Академический Документы
Профессиональный Документы
Культура Документы
Rev. New
EMR-4000
1
Metering,
27A Statistics and
Demand
Current and Volt.:
59A
unbalance
%THD and THD
74 Fund. and RMS
46 50J 50P 51 51P 51R 66 LOP
TC min./max./avg.
phasors and
angles
3 50
37 49S 50R SOTF CTS
BF
Power:
1 Fund. and RMS
55 MVA, Mwatt, Mvar,
47 32 32V
A/D PF
3 Waveform recorder
81
27M 59M 81 R 78V 51V 50X 51X
U/O Fault recorder
*
Event recorder
Trend recorder
IRIG-B00X Programmable Zone Analog Start recorder
Breaker Wear
SNTP Logic Interlocking Outputs
Statistics recorder
History function
14
Option standard
Load
Motor
URTD Assembly
49
2 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 3
IM02602009E EMR-4000
4 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 5
IM02602009E EMR-4000
6 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 7
IM02602009E EMR-4000
b6372993fc0c1d1d3d13cc398957566e
db6a01047e9fe3a8497292a8dcab3361
RMS Handoff: 0
File: C:\p4_data\deliverEMR-4000\generated\EMR-4000_user_manual_eaton_en.odt
This manual applies to devices (version):
Version 2.0.21
Build: 13994
8 www.eaton.com
EMR-4000 IM02602009E
• Zone selective interlocking improves coordination and tripping time, and saves money compared to a
traditional bus differential scheme.
• Programmable logic control functions to accommodate different control schemes, simplify the wiring of
the starter.
• Reduce trouble shooting time and maintenance costs- Trip and event recording in non-volatile memory
provides detailed information for analysis and system restoration. 6000 cycles of waveform capture aids
in post fault analysis (viewable using Powerport-E software).
• Front RS-232 port and Powerport-E software provides local computer access and User-friendly windows
based interface for relay settings, configuration, and data retrieval.
• Fast an easy troubleshooting, improved maintenance procedures and increased device security.
Provides detailed traceability for system configuration changes.
• Breaker trip circuit monitoring improves the reliability of the breaker operation.
Features
Protection Features
• Thermal protection (49/51)
- Locked rotor protection ( 49S/51)
• Phase overcurrent elements:
- Two instantaneous elements with timers ( 50P[1], 50P[2], and 50P[3])
- Three inverse time overcurrent elements (51P[1], 51P[2], and 51P[3])
- 11 standard curves
- Instantaneous or time delay reset
• Ground overcurrent elements:
- Two instantaneous measured elements with timers (50X[1], and 50X[2])
- Two instantaneous calculated elements with timers (50R[1], and 50R[2])
- Two inverse time overcurrent measured elements (51X[1], and 51X[2])
- Two inverse time overcurrent calculated elements (51R[1], and 51R[2])
- 11 standard curves
- Instantaneous or time delay reset
• Jam or Stall protection (50J[1], 50J[2])
• Phase unbalance negative sequence overcurrent (46[1], 46[2])).
• Underload protection (37[1], 37[2], 37[3])
• Temperature protection with optional URTD (49/38).
• Stars per hour (66)
• Switch onto fault protection
www.eaton.com 9
IM02602009E EMR-4000
Metering Features
• Amperes: Positive, negative and zero sequence.
• Volts: Positive, negative and zero sequence.
• Phase angles.
• Volt-amperes and VA demand.
• Watts and kW demand.
• kWh (forward, reverse, net).
• Vars and kvar demand.
• kvarh (lead, leg and net).
• Power factor.
• Frequency.
• % THD V and I.
• Magnitude THD V and I.
• Minimum/maximum recording.
• Trending (load profile over time)
• Minimum/maximum recording
• Temperature with remote URTD module
Monitoring Features
• Trip coil monitor
• Breaker wear primary and secondary (accumulated interrupted current).
• Oscillography (6000 cycles total).
• Fault data logs (up to 20 events).
• Sequence of events report (up to 300 events).
• Trending (load profile over time)
• Motor History
• Records the last 5 motor start profiles.
• Motor Start Trending.
• CT supervision
• VT supervision
• Clock (1 ms time stamping)
Diagnostic Features
• Motor Wellness - Broken rotor bar
10 www.eaton.com
EMR-4000 IM02602009E
Control Functions
• Transition for reduced voltage starts
• Incomplete sequence delay
• Permits numbers of cold starts
• Limits numbers of starts per hour
• Anti-backspin time delay
• Mechanical load shedding
• Zero speed switch for long acceleration motors
• Motor stop inputs
• Remote trip input
• Differential trip input
• Emergency override
• Breaker/Contactor open-close/stop-start
• Remote open-close (stop-start)
• Programmable I/O
• Programmable LEDs
• Programmable Logic
• Multiple setting groups
Communication Features
• Local HMI.
• Password protected.
• Addressable.
• IRIG-B
• Local communication port.
• Remote communication port:
-RS-232
-RS-485
• Protocols:
-Modbus-RTU
-Modbus-TCP (Optional)
-IEC61850 (Optional)
• Configuration software
www.eaton.com 11
IM02602009E EMR-4000
All functions concerning the type code will be defined. Should there be a description of any functions,
parameters, or inputs/outputs that do not apply to the device in use, please ignore that information.
All details and references are explained to the best of our knowledge and are based on our experience and
observations.
This manual describes the full featured versions of the devices, including all options.
All technical information and data included in this manual reflect their state at the time this document was issued.
Eaton Corporation reserves the right to carry out technical modifications in line with further development without
changing this manual and without previous notice. Therefore no claim can be brought based on the information
and descriptions included in this manual.
Text, graphics, and formulas do not always apply to the actual delivery scope. The drawings and graphics are
not true to scale. Eaton Corporation does not accept any liability for damage and operational failures caused by
operating errors or disregarding the directions of this manual.
No part of this manual is allowed to be reproduced or passed on to others in any form, unless Eaton Corporation
has issued advanced approval in writing.
This User manual is part of the delivery scope when purchasing the device. In case the device is passed on
(sold) to a third party, the manual has to be passed on as well.
Any repair work carried out on the device requires skilled and competent personnel with verifiable knowledge
and experienced with local safety regulations and have the necessary experience with working on electronic
protection devices and power installations.
IMPORTANT DEFINITIONS
The symbol/word combinations detailed below are designed to call the User's attention to issues that could affect
User safety and well being as well as the operating life of the device.
12 www.eaton.com
EMR-4000 IM02602009E
CAUTION, without the safety alert symbol, is used to address practices not
related to personal injury.
FOLLOW INSTRUCTIONS
Read this entire manual and all other publications pertaining to the work to
be performed before installing, operating, or servicing this equipment.
Practice all plant and safety instructions and precautions. Failure to follow
the instructions can cause personal injury and/or property damage.
PROPER USE
Typical applications for this product family/device line are for example:
• Feeder protection;
• Mains protection;
• Machine protection.
This device is not designed for any usage beyond these applications. This
applies also to the use as a partly completed machinery. The manufacturer
cannot be held liable for any resulting damage. The User alone bears the
risk if this device is used for any application for which it was not designed.
As to the appropriate use of the device: the technical data specified by
Eaton Corporation has to be met.
www.eaton.com 13
IM02602009E EMR-4000
OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was
produced. To verify that you have the latest revision, be sure to check the
Eaton Corporation website:
www.eaton.com
If the User's publication is not found on the web site, please contact Eaton
Customer Support to get the latest copy.
4. Do not remove any printed circuit board (PCB) from the device cabinet
unless absolutely necessary. If you must remove the PCB from the
device cabinet, follow these precautions:
• Do not touch any part of the PCB except the edges.
• When replacing a PCB, keep the new PCB in the plastic, anti-
static protective bag it comes in until you are ready to install
the PCB. Immediately after removing the old PCB from the
device cabinet, place it in the anti-static protective bag.
14 www.eaton.com
EMR-4000 IM02602009E
Eaton Corporation reserves the right to update any portion of this publication at any time. Information provided
by Eaton Corporation is believed to be correct and reliable. However, no responsibility is assumed by Eaton
Corporation unless otherwise expressly undertaken.
• 1 – Protective Relay;
• 1 – Mount (Standard or Projection);
• 1 – Quick Start Guide; and
• 2 – CDs
Disk 1 - Contains the User's Manual, Modbus Datapoint List, Wiring Diagram, and Device
Template for Off-line Parameter Setting;
Disk 2 - Contains PowerPort-E and Quality Manager software applications.
Please make sure the product label, wiring diagram, type code, and materials and description pertain to this
device. If you have any doubts, please contact Eaton Corporation's Customer Service Department.
Storage
The devices must not be stored outdoors. If stored, it must be stored in an area with temperature and humidity
control (see the Technical Data section contained in this manual).
Important Information
www.eaton.com 15
16
IM02602009E
Active
Adaptive Parameter
Device Planning:
<Name>
Parameter of a Module-Input with a
SelectionList/DropDown. An (1..n)
signal/output from the list or a pre-
<Name>
defined value can be selected. Direct Command
Signal: 1..n, Assignment List
Prot.I dir fwd
<Name>
Measured Values: IG
"inactive", the output 1 is active and set to "ItemNull", an "active"-signal will be 1..n,
1..n,
Assignment
VeEnableList
IG.nondir Trip at
output 2 is inactive. If the setting value VG=0 given out. No assignment,1..n
"IG.Block at VE=0" is set to "active", Inactive 1
the output 2 is active and the output 1
2
is inactive. Active
Symbols
www.eaton.com
Limit value monitoring with three I/ In
analog input values. Compares 3
analog values with the set limit; output IA
values are three different binary
values as a result of the comparision.
IB
If the analog signal exceeds the limit I/
In, the corresponding output signal
becomes "1". IC
"φ "=Elements with complex functions
AR.t-D
"gray-box".
φ
t-D 0 Limit value monitoring (Compared to V
<20%Vn
a fixed value). Compares a value with
the fixed set limit; output value is
binary as a result of the comparision.
If the signal exceeds the limit, the
corresponding output signal becomes
"1".
And
AND RS flip-flop a c
S Q
abcd b d
R1 Q
Or 0 0 Unchanged
OR 0101
1010
1101
Exclusive-XR
XOR Time stage: A "1" at the
input starts the element. If
the time <name>.t is Delay Timer Delay Timer
Negated Output
Band-pass (filter)
IH1
www.eaton.com
Counter
IH1 Edge triggered counter
Band-pass (filter) + Increment +
IH2 R Reset R
IH2
17
18
Each pickup of a module (except from
supervision modules but including BF) will
lead to a general pickup (collective pickup).
Name.Pickup 14
Output Signal 2 Name.Trip Phase A
Each trip of an active, trip authorized
IM02602009E
7 18
Name.Trip Phase C
Each trip of an active, trip authorized protection module
Please Refer to Diagram: IH2 will lead to a general trip.
IH2.Blo IG 8 18a
Name.TripCmd
Please Refer to Diagram: Direction Decision Each trip of an active, trip authorized protection module
www.eaton.com
Phase overcurrent will lead to a general trip.
Name. Fault in Projected Direction 9 18b
Name.TripCmd
Please Refer to Diagram: Direction Decision Each trip of an active, trip authorized protection module
Ground Fault will lead to a general trip.
Name. Fault in Projected Direction 10 19
Name.TripCmd
Please Refer to Diagram: Direction Decision Each trip of an active, trip authorized protection module
Ground Fault will lead to a general trip.
Prot - 50R - Direction Detection 10a 19a
Name.TripCmd
Each trip of an active, trip authorized protection module
Please Refer to Diagram: Direction Decision Ground will lead to a general trip.
Prot - 50X - Direction Detection Fault 10b 19b
Name.TripCmd
Each trip of an active, trip authorized protection module
Please Refer to Diagram: VTS will lead to a general trip.
VTS.Pickup 11 19c
Each trip of an active, trip authorized protection module
Please Refer to Diagram: VTS will lead to a general trip.
VTS.Pickup 12a 19d
www.eaton.com
33
Each phase selective pickup of a module (I, IG, V, VX
depending on the device type) will lead to a phase
selective general pickup (collective pickup). Please Refer to Diagram: Bkr.Bkr Manager
Name.Pickup IC 26 Bkr.Pos CLOSE 34
Each phase selective pickup of a module (I, IG, V, VX
depending on the device type) will lead to a phase
selective general pickup (collective pickup). Please Refer to Diagram: Bkr.Bkr Manager
Name.Pickup IC 26a Bkr.Pos OPEN 35
Each phase selective pickup of a module (I, IG, V, VX
depending on the device type) will lead to a phase
selective general pickup (collective pickup).
Please Refer to Diagram: Bkr.Bkr Manager
Name.Pickup IC 26b Bkr.Pos Indeterm 36
Each phase selective pickup of a module (I, IG, V, VX
depending on the device type) will lead to a phase
selective general pickup (collective pickup). Please Refer to Diagram: Bkr.Bkr Manager
Name.Pickup 27 Bkr.Pos Disturb 37
Please Refer to Diagram: LOP.LOP Blo
LOP.LOP Blo 38a
19
20
Please Refer to Diagram: Q->&V<.Decoupling Energy Resource
Q->&V<.Decoupling Energy Resource 39
Please Refer to Diagram: CTS.Pickup
IM02602009E
CTS.Pickup 40
Bkr.Prot CLOSE
Bkr.Prot CLOSE 41
Bkr.CLOSE Cmd
Bkr.CLOSE Cmd 42
EMR-4000
www.eaton.com
EMR-4000 IM02602009E
General Conventions
»Parameters are indicated by right and left double arrow heads and written in italic.«
»SIGNALS are indicated by right and left double arrow heads and small caps.«
Module and Instance (Element) names are displayed italic and underlined.
»Pushbuttons, Modes, and Menu entries are indicated by right and left double arrow heads.«
www.eaton.com 21
IM02602009E EMR-4000
Device
EMR-4000
Device Planning
Planning of a device means to reduce the functional range to a degree that suits the protection task to be fulfilled
(i.e.: the device shows only those functions needed or desired). If the User, for example, deactivates the voltage
protection function, all parameter branches related to this function will not appear in the parameter. All
corresponding events, signals, etc. will also be deactivated. Due to this change, the parameter trees become
very transparent.
Planning also involves adjustment of all basic system data (frequency, etc.).
The manufacturer does not accept liability for any personal or material
damage as a result of incorrect planning.
22 www.eaton.com
EMR-4000 IM02602009E
There are two mounts available for the EMR-4000: a Standard Mount and a Projection Mount. To order the
EMR-4000 with a Standard Mount, append the device code with a zero (0). To order the EMR-4000 with a Pro-
jection Mount, append the device code with a one (1). Refer to the table for details of the available device op-
tions.
EMR-4000 A 0 B A 1
Choose from the following options.
Hardware Option 1
8 DI, 5 Outputs, 4AO, Removable Terminals, Zone A
Interlocking,URTD Interface, IRIG-B, Small Display.
8 DI, 5 Outputs, 4AO, Removable Terminals, Zone B*
Interlocking,URTD Interface, IRIG-B, Large
Display*.
Hardware Option 2
Phase Current 5A/1A, Ground Current 5A/1A, 0
Power Supply Range: 19-300 Vdc, 40-250 Vac. (Zero)
Phase Current 5A/1A, Sensitive Ground Current 1
0.5A/0.1A, Power Supply Range: 19-300 Vdc,
40-250 Vac.
Communication Options
Modbus-RTU (RS-485) B
IEC-61850 H
Modbus-RTU + Modbus-TCP (RJ-45) I
Conformal Coating Options
None A
Conformal Coated Circuit Boards B
Mounting Options
Standard Mount 0
(Zero)
Projection Panel Mount 1
* Consult the factory for the availability of 11 outputs and larger display.
www.eaton.com 23
IM02602009E EMR-4000
Ordering Information
24 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 25
IM02602009E EMR-4000
26 www.eaton.com
EMR-4000 IM02602009E
Overview of Slots
Housing B2
Slot1 Slot2 Slot3 Slot4 Slot5 Slot6
X1 X2 X3 X4 X5 X6
Schematic Diagram
Grounding
The housing must be carefully grounded. Connect a ground cable (AWG
12-10 [4 to 6 mm2] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is
marked with the ground symbol (at the rear side of the device).
www.eaton.com 27
IM02602009E EMR-4000
A B C
X4.
1 VA/
2 VAB
3 VB/
4 VBC
5 VC/
6 VCA
7
VX
8
X3.
A B C
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
N
6
1A
7
IC' 5A
8 IC
9 N
1A
10
5A
11 IX
IX' N
12
IA IB IC
LOAD
28 www.eaton.com
EMR-4000 IM02602009E
Wye Input Wiring with Aux VX Input Connected to the Load Side of the Breaker and 1A
CTs in Residual Connection
A
A B C
X4.
1 VA/
2 VAB
3 VB/
4 VBC
5 VC/
6 VCA
7
VX
8
X3.
A B C
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
N
6
1A
7
IC' 5A
8 IC
9 N
1A
10
IA IB IC 5A
11 IX
IX' N
12
Ph-Ph VT
(A-B, B-C, C-A)
Either OR
Ph-G VT
(A-G, B-G, C-G)
LOAD
www.eaton.com 29
IM02602009E EMR-4000
X4.
A B C
1 VA/
2 VAB
3 VB/
4 VBC
5 VC/
6 VCA
7
VX
8
X3.
A B C
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
N
6
1A
7
IC' 5A
8 IC
9 N
1A
10
5A
11 IX
IX' N
12
IA IB IC
LOAD
30 www.eaton.com
EMR-4000 IM02602009E
Open Delta VTs Input Wiring with Aux VTs Connected to the Load Side of the Breaker
and 1A CTs in Residual Connection
A
X4.
A B C
1 VA/
2 VAB
3 VB/
4 VBC
5 VC/
6 VCA
7
VX
8
X3.
A B C
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
N
6
1A
7
IC' 5A
8 IC
9 N
1A
10
IA IB IC 5A
11 IX
IX' N
12
Ph-Ph VT
(A-B, B-C, C-A)
Either OR
Ph-G VT
(A-G, B-G, C-G)
LOAD
www.eaton.com 31
IM02602009E EMR-4000
X1 X2 X3 X4 X5 X6
The type of power supply card and the number of digital inputs on it used in this slot is dependent on the ordered
device type. The different variants have a different scope of functions.
Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].
32 www.eaton.com
EMR-4000 IM02602009E
• The auxiliary voltage inputs (wide-range power supply unit) are non-polarized. The device can be
powered with an AC or DC control voltage.
Digital Inputs
For each digital input group, the related voltage input range has to be
configured. Wrong switching thresholds can result in malfunctions/wrong
signal transfer times.
The digital inputs are provided with different switching thresholds (that are configurable) (two AC and five DC in-
put ranges). The following switching levels can be defined:
• 24 Vdc;
• 48 Vdc
• 60 Vdc;
• 110/120 Vac/dc; and
• 230/240 Vac/dc.
If a voltage >80% of the set switching threshold is applied at the digital input, the state change is recognized
(logically “1”). If the voltage is below 40% of the set switching threshold, the device detects logically “0”.
www.eaton.com 33
IM02602009E EMR-4000
Terminal Marking
X?.
1 PE
2 V+ Power Supply
3 V-
4 N.C.
5 COM1
6 DI1
7 COM2
8 DI2
9 COM3
10 COM
11 DI3
12 DI4
13 DI5
14 DI6
15 DI7
16 DI8
17 Do not use
18 Do not use
Pin Assignment
0+HTL-NT
PE
1
V+
2
Power Supply
V-
3
N.C.
4
COM1
5
DI1
6
COM2
7
DI2
8
COM3
9
COM3
18 17 16 15 14 13 12 11 10
DI3
DI4
DI5
DI6
DI7
DI8
Do not use
Do not use
34 www.eaton.com
EMR-4000 IM02602009E
X1 X2 X3 X4 X5 X6
The type of card in this slot is dependent on the ordered device type. The different variants have a different
scope of functions.
• (RO-4Z X2): Assembly Group with four Relay Outputs (two Form A and two Form C) and Zone
Interlocking.
Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].
www.eaton.com 35
IM02602009E EMR-4000
Terminal Marking
X?.
1 Do not use
2 Do not use
3
RO1
4
5
RO2
6
7
8 RO3
9
10
11 RO4
12
13
14 OUT
15 COM
16
17 IN
18 COM
Pin Assignment
RO-4Z X
Do not use
1
Do not use
2
3
RO1 N.O.
54
RO2 N.O.
6
RO3 N.C.
7
RO3 CMN
8
RO3 N.O.
9
18 17 16 15 14 13 12 11 10
RO4 N.C.
RO4 CMN
RO4 N.O.
OUT
COM
IN
COM
36 www.eaton.com
EMR-4000 IM02602009E
X1 X2 X3 X4 X5 X6
This slot contains the current transformer measuring inputs. Depending on the order code, this might be a
standard current measuring card or a sensitive ground current measuring card.
The input for ground current measuring either can be connected to a zero sequence current transformer or,
alternatively, it is possible to connect the summation current path of the phase current transformer to this input
(residual connection).
www.eaton.com 37
IM02602009E EMR-4000
• Make sure the transformer ratios and the power of the CTs are
correctly rated. If the rating of the CTs is not correct (overrated),
then the normal operational conditions may not be recognized. The
pickup value of the measuring unit amounts to approximately 3% of
the rated current of the device. Also, the CTs need a current greater
than approximately 3% of the rated current to ensure sufficient
accuracy.
38 www.eaton.com
EMR-4000 IM02602009E
Terminal Markings
X?.
1A
1
5A
2 IA
N
3
1A
4
5A
5 IB
N
6
1A
7
5A
8 IC
9 N
1A
10
5A
11 IX
12 N
Pin Assignment
0+HTL-TI-x
IA-1A 1
3 IA-N
IA-5A 2
IB-1A 4
6 IB-N
IB-5A 5
IC-1A 7
9 IC-N
IC-5A 8
IX-1A 10
12 IX-N
IX-5A 11
The sensitive ground current measuring inputs has a measuring input for 0.1 A and 0.5 A.
The input for ground current measuring either can be connected to a zero sequence current transformer or,
alternatively, it is possible to connect the summation current path of the phase current transformer to this input
(residual connection).
www.eaton.com 39
IM02602009E EMR-4000
40 www.eaton.com
EMR-4000 IM02602009E
Terminal Markings
X?.
1A
1
5A
2 IA
N
3
1A
4
5A
5 IB
N
6
1A
7
5A
8 IC
9 N
0.1A
10
0.5A
11 IX
12 N
Pin Assignment
IA-1A 1
3 IA-N
IA-5A 2
IB-1A 4
6 IB-N
IB-5A 5
IC-1A 7
9 IC-N
IC-5A 8
IX-0.1A 10
12 IX-N
IX-0.5A 11
www.eaton.com 41
IM02602009E EMR-4000
For current and voltage sensing function external wired and appropriate
current and voltage transformer shall be used, based on the required input
measurement ratings. Those devices provide the necessary insulation
functionality.
Due to the sensitiveness of these measuring inputs don´t use them for the measurement of ground short circuit
currents like they occur in solidly earthed networks.
If a sensitive measuring input should be used for the measurement of ground short circuit currents, it has to be
ensured, that the measuring currents are transformed by a matching transformer according to the technical data
of the protective device.
CT Connection Options
The current transformers may be connected in several ways, and the specified configuration affects the way
system measurements are made and results computed. The computation of the residual current IR, is
dependent on the system configuration setting for the CT connection. The configurations resulting from the
setting options are shown as well as the calculated IR residual current.
A B C
X3.
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
IA N
6
1A
7
IC' 5A
8 IC
9 N
IB 1A
10
5A
11 IX
12 N
IC
IR calc = IA + IB + IC = IG
42 www.eaton.com
EMR-4000 IM02602009E
A B C
X3.
1 1A
IA'
2 5A
IA
3 N
4 1A
IB'
5 5A
IB
IA
6 N
7 1A
IC'
8 5A
IC
9 N
IB 1A
10
IX' 5A
11 IX
12 N
IC
IR calc = IA + IB + IC
IX meas = IG
www.eaton.com 43
IM02602009E EMR-4000
A B C N
X3.
1A
1
IA' 5A
2 IA
N
3
1A
4
IB' 5A
5 IB
IA N
6
1A
7
IC' 5A
8 IC
9 N
IB 1A
10
IN' 5A
11 IX
12 N
IC
IR calc´
IN
IR calc = IG = IA + IB + IC - IN
IX meas=IN
44 www.eaton.com
EMR-4000 IM02602009E
A B C N
X3.
1A
1
IA' 5A
2 IA
N
3
1A
4
IA IB' 5A
5 IB
N
6
1A
IB 7
IC' 5A
8 IC
9 N
1A
IC
IR calc´ 10
5A
11 IX
12 N
IG = IA + IB + IC + IN
IR calc = IA + IB + IC = IG + IN
IN
IX meas = IG
www.eaton.com 45
IM02602009E EMR-4000
X1 X2 X3 X4 X5 X6
For the Open Delta connection the system parameter »Main VT con« has to
be set to »Open Delta«.
For the Wye connection the system parameter »Main VT con« has to be set
to »Wye«.
46 www.eaton.com
EMR-4000 IM02602009E
Terminal Marking
X?.
1
VL1/VL12
2
3
VL2/VL23
4
5
VL3/VL31
6
7
VX
8
Pin assignment
0+HTL-TU-x
VL1.1
1
VL1.2
2
VL2.1
3
VL2.2
4
VL3.1
5
6
VL3.2
VX1.1
7
8
VX1.2
Common VT Wirings
Check the installation direction of the VTs.
For current and voltage sensing function, externally wired and appropriate
current and voltage transformer must be used, based on the required input
measurement ratings. Those devices provide the necessary insulation
functionality.
www.eaton.com 47
IM02602009E EMR-4000
Now adjust the voltage values in the nominal voltage range with the corresponding nominal frequencies that are
not likely to cause over-voltage or under-voltage trips.
Compare the values shown in the device display with the readings of the measuring instruments. The deviation
must be according to the specifications in the Technical Data section.
VT Wye
A B C
X?.
A
1 VA/
VCA'
2 VAB
VAB' B
3 VB/
4 VBC
VBC' C
5 VC/
VAB N
6 VCA
VBC VA' VB' VC'
7
VCA VX
8
VA
VB
VC
48 www.eaton.com
EMR-4000 IM02602009E
VT Open Delta
A B C
X?.
A
1 VA/
VCA'
2 VAB
VAB' B
3 VB/
4 VBC
VBC' C
5 VC/
VAB VCA
6
VBC
7
VCA VX
8
www.eaton.com 49
IM02602009E EMR-4000
X1 X2 X3 X4 X5 X6
The type of card in this slot is dependent on the ordered device type. The different variants have a different
scope of functions.
There are 4 Analog Output channels that are configurable to either output 0-20 ma., 4-20 ma., or 0- 10 Volts.
Each of the 4 channels can be independently programmed to either of these three output modes.
For details on the Analog Output, please refer to the Technical Data.
50 www.eaton.com
EMR-4000 IM02602009E
Terminals
AN O 4
X?.
1 Analog Out 1
2 Analog Out 1 COM
3 Analog Out 2
4 Analog Out 2 COM
5 Analog Out 3
6 Analog Out 3 COM
7 Analog Out 4
8 Analog Out 4 COM
9 HF Shield
10 Do not use
11 Do not use
12 Do not use
13 Do not use
14 Do not use
15 Do not use
16 Do not use
17 Do not use
18 Do not use
Pin Assignment
AN O 4
Analog Out 1
1
Analog Out 2
3
Analog Out 3
5
Analog Out 4
7
HF Shield
9
Do not use
18 17 16 15 14 13 12 11 10
Do not use
Do not use
Do not use
Do not use
Do not use
Do not use
Do not use
Do not use
www.eaton.com 51
IM02602009E EMR-4000
X1 X2 X3 X4 X5 X6
Ethernet - RJ45
Terminal Marking
RxD +
RxD –
TxD +
TxD –
N.C.
N.C.
N.C.
N.C.
1 8
52 www.eaton.com
EMR-4000 IM02602009E
X1 X2 X3 X4 X5 X6
The data communication interface in the X103 slot is dependent on the ordered device type. The scope of
functions is dependent on the type of data communication interface.
• RS485 Terminals
Make sure that the tightening torque is 2-4 In-lb [0.22-0.45 Nm].
www.eaton.com 53
IM02602009E EMR-4000
Terminal Marking
Protective Relay
+5V GND
HF Shield
560 Ω
560Ω
120Ω
B(+)
A(-)
X103
1
2
3
4
5
6
Pin Assignment
Protective Relay
+5V GND
R1 R1 HF Shield
R1 = 560 Ω R2
R2 = 120 Ω
B(+)
A(-)
1 2 3 4 5 6
54 www.eaton.com
EMR-4000 IM02602009E
Protective Relay
+5V GND
HF Shield
R1 = 560 Ω R1 R1
R2
R2 = 120 Ω
1 2 3 4 5 6
B(+)
B(+)*
A(-)*
A(-)
Wiring Example: Device at the End of the BUS (Using the Integrated Terminal Resistor)
Protective Relay
+5V GND
HF Shield
R1 = 560 Ω R1 R1
R2
R2 = 120 Ω
1 2 3 4 5 6
B(+)
A(-)
www.eaton.com 55
IM02602009E EMR-4000
HF Shield
HF Shield
HF Shield
Common
Common
Common
Common
2.2nF 2.2nF 2.2nF 2.2nF
TR-N
TR-N
TR-N
TR-P
TR-P
TR-P
TR-P
TR-N
B(+)
B(+)
B(+)
B(+)
(internal) (internal) (internal) (internal)
A(-)
A(-)
A(-)
A(-)
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Shield at bus master side Shield at bus device side Shield at bus master side Shield at bus device side
connected to earth termination connected to earth termination connected to earth termination connected to earth termination
resistors used resistors used resistors not used resistors not used
HF Shield
HF Shield
HF Shield
HF Shield
Common
Common
Common
Common
TR-P
TR-P
TR-P
TR-N
TR-N
TR-N
B(+)
B(+)
B(+)
B(+)
A(-)
A(-)
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Shield at bus master side Shield at bus device side Shield at bus master side Shield at bus device side
connected to earth termination connected to earth termination connected to earth termination connected to earth termination
resistors used resistors used resistors not used resistors not used
56 www.eaton.com
EMR-4000 IM02602009E
X1 X2 X3 X4 X5 X6
This comprises the IRIG-B00X and the system contact (Supervision Contact).
Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].
Terminals
SC
IRIG-B+
IRIG-B-
X104
1
2
3
4
5
www.eaton.com 57
IM02602009E EMR-4000
0+HTL-uP-6 / 0+HTL-uP-14
X104
1 2 3 4 5
IRIG-B+
IRIG-B-
SC CMN
SC N.C.
SC N.O.
The Supervision Contact (SC) closes after the boot phase of the device if the protection is working. This Super-
vision Contact (SC) will open if an internal device error has occurred (please refer to the Self Supervision sec-
tion).
The System-OK contact (SC relay) cannot be configured. The system contact is a Form “C” contact that picks
up when the device is free from internal faults. While the device is booting up, the System OK relay (SC) re-
mains dropped-off (unenergized). As soon as the system is properly started, the System Contact picks up and
the assigned LED is activated accordingly (please refer to the Self Supervision section).
X120 - PC Interface
The interface is a 9-pole D-Sub at all device fronts.
Pin Assignment
1 5
6 9
1 DCD
2 RxD
3 TxD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
Housing shielded
58 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 59
IM02602009E EMR-4000
GND
H1 H2 H3
X4-2
EMR-4000
X4-3
(5 Amp Config.)
EMR-4000 X4-4
Relay 1* X4-5
X2-3 X2-4
X4-6
Relay 2
X2-8 X2-9
60 www.eaton.com
EMR-4000 IM02602009E
P 30A
1 5
(+) V
CS CS 86 B
10K
10K
V
C T
b
5B
V
V17
G R
EMR-4000
X2-8 X1-13 X1-2
B
lock X
2-5 50/51/N PWR
S
tart X
2-6 SUP
X2-9 X1-9 X1-3
86A
7A
125 Vdc Source
By Customer
86
86
13
7
Spare
Spare
Spare
Spare
V
SCH
V V V
See
V
4 7 6
V
1 5
V V
2
V V
V
3A
9
V V V V
3
13
Y V
7
V
8
V
9
V
10
V
3
LS
61
55
51
53
57
bb Y
D
5R D
b
D
b b
62
B6
58
56
52
54
TC
M b b V V V 16 V V 22
V 18 V 17 V V 15 V
LC D
PS2 P
S Y LS LS
bb 1 bb
DD 86
1D
14
4
V 24 V 21 V 20 V 19
P 30A V V V V
2 B
(-)
Typical Schematic for Feeder Breaker
www.eaton.com 61
IM02602009E EMR-4000
X 1 X2
GFCT
nd.
CTs
G
X4-1
X4-2
EMR-4000 X4-3
X4-4
X4-5
X4-6
Gnd.
X
3
2V3
nd.
X
G
V
2
X2-3
EM R
X2-4
X1-14
EM R
X1-9
X2-7
EM R
X2-8
Wiring Diagrams
Please refer to the file “emr-4000_wiring_diagrams.pdf” on your User manual CD.
62 www.eaton.com
EMR-4000 IM02602009E
• »Nominal voltage«;
• »Debouncing time«: A state change will only be adopted by the digital input after the debouncing time
has expired; and
t
Input Signal
0
The debouncing time will be started each time the state of the input signal
alternates.
In addition to the debouncing time that can be set via software, there is always a
hardware debouncing time (approx 12 ms) that cannot be turned of.
DI-8P X
Name of the Assembly group:
DI-8P X1
www.eaton.com 63
IM02602009E EMR-4000
64 www.eaton.com
EMR-4000 IM02602009E
Name Description
DI 1 Signal: Digital Input
DI 2 Signal: Digital Input
DI 3 Signal: Digital Input
DI 4 Signal: Digital Input
DI 5 Signal: Digital Input
DI 6 Signal: Digital Input
DI 7 Signal: Digital Input
DI 8 Signal: Digital Input
The module WiredInputs allows to alias Digital Inputs. By means of the menu [Device Para/WiredInputs] the
User can assign specific functions on digital inputs.
www.eaton.com 65
IM02602009E EMR-4000
Alias Example: The 52a contact will be assigned/connected to Digital input1 (DI1). Once the 52a is aliased
(linked) on the DI1, the signal »WiredInput.52A« can be used instead of the DI1 signal for further
processing within the protective relay. That means, from now on any state changes of the Digital Input1
will we represented by the »WiredInput.52A« signal.
66 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 67
IM02602009E EMR-4000
Set the following parameters for each of the relay output contacts.
The states of the module outputs and the signals (e.g. states of protective functions) can be assigned
to the relay output contacts. The relay output contacts are “dry-type“ contacts.
• Each relay output contact can be set as »Latched« (Latched = active or inactive). A latched relay output
contact will return to it's latched position after a loss of power to the protective device. A latched relay
output contact will keep it´s position as long as it has not been reset and as long as the power supply
feeds the protective relay. In the case of a loss of power to the protective device, the relays will return to
the latched position once the power is restored to the protective device (latched = relay output contacts
have a memory). A latched state of a relay output contact always needs to be reset after a power loss
even if the assignments are taken away (if the assignments are reprogrammed).
• Latched = inactive«:
If the latching function is »inactive«, the relay output and, respectively, the relay output contact will adopt
the state of those pickups that were assigned.
• »Latched = active«:
If the latching function is »active«, the state of the relay output and, respectively, the relay output contact
that was set by the pickups will be stored (they have a memory that needs to be reset).
68 www.eaton.com
EMR-4000 IM02602009E
The relay output contact can only be acknowledged after reset of those signals that had initiated
the setting of the relay and after expiration of the »t-OFF delay«.
• At signal changes, the minimal latching time (»t-OFF delay«) ensures that the relay will be maintained as
picked-up or released for at least this period.
www.eaton.com 69
70
Inverting Switch Off Delay
XOR
0 State of the Relay
OR
t-Off Delay Output
Assignment 1 OR
XOR
IM02602009E
Inverting 1
Assignment 2
XOR
Acknowledgment Options
Inverting 2
Assignment 3 AND S Q
OR
XOR
Inverting 3 R1 Q
Assignment 4
XOR
Inverting 4
EMR-4000
Assignment 5
XOR
Inverting 5
www.eaton.com
Assignment 6
XOR
Inverting 6
Assignment 7
XOR
Inverting 7
Latched
Inactive
Active
Acknowledge -HMI
Acknowledge-1..n, Assignment List OR
Acknowledge-Comm
EMR-4000 IM02602009E
• If »Latched is active«, each relay output contact can be acknowledged by a signal (for example: It could
be reset by the state of a digital input);
• Via the module »Ex Acknowledge« where all relay output contacts can be acknowledged at once if the
signal for external acknowledgment that was selected from the »Assignment list« becomes true (e.g.:
the state of a digital input); and
• Via Communication (Comm), all relay output contacts can be acknowledged at once.
RO-4ZI X - Settings
RO-4Z X2
www.eaton.com 71
IM02602009E EMR-4000
72 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 73
IM02602009E EMR-4000
74 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 75
IM02602009E EMR-4000
76 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 77
IM02602009E EMR-4000
78 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 79
IM02602009E EMR-4000
80 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 81
IM02602009E EMR-4000
Signals of RO-4ZI X
Name Description
ZI OUT Signal: Zone Interlocking OUT
RO 1 Signal: Relay Output
RO 2 Signal: Relay Output
RO 3 Signal: Relay Output
RO 4 Signal: Relay Output
DISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform
maintenance while eliminating the risk of taking an entire process
off-line. (Note: Zone Interlocking and Supervision Contact cannot
be disarmed). YOU MUST ENSURE that the relays are ARMED
AGAIN after maintenance
Outs forced Signal: The State of at least one Relay Output has been set by
force. That means that the state of at least one Relay is forced
and hence does not show the state of the assigned signals.
Analog Outputs
Available Elements:
Analog Outputs ,Analog Outputs ,Analog Outputs ,Analog Outputs
These outputs can be configured by the User to represent the status of User programmed parameters that are
available from the relay. The User will find the configuration menu for this feature under the [Device Para/
Analog Outputs] menu option. Here the User can define to which parameter the output will correlate. As with
any parameter, a password is required to configure this feature.
To program this feature, the User will select the Analog Outputs option under the main menu item “Device
PARA”. Then select the wrench icon which will allow the assignment of the output to a parameter monitored by
the relay. One of the following parameters may be selected:
Once the assignment has been made, the User can select the expected range of the parameter that will
correlate to the analog output. The User will be required to enter a “Range min”, and “Range max”. The “Range
min” will determine the value at which e.g. 4 mA will be transmitted by the relay. Likewise, the “Range max”
value will determine the value that will result in the transmission of a 20 mA output.
Protective relays which have voltage monitoring and protection will have 4 Analog Outputs in card slot X5, rather
than only 1 in slot x2. The connections of the Analog Output on terminals of X5 are numbered 1 through 8.
Also, the User can assign the Line to Line voltage to the Analog Outputs. The User must also select the output
type.
The E-Series relays can be programmed to output for three different ranges of either 0- 20ma , 4- 20 ma, or
0-10 Volts.
82 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Active
www.eaton.com 83
IM02602009E EMR-4000
Name Description
-.- No assignment
Voltage.VAB RMS Measured value: Phase-to-phase voltage (RMS)
Voltage.VBC RMS Measured value: Phase-to-phase voltage (RMS)
Voltage.VCA RMS Measured value: Phase-to-phase voltage (RMS)
Voltage.V1 Fund. Measured value (calculated): Symmetrical components positive
phase sequence voltage(Fundamental)
MStart.IA FLA Measured value: Phase current multiples of FLA
MStart.IB FLA Measured value: Phase current multiples of FLA
MStart.IC FLA Measured value: Phase current multiples of FLA
MStart.I3 PFLA avg Average RMS current of all 3 phases as multiples of FLA
MStart.I3P Fla Demand RMS current of all 3 phases calculated in a fixed demand window
as multiples of FLA
49.I2T Used Thermal capacity used.
49.I2T Remained Thermal capacity remained.
RTD.Hottest WD Hottest motor winding temperature in degrees C.
URTD.WD1 Winding 1
URTD.WD2 Winding 2
URTD.WD3 Winding 3
URTD.WD4 Winding 4
URTD.WD5 Winding 5
URTD.WD6 Winding 6
URTD.MB1 Motor Bearing 1
URTD.MB2 Motor Bearing 2
URTD.LB1 Load Bearing 1
URTD.LB2 LB 2
URTD.Aux1 Auxiliary1
URTD.Aux2 Auxiliary2
URTD.RTD Max maximum temperature of all channels_
84 www.eaton.com
EMR-4000 IM02602009E
LED Configuration
The LEDs can be configured within menu:
[Device Para/LEDs/Group X]
If LEDs are configured as »Latched=active«, they will keep (return to) their
blink code and color even if there is a power outage within the power
supply of the protective device.
If the LEDs are configured as »Latched=active«, they will also retain their
blink code and color even if the LEDs are reprogrammed in another way.
This also applies if the LEDs are set to »Latched = inactive«. Resetting a
LED that has latched a signal will always require an acknowledgement.
This chapter contains information on the LEDs that are placed on the left
hand side of the display (Group A).
If your device is also equipped with LEDs on the right hand side of the
display (Group B), the analog information in this chapter is valid. The only
difference between “Group A” and “Group B” is within the menu paths.
Via the »INFO« push-button, it is always possible to display the current pickups and alarm texts that are
assigned to an LED. Please refer to the Navigation section for a description of the »INFO« push-button
functionality.
• »Latching (self holding function)«: If »Latching« is set to »Active«, the state that is set by the pickups will
be stored until it is reset. If »Latching« is set to »Inactive«, the LED always adopts the state of those
pickups that were assigned.
• »LED active color«: LED lights up in this color when at least one of the allocated functions is valid (red,
red-flashing, green, green flashing, off).
• »LED inactive color«: LED lights up in this color when none of the allocated functions is valid (red, red-
flashing, green, green flashing, off).
• »Assignment 1...n« Apart from the LED for System OK, each LED can be assigned up to five functions
(e.g. pickups) out of the »Assignment list«.
www.eaton.com 85
IM02602009E EMR-4000
Acknowledgment Options
• A signal from the »LED Reset list« (e.g. digital inputs or communication signals) (If »Latched = active«);
• The »Ex Acknowledge« module - all LEDs can be acknowledged at once, if the signal for external
acknowledgment becomes true (e.g.: the state of a digital input); and
86 www.eaton.com
Assignment 1
XOR
Inverting 1
Assignment 2
XOR
Inverting 2
Assignment 3
XOR OR LED Active Color
Inverting 3 OR
Assignment 4
LED Inactive Color
XOR
Inverting 4
EMR-4000
Assignment 5
XOR
Inverting 5
www.eaton.com
AND S Q
R1 Q
Latched
Inactive
Active
Acknowledge -HMI
Acknowledge-1..n, Assignment List OR
Acknowledge-Comm
IM02602009E
87
IM02602009E EMR-4000
LED Settings
LEDs group A ,LEDs group B
88 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 89
IM02602009E EMR-4000
90 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 91
IM02602009E EMR-4000
92 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 93
IM02602009E EMR-4000
94 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 95
IM02602009E EMR-4000
96 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 97
IM02602009E EMR-4000
98 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 99
IM02602009E EMR-4000
100 www.eaton.com
EMR-4000 IM02602009E
Front Panel
1 2 3 4
Protective
Device
5
Softkeys
6 7 8 9 10
www.eaton.com 101
IM02602009E EMR-4000
102 www.eaton.com
EMR-4000 IM02602009E
• Navigation;
• Parameter decrement/increment;
www.eaton.com 103
IM02602009E EMR-4000
Softkey Description
• Via »SOFTKEY« »Up«, the User will be taken to the prior menu point/one parameter up by
scrolling upwards.
• Via »SOFTKEY« »Left«, the User will be taken one step back.
• Via »SOFTKEY« »Down«, the User will be taken to the next menu point/one parameter down
by scrolling downwards.
• Via »SOFTKEY« »Right«, the User will be taken to a sub-menu.
• Via »SOFTKEY« »Top of List«, the User will be taken directly to the top of a list.
• Via »SOFTKEY« »Bottom of List«, the User will be taken directly to the end of a list.
• Via »SOFTKEY« »+«, the related digit will be incremented. (Continuous pressure -> fast).
• Via »SOFTKEY« »-«, the related digit will be decremented. (Continuous pressure -> fast)
• Via »SOFTKEY« »Left«, the User will be taken one digit to the left.
104 www.eaton.com
EMR-4000 IM02602009E
Softkey Description
• Via »SOFTKEY« »Right«, the User will be taken one digit to the right.
• Via »SOFTKEY« »Parameter Setting«, the User will call up the parameter setting mode.
In order to return to the main menu, just keep pressing the Softkey »Arrow-Left« until you arrive at the »Main
Menu».
Key Description
á Move up within the navigation tree or parameter list.
Ctrl+O Opens the file opening dialog. Allows browsing through the file system for an existing
device file.
Ctrl+N Creates a new parameter file by means of a template.
www.eaton.com 105
IM02602009E EMR-4000
Key Description
Ctrl+Shift+T Moves back to the navigation window.
106 www.eaton.com
EMR-4000 IM02602009E
PowerPort-E
PowerPort-E is software that is used to configure a device and read data from a device. PowerPort-E provides
the following:
Installation of PowerPort-E
Port 52152 must not be blocked by a Firewall. If it is, the connection will be
blocked.
System Requirements: Windows 2000, Windows XP, Windows Vista, or Windows 7).
To install PowerPort-E:
• Select an installation path or confirm the standard installation path by mouse click on the »Continue«
button.
• Confirm the entry for the suggested installation folder by mouse click on the »Continue« button.
If the suggested installation folder was chosen in the procedure above, the User can now call up the program via
Uninstalling PowerPort-E
Via the [Start>System Control >Software] menu, the PowerPort-E application can be uninstalled from the com-
puter.
www.eaton.com 107
IM02602009E EMR-4000
If the PC/notebook does not have a serial interface, the User will need a
special USB-to-serial-adapter. If the USB-to-serial-adapter is correctly
installed, communication with the device can be established using the CD
provided (see the next section).
• Connect the PC/notebook with the device via a null modem cable.
• When initially setting up the connection, a dialog window appears with the information that, so far, a
direct connection with your protection device has not been established. Click on »Yes«.
• If, to this point, a location has not been set up on your PC, your location information has to be put in.
Confirm the pop-up window »Telephone and Modem Options« with »OK«.
• The Windows network connection assistant appears after the location information is set up. Select the
connection type »Establish direct connection to another computer«.
• Select the serial interface (COM-Port) where the device shall be connected.
• Select »To be used for all Users« in the »Availability of the connection« window.
• Do not change the connection name appearing in window »Name of the connection« and click the
button »Complete«.
108 www.eaton.com
EMR-4000 IM02602009E
• Finally, you arrive again in the window »Device Installation« from where you started establishing the
connection. Confirm the adjustments by clicking the »OK« button.
If the PC/notebook does not have a serial interface, the User will need a
special USB-to-serial-adapter. If the USB-to-serial-adapter is correctly
installed, communication with the device can be established using the CD
provided (see the next section).
• Connect your PC/notebook with the device via a null modem cable.
• When initially setting up the connection, a dialog window appears with the information that, so far, a
direct connection with your protection device has not been established. Click on »Yes«.
www.eaton.com 109
IM02602009E EMR-4000
• If, to this point, a location has not been set up on your PC, your location information has to be put in.
Confirm the following pop-up window »Telephone and Modem Options« by selecting »OK«.
• The Windows network connection assistant appears after the location information is set up. Select the
connection type »Establish direct connection to another computer«.
• Select the serial interface (COM-Port) where the device will be connected.
• Select »To be used for all Users« in the »Availability of the connection« window.
• Do not change the connection name appearing in the »Name of the connection« window and click the
»Complete« button.
• Finally, you arrive again in the »Device Installation« window where you started establishing the
connection. Confirm the adjustments by clicking the »OK« button.
