holes located on top and bottom (2 each) for flat surface attachment Negative blue STN LCD graphical display CCFL (fluorescent lamp) 240 x 64 pixels Up to 255 7-year typical battery backup for all memory sections and real-time clock Operating temperature range: 0 to 50C (32 to 122F) Operating humidity range: 5-95% RH, non-condensing

42

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ZGardCXController
Simplicity/EaseofUse Programmable operating parameters organized by menu interface keypad Connects up to 40 remote gas sensors Large LCD screen with audible/visual indication and relay contact outputs Auto-recognition of sensors Keypad on front panel permits user to program monitor for custom applications Password-protected to prevent unauthorized access Auto-recognition of failed communication Time delays menu selected o delays, adjustable from 0 to 600 seconds for warning and alarm Designed to host a series of Z Gard S Gas Sensors with RS-485 digital output, which are supported on a 4-wire data bus (network) Flexibility Zoning; user-programmable up to 9 discreet zones Each zone is capable of voting assignment Visual and audible alarm indications Programmable alarm relays Up to 7 optional remote relay modules can be coupled with the unit [Datasheet 07-2085]

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Microprocessor-based alarm monitoring system designed to interface with remote MSA Z Gard sensors
Specifications PowerRequirements Standard Optional RemoteSensorPower Temperature Operating Storage Temperature UserInterface DigitalDisplayScreen StatusDisplay NetworkCommunication Auto-Configuration Feature

120VAC, 50/60 Hz 10% at 2.5 amps 220VAC, 50/60 Hz 10% at 1.25 amps 24VDC @ 100mA, maximum of 40 MSA Z Gard S Gas Sensors -10 to 40C (14 to 104F) -20 to 50C (-4 to 122F) Keypad on the front panel of the monitor with menu driven operating parameters 4-line x 40-character backlit LCD screen displays the operating, alarm and fault diagnostic status of the system. Common LEDs for System OK- green, Warning- amber, Alarm- red and Sensor Fail- red RS-485, 4-wire serial communication for remote gas sensors and auxiliary modules

CONTROLLERS

Digitally-recognized remote devices (sensors and auxiliary modules). Each device residing on the RS-485 serial data bus shall be automatically assigned as a node on the network. Alarm&Warning Set-points Adjustable from 1 to 99% of operating range for each system sensor type NumberofRelays Standard 12 standard programmable Warning and Alarm relays, SPDT Auxiliary Relays 1 common Fault relay, SPDT, normally-energized (sensor fail) 1 common Warning relay, SPDT; 1 common Alarm relay, SPDT 1 common External Audible relay, SPDT RelayContactsRating 10 amps 1/8 H.P., 125VAC; 6 Amps 1/8 H.P., 277VAC 5 Amps, 30VDC RelayAction All programmable relays can be defined as normally-energized or de-energized and latching or non-latching RelayTimeDelays Menu-selected OFF delays, adjustable from 0 to 600 seconds for Warning and Alarm, eectively common to all active channels Set-upandCalibration Pre-configured at factory or configurable by user AudibleAlarm Audible alarm device, 93dB @ 0.3 meters Pushbutton Alarm Reset and Silence feature StrobesOptions Optional flashing strobes factory-mounted on the top of the enclosure. Enclosure Metal, NEMA 1 Weight 7.4 lbs. (7.9 kg) Dimensions 15 H (381 mm) x 12 W (305 mm) x 3.75 D (95 mm) Certification ENTELA (to CSA Standards)

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

43

Product Guide
ZGard CController
Microprocessor-based gas monitoring controller for a variety of alarm and control applications

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Simplicity/EaseofUse Flexibility Standard relay outputs for warning and Accepts 4 to 20mA or RS-485 inputs from alarm levels facilitate interfacing to MSA Z Gard S Sensors externally connected devices Can accept inputs from 1 to 8 remote Status LEDs located on front panel, sensors providing quick indication of system Eight-point version features keypad user status interface on front panel for controlling Fail safe operation output functions Audible alarm features alarm reset and local audible alarm silence pushbutton 4-20mA high select option available on all controllers representing readings from 0 to 100% full-scale Large easy-to-read LED display Specifications Multi-point unit displays scan active PowerRequirements channels at two-second intervals 1-point 110/220VAC, 50/60Hz +/-10% 0.15A / 0.10A On/o delay 4-point 110/220VAC, 50/60Hz +/-10% 0.50A / 0.25A Fault relay 8-point 110/220VAC, 50/60Hz +/-10% 1.00A / 0.50A System status LEDs SignalInput 4-20mA, 3-wire connection or RS-485, 4-wire connection RelaysContactRating 10 amps, 1/8 HP, 125 VAC; 6 amps, 1/8 HP, 220 VAC; 5 amps, 30 VDC NumberofRelays 1-point 3 relays total, Form C [Datasheet 07-2086] 4-point 6 relays total, Form C 8-point 10 relays total, Form C Relay Action Energized/non-energized; latching/non-latching DigitalReadout 4-digit LED with sequential scanning feature DigitalReadoutScale 1- and 4-point: 0 to 999 ppm; 8-point: 0 to 9999 ppm TemperatureRange Operating -10 to +40C (14 to 104F) Storage -20 to +50C (4 to 104F) Enclosure Standard Metal NEMA 1 Optional Fiberglass NEMA 4X design Weight 1-point 9.1 lb (4.12 kg) 4- & 8-point 13.2 lb (6 kg) Dimensions 1-point 11 H (292mm) x 10 W (254mm) x 3.75 D (95mm) 4-point 15 H (381mm) x 12 W (304mm) D x 3.75 (95mm) 8-point 13.5 H (340 mm) x 11.5 W (290 mm) x 5.5 D (139mm) Certification ENTELA (to CSA Standards)

CONTROLLERS

44

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
ZGardC485Controller
Economical and Reliable Microprocessor-Based Controller
Z Gard C 485 Controllers are economical, microprocessor-based gas monitoring systems which can solve a variety of alarm and control applications. The Z Gard C 485 Controller can interface with a wide choice of remote MSA Z Gard S Sensors. Models are available which can accept inputs from up to 8, 16, or 24 MSA Z Gard S Sensors. 4-wire digital RS-485 serial communication protocol. Sensor type is automatically detected. Set points and readout display are automatically adjusted to match the sensors operating range. Large LED readout displays the active channel number and corresponding sensor gas level. Display scans through all active channels at 2-second intervals. Each controller provides a 4-20mA highselect output signal representing the highest gas concentration level of the active sensors. A set of relay outputs for warning, alarm and sensor fail are provided for each zone. Both audible and visual LED alarm status indication Status LEDs Units are available with 1 or 2 zones. The 2-zone option accepts the sensor inputs in 2 groups. The 2-zone alarm feature with function jumper selection can be used to program the alarm relays action and the number of remote sensors.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

CONTROLLERS

[Datasheet 07-2084]

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

45

sectionfour
MSAFIREANDGASSYSTEMS

MSA FIRE AND GAS SYSTEMS

Product Guide
MODEL10KIntegratedFireandGasSystem
An NFPA 72-approved fire and gas controller

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

FIRE/GAS

48

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
The MODEL 10K Integrated Fire and Gas System represents the next generation in highly intelligent monitoring solutions designed to reduce hazard vulnerability and meet the world's most demanding safety standards. The MODEL 10K is an innovative, modular system that is highly scalable and delivers the following features and benefits: FM Approved - To NFPA 72 compliance as a system - Proprietary central station monitoring - As both fire alarm panel & gas controller - Fault tolerant digital communications - Releasing control panel Remote I/O capability Optional fiber optic communications Color touch-screen operator interface Data and event logging Supports third party device integration Gas calibration histories (combustible and H2S gas) Simple, reliable and cost-eective field wiring topology Addressable detection loop for buildings The MODEL 10K System is designed with Rockwell Automations industry-proven Allen-Bradley ControlLogix TM programmable logic controller (PLC) technology and MSA advanced gas and flame detection field devices. Oering intelligence, flexibility and reliability, the systems controller hardware configuration and software have been tested by Factory Mutual to verify NFPA 72 compliance. The principal elements of the MODEL 10K System include: Stand-alone local fire and gas alarm panel with touch screen operator interface Power supply and battery back-up to support the fire and gas system per NFPA 72 Optional ControlNet dual media (coaxial cable or fiber optic) fault tolerant communication network, which supports communication between the local gas and flame panels and the optional MODEL 10K Central Station Optional computer-based MODEL 10K Workstation (with AC-powered UPS) to provide FM-approved central station monitoring Scalable from small systems to large plants Link up to 13 local gas and fire alarm panels over a network up to 25 kilometers long Easy integration with third-party auxiliary devices such as horns, beacons and fire suppression systems FM-approved ModBus, Ethernet or ControlNet system communications to DCS or ESD Systems HART sensor communication support The systems local and network communications equipment is based on ControlNet, a widely used high-speed, industrially hardened control and communication protocol. The MSA MODEL 10K Fire and Gas System is ideal for use in compressor stations, drilling and production platforms, refineries and pipelines, LNG/LPG facilities, storage facilities, chemical plants, electric power plants and wastewater treatment plants.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