Protective
Relay
RS232
PowerPort-E
110 www.eaton.com
EMR-4000 IM02602009E
2. Installing a (virtual) modem (that is a precondition for TCP/IP communication via a null modem cable)/
(to be done within the Windows Phone and Modem dialog).
3. Establishing a network connection between PowerPort-E and the device (to be done within
PowerPort-E).
• Open the Windows Start menu and type “Phone and Modem” and RETURN.
• This opens the “Phone and Modem” Dialog.
• Go to the »Modem« tab.
• Click on the »Add« button.
• The Hardware Wizard window “Install New Modem” pops up.
• Set the check box “Don´t detect my modem; I will select it from a list”.
• Click on the »Next« button.
• Select Communications cable between two computers.
• Click on the »Next« button.
• Choose the correct COM-Port.
• Click on the »Next« button.
• Click on the »Finish« button.
• Select the new added modem and click on the »Properties« button.
• Go to the »General« tab.
• Click on the »Change settings« button.
• Go to the »Modem« tab.
• Within the Drop-Down Menu, set the correct baud rate = 115200.
• Close this dialog with the »OK« button.
• Close the Phone and Modem dialog with the »OK« button.
• You have to reboot your computer now!
• Connect the device to the PC/notebook via a correct null modem cable.
• Run PowerPort-E.
• Call up »Device Connection« within the menu »Device Connection«.
• Click on the »Settings« button.
• A connection wizard will pop up asking you How do you want to connect.
• Choose »Dial-up«.
• The telephone number must not be empty. Please enter any number (e.g. 1).
• The User name and password can be ignored.
• Click on the »OK« button.
www.eaton.com 111
IM02602009E EMR-4000
If your computer has no direct connection to the Internet, that means that it is placed behind a proxy server. In
certain circumstances, the device connection has to be modified. The device connection has to be provided with
the proxy settings.
Internet Explorer
For each connection, the proxy settings have to be set manually. Please proceed as follows.
• Set the check box »Use Proxy Server for this connection«.
• Enter the proxy settings that are available from your network administrator.
Firefox
The proxy settings are centrally managed, so there is no need to modify any settings.
(In case there is more than one protective device within the TCP/IP network
or establishing an unintentional wrong connection to a protective device
based on a wrong entered IP address.
112 www.eaton.com
EMR-4000 IM02602009E
The User MUST double check the IP addresses of the connection that is to
be established. That means, the User MUST first read out the IP address at
the HMI of the device (within menu [Device para/TCP IP]) then compare the
IP address with the list. If the addresses are identical, establish the
connection. If they are not, DO NOT establish the connection.
Call up the »Device parameter/TCP/IP« menu at the HMI (panel) and set the following parameters:
• TCP/IP address
• Subnet mask
• Gateway
PowerPort-E
TCP/IP
IP-Address
Device
Example
www.eaton.com 113
IM02602009E EMR-4000
Or:
PowerPort-E
TCP/IP
Ethernet
TCP/IP
TCP/IP TCP/IP
IP-Address
IP-Address
IP-Address
Protective Protective
...
Relay Relay
114 www.eaton.com
EMR-4000 IM02602009E
Part 1: If you don´t know the Slave ID of the device that should be connected via Modbus Tunnel, it can be read
out at the device.
• Call up the menu »Device parameter/Modbus« at the HMI (panel) and read out the Slave ID:
Part 2: Setting the IP address of the gateway and the Slave ID of the device that is to be connected via Modbus
tunnel using PowerPort-E
PowerPort-E
TCP/IP
Modbus RTU
SLAVE ID n
SLAVE ID 3
Protective Protective
...
Relay Relay
www.eaton.com 115
IM02602009E EMR-4000
PowerPort-E Troubleshooting
• Make sure that the Windows service Telephony is started. In [Start>System Control >Administration
>Services] the service »Telephony« must be visible and must have been started. If not, the service has
to be started.
• For establishing the connection, the User needs to have sufficient rights (administration rights).
• If a firewall is installed on your computer, TCP/IP port 52152 must have been released.
• If your computer does not have a serial interface, the User needs a USB-to-serial-adapter, approved by
Eaton Corporation. This adapter has to be properly installed.
• Ensure that a null modem cable is used (a standard serial cable without control wires does not enable
communication).
116 www.eaton.com
EMR-4000 IM02602009E
»Cancel«:
The warning is ignored and the connection adjustments remain as they are
set. This procedure is accepted for a limited time, but the User is required
to establish a correct connection at a later time.
• Close PowerPort-E.
• Click on the correct (in case there is more than one) entry »Connection cable between two computers«.
www.eaton.com 117
IM02602009E EMR-4000
The star symbol (in the device tree window) indicates that parameters in the
opened file (within PowerPort-E) differ from parameters stored on your
local hard disk.
If a parameter file is saved on the local hard drive, these parameters are no
longer classified to be modified and cannot be transmitted via the »Transfer
only modified parameters into the device« button.
In case the User has loaded and modified a parameter file from the device
and saved it to the local hard drive without transferring the parameters into
the device beforehand, the User cannot use the »Transfer only modified
parameters into the device« button. In this case, use the »Transfer all
parameters into the device« button.
The »Transfer only modified parameters into the device« button only works
if modified parameters are available in the PowerPort-E application.
In contrast, all parameters of the device are transferred when the »Transfer
all parameters into the device« button is pressed (provided all device
parameters are valid).
• In order to (re-)transfer changed parameters into the device, select »Transfer all parameters into the
device« in the »Device« menu.
• Confirm the safety inquiry »Shall the parameters be overwritten into the device?«.
• Confirm the inquiry »Parameters successfully updated?«. It is recommended to save the parameters
into a local file on your hard drive. Confirm »Shall The Data Be Saved Locally?“« with »Yes«
(recommended). Select a suitable folder on the hard disk.
• The changed parameter data are now saved in the chosen folder.
118 www.eaton.com
EMR-4000 IM02602009E
Click on »Save as ...« in the »File« menu. Specify a name, choose a folder on the hard disk, and save the
device data accordingly.
• Printer settings;
• Page preview;
• Printing; and
• Exporting the selected print range into a "txt" file.
The printing menu of the PowerPort-E software offers different types of printing ranges.
When exporting data, only the actual selected printing range will be
exported into a “txt” file. That means that if the User has chosen the
“Complete device parameter tree” printing range, then the “Complete
device parameter tree” will be exported. But, if the User has chosen the
“Actual working window” printing range, only that range of data will be
exported.
If the User exports a “txt” file, the content of this file is encoded as
Unicode. That means that, if the User wants to edit this file, the application
must support Unicode encoded files (e.g.: Microsoft Office 2003 or higher).
www.eaton.com 119
IM02602009E EMR-4000
The PowerPort-E application also enables the User to create a configuration/parameter file off-line using a
“Device Model”. The advantage of using a device model is that the User can pre-configure a device by setting
parameters in advance.
The User can also read the parameter file out of the device, further process it off-line (e.g.: from the office) and
finally re-transfer it to the device.
• Load an existing parameter file from a device (please refer to the Section “Loading Device Data When
Using PowerPort-E");
• Create a new parameter file (see below); or
• Open a locally saved parameter file (backup).
• In order to create a new off-line parameter file, select »Create new parameter file« within the »File«
menu.
• A working window pops- up. Please make sure that you select the right device type with the correct
version and configuration.
• In order to save the device configuration, select »Save« out of the »File« menu.
• Within the »Modify Device Configuration (Typecode)« menu, the User can modify the device
configuration or simply find out the type code of the current selection.
If the User wants to transfer the parameter file into a device, please refer to Section “Restoring Device Data
When using PowerPort-E”.
Measuring Values
120 www.eaton.com
EMR-4000 IM02602009E
• If the device data have not been loaded, select »Receive Data From The Device« from the »Device«
menu.
• Double click on the »Measured Values« icon within the »Operation« navigation tree.
• Double click the »Standard Values« or »Special values« within the »Measured values« tree.
• The measured and calculated values are now shown in tabular form in the window.
To have the measuring data read in a cyclic manner, select »Auto refresh«
in the »View« menu. The measured values are read out about every two
seconds.
If the device is not equipped with an voltage measuring card the first measuring input on the first current
measuring card (slot with the lowest number) will be used as the reference angle (»IA«).
www.eaton.com 121
IM02602009E EMR-4000
122 www.eaton.com
EMR-4000 IM02602009E
The first measuring input on the first measuring card (slot with the lowest number) is used as the reference
angle.
www.eaton.com 123
IM02602009E EMR-4000
124 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 125
IM02602009E EMR-4000
126 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 127
IM02602009E EMR-4000
Energy Counter
ECr
128 www.eaton.com
EMR-4000 IM02602009E
Statistics
Statistics
In the »Operation/Statistics« menu, the minimum, maximum, and mean values of the measured and calculated
quantities can be found. The statistics are ordered by »Standard values« and »Special values« (depending on
the type of device and the device planning).
In the »Device Parameter/Statistics« menu, the User can either set a fixed synchronization time and a
calculation interval or start and stop the statistics via a function (e.g.: digital input).
• If device data have not been downloaded recently, click »Receive Data From The Device« in the
»Device« menu.
• Double click on the »Statistics« icon within the »Operation« navigation tree.
The values can be read out cyclically. For this purpose, please select »Auto Refresh« out of the »View« menu.
Statistics (Configuration)
The Statistics module can be configured within the »Device Parameter/Statistics« menu.
The time interval, that is taken into account for the calculation of the statistics, can either be limited by a fixed
duration or it can be limited by a start function (freely assignable signal from the »assignment list« menu).
Fixed Duration:
If the statistics module is set to a fixed duration/time interval, the minimum, maximum, and average values
will be calculated and displayed continuously on the basis of this duration/time interval.
If the statistics module is to be initiated by a start function, the statistics will not be updated until the start
function becomes true (rising edge). At the same time, a new time interval will be started.
www.eaton.com 129
IM02602009E EMR-4000
• If device data have not been downloaded recently, click »Receive Data From The Device« in
the»Device« menu.
• Double click on the »Statistics« icon within the »Device Parameter« navagation tree.
Direct Commands
Parameter Description Setting Range Default Menu Path
ResFc all Resetting of all Statistic values (Current Inactive, Inactive [Operation
Demand, Power Demand, Min, Max) Active /Reset
/Flags]
ResFc I Resetting of Statistics - Current Demand Inactive, Inactive [Operation
Demand (avg, peak avg) Active /Reset
/Flags]
ResFc P Resetting of Statistics - Power Demand Inactive, Inactive [Operation
Demand (avg, peak avg) Active /Reset
/Flags]
ResFc Min Resetting of all Minimum values Inactive, Inactive [Operation
Active /Reset
/Flags]
ResFc Max Resetting of all Maximum values Inactive, Inactive [Operation
Active /Reset
/Flags]
130 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 131
IM02602009E EMR-4000
132 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 133
IM02602009E EMR-4000
134 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 135
IM02602009E EMR-4000
136 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 137
IM02602009E EMR-4000
138 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 139
IM02602009E EMR-4000
System Alarms
Available Elements:
SysA
Within the System Alarms menu [SyA] the User can configure:
• General Settings (activate/inactivate the Demand Management, optional assign a signal, that will block
the Demand Management);
• THD Protection.
Demand Management
Demand is the average of system current or power over a time interval (window). Demand management
supports the User to keep energy demand below target values bound by contract (with the energy supplier). If
the contractual target values are exceeded, extra charges are to be paid to the energy supplier.
Therefore, demand management helps the User detect and avoid averaged peak loads that are taken into
account for the billing. In order to reduce the demand charge respective to demand rate, peak loads, if possible,
should be diversified. That means, if possible, avoiding large loads at the same time. In order to assist the User
in analyzing the demand, demand management might inform the User by an alarm. The User might also use
demand alarms and assign them on relays in order to perform load shedding (where applicable).
Step1. Configure the general settings within the [Device Para/Demand] menu:
Example for a fixed window: If the range is set for 15 minutes, the protective device calculates
the average current or power over the past 15 minutes and updates the value every 15 minutes.
Example for a sliding window: If the sliding window is selected and the interval is set to 15
minutes, the protective device calculates and updates the average current or power continuously,
for the past 15 minutes (the newest measuring value replaces the oldest measuring value
continuously).
140 www.eaton.com
EMR-4000 IM02602009E
Duration
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Sliding
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
t-Delay
Average Calculation Pickup
0
Sliding
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
www.eaton.com 141
IM02602009E EMR-4000
Step 2. In addition, the Demand specific settings have to be configured in the [System Para/System
Alarms/Demand] menu:
• Determine if the demand should generate an alarm or if it should run in the silent mode
(Alarm active/inactive);
• Set the threshold; and
• Where applicable, set a delay time for the alarm.
Peak Demand
The protective device also saves the peak demand values for current and power. The quantities represent the
largest demand value since the demand values were last reset. Peak demands for current and system power
are date and time stamped.
Within the [Operation/Demand] menu, the current Demand and Peak demand values can be seen.
Minimum values since last reset: The minimum values are continuously compared to the last minimum value
for that measuring value. If the new value is less than the last minimum, the value is updated. Within the
[Device Para/Statistics] menu, a reset signal can be assigned.
Maximum values since last reset: The maximum values are continuously compared to the last maximum
value for that measuring value. If the new value is greater than the last maximum, the value is updated. Within
the [Device Para/Statistics] menu, a reset signal can be assigned.
THD Protection
In order to supervise power quality, the protective device can monitor the voltage (phase-to-phase) and current
THDs.
142 www.eaton.com
EMR-4000 IM02602009E
Name Description
Alarm Watt Power Signal: Alarm WATTS peak
Alarm VAr Power Signal: Alarm VArs peak
Alarm VA Power Signal: Alarm VAs peak
Alarm Watt Demand Signal: Alarm WATTS demand value
Alarm VAr Demand Signal: Alarm VARs demand value
Alarm VA Demand Signal: Alarm VAs demand value
Alm Current Demd Signal: Alarm Current demand value
Alarm I THD Signal: Alarm Total Harmonic Distortion Current
Alarm V THD Signal: Alarm Total Harmonic Distortion Voltage
Trip Watt Power Signal: Trip WATTS peak
Trip VAr Power Signal: Trip VArs peak
Trip VA Power Signal: Trip VAs peak
Trip Watt Demand Signal: Trip WATTS demand value
Trip VAr Demand Signal: Trip VARs demand value
Trip VA Demand Signal: Trip VAs demand value
Trip Current Demand Signal: Trip Current demand value
Trip I THD Signal: Trip Total Harmonic Distortion Current
Trip V THD Signal: Trip Total Harmonic Distortion Voltage
www.eaton.com 143
IM02602009E EMR-4000
144 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 145
IM02602009E EMR-4000
Resets
Collective Acknowledgments for Latched Signals:
Collective Acknowledgments
Individual Acknowledgment
If the User is within the parameter setting mode, the User cannot
acknowledge.
In case of a fault during parameter setting via the operating panel, the User
must first leave the parameter mode by pressing either the push-buttons
»C« or »OK« before accessing the »Acknowledgements« menu via the
push-button.
146 www.eaton.com
EMR-4000 IM02602009E
Manual Acknowledgment
• Press the »C« button on the panel.
• Select the item to be acknowledged via the softkeys:
• Relay Outputs;
• LEDs;
• SCADA;
• A trip command; or
• All the above mentioned items at once.
• If device data have not been downloaded recently, select »Receive Data From The Device« from the
»Device« menu.
External Acknowledgments
Within the [Ex Acknowledge] menu, the User can assign a signal (e.g.: the state of a digital input) from the
assignment list that:
Ack LED
Ex Acknowledge.Ack LED
1..n, Assignment List
Ack RO
Ex Acknowledge.Ack RO
1..n, Assignment List
Ack Comm
Ex Acknowledge.Ack Comm
1..n, Assignment List
Within the [Protection Para\Global Prot Para\TripControl] menu, the User can assign a signal that acknowledges
a pending trip command.
www.eaton.com 147
IM02602009E EMR-4000
• If device data have not been downloaded recently, select »Receive Data From The Device« from the
»Device« menu.
• Double click on the »Ex Acknowledge« icon within the operation menu.
• In the working window, the User can now assign each signal that resets all acknowledgeable LEDs, a
signal that resets all Relay Outputs, a signal that resets the SCADA signals respectively, and a signal
that acknowledges a pending trip command.
Name Description
-.- No assignment
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Modbus.Comm Cmd 1 Communication Command
Modbus.Comm Cmd 2 Communication Command
Modbus.Comm Cmd 3 Communication Command
Modbus.Comm Cmd 4 Communication Command
Modbus.Comm Cmd 5 Communication Command
Modbus.Comm Cmd 6 Communication Command
Modbus.Comm Cmd 7 Communication Command
Modbus.Comm Cmd 8 Communication Command
Modbus.Comm Cmd 9 Communication Command
Modbus.Comm Cmd 10 Communication Command
Modbus.Comm Cmd 11 Communication Command
Modbus.Comm Cmd 12 Communication Command
Modbus.Comm Cmd 13 Communication Command
148 www.eaton.com
EMR-4000 IM02602009E
Name Description
Modbus.Comm Cmd 14 Communication Command
Modbus.Comm Cmd 15 Communication Command
Modbus.Comm Cmd 16 Communication Command
Manual Resets
In the »Operation/Reset« menu, the User can:
• Reset counters;
• Delete records (e.g.: disturbance records); and
• Reset special things (like statistics, thermal replica, etc.).
• Press the »C-key« during a cold start, in order to access the »Reset« menu.
• Confirm »Reset device to factory defaults and reboot« with »Yes« in order to execute the reset to factory
defaults.«
www.eaton.com 149
IM02602009E EMR-4000
Status Display
In the status display within the »Operation« menu, the present state of all signals can be viewed. This means
the User is able to see if the individual signals are active or inactive at that moment. The User can see all
signals sorted by protective elements/modules.
State of the Module Input / Signal Is... Is Shown at the Panel as...
false / »0«
true / »1«
• If the device data have not been downloaded recently, select »Receive Data From The Device« from
»Device« menu.
• Double click on the »Status Display« icon within the operational data.
• Double click on a sub-folder (e.g. Prot) in order to see e.g. the states of the general alarms.
150 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 151
IM02602009E EMR-4000
Recorders
Waveform Recorder
Waveform rec
The waveform recorder works with 32 samples per cycle. It can be started by one of eight start events (selection
from the »Assignment list«/OR-Logic).
The waveform record contains the measuring values including the pre-trigger time. By means of PowerPort-
E/Quality Manager (option), the oscillographic curves of the analog (current, voltage) and digital channels/traces
can be shown and evaluated in a graphical form.
The waveform recorder has a storage capacity of 120 s (duration). The amount of records depends on the file
size of each record.
Determine the maximum recording time to register a waveform event. The maximum total length of a recording
is 10 s (including pre-trigger and post-trigger time).
To trigger the waveform recorder, up to eight signals can be selected from the »Assignment list«. The trigger
events are OR-linked. If a waveform record is written, a new waveform record cannot be triggered until all
trigger signals, which have triggered the previous waveform record, are gone.
Recording is only done for the time the assigned event exists (event controlled), plus the time for the pre- and
post-trigger, but not longer than 10 s. The time for the pre- and post-trigger is to be entered as percent of the
maximum file size.
The post-trigger time will be up to the "Post-trigger time" depending on the duration of
the trigger signal. The post-trigger will be the remaining time of the "Max file size" but,
at maximum, the "Post-trigger time".
Example
The waveform recorder is started by the general activation facility. After the fault has been cleared (plus follow-
up time), the recording process is stopped (but after 10 s at the latest).
The parameter »Auto Delete« defines how the device will react if a location to which to save the waveform
record is not available. In case »Auto Delete« is »Active«, the first recorded waveform will be overwritten
according to the FIFO principle. If the parameter is set to »Inactive«, recording of the waveform events will be
stopped until the storage location is manually released.
152 www.eaton.com
EMR-4000 IM02602009E
Start: 1
Trigger
Start: 2
Trigger
Start: 3
Trigger
Start: 4
Trigger
OR
Recording
Start: 5 OR
Trigger
Start: 6
Trigger
Start: 7
Trigger
Start: 8
Trigger
Man. Trigger
www.eaton.com 153
IM02602009E EMR-4000
Start 1 = Prot.Pickup
Start 2 = -.-
Start 3 = -.-
Start 4 = -.-
Start 5 = -.-
Start 6 = -.-
Start 7 = -.-
Start 8 = -.-
Auto overwriting = Active
1335 ms
Pre-trigger time
300 ms
1
Post-trigger time
365 ms
1
t-rec
2000 ms
1
2000 ms
1
154 www.eaton.com
EMR-4000 IM02602009E
Start 1 = Prot.Trip
Start 2 = -.-
Start 3 = -.-
Start 4 = -.-
Start 5 = -.-
Start 6 = -.-
Start 7 = -.-
Start 8 = -.-
t-rec < Max file size
Auto overwriting = Active
Post-trigger time = 25%
Pre-trigger time
300 ms
1
Post-trigger time
500 ms
1
t-rec
1000 ms
1
2000 ms
1
www.eaton.com 155
IM02602009E EMR-4000
• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.
• A pop-up will appear by double clicking on a waveform record. Choose a folder where the waveform
record is to be saved.
• The User can analyze the waveform records by means of the optionally available Quality Manager by
clicking on »Yes« when asked “Shall the received waveform record be opened by the Quality Manager?"
• Choose the waveform record that is to be deleted via »SOFTKEY« »up« and »SOFTKEY« »down«;
• Call up the detailed view of the waveform record via »SOFTKEY« »right«;
• Choose whether only the current or all waveform records should be deleted; and
156 www.eaton.com
EMR-4000 IM02602009E
• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.
www.eaton.com 157
IM02602009E EMR-4000
158 www.eaton.com
EMR-4000 IM02602009E
Name Description
Recording Signal: Recording
Memory full Signal: Memory Full
Clear fail Signal: Clear Failure in Memory
Res all rec Signal: All records deleted
Res record Signal: Delete Record
Man. Trigger Signal: Manual Trigger
Fault Recorder
Fault rec
The fault recorder can be started by one of eight start events (selection from the »Assignment list«/OR-Logic). It
can register up to 20 faults. The last of the recorded faults is stored in a fail-safe manner.
If one of the assigned trigger events becomes true, the fault recorder will be started. When a trigger event
happens, each fault is saved including the module and name, fault number, number of grid faults and record
number at that time. For each of the faults, the measuring values (at the time when the trigger event became
true) can be viewed.
Up to eight signals to trigger the fault recorder can be selected from the following list. The trigger events are
OR-linked.
www.eaton.com 159
IM02602009E EMR-4000
Start: 1
Trigger
Start: 2
Trigger
Start: 3
Trigger
Start: 4
Trigger
OR
Recording
Start: 5 OR
Trigger
Start: 6
Trigger
Start: 7
Trigger
Start: 8
Trigger
Man. Trigger
The parameter »Auto Delete« defines how the device will react if there is no saving place available. In case
»Auto Delete« is »Active«, the first recorded fault will be overwritten according to the FIFO principle. If the
parameter is set to »Inactive«, recording of the fault events will be stopped until the storage location is released
manually.
160 www.eaton.com
EMR-4000 IM02602009E
• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.
• Double click the »Fault Rec« icon within the »Operation/Recorders« tree.
• In order to receive more detailed information on a fault, click the »Plus Sign« in front of the fault number.
Via the print menu, the User can export the data into a file. Please proceed
as follows.
www.eaton.com 161
IM02602009E EMR-4000
162 www.eaton.com
EMR-4000 IM02602009E
Name Description
Res record Signal: Delete Record
Man. Trigger Signal: Manual Trigger
Event Recorder
Event rec
The event recorder can register up to 300 events and the last 50 (minimum) saved events are stored in non-
volatile memory, and therefore retained when power is lost to the unit. The following information is provided for
any of the events.
Record No. Fault No. No of grid faults Date of Record Module Name State
Sequential Number Number of the A grid fault No. can have Time stamp What has changed? Changed Value
ongoing fault. several Fault Nos.
• Select an event.
www.eaton.com 163
IM02602009E EMR-4000
• If the device data have not been loaded, click »Receive Data From The Device« in the »Device menu.
• Double click the »Event Rec« icon within the »Operation/Recorders« menu.
PowerPort-E is able to record more events than the device itself, if the
window of the event recorder is opened and »Automatic Up-Date« is set to
active.
Via the print menu, the User can export the data into a file. Please proceed
as follows.
Name Description
Res all rec Signal: All records deleted
164 www.eaton.com
EMR-4000 IM02602009E
Trend Recorder
Available Elements:
Trend rec
Functional Description
The Trend Data are data points stored by the Trend Recorder on the relay device over fixed intervals of time,
and can be downloaded from the device using PowerPort-E. A Trend Record is viewable using the Quality
Monitor software by selecting files saved by PowerPort-E with a file extension of “.ErTr”. The list of available
trend recorder data is viewable by selecting [Operation/ Recorders/Trend Recorder] on the front panel of the
relay.
When viewed within the Quality Manager, the trend record will show the observed values (up to 10) that the User
has specified. The available values are dependent on the ordered protective device.
Selecting the »Receive Trend Record« button will download data from the relay to the User's PC. By selecting
the »Refresh Trend Recorder«”, PowerPort-E updates the list of the Trend Recorder. The »Delete Trend
Recorder« function will clear all trend data from the relay, leaving the data files on the User's PC.
To view data using the Quality Manager, first the User must open the desired “.ErTr” file to be viewed from a
folder location previously designated by the User. Once the “.ErTr” file is open, the User will see the “Analog
Channels” that are monitored by the Trend Recorder. By clicking on the “Analog Channels”, all monitored
parameters are listed. To view a channel, the User must click on the left mouse key, then drag and drop the
channel onto the right side of the Quality Manager screen. The channel is then listed under the »Displayed
Channels«.
To remove a channel from view, the User must select the Trend Data to be removed in the »Displayed
Channels« menu tree, then click on the right mouse button to bring up the menu options. Here, the User will
find the »Remove« menu option that, when selected, will remove the trend data.
The User has to set the time interval. This defines the distance between two measuring points.
www.eaton.com 165
IM02602009E EMR-4000
Name Description
Hand Reset Hand Reset
166 www.eaton.com
EMR-4000 IM02602009E
Available Elements:
Start rec
The Motor Start Recorder is accessed using PowerPort-E or via the front panel interface of the relay. This
feature provides information recorded at the time of each start of the motor such as:
Similarly, data at the time of start can be viewed in the Quality Manager software. Here, the User can view the
RMS value of the phase currents, thermal capacity used, and temperatures measured by the URTD module if a
URTD is installed and attached to the relay.
The start recorder data is downloaded from the device when the User has selected the “Start Rec” feature. To
navigate to this feature, the User must go to the Operations / Recorders menu. Here the User will find the “Start
Rec” menu item. By selecting “Start Rec”, the Start Recorder Window will appear. To access data that has
been stored in the device using PowerPort E, the User must select the “Receive Start Recorder” button in the
upper left hand corner of the “Start Rec” window. When selected, the PowerPort-E software will retrieve the
stored records from the device.
A summary of the Start Recorder data can be retrieved by selecting the “Receive Summary Data” button in the
upper left hand corner of the “Start Rec” window. A list of all currently available Start Records is viewable by
selecting the “Refresh Start Recorder” button on the start recorder.
It is possible to delete individual recorders. First, select “Receive Start Recorder”, and then select the recorder
to be deleted by clicking on the record number, or record date followed by the selection of the “Delete Start
Record” button in the upper left hand corner of the “Start Rec” window.
To permanently remove all start records within a device's start recorder, select the “Delete All Start Records”
button also located in the upper left hand corner of the “Start Rec” window. This will remove all previously stored
start records within the device to which the User is presently connected.
When using PowerPort-E to view the Start Recorder data, the Start Recorder features can also be found by right
clicking anywhere within the “Start Rec” window.
www.eaton.com 167
IM02602009E EMR-4000
Name Description
Storing Signal: Data are saved
Statistic Recorder
The Statistic Recorder shows motor specific statistical data on a monthly base. The Statistic Recorder can
record up to 24 monthly reports. The reports are power fail-safe stored.
In order to view information from the Statistic Recorder, the User has to select [Operation/Recorder/Statisticrec]
from the menu tree.
By double clicking on the »Date of Record« statistics information can be viewed such as the number of starts,
the number of successful starts, the average start time, the »average I2T« value during any start, and the
average of all maximum currents value seen during each start.
History Function
The History function, accessible under the Operations menu, can be utilized as a counter or log of specific
occurrences monitored by the device. The types of occurrence that can be recorded include:
168 www.eaton.com
EMR-4000 IM02602009E
• Operations (OperationsCr);
• Alarms (AlarmCr);
• Trips (TripCr); and
• Totals (TotalCr).
1. Press the softkey under Menu in the display to access the “Operation” menu.
2. Press the right arrow softkey to access the Operation functions.
3. Use the softkeys under the up and down arrows to select “History” then press the softkey under the right
arrow to access the History functions.
4. Scroll to the type of occurrence to be viewed or reset then press the right arrow softkey
5. Scroll to the counter to be viewed or reset then press the right arrow softkey to access the counter. The
recorded data for the selected counter will be shown in the display. If the counter is not to be reset, use the
softkeys to return to the main menu.
6. To reset the counter, press the “Ack/Rst” softkey then press the softkey under the “Wrench” icon.
7. Using the softkeys, enter the password then press the “OK” softkey.
8. Press the softkey under “Yes” to reset the counter. Once the counter has been reset, use the softkeys to
return to the main menu.
www.eaton.com 169
IM02602009E EMR-4000
Time Synchronisation
The device gives the User the ability to synchronise the device with a central time generator. This provides the
following advantages:
• The time does not drift from the reference time. A continuously accumulating deviation of the reference
time thereby will be balanced. Also refer to the Specifications (Tolerances Real Time Clock) section.
• All time synchronised devices operate with the same time. Therefore, logged events of the individual
devices can be compared exactly and be evaluated (single events of the event recorder, disturbance
records).
• IRIG-B;
• SNTP;
• Communications-Protocol Modbus (RTU or TCP); and/or
• Communications-Protocol IEC60870-5-103.
These protocols use different hardware interfaces and are different in accuracy. Further information can be
found in the Specifications section.
Always use only one communication protocol for the time synchronisation.
Otherwise the correct function of the system clock cannot be guaranteed.
Please consider the accuracy of the time generator used. Deviations of the
time generator's time causes the same deviations on the device's system
time.
170 www.eaton.com
EMR-4000 IM02602009E
SNTP
SNTP
The device's system time will be synchronized by the connected SNTP server 1 to 4 times per minute. In turn,
the SNTP server synchronizes its time via NTP with other NTP servers. This is the normal case. Alternatively it
can receive its time via GPS, radio controlled clock, or the like.
If the server's “Stratum” has been set manually, it is not an indication of its quality or reliability.
TCP/IP
NTP-Server SNTP-Server
NTP-Protocol TCP/IP
(option) Protective Relay
SNTP-Protocol
Accuracy
The accuracy of the SNTP server used and the accuracy of its reference clock influences the accuracy of the
protection relay's clock.
With each transmitted time information, the SNTP server sends information about its accuracy:
• Stratum: The stratum gives information on how close the SNTP server within the cluster is to other NTP
servers that are connected to an atomic clock.
• Precision: This is the accuracy, the SNTP server provides the system time.
Also the performance (traffic and data package transmission time) of the connected network has an influence on
the accuracy of the time synchronization A locally installed SNTP server with an accuracy of ≤200 µsec is
recommended. If this cannot be provided, the connected server's accuracy can be checked in the
[Operation/Status Display/Time Sync.] menu:
www.eaton.com 171
IM02602009E EMR-4000
• The server quality gives information about the accuracy of the used server. The quality should be
GOOD or SUFFICENT. A server with BAD quality should not be used because this could cause
fluctuations of the time synchronization
• The network quality gives information about the network's load and data package transmission time.
The quality should be GOOD or SUFFICENT. A network with BAD quality should not be used because
this could cause fluctuations during time synchronization
SNTP Commissioning
Activate the SNTP time synchronization by means of the [Device Para/Time Sync./Sntp] menu:
Fault Analysis
If there is no SNTP signal for more than 120 sec., the SNTP status changes from “active” to “inactive” and an
entry in the Event Recorder will be set.
The SNTP functionality can be checked in the [Operation/Status Display/Time Sync./Sntp] menu.
If the SNTP status is not “active”, please proceed as follows:
172 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 173
IM02602009E EMR-4000
174 www.eaton.com
EMR-4000 IM02602009E
Name Description
SNTP active Signal: If there is no valid SNTP signal for 120 sec, SNTP is
regarded as inactive.
SNTP Counters
www.eaton.com 175
IM02602009E EMR-4000
SNTP Values
IRIG-B00X
IRIG-B
If you are using an IRIG time code that does not support the “year”
information (IRIG-B000, IRIG-B001, IRIG-B002, IRIG-B003), you have to set
the “year” manually within the device. In these cases the correct year
information is a precondition for a properly working IRIG-B.
Please note, that the signal IRIG-B.active only becomes true, if the Function
is set to active and the device receives valid IRIG-B data.
176 www.eaton.com
EMR-4000 IM02602009E
IRIG-B
Time Code Generator
Protective Relay
- +
To Other Devices
Based on the IRIG STANDARD 200-04, the device interface and software provides all time synchronization
formats IRIG-B00X (IRIG-B000 / B001 / B002 / B003 / B004 / B005 / B006 / B007) as described in the standard.
IRIG-B004 and higher will support/transmit the “year” information.
Time code B has a time frame of 1 second with an index count of 10 milliseconds and contains time-of-year and
year information in a binary code decimal (BCD) format, and seconds-of-day in straight binary seconds (SBS)
format.
The location of the IRIG-B interface depends to the device type. Please see the wiring diagram supplied with the
protective device.
Function
The following IRIG-B parameters can be set within the Device Parameters menu.
• Set the time zone parameter (choose one of the 36 UTC Time Zones).
www.eaton.com 177
IM02602009E EMR-4000
A signal will be issued if no IRIG-B time code is received for longer than 60 s.
The protective devices offer up to 18 IRIG-B assignment options for those control commands in order to carry
out the assigned action. That means if the IRIG-B time code is fed with the corresponding state of those control
commands, than they can be used for further processing within the devices (e.g.: in order to start statistics,
switch on or off street lighting).
178 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
Inverted Signal: IRIG-B inverted
Control Signal1 Signal: IRIG-B Control Signal
Control Signal2 Signal: IRIG-B Control Signal
Control Signal4 Signal: IRIG-B Control Signal
Control Signal5 Signal: IRIG-B Control Signal
Control Signal6 Signal: IRIG-B Control Signal
Control Signal7 Signal: IRIG-B Control Signal
www.eaton.com 179
IM02602009E EMR-4000
Name Description
Control Signal8 Signal: IRIG-B Control Signal
Control Signal9 Signal: IRIG-B Control Signal
Control Signal10 Signal: IRIG-B Control Signal
Control Signal11 Signal: IRIG-B Control Signal
Control Signal12 Signal: IRIG-B Control Signal
Control Signal13 Signal: IRIG-B Control Signal
Control Signal14 Signal: IRIG-B Control Signal
Control Signal15 Signal: IRIG-B Control Signal
Control Signal16 Signal: IRIG-B Control Signal
Control Signal17 Signal: IRIG-B Control Signal
Control Signal18 Signal: IRIG-B Control Signal
IRIG-B00X Values
180 www.eaton.com
EMR-4000 IM02602009E
Communication Protocols
Modbus®
Modbus
The master (substation control and protection system) can query information from the device, such as:
The master (control system) can give commands/instructions to the device, such as:
• Control of switchgear (where applicable, i.e.: each according to the applied device version);
• Change-over of parameter set;
• Reset and acknowledgment of pickups/signals;
• Adjustment of the date and time; and
• Control of pickup relays.
For detailed information on data point lists and error handling, please refer to the Modbus® documentation.
To allow configuration of the devices for Modbus® connection, some default values of the control system must be
available.
Modbus RTU
Part 1: Configuration of the Devices
• Baud rate.
www.eaton.com 181
IM02602009E EMR-4000
• »t-timeout«: communication errors are only identified after expiration of a supervision time »t-timeout«;
and
• Response time (defining the period within which an inquiry from the master has to be answered).
• For hardware connection to the control system, there is an RS485 interface at the rear side of the device
(RS485, fiber optic or terminals).
If, for example, an invalid memory address is inquired, error codes will be returned by the device that need to be
interpreted.
Modbus TCP
182 www.eaton.com
EMR-4000 IM02602009E
Call up »Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:
• TCP/IP address;
• Subnetmask; and
• Gateway.
• Setting a unit identifier is only necessary if a TCP network should be coupled to a RTU network.
• If a different port than the default port 502 should be used, please proceed as follows:
• Set the maximum acceptable time out for “no communication”. If this time has expired without any
communication, the device concludes a failure has occurred within the master system.
• There is a RJ45 interface at the rear side of the device for the hardware connection to the control
system.
www.eaton.com 183
IM02602009E EMR-4000
184 www.eaton.com
EMR-4000 IM02602009E
Name Description
Transmission Signal: Communication Active
Comm Cmd 1 Communication Command
Comm Cmd 2 Communication Command
Comm Cmd 3 Communication Command
Comm Cmd 4 Communication Command
Comm Cmd 5 Communication Command
Comm Cmd 6 Communication Command
Comm Cmd 7 Communication Command
Comm Cmd 8 Communication Command
Comm Cmd 9 Communication Command
Comm Cmd 10 Communication Command
Comm Cmd 11 Communication Command
Comm Cmd 12 Communication Command
Comm Cmd 13 Communication Command
Comm Cmd 14 Communication Command
Comm Cmd 15 Communication Command
Comm Cmd 16 Communication Command
www.eaton.com 185
IM02602009E EMR-4000
IEC 61850
IEC61850
Introduction
To understand the functioning and mode of operation of a substation in an IEC 61850 automation environment, it
is useful to compare the commissioning steps with those of a conventional substation in a Modbus TCP
environment. In a conventional substation, the individual Intelligent Electronic Devices (IEDs) communicate in a
vertical direction with the higher level control center via Communication. The horizontal communication is
exclusively realized by wiring relay outputs (RO) and digital inputs (DI) together.
In an IEC 61850 environment, communication between the IEDs takes place digitally (via Ethernet) by a service
called Generic Object Oriented Substation Event (GOOSE). By means of this service, information about events
is submitted between each IED. Therefore each IED has to know about the functional capability of all other
connected IEDs.
Each IEC 61850 capable device includes a description of its own functionality and communications skills (IED
Capability Description, *.ICD). By means of a Substation Configuration Tool to describe the structure of the
substation, assignment of the devices to the primary technique, etc., virtual wiring of the IEDs between each
186 www.eaton.com
EMR-4000 IM02602009E
other and with other switch gear of the substation can be achieved. A description of the substation configuration
will be generated in the form of a *.SCD file. Finally, this file has to be submitted to each device. Now the IEDs
are able to communicate with each other, react to interlockings, and operate switch gear.
Modbus-TCP IEC61850
Master Master
ModbusTCP
IEC61850
Ethernet Ethernet
Comm
Comm
IED1 IED2 IED3 IED1 IED2 IED3
DI RO DI RO DI RO
Commissioning steps for a conventional substation Commissioning steps for a substation with IEC 61850
with modbus TCP environment: environment:
Substation Configuration,
Generation of a Station Configuration Description (SCD) File
The substation configuration (i. e. connection of all logical nodes of protection and control devices) as well as
switch gear usually is done with a ”Substation Configuration Tool“. Therefore the ICD files of all connected IEDs
in the IEC 61850 environment have to be available. The result of the station wide “software wiring” can be
www.eaton.com 187
IM02602009E EMR-4000
Suitable Substation Configuration Tools (SCT) are available by the following Companies:
H&S, Hard- & Software Technologie GmbH & Co. KG, Dortmund (Germany) (www.hstech.de).
Applied Systems Engineering Inc. (www.ase-systems.com)
Kalki Communication Technologies Limited (www.kalkitech.com)
188 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 189
IM02602009E EMR-4000
Name Description
VirtInp1 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp2 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp3 Signal: Virtual Input (IEC61850 GGIO Ind)
190 www.eaton.com
EMR-4000 IM02602009E
Name Description
VirtInp4 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp5 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp6 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp7 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp8 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp9 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp10 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp11 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp12 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp13 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp14 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp15 Signal: Virtual Input (IEC61850 GGIO Ind)
VirtInp16 Signal: Virtual Input (IEC61850 GGIO Ind)
www.eaton.com 191
IM02602009E EMR-4000
192 www.eaton.com
EMR-4000 IM02602009E
Parameters
Parameter setting and planning can be done:
Parameter Definitions
Device Parameters
Device Parameters are part of the Device Parameter tree. By modifying the Device Parameters, the User may
(depending on the type of device):
System Parameters
System Parameters are part of the Device Parameter tree. System Parameters comprise the essential, basic
settings of your switchboard such as rated frequency and transformer ratios.
Protection Parameters
Protection Parameters are part of the Device Parameter tree. This Protection Parameters include the
following.
• Global Protection Parameters are part of the Protection Parameters: All settings and assignments
that are done within the Global Parameter tree are valid independent of the Setting Groups. They have
to be set only once. In addition, Global Protection Parameters include the parameters used for Breaker
Management.
• The Parameter Setting Switch is part of the Protection Parameters: The User may either directly
switch to a certain parameter setting group or determine the conditions for switching to another
parameter setting group.
• Setting Group Parameters are part of the Protection Parameters: By means of the Setting Group
Parameters, the User may individually adapt the protective device to the current conditions or grid
conditions. The Setting Group Parameters may be individually set in each Settings group.
www.eaton.com 193
IM02602009E EMR-4000
• Improving the Usability (Clarity): All protection modules that are currently unused can be hidden
(switched to invisible) through Device Planning. In the Device Planning menu, the User can adapt the
scope of functionality of the protective device exactly as needed. The User can improve the usability by
hiding all modules that are not currently needed.
• Adapting the device to the application: For those modules that are needed, determine how they
should be set up (e.g.: directional, non-directional, <, >...).
Direct Commands
Direct Commands are part of the Device Parameter tree but NOT part of the parameter file. They will be
executed directly (e.g.: Resetting of a Counter).
By means of the Module Inputs, information can be passed to and acted upon by the modules. The User can
assign signals to Module Inputs. The state of the signals that are assigned to an input can be viewed from the
Status Display. Module Inputs can be identified by an ”-I” at the end of the name.
Signals
Signals are part of the Device Parameter tree. The state of the signal is context-dependent.
• Signals represent the state of the installation/equipment (e.g.: position indicators of the breaker).
• Signals are assessments of the state of the grid and the equipment (System OK, Transformer failure
detected, ...).
• Signals represent decisions that are taken by the device (e.g.: Trip Command) based on the User
parameter settings.
194 www.eaton.com
Protection Para/Global Prot Para / I-Prot / I[1]...[n] / AdaptSet...
AdaptSet 4
&
AND
1..n, Assignment List
AdaptSet 3
AdaptSet 1
PSet-Switch
EMR-4000
&
AND AdaptSet 4
AdaptSet 3
PSet-Switch.Mode AdaptSet 2
AdaptSet 1
PS1
Standard [0…*In] [1...n] [0…s] [0.05...n] [1...n] [0…s] Active/Inactive Active/Inactive
PS2
[0…*In] [1...n] [0…s] [0.05...n] [1...n] [0…s] Active/Inactive Active/Inactive
www.eaton.com
PS3
[0…*In] [1...n] [0…s] [0.05...n] [1...n] [0…s] Active/Inactive Active/Inactive
PS4
[0…*In] [1...n] [0…s] [0.05...n] [1...n] [0…s] Active/Inactive Active/Inactive
PSS via Inp fct
Standard Standard Standard Standard Standard Standard Standard Standard
PSS via Comm
Function ExBlo Fc Rvs Blo Fc Blo TripCmd ExBlo TripCmd Fc Pickup Curve Shape t t-multiplier Reset Mode t-reset IH2 Blo Nondir Trip at V=0
Adaptive Parameter Sets
195
IM02602009E EMR-4000
By means of Adaptive Parameter Sets, the User can temporarily modify single parameters within the
Parameter Setting groups.
• Assign within the Global Parameter tree, within Protective Element I[1], an
activation signal for Adaptive Parameter Set 1.
The functionality of the IED (relay) can be enhanced / adapted, by means of Adaptive Parameters in order to
meet the requirements of modified states of the grid or the power supply system respectively, to manage
unpredictable events.
Moreover, the adaptive parameter can also be used to realize various special protective functions or to expand
the existing function modules in a simple way, without costly redesign the existing hardware or software platform.
The Adaptive Parameter feature allows, besides a standard parameter set, one of the four parameter sets
labeled from 1 to 4, to be used, for example, in a time overcurrent element under the control of the configurable
Set Control Logic. The dynamic switch-over of the adaptive parameter set is only active for a particular element
when its adaptive set control logic is configured and only as long as the activation signal is true.
For some protection elements, such as time overcurrent and instantaneous overcurrent ( 50P, 51P, 50G, 51G,
…), besides the “default” setting there exists another four “alternative” settings for pickup value, curve type, time
dial, and reset mode set values that can dynamically be switched-over by means of the configurable adaptive
setting control logic in the single set parameter.
If the Adaptive Parameter feature is not used, the adaptive set control logic will not be selected (assigned). The
protective elements work, in this case, just like a normal protection using the “Default” settings. If one of the
Adaptive Set Control logic is assigned to a logic function, the protective element will be “switched-over” to the
corresponding adaptive settings if the assigned logic function is asserted and will drop-out to the “Default” setting
if the assigned signal that has activated the Adaptive Set has dropped-out.
The use of Adaptive Parameters via the HMI (panel) differs a bit to the use
via PowerPort-E.
196 www.eaton.com
EMR-4000 IM02602009E
Adaptive Parameters can be also used via the HMI (instead of using the recommended PowerPort-E). The
principle method of using them via the HMI is as follows.
1. Assign an activation signal for an Adaptive Parameter Set within the Global Parameters »Global Para«
for a protective element (available for current functions only).
3. Go to the parameter that should be modified adaptively and call it up for editing (arrow-right-key).
Application Example
The tripping time »t« for the 50[1] element of »Parameter Set 1« should be desensitized (reduced) in case
Digital Input 2 becomes active.
1. Call up the menu [Protection Para/Global Protection Para/I-Prot/50[1]/Adaptive Para1] and assign Digital
Input 2 as activation signal.
3. Go to the tripping time parameter »t« by means of the softkey (arrow-down) and call up the submenu by
means of the softkey (arrow-right).
Check and confirm that the functionality is in compliance with your protection plan via a commissioning test.
Application Example
During a “Switch-OnTo-Fault” condition, the User is usually requested to make the embedded protective function
tripping of the faulted line faster, instantaneous, or sometimes non-directional.
Such a “Switch-OnTo-Fault” application can easily be realized using the Adaptive Parameter features
mentioned previously. The standard time overcurrent protection element (e.g.: 51P) should trip instantaneously
in case of SOTF condition,. If the SOTF logic function »SOTF ENABLED« is detecting a manual breaker close
condition, the relay switches to Adaptive Set 1 if the signal »SOTF.ENABLED« is assigned to Adaptive Set 1. The
corresponding Adaptive Set 1 will become active and than »t = 0« sec.
www.eaton.com 197
IM02602009E EMR-4000
The screen shot above shows the adaptive setting configurations following applications based on only one
simple overcurrent protection element:
Application Examples
• The output signal of the Switch OnTo Fault module can be used to activate an Adaptive Parameter Set
that sensitizes the overcurrent protection.
• The output signal of the Cold Load Pickup module can be used to activate an Adaptive Parameter Set
that desensitizes the overcurrent protection.
• By means of Adaptive Parameter Sets, an Adaptive Auto Reclosure can be realized. After a reclosure
attempt, the tripping thresholds or tripping curves of the overcurrent protection can be adapted.
• Depending on undervoltage, the overcurrent protection can be modified (voltage controlled). This
applies to devices that offer voltage protection only.
• The ground overcurrent protection can be modified by the residual voltage. This applies to devices that
offer voltage protection only.
• Dynamic and automatic adaption of the ground current settings in order to adapt the settings to different
loads (single-phase load diversity).