49

FIRE/GAS

sectionfive
MSACUSTOMPRODUCTS ANDACCESSORIES

MSA CUSTOM PRODUCTS/ACCESSORIES

Product Guide
MSACustomProducts
Individually designed gas detection solutions to fit your application
Special solutions sometimes require greater versatility and unique equipment configurations. MSAs Custom Products group oers individually designed solutions for customer monitoring, control and data acquisition applications. Our custom gas detection and flow systems are built to customer specifications and combine the advantages of various MSA instruments and sensors with our electrical and mechanical engineering expertise. Our design flexibility allows MSA Custom Products to meet virtually any gas monitoring need, as each custom system is individually designed to provide the very best solution to unique application requirements. MSA Custom Products provide customers with a distinctive combination of solutions, expertise and timeliness. Expertiseandexperienceincustom productdesignforover90years MSA engineers, manufactures, services and repairs all of our instruments and sensors Gas detection and flow systems meet ISO 9001 quality assurance requirements Timelinessandfastermanufacturing turnaround Ecient and timely quotation and manufacturing process Integrated custom systems use both standard components and custom features Howthecustomproductprocessworks Customer requirements are defined; team-based process includes sales representatives, engineers, and manufacturing personnel Review performed by MSA professional sales or custom products engineer Quotation is issued, complete with drawing package and other documentation as needed PastMSAcustomproductdesigns Rack-mounted gas monitoring systems Multi-point sequencing monitoring systems Process monitoring systems Networked sensor systems Facility management monitoring systems Customer-defined packaging solutions Shipboard rugged systems OEM packaging and labeling Sensingtechniquesforcombustible gases,toxicgasesandoxygenlevels Electrochemical Catalytic bead Solid state Surface acoustic wave Photoacoustic and non-dispersive infrared technologies Photoionization Thermal conductivity

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

Additionalcustomproductfeatures andoptions Automatic time-weighted averaging Custom enclosures Data acquisition and control Emissions monitoring Flow panels Custom signaling Gas sensor auto-standardization Intrinsically safe multi-point sampling Multiplexed sensors Non-intrusively calibrated sensors Process analysis and control Productivity tracking Record keeping Report generation Sequencing systems Toxic gas trending Total hydrocarbon detection Low- and sub-ppm analyzers

CUS TOM

52

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
MSA Custom Products develops custom systems for customers in industries globally. Our sales representatives can assess your monitoring needs and are factory-trained in the application and use of all MSA instrumentation. MSA also supports customers with a comprehensive repair and service organization. Contact your local MSA sales representative for a custom solution for your specific application. Applications General Industries - Shipboard - Refineries - Paper & Pulp Mills - Refrigeration Manufacturing - Confined Spaces Chemicals - Wastewater Treatment - Steel Mills - Stack Vents - Pipelines - Mining Parking Garages - Indoor Air Quality Engine Test Facilities - Heat Treating - Hvac - Food Processing Homeland Security.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

53

CUS TOM

Product Guide
Accessories
PowerSupplies External power supplies enable remote powering of sensors. Internal power supply options are also available. One remote power supply module can power: Up to 5 electrochemical or oxygen sensors Up to 3 combustible sensors SamplingPumpModules Sampling pumps are available to bring a remote sample to a sensor. The sampling modules are available in GP and XP versions of aspirated and pumped modules.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

StrobesandHorns Strobes and horns oer prominent visual and audible indications of system alerts.

DuctMountKits Duct mount kits allow the user to monitor air within ductwork. A quick-disconnect fitting enables the calibration gas to reach the sensor without having to remove the duct-mounted sensor.

Filters Filters for sample conditioning remove particulate liquids from the sample stream.

ACCES S ORIES

RemoteDisplayModules Remote display modules provide the ability to remotely view the status of a gas monitor.

54

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

sectionsix
CALIBRATIONANDSENSOR PLACEMENT

CALIBRATION AND SENSOR PLACEMENT

Product Guide
CalibrationKits
For calibrating instruments and sensors
MSA calibration kits, when used with the appropriate calibration gas, oer a quick, convenient, and economical method of checking the response of MSA gas sensors and gas detection instrumentation. Fourteen types of calibration kits are available, and one is sure to meet your particular needs. Calibration kits contain all the components necessary to calibrate your MSA equipment. They are housed in a lightweight carrying case for easy transportation to the job site or sensor location. MSA also has a wide assortment of calibration gases available.