198 www.eaton.com
EMR-4000 IM02602009E
Adaptive Parameter Sets are only available for devices with current
protection modules.
Name Description
-.- No assignment
27M[1].Pickup Signal: Pickup Voltage Element
27M[2].Pickup Signal: Pickup Voltage Element
59M[1].Pickup Signal: Pickup Voltage Element
59M[2].Pickup Signal: Pickup Voltage Element
47[1].Pickup Signal: Pickup Voltage Asymmetry
47[2].Pickup Signal: Pickup Voltage Asymmetry
SOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to
modify Overcurrent Protection Settings.
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
www.eaton.com 199
IM02602009E EMR-4000
Name Description
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
200 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
www.eaton.com 201
IM02602009E EMR-4000
Name Description
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
202 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
www.eaton.com 203
IM02602009E EMR-4000
Name Description
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
204 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
www.eaton.com 205
IM02602009E EMR-4000
Name Description
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
206 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance Active
Sys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive
www.eaton.com 207
IM02602009E EMR-4000
• Configure and reset operational data (event recorder/fault recorder/power meter/switching cycles).
If the device was not active within the parameter setting mode for a longer
time (can be set between 20 – 3600 seconds), the device will automatically
reset to »Display Only« mode (Please refer to the Appendix Module Panel).
As long as the User is within the parameter setting mode, the device cannot
acknowledge.
In order to change into the operation mode (»Parameter Setting«) please proceed as follows.
2. Press the »Wrench« soft key to temporarily change into the Parameter Setting mode.
As long as the User is within the parameter setting mode, a wrench icon
will be shown in the upper right corner of the display.
Password
Password Entry at the Panel
Passwords can be entered by way of the soft keys
1 2 3 4
208 www.eaton.com
EMR-4000 IM02602009E
• Soft key 3;
• Soft key 2;
• Soft key 4; and
• Soft key 4.
Password Changes
Passwords can be changed at the device in the »Device Para/Password« menu or by means of the PowerPort-E
software.
The password for the operation mode »Parameter setting and planning« enables the User to transfer
parameters from the PowerPort-E software into the device.
When the User wants to change a password, the existing one has to be entered first. The new password (up to
8 digits) is then to be confirmed twice. Please proceed as follows.
• In order to change the password, please enter the old password followed by pressing the »OK« key.
• Next, enter the new password and press the »OK« key.
• Finally, confirm your new password and press the »OK« key.
Password Forgotten
By pressing the »C« key during cold booting a reset menu will be called up. By selecting »Reset All
Passwords?« and confirming with »Yes« all passwords will be reset to the defaults »1234«.
• Change additional parameters and save all the altered parameters and have them adopted by the
system.
www.eaton.com 209
IM02602009E EMR-4000
• Press the »OK« key to save the changed parameters directly and to have them adopted by the device.
Confirm the parameter changes by pressing the »Yes« soft key or dismiss by pressing »No« soft key.
Press the »OK« key to initiate the final storage of all parameter changes. Confirm the parameter changes by
pressing the »Yes« soft key or dismiss by pressing the »No« soft key.
Plausibility Check
210 www.eaton.com
EMR-4000 IM02602009E
• If the device data have not been loaded, select »Data To Be Received From The Device« in the
»Device« menu.
• In the working window, a tabulated overview appears showing the parameters assigned to this protective
function.
• In this table, double-click the value/parameter to be changed (in this example: »Char«).
• Another window (pop-up) is opened where the User can select the required characteristic.
A star symbol in front of the changed parameters indicates that the alterations
have only temporarily been saved. They are not yet stored and adopted by the
software/device.
Plausibility Check
So it is possible to see from each point of the menu tree that conflicts have been
detected by the application.
www.eaton.com 211
IM02602009E EMR-4000
If the software detects a conflict, it rejects the saving and adopting of the
parameters.
• In order to transfer changed parameters into the device, please select »Transfer all parameters into the
device« in the »Device« menu.
• Confirm the inquiry »Shall The Data Be Saved Locally?« with »Yes« (recommended). Select a suitable
storing location on your hard disk.
• The changed parameter data is now saved in the data file chosen. Thereafter, the changed data is
transferred to the device and adopted.
Once the User has entered the parameter setting password, PowerPort-E
will not ask the User again for the password for at least 10 minutes. This
time interval will start again each time parameters are transmitted into the
device. If, for more than 10 minutes, no parameters are transmitted into the
device, PowerPort-E will again ask for the password when the User tries to
transmit parameters into the device.
Protection Parameters
Please note that by deactivating, for example protective functions, the User
also changes the functionality of the device.
The manufacturer does not accept liability for any personal or material
damage as a result of incorrect planning.
• Global Protection Parameters »Global Prot Para«: Here the User can find all protection parameters that
are universally valid. That means they are valid independent of the protection parameter sets.
• Setting Group Parameters »Set1..4«: The protection parameters that the User set within a parameter set
are only valid if the parameter set selected is switched to active.
212 www.eaton.com
EMR-4000 IM02602009E
Setting Groups
Setting Group Switch
Within the »Protection Para/P-Set Switch« menu, the User has the following possibilities:
Name Description
-.- No assignment
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
www.eaton.com 213
IM02602009E EMR-4000
Name Description
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
214 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
www.eaton.com 215
IM02602009E EMR-4000
Name Description
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
216 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
www.eaton.com 217
IM02602009E EMR-4000
Name Description
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
218 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
www.eaton.com 219
IM02602009E EMR-4000
Name Description
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
220 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance Active
www.eaton.com 221
IM02602009E EMR-4000
Name Description
Sys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive
• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.
• To configure the Setting Group Switch respectively, manually choose an active set.
Setting groups can only be copied if there are no conflicts (no red question
marks).
For applications using multiple settings groups, one can use the configuration file from the first group to create
the second group. With the help of PowerPort-E, the User can simply copy an existing setting group to another
(not yet configured) one. The User only needs to change those parameters where the two setting groups are
different.
To efficiently establish a second parameter set where only few parameters are different, proceed as follows.
• Then define both source and destination of the parameter sets to be copied (source = copy from;
destination: copy to).
• Assign a new file name to the revised device parameter file and save it on your hard disk (backup copy).
• To transfer the modified parameters back to the device, click on the »Device« menu item and select
»Transfer All Parameters into the Device«.
222 www.eaton.com
EMR-4000 IM02602009E
• Select the two parameter sets from the two drop down menus that are to be compared with each other.
• The values that are different from the set parameters will be listed in tabular form.
• Click on the Folder icon in order to select a file on your hard disk.
• Parameters that are not included in the target file version will be deleted.
• Open a parameter file or load the parameters from a device that should be converted.
• Enter a new file name (in order to prevent overwriting the original file).
• Choose the new file type from drop down menu »File Type«.
• Confirm the security check by clicking on »Yes« only if the User is sure that the file conversion should be
executed.
www.eaton.com 223
IM02602009E EMR-4000
Added parameter:
Deleted parameter:
224 www.eaton.com
EMR-4000 IM02602009E
Device Parameters
Sys
• If device data have not been downloaded recently, click »Receive Data From The Device« in the
»Device« menu.
• From the working window, the User can now synchronize the date and time of the device with the PC
(i.e.: that means that the device accepts the date and time from the PC).
Version
Within the»Device parameters/Version« menu, the User can obtain information on the software and hardware
versions.
In order to be able to transmit a parameter file (e.g.: created off line) into the
device, the following parameters must agree:
TCP/IP Settings
Warning: Mixing up IP Addresses
(In case there is more than one protective device within the TCP/IP network or
establishing an unintentional wrong connection to a protective device based on a
wrong entered IP address.
Transferring parameters into the wrong protective device might lead to death,
personal injury, or damage of electrical equipment.
In order to prevent faulty connections, the User MUST document and maintain a
list with the IP addresses of any switchboard/protective devices.
www.eaton.com 225
IM02602009E EMR-4000
The User MUST double check the IP addresses of the connection that is to be
established. That means, the User MUST first read out the IP address at the HMI
of the device (within menu [Device para/TCP IP]) then compare the IP address
with the list. If the addresses are identical, establish the connection. If they are
not, DO NOT establish the connection.
Within »Device Para / TCP/IP« menu, the TCP/IP settings have to be set.
The first-time setting of the TCP/IP Parameters can be done at the panel (HMI) only.
Call up »Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:
• TCP/IP address;
• Subnetmask; and
• Gateway.
226 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 227
IM02602009E EMR-4000
228 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 229
IM02602009E EMR-4000
Name Description
PS 1 Signal: Parameter Set 1
PS 2 Signal: Parameter Set 2
PS 3 Signal: Parameter Set 3
PS 4 Signal: Parameter Set 4
PSS manual Signal: Manual switch over of a Parameter Set
PSS via Comm Signal: Parameter Set Switch via Communication
PSS via Inp fct Signal: Parameter Set Switch via Input Function
Min. 1 param changed Signal: At least one parameter has been changed
Maint Mode Active Signal: Arc Flash Reduction Maintenance Active
Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive
MaintMode Manually Signal: Arc Flash Reduction Maintenance Manual Mode
Maint Mode Comm Signal: Arc Flash Reduction Maintenance Comm Mode
Maint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input Mode
Param to be saved Number of parameters to be saved. 0 means that all parameter
changes are overtaken.
Ack LED Signal: LEDs Acknowledgment
Ack RO Signal: Acknowledgment of the Relay Outputs
Ack Counter Signal: Reset of all Counters
Ack Comm Signal: Acknowledge Communication
Ack TripCmd Signal: Reset Trip Command
Ack LED-HMI Signal: LEDs Acknowledgment :HMI
Ack RO-HMI Signal: Acknowledgment of the Relay Outputs :HMI
Ack Counter-HMI Signal: Reset of all Counters :HMI
Ack Comm-HMI Signal: Acknowledge Communication :HMI
Ack TripCmd-HMI Signal: Reset Trip Command :HMI
Ack LED-Comm Signal: LEDs Acknowledgment :Communication
Ack RO-Comm Signal: Acknowledgment of the Relay Outputs :Communication
Ack Counter-Comm Signal: Reset of all Counters :Communication
Ack Comm-Comm Signal: Acknowledge Communication :Communication
Ack TripCmd-Comm Signal: Reset Trip Command :Communication
Res OperationsCr Signal:: Res OperationsCr
Res AlarmCr Signal:: Res AlarmCr
Res TripCr Signal:: Res TripCr
Res TotalCr Signal:: Res TotalCr
230 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 231
IM02602009E EMR-4000
System Parameters
System Para
Within the system parameters, the User can set all parameters that are relevant for the primary side and the
mains operational method like frequency, primary and secondary values, and the star point treatment.
232 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 233
IM02602009E EMR-4000
Blocking
The device provides a function for temporary blocking of the complete protection functionality or of single
protections.
Permanent Blocking
Switching “On” or “Off” the Complete Protection Functionality
In the »Protection« module, the complete protection of the device can be switched “On” or “Off”. Set the
Function parameter to »Active« or »Inactive« in the »Prot« module.
Each of the modules can be switched “On” or “Off” (permanently). This is achieved when the »Function«
parameter is set to »Active« or »Inactive« in the respective module.
In each of the protections, the tripping command to the breaker can be permanently blocked. For this purpose,
the »TripCmd Blo« parameter has to be set to »Active«.
Temporary Blocking
To Block the Complete Protection of the Device Temporarily by a Signal
In the »Prot« module, the complete protection of the device can be blocked temporarily by a signal. On the
condition that a module-external blocking is permitted (»ExBlo Fc=active«). In addition to this, a related blocking
signal from the »Assignment list« must have been assigned. For the time the allocated blocking signal is active,
the module is blocked.
If the »Prot« module is blocked, the complete protection function does not
work. As long as the blocking signal is active, the device cannot protect
any components.
• In order to establish a temporary blockage of a protection module, the parameter »ExBlo Fc« of the
module has to be set to »Active«. This gives the permission: »This module can be blocked«.
• Within the general protection parameters, a signal has to be additionally chosen from the »Assignment
list«. The blocking only becomes active when the assigned signal is active.
234 www.eaton.com
EMR-4000 IM02602009E
The tripping command of any of the protection modules can be blocked from an external signal. In this case,
external does not only mean from outside the device, but also from outside the module. Not only real external
signals are permitted to be used as blocking signals (for example: the state of a digital input), but the User can
also choose any other signal from the »Assignment list«.
• In order to establish a temporary blockage of a protection element, the parameter »ExBlo TripCmd Fc« of
the module has to be set to »Active«. This gives the permission: »The tripping command of this element
can be blocked«.
• Within the general protection parameters, an additional signal has to be chosen and assigned to the
»ExBlo« parameter from the »Assignment list«. If the selected signal is activated, the temporary
blockage becomes effective.
www.eaton.com 235
236
IM02602009E
Trip Blockings
Name.Blo TripCmd
EMR-4000
Inactive
Active
www.eaton.com
Name.Blo TripCmd
OR 3
Name.ExBlo TripCmd Fc
Inactive
Active
Name.ExBlo TripCmd
AND
Name.ExBlo TripCmd
Name.ExBlo TripCmd-I
1..n, Assignment List
To Activate or Deactivate the Tripping Command of a Protection Module
EMR-4000 IM02602009E
Name.ExBlo2-I
Name.ExBlo
Name.ExBlo1-I
2
Name.Active
AND
AND
OR
(The General Protection module is not deactivated or blocked)
Name =All Modules That Are Blockable
Name.ExBlo 1
Name.ExBlo 2
Inactive
Inactive
Active
Active
Prot. Active
Blockings
Current protective functions cannot only be blocked permanently (»Function = Inactive«) or temporarily by any
blocking signal from the »Assignment list«, but also by »Reverse Interlocking«.
All other protection functions can be activated, deactivated, or blocked in the same manner.
www.eaton.com 237
238
IM02602009E
Blockings **
Name = I[1]...[n], IG[1]...[n]
Name.Function
Inactive
Active
Name.Active
AND 4
Name.ExBlo Fc
Inactive
Active
Name.ExBlo
AND
EMR-4000
Name.ExBlo 1
Name.ExBlo1-I
1..n, Assignment List
OR
www.eaton.com
Name.ExBlo 2
Name.ExBlo2-I
1..n, Assignment List
Name.Rvs Blo Fc
Inactive
Active
Name.Rvs Blo
AND
Name.Rvs Blo
Name.Rvs Blo-I
1..n, Assignment List
EMR-4000 IM02602009E
The »Protection« module serves as the outer frame for all other protection modules (i.e.: they are all enclosed by
the »Protection« Module).
If the master »Protection« module is allowed to be temporarily blocked and the allocated blocking signals are
active, then all protection functions will be disabled. In such a case, the protective function is »Inactive«.
Protection Active:
If the master »Protection« module was activated and a blockade for this module was not activated respectively,
the assigned blocking signals are inactive at that moment, then the »Protection« is »Active«.
If the signal becomes true, then all protective and supervisory functions will be blocked as long as one of these
signals are true.
www.eaton.com 239
240
Prot - Active
IM02602009E
Prot.Available
AND
Measured Values: OK
Prot.Active
AND 1
EMR-4000
Prot.ExBlo Fc
Inactive
www.eaton.com
Active
Prot.ExBlo
AND
Prot.ExBlo 1
Prot.ExBlo1-I
1..n, Assignment List
OR
Prot.ExBlo 2
Prot.ExBlo2-I
1..n, Assignment List
Prot.ExBlo 3**
Prot.ExBlo3-I
Selection List
Each protection element generates its own pickup and trip signals, which are automatically passed onto the
»Prot« module where the phase based and general (collective) pickup and trip signals are generated. The
»Prot« module serves as a top level and a common place to group all pickups and trips from each individual
protection element.
For instance, »PROT.PICKUP PHASE A« is the phase A pickup signal OR-ed from all protection elements; »PROT.TRIP
PHASE A« is the phase A trip signal OR-ed from all protection elements; »PROT.PICKUP« is the collective pickup
signal OR-ed from all protection elements; Prot.Trip is the collective Trip signal OR-ed from all protection
elements, and etc. The Tripping commands of the protection elements have to be fed to the »Bkr Manager«
module for further trip request processing.
If a protection element is activated and respectively decides to trip, two pickup signals will be created.
1. The module or the protection element issues an pickup/alarm (e.g.: »50P[1].PICKUP or »50P[1].TRIP«).
2. The master »Prot« module collects/summarizes the signals and issues a pickup/alarm or a trip signal
»PROT.PICKUP« »PROT.TRIP«.
www.eaton.com 241
242
IM02602009E
Prot.Pickup
Prot.Trip
Name = Each pickup of a module (except from supervision modules but including BF) will lead to a general pickup (collective pickup).
Name = Each trip of an active, trip authorized protection module will lead to a general trip.
EMR-4000
www.eaton.com
Name.Trip
15
Name.Pickup
14 Name.Trip
15 Prot.Trip
Name.Pickup OR
14 ... Prot.Pickup
OR
...
Name[n].Trip
15
Name.Pickup
14
Prot.Pickup
50P[1]...[n].Pickup IA*
24a
51P[1]...[n].Pickup IA* Prot.Pickup Phase A
24b OR
V[n].Pickup Phase A*
28
50P[1]...[n].Pickup IB*
25a
V[n].Pickup Phase B*
29
50P[1]...[n].Pickup IC*
www.eaton.com
26a
51P[1]...[n].Pickup IC* Prot.Pickup Phase C
OR
V[n].Pickup Phase C*
30
50X[1]...[n].Pickup*
27a
51X[1]...[n].Pickup*
27b
OR Prot.Pickup IX or IR
50R[1]...[n].Pickup*
27c
51R[1]...[n].Pickup*
27d
59[n].Pickup*
31
IM02602009E
243
IM02602009E EMR-4000
244 www.eaton.com
EMR-4000 IM02602009E
Name Description
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip IX or IR Signal: General Trip Ground Fault
Trip Signal: General Trip
Res Fault a Mains No Signal: Resetting of fault number and number of grid faults.
www.eaton.com 245
IM02602009E EMR-4000
Switchgear/Breaker - Manager
Bkr
Breaker Configuration
For the configuration of the breaker, great attention has to be payed to the following steps:
• Wiring
• Switching Authority
• POS Indicators wiring
• General Settings
• Trip Manager
• Interlockings
• Ex OPEN/CLOSE (Option)
• Synchronous Switching
It is recommended to use the status display in order to verify and analyze each of the steps.
The User has to establish the wiring of the Position Indicators of the Breaker to the Digital Inputs of the
protective device (52a or 52b or (both recommended)).
The User has to wire a Relay Output for the Trip command.
In case, the protective device is used for control purposes, two additional Relay Outputs have to be wired for the
Control commands (issue the OPEN and CLOSE commands). That means the Relay Output for the Breaker
Open and the Relay Output for the Breaker Close command.
Switching Authority
For the Switching Authority [Control\General Settings], the following general settings are possible:
To identify the current position of the switchgear, the switchgear contact outputs have to be used (called 52a/52b
at a breaker). The Position Indication can work on either one or both of these inputs. Nevertheless, it is
246 www.eaton.com
EMR-4000 IM02602009E
The protective device monitors and evaluates continuously the Status of the Input Signals CinBkr52a-I and
CinBkr52b-I. These signals are validated based on the supervision timers »t-Move CLOSE« and »t-Move
OPEN« validation functions. As a result, the breaker position will be detected by the following signals:
• Pos CLOSE;
• Pos OPEN;
• Pos Indeterm;
• Pos Disturb; and
• Pos State (0, 1, 2 or 3).
The following table shows how breaker positions are validated based on 52a and 52b:
1 1 0 0 1 0 0
(while a Moving (while a Moving Intermediate
timer is running) timer is running)
0 1 0 1 0 0 1
OFF
1 0 1 0 0 0 2
ON
0 0 0 0 0 1 3
(Moving timer (Moving timer Disturbed
elapsed) elapsed)
1 1 0 0 0 1 3
(Moving timer (Moving timer Disturbed
elapsed) elapsed)
If for any reason only one breaker contact (52a or 52b) is wired, the Single Contact Indication can be used.
The moving time supervision works only in one direction. If the 52a signal is connected to the device, only the
“CLOSE command” can be supervised and if the 52b signal is connected to the device, only the “OPEN
command” can be supervised.
If the single contact indication is used, the »SI SINGLECONTACTIND« will become true.
www.eaton.com 247
IM02602009E EMR-4000
NOTICE: In case of single contact indication, the protective device can monitor either
the 52a or the 52b contact only. In case of the 52a, the device will monitor / supervise
the CLOSE command. In case of the 52b, the device will monitor / supervise the
OPEN command.
If only the 52a signal is used for the Status Indication of an “CLOSE command”, the switch command will also
start the moving time, the position indication indicates an INTERMEDIATE position during this time interval.
When the switchgear reaches the end position indicated by the Pos CLOSE signal, the moving time will be
terminated. If the moving time elapsed before the switchgear has reached the end position, the switching
operation was not successful and the Position Indication will change to Pos DISTURB.
An OPEN command also starts the moving time. Because the device does not receive an open signal by the
breaker, it assumes that the breaker is in open position after the moving time has elapsed.
The following table shows how breaker positions are validated based on 52a only.
0 Not wired 0 1 0 0 1
OFF
1 Not wired 1 0 0 0 2
ON
1 Not wired 0 0 0 1 3
(after t-Move (after t-Move Disturbed
CLOSE is elapsed) CLOSE is elapsed)
If only the 52b signal is used for the monitoring of the “OPEN command”, the switch command will start the
moving timer. The Position Indication will indicate an INTERMEDIATE position. If the moving time elapsed
before the switchgear has reached the OPEN position, the switching operation was not successful and the
Position Indication will change to Pos DISTURB.
A CLOSE command also starts the moving time. Because the device does not receive a close signal by the
breaker, it assumes that the breaker is in close position after the moving time has elapsed.
The following table shows how breaker positions are validated based on 52b only.
Not wired 0 0 1 0 0 1
OFF
Not wired 1 1 0 0 0 2
ON
248 www.eaton.com
EMR-4000 IM02602009E
General Settings
In the menu [Control/Breaker/General Settings], the moving times for opening and closing of the breaker can be
set.
Trip Manager
In the Trip Manger, all tripping commands are combined by an "OR" logic. The actual tripping command to the
breaker is exclusively given by the Trip Manager. This means that only tripping commands which are assigned
in the Trip Manager lead to an operation of the breaker. In addition, the User can set the minimum hold time of
the tripping command within this module and define whether the tripping command is latched or not.
Tripable Elements
Name Description
-.- No assignment
50P[1].TripCmd Signal: Trip Command
50P[2].TripCmd Signal: Trip Command
50P[3].TripCmd Signal: Trip Command
51P[1].TripCmd Signal: Trip Command
51P[2].TripCmd Signal: Trip Command
51P[3].TripCmd Signal: Trip Command
50X[1].TripCmd Signal: Trip Command
50X[2].TripCmd Signal: Trip Command
51X[1].TripCmd Signal: Trip Command
51X[2].TripCmd Signal: Trip Command
50R[1].TripCmd Signal: Trip Command
50R[2].TripCmd Signal: Trip Command
51R[1].TripCmd Signal: Trip Command
51R[2].TripCmd Signal: Trip Command
46[1].TripCmd Signal: Trip Command
46[2].TripCmd Signal: Trip Command
ZI.TripCmd Signal: Zone Interlocking Trip Command
www.eaton.com 249
IM02602009E EMR-4000
B re a k e r
Trigger [x]
HMI
250 www.eaton.com
Bkr.Trip Bkr
Name =Each trip of an active, trip authorized protection module will lead to a general trip.
Name.TripCmd
15
OR
Name.TripCmd
15
Name.TripCmd
15 . Bkr.t-TripCmd
. 1
. OR t
. Bkr.Trip Bkr
OR 11
Name.TripCmd
15
Name.TripCmd
15
EMR-4000
www.eaton.com
Bkr.Latched
AND S Q
Active
R1 Q
Inactive
Acknowledge -HMI
Bkr.Res TripCmdCr
R
IM02602009E
251
IM02602009E EMR-4000
Interlockings
There are three interlocking inputs for each switching direction (OPEN/CLOSE) available. Switching into the
corresponding switching direction can be inhibited via these inputs. Please note: The Protection Trip commands
and the reclosure command of the auto reclosure module will be issued without interlocking. In cases when the
breaker must not be opened, the protection trip command has to be inhibited by a separate blocking signal.
Bkr.TripCmd
41
42
Bkr.OPEN Cmd
Bkr.Prot CLOSE
Bkr.CLOSE Cmd
AND
AND
following commands:
Digital Input:
commands:
15
15
15
252 www.eaton.com
EMR-4000 IM02602009E
Ex OPEN/CLOSE
If the breaker should be opened or closed by an external signal, the User can assign one signal that will trigger
the CLOSE and one signal that will trigger the OPEN command (e.g.: digital inputs or output signals of the
Logic).
An applied CLOSE command will be overwritten by an upcoming OPEN command. An applied OPEN command
will not be overwritten by an upcoming CLOSE command, that means, the OPEN command is dominantly.
Synchronous Switching
If a signal is assigned to the »Synchronism« input, the closing of the switchgear will be performed only when this
signal gets active during the maximum allowed waiting time »t-MaxSyncSuperv«.
HMI
SCADA
Autoreclosure CLOSE
SyncCheck
Ready to CLOSE
Breaker CLOSE
Initiative
www.eaton.com 253
IM02602009E EMR-4000
254 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 255
IM02602009E EMR-4000
256 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 257
IM02602009E EMR-4000
258 www.eaton.com
EMR-4000 IM02602009E
Name Description
SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary
contact (pole) only. Thus indeterminate and disturbed Positions
cannot be detected.
Pos not CLOSE Signal: Pos not CLOSE
Pos CLOSE Signal: Breaker is in CLOSE-Position
Pos OPEN Signal: Breaker is in OPEN-Position
Pos Indeterm Signal: Breaker is in Indeterminate Position
Pos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-
back signals (Position Indicators) contradict themselves. After
expiring of a supervision timer this signal becomes true.
State Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 =
CLOSE, 3 = Disturbed)
Ready Signal: Breaker is ready for operation.
Interl CLOSE Signal: One or more IL_Close inputs are active.
Interl OPEN Signal: One or more IL_Open inputs are active.
CES succesf Command Execution Supervision: Switching command executed
successfully.
CES Disturbed Command Execution Supervision: Switching Command
unsuccessful. Switchgear in disturbed position.
CES Fail TripCmd Command Execution Supervision: Trip command not executed.
CES SwitchgDir Command Execution Supervision respectively Switching Direction
Control: This signal becomes true, if a switch command is issued
even though the switchgear is already in the requested position.
Example: A switchgear that is already OPEN should be switched
OPEN again (doubly). The same applies to CLOSE commands.
CES CLOSE d OPEN Command Execution Supervision: CLOSE Command during a
pending OPEN Command.
CES SG not ready Command Execution Supervision: Switchgear not ready
CES Field Interl Command Execution Supervision: Switching Command not
executed because of field interlocking.
www.eaton.com 259
IM02602009E EMR-4000
Name Description
Prot CLOSE Signal: CLOSE command issued by the Prot module
TripCmd Signal: Trip Command
Ack TripCmd Signal: Acknowledge Trip Command
Bwear Slow Breaker Signal: Slow Breaker Alarm
Res Bwear Sl Breaker Signal: Resetting the slow breaker alarm
CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on
the setting the signal may include the CLOSE command of the
Prot module.
OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on
the setting the signal may include the OPEN command of the Prot
module.
CLOSE Cmd manual Signal: CLOSE Cmd manual
OPEN Cmd manual Signal: OPEN Cmd manual
Manually switching a switchgear at the device panel is possible at the following switching authorities:
• Local
• Local and Remote
2. Select the »Control« menu by using the »up« or »down« softkeys and press the »right« arrow softkey
button.
3. Select the »Control« menu by using the »up« or »down« softkeys and press the »right« arrow softkey
button.
4. A symbol for the switchgear and its status (ON, OFF, intermediate or disturbed) is displayed.
5. Dependent on the status (ON/OFF), the switchgear can be switched ON or OFF by the corresponding
softkey.
260 www.eaton.com
EMR-4000 IM02602009E
1
(Off)
2
(ON)
3
(Disturbed)
Name Description
Local Switching Authority: Local
Remote Switching Authority: Remote
NonInterl Non-Interlocking is active
CES SAuthority Command Execution Supervision: Switching Command not
executed. No switching authority.
CES DoubleOperating Command Execution Supervision: A second switch command is in
conflict with a pending one.
No. of rej. com. No. of rej. com.
because Locked by ParaSystem because Locked by ParaSystem
www.eaton.com 261
IM02602009E EMR-4000
• Calculation of the Breaker Open Capacity »Bkr OPEN capacity«. 100% means that breaker
maintenance is mandatory now.
• Breaker Wear Curve
• Monitoring of total CLOSE/OPEN cycles and alarm for max allowed CLOSE/OPEN cycles per hour.
The User has to maintain the breaker accordingly to the maintenance schedule that is to be provided by the
manufacturer (breaker operation statistics). By means of up to ten points that the User can replicate the breaker
wear curve within menu [Control/Breaker/BWear]. Each point has two settings: the interrupt current in kilo
amperes and the allowed operation counts. The first point is always the number of allowed operations if no
current is flowing (zero current). No matter how many points are used, the operation counts the last point as
zero. The protective relay will interpolate the allowed operations based on the breaker wear curve. When the
interrupted current is greater than the interrupt current at the last point, the protective relay will assume zero
operation counts.
4
1× 10
0.0 1.2
10000 10000
3
1× 10
Number of Operations
8.0
150
100
20.0
10 12
20.0
1 0
0.1 1 10 100
262 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 263
IM02602009E EMR-4000
Name Description
Operations Alarm Signal: Service Alarm, too many Operations
Isum Intr trip: IA Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IA
Isum Intr trip: IB Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IB
Isum Intr trip: IC Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IC
264 www.eaton.com
EMR-4000 IM02602009E
Name Description
Isum Intr trip Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded in at least one phase.
Res TripCmdCr Signal: Resetting of the Counter: total number of trip commands
Res Isum trip Signal: Reset summation of the tripping currents
WearLevel Alarm Signal: Breaker Wear curve Alarm Level in %
WearLevel Lockout Signal: Breaker Wear Curve Lockout Level in %
Res Bwear Curve Signal: Res Bwear Curve
Isum Intr ph Alm Signal: Isum Intr ph Alm
Res Isum Intr ph Alm Signal: Res Isum Intr ph Alm
www.eaton.com 265
IM02602009E EMR-4000
Name Description
-.- No assignment
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
266 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 267
IM02602009E EMR-4000
Name Description
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
268 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
www.eaton.com 269
IM02602009E EMR-4000
Name Description
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
270 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 271
IM02602009E EMR-4000
Name Description
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
272 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
www.eaton.com 273
IM02602009E EMR-4000
Name Description
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
274 www.eaton.com
EMR-4000 IM02602009E
Protective Elements
IOC Function
Elements:
IOC Function
Functional Description
The instantaneous overcurrent function (IOC) or 50P[x] is intended to protect in the event of a high-current fault.
The example IOC setting used in the Motor Protection Curve (see the Motor Protection Curve Examples in the
Ultimate Trip Current Section) is 12 times (1,200%) of FLA. In general, the instantaneous IOC should be at least
1.5 times LRC, well above the locked rotor current normally seen at the moment of a start.
IOC should trip fast and therefore no run or pickup delay is provided. A start delay is set at a minimum of two
cycles (0.03 sec.), or more if needed to block IOC tripping on magnetizing inrush when the motor is first
energized. An additional IOC time delay setting is set at a default of zero seconds.
The IOC sets the instantaneous overcurrent trip limit in percentage of the FLA above at which the relay trips.
This trip type can be set to Inactive to deactivate this protective device element. For currents clearly above the
setting, the IOC function picks up in two power cycles or less. The IOC setting must be below (1,130 * PCT/
FLA) or 1,600%, whichever is less.
This setting sets the number of power cycles after a start is recognized until the IOC trip and alarm functions are
enabled. Use this delay to inhibit IOC tripping on a current peak caused by magnetic inrush when the motor is
first energized (usually two to three cycles).
Load Shedding
Available elements:
MLS
Functional Description
In some applications, the the protective device can forestall a JAM alarm or trip, or a thermal trip, by sending a
signal to the process to reduce loading. The load-shedding function, if enabled, closes or opens a relay contact
to shed process load when the motor load current goes above the Load-shed Drop threshold, for a time
exceeding the Drop Delay t. This could, for example, be connected to stop flow of material into the driven
process until the load current drops below the load-shed dropout threshold, for the time determined by the Drop
Delay t.
Set the load-shed pickup current comfortably below the JAM trip level. It may be useful to set it below the
Ultimate Trip Current, particularly if RTDs are not used.
The load shed function provides a contact output signal that the User connects to the process equipment, to
reduce loading on the motor if it becomes too large. For example, the contact might be used to temporarily stop
the flow of heavy materials onto a conveyor driven by the protected motor. In this way, the protective device tries
to alleviate an overload before it reaches an outright thermal protective trip. When the load is reduced, the
contact returns to the normal state and the process can resume loading of the motor.
The load shed function, which is active only during the RUN state of the motor, is configured with settings “MLS -
Mechanical Load Shedding”, under each of the the Setting groups (Set 1 for example).
www.eaton.com 275
IM02602009E EMR-4000
276 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Pickup Signal: Pickup
Trip Signal: Trip
JAM
Elements
50J[1] ,50J[2]
Functional Description
When the motor is running, a current increase above normal load may be an indication of a malfunction in the
load. JAM protection recognizes mechanical problems, such as broken drive gears.
Refer to the JAM protection limit (the right vertical line in the “Underload and JAM Trip Function” curve example).
In this curve example, the JAM trip is set at 150% of FLA.
www.eaton.com 277
IM02602009E EMR-4000
The protective device can be configured for a JAM alarm and/or a JAM trip. There are two JAM elements:
They are located under the >>Protection Parma<< menu, under each setting group (Set 1 for example). It is
suggested to use 50J[1] for JAM trip, and 50J[2] for JAM alarm. Each can be disabled by entering the JAM
setting menu and then selecting “Inactive”. It can also be blocked by various blocking elements set by the User
under the >>Global Prot Par / JAM<< menu. In the “Underload and JAM Trip Function” curve, the Trip settings
are represented by two vertical lines, both well above the normal load current. This curve also applies to JAM
setting configured as an alarm. Be sure to set the alarm level below the trip level.
Both trips and alarms are held off by the JAM Start Delay located under the >>Global Prot Para / Motor-start
Start Delay Timers<<. Use the start delay to block tripping and alarming until the motor current drops to
continuous load level. Use run delays to avoid nuisance alarms or trips for load transients.
To configure this function for operation under an alarm condition, the User must assign the functions pickup
[(50J[1].Pickup) for example] to an relay output contact, under >>Device Parm / Relay Outs<< that the User has
identified as the Alarm relay output contact. Likewise, to illuminate an LED under a functions alarm condition,
LED2 must be assigned the functions pickup. Several elements are configure as such at the factory for
convenience.
278 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 279
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup
Trip Signal: Trip
TripCmd Signal: Trip Command
280 www.eaton.com
EMR-4000 IM02602009E
Set the JAM Start delay timer to one second. Set the JAM function to “Active” and Threshold to “2 X FLA”. Set
the JAM “Delay T” to one second. Apply current of “2 X FLA” setting for one second. The relay should not trip.
Apply the same current for 3 seconds. The unit should trip in 2 to 3 seconds.
The Locked-rotor protection function is a integral part of the thermal model and is used to protect the motor in
the event that the motor fails to start or accelerate after being energized. The heating in the motor during this
period of time can be significantly higher than the heating at rated current, ranging from 10 to 50 times the
normal rated heating. The time that a motor can remain at a standstill after being energized varies with the
applied voltage and has an I2T limit.
When determining the heat in the motor during this period of time, both the negative and positive sequence
currents are used in the equation that approximates the heat generated in a locked rotor condition. The heat
can be approximated by the equation:
I2 H = I12 + K I2 2
where :
Settings for the LRC (Locked Rotor Current) can be found under the System Parameters. The LRC value is a
multiplier of the Full Load amps (FLA) setting and ranges from 300 to 1200 % of FLA.
The value of K = 6.01 should be used to mimic the thermal model of Eaton's MP3000 and MP4000 motor relays.
www.eaton.com 281
IM02602009E EMR-4000
1. Start cycle;
2. Run cycle;
3. Stop cycle; and
4. Trip state.
Under normal conditions, the motor operations should go through stop, start, run, and stop cycles that are
referred to as a complete operation sequence; while under certain abnormal conditions, the motor could go from
start to stop, or start to trip, or run to trip. If other protection trips occur at either the start or run cycle, the motor
will be forced to go to trip mode. After motor currents are terminated, the motor will go into the stop cycle. A
motor start is blocked by the hidden state “Block” as shown in the motor start diagram, if any of the following
conditions are noted - motor starts limit, starting frequency, thermal and mechanical constraints. The User may
choose to use the blocked state to block the motor from starting or use it as an alarm or indication.
The Start Control Module drawing shows an example of how the protective device reacts to a normal operating-
cycle current profile. Initially, the motor is stopped and the current is zero. As long as the protective device is
not in a trip state, it permits contactor energization by closing its trip contact in series with the contactor. The
contactor is energized by the operator or process control system through a normal two-wire or three-wire motor
control scheme, external to the protective device. The protective device declares a motor start when it senses a
motor current that exceeds 30% of the FLA setting. Meanwhile, the transition timer (TRNT) begins to run. The
282 www.eaton.com
EMR-4000 IM02602009E
protective device also monitors the large starting current, noting when the current falls below the transition level
TRNC.
Start to Run transition is based on the setting TRN Criteria, which has four transition behaviors for the User to
select:
•TRN T - Transition to RUN after time setting TRNT only. Current is ignored.
•TRN I - Transition when starting current drops below the setting only. If the time set in TRNT
expires before the current transition, the motor trips.
•TRN T or I - Transition on time or current, whichever comes first.
•TRN T and I - Transition on time and current. Both must occur, and the current must drop below the
setting before the time delay expires. If the timer expires before the current falls below the
set transition level, the motor trips.
If there is no transition trip, the protective device relay declares a successful transition to RUN cycle and the
corresponding transition flag(s) (current or time, or both, depending on the settings and motor current) is set.
The transition flag(s) is the part of the global output list, which can be assigned to any module input or relay
output contact. If it is assigned to a relay output contact, it can control a reduced-voltage starter, switching to full
running voltage.
Even if the transition control output contact is not used, the transition function can provide clear indications of the
actual state of the motor (START versus RUN) on the front panel display and via data communications. A good
way to do this is to use the settings of TRN Criteria = TRN T or I and TRNC = 130% of FLA. Modify the latter, if
needed, to lie at a transition value between the starting current and post-start maximum load current. Set the
transition timer well beyond the normal start time to avoid a transition trip.
Start Delays
When the protective device declares a START, all start timers of the enabled functions begin to time. Each of
these timers blocks the respective function until the set delay expires. These start timers are affected by
transitions - they run for the set time, which may be less than or greater than the time of transition. These start
delay timers include:
Note that the generic start delays are not tied to anything, and they can be used to block anything at the User’s
choice.
Eaton E-Series Motor Relays that have the ability to measure Voltage also have the following additional start
delay timers:
** - If the time delay for these timers is set to zero, these timers will not wait for the protective device to
declare a START. The protective function will be active immediately.
www.eaton.com 283
IM02602009E EMR-4000
Start Limits
Because motor starting consumes a considerable amount of thermal energy compared to its normal load
conditions, the number of starts in a given time period must be monitored and controlled. The protective device
has three functions that contribute to the start limits monitoring. These are:
Most motors can tolerate some number of consecutive cold starts before the time between starts is enforced.
The protective device treats a start as the first in a sequence of cold starts if the motor has been stopped for at
least the time period that is the greatest of one hour and TBS. Subsequent starts are treated as additional cold
starts in the same sequence, only if they run no more than ten minutes, until the set number of cold starts is
reached. Once the motor is in the cold starting sequence, it will ignore TBS and SPH limits. The cold start
sequence will be terminated if the motor has run for more than ten minutes for a cold start before it exhausts
NOCS, then starts after this are subject to time and count limits imposed by TBS and SPH. If the motor reaches
the NOCS limit in a cold start sequence, NOCS block flag will be set and TBS will start to time. When TBS
reaches its limit while the NOCS block flag is still set, the cold start sequence will be terminated and the NOCS
block will be released. Meanwhile, the SPH will start to count at the last start in the complete cold start
sequence.
Stop Cycle
The run cycle continues until the motor current level falls below the Stop Current Threshold setting current on all
three phases. Then a stop is declared. The start limits (also referred as Jogging start limits) and the anti-
backspin time delay (ABS) are checked. If blocking conditions exist, the protective device can be configured to
block a motor from starting. Remaining jogging block times are displayed and counted down, indicating how
long to wait. If there are no such starting block conditions in effect, the protective device is ready for a new start.
ABS sets the time in seconds before a motor restart is permitted after a trip or stop condition. This function can
be set to OFF.
This function is used with a motor driving a pump working into a head, or any other load that tends to spin in a
reverse direction (backspin) when the motor is de-energized. It blocks starting during the time when the motor
might be rotating in reverse following a trip. Also, this function may be used simply to set idle time (time between
stop and start) before a restart is permitted.
A motor can be blocked through a digital input. If this feature is enabled, the User must make sure that both the
Motor Start and Digital Input modules are configured properly.
Thermal Block
Besides the previously mentioned start monitoring and controlling means, the motor can be blocked if the
thermal capacity used exceeds the alarm level. It is the User’s choice to turn on or off this feature and set an
appropriate alarm level in the thermal model module.
Blocked Condition
Note that the protective device has two types of blocking outputs: individual block and a general block. The
individual blocking functions are as follows:
284 www.eaton.com
EMR-4000 IM02602009E
When any of Anti-Backspin, thermal, and external blocks are on, the general blocked flag will be set. The TBS
and SPH can turn on the general blocked flag only if the motor is not in a cold start sequence; NOCS block can
not cause the general blocked flag to be set.
Forced Starting
It is recommended that the User wires the general blocked output to the motor trip circuit for preventing the
motor from starting under these blocked conditions. If the User chooses not to do this for their applications, a
Forced Starting flag will be set when the motor is started with the blocked conditions. This flag can only be reset
manually though PowerPort-E or from the front panel.
If any of the motor protective functions operate while the motor starts or runs, the protective device can open its
trip contact if so configured. It may also open its trip contact after a stop is recognized if any jogging function
time limit is blocking the next start. In either case, the protective device expects that the contactor has opened in
response and that no current flows.
If the protective device senses noticeable current for more than about a second whenever it is tripped, it sets a
Trip Bypass flag. This means that the relay blocking of the contactor has been circumvented by the User to start
the motor. If the current fails to stop when the protective device trips a running motor, it may be because of a
User trip bypass or because of a stuck contactor.
Consider the possibility of backup protection for a contactor opening failure. Configure one of the relay output
contacts to pick up for a trip bypass. Connect the contact to trip an upstream breaker. This protects the motor
from damage in case of a stuck contactor (at the cost of interrupting other loads connected to the same
breaker).
ZSS enables the function that verifies if the motor begins to physically spin after a start. It requires a zero-speed
switch on the motor, which is closed at rest and opens as the rotor reaches (5%-10%) its normal speed.
Connect the zero-speed switch contact to one of the protective device Discrete Inputs. If the contact fails to
open within LRT/2 (one-half of locked-rotor time) after a start, the relay trips with a zero-speed switch trip
message.
This protection is always useful, but is essential if the Long Acceleration Time (LAT) function setting is used.
With ZSS being enabled and being mapped to one of the digital inputs, the protective device checks the ZSS
input status at the very moment it sees a start - it wants to sense the initially closed zero-speed switch, which
opens shortly thereafter as the motor spins. If it fails to find the closed contact, it trips immediately. Check the
wiring and contact for problems.
When the LAT function is enabled, the LAT timer is used to set a time interval during which the motor is
permitted to accelerate a high-inertia load, which is longer than the locked-rotor time. This function can be (and
usually should be) set to OFF. If the thermal-model accumulator bucket fills to 100% during the long
acceleration time, it is limited to that value and the thermal trip is held off until the LAT timer expires. By then,
the thermal bucket level must have decreased (thermal model cooled) below 100% or the motor trips.
The LAT function should be used but not limited only on motors with a zero-speed switch (a normally-closed
contact that opens when the motor actually begins to spin). Connect the zero-speed switch contact to one of the
protective device Discrete Inputs. The Zero-Speed Switch function must be enabled (ZSS ON). The protective
device requires the zero-speed switch to open within LRT/2 (one-half of locked-rotor time) after a start, or the
motor is tripped by the ZSS function. This protects a completely stalled motor from being damaged when the
LAT timer blocks the locked-rotor thermal trip.
www.eaton.com 285
IM02602009E EMR-4000
The long acceleration time (LAT) function can block the critical LRC-LRT
rotor thermal protection during a start and destroy the motor. Turn LAT
OFF unless absolutely needed and the motor's suitability for this starting
duty has been confirmed. Use only with zero speed switch function ZSS
ON and switch input connected to protect a stalled motor.
The User can temporarily defeat the I2t thermal protection limit after a start by setting a Long Acceleration Time
delay. This can be a dangerous setting that blocks thermal tripping and holds the bucket at a 100% level if the
load takes a long time to reach running speed. An example is a motor spinning a large centrifuge. In using LAT,
the User can take advantage of the partial cooling from airflow produced by the motor spinning at below-normal
speed, as compared to unfanned heating of a locked rotor. The motor must be rated for this severe starting
duty. Also, the User must ensure that the motor actually has begun to spin well before the locked-rotor time has
expired. This is accomplished by connecting a zero-speed switch to a Discrete Input and turning on ZSS
function. The zero-speed switch is a contact that is closed when the motor is at rest, and opens as the motor
begins to spin, usually at 5-10% of running speed. If ZSS is set to ON and the protective device relay does not
sense the contact open in one-half the locked-rotor time setting, it trips the motor.
Turn OFF LAT unless the application specifically demands it. Use a zero
speed switch with LAT. Using an LAT setting greater than locked rotor time
without a zero speed switch temporarily defeats thermal protection and
damages the motor if the rotor actually is locked.
If LAT is used, check the settings of transition time TRNT and jam start delay to be sure they are coordinated
with the prolonged starting cycle.
The incomplete sequence function requires a report back contact from the process that the motor runs - any
indication that the process has started to operate as expected some time after the motor start. If the process
does not start up correctly, the contact does not close within the expected time. If a problem develops later on,
the report back contact opens. In either case, the open contact state indicates that the motor should be tripped.
To use this function, set a time limit for report back here and define the start of report back timing. Connect the
report-back contact to one of the protective device Discrete Inputs. If this input is not energized before the set
time expires, the relay will trip for incomplete sequence.
Note that the input must be energized continuously after the time delay has expired to hold off this trip.
Emergency Override
If enabled, an emergency override can be executed by pushing the Emrg Override button behind the front panel
security door. In any case, an emergency override can be performed by a remote contact connected to any one
of the discrete inputs programmed as EMG OVR, or via front panel under Operations\Reset menu. The as-
shipped setting is disabled.
Emergency override allows a panic restart of a tripped motor without completely disabling protection. When the
override request is received, the thermal-model accumulator bucket is drained to its initial level of 40°C (104°F).
Jogging limit counters and timing, including anti-backspin timing, are reset. Cold starts are fully restored.
The motor protection is now in the state it would be in if the motor had been standing for a long time prior to the
moment of the override. This allows an immediate restart of the motor. The override can also delay an
impending thermal trip of a running motor. The emergency override action is counted in the history record, and
noted with its time tag in the logbook record.
286 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 287
IM02602009E EMR-4000
288 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 289
IM02602009E EMR-4000
290 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 291
IM02602009E EMR-4000
292 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
Blo TripCmd Signal: Trip Command blocked
Trip Signal: Trip
TripCmd Signal: Trip Command
Start Signal: Motor is in start mode
Run Signal: Motor is in run mode
Stop Signal: Motor is in stop mode
Blo Signal: Motor is blocked for starting or transition to Run mode
NOCSBlocked Signal: Motor is prohibited to start due to number of cold start
limits
SPHBlocked Signal: Motor is prohibited to start due to starts per hour limits
SPHBlockAlarm Signal: Motor is prohibited to start due to starts per hour limits,
would come active in the next stop
TBSBlocked Signal: Motor is prohibited to start due to time between starts limits
ThermalBlock Signal: Thermal block
RemBlockStart Signal: Motor is prohibited to start due to external blocking through
digital input DI
TransitionTrip Signal: Start transition fail trip
ZSSTrip Signal: Zero speed trip (possible locked rotor)
INSQSP2STFaill Signal: Fail to transit from stop to start based on reported back
time
INSQSt2RunFail Signal: Fail to transit from start to run based on reported back time
LATBlock Signal: Long acceleration timer enforced
ColdStartSeq Signal: Motor cold start sequence flag
ForcedStart Signal: Motor being forced to start
TripPhaseReverse Signal: Relay tripped because of phase reverse detection
EmergOverrideDI Signal: Emergency override start blocking through digital input DI
EmergOverrideUI Signal: Emergency override start blocking through front panel
ABKActive Signal: Anti-backspin is active. For certain applications, such as
pumping a fluid up a pipe, the motor may be driven backward for a
period of time after it stops. The anti-backspin timer prevents
starting the motor while it is spinning in the reverse direction.
GOCStartBlock Signal: Ground Instantaneous Overcurrent Start Delay. GOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter
IOCStartBlock Signal: Phase Instantaneous Overcurrent Start Delay. IOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter
ULoadStartBlock Signal: Underload Start Delay. Underload(Instantaneous
Overcurrent) elements are blocked for the time programmed under
this parameter
www.eaton.com 293
IM02602009E EMR-4000
Name Description
JamStartBlock Signal: JAM Start Delay. JAM(Instantaneous Overcurrent)
elements are blocked for the time programmed under this
parameter
UnbalStartBlock Signal: Motor start block current unbalance signal
Blo-Generic1 Generic Start Delay. This value can be used to block any
protective element.1
Blo-Generic2 Generic Start Delay. This value can be used to block any
protective element.2
Blo-Generic3 Generic Start Delay. This value can be used to block any
protective element.3
Blo-Generic4 Generic Start Delay. This value can be used to block any
protective element.4
Blo-Generic5 Generic Start Delay. This value can be used to block any
protective element.5
I_Transit Signal: Current transition signal
T_Transit Signal: Time transition signal
StartMotorCmd Signal: Start motor command
MotorStopBlo Signal: Motor stop block other protection functions
RFD_IA_Normal Signal: System IA RotaryFieldDetection Normal
RFD_IA_Reverse Signal: System IA RotaryFieldDetection Reverse
VUnbalStartBlock Signal: Motor start block voltage unbalance signal.
UnderVStartBlock Signal: Undervoltage Start Delay. Undervoltage elements are
blocked for the time programmed under this parameter
OverVStartBlock Signal: Overvoltage Start Delay. Overvoltage elements are
blocked for the time programmed under this parameter
PowerStartBlock Signal: Power Start Delay. Power elements are blocked for the
time programmed under this parameter
PFacStartBlock Signal: Power Factor Start Delay. Power Factor elements are
blocked for the time programmed under this parameter
FrqStartBlock Signal: Frequency Start Delay. Frequency elements are blocked
for the time programmed under this parameter
294 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 295
IM02602009E EMR-4000
296 www.eaton.com
EMR-4000 IM02602009E
Motor Wellness
Available elements:
Motor Diagnosis
Where: fsb = frequency components of the current due to broken rotor bars, also known as sidebands; f1 =
power supply frequency (Hz); s = operating slip (per unit).
In the predictor equations, the ratios between the slip and the fundamental are the main input parameters. Other
parameters are:
• Motor’s horse power;
• Number of the rotor bars;
www.eaton.com 297
IM02602009E EMR-4000
Two algorithms are available and selectable in the EMR4000. The first uses a standard FFT, while the second
implements an enhanced FFT, which provides better accuracy by introducing additional signal processing. Both
require stable current signal conditions and near full load current, which are continuously monitored by the
algorithm. The algorithm will only process data when these stable conditions are met.
The stator current is a non-stationary signal whose properties vary with respect to the time variant normal
operation conditions of the motors such as load torque and power operation supply. On the other hand, a rotor
bar failure develops very slowly, therefor it is not necessary to monitor continuously due to the signal unstable
conditions.
There are two states which indicate the stage of Broken Bar Detection (BBD). An “alarm” state indicates a
broken rotor bar, while an additional state is indicated if the signal is not good enough to performing a reliable
analysis.
Additional values give more detailed information about the signal condition:
“GREEN” (No fault), “YELLOW” (Unclear), or “RED” (broken rotor bar detected) statuses are displayed in real
time.
Under a Yellow signal condition, any one of the following signal conditions may be display for clarity:
• “INVALID_FREQUENCY”; The frequency with +-0.1 of the nominated frequency is required.
• “INVALID_DATA”: Such as two consecutive zeros.
• “UNSTABLED_SIGNAL”; - The stability of the signal is required.
• “UNSTABLED_FREQUENCY”; - The stability of the frequency is required.
• “INSUFFICIENT_LOAD” - At least 85% of the full load is required.
The time between the BBD is selectable. The default is 3600 sec.
298 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 299
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
BBDAlarm Signal: BBDAlarm
BBDReliable Signal: Indicates if signal is valid for a broken bar detection.
Thermal Model
Available Elements:
49
This protective device provides a thermal model that is similar to Eaton’s MP-3000 motor relay to approximate
the thermal capacity used. The thermal model can work with or without the URTD. The RTD-based direct
temperature trips and alarms are independent of the thermal model. Without the URTD, meaning the URTD is
not connected to the protective device or it is connected but not configured for the thermal protection trips, the
thermal model protection will be solely based on the following settings:
The first four settings (1-4) dictate the maximum allowable thermal limit curve of the protected equipment, and
the last four settings (6-9) define the thermal trip and alarm curves relative to the thermal limit curve. Setting 5 is
used for cooling or damping.
300 www.eaton.com
EMR-4000 IM02602009E
I 2LR∗T LR
TripTime= when I ef SF∗FLA
I 2ef
If the direct stator temperature measurements are available, the thermal replica model will be modified to include
the heat loss between stator and rotor. As a result, the motor will be able to run longer under overload
conditions. The heat loss serves as a cooling. At some point, the cooling effect will cancel the heat increment
so that the thermal capacity used will reach some steady-state level that may be below the trip or alarm limit.
This equivalently raises the service factor and shifts the trip curve right.
If the thermal capacity used is held at a level that is below the trip threshold, the thermal model will not trip. To
prevent the protected equipment from overheating, the direct temperature trip function must be enabled. Keep
in mind that in order for the stator temperature to be effective in the thermal replica model, the following
conditions must be met:
• Some RTD channels must be configured to measure the winding temperatures; and
• These RTD channels must be enabled for trip.
Knowing the maximum steady stator temperature qS (°C), the thermal capacity used can be estimated by the
following formula.
0S I 2ef ∗50
TC Used %= when I ef ITH ∗FLA
240 I 2LR∗T LR
Take for example, ILR = 6FLA, TLR = 15, and thermal trip level of 100%. The relationship between the effective
current threshold and the stator temperature can be seen in the Stator Temperature Effect on Current Threshold
Curve.
www.eaton.com 301
IM02602009E EMR-4000
From the graph, it is seen that the lower the stator temperature, the higher the effective current threshold.
Without stator temperature, given the current threshold of 1.0 FLA and 2.0 FLA of the stator phase current, the
thermal model will use the full thermal capacity in 139.54 seconds. However, if the stator temperature is known
as 100°C (212°F), the effective ultimate trip current threshold is raised to 2.55 FLA and the thermal capacity
used will reach a steady state of 77.5%. As a result, the thermal model will never trip under this condition. From
this example, it can be seen that the stator RTD could keep the motor running under overload condition. In this
case, the appropriate direct stator temperature trip function must be enabled.
302 www.eaton.com
EMR-4000 IM02602009E
In the Thermal Replica Model Trip Curves with and without RTD, the unmarked lines are the thermal limit curves
and the marked lines are the trip curves. From the curve without RTD, it can be seen that one can change the
thermal current threshold to shift the upper portion of the trip curve right to allow the motor to run at a higher
overload condition than is specified with the service factor. From the curve with RTD, it can be seen that the
stator RTD pushes the effective thermal current threshold to 2.55 FLA on the thermal limit curve (unmarked
line). The marked line is the trip curve with 80% thermal capacity trip threshold, so actual effective thermal
current threshold for the trip curve is about 2.05 FLA. Although in this case, the thermal current threshold is set
to 1.50 FLA, it is effectively raised to a higher level with the stator RTD. Keep in mind that thermal limit and trip
curves shown are based on the example above. They will vary with other sets of the settings.
www.eaton.com 303
IM02602009E EMR-4000
304 www.eaton.com
EMR-4000 IM02602009E
Name Description
Alarm Pickup Signal: Alarm Pickup
Alarm Timeout Signal: Alarm Timeout
RTD effective RTD effective
Load above SF Load above Service Factor
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup
Trip Signal: Trip
TripCmd Signal: Trip Command
www.eaton.com 305
IM02602009E EMR-4000
Functional Description
The Ultimate Trip Current (UTC) sets the current level at which a trip eventually occurs and is settable to a value
as a percentage of Full Load Amps (FLA). This value represents the vertical line on the upper portion of the
non-RTD as shown in the protection trip curve labeled Motor Protection Curve Example 2 ( with out RTD). The
ultimate trip current setting in this example is at 1 times the FLA.
Note that in systems where an RTD is used the UTC pickup point is biased by the measured temperature. This
is shown in the example trip curve labeled Motor Protection Curve Example 3 ( with RTD) were you will see a
shift in the UTC value to 2 times the FLA
For normal use, set UTC to the service factor times 100%. The available range is 85% to 150%. The service
factor is found on the motor nameplate or in the manufacturer’s data. Note that the relay does not trip at the
moment the current goes above UTC during motor running. Instead, it models the gradual stator heating for
currents above UTC,and trips only after some time has passed. The trip time depends on a variety of setting
and operating factors, including the motor nameplate data contained in other setting values.
Use a conservative value. In this case, a lower value of UTC than that dictated by the service factor if the motor
ambient temperatures may rise above 40ºC (104ºF) and the optional URTD Module is not used. Also, consider
lowering the UTC value if the motor is suitably rated, yet additional safety is critical for the application.
If UTC is set above 100% times the service factor, motor damage could
result.
If stator RTDs are not used and there is the possibility that the ambient may rise above 40°C (104°F), the
ultimate trip current should be set below the value indicated by the nameplate service factor to avoid stator
insulation damage or loss of motor life.
If stator temperature measurements are available, the algorithm may keep from tripping, even if the effective
current is above the ultimate trip current setting, depending on stator temperature reports. It is still important to
set a correct ultimate trip current so that the motor is well protected. If the RTDs, the module, or its
communications to the relay fail, the algorithm falls back to use of UTC. Also, note that if all RTD channels are
set to OFF, the algorithm reverts to the non- RTD calculation, which is based strictly on UTC.
306 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 307
IM02602009E EMR-4000
308 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 309
IM02602009E EMR-4000
Underload Module
Elements
37[1] ,37[2] ,37[3]
Functional Description
When the motor is running, a current reduction might indicate a malfunction in the load. Underload protection
recognizes mechanical problems, such as a blocked flow or loss of back pressure in a pump, or a broken drive
belt or drive shaft.
Refer to the underload protection limit - the left vertical line in the Underload and Jam Trip Function example. In
the example, the underload trip is set at 60% of FLA. The protective device can be configured for underload
alarm and underload trip. Each can be disabled by entering the >>Underload Setting<< menu and then selecting
“Inactive”.
These would be represented by two such vertical lines, both below the normal load current. Be sure to set the
alarm level above the trip level. Both trips and alarms are held off by the start delay. Each has its own run or
pickup delay. Use the start delay to block tripping until the load stabilizes after a start. Use run delays to avoid
nuisance alarms or trips for load transients.
To configure this function for operation under an alarm condition, the User must assign the functions pickup ( for
example 50J[1].Pickup) to an relay output contact, under >>Device Parm / Relay Outs<< that the User has
310 www.eaton.com
EMR-4000 IM02602009E
identified as the Alarm relay output. Likewise, to illuminate an LED under a functions alarm condition, LED 2
must be assigned the functions pickup. Several elements are configure as such at the factory for convenience.
www.eaton.com 311
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
312 www.eaton.com
EMR-4000 IM02602009E
Name Description
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup
Trip Signal: Trip
TripCmd Signal: Trip Command
If using inrush blockings, the tripping delay of the current protection functions
must be at least 30 ms or more in order to prevent faulty trippings (applies only
to devices which are equipped with Inrush protection).
Explanation
t = Tripping delay
I = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
This element offers a criterion setting. The criterion setting tells if the threshold is based on the fundamental
(Phasor) or RMS.
For Tripping curves, please refer to the “Appendix/Instantaneous Current Curves (Phase)” section.
www.eaton.com 313
314
IM02602009E
50P[1]...[n]
16a
AND
Please Refer to Diagram: IH2*
5 IH2.Blo Phase A Name.Trip Phase B
AND 17a
AND
Please Refer to Diagram: IH2*
6 IH2.Blo Phase B Name.Trip Phase C
Name.Pickup
AND 18a
Name.t
EMR-4000
AND
Please Refer to Diagram: IH2* AND
7 IH2.Blo Phase C
φ
DEFT
www.eaton.com
Name.Criterion
OR t
AND OR
Name.Trip
0
Fund.
Name.Pickup
www.eaton.com 315
IM02602009E EMR-4000
316 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 317
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup IA Signal: Pickup IA
Pickup IB Signal: Pickup IB
Pickup IC Signal: Pickup IC
Pickup Signal: Pickup
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
• Signals to be measured for each current protection element: the threshold values, total tripping time
(recommended), or alternatively tripping delays and the drop-out ratios; each time 3 x single-phase and
1 x three-phase.
318 www.eaton.com
EMR-4000 IM02602009E
Eaton recommends measuring the total tripping time instead of the tripping
delay. The tripping delay should be specified by the User. The total
tripping time is measured at the position signaling contact of the breaker
(not at the relay output contacts!).
Total tripping time = tripping delay (please refer to the tolerances of the
protection elements)
+ breaker operating time (about 50 ms)
Please take the breaker operating times from the technical data specified in
the relevant documentation provided by the breaker manufacturer.
Necessary means:
• Current source;
• Current meters; and
• Timer.
Procedures:
If using inrush blockings, the tripping delay of the current protection functions
must be at least 30 ms or more in order to prevent faulty trippings (applies only
to devices which are equipped with Inrush protection).
www.eaton.com 319
IM02602009E EMR-4000
• NINV (IEC/XInv);
• VINV (IEC/XInv);
• LINV (IEC/XInv);
• EINV (IEC/XInv);
• MINV (ANSI/XInv);
• VINV (ANSI/XInv);
• EINV (ANSI/XInv);
• Thermal Flat;
• Therm Flat IT;
• Therm Flat I2T; and
• Therm Flat I4T.
For tripping curves please refer to the “Appendix/Time Current Curves (PHASE)” section.
320 www.eaton.com
51P[1]...[n]
16b
AND
Please Refer to Diagram: IH2*
5 IH2.Blo Phase A Name.Trip Phase B
AND 17b
AND
Please Refer to Diagram: IH2*
6 Name.Curve Shape
IH2.Blo Phase B Name.Trip Phase C
AND Name.t-reset
Please Refer to Diagram: IH2* AND
7 IH2.Blo Phase C
Name.Reset Mode
φ
INV
www.eaton.com
Name.Criterion
OR
AND OR
Name.Trip
Fund.
IB φ
AND
Name.TripCmd
IC
Imax Imax
321
IM02602009E EMR-4000
322 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 323
IM02602009E EMR-4000
t-reset Reset time for intermittent phase failures 0.00 - 60.00s 0s [Protection Para
(INV characteristics only) /<n>
/I-Prot
Available if:Reset Mode = t-delay /51P[1]]
324 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup IA Signal: Pickup IA
Pickup IB Signal: Pickup IB
Pickup IC Signal: Pickup IC
Pickup Signal: Pickup
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
• Signals to be measured for each current protection element: the threshold values, total tripping time
(recommended), or alternatively tripping delays and the drop-out ratios; each time 3 x single-phase and
1 x three-phase.
www.eaton.com 325
IM02602009E EMR-4000
Eaton recommends measuring the total tripping time instead of the tripping
delay. The tripping delay should be specified by the User. The total
tripping time is measured at the position signaling contact of the breaker
(not at the relay output contacts!).
Total tripping time = tripping delay (please refer to the tolerances of the
protection stages)
+ breaker operating time (about 50 ms)
Please take the breaker operating times from the technical data specified in
the relevant documentation provided by the breaker manufacturer.
Necessary means:
• Current source;
• Current meters; and
• Timer.
Procedure:
The 51V element restrains operation which reduces pickup levels. This allows the User to lower the pickup
value of the 51V elements with the corresponding phase input voltage (phase-to-phase or phase-to-ground,
depending on the setting of »Main VT con« within the System Parameters). When the minimum fault phase
current is close to the load current, it may make the phase time overcurrent protection coordination difficult. In
this case, an undervoltage function may be used to alleviate this situation. When the voltage (RMS) is low, the
phase time overcurrent pickup threshold may be set low accordingly, so that the phase time overcurrent
protection may achieve adequate sensitivity and better coordination. The device uses a simple linear model to
326 www.eaton.com
EMR-4000 IM02602009E
determine the effective pickup by characterizing the relationship between the voltage and the phase time
overcurrent pickup threshold.
Once the voltage restraint is activated, the effective phase time overcurrent pickup threshold will be the
calculated Pickup% times the phase time overcurrent pickup setting. The effective pickup threshold must be
within the setting range allowed and, if it is less, the minimum pickup value will be used.
Pickup%
100%
25%
That means:
• Vmin = 0.25*Vmax;
• Pickup%min = 25%;
• Pickup% = 25%, if V <= Vmin;
• Pickup% = 1/Vmax*(V - Vmin) + 25%, if Vmin < V < Vmax;
• Pickup% = 100%, if V >= Vmax.
For tripping curves, please refer to the“Appendix/Instantaneous Current Curves (Phase)” section.
If this element should be blocked in case of a Loss Of Potential, »LOP BLO« has to be set to »active«.
In case that within the System Parameters "Main VT con" is set to "Open-Delta":
Vn=Main VT sec .
MainVT sec
Vn=
3
www.eaton.com 327
IM02602009E EMR-4000
51V[1]...[n]
AND 17b
AND
AND Name.t-reset
AND
7 Please Refer to Diagram: IH2*
IH2.Blo Phase C
Name.Reset Mode
φ
INV
OR
AND OR
Name.Trip
51V Pickup =
%Pickup * 51P
Pickup
IA
RMS
IB
AND
RMS Name.TripCmd
IC
RMS
Based on above parameters ,
tripping times and reset modes will
AND 15
be calculated by the device .
Imax Imax
φ
Pickup%
VA
100%
RMS
VB
RMS
%Pickup
VC
25%
RMS V
25%
VRestraint max
328 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 329
IM02602009E EMR-4000
330 www.eaton.com
EMR-4000 IM02602009E
t-reset Reset time for intermittent phase failures 0.00 - 60.00s 0s [Protection Para
(INV characteristics only) /<n>
/I-Prot
Available if:Reset Mode = t-delay /51P[2]]
VRestraint max Maximum voltage restraint level. Definition 0.04 - 1.30Vn 1.00Vn [Protection Para
of Vn: Vn is dependent on the System /<n>
Parameter setting of "Main VT con". When /I-Prot
the System Parameters "Main VT con" is /51P[2]]
set to "Open-Delta" , "Vn = Main VT sec ".
When the System Parameters "Main VT
con" is set to "Wye", "Vn = Main VT
sec/SQRT(3)".
www.eaton.com 331
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup IA Signal: Pickup IA
Pickup IB Signal: Pickup IB
Pickup IC Signal: Pickup IC
Pickup Signal: Pickup
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
332 www.eaton.com
EMR-4000 IM02602009E
Name Description
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
Signals to be measured for Voltage Restraint element: the threshold values, total tripping time (recommended),
or alternatively tripping delays and the dropout ratios; each time 3 x single-phase and 1 x three-phase.
Eaton recommends measuring the total tripping time instead of the tripping
delay. The tripping delay should be specified by the customer. The total
tripping time is measured at the position signaling contact of the breaker
(not at the relay output contacts!).
Total tripping time = tripping delay (please refer to the tolerances of the
protection stages)
+ breaker operating time (about 50 ms)
Please take the breaker operating times from the technical data specified in
the relevant documentation provided by the breaker manufacturer.
Necessary means:
• Current source;
• Voltage Source;
• Current and Voltage meters; and
• Timer.
Procedure:
www.eaton.com 333
IM02602009E EMR-4000
Functional Description
This CT has a large primary window through which all three-phase conductors can pass. The most common
ground fault CTs have a ratio of 50:5 or 50:1.
The protective device is recognized to UL 1053, Ground Fault Protective Device standard. This may eliminate
the need for a separate ground fault protector in many applications that formerly required one.
Note that the ground fault current settings 50R[x] and 50X [x] are based on the ground CT rated primary
current (In), not on FLA or the phase CT ratio. For example, a pickup setting of 0.10 gives a trip or alarm for an
actual ground leakage current of 5 A on the primary side of the sensor with a 50:5 CT.
This function is only useful for a grounded power system. The ground return is normally made from the neutral
of the secondary wire winding of the supply power transformer. Resistance grounding is acceptable as long as
the resulting fault current is at a level the protective device can be set to detect.
The ground CT, which provides sensitive protection for high-resistance ground faults, may saturate for a robust
heavy-current ground fault in a solidly-grounded system. Minimize the saturation problem by minimizing the
burden. Use the shortest and heaviest leads possible between the ground CT and the relay. The relay itself has
very low burden, usually much lower than the connecting wiring. Calculate the current magnitude that saturates
the ground CT. Consider the CT secondary voltage capability and the total burden of the CT secondary winding
itself, the connecting wires, and the relay. Make sure this saturation current is well above the minimum
sensitivity of the phase IOC function and/or the motor fuses.
A residual connection – the wired summation of the phase CT circuits through the ground CT input – requires a
much higher ground fault time setting to avoid false tripping. Thus, sensitivity is not nearly as good as with a
separate flux-canceling CT.
If the relay is installed where a residual connection is used, XCT should be set to the same value as CT Pri. The
User must then set the ground fault trip level at a high value to avoid nuisance tripping from CT ratio errors, third
harmonic and certain higher harmonics, or other measurement errors producing false residual currents. Monitor
the metered ground current during various loading conditions to ensure a good margin between these error
currents and the ground fault trip current setting 50R [x]. Also, watch out for phase CTs that saturate during
motor starting. The saturation produces a large residual current and a ground fault trip. This may be a problem
if the CTs have a low voltage capability (e.g.: C5 or C10), have long wiring runs, or are otherwise heavily
burdened.
334 www.eaton.com
EMR-4000 IM02602009E
For tripping curves please refer to the “Appendix/Instantaneous Current Curves (Ground Current Calculated)”
section.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents. However, this is only
possible if the current transformers are Wye-connected.
www.eaton.com 335
IM02602009E EMR-4000
336 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 337
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup IX or IR
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
338 www.eaton.com
EMR-4000 IM02602009E
• NINV (IEC/XInv);
• VINV (IEC/XInv);
• LINV (IEC/XInv);
• EINV (IEC/XInv);
• MINV (ANSI/XInv);
• VINV (ANSI/XInv);
• EINV (ANSI/XInv);
• Thermal Flat;
• Therm Flat IT;
• Therm Flat I2T; and
• Therm Flat I4T.
For tripping curves please refer to the “Appendix/Time Current Curves (Ground Current)” section.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents. However, this is only
possible if the current transformers are Wye-connected.
www.eaton.com 339
340
IM02602009E
51R[1]...[n]
Name = 51R[1]...[n]
Name.IGH2 Blo*
Name.Pickup
14 27d
Name.IGH2 Blo
Inactive
Active
AND AND
Please Refer to Diagram: IH2*
8 IH2.Blo IG
Name.Curve Shape
Name.t-multiplier
EMR-4000
Name.t-reset
Name.Reset Mode
www.eaton.com
φ
Name.Criterion INV
Fund.
IX Calculated
φ
Name.TripCmd
Based on above parameters, tripping
AND 15 19d
times and reset modes will be calculated
by the device.
www.eaton.com 341
IM02602009E EMR-4000
342 www.eaton.com
EMR-4000 IM02602009E
t-reset Reset time for intermittent phase failures 0.00 - 60.00s 0.00s [Protection Para
(INV characteristics only) /<n>
/I-Prot
Only available if:Reset Mode = t-delay /51R[1]]
www.eaton.com 343
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup IX or IR
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
344 www.eaton.com
EMR-4000 IM02602009E
For tripping curves please refer to the “Appendix/Instantaneous Current Curves (Ground Current Measured)”
section.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents. However, this is only
possible if the current transformers are Wye-connected.
www.eaton.com 345
346
IM02602009E
50X[1]...[n]
Name = 50X[1]...[n]
Name.IGH2 Blo*
Name.Pickup
14 27a
Name.IGH2 Blo
Inactive
Active
AND AND
Please Refer to Diagram: IH2*
8 IH2.Blo IG
EMR-4000
Name.Pickup
www.eaton.com
Name.Criterion Name.t
φ
DEFT
Fund.
Name.TripCmd
Based on above parameters, AND 15 19a
tripping times and reset modes
will be calculated by the device.
www.eaton.com 347
IM02602009E EMR-4000
348 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 349
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup IX or IR
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
• NINV (IEC/XInv);
• VINV (IEC/XInv);
• LINV (IEC/XInv);
350 www.eaton.com
EMR-4000 IM02602009E
• EINV (IEC/XInv);
• MINV (ANSI/XInv);
• VINV (ANSI/XInv);
• EINV (ANSI/XInv);
• Thermal Flat;
• Therm Flat IT;
• Therm Flat I2T; and
• Therm Flat I4T.
For tripping curves please refer to the “Appendix/Time Current Curves (Ground Current)” section.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents. However, this is only
possible if the current transformers are Wye-connected.
www.eaton.com 351
352
IM02602009E
51X[1]...[n]
Name = 51X[1]...[n]
Name.IGH2 Blo*
Name.Pickup
14 27b
Name.IGH2 Blo
Inactive
Active
AND AND
Please Refer to Diagram: IH2*
8 IH2.Blo IG
Name.Curve Shape
Name.t-multiplier
EMR-4000
Name.t-reset
Name.Reset Mode
www.eaton.com
φ
Name.Criterion INV
Fund.
RMS
Name.Trip
Name.Pickup AND
IX Measured
φ
www.eaton.com 353
IM02602009E EMR-4000
Pickup If the pickup value is exceeded, the module/ 0.002 - 2.000In 0.02In [Protection Para
(sensitive) element will be started. /<n>
/I-Prot
Dependency Dependency Dependency /51X[1]]
354 www.eaton.com
EMR-4000 IM02602009E
t-reset Reset time for intermittent phase failures 0.00 - 60.00s 0.00s [Protection Para
(INV characteristics only) /<n>
/I-Prot
Only available if:Reset Mode = t-delay /51X[1]]
www.eaton.com 355
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup IX or IR
Trip Signal: Trip
TripCmd Signal: Trip Command
Active AdaptSet Active Adaptive Parameter
DefaultSet Signal: Default Parameter Set
AdaptSet 1 Signal: Adaptive Parameter 1
AdaptSet 2 Signal: Adaptive Parameter 2
AdaptSet 3 Signal: Adaptive Parameter 3
AdaptSet 4 Signal: Adaptive Parameter 4
356 www.eaton.com
EMR-4000 IM02602009E
ZI - Zone Interlocking
Elements
ZI
Zone interlocking is a communication scheme used with breakers and protective relays to improve the level of
protection in a power distribution system. This is achieved through communication between the downstream
and upstream devices in a power system. The zones are classified by their location downstream of the main
circuit protective device which is generally defined as Zone 1.
By definition, a selectively coordinated system is one where by adjusting the trip unit pickup and time delay
settings, the breaker closest to the fault trips first. The upstream breaker serves two functions: (1) back-up
protection to the downstream breaker and (2) protection of the conductors between the upstream and
downstream breakers.
For faults which occur on the conductors between the upstream and downstream breakers, it is ideal for the
upstream breaker to trip with no time delay. This is the feature provided by Zone Selective Interlocking.
The zone interlocking information can be transferred to or received from other compatible zone interlocking
devices by means of suitable communication cables. The single zone interlock terminal block, with its 3-wire
scheme, can be used for either phase zone interlocking, ground zone interlocking, or a combination of the two.
If phase and ground zone interlocking are combined, the potential consequences must be understood before
implementation.
Systems containing multiple sources, or where the direction of power flow varies,
require special considerations, or may not be suitable for this feature.
• Remove zone interlocking OUTPUT signal immediately after detection of a breaker failure.
• Reset time (about ten cycles - settable) to interrupt OUTPUT signal for durable trip signal.
• Small trip delay (about three cycles – settable) to wait for downstream devices interlocking signals.
• Zone interlocking trip signal only possible by absence of zone interlocking INPUT signals.
• Configurable zone interlocking trip functions (protective functions serve as zone interlocking trip
functions).
• Zone interlocking trip function pickup and tripping characteristic adaption using adaptive settings
controlled by the zone interlocking input signals.
www.eaton.com 357
IM02602009E EMR-4000
Via an external input signal, the zone interlocking can also be blocked if the parameter »ExtBlockTripCMD« is
assigned.
• General: This group comprises the settings used to control the general usage of the zone interlocking
module.
• The OUTPUT group comprises the settings to configure the zone interlocking output logic. If the zone
interlocking application is used to a downstream device, the settings in OUTPUT group should be
programmed accordingly. If the zone interlocking application is only used for an upstream device (main
breaker or Zone 1), the setting ZoneInterlockOut within the OUTPUT group should be disabled.
358 www.eaton.com
EMR-4000 IM02602009E
The TRIP group comprises the settings used to configure the zone interlocking TRIP logic. If the zone
interlocking application is applied to an upstream device, (main breaker or Zone 1), the settings in the
TRIP group should be programmed accordingly. If the zone interlocking application is only used for a
downstream device (feeder breaker or Zone 2), the setting ZoneInterlockTrip in TRIP group should be
disabled.
Setting the above mentioned setting groups accordingly the zone interlocking module can be configured as:
• Midstream device application (using both OUTPUT and TRIP logic together).
The following menu and tables show the detailed information about the settings.
www.eaton.com 359
IM02602009E EMR-4000
The following current protective function elements serve as the Phase Zone Interlock OUTPUT start functions:
• 51P[1];
• 50P[1]; and
• 50P[2].
The following current protective function serves as the Ground Zone Interlock OUTPUT start functions:
• 51X[1];
• 50X[1];
• 51R[1]; and
• 50R[1].
51P[1].Pickup
t
51P[1].Trip
Reset Timer
10 Cycles
1
ZI.Bkr Blo
ZI.OUT
t
STATE
TRANSFER STANDBY STARTED TRIPPED RESET STANDBY
360 www.eaton.com
X2: ZI.Zone Out
50P[1].Pickup
50P[2].Pickup
OR
51P[1].Pickup
OR AND
50P[2].TripCmd
OR
51P[1].TripCmd
EMR-4000
Ground
www.eaton.com
ZI[1].Bkr Blo
OR
51X[1].Pickup
OR
50R[1].Pickup
t 166 ms
51R[1].Pickup AND
50X[1].TripCmd
51X[1].TripCmd
OR
50R[1].TripCmd
51R[1].TripCmd
IM02602009E
361
IM02602009E EMR-4000
The following overcurrent protection elements trigger Phase Zone-Interlock trip functions:
• 1.5 * 51P[1];
• 50P[1]; and
• 50P[2].
The following overcurrent protection elements trigger Ground Zone Interlock trip functions:
• 51X[1];
• 50X[1];
• 51R[1]; and
• 50R[1].
51P[1].Pickup
ZI.IN
ZI.Pickup
ZI.Trip
1
t
0
362 www.eaton.com
X2: ZI.Zone Trip
50P[1].Pickup
OR AND
ZI[1].Phase Trip
t 50 ms
AND
ZI[1].Trip
OR
ZI.IN
EMR-4000
Inactive AND 15
Phase
Ground
www.eaton.com
ZI[1].Ground Trip
t 50 ms
OR AND
AND
50X[1].Pickup
ZI[1].Ground Pickup
51X[1].Pickup
OR 14
50R[1].Pickup
51R[1].Pickup
ZI[1].Pickup
OR 14
363
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Bkr Blo Signal: Blocked by Breaker Failure
Phase Pickup Signal: Zone Interlocking Phase Pickup
Phase Trip Signal: Zone Interlocking Phase Trip
Ground Pickup Signal: Zone Interlocking Ground Pickup
Ground Trip Signal: Zone Interlocking Ground Trip
Pickup Signal: Pickup Zone Interlocking
Trip Signal: Zone Interlocking Trip
TripCmd Signal: Zone Interlocking Trip Command
Phase OUT Signal: Zone Interlocking Phase OUT
Ground OUT Signal: Zone Interlocking Ground OUT
OUT Signal: Zone Interlocking OUT
IN Signal: Zone Interlocking IN
The zone interlocking connection between relays is done by means of a twisted shielded cable. Downstream
zone interlock outputs may be paralleled from up to ten devices (FP-5000 or DT-3000 or a combination of both)
for connection to upstream zone interlocked relays.
364 www.eaton.com
EMR-4000 IM02602009E
Zone 1
FP-X000
J3
Out 1
In 4
Com 2
Zone 2
EDR-X000
FP-X000
X2 J3
Shield 13 Out 1
Out 14 In 4
Com 15 Com 2
Shield 16
In 17
Com 18
Zone 3
DT-3000 EDR-X000 FP-X000
Out 13 J3
Ground X2
In 14 Out 1
Out 15 Shield 13
Phase In 4
In 16 Out 14
Com 2
Com 18 Com 15
Shield 16
In 17
Com 18
By means of the zone interlocking terminals, the device can be connected to other Eaton protective devices such
as an FP5000, DT3000, etc.
As an upstream device, the terminals - Phase/Ground IN should be connected to the OUT terminals of up to ten
downstream device(s) by means of a dedicated cable wired in parallel. As a downstream device, the terminals -
Phase/Ground OUT should be connected to the IN terminals of an upstream device by means of a dedicated
cable.
www.eaton.com 365
IM02602009E EMR-4000
X?.
1 IRIG-B+
2 IRIG-B-
3
4
5
6
7
8 RO3
9
10
11 SC
12
13
14 OUT
15 COM
16
17 IN
18 COM
X?.
1 Do not use
2 Do not use
3
RO1
4
5
RO2
6
7
8 RO3
9
10
11 RO4
12
13
14 OUT
15 COM
16
17 IN
18 COM
366 www.eaton.com
EMR-4000 IM02602009E
This is the 46 device Current Unbalance setting, which works similar to the 47 device Voltage Unbalance setting.
The positive and negative sequence currents are calculated from the 3-phase currents. The Threshold setting
defines a minimum operating current magnitude of either I1 or I2 for the 46 function to operate, which insures
that the relay has a solid basis for initiating a current unbalance trip. The »%(I2/I1)« setting is the unbalance trip
pickup setting. It is defined by the ratio of negative sequence current to positive sequence current »%(I2/I1)« for
ABC rotation and »%(I1/I2)« for ACB rotation. The device will automatically select the correct ratio based on the
Phase Sequence setting in the System Configuration group described above.
This function requires positive or negative sequence current magnitude above the threshold setting and the
percentage current unbalance above the »%(I2/I1)« setting before allowing a current unbalance trip. Therefore,
both the threshold and percent settings must be met for the specified Delay time setting before the relay initiates
a trip for current unbalance.
www.eaton.com 367
368
IM02602009E
46[1]...[n]
Name = 46[1]...[n]
Name.Pickup
14
Name.t
Name.Threshold
t Name.Trip
AND
0
www.eaton.com
I2
IA
IB PPS
AND
NPS
Name.TripCmd
IC Filter AND 15
Name.%(I2/I1)
%(I2/I1)
www.eaton.com 369
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Negative Sequence
Trip Signal: Trip
TripCmd Signal: Trip Command
370 www.eaton.com
EMR-4000 IM02602009E
Necessary means:
• Three-phase current source with adjustable current unbalance; and
• Timer.
Procedure:
• Ensure that the phase sequence is the same as that set in the system parameters.
• Check the measuring value for the unbalanced current »I2 Fund.«. The measuring value displayed for
»I2 Fund.« should be zero (within the physical measuring accuracy).
If the displayed magnitude for I2 Fund. is the same as that for the balanced
nominal currents fed to the relay, it implies that the phase sequence of the
currents seen by the relay is reversed.
• Again check the measuring value of the unbalanced current »I2 Fund.« in the »Measuring Values«
menu.
The measuring value of the unbalanced current »I2 Fund.« should now be 33%.
• Once again check the measuring value of the unbalanced current I2 Fund. in the »Measuring Values«
menu. The measuring value of the asymmetrical current »I2 Fund.« should be again 33%.
www.eaton.com 371
IM02602009E EMR-4000
• Again check the measuring value of unbalanced current »I2 Fund.« in the »Measuring Values« menu.
The measuring value of the unbalanced current »I2 Fund.« should still be 33%.
• Switch off IA (the threshold value »Threshold« for »I2 Fund.« must be below 33%).
The present current unbalance »I2 Fund.« corresponds with 1/3 of the existing phase current displayed.
• Configure minimum »%(I2/I1)« setting (2%) and an arbitrary threshold value »Threshold« (I2 Fund.).
• For testing the threshold value, a current has to be fed to phase A which is lower than three times the
adjusted threshold value »Threshold« (I2 Fund.).
• Feeding only phase A results in »%(I2/I1) = 100%«, so the first condition »%(I2/I1) >= 2%« is always
fulfilled.
Having tripped the relay in the previous test, now decrease the phase A current. The drop-out ratio must not be
higher than 0.97 times the threshold value.
Testing %(I2/I1)
• Configure minimum threshold value »Threshold« (I2 Fund.) (0.01 x In) and set »%(I2/I1)« greater or
equal to 10%.
• Apply a balanced three-phase current system (nominal currents). The measuring value of »%(I2/I1)«
should be 0%.
• Now increase the phase A current. With this configuration, the threshold value »Threshold« (I2 Fund.)
should be reached before the value »%(I2/I1)« reaches the set »%(I2/I1)« ratio threshold.
Having tripped the relay in the previous test, now decrease the phase A current. The drop-out of »%(I2/I1)« has
to be 1% below the »%(I2/I1)«setting.
The measured trip delays, threshold values, and drop-out ratios are within the permitted deviations/tolerances,
specified under Technical Data.
372 www.eaton.com
EMR-4000 IM02602009E
In case a faulty line is energized (e.g.: when an grounding switch is in the CLOSE position), an instantaneous trip
is required. The SOTF module is provided to generate a permissive signal for other protection functions such as
overcurrents to accelerate their trips. The SOTF condition is recognized according to the User’s operation mode
that can be based on:
This protection module can initiate a high speed trip of the overcurrent protection modules. The module can be
started via a digital input that indicates that the breaker is manually closed.
This module issues a signal only (the module is not armed and does not
issue a trip command).
www.eaton.com 373
374
IM02602009E
SOTF
Name = SOTF
SOTF.I<
Bkr.Prot CLOSE
41
SOTF.Mode
Bkr State
EMR-4000
SOTF.
I< t-enable
t SOTF.enabled
OR AND
Bkr State And I<
T 0
OR
Bkr manual CLOSE
www.eaton.com
Ext SOTF
SOTF.I<
IA
AND
IB
AND
IC
Ext SOTF
www.eaton.com 375
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Rvs Blo Signal: Reverse Blocking
enabled Signal: Switch Onto Fault enabled. This Signal can be used to
modify Overcurrent Protection Settings.
I< Signal: No Load Current.
Testing the module Switch Onto Fault according to the configured operating mode:
Necessary means:
376 www.eaton.com
EMR-4000 IM02602009E
• Ampere meters (may be needed if the Enable Mode depends on current); and
• Timer.
Mode I< (In order to test the effectiveness): Initially, do not feed any current.
Start the timer and feed with an abruptly changing current that is distinctly
greater than the I<-threshold to the measuring inputs of the relay.
Mode I< and Bkr state: Simultaneously, manually switch on the breaker
and feed with an abrupt change current that is distinctly greater than the
I<-threshold.
Mode Bkr state: The breaker has to be in the OFF position. The signal
„SOTF.ENABLED“=0 is false. If the breaker is switched on, the signal
„SOTF.ENABLED“=1 becomes true as long as the timer t-effective is running.
• The breaker has to be in the OPEN position. There must be no load current.
Testing:
• Manually switch the breaker to the CLOSE position and start the timer at the same time.
• After the hold time t-enable is expired, the state of the signal has to change to "SOTF.enabled“=0.
The measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond
with those values, specified in the adjustment list. Permissible deviations/tolerances can be found in the Tech-
nical Data section.
www.eaton.com 377
IM02602009E EMR-4000
In case that within the System Parameters "Main VT con" is set to "Open-Delta":
Vn=Main VT sec .
MainVT sec
Vn=
3
This is the 27 device undervoltage setting for the main three phase VT. This function consists of a Phase, a
Pickup, a Delay setting. The Phase setting allows the User to select at which phase (any one, any two, or all)
the undervoltage function operates. The Pickup setting is the magnitude at which the undervoltage element
operates. The Delay setting is the time period an undervoltage must occur before the device initiates a trip.
Depending on the settings within the System Parameters, the element works based on phase-to-phase (»Open-
Delta«) or phase-to-ground (»wye«) voltages. This element will operate depending on the phase setting: if any
one, any two, or all of the voltage(s) that is/are selected by the Phase setting drop(s) below the set point. This
element works based on RMS values.
An undervoltage pickup occurs when the measured voltage drops below the UV Threshold setting. The
undervoltage trip is set when the voltage stays below the threshold setting for the delay time specified (within the
number of phases specified by the phase setting). The undervoltage pickup and trip is reset when the voltage
rises above the drop-out ratio specified in Specifications section for the undervoltage protection.
If the element should be blocked in the event of a “Loss of Potential”, the »LOP BLO« parameter must be set to
»active«.
If the VT measurement location is not at the bus bar side but at the output side,
the following has to be taken into account.
When the auxiliary voltage is switched on and the measuring voltage has not yet
been applied, undervoltage tripping has to be prevented by an »External
Blocking«. Otherwise a continuous tripping would occur, disabling the ability to
energize again.
378 www.eaton.com
EMR-4000 IM02602009E
If phase voltages are applied to the measuring inputs of the device and system
parameter »VT con« is set to »Phase-to-ground«, the messages issued by the
voltage protection module in case of actuation or trip should be interpreted as
follows:
However, if line-to-line voltages are applied to the measuring inputs and system
parameter »VT con« is set to »Phase to Phase«, then the messages should be
interpreted as follows:
www.eaton.com 379
380
IM02602009E
27M[1]...[n]
Name = 27M[1]...[n]
Name.Pickup Phase A
Name.LOP Blo
28
Inactive Name.Pickup Phase B
Active
29
Name.Pickup Phase C
30
AND
LOP.LOP Blo Name.Pickup
38 14
Name.Trip Phase A
EMR-4000
AND 20
Name.Trip Phase B
www.eaton.com
Name.Mode
AND 21
any one
any two
AND all
Name.Trip Phase C
V< AND 22
VA
AND
RMS
AND AND Name.t
VB
RMS t Name.Trip
OR
VC 0
RMS
AND
AND OR Name.TripCmd
www.eaton.com 381
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Phase A Signal: Pickup Phase A
Pickup Phase B Signal: Pickup Phase B
382 www.eaton.com
EMR-4000 IM02602009E
Name Description
Pickup Phase C Signal: Pickup Phase C
Pickup Signal: Pickup Voltage Element
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip Signal: Trip
TripCmd Signal: Trip Command
• For testing the threshold values, the test voltage has to be decreased until the relay is activated.
• For detection of the drop-out ratio, the measuring quantity has to be increased to achieve more than
103% of the trip value. At 103% of the trip value, the relay is to drop-out at the earliest moment.
www.eaton.com 383
IM02602009E EMR-4000
In case that within the System Parameters "Main VT con" is set to "Open-Delta":
Vn=Main VT sec .
MainVT sec
Vn=
3
This is the 59 device Overvoltage setting for the Main VT. This element consists of a Phase, a Pickup, and a
Delay setting. The Phase setting allows the User to select which phase (any one, any two, or all) the
Overvoltage function operates. Depending on the settings within the System Parameters, the element works
based on phase-to-phase (»Open-Delta«) or phase-to-ground (»wye«) voltages. This element will operate
depending on the phase setting: if any one, any two, or all of the voltage(s) that is/are selected by the Phase
setting rise(s) above the set point. This element works based on RMS values.
An overvoltage pickup occurs when the measured voltage rises above the overvoltage Threshold setting. The
overvoltage trip is set when the voltage stays above the threshold setting for the delay time specified (within the
number of phases specified by the phase setting). The overvoltage pickup and trip is reset when the voltage
falls below the drop-out ratio specified in Specifications section for the overvoltage protection.
If phase voltages are applied to the measuring inputs of the device and system
parameter »VT con« is set to »Phase-to-ground«, the messages issued by the
voltage protection module in case of actuation or trip should be interpreted as
follows:
However,if line-to-line voltages are applied to the measuring inputs and system
parameter »VT con« is set to »Phase to Phase«, then the messages should be
interpreted as follows:
384 www.eaton.com
59M[1]...[n]
Name = 59M[1]...[n]
Name.Pickup Phase A
28
Name.Pickup Phase B
29
Name.Pickup Phase C
30
Name.Pickup
14
Name.Trip Phase A
EMR-4000
AND 20
Name.Mode
Name.Trip Phase B
www.eaton.com
any one AND 21
any two
all
AND Name.Trip Phase C
V> AND 22
VA
AND
RMS
AND AND Name.t
VB
RMS t Name.Trip
OR
VC 0
RMS AND
AND OR Name.TripCmd
385
IM02602009E EMR-4000
386 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
www.eaton.com 387
IM02602009E EMR-4000
Name Description
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Phase A Signal: Pickup Phase A
Pickup Phase B Signal: Pickup Phase B
Pickup Phase C Signal: Pickup Phase C
Pickup Signal: Pickup Voltage Element
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip Signal: Trip
TripCmd Signal: Trip Command
Necessary means:
• Three phase AC voltage source;
• Timer for measuring of the tripping time; and
• Voltmeter.
388 www.eaton.com
EMR-4000 IM02602009E
This is the 27A device Undervoltage setting for the Auxiliary VT. This device setting works exactly the same as
the 27M except it is a single-phase element only operating from the Auxiliary VT input. The Alarm Delay is the
time period a LOP must occur before the device initiates a »LOP BLO« signal that can be used to block other
elements like 51V (Voltage Restraint).
www.eaton.com 389
390
IM02602009E
27A[1]...[n]
Name = 27A[1]...[n]
Name.Pickup
14 31
www.eaton.com
Name.t
Name.V<
t Name.Trip
AND
V 0
RMS
Name.TripCmd
AND 15 23
Please Refer to Diagram: Trip Blockings
3 (Tripping command not deactivated or blocked. )
EMR-4000 IM02602009E
www.eaton.com 391
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Residual Voltage Supervision-Element
Trip Signal: Trip
TripCmd Signal: Trip Command
392 www.eaton.com
EMR-4000 IM02602009E
Necessary components:
• One-phase AC voltage source;
• Timer for measuring of the tripping time; and
• Voltmeter.