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

C A LIBR ATIO N

56

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
InstrumentCalibration
Whether an instrument warns and/ or alarms at the proper time depends on its ability to translate the quantity of gas it detects into an accurate reading. Calibration refers to an instruments measurement accuracy relative to a known concentration of gas. Gas detectors perform relative measurements: rather than independently assessing the quantity of gas present, they measure the concentration of the air sample and then compare it to the known concentration of the gas that the instrument is configured to sample. This known concentration serves as the instruments measurement scale, or reference point. If the instruments reference point has moved, then its reading will also move. This is called calibration drift and it happens to most instruments over time. (Common causes of calibration drift include the normal degradation of sensors, exposure of the sensor to poisons, and harsh operating conditions.) When an instrument experiences calibration drift it can still measure the quantity of gas present, but it cannot convert it into an accurate numerical reading. Regular calibration with a certified standard gas concentration updates the instruments reference point, re-enabling it to produce accurate readings. There are two methods of verifying instrument calibration: through a functional or bump test (or span check) or by performing a full calibration. Each is appropriate under certain conditions. Bump(orSpan)Check A bump check is a means of verifying calibration by exposing the instrument to a known concentration of test gas. The instrument reading is then compared to the actual quantity of gas present (as indicated on the cylinder). If the instruments response is within an acceptable range of the actual concentration then its calibration is verified. When performing a bump test, the test gas concentration should be high enough to trigger the instrument alarm. If the bump test results are not within the acceptable range, then a full calibration must be performed. FullCalibration A full calibration is the adjustment of the instruments reading to coincide with known concentrations (generally a certified standard) of zero and span gases, to compensate for calibration drift. In most cases, a full calibration is only necessary when an instrument does not pass the bump test (or after it has been serviced). ZeroCheck A zero check is performed to verify that the instrument reads true zero (also referred to as the baseline) in an environment in which no amount of target gas is present. Common situations in which a zero check is performed include: after exposure of the sensor to a sensor contaminant after the sensor has been exposed to a very high concentration of the target gas

General Industry HVAC Water & Wastewater Oil, Gas & Petrochemical

as the sensor ages, since it may gradually drift after the unit has operated in varying background conditions (e.g. humidity levels) after exposure to extreme conditions (e.g. high temperature or humidity) If the instrument fails the zero check, then a zero adjustmentwhich sets the instrument to true zeroshould be performed. FrequencyofCalibration The frequency of calibration depends on the sensors operating time, conditions of use (including chemical exposure) and user experience with the instrument. New sensors should be calibrated more often until the calibration records prove sensor stability. The calibration frequency can then be reduced to the schedule set by the safety ocer or plant manager. Before calibrating the sensors, it is good practice to apply power to the unit to allow the sensor to adapt to the new environment. Sensors should be powered at least one full hour before any calibration attempt is made.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

57

C A LIBR ATIO N

Product Guide
MSAGuidetoGasSensorSelectionandPlacement
STEP 1: To determine where to place sensors, perform an analysis of the potential gas hazards in your facility. STEP 2: Create drawings indicating all potential leak sites, as well as the severity of each sites hazard potential. There are two main categories of hazardous locations: A. Potential gas discharge points. These are places where hazardous gases may be released, such as valve stem seals, gaskets, compression fittings and expansion joints. B. Potential contact areas. These are places where hazardous gases may endanger workers, or damage equipment or property. Examples include populated areas, confined spaces, pits, stairwells, crawl spaces, shelters, and residential, business and industrial environments located nearby. STEP 3: Since gases do not always behave in the same way, take air flow conditions, as well as potential gas pockets, into consideration before placing sensors. MSA smoke tubes (P/N 458481) can be useful in measuring the direction and rate of air flow to determine areas where gases may accumulate. In general, when placing sensors the following principles should be considered: Place sensors in areas where the air currents are likely to produce the highest gas concentration, including areas where gas buildup is likely, such as corners or stopping points of moving devices that release gas. If you are attempting to take a representative room sample, do not place sensors near entrances or fresh air vents (because the sample concentration will be diluted by incoming air) unless there is a need to sample that specific area of the room. Place sensors close to the possible gas/leak source. Place combustible gas sensors between the potential leak and the ignition source. Place toxic gas and oxygen sensors between the potential leak and the populated area, and in the workers breathing zone. Consider ease of access to the sensor for maintenance requirements, such as periodic calibration. Use a remote sensor for high or inaccessible locations. Avoid mounting sensors near radio transmitters or other RFI-producing sources (e.g., welding activity and induction heaters), to reduce possible RF interference. Avoid locations where airborne particles may coat or contaminate the sensor, such as paint booths. Install sensors in a position that prevents water or dust accumulation on the sensor head (which may impede the diusion of gas into the sensor). The preferred position is facing downward, but horizontal placement is also acceptable. Facility air intakes are generally good locations for sensors. Ensure that the entire area in question is suciently monitored, including little-used areas such as closets, warehouses and other storage areas. Factor in the vapor density of the monitored gases when compared to air.