This is the 59 device Overvoltage setting for the Auxiliary VT. This device setting works exactly the same as the
59M, except it is a single-phase element only operating from the Auxiliary VT input.
www.eaton.com 393
394
IM02602009E
59A[1]...[n]
Name = 59A[1]...[n]
Name.Pickup
14 31
www.eaton.com
Name.t
Name.Pickup
t Name.Trip
AND
V 0
RMS
Name.TripCmd
AND 15 23
Please Refer to Diagram: Trip Blockings
3 (Tripping command not deactivated or blocked. )
EMR-4000 IM02602009E
www.eaton.com 395
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Residual Voltage Supervision-Element
Trip Signal: Trip
TripCmd Signal: Trip Command
396 www.eaton.com
EMR-4000 IM02602009E
Necessary components:
• One-phase AC voltage source;
• Timer for measuring of the tripping time; and
• Voltmeter.
This is the 47 device Voltage Unbalance setting, which consists of the Threshold, %(V2/V1), and Delay settings.
The voltage unbalance function is based on the Main VT system 3-phase voltages.
The positive and negative sequence voltages are calculated from the 3-phase voltages. The Threshold setting
defines a minimum operating voltage magnitude of either V1 or V2 for the 47 function to operate, which ensures
that the relay has a solid basis for initiating a voltage unbalance trip. This is a supervisory function and not a trip
level.
The %(V2/V1) setting is the unbalance trip pickup setting. It is defined by the ratio of negative sequence voltage
www.eaton.com 397
IM02602009E EMR-4000
to positive sequence voltage (% Unbalance=V2/V1), or %(V2/V1) for ABC rotation and %(V1/V2) for ACB
rotation. The device will automatically select the correct ratio based on the Phase Sequence setting in the
System Configuration group described above.
This function requires positive or negative sequence voltage magnitude above the threshold setting and the
percentage voltage unbalance above the %(V2/V1) setting before allowing a voltage unbalance trip. Therefore,
both the threshold and percent settings must be met for the specified Delay time setting before the relay initiates
a trip for voltage unbalance.
The voltage unbalance pickup and trip functions are reset when the positive and negative sequence voltages V1
and V2 drop below the Threshold setting or (V2/V1) drops below the %(V2/V1) setting minus 1%.
398 www.eaton.com
47[1]...[n]
Name = 47[1]...[n]
Device Planning
Name.Mode
V1>
V1<
Threshold
Name.Pickup
Name.Threshold
PPS V1
Name.t
Filter
www.eaton.com
t Name.Trip
AND
VA 0 14
VB AND
VC
Name.%(V2/V1)
NPS V2
Name.TripCmd
AND 15
Filter
399
IM02602009E EMR-4000
400 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
www.eaton.com 401
IM02602009E EMR-4000
Name Description
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Voltage Asymmetry
Trip Signal: Trip
TripCmd Signal: Trip Command
Necessary means:
• Three-phase AC voltage source with adjustable voltage unbalance; and
• Timer.
Procedure:
• Ensure that the phase sequence is the same as that set in the system parameters.
• Check the measuring value for the unbalanced voltage »V2 Fund.«. The measuring value displayed for
»V2 Fund.« should be zero (within the physical measuring accuracy).
If the displayed magnitude for V2 Fund. is the same as that for the balanced
nominal voltages fed to the relay, it implies that the phase sequence of the
voltages seen by the relay is reversed.
• Again check the measuring value of the unbalanced voltage »V2 Fund.« in the [Measured
Values/Voltage] menu. The measuring value of the unbalanced voltage »V2 Fund.« should now be 33%
of the nominal voltage.
402 www.eaton.com
EMR-4000 IM02602009E
• Once again check the measuring value of the unbalanced voltage »V2 Fund.« in the [Measured Values/
Voltage] menu. The measuring value of the unbalanced voltage »V2 Fund.« should be again 33%.
• Again check the measuring value of unbalanced voltage »V2 Fund.« in the [Measured Values/Voltage]
menu. The measuring value of the unbalanced voltage »V2 Fund.« should still be 33%.
• Switch off VA (the threshold value »Threshold« for »V2 Fund.« must be below 33% of the nominal
voltage Vn).
The present voltage unbalance »V2 Fund.« corresponds with 1/3 of the existing phase voltage displayed.
• Configure minimum »%(V2/V1)« setting (2%) and an arbitrary threshold value »Threshold« (V2 Fund.).
• For testing the threshold value, a voltage has to be fed to phase A which is lower than three times the
adjusted threshold value »Threshold« (V2 Fund.).
• Feeding only phase A results in »%(V2/V1) = 100%«, so the first condition »%(V2/V1) >= 2%« is always
fulfilled.
Having tripped the relay in the previous test, now decrease the phase A voltage. The drop-out ratio must not be
higher than 0.97 times the threshold value.
Testing %(V2/V1)
• Configure minimum threshold value »Threshold« (V2 Fund.) (0.01 x Vn) and set »%(V2/V1)« greater or
equal to 10%.
• Apply a balanced three-phase voltage system (nominal voltages). The measuring value of »%(V2/V1)«
should be approximately 0%.
• Now increase the phase A voltage. With this configuration, the threshold value »Threshold« (V2 Fund.)
should be reached before the value »%(V2/V1)« reaches the set »%(V2/V1)« ratio threshold.
www.eaton.com 403
IM02602009E EMR-4000
Having tripped the relay in the previous test, now decrease the phase A voltage. The drop-out of »%(V2/V1)«
has to be 1% below the »%(V2/V1)«setting.
The measured trip delays, threshold values, and drop-out ratios are within the permitted deviations/tolerances,
specified under Technical Data.
The measuring principle of the frequency supervision is based in general on the time measurement of complete
cycles, whereby a new measurement is started at each zero passage. The influence of harmonics on the
measuring result is thus minimized.
V(t) T
T
Frequency tripping is sometimes not desired by low measured voltages which, for instance. occur during
alternator acceleration. All frequency supervision functions are blocked if the voltage is lower 0.15 times Vn.
Frequency Functions
Due to its various frequency functions, the device is very flexible. That makes it suitable for a wide range of
applications where frequency supervision is an important criterion.
In the Device Planning menu, the User can decide how to use each of the six frequency elements.
404 www.eaton.com
EMR-4000 IM02602009E
• 81U – Underfrequency;
• 81O – Overfrequency;
• 81R – Rate of Change of Frequency (df/dt);
• 81UR – Underfrequency and Rate of Change of Frequency (df/dt);
• 81OR – Overfrequency and Rate of Change of Frequency (df/dt);
• 81UΔR – Underfrequency and DF/DT (absolute frequency change per definite time interval);
• 81OΔR – Overfrequency and DF/DT (absolute frequency change per definite time interval); and
• 78V – Vector Surge.
81U – Underfrequency
This protection element provides a pickup threshold and a tripping delay. If the frequency falls below the set
pickup threshold, an alarm will be issued instantaneously. If the frequency remains under the set pickup
threshold until the tripping delay has elapsed, a tripping command will be issued.
With this setting, the frequency element protects electrical generators, loads, or electrical operating equipment in
general against underfrequency.
81O – Overfrequency
This protection element provides a pickup threshold and a tripping delay. If the frequency exceeds the set
pickup threshold, an alarm will be issued instantaneously. If the frequency remains above the set pickup
threshold until the tripping delay has elapsed, a tripping command will be issued.
With this setting, the frequency element protects electrical generators, loads, or electrical operating equipment in
general against overfrequency.
Working Principle
The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase
voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode
set in the Device Planning (81U or 81O), the phase voltages are compared to the set pickup threshold for over-
or under-frequency. If in any of the phases, the frequency exceeds or falls below the set pickup threshold and if
there are no blocking commands for the frequency element, an alarm is issued instantaneously and the tripping
delay timer is started. When the frequency still exceeds or is below the set pickup threshold after the tripping
delay timer has elapsed, a tripping command will be issued.
www.eaton.com 405
406
IM02602009E
81[1]...[n]:81U-Under Or 81O-Over
Name = 81[1]...[n]
Device Planning
Name.Pickup 81
Name.Mode
Name.Pickup
81U-Under: 81O-Over
81O-Over: 81U-Under
14
Name.f
VA
(81O-Over|81U- Name.t
Name.Trip 81
Under)
VB Frequency Calculation t Name.Trip
f AND
0
VC
EMR-4000
Name.TripCmd
AND 15
www.eaton.com
<15%Vn
Name.Blo by V<
<15%Vn AND
<15%Vn
Electrical generators running in parallel with the mains (e. g.: industrial internal power supply plants) should be
separated from the mains when failure in the intra-system occurs for the following reasons:
• Damage to electrical generators must be prevented when mains voltage is recovering asynchronously
(e. g.: after a short interruption).
A reliable criterion of detecting mains failure is the measurement of the rate of change of frequency 81R (df/dt).
The precondition for this is a load flow via the mains coupling point. At mains failure, the load flow change
spontaneously leads to an increasing or decreasing frequency. At active power deficit of the internal power
station, a linear drop of the frequency occurs and a linear increase occurs at power excess. Typical frequency
gradients during application of "mains decoupling" are in the range of 0.5 Hz/s up to over 2 Hz/s.
The protective device detects the instantaneous frequency gradient 81R (df/dt) of each mains voltage period.
Through multiple evaluations of the frequency gradient in sequence, the continuity of the directional change (sign
of the frequency gradient) is determined. Because of this special measuring procedure, a high safety in tripping
and thus a high stability against transient processes (e. g.: switching procedure) are achieved.
The frequency gradient (rate of change of frequency [df/dt]) may have a negative or positive sign, depending on
frequency increase (positive sign) or decrease (negative sign).
In the frequency parameter sets, the User can define the kind of df/dt mode:
This protection element provides a tripping threshold and a tripping delay. If the frequency gradient df/dt
exceeds or falls below the set tripping threshold, an alarm will be issued instantaneously. If the frequency
gradient remains still above/below the set tripping threshold until the tripping delay has elapsed, a tripping
command will be issued.
Working Principle
The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase
voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode
set in the Device Planning (81R), the phase voltages are compared to the set frequency gradient (df/dt)
threshold. If in any of the phases, the frequency gradient exceeds or falls below the set pickup threshold (acc. to
the set df/dt mode) and if there are no blocking commands for the frequency element, an alarm is issued
instantaneously and the tripping delay timer is started. When the frequency gradient still exceeds or is below the
set pickup threshold after the tripping delay timer has elapsed, a tripping command will be issued.
www.eaton.com 407
408
IM02602009E
Name.Pickup
14
Name.Mode t
Name.Trip
df/dt Mode AND
0
81R-Rate of Change
Positive df/dt
EMR-4000
Negative df/dt
Absolute df/dt
www.eaton.com
VB
df/dt Calculation -df/dt
VC
Idf/dtI Name.TripCmd
AND 15
<15%Vn
Name.Blo by V<
<15%Vn AND
<15%Vn
With this setting, the frequency element supervises if the frequency falls below a set pickup threshold and if the
frequency gradient exceeds a set threshold at the same time.
In the selected frequency parameter set 81[X], an underfrequency pickup threshold f<, a frequency gradient
df/dt, and a tripping delay can be set.
Whereby:
With this setting, the frequency element supervises if the frequency exceeds a set pickup threshold and if the
frequency gradient exceeds a set threshold at the same time.
In the selected frequency parameter set 81[X], an overfrequency pickup threshold f>, a frequency gradient df/dt,
and a tripping delay can be set.
Whereby:
Working Principle
The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase
voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode
set in the Device Planning (81UR & df/dt or 81OR & dt/dt), the phase voltages are compared to the set
frequency pickup threshold and the set frequency gradient (df/dt) threshold. If in any of the phases, both the
frequency and the frequency gradient exceed or falls below the set thresholds and if there are no blocking
commands for the frequency element, an alarm is issued instantaneously and the tripping delay timer is started.
When the frequency and the frequency gradient still exceed or are below the set threshold after the tripping
delay timer has elapsed, a tripping command will be issued.
www.eaton.com 409
410
IM02602009E
Name.Pickup 81
Please Refer to Diagram: Blockings
2 (Element is not deactivated and no active blocking signals) Name.Pickup df/dt | DF/DT
81O-Over f
VA 81U-Under
Name.Trip df/dt | DF/DT
VB Frequency Calculation
f f
Name.Trip 81
VC Name.t
t
Name.Trip
df/dt Mode AND
0
Positive df/dt
EMR-4000
Negative df/dt
Absolute df/dt
www.eaton.com
df/dt Calculation -df/dt
Idf/dtI Name.TripCmd
AND 15
<15%Vn
Name.Blo by V<
<15%Vn AND
<15%Vn
With this setting, the frequency element supervises the frequency and the absolute frequency difference during a
definite time interval.
In the selected frequency parameter set 81[X], an underfrequency pickup threshold f<, a threshold for the
absolute frequency difference (frequency decrease) DF and supervision interval DT can be set.
With this setting, the frequency element supervises the frequency and the absolute frequency difference during a
definite time interval.
In the selected frequency parameter set 81[X], an overfrequency pickup threshold f>, a threshold for the
absolute frequency difference (frequency increase) DF and supervision interval DT can be set.
Working Principle
The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase
voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode
set in the Device Planning (81UR & DF/DT or 81OR & DF/DT), the phase voltages are compared to the set
frequency pickup threshold and the set frequency decrease or increase threshold DF.
If in any of the phases, the frequency exceeds or falls below the set pickup threshold and if there are no blocking
commands for the frequency element, an alarm is issued instantaneously. At the same time the timer for the
supervision interval DT is started. When, during the supervision interval DT, the frequency still exceeds or is
below the set pickup threshold and the frequency decrease/increase reaches the set threshold DF, a tripping
command will be issued.
Case 1:
When the frequency falls below a set f< threshold (81U) at t1, the DF/DT element energizes. If the frequency
difference (decrease) does not reach the set value DF before the time interval DT has expired, no trip will occur.
The frequency element remains blocked until the frequency falls below the underfrequency threshold f< (81U)
again.
Case 2:
When the frequency falls below a set f< threshold (81U) at t4, the DF/DT element energizes. If the frequency
difference (decrease) reaches the set value DF before the time interval DT has expired (t5), a trip command is
issued.
www.eaton.com 411
412
IM02602009E
Device Planning
Name.Pickup
Name.Mode
14
81ODR- Over & DF/DT
VA
81UDR- Under & DF/DT
Name.Trip df/dt | DF/DT
VB 81O-Over f
Frequency Calculation DT Name.Trip 81
f 1
VC 81U-Under
AND t Name.Trip
AND
<name>.81+D
F
EMR-4000
Name.TripCmd
AND 15
www.eaton.com
Name.Blo by V<
<15%Vn
<15%Vn AND
<15%Vn
Trip
f
Reset
Temporarily Blocking
fN
81U-Under
DF
DF
DF
EMR-4000
www.eaton.com
t
DT DT
t1 t2 t3 t4 t6
t5
IM02602009E
413
IM02602009E EMR-4000
The vector surge supervision protects synchronous generators in mains parallel operation due to very fast
decoupling in case of mains failure. Very dangerous are mains auto reclosings for synchronous generators. The
mains voltage returning typically after 300 ms can hit the generator in asynchronous position. A very fast
decoupling is also necessary in case of long time mains failures.
A very fast decoupling in case of mains failures for synchronous generators is very difficult. Voltage supervision
units cannot be used because the synchronous alternator, as well as the load impedance, support the
decreasing voltage.
In this situation, the mains voltage drops only after some 100 ms below the pickup threshold of the voltage
supervision and, therefore, a safe detection of mains auto reclosings is not possible with voltage supervision
only.
Frequency supervision is partially unsuitable because only a highly loaded generator decreases its speed within
100 ms. Current relays detect a fault only when short-circuit type currents exist, but cannot avoid their
development. Power relays are able to pickup within 200 ms, but they also cannot prevent the power from rising
to short-circuit values. Since power changes are also caused by sudden loaded alternators, the use of power
relays can be problematic.
Whereas the vector surge supervision of the device detects mains failures within 60 ms without the restrictions
described above because it is specially designed for applications where very fast decoupling from the mains is
required. Adding the typical operating time of a breaker or contactor, the total disconnection time remains below
150 ms.
Basic requirement for tripping of the generator/mains monitor is a change in load of more than 15 - 20% of the
rated load. Slow changes of the system frequency, for instance at regulating processes (adjustment of speed
regulator), do not cause the relay to trip.
Trippings can also be caused by short-circuits within the grid, because a voltage vector surge higher than the
preset value can occur. The magnitude of the voltage vector surge depends on the distance between the short-
circuit and the generator. This function is also of advantage to the Power Utility Company because the mains
short-circuit capacity and, consequently, the energy feeding the short-circuit is limited.
To prevent a possible false tripping, the vector surge measuring is blocked at a low input voltage <15% Vn. The
undervoltage lockout acts faster then the vector surge measurement.
Vector surge tripping is blocked by a phase loss so that a VT fault (e. g.: faulty VTs fuse) does not cause false
tripping.
414 www.eaton.com
EMR-4000 IM02602009E
V = I1* j Xd I1 I2
VP V1 Grid
V1
VP
V = I1* j Xd
Grid/Load
Generator
The rotor displacement angle between stator and rotor is dependent on the mechanical moving torque of the
generator shaft. The mechanical shaft power is balanced with the electrical fed mains power and, therefore, the
synchronous speed keeps constant.
www.eaton.com 415
IM02602009E EMR-4000
V´ = I´1* j Xd
I1
VP V´1 Grid
In case of mains failure or auto-reclosing, the generator suddenly feeds a very high load. The rotor
displacement angle is decreased repeatedly and the voltage vector V1 changes its direction (V1').
V1 V´1
VP
V´ = I´1* j Xd
Generator Load
416 www.eaton.com
EMR-4000 IM02602009E
Trip
t=0 t
As shown in the voltage/time diagram, the instantaneous value of the voltage jumps to another value and the
phase position changes. This is called phase or vector surge.
The relay measures the cycle duration. A new measuring is started at each zero passage. The measured cycle
duration is internally compared with a reference time and from this the deviation of the cycle duration of the
voltage signal is ascertained. In case of a vector surge as shown in the above graphic, the zero passage occurs
either earlier or later. The established deviation of the cycle duration is in compliance with the vector surge
angle. If the vector surge angle exceeds the set value, the relay trips immediately.
Tripping of the vector surge is blocked in case of loss of one or more phases of the measuring voltage.
Working Principle
The vector surge element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase
voltages is below 15% Vn, the vector surge calculation is blocked. According to the frequency supervision mode
set in the Device Planning (78V), the phase voltages are compared to the set vector surge threshold. If in any of
the phases, the vector surge exceeds the set threshold and if there are no blocking commands for the frequency
element, an alarm and a trip command is issued instantaneously.
www.eaton.com 417
418
IM02602009E
Name.Pickup
VA Name.78V vector
surge
78V vector
www.eaton.com
VB
Delta phi Calculation surge
VC
Name.TripCmd
AND 15
<15%Vn
Name.Blo by V<
<15%Vn AND
<15%Vn
www.eaton.com 419
IM02602009E EMR-4000
420 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo by V< Signal: Module is blocked by undervoltage.
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup 81 Signal: Pickup Frequency Protection
Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
Pickup Vector Surge Signal: Pickup Vector Surge
Pickup Signal: Pickup Frequency Protection (collective signal)
Trip 81 Signal: Frequency has exceeded the limit.
Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
Trip Vector Surge Signal: Trip delta phi
www.eaton.com 421
IM02602009E EMR-4000
Name Description
Trip Signal: Trip Frequency Protection (collective signal)
TripCmd Signal: Trip Command
Necessary means:
• Three-phase voltage source with variable frequency; and
• Timer
Procedure:
• For testing the threshold values, the frequency has to be decreased until the protection element is
422 www.eaton.com
EMR-4000 IM02602009E
activated.
• For detection of the fallback ratio, the measuring quantity has to be increased to more than 100.05% of
the trip value (or 0.05% fn). At 100.05% of the trip value the relay is to fall back at the earliest (or 0.05%
fn).
Necessary means:
• Three-phase voltage source and
• Frequency generator that can generate and measure a linear, defined rate of change of frequency.
Procedure:
Necessary means:
• Three-phase voltage source and
• Frequency generator that can generate and measure a linear, defined rate of change of frequency.
Procedure:
www.eaton.com 423
IM02602009E EMR-4000
Necessary means:
• Three-phase voltage source and
• Frequency generator that can generate and measure a linear, defined rate of change of frequency.
Procedure:
Necessary means:
• Three-phase voltage source and
• Frequency generator that can generate and measure a defined frequency change.
Procedure:
Necessary means:
• Three-phase voltage source and
• Frequency generator that can generate and measure a defined frequency change.
424 www.eaton.com
EMR-4000 IM02602009E
Procedure:
Necessary means:
• Three-phase voltage source that can generate a definite step (sudden change) of the voltage pointers
(phase shift).
Procedure:
32 - Power Protection
Available Elements:
32[1] ,32[2] ,32[3]
This is the 32 device Power Protection setting. Each element can be set to one of five settings:
• Do Not Use;
• Over Forward Power (P>);
• Under Forward Power (P<);
• Over Reverse Power (Pr>); and
• Under Reverse Power (Pr<).
Each element consists of a Pickup and a Delay setting. These elements are based on rated apparent power
VAn.
The following graphics show the areas that are protected by the corresponding modes.
www.eaton.com 425
IM02602009E EMR-4000
Pickup P>
Pickup P<
426 www.eaton.com
EMR-4000 IM02602009E
Pickup Pr>
Pickup Pr<
www.eaton.com 427
428
IM02602009E
32[1]...[n]
Name = 32[1]...[n]
Name.Pickup
14
Loss of Potential Blo
active
Name.t
Please Refer to Diagram:.LOP
38 t Name.Trip
OR AND AND
Please Refer to Diagram:.CTS 0
40
EMR-4000
www.eaton.com
Pickup P<
Pickup Pr> OR
Pickup Pr<
Name.Mode
Syst W RMS
www.eaton.com 429
IM02602009E EMR-4000
430 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Power Protection
Trip Signal: Trip Power Protection
TripCmd Signal: Trip Command
www.eaton.com 431
IM02602009E EMR-4000
• P>;
• P<;
• Pr>; and
• Pr<.
Necessary means:
• Feed rated voltage and rated current to the measuring inputs of the relay.
• Adjust the current pointers 30 degrees lagging to the voltage pointers.
• The following measuring values have to be shown:
• P=0.86 Pn;
• Q=0.5 Qn; and
• S=1 Sn.
If the measured values are shown with a negative (algebraic) sign, check
the wiring.
432 www.eaton.com
EMR-4000 IM02602009E
The examples shown within this chapter have to be carried out with the
tripping values and tripping delays that apply to the User's switchboard.
If the User is testing „greater than thresholds“ (e.g.: P>), start at 80% of the
tripping value and increase the object to be tested until the relay picks up.
In case the User is testing „less than thresholds“ (e.g.: P<), start at 120% of
the tripping value and reduce the object to be tested until the relay picks
up.
If the User is testing tripping delays of „greater than“ modules (e.g.: P>),
start a timer simultaneously with an abrupt change of the object to be
tested from 80% of the tripping value to 120% of the tripping value.
If the User is testing tripping delays of „less than“ modules (e.g.: P<), start
a timer simultaneously with an abrupt change of the object to be tested
from 120% of the tripping value to 80% of the tripping value.
P>
• Feed rated voltage and 0.9 times rated current in phase to the measuring inputs of the relay (PF=1).
• The measured values for the active power „P“ must show a positive algebraic sign.
• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.9 times rated current in phase to the measuring inputs of the relay (PF=1).
• The measured values for the active power „P“ must show a positive algebraic sign.
• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage
remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
www.eaton.com 433
IM02602009E EMR-4000
P<
• Feed rated voltage and 0.5 times rated current in phase to the measuring inputs of the relay (PF=1).
• The measured values for the active power „P“ must show a positive algebraic sign.
• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured.
• Feed rated voltage and 0.5 times rated current in phase to the measuring inputs of the relay (PF=1).
• The measured values for the active power „P“ must show a positive algebraic sign.
• In order to test the tripping delay feed, 0.5 times rated current to the measuring inputs of the relay.
Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and
voltage remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
Pr>
• Feed rated voltage and 0.9 times rated current with 180 degree phase angle between voltage and
current pointers to the measuring inputs of the relay.
• The measured values for the active power „P“ must show a negative algebraic sign.
• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.9 times rated current with 180 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „P“ must show a negative algebraic sign.
434 www.eaton.com
EMR-4000 IM02602009E
• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage
remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
Pr<
• Feed rated voltage and 0.5 times rated current with 180 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „P“ must show a negative algebraic sign.
• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.5 times rated current with 180 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „P“ must show a negative algebraic sign.
• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and
voltage remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
www.eaton.com 435
IM02602009E EMR-4000
This is the 32V device Reactive Power Protection setting. Each element can be set to one of five settings:
• Do Not Use;
• Over Forward Reactive Power (Q>);
• Under Forward Reactive Power (Q<);
• Over Reverse Reactive Power (Qr>); and
• Under Reverse Reactive Power (Qr<).
Each element consists of a Pickup and a Delay setting. These elements are based on rated apparent power
Van.
The following graphics show the areas that are protected by the corresponding modes.
Trip Region
Pickup Q>
No Trip
No Trip
Pickup Q<
Trip Region
436 www.eaton.com
EMR-4000 IM02602009E
P
No Trip
Pickup Qr>
Trip Region
Trip Region
Pickup Qr<
No Trip
www.eaton.com 437
438
IM02602009E
32V[1]...[n]
Name = 32V[1]...[n]
Name.Pickup
14
Loss of Potential Blo
active
www.eaton.com
Pickup Q<
Pickup Qr> OR
Pickup Qr<
Name.Mode
www.eaton.com 439
IM02602009E EMR-4000
440 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Power Protection
Trip Signal: Trip Power Protection
TripCmd Signal: Trip Command
www.eaton.com 441
IM02602009E EMR-4000
• Q>;
• Q<;
• Qr>; and
• Qr<.
Necessary means:
• Feed rated voltage and rated current to the measuring inputs of the relay.
If the measured values are shown with a negative (algebraic) sign, check
the wiring.
442 www.eaton.com
EMR-4000 IM02602009E
The examples shown within this chapter have to be carried out with the
tripping values and tripping delays that apply to the User's switchboard.
If the User is testing „greater than thresholds“ (e.g.: Q>), start at 80% of the
tripping value and increase the object to be tested until the relay picks up.
In case the User is testing „less than thresholds“ (e.g.: Q<), start at 120% of
the tripping value and reduce the object to be tested until the relay picks
up.
If the User is testing tripping delays of „greater than“ modules (e.g.: Q>),
start a timer simultaneously with an abrupt change of the object to be
tested from 80% of the tripping value to 120% of the tripping value.
If the User is testing tripping delays of „less than“ modules (e.g.: Q<), start
a timer simultaneously with an abrupt change of the object to be tested
from 120% of the tripping value to 80% of the tripping value.
Q>
• Feed rated voltage and 0.9 times rated current (90 degrees phase shift) to the measuring inputs of the
relay (PF=0).
• The measured values for the active power „Q“ must show a positive algebraic sign.
• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.9 times rated current (90 degree phase shift) to the measuring inputs of the
relay (PF=0).
• The measured values for the active power „Q“ must show a positive algebraic sign.
• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage
remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
www.eaton.com 443
IM02602009E EMR-4000
Q<
• Feed rated voltage and 0.5 times rated current (90 degree phase shift) to the measuring inputs of the
relay (PF=0).
• The measured values for the active power „Q“ must show a positive algebraic sign.
• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.5 times rated current (90 degree phase shift) to the measuring inputs of the
relay (PF=0).
• The measured values for the active power „Q“ must show a positive algebraic sign.
• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and
voltage remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
Qr>
• Feed rated voltage and 0.9 times rated current with -90 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „Q“ must show a negative algebraic sign.
• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.9 times rated current with -90 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
444 www.eaton.com
EMR-4000 IM02602009E
• The measured values for the active power „Q“ must show a negative algebraic sign.
• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay.
Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage
remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
Qr<
• Feed rated voltage and 0.5 times rated current with -90 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „Q“ must show a negative algebraic sign.
• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage
remains constant. Compare the measured pickup value to the configured value.
• Feed rated voltage and 0.5 times rated current with -90 degree phase shift between voltage and current
pointers to the measuring inputs of the relay.
• The measured values for the active power „Q“ must show a negative algebraic sign.
• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay.
Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and
voltage remains constant. Measure the tripping delay at the output of the relay.
The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-
cal Data section.
www.eaton.com 445
IM02602009E EMR-4000
The Apparent Power Factor is computed by dividing real power (watts) by volt-amperes. The apparent power
factor computation includes harmonics.
Watt
PF apparent =
VA
The Displacement Power Factor is computed by dividing the fundamental watts by the fundamental volt-
amperes as shown below. This definition is only valid at the system fundamental operating frequency. The
Displacement Power Factor isolates the fundamental portion of the Power Factor from the effects of harmonics.
Watt
PF displacement =
Watt 2var 2
These elements supervise the Power Factor within a defined area (limits).
Q
leading lagging
PF<0 PF>0
90°<phi<180° 0°<phi<90°
lagging leading
PF>0 PF<0
180°<phi<270° 270°<phi<360°
446 www.eaton.com
PF[1]...[n]
Name = PF[1]...[n]
Name.Pickup
14
RMS
EMR-4000
φ Name.PF Name .t
PF t Name.Trip
AND
0
www.eaton.com
Name.TripCmd
AND 15
V
<20%Vn
Name.Impossible
OR
OR
Imax
<0.5%In
447
IM02602009E EMR-4000
448 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 449
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Power Factor
Trip Signal: Trip Power Factor
TripCmd Signal: Trip Command
Compensator Signal: Compensation Signal
Impossible Signal: Pickup Power Factor Impossible
Necessary means:
• Feed the rated voltage and rated current to the measuring inputs of the relay.
If the measured values are shown with a negative (algebraic) sign, check
the wiring.
450 www.eaton.com
EMR-4000 IM02602009E
In this example, the PF-Trigger is set to 0.86 = 30° (lagging) and the PF-
Reset is set to 0.86 = 30° (leading).
Carry out the test with the settings (trigger and reset) that fit the
switchboard.
Testing the threshold values (Trigger) (PF Trigger: Example = 0.86 lagging):
• Feed the rated voltage and rated current in phase to the measuring inputs of the relay (PF=1).
• Adjust the angle between the voltage and current (current pointer lagging) until the relay picks up.
• Reduce the angle between voltage and current beyond PF = 1 (current pointer leading) until the alarm
drops off.
• Feed the rated voltage and rated current in phase to the measuring inputs of the relay (PF=1).
• Adjust the angle between voltage and current (current pointer lagging) with an abrupt change to
PF = 0.707 (45°) lagging.
• Measure the tripping delay at the output of the relay. Compare the measured tripping time to the
selected trip time.
The measured total tripping delays, threshold, and reset values correspond with those values specified in the ad-
justment list. Permissible deviations/tolerances can be found the Technical Data section.
By means of these elements, the protective device can detect and execute pickups and trips that are issued by
other external devices. This can be helpful, for logging purposes, if the other device is not equipped with an
event or disturbance recorder. This might also be helpful if the other device has no communication (SCADA)
interface.
www.eaton.com 451
452
IM02602009E
ExP[1]...[n]
Name = ExP[1]...[n]
EMR-4000
Name.Trip-I
www.eaton.com
and no active blocking
signals)
Name.Alarm Name.Alarm
AND 14
1..n, Assignment List
Name.Trip Name.Trip
AND
1..n, Assignment List
Name.TripCmd
Please Refer to Diagram: Trip Blockings AND 15
3 (Tripping command not deactivated or blocked. )
EMR-4000 IM02602009E
www.eaton.com 453
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Alarm Signal: Alarm
Trip Signal: Trip
TripCmd Signal: Trip Command
454 www.eaton.com
EMR-4000 IM02602009E
Necessary means:
Procedure:
Simulate the functionality of the External Protection (pickup, trip, and blockings) by (de-)energizing the digital
inputs.
All external pickups, external trips, and external blockings are correctly recognized and processed by the device.
www.eaton.com 455
IM02602009E EMR-4000
Supervision
Trigger Modes
There are three trigger modes for the breaker failure available. In addition, there are three assignable trigger
inputs available.
• All Trips: All trip signals that are assigned to this breaker (within the breaker manager) will start the BF
module.
• Current Trips: All current trips that are assigned to this breaker (within the breaker manager) will start the
BF module.
• External Trips: All external trips that are assigned to this breaker (within the breaker manager) will start
the BF module.
In addition, the User can also select none (e.g.: if the User intends to use one of the three additional assignable
trigger inputs).
Those trips can exclusively start the breaker failures that are assigned
within the breaker manager to the breaker that is to be supervised.
Select the winding side from which the measured currents should be taken
in case this protective device is a transformer differential protection.
456 www.eaton.com
BF
Name = BF
Trigger
All Trips
Current Trips
External Trips
BF.Pickup
15 15 15 All Trips
Current Trips
15 15 Name.t-BF
EMR-4000
www.eaton.com
OR
BF.Trigger1
BF.Trigger1-I
BF.Trigger2
BF.Trigger2-I
BF.Trigger3
BF.Trigger3-I
BF.Lockout
Name.I-BF > S 1
IA Res Lockout
R1 1
IB
AND
IC
IM02602009E
457
IM02602009E EMR-4000
• The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
• + The tripping delay of the device (please refer to the Technical Data
section);
458 www.eaton.com
EMR-4000 IM02602009E
I-BF > Current level that needs to exist after Trip 0.00 - 0.10In 0.00In [Protection Para
Command has been given. /<n>
/Supervision
/BF]
t-BF If the delay time is expired, an BF alarm is 0.00 - 10.00s 0.20s [Protection Para
given out. /<n>
/Supervision
/BF]
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
www.eaton.com 459
IM02602009E EMR-4000
Name Description
Pickup Signal: BF-Module Started (Pickup)
Trip Signal: Breaker Failure Trip
Lockout Signal: Lockout
Res Lockout Signal: Reset Lockout
Name Description
-.- No assignment
MStart.TripCmd Signal: Trip Command
50P[1].TripCmd Signal: Trip Command
50P[2].TripCmd Signal: Trip Command
50P[3].TripCmd Signal: Trip Command
51P[1].TripCmd Signal: Trip Command
51P[2].TripCmd Signal: Trip Command
51P[3].TripCmd Signal: Trip Command
50X[1].TripCmd Signal: Trip Command
50X[2].TripCmd Signal: Trip Command
51X[1].TripCmd Signal: Trip Command
51X[2].TripCmd Signal: Trip Command
50R[1].TripCmd Signal: Trip Command
50R[2].TripCmd Signal: Trip Command
51R[1].TripCmd Signal: Trip Command
51R[2].TripCmd Signal: Trip Command
27M[1].TripCmd Signal: Trip Command
27M[2].TripCmd Signal: Trip Command
59M[1].TripCmd Signal: Trip Command
59M[2].TripCmd Signal: Trip Command
27A[1].TripCmd Signal: Trip Command
27A[2].TripCmd Signal: Trip Command
59A[1].TripCmd Signal: Trip Command
59A[2].TripCmd Signal: Trip Command
46[1].TripCmd Signal: Trip Command
460 www.eaton.com
EMR-4000 IM02602009E
Name Description
46[2].TripCmd Signal: Trip Command
47[1].TripCmd Signal: Trip Command
47[2].TripCmd Signal: Trip Command
81[1].TripCmd Signal: Trip Command
81[2].TripCmd Signal: Trip Command
81[3].TripCmd Signal: Trip Command
81[4].TripCmd Signal: Trip Command
81[5].TripCmd Signal: Trip Command
81[6].TripCmd Signal: Trip Command
32[1].TripCmd Signal: Trip Command
32[2].TripCmd Signal: Trip Command
32[3].TripCmd Signal: Trip Command
32V[1].TripCmd Signal: Trip Command
32V[2].TripCmd Signal: Trip Command
32V[3].TripCmd Signal: Trip Command
PF-55D[1].TripCmd Signal: Trip Command
PF-55D[2].TripCmd Signal: Trip Command
PF-55A[1].TripCmd Signal: Trip Command
PF-55A[2].TripCmd Signal: Trip Command
ZI.TripCmd Signal: Zone Interlocking Trip Command
49.TripCmd Signal: Trip Command
50J[1].TripCmd Signal: Trip Command
50J[2].TripCmd Signal: Trip Command
37[1].TripCmd Signal: Trip Command
37[2].TripCmd Signal: Trip Command
37[3].TripCmd Signal: Trip Command
RTD.TripCmd Signal: Trip Command
ExP[1].TripCmd Signal: Trip Command
ExP[2].TripCmd Signal: Trip Command
ExP[3].TripCmd Signal: Trip Command
ExP[4].TripCmd Signal: Trip Command
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
www.eaton.com 461
IM02602009E EMR-4000
Name Description
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
462 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
www.eaton.com 463
IM02602009E EMR-4000
Name Description
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
464 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 465
IM02602009E EMR-4000
Name Description
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
466 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
www.eaton.com 467
IM02602009E EMR-4000
Name Description
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
468 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 469
IM02602009E EMR-4000
Name Description
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
Name Description
-.- No assignment
MStart.TripCmd Signal: Trip Command
50P[1].TripCmd Signal: Trip Command
50P[2].TripCmd Signal: Trip Command
50P[3].TripCmd Signal: Trip Command
51P[1].TripCmd Signal: Trip Command
51P[2].TripCmd Signal: Trip Command
51P[3].TripCmd Signal: Trip Command
50X[1].TripCmd Signal: Trip Command
50X[2].TripCmd Signal: Trip Command
51X[1].TripCmd Signal: Trip Command
51X[2].TripCmd Signal: Trip Command
50R[1].TripCmd Signal: Trip Command
50R[2].TripCmd Signal: Trip Command
51R[1].TripCmd Signal: Trip Command
51R[2].TripCmd Signal: Trip Command
27M[1].TripCmd Signal: Trip Command
27M[2].TripCmd Signal: Trip Command
59M[1].TripCmd Signal: Trip Command
59M[2].TripCmd Signal: Trip Command
27A[1].TripCmd Signal: Trip Command
470 www.eaton.com
EMR-4000 IM02602009E
Name Description
27A[2].TripCmd Signal: Trip Command
59A[1].TripCmd Signal: Trip Command
59A[2].TripCmd Signal: Trip Command
46[1].TripCmd Signal: Trip Command
46[2].TripCmd Signal: Trip Command
47[1].TripCmd Signal: Trip Command
47[2].TripCmd Signal: Trip Command
81[1].TripCmd Signal: Trip Command
81[2].TripCmd Signal: Trip Command
81[3].TripCmd Signal: Trip Command
81[4].TripCmd Signal: Trip Command
81[5].TripCmd Signal: Trip Command
81[6].TripCmd Signal: Trip Command
32[1].TripCmd Signal: Trip Command
32[2].TripCmd Signal: Trip Command
32[3].TripCmd Signal: Trip Command
32V[1].TripCmd Signal: Trip Command
32V[2].TripCmd Signal: Trip Command
32V[3].TripCmd Signal: Trip Command
PF-55D[1].TripCmd Signal: Trip Command
PF-55D[2].TripCmd Signal: Trip Command
PF-55A[1].TripCmd Signal: Trip Command
PF-55A[2].TripCmd Signal: Trip Command
ZI.TripCmd Signal: Zone Interlocking Trip Command
49.TripCmd Signal: Trip Command
50J[1].TripCmd Signal: Trip Command
50J[2].TripCmd Signal: Trip Command
37[1].TripCmd Signal: Trip Command
37[2].TripCmd Signal: Trip Command
37[3].TripCmd Signal: Trip Command
RTD.TripCmd Signal: Trip Command
ExP[1].TripCmd Signal: Trip Command
ExP[2].TripCmd Signal: Trip Command
ExP[3].TripCmd Signal: Trip Command
ExP[4].TripCmd Signal: Trip Command
www.eaton.com 471
IM02602009E EMR-4000
Name Description
-.- No assignment
ExP[1].TripCmd Signal: Trip Command
ExP[2].TripCmd Signal: Trip Command
ExP[3].TripCmd Signal: Trip Command
ExP[4].TripCmd Signal: Trip Command
The time that is configured for the BF MUST NOT be below the breaker
control time, otherwise an unwanted operation of the BF is caused by any
protective trip.
Object to Be Tested:
Necessary Means:
• Current source;
• Current meter; and
• Timer.
When testing, the applied test current must always be higher than the
tripping threshold »I-BF«. If the test current falls below the threshold while
the breaker is in the “Off” position, no pickup will be generated.
Procedure (Single-Phase):
For testing the tripping time of the BF protection, a test current has to be higher than the threshold value of one
of the current protection modules that are assigned to trigger the BF protection. The BF trip delay can be
measured from the time when one of the triggering inputs becomes active to the time when the BF protection trip
is asserted.
To avoid wiring errors, checked to make sure the breaker in the upstream system switches off.
The time, measured by the timer, should be in line with the specified tolerances.
The actual times measured comply with the set-point times. The breaker in the higher-level section switches off.
472 www.eaton.com
EMR-4000 IM02602009E
Most functions of metering, protection, and control in the relay rely on correct current measurements. It is
important to make sure the CT connections and their operations are correct. The failures (including CT
secondary wire broken, insulation broken down, broken wiring between CT and relay, and mismatched
polarities) will cause the incorrect current measurements. The other CT errors (due to the magnetizing current
that is proportional to the primary current, CT saturation, and measuring circuit and quantization error) can also
cause inaccurate current measurements.
The CTS utilizes the Kirchhoff’s current law to detect a CT failure and can differentiate the wiring errors from the
measurement errors by adding biases to offset the measurement related errors. The biases include two terms,
one of which is related to the static error that accounts for CT magnetizing characteristic differences and current
measurement circuit calibration errors and other is the dynamic error that is proportional to the measured
maximum current due to CT transformation characteristics. The CTs are assumed to be used in the wye-
grounded winding sides. Under normal conditions, the mismatch between the calculated and the measured zero
sequence current should be less than the bias value. However, if there is a CT wiring error, such relationship
will not hold true. If the mismatch exceeds the bias for a specified time, an alarm will be generated.
KI is the ratio of the ground CT ratio over the phase CT ratio, and it is automatically calculated from the rated
system parameters.
∆I = The static error, a minimum mismatch allowed between the calculated and measured zero
sequence current.
Kd = The dynamic error factor, a restrain slope that defines a percentage error generated by a
high current.
Imax = maximum phase current.
Total bias value = ∆I + Kd x Imax.
Limit Value
Kd*Imax
Imax
If the current is measured in two phases only (for example only IA/IB) or if
there is no separate ground current measuring (e.g.: normally via a zero
sequence CT), the supervision function should be deactivated.
www.eaton.com 473
474
IM02602009E
CTS
IA
www.eaton.com
IB IX
Calculated CTS.
IC I
Kd
CTS.t
+ t CTS.Pickup
AND
Σ 0 40
Phase or Ground Current Transformer Failure
IX
EMR-4000 IM02602009E
www.eaton.com 475
IM02602009E EMR-4000
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Pickup Signal: Pickup Current Transformer Measuring Circuit Supervision
Preconditions:
1.Measurement of all three-phase currents (are applied to the measuring
inputs of the device).
2.The ground current is detected via a zero sequence transformer (not in
residual connection).
Object to Be Tested:
Check of the CT Supervision (by comparing the calculated with the measured ground current).
Necessary Means:
Procedure, Part 1:
476 www.eaton.com
EMR-4000 IM02602009E
Procedure, Part 2:
• Feed a three-phase, symmetrical current system (approx. nominal current) to the secondary side.
• Feed a current that is higher than the threshold value for the measuring circuit supervision to the ground
current measuring input.
• Make sure that the »CTS.ALARM« signal is generated.
The trip circuit monitoring is used for monitoring if the trip circuit is ready for opening operations. The monitoring
can be fulfilled by two ways. The first assumes only 52a is used in the trip circuit. The second assumes that, in
addition to 52a, 52b is also used for the circuit monitoring. Two options either 52a only (or breaker closed) or
both (52a and 52b) are provided for the User to select based on use of the breaker status in the trip circuit. With
52a only in the trip circuit, the monitoring is only effective when the breaker is closed while if both 52a and 52b
are used, the trip circuit will be monitored all time as long as the control power is on.
The trip circuit continuity is monitored through the digital inputs DI1 and DI2, and the breaker status 52a or 52b
or both must be monitored through the other digital inputs. Note that the digital inputs used for this purpose
must be configured properly based on the trip circuit control voltage and also that the de-bouncing times must be
set to minimum. If the trip circuit is detected broken, an alarm will be issued with a specified delay, which must
be greater than a period from the time when a trip contact is closed to the time when the breaker status is clearly
recognized by the relay.
In Slot 1 has two digital inputs, each of which has a separate root (contact
separation) for the trip circuit supervision.
In this case, the trip circuit supply voltage serves also as supply voltage for the digital inputs and so the supply
voltage failure of a trip circuit can be detected directly.
In order to identify a conductor failure in the trip circuit on the supply line or in the trip coil, the off-coil has to be
looped-in to the supervision circuit.
The time delay is to be set in a way that switching actions cannot cause false trips in this module.
www.eaton.com 477
IM02602009E EMR-4000
- DC
X1
1 PE TC
2 V+
3 V-
52a 52b
4
COM1 5 Trip
DI1 6
+DC
COM2 7
DI2 8
9
10
11
12
W1-52a
13
W1-52b
14
15
16
17
18
DI-Threshold
X1
6 AND
5
t-TCM
TCM.Pickup
t
OR
0
DI-Threshold
X1
8 AND
7
478 www.eaton.com
EMR-4000 IM02602009E
Trip Circuit Monitoring for One Breaker: Auxiliary Contacts (52a Only) in Trip Circuit.
- DC
X1
1 PE TC
2 V+
3 V-
52a 52b
4
COM1 5 Trip
DI1 6
+DC
7
8
9
10
11
12
W1-52a
13
W1-52b
14
15
16
17
18 52a only in Trip Circuit
DI-Threshold
X1
6 t-TCM
TCM.Pickup
5 AND
t
Bkr.Pos CLOSE
www.eaton.com 479
IM02602009E EMR-4000
480 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Pickup Signal: Pickup Trip Circuit Supervision
Not Possible Not possible because no state indicator assigned to the breaker.
For breakers that trip by means of little energy (e.g.: via an optocoupler), it
has to be ensured that the current applied by the digital inputs will not
cause false tripping of the breaker.
Object to Be Tested:
Test of the trip circuit monitoring (with 52a and 52b contact).
Procedure, Part 1:
Simulate failure of the control voltage in the power circuits.
Procedure, Part 2:
Simulate a broken cable in the breaker control circuit.
LOP function detects the loss of voltage in any of the voltage input measuring circuits and uses the following
measured values and information to detect an LOP condition:
• Three-phase voltages;
www.eaton.com 481
IM02602009E EMR-4000
• Three-phase currents;
• Breaker status
Once an LOP condition is detected and it lasts longer than an adjustable minimum pickup time, the LOP Pickup
will be set. The LOP Block will only be set if the LOP-Block control setting is set to enabled (activated). The
LOP Pickup and LOP Block signals can both be used as logical signal to block the protective functions which
use the voltage information such as voltage restraint. The minimum pickup timer is used to prevent short time
incorrect operation of the LOP function during breaker switching-on operation.
482 www.eaton.com
LOP[1]...[n] Name = LOP
Inactive
Active
V < 1.0 V
VA/VAB
VB/VBC OR
VC/VCA
Name.Pickup
%(V2/V1) > 40%
%(V2/V1)
0.0 9999 s
OR 100 ms
t-Pickup
S Q 0
Name.LOP Blo
AND 0 AND 38
V0 < 1.0 V
t-ResetDelay
R
V0
EMR-4000
50 ms
www.eaton.com
AND
IA
IB AND
IC
3*I0
483
IM02602009E EMR-4000
484 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Pickup Signal: Pickup Loss of Potential
LOP Blo Signal: Loss of Potential blocks other elements
Ex FF VT Signal: Ex FF VT
Ex FF GVT Signal: Alarm Fuse Failure Ground Voltage Transformers
Necessary means:
Procedure part 1:
Examine if the output signals »LOP BLO « (200ms delay) and »LOP« only become true if:
www.eaton.com 485
IM02602009E EMR-4000
The output signals only become true if all the above mentioned conditions are fulfilled.
Procedure part 2:
Assign the »LOP« or »LOP BLO« output signals to all protection element that should be blocked by LOP (e.g.:
Undervoltage Protection, Voltage Restraint...).
Test if those elements are blocked if the LOP modules issue a blocking signal.
All elements that should be blocked in case of LOP are blocked if the conditions (Procedure part 1) are fulfilled.
Self Supervision
The System-OK contact (SC relay, life-contact) cannot be configured. The system contact is a Form “C” contact
that picks up when the device is free from internal faults. While the device is booting up, the System OK relay
(SC) remains dropped-off (unenergized). As soon as the system is properly started (and protection is active),
the System Contact picks up and the System LED is activated accordingly.
The devices are continuously monitored and supervised by different methods during normal operation as well as
during the start-up phase.
In case of failures that cannot be corrected immediately, 3 restarts within 20 minutes are accepted before the
device will be deactivated. In such a case, the device should be removed for service to ensure continuous
correct operation. The Eaton Customer Service contact information and address can be found at the front of this
manual.
In case of any failures, the recorders of the device should be left untouched to ensure an easy diagnosis and
proper repair at the factory. Besides the records and visible indications to the customer, there is internal
information about failures. These allow Eaton service personnel at the repair facility to make a detailed analysis
486 www.eaton.com
EMR-4000 IM02602009E
Self supervision is applied by different functions at different cyclic or non-cyclic timings to the following parts and
functions of the device:
Faultless cyclic operation of the software is supervised by timing analysis and checking results of different
functions. Errors of the software (watchdog function) lead to restarting the device and switching off the System-
OK contact (life contact). In addition, the “System-OK” LED will blink red after 3 unsuccessful attempts to restart
the device within a time period of 20 minutes.
The main processor cyclically monitors the operation of the signal processor and initiates corrective actions or
restart of the device in case of faulty operation. Data and files are generally secured against unintended
overwriting or faulty changes by check-sums.
The measuring unit continuously checks the measured data by comparing received data with data from a
second channel sampled in parallel.
The auxiliary voltage is monitored continuously. If the voltage of one of the different supply circuits falls below a
certain threshold, a restart of the device is initiated. If the voltage staggers around the threshold, the device also
starts again after several seconds. Additionally the level of all internal supply voltage groups are continuously
monitored.
Independent of these separate monitoring functions, the intermediate voltage circuit is buffered until all important
and relevant operational and fault-data have been saved and the device initiates a restart.
The reboot will also be logged within the event recorder. Rebooting causes an event named “Sys.Reboot”.
Error Messages/Codes
1. Reboot after clean switching off of the device - Normal reboot after clean shut-down of the
device.
2. Reboot by User command - User-initiated reboot through panel command.
3. Super reset - Reset to factory settings.
4. Restart by debugger - Eaton internally for system-analysis purposes.
5. Restart because of configuration changes.
6. General failure - Reboot without definite reason.
7. Reboot by “SW-system abort” (HOST-side) - Summary of several reboot reasons detected by the
software (i.e.: wrong pointer, corrupted files, etc.).
8. Reboot by watchdog timeout (HOST-side) - Signaling if the protection-class-task hangs.
9. Reboot by system abort (DSP-side) - Summary of several reboot reasons detected by software
(i.e.: wrong pointer, DSP-side).
www.eaton.com 487
IM02602009E EMR-4000
Error Messages/Codes
10. Reboot by watchdog timeout (DSP-side) - Appears when DSP sequence needs too long for one
cycle.
11. Loss of auxiliary voltage or low voltage reboot after loss of auxiliary voltage or voltage dropping
below reboot level but not becoming zero.
12. Faulty memory access - Message of MMU (memory mapping unit) that prohibited memory
access has occurred.
488 www.eaton.com
EMR-4000 IM02602009E
Programmable Logic
Available Elements (Equations):
Logic
General Description
The protective device includes programmable logic equations for programming inputs, outputs, blocking of
protective functions, and custom logic functions in the relay.
The logic provides control of the relay output contacts based on the state of the inputs that can be chosen from
the assignment list (protective function pickups, protective function states, breaker states, system alarms, and
module inputs). The User can use the output signals of a logic equation as inputs in higher equations (e.g.: the
output signal of logic equation 10 might be used as an input of logic equation 11).
Principle Overview.
Type of logic gate selectable Gate Out
Delay Timer
IN2 Inverting settable AND
OR Set Out
t-On Delay Inverting settable Q
S
NAND
If no signal is assigned to a logic gate (All inputs are "0"), then the output of the gate will be set as follows:
If at least one input signal is assigned to a gate all not assigned inputs are set to:
www.eaton.com 489
490
IM02602009E
LE[1]...[n]
LE[x].IN1
Active Gate
Timer Out
Inactive
AND
LE[x].IN2
OR
1..n, Assignment List
XOR NAND
Inverting2
Detailed Overview – Overall Logic Diagram.
Active
NOR
Inactive Delay Timer
LE[x].IN3 φ
1..n, Assignment List
t-On Delay
EMR-4000
AND
XOR OR Out
Inverting3
NAND t-Off Delay XOR S Q
Active NOR Out inverted
Inactive R Q
www.eaton.com
LE[x].IN4
Inverting Set
XOR
Inverting4
Active
Active
Inactive
Inactive
LE[x].Reset Latched
XOR
Inverting Reset
Active
Inactive
EMR-4000 IM02602009E
Gate
AND AND OR OR
Input Signals
The User can assign up to four Input signals (from the assignment list) to the inputs of the gate.
Latching
The timer issues two signals: an unlatched and a latched signal. The latched output can optionally be inverted.
In order to reset the latched signal, the User has to assign a reset signal from the assignment list. Optionally,
the reset signal can also be inverted.
If no »Reset Latched« signal is assigned, then the »LATCH OUT «signal will be identical with the »TIMER OUT «
signal.
Cascading in an ascending sequence means that the User utilizes the output signal of “Logic Equation n” as
input of “Logic Equation n+1”. If the state of “Logic Equation n” changes, the state of the output of “Logic
Equation n+1” will be updated within the same cycle.
Cascading in a descending sequence means that the User utilizes the output signal of “Logic Equation n+1” as
input of “Logic Equation n”. If the output of “Logic Equation n+1” changes, this change of the feed back signal at
the input of “Logic Equation n” will be delayed for one cycle.
www.eaton.com 491
IM02602009E EMR-4000
LE2.IN2
LE1.IN4
Output of Logic Equation 2
Logic Equation2
LE2.IN3
LE2.IN4
LE1.IN1
LE2.IN2
LE1.IN4
Output of Logic Equation 2
Logic Equation2
LE2.IN3
LE3.IN2
LE2.IN4
Output of Logic Equation 3
Logic Equation3
LE3.IN3
LE3.IN4
Cascading in Descending Order
LE2.IN1
Update within the same evaluation cycle
LE1.IN2
LE2.IN4
Output of Logic Equation1
Logic Equation1
LE1.IN3
LE1.IN4
LE3.IN1
LE2.IN2 Update within the next but one evaluation cycle (2 cycles
delay)
LE3.IN4
Output of Logic Equation 2
Logic Equation2
LE2.IN3
LE1.IN2
LE2.IN4
Output of Logic Equation 1
Logic Equation1
LE1.IN3
LE1.IN4
492 www.eaton.com
EMR-4000 IM02602009E
Do not use logic equations unless the User can ensure the safe
functionality.
• Within the Device Planning, set the number of required Logic Equations.
• If the latched output signal is used, assign a reset signal to the reset input.
• Within the »status display«, the User can check the status of the logical inputs and outputs of the logic
equation.
In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of
descending sequences (Please refer to the Cascading Logical Outputs section).
By means of the Status Display [Operation/Status Display], the logical states can be verified.
Do not use logic equations unless the User can ensure the safe
functionality.
• Within the Device Planning, set the number of required Logic Equations.
www.eaton.com 493
IM02602009E EMR-4000
• If the latched output signal is used, assign a reset signal to the reset input.
• Within the »status display«, the User can check the status of the logical inputs and outputs of the logic
equation.
In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of
descending sequences (Please refer to section: Cascading Logical Outputs).
By means of the Status Display [Operation/Status Display], the logical states can be verified.
Name Description
-.- No assignment
Prot.Active Signal: Active
Prot.Available Signal: Protection is available.
Prot.I dir fwd Signal: Phase current failure forward direction
Prot.I dir n poss Signal: Phase fault - missing reference voltage
Prot.I dir rev Signal: Phase current failure reverse direction
Prot.IR dir fwd Signal: IR Ground fault (calculated) forward
Prot.IR dir n poss Signal: IR Ground fault (calculated) direction detection not possible
Prot.IR dir rev Signal: IR Ground fault (calculated) reverse direction
Prot.IX dir fwd Signal: IX Ground fault (measured) forward
Prot.IX dir n poss Signal: IX Ground fault (measured) direction detection not possible
Prot.IX dir rev Signal: IX Ground fault (measured) reverse direction
Prot.Pickup Signal: General Pickup
Prot.Trip Signal: General Trip
Bkr.SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary
contact (pole) only. Thus indeterminate and disturbed Positions
cannot be detected.
Bkr.Pos not CLOSE Signal: Pos not CLOSE
Bkr.Pos CLOSE Signal: Breaker is in CLOSE-Position
Bkr.Pos OPEN Signal: Breaker is in OPEN-Position
Bkr.Pos Indeterm Signal: Breaker is in Indeterminate Position
494 www.eaton.com
EMR-4000 IM02602009E
Name Description
Bkr.Pos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-
back signals (Position Indicators) contradict themselves. After
expiring of a supervision timer this signal becomes true.
Bkr.Ready Signal: Breaker is ready for operation.
Bkr.Interl CLOSE Signal: One or more IL_Close inputs are active.
Bkr.Interl OPEN Signal: One or more IL_Open inputs are active.
Bkr.CES succesf Command Execution Supervision: Switching command executed
successfully.
Bkr.CES Disturbed Command Execution Supervision: Switching Command
unsuccessful. Switchgear in disturbed position.
Bkr.CES Fail TripCmd Command Execution Supervision: Trip command not executed.
Bkr.CES SwitchgDir Command Execution Supervision respectively Switching Direction
Control: This signal becomes true, if a switch command is issued
even though the switchgear is already in the requested position.
Example: A switchgear that is already OPEN should be switched
OPEN again (doubly). The same applies to CLOSE commands.
Bkr.CES CLOSE d OPEN Command Execution Supervision: CLOSE Command during a
pending OPEN Command.
Bkr.CES SG not ready Command Execution Supervision: Switchgear not ready
Bkr.CES Field Interl Command Execution Supervision: Switching Command not
executed because of field interlocking.
Bkr.Prot CLOSE Signal: CLOSE command issued by the Prot module
Bkr.TripCmd Signal: Trip Command
Bkr.Ack TripCmd Signal: Acknowledge Trip Command
Bkr.Bwear Slow Breaker Signal: Slow Breaker Alarm
Bkr.Res Bwear Sl Breaker Signal: Resetting the slow breaker alarm
Bkr.CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on
the setting the signal may include the CLOSE command of the
Prot module.
Bkr.OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on
the setting the signal may include the OPEN command of the Prot
module.
Bkr.CLOSE Cmd manual Signal: CLOSE Cmd manual
Bkr.OPEN Cmd manual Signal: OPEN Cmd manual
MStart.Start Pickup Signal: Pickup
MStart.Trip Signal: Trip
MStart.TripCmd Signal: Trip Command
MStart.Stop Signal: Motor is in stop mode
MStart.Start Signal: Motor is in start mode
MStart.Run Signal: Motor is in run mode
MStart.Blo Signal: Motor is blocked for starting or transition to Run mode
MStart.I_Transit Signal: Current transition signal
MStart.T_Transit Signal: Time transition signal
www.eaton.com 495
IM02602009E EMR-4000
Name Description
MStart.NOCSBlocked Signal: Motor is prohibited to start due to number of cold start
limits
MStart.SPHBlocked Signal: Motor is prohibited to start due to starts per hour limits
MStart.SPHBlockAlarm Signal: Motor is prohibited to start due to starts per hour limits,
would come active in the next stop
MStart.TBSBlocked Signal: Motor is prohibited to start due to time between starts limits
MStart.ThermalBlock Signal: Thermal block
MStart.RemBlockStart Signal: Motor is prohibited to start due to external blocking through
digital input DI
MStart.TransitionTrip Signal: Start transition fail trip
MStart.ZSSTrip Signal: Zero speed trip (possible locked rotor)
MStart.INSQSP2STFaill Signal: Fail to transit from stop to start based on reported back
time
MStart.INSQSt2RunFail Signal: Fail to transit from start to run based on reported back time
MStart.LATBlock Signal: Long acceleration timer enforced
MStart.ColdStartSeq Signal: Motor cold start sequence flag
MStart.ForcedStart Signal: Motor being forced to start
MStart.TripPhaseReverse Signal: Relay tripped because of phase reverse detection
MStart.EmergOverrideDI Signal: Emergency override start blocking through digital input DI
MStart.EmergOverrideUI Signal: Emergency override start blocking through front panel
MStart.ABKActive Signal: Anti-backspin is active. For certain applications, such as
pumping a fluid up a pipe, the motor may be driven backward for a
period of time after it stops. The anti-backspin timer prevents
starting the motor while it is spinning in the reverse direction.
MStart.StartMotorCmd Signal: Start motor command
MStart.MotorStopBlo Signal: Motor stop block other protection functions
50P[1].Pickup Signal: Pickup
50P[1].Trip Signal: Trip
50P[1].TripCmd Signal: Trip Command
50P[2].Pickup Signal: Pickup
50P[2].Trip Signal: Trip
50P[2].TripCmd Signal: Trip Command
50P[3].Pickup Signal: Pickup
50P[3].Trip Signal: Trip
50P[3].TripCmd Signal: Trip Command
51P[1].Pickup Signal: Pickup
51P[1].Trip Signal: Trip
51P[1].TripCmd Signal: Trip Command
51P[2].Pickup Signal: Pickup
51P[2].Trip Signal: Trip
51P[2].TripCmd Signal: Trip Command
496 www.eaton.com
EMR-4000 IM02602009E
Name Description
51P[3].Pickup Signal: Pickup
51P[3].Trip Signal: Trip
51P[3].TripCmd Signal: Trip Command
50X[1].Pickup Signal: Pickup IX or IR
50X[1].Trip Signal: Trip
50X[1].TripCmd Signal: Trip Command
50X[2].Pickup Signal: Pickup IX or IR
50X[2].Trip Signal: Trip
50X[2].TripCmd Signal: Trip Command
51X[1].Pickup Signal: Pickup IX or IR
51X[1].Trip Signal: Trip
51X[1].TripCmd Signal: Trip Command
51X[2].Pickup Signal: Pickup IX or IR
51X[2].Trip Signal: Trip
51X[2].TripCmd Signal: Trip Command
50R[1].Pickup Signal: Pickup IX or IR
50R[1].Trip Signal: Trip
50R[1].TripCmd Signal: Trip Command
50R[2].Pickup Signal: Pickup IX or IR
50R[2].Trip Signal: Trip
50R[2].TripCmd Signal: Trip Command
51R[1].Pickup Signal: Pickup IX or IR
51R[1].Trip Signal: Trip
51R[1].TripCmd Signal: Trip Command
51R[2].Pickup Signal: Pickup IX or IR
51R[2].Trip Signal: Trip
51R[2].TripCmd Signal: Trip Command
27M[1].Pickup Signal: Pickup Voltage Element
27M[1].Trip Signal: Trip
27M[1].TripCmd Signal: Trip Command
27M[2].Pickup Signal: Pickup Voltage Element
27M[2].Trip Signal: Trip
27M[2].TripCmd Signal: Trip Command
59M[1].Pickup Signal: Pickup Voltage Element
59M[1].Trip Signal: Trip
59M[1].TripCmd Signal: Trip Command
59M[2].Pickup Signal: Pickup Voltage Element
59M[2].Trip Signal: Trip
59M[2].TripCmd Signal: Trip Command
www.eaton.com 497
IM02602009E EMR-4000
Name Description
27A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element
27A[1].Trip Signal: Trip
27A[1].TripCmd Signal: Trip Command
27A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element
27A[2].Trip Signal: Trip
27A[2].TripCmd Signal: Trip Command
59A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element
59A[1].Trip Signal: Trip
59A[1].TripCmd Signal: Trip Command
59A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element
59A[2].Trip Signal: Trip
59A[2].TripCmd Signal: Trip Command
46[1].Pickup Signal: Pickup Negative Sequence
46[1].Trip Signal: Trip
46[1].TripCmd Signal: Trip Command
46[2].Pickup Signal: Pickup Negative Sequence
46[2].Trip Signal: Trip
46[2].TripCmd Signal: Trip Command
47[1].Pickup Signal: Pickup Voltage Asymmetry
47[1].Trip Signal: Trip
47[1].TripCmd Signal: Trip Command
47[2].Pickup Signal: Pickup Voltage Asymmetry
47[2].Trip Signal: Trip
47[2].TripCmd Signal: Trip Command
81[1].Pickup Signal: Pickup Frequency Protection (collective signal)
81[1].Pickup 81 Signal: Pickup Frequency Protection
81[1].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[1].Pickup Vector Surge Signal: Pickup Vector Surge
81[1].Trip Signal: Trip Frequency Protection (collective signal)
81[1].TripCmd Signal: Trip Command
81[1].Trip 81 Signal: Frequency has exceeded the limit.
81[1].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[1].Trip Vector Surge Signal: Trip delta phi
81[2].Pickup Signal: Pickup Frequency Protection (collective signal)
81[2].Pickup 81 Signal: Pickup Frequency Protection
81[2].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[2].Pickup Vector Surge Signal: Pickup Vector Surge
81[2].Trip Signal: Trip Frequency Protection (collective signal)
498 www.eaton.com
EMR-4000 IM02602009E
Name Description
81[2].TripCmd Signal: Trip Command
81[2].Trip 81 Signal: Frequency has exceeded the limit.
81[2].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[2].Trip Vector Surge Signal: Trip delta phi
81[3].Pickup Signal: Pickup Frequency Protection (collective signal)
81[3].Pickup 81 Signal: Pickup Frequency Protection
81[3].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[3].Pickup Vector Surge Signal: Pickup Vector Surge
81[3].Trip Signal: Trip Frequency Protection (collective signal)
81[3].TripCmd Signal: Trip Command
81[3].Trip 81 Signal: Frequency has exceeded the limit.
81[3].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[3].Trip Vector Surge Signal: Trip delta phi
81[4].Pickup Signal: Pickup Frequency Protection (collective signal)
81[4].Pickup 81 Signal: Pickup Frequency Protection
81[4].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[4].Pickup Vector Surge Signal: Pickup Vector Surge
81[4].Trip Signal: Trip Frequency Protection (collective signal)
81[4].TripCmd Signal: Trip Command
81[4].Trip 81 Signal: Frequency has exceeded the limit.
81[4].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[4].Trip Vector Surge Signal: Trip delta phi
81[5].Pickup Signal: Pickup Frequency Protection (collective signal)
81[5].Pickup 81 Signal: Pickup Frequency Protection
81[5].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[5].Pickup Vector Surge Signal: Pickup Vector Surge
81[5].Trip Signal: Trip Frequency Protection (collective signal)
81[5].TripCmd Signal: Trip Command
81[5].Trip 81 Signal: Frequency has exceeded the limit.
81[5].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[5].Trip Vector Surge Signal: Trip delta phi
81[6].Pickup Signal: Pickup Frequency Protection (collective signal)
81[6].Pickup 81 Signal: Pickup Frequency Protection
81[6].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[6].Pickup Vector Surge Signal: Pickup Vector Surge
81[6].Trip Signal: Trip Frequency Protection (collective signal)
www.eaton.com 499
IM02602009E EMR-4000
Name Description
81[6].TripCmd Signal: Trip Command
81[6].Trip 81 Signal: Frequency has exceeded the limit.
81[6].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[6].Trip Vector Surge Signal: Trip delta phi
32[1].Pickup Signal: Pickup Power Protection
32[1].Trip Signal: Trip Power Protection
32[1].TripCmd Signal: Trip Command
32[2].Pickup Signal: Pickup Power Protection
32[2].Trip Signal: Trip Power Protection
32[2].TripCmd Signal: Trip Command
32[3].Pickup Signal: Pickup Power Protection
32[3].Trip Signal: Trip Power Protection
32[3].TripCmd Signal: Trip Command
32V[1].Pickup Signal: Pickup Power Protection
32V[1].Trip Signal: Trip Power Protection
32V[1].TripCmd Signal: Trip Command
32V[2].Pickup Signal: Pickup Power Protection
32V[2].Trip Signal: Trip Power Protection
32V[2].TripCmd Signal: Trip Command
32V[3].Pickup Signal: Pickup Power Protection
32V[3].Trip Signal: Trip Power Protection
32V[3].TripCmd Signal: Trip Command
PF-55D[1].Pickup Signal: Pickup Power Factor
PF-55D[1].Trip Signal: Trip Power Factor
PF-55D[1].TripCmd Signal: Trip Command
PF-55D[2].Pickup Signal: Pickup Power Factor
PF-55D[2].Trip Signal: Trip Power Factor
PF-55D[2].TripCmd Signal: Trip Command
PF-55A[1].Pickup Signal: Pickup Power Factor
PF-55A[1].Trip Signal: Trip Power Factor
PF-55A[1].TripCmd Signal: Trip Command
PF-55A[2].Pickup Signal: Pickup Power Factor
PF-55A[2].Trip Signal: Trip Power Factor
PF-55A[2].TripCmd Signal: Trip Command
ZI.Ground OUT Signal: Zone Interlocking Ground OUT
ZI.Ground Pickup Signal: Zone Interlocking Ground Pickup
ZI.Ground Trip Signal: Zone Interlocking Ground Trip
ZI.IN Signal: Zone Interlocking IN
ZI.OUT Signal: Zone Interlocking OUT
500 www.eaton.com
EMR-4000 IM02602009E
Name Description
ZI.Phase OUT Signal: Zone Interlocking Phase OUT
ZI.Phase Pickup Signal: Zone Interlocking Phase Pickup
ZI.Phase Trip Signal: Zone Interlocking Phase Trip
ZI.Pickup Signal: Pickup Zone Interlocking
ZI.Trip Signal: Zone Interlocking Trip
ZI.TripCmd Signal: Zone Interlocking Trip Command
49.Pickup Signal: Pickup
49.Trip Signal: Trip
49.TripCmd Signal: Trip Command
50J[1].Pickup Signal: Pickup
50J[1].Trip Signal: Trip
50J[1].TripCmd Signal: Trip Command
50J[2].Pickup Signal: Pickup
50J[2].Trip Signal: Trip
50J[2].TripCmd Signal: Trip Command
37[1].Pickup Signal: Pickup
37[1].Trip Signal: Trip
37[1].TripCmd Signal: Trip Command
37[2].Pickup Signal: Pickup
37[2].Trip Signal: Trip
37[2].TripCmd Signal: Trip Command
37[3].Pickup Signal: Pickup
37[3].Trip Signal: Trip
37[3].TripCmd Signal: Trip Command
MLS.Pickup Signal: Pickup
MLS.Trip Signal: Trip
RTD.Alarm Alarm RTD Temperature Protection
RTD.Trip Signal: Trip
RTD.TripCmd Signal: Trip Command
SOTF.Active Signal: Active
SOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to
modify Overcurrent Protection Settings.
SOTF.I< Signal: No Load Current.
ExP[1].Alarm Signal: Alarm
ExP[1].Trip Signal: Trip
ExP[1].TripCmd Signal: Trip Command
ExP[2].Alarm Signal: Alarm
ExP[2].Trip Signal: Trip
ExP[2].TripCmd Signal: Trip Command
www.eaton.com 501
IM02602009E EMR-4000
Name Description
ExP[3].Alarm Signal: Alarm
ExP[3].Trip Signal: Trip
ExP[3].TripCmd Signal: Trip Command
ExP[4].Alarm Signal: Alarm
ExP[4].Trip Signal: Trip
ExP[4].TripCmd Signal: Trip Command
BF.Lockout Signal: Lockout
BF.Pickup Signal: BF-Module Started (Pickup)
BF.Trip Signal: Breaker Failure Trip
TCM.Not Possible Not possible because no state indicator assigned to the breaker.
TCM.Pickup Signal: Pickup Trip Circuit Supervision
CTS.Pickup Signal: Pickup Current Transformer Measuring Circuit Supervision
LOP.Pickup Signal: Pickup Loss of Potential
Wired Inputs.52a M1-I State of the module input: Main 1 Breaker Closed
Wired Inputs.52b M1-I State of the module input: Main 1 Breaker Open
Wired Inputs.TOCa M1-I State of the module input: Main 1 Breaker Connected
Wired Inputs.43/10 M1-I State of the module input: Main 1 Breaker Selected To Trip
Wired Inputs.52a M2-I State of the module input: Main 2 Breaker Closed
Wired Inputs.52b M2-I State of the module input: Main 2 Breaker Open
Wired Inputs.TOCa M2-I State of the module input: Main 2 Breaker Connected
Wired Inputs.43/10 M2-I State of the module input: Main 2 Breaker Selected To Trip
Wired Inputs.52a T -I State of the module input: Tie Breaker Closed
Wired Inputs.52b T-I State of the module input: Tie Breaker Open
Wired Inputs.TOCa T-I State of the module input: Tie Breaker Connected
Wired Inputs.43/10 T-I State of the module input: Tie Breaker Selected To Trip
Wired Inputs.43 M-I State of the module input: System In Manual
Wired Inputs.43 A-I State of the module input: System in Auto
Wired Inputs.43 P1-I State of the module input: Preferred Source 1
Wired Inputs.43 P2-I State of the module input: Preferred Source 2
Wired Inputs.Bkr Trouble-I Breaker Trouble
Wired Inputs.MainCont-I State of the module input: Main Contactor
Wired Inputs.StartCont-I State of the module input: Starting Contactor
Wired Inputs.RunCont-I State of the module input: Running Contactor (inc sequence)
Wired Inputs.Start -I State of the module input: Start
Wired Inputs.Stop-I State of the module input: Stop
Wired Inputs.ExtPer1-I State of the module input: $$
(External_Signals_External_Permissive_h)
Wired Inputs.ExtPer2-I State of the module input: $$
(External_Signals_External_Permissive_h)
Wired Inputs.ExtTip1-I State of the module input: External Trip1
502 www.eaton.com
EMR-4000 IM02602009E
Name Description
Wired Inputs.ExtTip-I2 State of the module input: External Trip2
Wired Inputs.Forward-I State of the module input: Forward
Wired Inputs.Reverse-I State of the module input: Reverse
Wired Inputs.GrpSetSelect-I State of the module input: Group Setting Select
Wired Inputs.Jog Forward-I State of the module input: JogFow
Wired Inputs.Jog reverse-I State of the module input: JogRev
Wired Inputs.speed1-I State of the module input: Speed1
Wired Inputs.Local-I State of the module input: Local (Remote)
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
RO-4Z X2.ZI OUT Signal: Zone Interlocking OUT
RO-4Z X2.RO 1 Signal: Relay Output
RO-4Z X2.RO 2 Signal: Relay Output
RO-4Z X2.RO 3 Signal: Relay Output
RO-4Z X2.RO 4 Signal: Relay Output
IEC61850.VirtOut1-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut2-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut3-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut4-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut5-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut6-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut7-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut8-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut9-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut10-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut11-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut12-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut13-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut14-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut15-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut16-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtInp1 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp2 Signal: Virtual Input (IEC61850 GGIO Ind)
www.eaton.com 503
IM02602009E EMR-4000
Name Description
IEC61850.VirtInp3 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp4 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp5 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp6 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp7 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp8 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp9 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp10 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp11 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp12 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp13 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp14 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp15 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp16 Signal: Virtual Input (IEC61850 GGIO Ind)
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
504 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 505
IM02602009E EMR-4000
Name Description
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
506 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
www.eaton.com 507
IM02602009E EMR-4000
Name Description
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
508 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 509
IM02602009E EMR-4000
Name Description
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
510 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
www.eaton.com 511
IM02602009E EMR-4000
Name Description
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
SysA.Alm Current Demd Signal: Alarm Current demand value
SysA.Alarm I THD Signal: Alarm Total Harmonic Distortion Current
SysA.Alarm V THD Signal: Alarm Total Harmonic Distortion Voltage
SysA.Alarm VA Demand Signal: Alarm VAs demand value
SysA.Alarm VA Power Signal: Alarm VAs peak
SysA.Alarm VAr Demand Signal: Alarm VARs demand value
SysA.Alarm VAr Power Signal: Alarm VArs peak
SysA.Alarm Watt Demand Signal: Alarm WATTS demand value
SysA.Alarm Watt Power Signal: Alarm WATTS peak
SysA.Trip Current Demand Signal: Trip Current demand value
SysA.Trip I THD Signal: Trip Total Harmonic Distortion Current
SysA.Trip V THD Signal: Trip Total Harmonic Distortion Voltage
SysA.Trip VA Demand Signal: Trip VAs demand value
SysA.Trip VA Power Signal: Trip VAs peak
SysA.Trip VAr Demand Signal: Trip VARs demand value
SysA.Trip VAr Power Signal: Trip VArs peak
SysA.Trip Watt Demand Signal: Trip WATTS demand value
512 www.eaton.com
EMR-4000 IM02602009E
Name Description
SysA.Trip Watt Power Signal: Trip WATTS peak
Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance Active
Sys.Maint Mode Comm Signal: Arc Flash Reduction Maintenance Comm Mode
Sys.Maint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input Mode
Sys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive
Sys.MaintMode Manually Signal: Arc Flash Reduction Maintenance Manual Mode
Sys.Maint Mode-I Module Input State: Arc Flash Reduction Maintenance Switch
Sys.Min. 1 param changed Signal: At least one parameter has been changed
Sys.PS 1 Signal: Parameter Set 1
Sys.PS 2 Signal: Parameter Set 2
Sys.PS 3 Signal: Parameter Set 3
Sys.PS 4 Signal: Parameter Set 4
Sys.PS1-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS2-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS3-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS4-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PSS manual Signal: Manual switch over of a Parameter Set
Sys.PSS via Comm Signal: Parameter Set Switch via Communication
Sys.PSS via Inp fct Signal: Parameter Set Switch via Input Function
Sys.Res AlarmCr Signal:: Res AlarmCr
Sys.Res OperationsCr Signal:: Res OperationsCr
Sys.Res TotalCr Signal:: Res TotalCr
Sys.Res TripCr Signal:: Res TripCr
www.eaton.com 513
IM02602009E EMR-4000
514 www.eaton.com
EMR-4000 IM02602009E
Name Description
LE1.Gate Out Signal: Output of the logic gate
LE1.Timer Out Signal: Timer Output
LE1.Out Signal: Latched Output (Q)
LE1.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 515
IM02602009E EMR-4000
The protective device provides tripping and alarming functions based on the direct temperature measurements
read from Eaton’s (URTD) device that has 11 temperature sensor channels or Eaton’s (URTDII) device that has
11 or 12 temperature sensor channels. Each channel will have one trip function without an intended delay and
one alarm function with a delay.
• Each individual »Alarm Function« will have a threshold setting range, and can be individually enabled or
disabled. Since the temperature cannot change instantaneously (which is a way that temperature differs
from current), the “delay” is essentially built in to the function due to the fact that the temperature will
take some time to increase from room temperature to the “trip threshold” level.
The entire function can be turned off or on, or individual channels can be turned off or on.
516 www.eaton.com
RTD
Each Channel (RTD):
W1-A, W1-B, W1-C, W2-A, W2-B,W2-C, Amb1, Amb2, Aux1, Aux2, Aux3
RTD.Trip Function
Inactive
RTD.TripCmd
Active AND 15
RTD.Trip
RTD Temperature
EMR-4000
www.eaton.com
RTD.Alarm Function
Inactive
RTD.Timeout Alarm
Active AND
RTD.Alarm t-Delay
RTD Temperature t
0
RTD.Alarm
AND 14
OR
RTD.Invalid
Superv AND
IM02602009E
517
IM02602009E EMR-4000
518 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 519
IM02602009E EMR-4000
520 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 521
IM02602009E EMR-4000
522 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 523
IM02602009E EMR-4000
524 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 525
IM02602009E EMR-4000
526 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 527
IM02602009E EMR-4000
528 www.eaton.com
EMR-4000 IM02602009E
Name Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Alarm Alarm RTD Temperature Protection
Trip Signal: Trip
TripCmd Signal: Trip Command
WD 1 Trip Winding 1 Signal: Trip
WD 1 Alarm Winding 1 Alarm RTD Temperature Protection
WD 1 Timeout Alarm Winding 1 Timeout Alarm
WD 1 Invalid Winding 1 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
WD 2 Trip Winding 2 Signal: Trip
WD 2 Alarm Winding 2 Alarm RTD Temperature Protection
WD 2 Timeout Alarm Winding 2 Timeout Alarm
WD 2 Invalid Winding 2 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
WD 3 Trip Winding 3 Signal: Trip
WD 3 Alarm Winding 3 Alarm RTD Temperature Protection
WD 3 Timeout Alarm Winding 3 Timeout Alarm
WD 3 Invalid Winding 3 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
WD 4 Trip Winding 4 Signal: Trip
WD 4 Alarm Winding 4 Alarm RTD Temperature Protection
WD 4 Timeout Alarm Winding 4 Timeout Alarm
WD 4 Invalid Winding 4 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
WD 5 Trip Winding 5 Signal: Trip
WD 5 Alarm Winding 5 Alarm RTD Temperature Protection
WD 5 Timeout Alarm Winding 5 Timeout Alarm
WD 5 Invalid Winding 5 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
WD 6 Trip Winding 6 Signal: Trip
www.eaton.com 529
IM02602009E EMR-4000
Name Description
WD 6 Alarm Winding 6 Alarm RTD Temperature Protection
WD 6 Timeout Alarm Winding 6 Timeout Alarm
WD 6 Invalid Winding 6 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
MB 1 Trip Motor Bearing 1 Signal: Trip
MB 1 Alarm Motor Bearing 1 Alarm RTD Temperature Protection
MB 1 Timeout Alarm Motor Bearing 1 Timeout Alarm
MB 1 Invalid Motor Bearing 1 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
MB 2 Trip Motor Bearing 2 Signal: Trip
MB 2 Alarm MB 2 Alarm RTD Temperature Protection
MB 2 Timeout Alarm Motor Bearing 2 Timeout Alarm
MB 2 Invalid Motor Bearing 2 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
LB 1 Trip Load Bearing 1 Signal: Trip
LB 1 Alarm LB 1 Alarm RTD Temperature Protection
LB 1 Timeout Alarm Load Bearing 1 Timeout Alarm
LB 1 Invalid Load Bearing 1 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
LB 2 Trip Load Bearing 2 Signal: Trip
LB 2 Alarm LB 2 Alarm RTD Temperature Protection
LB 2 Timeout Alarm Load Bearing 2 Timeout Alarm
LB 2 Invalid Load Bearing 2 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
Aux1 Trip Auxiliary 1 Signal: Trip
Aux1 Alarm Auxiliary 1 Alarm RTD Temperature Protection
Aux1 Timeout Alarm Auxiliary 1 Timeout Alarm
Aux1 Invalid Auxiliary 1 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
Trip WD Group Trip all Windings
Alarm WD Group Alarm all Windings
TimeoutAlmWDGrp TimeoutAlmWDGrp
WD Group Invalid Winding Group Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
Trip MB Group Trip all Motor Bearings
Alarm MB Group Alarm all Motor Bearings
TimeoutAlmMBGrp Timeout Alarm all Motor Bearings
MB Group Invalid Motor Bearing Group Signal: Invalid Temperature Measurement
Value (e.g caused by an defective or interrupted RTD
Measurement)
Trip LB Group Trip all Load Bearings
Alarm LB Group Alarm all Load Bearings
530 www.eaton.com
EMR-4000 IM02602009E
Name Description
TimeoutAlmLBGrp Timeout Alarm all Load Bearings
LB Group Invalid Load Bearing Group Signal: Invalid Temperature Measurement
Value (e.g caused by an defective or interrupted RTD
Measurement)
Trip Any Group Trip Any Group
Alarm Any Group Alarm Any Group
TimeoutAlmAnyGrp Timeout Alarm Any Group
Voting Trip Grp 1 Voting Trip Grp 1
Voting Trip Grp 2 Voting Trip Grp 2
Timeout Alarm Alarm timeout expired
Aux2 Trip Auxiliary 2 Signal: Trip
Aux2 Alarm Auxiliary 2 Alarm RTD Temperature Protection
Aux2 Timeout Alarm Auxiliary 2 Timeout Alarm
Aux2 Invalid Auxiliary 2 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
Trip Aux Group Trip Auxiliary Group
Alarm Aux Group Alarm Auxiliary Group
TimeoutAlmAuxGrp Timeout Alarm Auxiliary Group
AuxGrpInvalid Invalid Auxiliary Group
www.eaton.com 531
IM02602009E EMR-4000
532 www.eaton.com
EMR-4000 IM02602009E
The URTDII conveys multiplexed temperature data back to the relay via a single optical fiber. The URTDII may
be mounted remotely from the protective device. The fiber optic connector is located on the X102 terminal of the
protective device.
Consider the benefit of mounting the URTDII module away from the protective device and as close to the
protected equipment as possible. The big bundle of RTD wires to the protected equipment becomes much
shorter. The URTDII may be placed up to 400 ft (121.9 m) from the protective device with the optical fiber
connection. Note that the URTDII will require a power supply connection at its remote location.
Connect a suitable source to the power terminals J10A-1 and J10A-2 on the URTDII module. Connect any of
the Shield terminals to a non-current-carrying safety ground. It is recommended to have a ground connection on
both sides of the unit.
www.eaton.com 533
IM02602009E EMR-4000
The previous figure shows the fiber optic connections between the URTDII Module and the protective device.
The protective device supports the optical fiber connection. The following table lists the fiber optic order options.
The optical fiber is the only method of transmitting temperature data from the URTDII Module to the protective
device.
Preassembled plastic optical fibers with connectors can be ordered from Eaton, or from any distributor of Agilent
Technologies® optical fiber products. In addition, these same distributors offer long rolls of cable with connectors
that can be installed in the field. Some distributors will make custom lengths to order.
Surplus length of a pre-cut fiber does not cause a problems. Simply coil
and tie the excess fiber at a convenient point. Avoid high tie pressure.
Bending radius of the fiber should be greater than 2 in. (50.8 mm).
The fiber termination at the URTDII simply snaps into or out of the connector. To connect the fiber termination
at the protective device, push the plug of the fiber optic onto the device interface then turn it until it “snaps”.
The protective device as well as the URTDII have various power supply
options. Make certain that the power supply is acceptable for both units
before connecting the same power supply to both devices.
534 www.eaton.com
EMR-4000 IM02602009E
RTD Control URTDII Connection Name Terminals Transformer Temperature Monitoring Point
RTD2: MW2 J2-5, J2-6 W1-B - Transformer Winding 1,
Alarm Functional Phase B RTD Temperature.
Trip Functional
W1-B Alarm
W1-B t-Delay
W1-B Trip
RTD3: MW3 J2-8, J2-9 W1-C - Transformer Winding 1,
Alarm Functional Phase C RTD Temperature.
Trip Functional
W1-C Alarm
W1-C t-Delay
W1-C Trip
RTD4: MW4 J2-12, J2-13 W2-A - Transformer Winding 2,
Alarm Functional Phase A RTD Temperature.
Trip Functional
W2-A Alarm
W2-A t-Delay
W2-A Trip
RTD5: MW5 J2-15, J2-16 W2-B - Transformer Winding 2,
Alarm Functional Phase B RTD Temperature.
Trip Functional
W2-B Alarm
W2-B t-Delay
W2-B Trip
RTD6: MW6 J2-19, J2-20 W2-C - Transformer Winding 2,
Alarm Functional Phase C RTD Temperature.
Trip Functional
W2-C Alarm
W2-C t-Delay
W2-C Trip
RTD7: MB1 J10B-19, J10B-20 AMB1 - Transformer Ambient RTD
Alarm Functional Temperature (1).
Trip Functional
Amb1 Alarm
Amb1 t-Delay
Amb1 Trip
RTD8: MB2 J10B-15, J10B-16 AMB2 - Transformer Ambient RTD
Alarm Functional Temperature (2).
Trip Functional
Amb2 Alarm
Amb2 t-Delay
Amb2 Trip
RTD9: LB1 J10B-12, J10B-13 AUX1 – User Defined RTD Temperature.
Alarm Functional
Trip Functional
Aux1 Alarm
Aux1 t-Delay
Aux1 Trip
RTD10: LB2 J10B-8, J10B-9 AUX2 – User Defined RTD Temperature.
Alarm Functional
Trip Functional
Aux2 Alarm
Aux2 t-Delay
Aux2 Trip
www.eaton.com 535
IM02602009E EMR-4000
RTD Control URTDII Connection Name Terminals Transformer Temperature Monitoring Point
RTD11: AUX1 J10B-5, J10B-6 AUX3 – User Defined RTD Temperature.
Alarm Functional
Trip Functional
Aux3 Alarm
Aux3 t-Delay
Aux3 Trip
RTD12: AUX2 J10B-1, J10B-2 AUX4 – User Defined RTD Temperature.
Alarm Functional
Trip Functional
Aux4 Alarm
Aux4 t-Delay
Aux4 Trip
The three terminals for any unused RTD input channel should be wired together. For example, if MW5 and
MW6 are unused, MW5 terminals J2-15, J2-16, and J2-17 should be wired together and MW6 terminals J2-19,
J2-20, J2- 21 should be separately wired together.
Universal
RTD Module II
RTD 1 - C 21
2 + + 20
3 C - 19 RTD
Shield/Drain Shield/Drain
Wire 4 S Auxiliary S 18 Wire
RTD 5 - C 17
6 + + 16
7 C - 15 RTD
RTD 8 - C 14
9 + + 13
10 C
Load Motor - 12 RTD
J10B
Shield/Drain Shield/Drain
11 S S 11
J2
Motor Motor
Terminals Terminals
DO NOT CONNECT CABLE'S SHIELD WIRE AT THIS END!
USE TAPE TO INSULATE
See the figure above for wiring of RTDs to the URTD inputs. Use #18 AWG, three-conductor shielded cable.
536 www.eaton.com
EMR-4000 IM02602009E
Note the connection rules in the figure. When making connections to a two-lead RTD, connect two of the cable
conductors to one of the RTD leads as shown. Make this connection as close to the transformer as possible.
Connect the third cable conductor to the remaining RTD lead.
Connect the shield / drain wire to the Shield terminal as shown in the figure. The RTD cable shield should be
connected only at the URTD end, and insulated at the RTD end. The RTD's themselves must not be grounded
at the object to be protected.
Remember to set the URTDII module DIP switches according to the types of RTDs in each of the channels (see
I.L. IL02602013E).
www.eaton.com 537
IM02602009E EMR-4000
538 www.eaton.com
EMR-4000 IM02602009E
Name Description
WD3 Superv Signal: Supervision Channel WD3
WD4 Superv Signal: Supervision Channel WD4
WD5 Superv Signal: Supervision Channel WD5
WD6 Superv Signal: Supervision Channel WD6
MB1 Superv Signal: Supervision Channel MB1
MB2 Superv Signal: Supervision Channel MB2
LB1 Superv Signal: Supervision Channel LB1
LB2 Superv Signal: Supervision Channel LB2
Aux1 Superv Signal: Supervision Channel Aux1
Aux2 Superv Signal: Supervision Channel Aux2
Superv Signal: URTD Supervision Channel
active Signal: URTD active
Outs forced Signal: The State of at least one Relay Output has been set by
force. That means that the state of at least one Relay is forced and
hence does not show the state of the assigned signals.
www.eaton.com 539
IM02602009E EMR-4000
540 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 541
IM02602009E EMR-4000
Commissioning
Before starting work on an open switchboard, it is required that the switchboard is de-energized and the following
five safety regulations have been met.
Safety precautions:
• Disconnect the power supply;
• Secure against reconnection;
• Verify that the equipment is de-energized;
• Connect to ground and short-circuit all phases; and
• Cover or safeguard all live adjacent parts.
Even when the auxiliary voltage is switched off, it is likely that there are still
hazardous voltages at the component connections.
Commissioning/Protection Test
542 www.eaton.com
EMR-4000 IM02602009E
With any test of the protection functions, the following has to be checked:
Check all general trip blockings. All general trip blockings MUST be tested.
Prior to the initial operation of the protection device, all tripping times and
values shown in the adjustment list MUST be confirmed by a secondary
test.
www.eaton.com 543
IM02602009E EMR-4000
Ensure that the cabinet is de-energized and that there are no voltages that
could lead to injury of personnel.
Disconnect the terminals at the rear-side of the device. DO NOT pull any
cable – pull on the plug! If it is stuck, use a screw driver.
Fasten the cables and terminals in the cabinet by means of cable clips to
ensure that no accidental electrical connections are caused.
Hold the device at the front-side while removing the mounting nuts.
544 www.eaton.com
EMR-4000 IM02602009E
General
Within the [Service/General] menu, the User can initiate a reboot of the device.
Maintenance Mode
Principle – General Use
The Maintenance Mode can be used to reduce arc flash levels.
Refer to Std. NFPA70E.
The Maintenance Mode can improve safety by providing a simple and reliable method to reduce fault clearing
time and lower incident energy levels at energized panels. The Maintenance Mode allows the User to switch to
more sensitive settings via the HMI/panel, Communication, or via a Digital Input while maintenance work is being
performed at an energized panel or device. The more sensitive settings provide greater security for
maintenance personnel and helps reduce the possibility of injury.
The status of the Maintenance Mode (active/inactive) is stored power fail-safe.
Manual activation is only possible via the HMI/panel (not via PowerPort-E).
Before Use
The sensitivity settings for the Maintenance Mode have to be calculated
and programmed into the device (according to Std. NFPA70E).
They are not part of the device by default.
www.eaton.com 545
IM02602009E EMR-4000
When the Maintenance Mode is enabled and fault current causes its operation, the fault clearing time of the
associated breaker has to be very fast. Calculate the sensitivity setting on the basis of Std. NFPA70E.
Program those sensitivity settings either into a setting group or into Adaptive Parameters.
The Maintenance Mode offers two output signals: “Maint Mode activated” and “Maint Mode not activated”.
• Switch to another setting group (in case the sensitivity settings are saved within this setting group);
• Activate “Adaptive Parameters” (in case the sensitivity settings are saved within these adaptive
parameters); and/or
• Block or activate dedicated functions.
• Switch back to the standard setting group when Maintenance Mode should not be used.
For fast access, the Maintenance Mode can be accessed by means of the »Softkey« Maint on the start screen
(root) of the device.
546 www.eaton.com
Sys
Sys.Maint Mode DI
Sys.MaintMode Manually
Inactive
Sys.Maint Mode Mode
Active
Inactive
AND
Activation Manually
EMR-4000
Activation via DI
www.eaton.com
Comm Cmd Sys.Maint Mode Active
AND
547
IM02602009E EMR-4000
For commissioning purposes or for maintenance, relay output contacts can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Force RO], relay output contacts can be
set by force:
• Permanent; or
• Via timeout.
If they are set with a timeout, they will keep their “Force Position” only as long as this timer runs. If the timer
expires, the relay will operate normally. If they are set as Permanent, they will keep the “Force Position”
continuously.
Forcing an entire group takes precedence over forcing a single relay output contact!
Keep in mind, that forcing all relay output contacts (of the same assembly
group) takes precedence over the force command of a single relay output
contact.
The parameters, their defaults, and setting ranges have to be taken from
the Relay Output Contacts section.
548 www.eaton.com
EMR-4000 IM02602009E
The User MUST ENSURE that the relay output contacts are ARMED AGAIN
after maintenance is complete. If they are not armed, the protective device
WILL NOT provide protection.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/DISARMED] entire groups of relay output
contacts can be disarmed:
• Permanent; or
• Via timeout.