GasDensityandSensorPlacement
Gases carbon dioxide, heavy hydrocarbons hydrogen, methane Gas Density greater than air less than air Sensor Placement closer to the ground near the ceiling according to air current path, at or near breathing level (usually 4 to 6 ft. from floor)

carbon monoxide, nitrogen similar to air

C A LIBR ATIO N

58

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

Product Guide
CombustibleGasSensors Hydrogen and methane are lighter than air, so place sensors near the ceiling, and in ceiling corners where pockets of air may collect. For electric motor monitoring, place sensors near the ignition source. Gasoline is heavier than air, so place sensors nearbut not directly onthe floor. When monitoring multiple combustible gases, calibrate the instrument for the least sensitive gas. Toxic&OxygenGasSensors Place carbon monoxide and carbon dioxide sensors for indoor air quality monitoring near air intake ducts. In general, in occupied areas (e.g., confined spaces) monitor for oxygen and toxic gases in the workers breathing zone (4-6 ft.). This will vary, depending on whether the density of the gas is heavier, the same as, or lighter than, air or oxygen. Gas cylinder storage areas: If they are ventilated, place sensors near the return air vent. Acid/ solvent drum storage areas: These gases are heavier than air (e.g., heavy hydrocarbons) so place sensors close to the ground and in corners where air may collect in pockets. If the hazard is outside, place sensors near the air intake for both combustible and toxic gas monitoring; if the hazard is inside, place sensors near the exhaust. Some gases may collect in pockets in room corners, at both floor and ceiling levels. Place sensors in these areas if necessary. RefrigerantMonitorPlacement ASHRAE 15 states that a refrigerant monitor capable of detecting the TLV for a refrigerant gas must be installed in a mechanical equipment room. Place the end of the sample line in the location most likely to develop a refrigerant gas leak or spill. Such areas include valves, fittings and the chiller itself. Also, monitor any refrigerant storage location. It is good practice to keep all sampling lines as short as possible when an aspirated or pumped sampling system is used. Since most refrigerant gases are heavier than air, monitor these gases close to the floor. Any pits, stairwells or trenches are likely to fill with refrigerant gas before the main area. It may be necessary to monitor these locations for refrigerant gas. If ventilation exists in the chiller room, MSA smoke tubes (P/N 458481) will help to determine the most appropriate gas monitoring locations. Monitor displays can be placed just outside the doorway of the monitored area, enabling personnel to check the status before entering the area. ASHRAE Standard 147P states the following:4.8 Refrigerant Monitor. On large refrigerating systems for which a refrigerant monitor is required per ASHRAE 15, a refrigerant monitor capable of detecting refrigerant concentrations of 1 ppm by volume or less shall be used to provide early warning of leaks.

Toxic&CombustibleSensors Place sensors near the potential release source for process monitoring applications (e.g., pipelines, valves).

Note: : This is for informational purposes only and is intended for use as a general guide to important considerations in sensor placement. It is not intended to serve as an exhaustive review of all considerations. Due to the large number of variables present, each site should be considered individually by a trained professional. The services of an Industrial Hygienist (CIH) or Safety Professional (CSP) should be considered if an onsite survey is required.

M S A Cu s t o m e r S e r v i c e 1 - 8 0 0 - M S A - I N S T w w w. M S A n e t . c o m

59

C A LIBR ATIO N

Note: This Bulletin contains only a general description of the products shown. While uses and performance capabilities are described, under no circumstances shall the products be used by untrained or unqualified individuals and not until the product instructions including any warnings or cautions provided have been thoroughly read and understood. Only they contain the complete and detailed information concerning proper use and care of these products.

MSACorporateCenter 1000 Cranberry Woods Drive Cranberry Township, PA 16066 USA Phone 724-776-8600 www.MSAnet.com U.S.CustomerServiceCenter Phone 1-800-MSA-INST Fax 1-800-967-0398 MSACanada Phone 1-800-MSA-INST Fax 1-800-967-0398 MSAMexico Phone 01 800 672 7222 Fax 52 - 44 2227 3943 MSAInternational Phone 724-776-8626 Toll Free 1-800-672-7777 Fax 724-741-1559

Officesandrepresentativesworldwide
For further information:

ID07-2160-MC/Dec2011
MSA2011PrintedinU.S.A.