If they are set with a timeout, they will keep their “Disarm Position” only as long as this timer runs. If the timer
expires, the relay output contacts will operate normally. If they are set Permanent, they will keep the “Disarm
State” continuously.
www.eaton.com 549
IM02602009E EMR-4000
Forcing RTDs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
RTD/UTRD section.
For commissioning purposes or for maintenance, RTD temperatures can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/URTD], RTD temperatures can be set by
force:
• Permanent; or
• Via timeout.
If they are set with a timeout, they will keep their “Forced Temperature” only as long as this timer runs. If the
timer expires, the RTD will operate normally. If they are set as »Permanent«, they will keep the “Forced
Temperature” continuously. This menu will show the measured values of the RTDs until the User activates the
force mode by calling up the »Function«. As soon as the force mode is activated, the shown values will be
frozen as long as this mode is active. Now the User can force RTD values. As soon as the force mode is
deactivated, measured values will again be shown.
The parameters, their defaults, and setting ranges have to be taken from
Analog Output section.
For commissioning purposes or for maintenance, Analog Outputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Outputs], Analog Outputs can be
set by force:
• Permanent; or
• Via timeout.
If they are set with a timeout, they will keep their “Forced Value” only as long as this timer runs. If the timer
expires, the Analog Output will operate normally. If they are set as »Permanent«, they will keep the “Forced
Value” continuously. This menu will show the current value that is assigned to the Analog Output until the User
activates the force mode by calling up the »Function«. As soon as the force mode is activated, the shown
values will be frozen as long as this mode is active. Now the User can force Analog Output values. As soon as
the force mode is deactivated, measured values will again be shown.
550 www.eaton.com
EMR-4000 IM02602009E
For commissioning support and in order to analyze failures, the protective device offers the option to simulate
measuring quantities. The simulation menu can be found within the [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave gen] menu. The simulation cycle consists of three states:
• Pre-failure;
• Failure; and
• Post-failure State (Phase).
Within the [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Configuration] sub-menu, the
duration of each phase can be set. In addition; the measuring quantities to be simulated can be determined
(e.g.: voltages, currents, and the corresponding angles) for each phase (and ground).
Setting the device into the simulation mode means taking the protective
device out of operation for the duration of the simulation. Do not use this
feature during operation of the device if the User cannot guarantee that
there is a running and properly working backup protection.
Sgen
www.eaton.com 551
IM02602009E EMR-4000
**Please note: Due to internal dependencies, the frequency of the simulation module is 0.16% greater than the rated one.
552 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 553
IM02602009E EMR-4000
554 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 555
IM02602009E EMR-4000
556 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 557
IM02602009E EMR-4000
558 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 559
IM02602009E EMR-4000
560 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 561
IM02602009E EMR-4000
Name Description
Running Signal: Measuring value simulation is running
State Signal: Wave generation states: 0=AdcNormal, 1=PreFault,
2=Fault, 3=Post, 4=InitReset
562 www.eaton.com
EMR-4000 IM02602009E
Technical Data
Use Copper conductors only, 75°C (167°F).
Conductor size AWG 14 [2.5 mm].
Routine Test
Insulation Test Acc. to IEC60255-5: All tests to be carried out against ground and other input and output circuits.
Aux. Voltage Supply, Digital Inputs, 2.5 kV (eff.) / 50 Hz
Current Measuring Inputs, Signal Relay Outputs:
Voltage Measuring Inputs: 3.0 kV (eff.) / 50 Hz
All Wire-Bound Communication Interfaces: 1.5 kV DC
Housing
Housing B2: Height / Width 183 mm (7.205 in.)/ 212.7 mm (8.374 in.)
Housing Depth (Incl. Terminals): 208 mm (8.189 in.)
Material, Housing: Aluminum extruded section
Material, Front Panel: Aluminum/Foil front
Mounting Position: Horizontal (±45° around the X-axis must be permitted)
Weight: Approx. 4.2 kg (9.259 lb)
www.eaton.com 563
IM02602009E EMR-4000
Frequency Measurement
Nominal Frequencies: 50 Hz / 60 Hz
564 www.eaton.com
EMR-4000 IM02602009E
Voltage Supply
Aux. Voltage: 24 - 270 Vdc / 48 - 230 Vac (-20/+10%)
Buffer Time in Case of Supply Failure: >= 50 ms at minimal aux. voltage
Interrupted communication is permitted.
Max. Permissible Making Current: 18 A peak value for <0.25 ms
12 A peak value for <1 ms
Power Consumption
Power Supply Range: Power consumption Max. Power Consumption
in Idle Mode
24 - 270 Vdc: Approx. 7 W Approx.13 W
48 - 230 Vac Approx. 7 VA Approx.13 VA
(For Frequencies of 50-60 Hz):
Display
Display Type: LCD with LED background illumination
Resolution - Graphics Display: 128 x 64 pixel
Digital Inputs
Max. Input Voltage: 300 Vdc / 259 Vac
Input Current: <4 mA
Reaction Time: <20 ms
Fallback Time: <30 ms
www.eaton.com 565
IM02602009E EMR-4000
Un = 48 V / 60Vdc
Switching Threshold 2 ON: Min. 42.6 Vdc
Switching Threshold 2 OFF: Max. 21.3 Vdc
Un = 110 / 120 Vac / dc
Switching Threshold 3 ON: Min. 88.0 Vdc / 88.0 Vac
Switching Threshold 3 OFF: Max. 44.0 Vdc / 44.0 Vac
Un = 230 / 240 Vac / dc
Switching Threshold 4 ON: Min. 184 Vdc / 184 Vac
Switching Threshold 4 OFF: Max. 92 Vdc / 92 Vac
Terminals: Screw-type terminal
Relay Outputs
Continuous Current: 5 A ac / dc
Max. Make Current: 25 A ac / 25 A dc for 4 s
30 A / 230Vac according to ANSI IEEE Std C37.90-2005
30 A / 250Vdc according to ANSI IEEE Std C37.90-2005
Max. Breaking Current: 5 A ac up to 240 Vac
5 A dc up to 30 V (resistive)
0.3 A dc at 250 V (resistive)
Max. Switching Voltage: 250 V ac / 250 Vdc
Switching Capacity: 1,250 VA
Contact Type: Form C or normally open contact
Terminals: Screw-type terminals
Analog Outputs
The following technical data only apply to devices, which are equipped with analog outputs. Please refer to the
order code of your device.
The mode of each output can be individually selected between current or voltage output. Shielded cable for the
analog outputs is recommended. The terminals of the HF shield should be used, when connecting the shield to
ground on both sides of the cable is not possible. On one side of the cable the shield has to be directly connect-
ed to ground. In case of the use of unshielded twisted pair cables, the length must not exceed 10 m. All analog
outputs have a common potential. Each output has an own common terminal.
Current mode
Range: 0-20 mA
Max. load resistance: 1 kΩ
Voltage mode
Range: 0-10 V maximum output current 20 mA
Accuracy 0.5% of the nominal value 20 mA resp. 10 V
566 www.eaton.com
EMR-4000 IM02602009E
Influence of temperature to accuracy <1% (within the range of 0°C to +60°C (+32°F to +140°F)
Test voltage of outputs (one group)
against other electrical groups 2.5 kV
Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High) 4.75 to 5.25 Vdc
Output voltage (Low) 0.0 to +0.5 Vdc
Zone In:
Nominal input voltage +5 Vdc
Max. input voltage +5.5 Vdc
Switching threshold ON min. 4.0 Vdc
Switching threshold OFF max. 1.5 Vdc
RS485*
Master/Slave: Slave
Connection: 6 screw-clamping terminals RM 3.5 mm (138 MIL)
(terminating resistors internal)
The RS485 interface is realized via terminals. The communication cable has
to be shielded. The shielding has to be fixed at the screw that is marked
with the ground symbol (rear side of the device).
Fiber Optic*
Master/Slave: Slave
Connection: ST-Plug
URTD-Interface*
Connection: Versatile Link
www.eaton.com 567
IM02602009E EMR-4000
Boot Phase
After switching on the power supply, the protection will be available in approximately 22 seconds. After
approximately 2,5 min, the boot phase is completed (HMI and Communication initialized).
568 www.eaton.com
EMR-4000 IM02602009E
Standards
Approvals
• UL-listed file: e217753
Design Standards
Generic Standard EN 61000-6-2
EN 61000-6-3
Product Standard IEC 60255-6
EN 50178
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 14-95 (Industrial Control Equipment)
ANSI C37.90
www.eaton.com 569
IM02602009E EMR-4000
Environmental Tests
Classification:
IEC 60068-1 Climatic 20/060/56
Classification
570 www.eaton.com
EMR-4000 IM02602009E
Mechanical Tests
Test Fc: Vibration Response Test
IEC 60068-2-6 (10 Hz – 59 Hz) 0.0014 in. (0.035 mm)
IEC 60255-21-1 Displacement
Class 1
(59Hz – 150Hz) 0.5 gn
Acceleration
Number of cycles in each axis 1
www.eaton.com 571
IM02602009E EMR-4000
Specifications
Used Protocol Time drift over one month Deviation to time generator
572 www.eaton.com
EMR-4000 IM02602009E
* For earth current sensitive the precision does not depend on the
nominal value but is referenced to 100 mA (with In =1 A) respectively.
500 mA (with In = 5 A)
www.eaton.com 573
IM02602009E EMR-4000
Frequency Measurement
Nominal frequency: 50 Hz / 60 Hz
Precision: ±0.05% of fn within the range of 40-70 Hz at voltages >50 V
Voltage dependency: frequency acquisition of 5 V – 800 V
Energy measurement*
Power Measurement*
*
Tolerance at 0.8 … 1.2xVn (with Vn=100V) , |PF|>0.5, symmetrically feeded
Units are selected automatically depending on CT and VT ratings for best fit.
Sn=1.73 * VT rating * CT rating
574 www.eaton.com
EMR-4000 IM02602009E
The tripping delay relates to the time between alarm and trip. The accuracy
of the operating time relates to the time between when the measured value
has exceeded the threshold until the protection element is picked-up.
www.eaton.com 575
IM02602009E EMR-4000
576 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 577
IM02602009E EMR-4000
578 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 579
IM02602009E EMR-4000
580 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 581
IM02602009E EMR-4000
582 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 583
IM02602009E EMR-4000
Appendix
The following terms, abbreviations, and acronyms are used in this manual. Please refer to this section for their
meanings / definitions.
A Ampere(s), Amp(s)
AC Alternating current
A/D Analog to digital
Ack. Acknowledge
AMP Ampere(s), Amp(s)
AND Logical gate (The output becomes true if all Input signals are true.)
ANG Angle
ANSI American National Standards Institute
AR Automatic reclosure
AUX Auxiliary
AVG, avg Average
AWG American wire gauge
BF Breaker failure
BFI Breaker failure initiate
BKR, bkr Breaker
Blo Blocking(s)
°C Degrees Celsius
calc Calculated
CB Circuit breaker
CD Compact disk
Char Curve shape
CHK Check
CHNL Channel
Cmd. Command
CMND Command
CMN Common input
COM Common input
Comm Communication
COMP Compensated, comparison
CONN Connection
CONT Continuous, contact
CPU Central processing unit
Cr. Counter(s)
CRT, CRNT Current
CSA Canadian Standards Association
CT Control transformer
Ctrl. Control
CTS Current transformer supervision
d Day
D/A Digital to analog
D-Sub-Plug Communication interface
DC, dc Direct current
DEFT Definite time characteristic (Tripping time does not depend on the height of the current.)
DFLT Default
DGNST Diagnostics
DI Digital Input
Diagn. Diagnosis
584 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 585
IM02602009E EMR-4000
586 www.eaton.com
EMR-4000 IM02602009E
ms Milli-second(s)
MTA Maximum torque angle
MTR Motor
MV Medium voltage
mVA Milli volt amperes (Power)
MVA Mega volt-ampere (total 3-phase)
MVA A Mega volt-ampere (phase A)
MVA B Mega volt-ampere (phase B)
MVA C Mega volt-ampere (phase C)
MVAR Mega Var (total 3-phase)
MVAR A Mega Var (phase A)
MVAR B Mega Var (phase B)
MVAR C Mega Var (phase C)
MVARH Mega Var-Hour
MW Megawatt(s) (total 3-phase)
MW A Megawatt(s) (phase A)
MW B Megawatt(s) (phase B)
MW C Megawatt(s) (phase C)
MWH Megawatt-Hour(s)
N Neutral
N/A, n/a Not applicable
N.C. Not connected
NEG Negative
NINV Normal inverse tripping characteristic
Nm Newton-meter
No Number
N.O. Normal open (Contact)
NOM, Nom. Nominal
NT Manufacturer internal product designation code
O Over
OC, O/C Overcurrent
O/P, Op, OUT Output
OV Overvoltage
OVERFREQ Overfrequency
OVLD Overload
P Phase
Para. Parameter
PC Personal computer
PCB Printed circuit board
PE Protected Earth
PF Power factor (total 3-phase)
PF A Power factor (phase A)
PF B Power factor (phase B)
PF C Power factor (phase C)
Ph Phase
POS Positive
PRESS Pressure
PRI, pri Primary
PROT, Prot Protection Module (Master Module), protection
PS1 Parameter set 1
PS2 Parameter set 2
PS3 Parameter set 3
PS4 Parameter set 4
www.eaton.com 587
IM02602009E EMR-4000
588 www.eaton.com
EMR-4000 IM02602009E
www.eaton.com 589
IM02602009E EMR-4000
t = Tripping delay
I = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
DEFT
100
I
Pickup
0.01 40
10
t [s]
300 s
t
0.1
0.0 s
0.01
1 10
I
Pickup
590 www.eaton.com
EMR-4000 IM02602009E
• NINV (IEC/XInv);
• VINV (IEC/XInv);
• LINV (IEC/XInv);
• EINV (IEC/XInv);
• MINV (ANSI/XInv);
• VINV (ANSI/XInv);
• EINV (ANSI/XInv);
• Thermal Flat;
• Therm Flat IT;
• Therm Flat I2T; and
• Therm Flat I4T.
Explanation:
t = Tripping delay
I = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
www.eaton.com 591
IM02602009E EMR-4000
IEC NINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
0.14 0.14
t= 2 *t-multiplier [s] t= 0.02 *t-multiplier [s]
I I
(Pickup) -1 (Pickup) -1
t [s] t-multiplier
592 www.eaton.com
EMR-4000 IM02602009E
IEC VINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
13.5 13.5
t= *t-multiplier [s] t= *t-multiplier [s]
I 2 I
(Pickup)-1 (Pickup)-1
t [s]
t-multiplier
www.eaton.com 593
IM02602009E EMR-4000
IEC LINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
120 120
t= *t-multiplier [s] t= *t-multiplier [s]
I 2 I
(Pickup)-1 ( Pickup)-1
t [s] t-multiplier
594 www.eaton.com
EMR-4000 IM02602009E
IEC EINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
80 80
t= 2
*t-multiplier [s] t= 2
*t-multiplier [s]
I I
(Pickup) -1 (Pickup) -1
t [s] t-multiplier
www.eaton.com 595
IM02602009E EMR-4000
ANSI MINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
I
4.85
(Pickup)
2
-1
*t-multiplier [s] t=
( 0.0515
I
0.02
(Pickup) -1
+ 0.1140
) *t-multiplier [s]
t [s] t-multiplier
596 www.eaton.com
EMR-4000 IM02602009E
ANSI VINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
21.6
I
(Pickup
2
)-1
*t-multiplier [s] t=
( I
(Pickup)
19.61
2
-1
+ 0.491
) *t-multiplier [s]
t [s] t-multiplier
www.eaton.com 597
IM02602009E EMR-4000
ANSI EINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
29.1
I 2
(Pickup)-1
*t-multiplier [s] t=
( I
(Pickup)
28.2
2
-1
+ 0.1217
) *t-multiplier [s]
t [s] t-multiplier
598 www.eaton.com
EMR-4000 IM02602009E
Therm Flat
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 2
5*3 5*1
t= 0
*t-multiplier [s] t= 0
*t-multiplier [s]
I I
( In ) ( In )
t = 45 *t-multiplier [s]
4
1× 10
3
1× 10
TM[s]=
10
5
100
2
1.0
t [s] 10
0.5 t-multiplier
1
0.05
0.1
0.01
0.01 0.1 1 10 100
www.eaton.com 599
IM02602009E EMR-4000
IT
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 1
5*3 5*3
t= 0 *t-multiplier [s] t= *t-multiplier [s]
I 1
( In ) ( I
)
In
4
1× 10
3
1× 10
100
TM[s]=
t [s] t-multiplier
10
10
5
2
1
1.0
0.5
0.1
0.05
0.01
0.01 0.1 1 10 100
600 www.eaton.com
EMR-4000 IM02602009E
I2T
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 2
5*3 5*3
t= *t-multiplier [s] t= 2 *t-multiplier [s]
I 0
I
( In ) ( In )
4
1× 10
3
1× 10
100
t [s] t-multiplier
10
TM[s]=
1
10
5
0.1 2
1.0
0.5
0.05
0.01
0.01 0.1 1 10 100
x * Pickup (Multiples of Pickup)
www.eaton.com 601
IM02602009E EMR-4000
I4T
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 4
5*3 5*3
t= 0 *t-multiplier [s] t= *t-multiplier [s]
I I
4
( In ) ( In )
4
1× 10
3
1× 10
100
t [s] t-multiplier
10
TM[s]=
1
10
5
0.1 2
1.0
0.5
0.05
0.01
0.01 0.1 1 10 100
602 www.eaton.com
EMR-4000 IM02602009E
Explanation:
t = Tripping delay
IG = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents; but this is only possible
if the current transformers are Wye-connected.
DEFT
100
IR calc
Pickup
I/I>
0.01 20
40
10
t [s]
300 s
t
0.1
0.0 s
0.01
1 10
IR calc
Pickup
www.eaton.com 603
IM02602009E EMR-4000
Explanation:
t = Tripping delay
IX = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents; but this is only possible
if the current transformers are Wye-connected.
DEFT
100
IX
Pickup
I/I>
0.01 20
40
10
t [s]
300 s
t
0.1
0.0 s
0.01
1 10
IX
Pickup
604 www.eaton.com
EMR-4000 IM02602009E
• NINV (IEC/XInv);
• VINV (IEC/XInv);
• LINV (IEC/XInv);
• EINV (IEC/XInv);
• MINV (ANSI/XInv);
• VINV (ANSI/XInv);
• EINV (ANSI/XInv);
• Thermal Flat;
• Therm Flat IT;
• Therm Flat I2T; and
• Therm Flat I4T.
Explanation:
t = Tripping delay
IG = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents; but this is only possible
if the current transformers are Wye-connected.
www.eaton.com 605
IM02602009E EMR-4000
IEC NINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
0.14 0.14
t= 2 *t-multiplier [s] t= 0.02 *t-multiplier [s]
IG IG
(Pickup) -1 (Pickup) -1
t [s] t-multiplier
606 www.eaton.com
EMR-4000 IM02602009E
IEC VINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
13.5 13.5
t= *t-multiplier [s] t= *t-multiplier [s]
IG 2 IG
(Pickup)-1 (Pickup) -1
t [s]
t-multiplier
www.eaton.com 607
IM02602009E EMR-4000
IEC LINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
120 120
t= *t-multiplier [s] t= *t-multiplier [s]
IG 2 IG
(Pickup
)-1 (Pickup)-1
t [s] t-multiplier
608 www.eaton.com
EMR-4000 IM02602009E
IEC EINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
80 80
t= *t-multiplier [s] t= *t-multiplier [s]
IG 2 IG 2
(Pickup) -1 (Pickup) -1
t [s] t-multiplier
www.eaton.com 609
IM02602009E EMR-4000
ANSI MINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
4.85
IG
2
(Pickup) -1
*t-multiplier [s] t=
( 0.0515
IG
0.02
(Pickup) -1
+ 0.1140
) *t-multiplier [s]
t [s] t-multiplier
610 www.eaton.com
EMR-4000 IM02602009E
ANSI VINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
21.6
IG 2
(Pickup
)-1
*t-multiplier [s] t=
( 19.61
IG
2
(Pickup) -1
+ 0.491
) *t-multiplier [s]
t [s] t-multiplier
www.eaton.com 611
IM02602009E EMR-4000
ANSI EINV
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
t=
29.1
IG 2
(Pickup
)-1
*t-multiplier [s] t=
( 28.2
IG
2
(Pickup) -1
+ 0.1217
) *t-multiplier [s]
t [s] t-multiplier
612 www.eaton.com
EMR-4000 IM02602009E
Therm Flat
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2
5*1 5
t= *t-multiplier [s] t= 0 *t-multiplier [s]
IG 0 IG
(IGnom) (IGnom)
t = 5 *t-multiplier [s]
4
1× 10
3
1× 10
TM[s]=
10
5
100
2
1
0.05
0.1
0.01
0.01 0.1 1 10 100
www.eaton.com 613
IM02602009E EMR-4000
IT
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 1
5*1 5*1
t= 0 *t-multiplier [s] t= *t-multiplier [s]
IG IG
1
(IGnom) (IGnom)
1× 104
3
1× 10
100
t [s] 10
TM[s]= t-multiplier
5
10
5 2
1
2
1.0
0.1 0.5
0.05
0.01
0.01 0.1 1 10 100
614 www.eaton.com
EMR-4000 IM02602009E
I2T
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 2
5*1 5*1
t= *t-multiplier [s] t= 2 *t-multiplier [s]
IG 0
IG
(IGnom) (IGnom)
4
1× 10
3
1× 10
100
t [s] 10 t-multiplier
TM[s]=
1
10
0.1 2
1.0
0.5
0.05
0.01
0.01 0.1 1 10 100
www.eaton.com 615
IM02602009E EMR-4000
I4T
Notice!
Various Reset Modes are available. Resetting via characteristic, delayed, and
instantaneous.
Reset Trip
2 4
5*1 5*1
t= 0 *t-multiplier [s] t= *t-multiplier [s]
IG IG
4
(IGnom) (IGnom)
4
1× 10
3
1× 10
100
t [s] 10 t-multiplier
TM[s]=
1 10
5
2
0.1
1.0
0.5
0.05
0.01
0.01 0.1 1 10 100
616 www.eaton.com
EMR-4000 IM02602009E
Assignment List
The »ASSIGNMENT LIST« below summarizes all module outputs (signals) and inputs (e.g.: states of the
assignments).
Name Description
-.- No assignment
Prot.Available Signal: Protection is available.
Prot.Active Signal: Active
Prot.ExBlo Signal: External Blocking
Prot.Pickup Phase A Signal: General Pickup Phase A
Prot.Pickup Phase B Signal: General Pickup Phase B
Prot.Pickup Phase C Signal: General Pickup Phase C
Prot.Pickup IX or IR Signal: General Pickup - Ground Fault
Prot.Pickup Signal: General Pickup
Prot.Trip Phase A Signal: General Trip Phase A
Prot.Trip Phase B Signal: General Trip Phase B
Prot.Trip Phase C Signal: General Trip Phase C
Prot.Trip IX or IR Signal: General Trip Ground Fault
Prot.Trip Signal: General Trip
Prot.Res Fault a Mains No Signal: Resetting of fault number and number of grid faults.
Prot.ExBlo1-I Module Input State: External Blocking1
Prot.ExBlo2-I Module Input State: External Blocking2
Ctrl.Local Switching Authority: Local
Ctrl.Remote Switching Authority: Remote
Ctrl.NonInterl Non-Interlocking is active
Ctrl.NonInterl-I Non-Interlocking
Bkr.SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary
contact (pole) only. Thus indeterminate and disturbed Positions
cannot be detected.
Bkr.Pos not CLOSE Signal: Pos not CLOSE
Bkr.Pos CLOSE Signal: Breaker is in CLOSE-Position
Bkr.Pos OPEN Signal: Breaker is in OPEN-Position
Bkr.Pos Indeterm Signal: Breaker is in Indeterminate Position
Bkr.Pos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-
back signals (Position Indicators) contradict themselves. After
expiring of a supervision timer this signal becomes true.
Bkr.Ready Signal: Breaker is ready for operation.
Bkr.Interl CLOSE Signal: One or more IL_Close inputs are active.
Bkr.Interl OPEN Signal: One or more IL_Open inputs are active.
Bkr.CES succesf Command Execution Supervision: Switching command executed
successfully.
www.eaton.com 617
IM02602009E EMR-4000
Name Description
Bkr.CES Disturbed Command Execution Supervision: Switching Command
unsuccessful. Switchgear in disturbed position.
Bkr.CES Fail TripCmd Command Execution Supervision: Trip command not executed.
Bkr.CES SwitchgDir Command Execution Supervision respectively Switching Direction
Control: This signal becomes true, if a switch command is issued
even though the switchgear is already in the requested position.
Example: A switchgear that is already OPEN should be switched
OPEN again (doubly). The same applies to CLOSE commands.
Bkr.CES CLOSE d OPEN Command Execution Supervision: CLOSE Command during a
pending OPEN Command.
Bkr.CES SG not ready Command Execution Supervision: Switchgear not ready
Bkr.CES Field Interl Command Execution Supervision: Switching Command not
executed because of field interlocking.
Bkr.Prot CLOSE Signal: CLOSE command issued by the Prot module
Bkr.TripCmd Signal: Trip Command
Bkr.Ack TripCmd Signal: Acknowledge Trip Command
Bkr.Bwear Slow Breaker Signal: Slow Breaker Alarm
Bkr.Res Bwear Sl Breaker Signal: Resetting the slow breaker alarm
Bkr.CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on
the setting the signal may include the CLOSE command of the
Prot module.
Bkr.OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on
the setting the signal may include the OPEN command of the Prot
module.
Bkr.CLOSE Cmd manual Signal: CLOSE Cmd manual
Bkr.OPEN Cmd manual Signal: OPEN Cmd manual
Bkr.CinBkr-52a-I Feed-back signal of the Bkr (52a)
Bkr.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)
Bkr.Ready-I Module Input State: Breaker Ready
Bkr.Ack TripCmd-I State of the module input: Acknowledgment Signal (only for
automatic acknowledgment). Module input signal
Bkr.Interl CLOSE1-I State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE2-I State of the module input: Interlocking of the CLOSE command
Bkr.Interl CLOSE3-I State of the module input: Interlocking of the CLOSE command
Bkr.Interl OPEN1-I State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN2-I State of the module input: Interlocking of the OPEN command
Bkr.Interl OPEN3-I State of the module input: Interlocking of the OPEN command
Bkr.SC CLOSE-I State of the module input: Switching CLOSE Command, e.g. the
state of the Logic or the state of the digital input
Bkr.SC OPEN-I State of the module input: Switching OPEN Command, e.g. the
state of the Logic or the state of the digital input
Bkr.Operations Alarm Signal: Service Alarm, too many Operations
Bkr.Isum Intr trip: IA Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IA
618 www.eaton.com
EMR-4000 IM02602009E
Name Description
Bkr.Isum Intr trip: IB Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IB
Bkr.Isum Intr trip: IC Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IC
Bkr.Isum Intr trip Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded in at least one phase.
Bkr.Res TripCmdCr Signal: Resetting of the Counter: total number of trip commands
Bkr.Res Isum trip Signal: Reset summation of the tripping currents
Bkr.WearLevel Alarm Signal: Breaker Wear curve Alarm Level in %
Bkr.WearLevel Lockout Signal: Breaker Wear Curve Lockout Level in %
Bkr.Res Bwear Curve Signal: Res Bwear Curve
Bkr.Isum Intr ph Alm Signal: Isum Intr ph Alm
Bkr.Res Isum Intr ph Alm Signal: Res Isum Intr ph Alm
MStart.Active Signal: Active
MStart.Blo TripCmd Signal: Trip Command blocked
MStart.Trip Signal: Trip
MStart.TripCmd Signal: Trip Command
MStart.Start Signal: Motor is in start mode
MStart.Run Signal: Motor is in run mode
MStart.Stop Signal: Motor is in stop mode
MStart.Blo Signal: Motor is blocked for starting or transition to Run mode
MStart.NOCSBlocked Signal: Motor is prohibited to start due to number of cold start
limits
MStart.SPHBlocked Signal: Motor is prohibited to start due to starts per hour limits
MStart.SPHBlockAlarm Signal: Motor is prohibited to start due to starts per hour limits,
would come active in the next stop
MStart.TBSBlocked Signal: Motor is prohibited to start due to time between starts limits
MStart.ThermalBlock Signal: Thermal block
MStart.RemBlockStart Signal: Motor is prohibited to start due to external blocking through
digital input DI
MStart.TransitionTrip Signal: Start transition fail trip
MStart.ZSSTrip Signal: Zero speed trip (possible locked rotor)
MStart.INSQSP2STFaill Signal: Fail to transit from stop to start based on reported back
time
MStart.INSQSt2RunFail Signal: Fail to transit from start to run based on reported back time
MStart.LATBlock Signal: Long acceleration timer enforced
MStart.ColdStartSeq Signal: Motor cold start sequence flag
MStart.ForcedStart Signal: Motor being forced to start
MStart.TripPhaseReverse Signal: Relay tripped because of phase reverse detection
MStart.EmergOverrideDI Signal: Emergency override start blocking through digital input DI
MStart.EmergOverrideUI Signal: Emergency override start blocking through front panel
www.eaton.com 619
IM02602009E EMR-4000
Name Description
MStart.ABKActive Signal: Anti-backspin is active. For certain applications, such as
pumping a fluid up a pipe, the motor may be driven backward for a
period of time after it stops. The anti-backspin timer prevents
starting the motor while it is spinning in the reverse direction.
MStart.GOCStartBlock Signal: Ground Instantaneous Overcurrent Start Delay. GOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter
MStart.IOCStartBlock Signal: Phase Instantaneous Overcurrent Start Delay. IOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter
MStart.ULoadStartBlock Signal: Underload Start Delay. Underload(Instantaneous
Overcurrent) elements are blocked for the time programmed under
this parameter
MStart.JamStartBlock Signal: JAM Start Delay. JAM(Instantaneous Overcurrent)
elements are blocked for the time programmed under this
parameter
MStart.UnbalStartBlock Signal: Motor start block current unbalance signal
MStart.Blo-Generic1 Generic Start Delay. This value can be used to block any
protective element.1
MStart.Blo-Generic2 Generic Start Delay. This value can be used to block any
protective element.2
MStart.Blo-Generic3 Generic Start Delay. This value can be used to block any
protective element.3
MStart.Blo-Generic4 Generic Start Delay. This value can be used to block any
protective element.4
MStart.Blo-Generic5 Generic Start Delay. This value can be used to block any
protective element.5
MStart.I_Transit Signal: Current transition signal
MStart.T_Transit Signal: Time transition signal
MStart.StartMotorCmd Signal: Start motor command
MStart.MotorStopBlo Signal: Motor stop block other protection functions
MStart.RFD_IA_Normal Signal: System IA RotaryFieldDetection Normal
MStart.RFD_IA_Reverse Signal: System IA RotaryFieldDetection Reverse
MStart.VUnbalStartBlock Signal: Motor start block voltage unbalance signal.
MStart.UnderVStartBlock Signal: Undervoltage Start Delay. Undervoltage elements are
blocked for the time programmed under this parameter
MStart.OverVStartBlock Signal: Overvoltage Start Delay. Overvoltage elements are
blocked for the time programmed under this parameter
MStart.PowerStartBlock Signal: Power Start Delay. Power elements are blocked for the
time programmed under this parameter
MStart.PFacStartBlock Signal: Power Factor Start Delay. Power Factor elements are
blocked for the time programmed under this parameter
MStart.FrqStartBlock Signal: Frequency Start Delay. Frequency elements are blocked
for the time programmed under this parameter
MStart.Remote Open-I State of the module input: Remote Open. User can tie a digital
input to this input. You will see this signals in the recorder
620 www.eaton.com
EMR-4000 IM02602009E
Name Description
MStart.Remote Close-I State of the module input: Remote Close. User can tie a digital
input to this input. You will see this signal in the recorder
MStart.RemoteReset-I State of the module input: Remote Reset
MStart.Motor Start Signal-I State of the module input: Motor Start Signal. User can tie a digital
input to this Input. If "Start-I" becomes true, "StartMotor
Command" becomes true for at least 500ms.
MStart.Stop-I State of the module input: Stop Motor Signal
MStart.StartBlock-I State of the module input: Start Motor Signal
MStart.EmgOvr-I State of the module input: Emergency Override. Signal has to be
active in order to release the thermal capacity of the motor.
Please notice that by doing this you run the risk of damaging the
motor. “EMGOVR” has to be set to “DI” or “DI or UI” for this input
to take effect
MStart.INSQ-I State of the module input: INcomplete SeQuence
MStart.ThermSwitch-I State of the module input: Therm Switch
MStart.ZSS-I State of the module input: Zero Speed Switch
50P[1].Active Signal: Active
50P[1].ExBlo Signal: External Blocking
50P[1].Rvs Blo Signal: Reverse Blocking
50P[1].Blo TripCmd Signal: Trip Command blocked
50P[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
50P[1].Pickup IA Signal: Pickup IA
50P[1].Pickup IB Signal: Pickup IB
50P[1].Pickup IC Signal: Pickup IC
50P[1].Pickup Signal: Pickup
50P[1].Trip Phase A Signal: General Trip Phase A
50P[1].Trip Phase B Signal: General Trip Phase B
50P[1].Trip Phase C Signal: General Trip Phase C
50P[1].Trip Signal: Trip
50P[1].TripCmd Signal: Trip Command
50P[1].DefaultSet Signal: Default Parameter Set
50P[1].AdaptSet 1 Signal: Adaptive Parameter 1
50P[1].AdaptSet 2 Signal: Adaptive Parameter 2
50P[1].AdaptSet 3 Signal: Adaptive Parameter 3
50P[1].AdaptSet 4 Signal: Adaptive Parameter 4
50P[1].ExBlo1-I Module Input State: External Blocking1
50P[1].ExBlo2-I Module Input State: External Blocking2
50P[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50P[1].Rvs Blo-I Module Input State: Reverse Blocking
50P[1].AdaptSet1-I Module Input State: Adaptive Parameter1
50P[1].AdaptSet2-I Module Input State: Adaptive Parameter2
www.eaton.com 621
IM02602009E EMR-4000
Name Description
50P[1].AdaptSet3-I Module Input State: Adaptive Parameter3
50P[1].AdaptSet4-I Module Input State: Adaptive Parameter4
50P[2].Active Signal: Active
50P[2].ExBlo Signal: External Blocking
50P[2].Rvs Blo Signal: Reverse Blocking
50P[2].Blo TripCmd Signal: Trip Command blocked
50P[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
50P[2].Pickup IA Signal: Pickup IA
50P[2].Pickup IB Signal: Pickup IB
50P[2].Pickup IC Signal: Pickup IC
50P[2].Pickup Signal: Pickup
50P[2].Trip Phase A Signal: General Trip Phase A
50P[2].Trip Phase B Signal: General Trip Phase B
50P[2].Trip Phase C Signal: General Trip Phase C
50P[2].Trip Signal: Trip
50P[2].TripCmd Signal: Trip Command
50P[2].DefaultSet Signal: Default Parameter Set
50P[2].AdaptSet 1 Signal: Adaptive Parameter 1
50P[2].AdaptSet 2 Signal: Adaptive Parameter 2
50P[2].AdaptSet 3 Signal: Adaptive Parameter 3
50P[2].AdaptSet 4 Signal: Adaptive Parameter 4
50P[2].ExBlo1-I Module Input State: External Blocking1
50P[2].ExBlo2-I Module Input State: External Blocking2
50P[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50P[2].Rvs Blo-I Module Input State: Reverse Blocking
50P[2].AdaptSet1-I Module Input State: Adaptive Parameter1
50P[2].AdaptSet2-I Module Input State: Adaptive Parameter2
50P[2].AdaptSet3-I Module Input State: Adaptive Parameter3
50P[2].AdaptSet4-I Module Input State: Adaptive Parameter4
50P[3].Active Signal: Active
50P[3].ExBlo Signal: External Blocking
50P[3].Rvs Blo Signal: Reverse Blocking
50P[3].Blo TripCmd Signal: Trip Command blocked
50P[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
50P[3].Pickup IA Signal: Pickup IA
50P[3].Pickup IB Signal: Pickup IB
50P[3].Pickup IC Signal: Pickup IC
50P[3].Pickup Signal: Pickup
50P[3].Trip Phase A Signal: General Trip Phase A
622 www.eaton.com
EMR-4000 IM02602009E
Name Description
50P[3].Trip Phase B Signal: General Trip Phase B
50P[3].Trip Phase C Signal: General Trip Phase C
50P[3].Trip Signal: Trip
50P[3].TripCmd Signal: Trip Command
50P[3].DefaultSet Signal: Default Parameter Set
50P[3].AdaptSet 1 Signal: Adaptive Parameter 1
50P[3].AdaptSet 2 Signal: Adaptive Parameter 2
50P[3].AdaptSet 3 Signal: Adaptive Parameter 3
50P[3].AdaptSet 4 Signal: Adaptive Parameter 4
50P[3].ExBlo1-I Module Input State: External Blocking1
50P[3].ExBlo2-I Module Input State: External Blocking2
50P[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50P[3].Rvs Blo-I Module Input State: Reverse Blocking
50P[3].AdaptSet1-I Module Input State: Adaptive Parameter1
50P[3].AdaptSet2-I Module Input State: Adaptive Parameter2
50P[3].AdaptSet3-I Module Input State: Adaptive Parameter3
50P[3].AdaptSet4-I Module Input State: Adaptive Parameter4
51P[1].Active Signal: Active
51P[1].ExBlo Signal: External Blocking
51P[1].Rvs Blo Signal: Reverse Blocking
51P[1].Blo TripCmd Signal: Trip Command blocked
51P[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
51P[1].Pickup IA Signal: Pickup IA
51P[1].Pickup IB Signal: Pickup IB
51P[1].Pickup IC Signal: Pickup IC
51P[1].Pickup Signal: Pickup
51P[1].Trip Phase A Signal: General Trip Phase A
51P[1].Trip Phase B Signal: General Trip Phase B
51P[1].Trip Phase C Signal: General Trip Phase C
51P[1].Trip Signal: Trip
51P[1].TripCmd Signal: Trip Command
51P[1].DefaultSet Signal: Default Parameter Set
51P[1].AdaptSet 1 Signal: Adaptive Parameter 1
51P[1].AdaptSet 2 Signal: Adaptive Parameter 2
51P[1].AdaptSet 3 Signal: Adaptive Parameter 3
51P[1].AdaptSet 4 Signal: Adaptive Parameter 4
51P[1].ExBlo1-I Module Input State: External Blocking1
51P[1].ExBlo2-I Module Input State: External Blocking2
51P[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
www.eaton.com 623
IM02602009E EMR-4000
Name Description
51P[1].Rvs Blo-I Module Input State: Reverse Blocking
51P[1].AdaptSet1-I Module Input State: Adaptive Parameter1
51P[1].AdaptSet2-I Module Input State: Adaptive Parameter2
51P[1].AdaptSet3-I Module Input State: Adaptive Parameter3
51P[1].AdaptSet4-I Module Input State: Adaptive Parameter4
51P[2].Active Signal: Active
51P[2].ExBlo Signal: External Blocking
51P[2].Rvs Blo Signal: Reverse Blocking
51P[2].Blo TripCmd Signal: Trip Command blocked
51P[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
51P[2].Pickup IA Signal: Pickup IA
51P[2].Pickup IB Signal: Pickup IB
51P[2].Pickup IC Signal: Pickup IC
51P[2].Pickup Signal: Pickup
51P[2].Trip Phase A Signal: General Trip Phase A
51P[2].Trip Phase B Signal: General Trip Phase B
51P[2].Trip Phase C Signal: General Trip Phase C
51P[2].Trip Signal: Trip
51P[2].TripCmd Signal: Trip Command
51P[2].DefaultSet Signal: Default Parameter Set
51P[2].AdaptSet 1 Signal: Adaptive Parameter 1
51P[2].AdaptSet 2 Signal: Adaptive Parameter 2
51P[2].AdaptSet 3 Signal: Adaptive Parameter 3
51P[2].AdaptSet 4 Signal: Adaptive Parameter 4
51P[2].ExBlo1-I Module Input State: External Blocking1
51P[2].ExBlo2-I Module Input State: External Blocking2
51P[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
51P[2].Rvs Blo-I Module Input State: Reverse Blocking
51P[2].AdaptSet1-I Module Input State: Adaptive Parameter1
51P[2].AdaptSet2-I Module Input State: Adaptive Parameter2
51P[2].AdaptSet3-I Module Input State: Adaptive Parameter3
51P[2].AdaptSet4-I Module Input State: Adaptive Parameter4
51P[3].Active Signal: Active
51P[3].ExBlo Signal: External Blocking
51P[3].Rvs Blo Signal: Reverse Blocking
51P[3].Blo TripCmd Signal: Trip Command blocked
51P[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
51P[3].Pickup IA Signal: Pickup IA
51P[3].Pickup IB Signal: Pickup IB
624 www.eaton.com
EMR-4000 IM02602009E
Name Description
51P[3].Pickup IC Signal: Pickup IC
51P[3].Pickup Signal: Pickup
51P[3].Trip Phase A Signal: General Trip Phase A
51P[3].Trip Phase B Signal: General Trip Phase B
51P[3].Trip Phase C Signal: General Trip Phase C
51P[3].Trip Signal: Trip
51P[3].TripCmd Signal: Trip Command
51P[3].DefaultSet Signal: Default Parameter Set
51P[3].AdaptSet 1 Signal: Adaptive Parameter 1
51P[3].AdaptSet 2 Signal: Adaptive Parameter 2
51P[3].AdaptSet 3 Signal: Adaptive Parameter 3
51P[3].AdaptSet 4 Signal: Adaptive Parameter 4
51P[3].ExBlo1-I Module Input State: External Blocking1
51P[3].ExBlo2-I Module Input State: External Blocking2
51P[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
51P[3].Rvs Blo-I Module Input State: Reverse Blocking
51P[3].AdaptSet1-I Module Input State: Adaptive Parameter1
51P[3].AdaptSet2-I Module Input State: Adaptive Parameter2
51P[3].AdaptSet3-I Module Input State: Adaptive Parameter3
51P[3].AdaptSet4-I Module Input State: Adaptive Parameter4
50X[1].Active Signal: Active
50X[1].ExBlo Signal: External Blocking
50X[1].Rvs Blo Signal: Reverse Blocking
50X[1].Blo TripCmd Signal: Trip Command blocked
50X[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
50X[1].Pickup Signal: Pickup IX or IR
50X[1].Trip Signal: Trip
50X[1].TripCmd Signal: Trip Command
50X[1].DefaultSet Signal: Default Parameter Set
50X[1].AdaptSet 1 Signal: Adaptive Parameter 1
50X[1].AdaptSet 2 Signal: Adaptive Parameter 2
50X[1].AdaptSet 3 Signal: Adaptive Parameter 3
50X[1].AdaptSet 4 Signal: Adaptive Parameter 4
50X[1].ExBlo1-I Module Input State: External Blocking1
50X[1].ExBlo2-I Module Input State: External Blocking2
50X[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50X[1].Rvs Blo-I Module Input State: Reverse Blocking
50X[1].AdaptSet1-I Module Input State: Adaptive Parameter1
50X[1].AdaptSet2-I Module Input State: Adaptive Parameter2
www.eaton.com 625
IM02602009E EMR-4000
Name Description
50X[1].AdaptSet3-I Module Input State: Adaptive Parameter3
50X[1].AdaptSet4-I Module Input State: Adaptive Parameter4
50X[2].Active Signal: Active
50X[2].ExBlo Signal: External Blocking
50X[2].Rvs Blo Signal: Reverse Blocking
50X[2].Blo TripCmd Signal: Trip Command blocked
50X[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
50X[2].Pickup Signal: Pickup IX or IR
50X[2].Trip Signal: Trip
50X[2].TripCmd Signal: Trip Command
50X[2].DefaultSet Signal: Default Parameter Set
50X[2].AdaptSet 1 Signal: Adaptive Parameter 1
50X[2].AdaptSet 2 Signal: Adaptive Parameter 2
50X[2].AdaptSet 3 Signal: Adaptive Parameter 3
50X[2].AdaptSet 4 Signal: Adaptive Parameter 4
50X[2].ExBlo1-I Module Input State: External Blocking1
50X[2].ExBlo2-I Module Input State: External Blocking2
50X[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50X[2].Rvs Blo-I Module Input State: Reverse Blocking
50X[2].AdaptSet1-I Module Input State: Adaptive Parameter1
50X[2].AdaptSet2-I Module Input State: Adaptive Parameter2
50X[2].AdaptSet3-I Module Input State: Adaptive Parameter3
50X[2].AdaptSet4-I Module Input State: Adaptive Parameter4
51X[1].Active Signal: Active
51X[1].ExBlo Signal: External Blocking
51X[1].Rvs Blo Signal: Reverse Blocking
51X[1].Blo TripCmd Signal: Trip Command blocked
51X[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
51X[1].Pickup Signal: Pickup IX or IR
51X[1].Trip Signal: Trip
51X[1].TripCmd Signal: Trip Command
51X[1].DefaultSet Signal: Default Parameter Set
51X[1].AdaptSet 1 Signal: Adaptive Parameter 1
51X[1].AdaptSet 2 Signal: Adaptive Parameter 2
51X[1].AdaptSet 3 Signal: Adaptive Parameter 3
51X[1].AdaptSet 4 Signal: Adaptive Parameter 4
51X[1].ExBlo1-I Module Input State: External Blocking1
51X[1].ExBlo2-I Module Input State: External Blocking2
51X[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
626 www.eaton.com
EMR-4000 IM02602009E
Name Description
51X[1].Rvs Blo-I Module Input State: Reverse Blocking
51X[1].AdaptSet1-I Module Input State: Adaptive Parameter1
51X[1].AdaptSet2-I Module Input State: Adaptive Parameter2
51X[1].AdaptSet3-I Module Input State: Adaptive Parameter3
51X[1].AdaptSet4-I Module Input State: Adaptive Parameter4
51X[2].Active Signal: Active
51X[2].ExBlo Signal: External Blocking
51X[2].Rvs Blo Signal: Reverse Blocking
51X[2].Blo TripCmd Signal: Trip Command blocked
51X[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
51X[2].Pickup Signal: Pickup IX or IR
51X[2].Trip Signal: Trip
51X[2].TripCmd Signal: Trip Command
51X[2].DefaultSet Signal: Default Parameter Set
51X[2].AdaptSet 1 Signal: Adaptive Parameter 1
51X[2].AdaptSet 2 Signal: Adaptive Parameter 2
51X[2].AdaptSet 3 Signal: Adaptive Parameter 3
51X[2].AdaptSet 4 Signal: Adaptive Parameter 4
51X[2].ExBlo1-I Module Input State: External Blocking1
51X[2].ExBlo2-I Module Input State: External Blocking2
51X[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
51X[2].Rvs Blo-I Module Input State: Reverse Blocking
51X[2].AdaptSet1-I Module Input State: Adaptive Parameter1
51X[2].AdaptSet2-I Module Input State: Adaptive Parameter2
51X[2].AdaptSet3-I Module Input State: Adaptive Parameter3
51X[2].AdaptSet4-I Module Input State: Adaptive Parameter4
50R[1].Active Signal: Active
50R[1].ExBlo Signal: External Blocking
50R[1].Rvs Blo Signal: Reverse Blocking
50R[1].Blo TripCmd Signal: Trip Command blocked
50R[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
50R[1].Pickup Signal: Pickup IX or IR
50R[1].Trip Signal: Trip
50R[1].TripCmd Signal: Trip Command
50R[1].DefaultSet Signal: Default Parameter Set
50R[1].AdaptSet 1 Signal: Adaptive Parameter 1
50R[1].AdaptSet 2 Signal: Adaptive Parameter 2
50R[1].AdaptSet 3 Signal: Adaptive Parameter 3
50R[1].AdaptSet 4 Signal: Adaptive Parameter 4
www.eaton.com 627
IM02602009E EMR-4000
Name Description
50R[1].ExBlo1-I Module Input State: External Blocking1
50R[1].ExBlo2-I Module Input State: External Blocking2
50R[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50R[1].Rvs Blo-I Module Input State: Reverse Blocking
50R[1].AdaptSet1-I Module Input State: Adaptive Parameter1
50R[1].AdaptSet2-I Module Input State: Adaptive Parameter2
50R[1].AdaptSet3-I Module Input State: Adaptive Parameter3
50R[1].AdaptSet4-I Module Input State: Adaptive Parameter4
50R[2].Active Signal: Active
50R[2].ExBlo Signal: External Blocking
50R[2].Rvs Blo Signal: Reverse Blocking
50R[2].Blo TripCmd Signal: Trip Command blocked
50R[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
50R[2].Pickup Signal: Pickup IX or IR
50R[2].Trip Signal: Trip
50R[2].TripCmd Signal: Trip Command
50R[2].DefaultSet Signal: Default Parameter Set
50R[2].AdaptSet 1 Signal: Adaptive Parameter 1
50R[2].AdaptSet 2 Signal: Adaptive Parameter 2
50R[2].AdaptSet 3 Signal: Adaptive Parameter 3
50R[2].AdaptSet 4 Signal: Adaptive Parameter 4
50R[2].ExBlo1-I Module Input State: External Blocking1
50R[2].ExBlo2-I Module Input State: External Blocking2
50R[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50R[2].Rvs Blo-I Module Input State: Reverse Blocking
50R[2].AdaptSet1-I Module Input State: Adaptive Parameter1
50R[2].AdaptSet2-I Module Input State: Adaptive Parameter2
50R[2].AdaptSet3-I Module Input State: Adaptive Parameter3
50R[2].AdaptSet4-I Module Input State: Adaptive Parameter4
51R[1].Active Signal: Active
51R[1].ExBlo Signal: External Blocking
51R[1].Rvs Blo Signal: Reverse Blocking
51R[1].Blo TripCmd Signal: Trip Command blocked
51R[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
51R[1].Pickup Signal: Pickup IX or IR
51R[1].Trip Signal: Trip
51R[1].TripCmd Signal: Trip Command
51R[1].DefaultSet Signal: Default Parameter Set
51R[1].AdaptSet 1 Signal: Adaptive Parameter 1
628 www.eaton.com
EMR-4000 IM02602009E
Name Description
51R[1].AdaptSet 2 Signal: Adaptive Parameter 2
51R[1].AdaptSet 3 Signal: Adaptive Parameter 3
51R[1].AdaptSet 4 Signal: Adaptive Parameter 4
51R[1].ExBlo1-I Module Input State: External Blocking1
51R[1].ExBlo2-I Module Input State: External Blocking2
51R[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
51R[1].Rvs Blo-I Module Input State: Reverse Blocking
51R[1].AdaptSet1-I Module Input State: Adaptive Parameter1
51R[1].AdaptSet2-I Module Input State: Adaptive Parameter2
51R[1].AdaptSet3-I Module Input State: Adaptive Parameter3
51R[1].AdaptSet4-I Module Input State: Adaptive Parameter4
51R[2].Active Signal: Active
51R[2].ExBlo Signal: External Blocking
51R[2].Rvs Blo Signal: Reverse Blocking
51R[2].Blo TripCmd Signal: Trip Command blocked
51R[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
51R[2].Pickup Signal: Pickup IX or IR
51R[2].Trip Signal: Trip
51R[2].TripCmd Signal: Trip Command
51R[2].DefaultSet Signal: Default Parameter Set
51R[2].AdaptSet 1 Signal: Adaptive Parameter 1
51R[2].AdaptSet 2 Signal: Adaptive Parameter 2
51R[2].AdaptSet 3 Signal: Adaptive Parameter 3
51R[2].AdaptSet 4 Signal: Adaptive Parameter 4
51R[2].ExBlo1-I Module Input State: External Blocking1
51R[2].ExBlo2-I Module Input State: External Blocking2
51R[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
51R[2].Rvs Blo-I Module Input State: Reverse Blocking
51R[2].AdaptSet1-I Module Input State: Adaptive Parameter1
51R[2].AdaptSet2-I Module Input State: Adaptive Parameter2
51R[2].AdaptSet3-I Module Input State: Adaptive Parameter3
51R[2].AdaptSet4-I Module Input State: Adaptive Parameter4
27M[1].Active Signal: Active
27M[1].ExBlo Signal: External Blocking
27M[1].Blo TripCmd Signal: Trip Command blocked
27M[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
27M[1].Pickup Phase A Signal: Pickup Phase A
27M[1].Pickup Phase B Signal: Pickup Phase B
27M[1].Pickup Phase C Signal: Pickup Phase C
www.eaton.com 629
IM02602009E EMR-4000
Name Description
27M[1].Pickup Signal: Pickup Voltage Element
27M[1].Trip Phase A Signal: General Trip Phase A
27M[1].Trip Phase B Signal: General Trip Phase B
27M[1].Trip Phase C Signal: General Trip Phase C
27M[1].Trip Signal: Trip
27M[1].TripCmd Signal: Trip Command
27M[1].ExBlo1-I Module Input State: External Blocking1
27M[1].ExBlo2-I Module Input State: External Blocking2
27M[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
27M[2].Active Signal: Active
27M[2].ExBlo Signal: External Blocking
27M[2].Blo TripCmd Signal: Trip Command blocked
27M[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
27M[2].Pickup Phase A Signal: Pickup Phase A
27M[2].Pickup Phase B Signal: Pickup Phase B
27M[2].Pickup Phase C Signal: Pickup Phase C
27M[2].Pickup Signal: Pickup Voltage Element
27M[2].Trip Phase A Signal: General Trip Phase A
27M[2].Trip Phase B Signal: General Trip Phase B
27M[2].Trip Phase C Signal: General Trip Phase C
27M[2].Trip Signal: Trip
27M[2].TripCmd Signal: Trip Command
27M[2].ExBlo1-I Module Input State: External Blocking1
27M[2].ExBlo2-I Module Input State: External Blocking2
27M[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
59M[1].Active Signal: Active
59M[1].ExBlo Signal: External Blocking
59M[1].Blo TripCmd Signal: Trip Command blocked
59M[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
59M[1].Pickup Phase A Signal: Pickup Phase A
59M[1].Pickup Phase B Signal: Pickup Phase B
59M[1].Pickup Phase C Signal: Pickup Phase C
59M[1].Pickup Signal: Pickup Voltage Element
59M[1].Trip Phase A Signal: General Trip Phase A
59M[1].Trip Phase B Signal: General Trip Phase B
59M[1].Trip Phase C Signal: General Trip Phase C
59M[1].Trip Signal: Trip
59M[1].TripCmd Signal: Trip Command
59M[1].ExBlo1-I Module Input State: External Blocking1
630 www.eaton.com
EMR-4000 IM02602009E
Name Description
59M[1].ExBlo2-I Module Input State: External Blocking2
59M[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
59M[2].Active Signal: Active
59M[2].ExBlo Signal: External Blocking
59M[2].Blo TripCmd Signal: Trip Command blocked
59M[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
59M[2].Pickup Phase A Signal: Pickup Phase A
59M[2].Pickup Phase B Signal: Pickup Phase B
59M[2].Pickup Phase C Signal: Pickup Phase C
59M[2].Pickup Signal: Pickup Voltage Element
59M[2].Trip Phase A Signal: General Trip Phase A
59M[2].Trip Phase B Signal: General Trip Phase B
59M[2].Trip Phase C Signal: General Trip Phase C
59M[2].Trip Signal: Trip
59M[2].TripCmd Signal: Trip Command
59M[2].ExBlo1-I Module Input State: External Blocking1
59M[2].ExBlo2-I Module Input State: External Blocking2
59M[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
27A[1].Active Signal: Active
27A[1].ExBlo Signal: External Blocking
27A[1].Blo TripCmd Signal: Trip Command blocked
27A[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
27A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element
27A[1].Trip Signal: Trip
27A[1].TripCmd Signal: Trip Command
27A[1].ExBlo1-I Module Input State: External Blocking1
27A[1].ExBlo2-I Module Input State: External Blocking2
27A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
27A[2].Active Signal: Active
27A[2].ExBlo Signal: External Blocking
27A[2].Blo TripCmd Signal: Trip Command blocked
27A[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
27A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element
27A[2].Trip Signal: Trip
27A[2].TripCmd Signal: Trip Command
27A[2].ExBlo1-I Module Input State: External Blocking1
27A[2].ExBlo2-I Module Input State: External Blocking2
27A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
59A[1].Active Signal: Active
www.eaton.com 631
IM02602009E EMR-4000
Name Description
59A[1].ExBlo Signal: External Blocking
59A[1].Blo TripCmd Signal: Trip Command blocked
59A[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
59A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element
59A[1].Trip Signal: Trip
59A[1].TripCmd Signal: Trip Command
59A[1].ExBlo1-I Module Input State: External Blocking1
59A[1].ExBlo2-I Module Input State: External Blocking2
59A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
59A[2].Active Signal: Active
59A[2].ExBlo Signal: External Blocking
59A[2].Blo TripCmd Signal: Trip Command blocked
59A[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
59A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element
59A[2].Trip Signal: Trip
59A[2].TripCmd Signal: Trip Command
59A[2].ExBlo1-I Module Input State: External Blocking1
59A[2].ExBlo2-I Module Input State: External Blocking2
59A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
46[1].Active Signal: Active
46[1].ExBlo Signal: External Blocking
46[1].Blo TripCmd Signal: Trip Command blocked
46[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
46[1].Pickup Signal: Pickup Negative Sequence
46[1].Trip Signal: Trip
46[1].TripCmd Signal: Trip Command
46[1].ExBlo1-I Module Input State: External Blocking1
46[1].ExBlo2-I Module Input State: External Blocking2
46[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
46[2].Active Signal: Active
46[2].ExBlo Signal: External Blocking
46[2].Blo TripCmd Signal: Trip Command blocked
46[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
46[2].Pickup Signal: Pickup Negative Sequence
46[2].Trip Signal: Trip
46[2].TripCmd Signal: Trip Command
46[2].ExBlo1-I Module Input State: External Blocking1
46[2].ExBlo2-I Module Input State: External Blocking2
46[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
632 www.eaton.com
EMR-4000 IM02602009E
Name Description
47[1].Active Signal: Active
47[1].ExBlo Signal: External Blocking
47[1].Blo TripCmd Signal: Trip Command blocked
47[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
47[1].Pickup Signal: Pickup Voltage Asymmetry
47[1].Trip Signal: Trip
47[1].TripCmd Signal: Trip Command
47[1].ExBlo1-I Module Input State: External Blocking1
47[1].ExBlo2-I Module Input State: External Blocking2
47[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
47[2].Active Signal: Active
47[2].ExBlo Signal: External Blocking
47[2].Blo TripCmd Signal: Trip Command blocked
47[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
47[2].Pickup Signal: Pickup Voltage Asymmetry
47[2].Trip Signal: Trip
47[2].TripCmd Signal: Trip Command
47[2].ExBlo1-I Module Input State: External Blocking1
47[2].ExBlo2-I Module Input State: External Blocking2
47[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[1].Active Signal: Active
81[1].ExBlo Signal: External Blocking
81[1].Blo by V< Signal: Module is blocked by undervoltage.
81[1].Blo TripCmd Signal: Trip Command blocked
81[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
81[1].Pickup 81 Signal: Pickup Frequency Protection
81[1].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[1].Pickup Vector Surge Signal: Pickup Vector Surge
81[1].Pickup Signal: Pickup Frequency Protection (collective signal)
81[1].Trip 81 Signal: Frequency has exceeded the limit.
81[1].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[1].Trip Vector Surge Signal: Trip delta phi
81[1].Trip Signal: Trip Frequency Protection (collective signal)
81[1].TripCmd Signal: Trip Command
81[1].ExBlo1-I Module Input State: External Blocking1
81[1].ExBlo2-I Module Input State: External Blocking2
81[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[2].Active Signal: Active
www.eaton.com 633
IM02602009E EMR-4000
Name Description
81[2].ExBlo Signal: External Blocking
81[2].Blo by V< Signal: Module is blocked by undervoltage.
81[2].Blo TripCmd Signal: Trip Command blocked
81[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
81[2].Pickup 81 Signal: Pickup Frequency Protection
81[2].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[2].Pickup Vector Surge Signal: Pickup Vector Surge
81[2].Pickup Signal: Pickup Frequency Protection (collective signal)
81[2].Trip 81 Signal: Frequency has exceeded the limit.
81[2].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[2].Trip Vector Surge Signal: Trip delta phi
81[2].Trip Signal: Trip Frequency Protection (collective signal)
81[2].TripCmd Signal: Trip Command
81[2].ExBlo1-I Module Input State: External Blocking1
81[2].ExBlo2-I Module Input State: External Blocking2
81[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[3].Active Signal: Active
81[3].ExBlo Signal: External Blocking
81[3].Blo by V< Signal: Module is blocked by undervoltage.
81[3].Blo TripCmd Signal: Trip Command blocked
81[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
81[3].Pickup 81 Signal: Pickup Frequency Protection
81[3].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[3].Pickup Vector Surge Signal: Pickup Vector Surge
81[3].Pickup Signal: Pickup Frequency Protection (collective signal)
81[3].Trip 81 Signal: Frequency has exceeded the limit.
81[3].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[3].Trip Vector Surge Signal: Trip delta phi
81[3].Trip Signal: Trip Frequency Protection (collective signal)
81[3].TripCmd Signal: Trip Command
81[3].ExBlo1-I Module Input State: External Blocking1
81[3].ExBlo2-I Module Input State: External Blocking2
81[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[4].Active Signal: Active
81[4].ExBlo Signal: External Blocking
81[4].Blo by V< Signal: Module is blocked by undervoltage.
81[4].Blo TripCmd Signal: Trip Command blocked
81[4].ExBlo TripCmd Signal: External Blocking of the Trip Command
634 www.eaton.com
EMR-4000 IM02602009E
Name Description
81[4].Pickup 81 Signal: Pickup Frequency Protection
81[4].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[4].Pickup Vector Surge Signal: Pickup Vector Surge
81[4].Pickup Signal: Pickup Frequency Protection (collective signal)
81[4].Trip 81 Signal: Frequency has exceeded the limit.
81[4].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[4].Trip Vector Surge Signal: Trip delta phi
81[4].Trip Signal: Trip Frequency Protection (collective signal)
81[4].TripCmd Signal: Trip Command
81[4].ExBlo1-I Module Input State: External Blocking1
81[4].ExBlo2-I Module Input State: External Blocking2
81[4].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[5].Active Signal: Active
81[5].ExBlo Signal: External Blocking
81[5].Blo by V< Signal: Module is blocked by undervoltage.
81[5].Blo TripCmd Signal: Trip Command blocked
81[5].ExBlo TripCmd Signal: External Blocking of the Trip Command
81[5].Pickup 81 Signal: Pickup Frequency Protection
81[5].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[5].Pickup Vector Surge Signal: Pickup Vector Surge
81[5].Pickup Signal: Pickup Frequency Protection (collective signal)
81[5].Trip 81 Signal: Frequency has exceeded the limit.
81[5].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[5].Trip Vector Surge Signal: Trip delta phi
81[5].Trip Signal: Trip Frequency Protection (collective signal)
81[5].TripCmd Signal: Trip Command
81[5].ExBlo1-I Module Input State: External Blocking1
81[5].ExBlo2-I Module Input State: External Blocking2
81[5].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
81[6].Active Signal: Active
81[6].ExBlo Signal: External Blocking
81[6].Blo by V< Signal: Module is blocked by undervoltage.
81[6].Blo TripCmd Signal: Trip Command blocked
81[6].ExBlo TripCmd Signal: External Blocking of the Trip Command
81[6].Pickup 81 Signal: Pickup Frequency Protection
81[6].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-
change
81[6].Pickup Vector Surge Signal: Pickup Vector Surge
www.eaton.com 635
IM02602009E EMR-4000
Name Description
81[6].Pickup Signal: Pickup Frequency Protection (collective signal)
81[6].Trip 81 Signal: Frequency has exceeded the limit.
81[6].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT
81[6].Trip Vector Surge Signal: Trip delta phi
81[6].Trip Signal: Trip Frequency Protection (collective signal)
81[6].TripCmd Signal: Trip Command
81[6].ExBlo1-I Module Input State: External Blocking1
81[6].ExBlo2-I Module Input State: External Blocking2
81[6].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
32[1].Active Signal: Active
32[1].ExBlo Signal: External Blocking
32[1].Blo TripCmd Signal: Trip Command blocked
32[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
32[1].Pickup Signal: Pickup Power Protection
32[1].Trip Signal: Trip Power Protection
32[1].TripCmd Signal: Trip Command
32[1].ExBlo1-I Module Input State: External Blocking
32[1].ExBlo2-I Module Input State: External Blocking
32[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
32[2].Active Signal: Active
32[2].ExBlo Signal: External Blocking
32[2].Blo TripCmd Signal: Trip Command blocked
32[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
32[2].Pickup Signal: Pickup Power Protection
32[2].Trip Signal: Trip Power Protection
32[2].TripCmd Signal: Trip Command
32[2].ExBlo1-I Module Input State: External Blocking
32[2].ExBlo2-I Module Input State: External Blocking
32[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
32[3].Active Signal: Active
32[3].ExBlo Signal: External Blocking
32[3].Blo TripCmd Signal: Trip Command blocked
32[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
32[3].Pickup Signal: Pickup Power Protection
32[3].Trip Signal: Trip Power Protection
32[3].TripCmd Signal: Trip Command
32[3].ExBlo1-I Module Input State: External Blocking
32[3].ExBlo2-I Module Input State: External Blocking
32[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
636 www.eaton.com
EMR-4000 IM02602009E
Name Description
32V[1].Active Signal: Active
32V[1].ExBlo Signal: External Blocking
32V[1].Blo TripCmd Signal: Trip Command blocked
32V[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
32V[1].Pickup Signal: Pickup Power Protection
32V[1].Trip Signal: Trip Power Protection
32V[1].TripCmd Signal: Trip Command
32V[1].ExBlo1-I Module Input State: External Blocking
32V[1].ExBlo2-I Module Input State: External Blocking
32V[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
32V[2].Active Signal: Active
32V[2].ExBlo Signal: External Blocking
32V[2].Blo TripCmd Signal: Trip Command blocked
32V[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
32V[2].Pickup Signal: Pickup Power Protection
32V[2].Trip Signal: Trip Power Protection
32V[2].TripCmd Signal: Trip Command
32V[2].ExBlo1-I Module Input State: External Blocking
32V[2].ExBlo2-I Module Input State: External Blocking
32V[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
32V[3].Active Signal: Active
32V[3].ExBlo Signal: External Blocking
32V[3].Blo TripCmd Signal: Trip Command blocked
32V[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
32V[3].Pickup Signal: Pickup Power Protection
32V[3].Trip Signal: Trip Power Protection
32V[3].TripCmd Signal: Trip Command
32V[3].ExBlo1-I Module Input State: External Blocking
32V[3].ExBlo2-I Module Input State: External Blocking
32V[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
PF-55D[1].Active Signal: Active
PF-55D[1].ExBlo Signal: External Blocking
PF-55D[1].Blo TripCmd Signal: Trip Command blocked
PF-55D[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
PF-55D[1].Pickup Signal: Pickup Power Factor
PF-55D[1].Trip Signal: Trip Power Factor
PF-55D[1].TripCmd Signal: Trip Command
PF-55D[1].Compensator Signal: Compensation Signal
PF-55D[1].Impossible Signal: Pickup Power Factor Impossible
www.eaton.com 637
IM02602009E EMR-4000
Name Description
PF-55D[1].ExBlo1-I Module Input State: External Blocking
PF-55D[1].ExBlo2-I Module Input State: External Blocking
PF-55D[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
PF-55D[2].Active Signal: Active
PF-55D[2].ExBlo Signal: External Blocking
PF-55D[2].Blo TripCmd Signal: Trip Command blocked
PF-55D[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
PF-55D[2].Pickup Signal: Pickup Power Factor
PF-55D[2].Trip Signal: Trip Power Factor
PF-55D[2].TripCmd Signal: Trip Command
PF-55D[2].Compensator Signal: Compensation Signal
PF-55D[2].Impossible Signal: Pickup Power Factor Impossible
PF-55D[2].ExBlo1-I Module Input State: External Blocking
PF-55D[2].ExBlo2-I Module Input State: External Blocking
PF-55D[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
PF-55A[1].Active Signal: Active
PF-55A[1].ExBlo Signal: External Blocking
PF-55A[1].Blo TripCmd Signal: Trip Command blocked
PF-55A[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
PF-55A[1].Pickup Signal: Pickup Power Factor
PF-55A[1].Trip Signal: Trip Power Factor
PF-55A[1].TripCmd Signal: Trip Command
PF-55A[1].Compensator Signal: Compensation Signal
PF-55A[1].Impossible Signal: Pickup Power Factor Impossible
PF-55A[1].ExBlo1-I Module Input State: External Blocking
PF-55A[1].ExBlo2-I Module Input State: External Blocking
PF-55A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
PF-55A[2].Active Signal: Active
PF-55A[2].ExBlo Signal: External Blocking
PF-55A[2].Blo TripCmd Signal: Trip Command blocked
PF-55A[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
PF-55A[2].Pickup Signal: Pickup Power Factor
PF-55A[2].Trip Signal: Trip Power Factor
PF-55A[2].TripCmd Signal: Trip Command
PF-55A[2].Compensator Signal: Compensation Signal
PF-55A[2].Impossible Signal: Pickup Power Factor Impossible
PF-55A[2].ExBlo1-I Module Input State: External Blocking
PF-55A[2].ExBlo2-I Module Input State: External Blocking
PF-55A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
638 www.eaton.com
EMR-4000 IM02602009E
Name Description
ZI.Active Signal: Active
ZI.ExBlo Signal: External Blocking
ZI.Blo TripCmd Signal: Trip Command blocked
ZI.ExBlo TripCmd Signal: External Blocking of the Trip Command
ZI.Bkr Blo Signal: Blocked by Breaker Failure
ZI.Phase Pickup Signal: Zone Interlocking Phase Pickup
ZI.Phase Trip Signal: Zone Interlocking Phase Trip
ZI.Ground Pickup Signal: Zone Interlocking Ground Pickup
ZI.Ground Trip Signal: Zone Interlocking Ground Trip
ZI.Pickup Signal: Pickup Zone Interlocking
ZI.Trip Signal: Zone Interlocking Trip
ZI.TripCmd Signal: Zone Interlocking Trip Command
ZI.Phase OUT Signal: Zone Interlocking Phase OUT
ZI.Ground OUT Signal: Zone Interlocking Ground OUT
ZI.OUT Signal: Zone Interlocking OUT
ZI.IN Signal: Zone Interlocking IN
ZI.ExBlo1-I Module Input State: External Blocking1
ZI.ExBlo2-I Module Input State: External Blocking2
ZI.ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
ZI.Bkr Blo-I Signal: Blocked by Breaker Failure
49.Alarm Pickup Signal: Alarm Pickup
49.Alarm Timeout Signal: Alarm Timeout
49.RTD effective RTD effective
49.Load above SF Load above Service Factor
49.Active Signal: Active
49.ExBlo Signal: External Blocking
49.Blo TripCmd Signal: Trip Command blocked
49.ExBlo TripCmd Signal: External Blocking of the Trip Command
49.Pickup Signal: Pickup
49.Trip Signal: Trip
49.TripCmd Signal: Trip Command
49.ExBlo1 Module Input State: External Blocking
49.ExBlo2 Module Input State: External Blocking
49.ExBlo TripCmd Module Input State: External Blocking of the Trip Command
50J[1].Active Signal: Active
50J[1].ExBlo Signal: External Blocking
50J[1].Rvs Blo Signal: Reverse Blocking
50J[1].Blo TripCmd Signal: Trip Command blocked
50J[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
www.eaton.com 639
IM02602009E EMR-4000
Name Description
50J[1].Pickup Signal: Pickup
50J[1].Trip Signal: Trip
50J[1].TripCmd Signal: Trip Command
50J[1].ExBlo1-I Module Input State: External Blocking1
50J[1].ExBlo2-I Module Input State: External Blocking2
50J[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50J[1].Rvs Blo-I Module Input State: Reverse Blocking
50J[2].Active Signal: Active
50J[2].ExBlo Signal: External Blocking
50J[2].Rvs Blo Signal: Reverse Blocking
50J[2].Blo TripCmd Signal: Trip Command blocked
50J[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
50J[2].Pickup Signal: Pickup
50J[2].Trip Signal: Trip
50J[2].TripCmd Signal: Trip Command
50J[2].ExBlo1-I Module Input State: External Blocking1
50J[2].ExBlo2-I Module Input State: External Blocking2
50J[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
50J[2].Rvs Blo-I Module Input State: Reverse Blocking
37[1].Active Signal: Active
37[1].ExBlo Signal: External Blocking
37[1].Rvs Blo Signal: Reverse Blocking
37[1].Blo TripCmd Signal: Trip Command blocked
37[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
37[1].Pickup Signal: Pickup
37[1].Trip Signal: Trip
37[1].TripCmd Signal: Trip Command
37[1].ExBlo1-I Module Input State: External Blocking1
37[1].ExBlo2-I Module Input State: External Blocking2
37[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
37[1].Rvs Blo-I Module Input State: Reverse Blocking
37[2].Active Signal: Active
37[2].ExBlo Signal: External Blocking
37[2].Rvs Blo Signal: Reverse Blocking
37[2].Blo TripCmd Signal: Trip Command blocked
37[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
37[2].Pickup Signal: Pickup
37[2].Trip Signal: Trip
37[2].TripCmd Signal: Trip Command
640 www.eaton.com
EMR-4000 IM02602009E
Name Description
37[2].ExBlo1-I Module Input State: External Blocking1
37[2].ExBlo2-I Module Input State: External Blocking2
37[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
37[2].Rvs Blo-I Module Input State: Reverse Blocking
37[3].Active Signal: Active
37[3].ExBlo Signal: External Blocking
37[3].Rvs Blo Signal: Reverse Blocking
37[3].Blo TripCmd Signal: Trip Command blocked
37[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
37[3].Pickup Signal: Pickup
37[3].Trip Signal: Trip
37[3].TripCmd Signal: Trip Command
37[3].ExBlo1-I Module Input State: External Blocking1
37[3].ExBlo2-I Module Input State: External Blocking2
37[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
37[3].Rvs Blo-I Module Input State: Reverse Blocking
MLS.Active Signal: Active
MLS.ExBlo Signal: External Blocking
MLS.Pickup Signal: Pickup
MLS.Trip Signal: Trip
MLS.ExBlo1-I Module Input State: External Blocking1
MLS.ExBlo2-I Module Input State: External Blocking2
RTD.Active Signal: Active
RTD.ExBlo Signal: External Blocking
RTD.Blo TripCmd Signal: Trip Command blocked
RTD.ExBlo TripCmd Signal: External Blocking of the Trip Command
RTD.Alarm Alarm RTD Temperature Protection
RTD.Trip Signal: Trip
RTD.TripCmd Signal: Trip Command
RTD.WD 1 Trip Winding 1 Signal: Trip
RTD.WD 1 Alarm Winding 1 Alarm RTD Temperature Protection
RTD.WD 1 Timeout Alarm Winding 1 Timeout Alarm
RTD.WD 1 Invalid Winding 1 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.WD 2 Trip Winding 2 Signal: Trip
RTD.WD 2 Alarm Winding 2 Alarm RTD Temperature Protection
RTD.WD 2 Timeout Alarm Winding 2 Timeout Alarm
RTD.WD 2 Invalid Winding 2 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.WD 3 Trip Winding 3 Signal: Trip
www.eaton.com 641
IM02602009E EMR-4000
Name Description
RTD.WD 3 Alarm Winding 3 Alarm RTD Temperature Protection
RTD.WD 3 Timeout Alarm Winding 3 Timeout Alarm
RTD.WD 3 Invalid Winding 3 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.WD 4 Trip Winding 4 Signal: Trip
RTD.WD 4 Alarm Winding 4 Alarm RTD Temperature Protection
RTD.WD 4 Timeout Alarm Winding 4 Timeout Alarm
RTD.WD 4 Invalid Winding 4 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.WD 5 Trip Winding 5 Signal: Trip
RTD.WD 5 Alarm Winding 5 Alarm RTD Temperature Protection
RTD.WD 5 Timeout Alarm Winding 5 Timeout Alarm
RTD.WD 5 Invalid Winding 5 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.WD 6 Trip Winding 6 Signal: Trip
RTD.WD 6 Alarm Winding 6 Alarm RTD Temperature Protection
RTD.WD 6 Timeout Alarm Winding 6 Timeout Alarm
RTD.WD 6 Invalid Winding 6 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.MB 1 Trip Motor Bearing 1 Signal: Trip
RTD.MB 1 Alarm Motor Bearing 1 Alarm RTD Temperature Protection
RTD.MB 1 Timeout Alarm Motor Bearing 1 Timeout Alarm
RTD.MB 1 Invalid Motor Bearing 1 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
RTD.MB 2 Trip Motor Bearing 2 Signal: Trip
RTD.MB 2 Alarm MB 2 Alarm RTD Temperature Protection
RTD.MB 2 Timeout Alarm Motor Bearing 2 Timeout Alarm
RTD.MB 2 Invalid Motor Bearing 2 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
RTD.LB 1 Trip Load Bearing 1 Signal: Trip
RTD.LB 1 Alarm LB 1 Alarm RTD Temperature Protection
RTD.LB 1 Timeout Alarm Load Bearing 1 Timeout Alarm
RTD.LB 1 Invalid Load Bearing 1 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
RTD.LB 2 Trip Load Bearing 2 Signal: Trip
RTD.LB 2 Alarm LB 2 Alarm RTD Temperature Protection
RTD.LB 2 Timeout Alarm Load Bearing 2 Timeout Alarm
RTD.LB 2 Invalid Load Bearing 2 Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
RTD.Aux1 Trip Auxiliary 1 Signal: Trip
RTD.Aux1 Alarm Auxiliary 1 Alarm RTD Temperature Protection
RTD.Aux1 Timeout Alarm Auxiliary 1 Timeout Alarm
642 www.eaton.com
EMR-4000 IM02602009E
Name Description
RTD.Aux1 Invalid Auxiliary 1 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.Trip WD Group Trip all Windings
RTD.Alarm WD Group Alarm all Windings
RTD.TimeoutAlmWDGrp TimeoutAlmWDGrp
RTD.WD Group Invalid Winding Group Signal: Invalid Temperature Measurement Value
(e.g caused by an defective or interrupted RTD Measurement)
RTD.Trip MB Group Trip all Motor Bearings
RTD.Alarm MB Group Alarm all Motor Bearings
RTD.TimeoutAlmMBGrp Timeout Alarm all Motor Bearings
RTD.MB Group Invalid Motor Bearing Group Signal: Invalid Temperature Measurement
Value (e.g caused by an defective or interrupted RTD
Measurement)
RTD.Trip LB Group Trip all Load Bearings
RTD.Alarm LB Group Alarm all Load Bearings
RTD.TimeoutAlmLBGrp Timeout Alarm all Load Bearings
RTD.LB Group Invalid Load Bearing Group Signal: Invalid Temperature Measurement
Value (e.g caused by an defective or interrupted RTD
Measurement)
RTD.Trip Any Group Trip Any Group
RTD.Alarm Any Group Alarm Any Group
RTD.TimeoutAlmAnyGrp Timeout Alarm Any Group
RTD.Voting Trip Grp 1 Voting Trip Grp 1
RTD.Voting Trip Grp 2 Voting Trip Grp 2
RTD.Timeout Alarm Alarm timeout expired
RTD.Aux2 Trip Auxiliary 2 Signal: Trip
RTD.Aux2 Alarm Auxiliary 2 Alarm RTD Temperature Protection
RTD.Aux2 Timeout Alarm Auxiliary 2 Timeout Alarm
RTD.Aux2 Invalid Auxiliary 2 Signal: Invalid Temperature Measurement Value (e.g
caused by an defective or interrupted RTD Measurement)
RTD.Trip Aux Group Trip Auxiliary Group
RTD.Alarm Aux Group Alarm Auxiliary Group
RTD.TimeoutAlmAuxGrp Timeout Alarm Auxiliary Group
RTD.AuxGrpInvalid Invalid Auxiliary Group
RTD.ExBlo1-I Module Input State: External Blocking1
RTD.ExBlo2-I Module Input State: External Blocking2
RTD.ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
Motor Diagnosis.Active Signal: Active
Motor Diagnosis.ExBlo Signal: External Blocking
Motor Diagnosis.BBDAlarm Signal: BBDAlarm
Motor Diagnosis.BBDReliable Signal: Indicates if signal is valid for a broken bar detection.
www.eaton.com 643
IM02602009E EMR-4000
Name Description
Motor Diagnosis.ExBlo1-I Module Input State: External Blocking1
Motor Diagnosis.ExBlo2-I Module Input State: External Blocking2
SOTF.Active Signal: Active
SOTF.ExBlo Signal: External Blocking
SOTF.Rvs Blo Signal: Reverse Blocking
SOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to
modify Overcurrent Protection Settings.
SOTF.I< Signal: No Load Current.
SOTF.ExBlo1-I Module Input State: External Blocking
SOTF.ExBlo2-I Module Input State: External Blocking
SOTF.Rvs Blo-I Module Input State: Reverse Blocking
SOTF.Ext SOTF-I Module Input State: External Switch Onto Fault Alarm
ExP[1].Active Signal: Active
ExP[1].ExBlo Signal: External Blocking
ExP[1].Blo TripCmd Signal: Trip Command blocked
ExP[1].ExBlo TripCmd Signal: External Blocking of the Trip Command
ExP[1].Alarm Signal: Alarm
ExP[1].Trip Signal: Trip
ExP[1].TripCmd Signal: Trip Command
ExP[1].ExBlo1-I Module Input State: External Blocking1
ExP[1].ExBlo2-I Module Input State: External Blocking2
ExP[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
ExP[1].Alarm-I Module Input State: Alarm
ExP[1].Trip-I Module Input State: Trip
ExP[2].Active Signal: Active
ExP[2].ExBlo Signal: External Blocking
ExP[2].Blo TripCmd Signal: Trip Command blocked
ExP[2].ExBlo TripCmd Signal: External Blocking of the Trip Command
ExP[2].Alarm Signal: Alarm
ExP[2].Trip Signal: Trip
ExP[2].TripCmd Signal: Trip Command
ExP[2].ExBlo1-I Module Input State: External Blocking1
ExP[2].ExBlo2-I Module Input State: External Blocking2
ExP[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
ExP[2].Alarm-I Module Input State: Alarm
ExP[2].Trip-I Module Input State: Trip
ExP[3].Active Signal: Active
ExP[3].ExBlo Signal: External Blocking
ExP[3].Blo TripCmd Signal: Trip Command blocked
644 www.eaton.com
EMR-4000 IM02602009E
Name Description
ExP[3].ExBlo TripCmd Signal: External Blocking of the Trip Command
ExP[3].Alarm Signal: Alarm
ExP[3].Trip Signal: Trip
ExP[3].TripCmd Signal: Trip Command
ExP[3].ExBlo1-I Module Input State: External Blocking1
ExP[3].ExBlo2-I Module Input State: External Blocking2
ExP[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
ExP[3].Alarm-I Module Input State: Alarm
ExP[3].Trip-I Module Input State: Trip
ExP[4].Active Signal: Active
ExP[4].ExBlo Signal: External Blocking
ExP[4].Blo TripCmd Signal: Trip Command blocked
ExP[4].ExBlo TripCmd Signal: External Blocking of the Trip Command
ExP[4].Alarm Signal: Alarm
ExP[4].Trip Signal: Trip
ExP[4].TripCmd Signal: Trip Command
ExP[4].ExBlo1-I Module Input State: External Blocking1
ExP[4].ExBlo2-I Module Input State: External Blocking2
ExP[4].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command
ExP[4].Alarm-I Module Input State: Alarm
ExP[4].Trip-I Module Input State: Trip
BF.Active Signal: Active
BF.ExBlo Signal: External Blocking
BF.Pickup Signal: BF-Module Started (Pickup)
BF.Trip Signal: Breaker Failure Trip
BF.Lockout Signal: Lockout
BF.Res Lockout Signal: Reset Lockout
BF.ExBlo1-I Module Input State: External Blocking1
BF.ExBlo2-I Module Input State: External Blocking2
BF.Trigger1 Module Input: Trigger that will start the BF
BF.Trigger2 Module Input: Trigger that will start the BF
BF.Trigger3 Module Input: Trigger that will start the BF
TCM.Active Signal: Active
TCM.ExBlo Signal: External Blocking
TCM.Pickup Signal: Pickup Trip Circuit Supervision
TCM.Not Possible Not possible because no state indicator assigned to the breaker.
TCM.CinBkr-52a-I Feed-back signal of the Bkr (52a)
TCM.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)
TCM.ExBlo1-I Module Input State: External Blocking1
www.eaton.com 645
IM02602009E EMR-4000
Name Description
TCM.ExBlo2-I Module Input State: External Blocking2
CTS.Active Signal: Active
CTS.ExBlo Signal: External Blocking
CTS.Pickup Signal: Pickup Current Transformer Measuring Circuit Supervision
CTS.ExBlo1-I Module Input State: External Blocking1
CTS.ExBlo2-I Module Input State: External Blocking2
LOP.Active Signal: Active
LOP.ExBlo Signal: External Blocking
LOP.Pickup Signal: Pickup Loss of Potential
LOP.LOP Blo Signal: Loss of Potential blocks other elements
LOP.Ex FF VT Signal: Ex FF VT
LOP.Ex FF GVT Signal: Alarm Fuse Failure Ground Voltage Transformers
LOP.ExBlo1-I Module Input State: External Blocking1
LOP.ExBlo2-I Module Input State: External Blocking2
LOP.Ex FF VT-I State of the module input: Alarm Fuse Failure Voltage
Transformers
LOP.Ex FF GVT-I State of the module input: Alarm Fuse Failure Ground Voltage
Transformers
URTD.WD1 Superv Signal: Supervision Channel WD1
URTD.WD2 Superv Signal: Supervision Channel WD2
URTD.WD3 Superv Signal: Supervision Channel WD3
URTD.WD4 Superv Signal: Supervision Channel WD4
URTD.WD5 Superv Signal: Supervision Channel WD5
URTD.WD6 Superv Signal: Supervision Channel WD6
URTD.MB1 Superv Signal: Supervision Channel MB1
URTD.MB2 Superv Signal: Supervision Channel MB2
URTD.LB1 Superv Signal: Supervision Channel LB1
URTD.LB2 Superv Signal: Supervision Channel LB2
URTD.Aux1 Superv Signal: Supervision Channel Aux1
URTD.Aux2 Superv Signal: Supervision Channel Aux2
URTD.Superv Signal: URTD Supervision Channel
URTD.active Signal: URTD active
URTD.Outs forced Signal: The State of at least one Relay Output has been set by
force. That means that the state of at least one Relay is forced
and hence does not show the state of the assigned signals.
Wired Inputs.Bkr Trouble-I Breaker Trouble
Wired Inputs.52a M1-I State of the module input: Main 1 Breaker Closed
Wired Inputs.52b M1-I State of the module input: Main 1 Breaker Open
Wired Inputs.TOCa M1-I State of the module input: Main 1 Breaker Connected
Wired Inputs.43/10 M1-I State of the module input: Main 1 Breaker Selected To Trip
646 www.eaton.com
EMR-4000 IM02602009E
Name Description
Wired Inputs.52a M2-I State of the module input: Main 2 Breaker Closed
Wired Inputs.52b M2-I State of the module input: Main 2 Breaker Open
Wired Inputs.TOCa M2-I State of the module input: Main 2 Breaker Connected
Wired Inputs.43/10 M2-I State of the module input: Main 2 Breaker Selected To Trip
Wired Inputs.52a T -I State of the module input: Tie Breaker Closed
Wired Inputs.52b T-I State of the module input: Tie Breaker Open
Wired Inputs.TOCa T-I State of the module input: Tie Breaker Connected
Wired Inputs.43/10 T-I State of the module input: Tie Breaker Selected To Trip
Wired Inputs.43 M-I State of the module input: System In Manual
Wired Inputs.43 A-I State of the module input: System in Auto
Wired Inputs.43 P1-I State of the module input: Preferred Source 1
Wired Inputs.43 P2-I State of the module input: Preferred Source 2
Wired Inputs.MainCont-I State of the module input: Main Contactor
Wired Inputs.StartCont-I State of the module input: Starting Contactor
Wired Inputs.RunCont-I State of the module input: Running Contactor (inc sequence)
Wired Inputs.Start -I State of the module input: Start
Wired Inputs.Stop-I State of the module input: Stop
Wired Inputs.ExtPer1-I State of the module input: $$
(External_Signals_External_Permissive_h)
Wired Inputs.ExtPer2-I State of the module input: $$
(External_Signals_External_Permissive_h)
Wired Inputs.ExtTip1-I State of the module input: External Trip1
Wired Inputs.ExtTip-I2 State of the module input: External Trip2
Wired Inputs.Forward-I State of the module input: Forward
Wired Inputs.Reverse-I State of the module input: Reverse
Wired Inputs.GrpSetSelect-I State of the module input: Group Setting Select
Wired Inputs.Jog Forward-I State of the module input: JogFow
Wired Inputs.Jog reverse-I State of the module input: JogRev
Wired Inputs.speed1-I State of the module input: Speed1
Wired Inputs.Local-I State of the module input: Local (Remote)
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
RO-4Z X2.ZI OUT Signal: Zone Interlocking OUT
RO-4Z X2.RO 1 Signal: Relay Output
www.eaton.com 647
IM02602009E EMR-4000
Name Description
RO-4Z X2.RO 2 Signal: Relay Output
RO-4Z X2.RO 3 Signal: Relay Output
RO-4Z X2.RO 4 Signal: Relay Output
RO-4Z X2.DISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform
maintenance while eliminating the risk of taking an entire process
off-line. (Note: Zone Interlocking and Supervision Contact cannot
be disarmed). YOU MUST ENSURE that the relays are ARMED
AGAIN after maintenance
RO-4Z X2.Outs forced Signal: The State of at least one Relay Output has been set by
force. That means that the state of at least one Relay is forced
and hence does not show the state of the assigned signals.
Analog Outputs.Active Active
Analog Outputs.Active Active
Analog Outputs.Active Active
Analog Outputs.Active Active
Event rec.Res all rec Signal: All records deleted
Waveform rec.Recording Signal: Recording
Waveform rec.Memory full Signal: Memory Full
Waveform rec.Clear fail Signal: Clear Failure in Memory
Waveform rec.Res all rec Signal: All records deleted
Waveform rec.Res record Signal: Delete Record
Waveform rec.Man. Trigger Signal: Manual Trigger
Waveform rec.Start1-I State of the module input: Trigger event / start recording if:
Waveform rec.Start2-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start3-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start4-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start5-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start6-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start7-I State of the module inpu: Trigger event / start recording if:
Waveform rec.Start8-I State of the module inpu: Trigger event / start recording if:
Fault rec.Res record Signal: Delete Record
Fault rec.Man. Trigger Signal: Manual Trigger
Fault rec.Start1-I State of the module input: Trigger event / start recording if:
Fault rec.Start2-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start3-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start4-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start5-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start6-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start7-I State of the module inpu: Trigger event / start recording if:
Fault rec.Start8-I State of the module inpu: Trigger event / start recording if:
Trend rec.Hand Reset Hand Reset
648 www.eaton.com
EMR-4000 IM02602009E
Name Description
ECr.Cr OflwW VAh Net Signal: Counter Overflow VAh Net
ECr.Cr OflwW Wh Net Signal: Counter Overflow Wh Net
ECr.Cr OflwW Wh Fwd Signal: Counter Overflow Wh Fwd
ECr.Cr OflwW Wh Rev Signal: Counter Overflow Wh Rev
ECr.Cr OflwW VArh Net Signal: Counter Overflow VArh Net
ECr.Cr OflwW VArh Lag Signal: Counter Overflow VArh Lag
ECr.Cr OflwW VArh Lead Signal: Counter Overflow VArh Lead
ECr.VAh Net Res Cr Signal: VAh Net Reset Counter
ECr.Wh Net Res Cr Signal: Wh Net Reset Counter
ECr.Wh Fwd Res Cr Signal: Wh Fwd Reset Counter
ECr.Wh Rev Res Cr Signal: Wh Rev Reset Counter
ECr.VArh Net Res Cr Signal: VArh Net Reset Counter
ECr.VArh Lag Res Cr Signal: VArh Lag Reset Counter
ECr.VArh Lead Res Cr Signal: VArh Lead Reset Counter
ECr.Res all Energy Cr Signal: Reset of all Energy Counters
ECr.Cr OflwW VAh Net Signal: Counter VAh Net will overflow soon
ECr.Cr OflwW Wh Net Signal: Counter Wh Net will overflow soon
ECr.Cr OflwW Wh Fwd Signal: Counter Wh Fwd will overflow soon
ECr.Cr OflwW Wh Rev Signal: Counter Wh Rev will overflow soon
ECr.Cr OflwW VArh Net Signal: Counter VArh Net will overflow soon
ECr.Cr OflwW VArh Lag Signal: Counter VArh Lag will overflow soon
ECr.Cr OflwW VArh Lead Signal: Counter VArh Lead will overflow soon
Start rec.Storing Signal: Data are saved
Start rec.MotorStart Module input state: Start of recorder
Start rec.MotorRun Module input state: Motor is in run mode
Start rec.Motor Speed2 Module input state: Motor operates in speed 2
Start rec.ITransit Module input state: Motor operations transition on current
Modbus.Transmission Signal: Communication Active
Modbus.Comm Cmd 1 Communication Command
Modbus.Comm Cmd 2 Communication Command
Modbus.Comm Cmd 3 Communication Command
Modbus.Comm Cmd 4 Communication Command
Modbus.Comm Cmd 5 Communication Command
Modbus.Comm Cmd 6 Communication Command
Modbus.Comm Cmd 7 Communication Command
Modbus.Comm Cmd 8 Communication Command
Modbus.Comm Cmd 9 Communication Command
Modbus.Comm Cmd 10 Communication Command
Modbus.Comm Cmd 11 Communication Command
www.eaton.com 649
IM02602009E EMR-4000
Name Description
Modbus.Comm Cmd 12 Communication Command
Modbus.Comm Cmd 13 Communication Command
Modbus.Comm Cmd 14 Communication Command
Modbus.Comm Cmd 15 Communication Command
Modbus.Comm Cmd 16 Communication Command
IEC61850.VirtInp1 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp2 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp3 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp4 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp5 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp6 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp7 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp8 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp9 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp10 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp11 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp12 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp13 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp14 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp15 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtInp16 Signal: Virtual Input (IEC61850 GGIO Ind)
IEC61850.VirtOut1-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut2-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut3-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut4-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut5-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut6-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut7-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut8-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut9-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut10-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut11-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut12-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut13-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut14-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut15-I Module input state: Binary state of the Virtual Output (GGIO)
IEC61850.VirtOut16-I Module input state: Binary state of the Virtual Output (GGIO)
IRIG-B.Active Signal: Active
IRIG-B.Inverted Signal: IRIG-B inverted
650 www.eaton.com
EMR-4000 IM02602009E
Name Description
IRIG-B.Control Signal1 Signal: IRIG-B Control Signal
IRIG-B.Control Signal2 Signal: IRIG-B Control Signal
IRIG-B.Control Signal4 Signal: IRIG-B Control Signal
IRIG-B.Control Signal5 Signal: IRIG-B Control Signal
IRIG-B.Control Signal6 Signal: IRIG-B Control Signal
IRIG-B.Control Signal7 Signal: IRIG-B Control Signal
IRIG-B.Control Signal8 Signal: IRIG-B Control Signal
IRIG-B.Control Signal9 Signal: IRIG-B Control Signal
IRIG-B.Control Signal10 Signal: IRIG-B Control Signal
IRIG-B.Control Signal11 Signal: IRIG-B Control Signal
IRIG-B.Control Signal12 Signal: IRIG-B Control Signal
IRIG-B.Control Signal13 Signal: IRIG-B Control Signal
IRIG-B.Control Signal14 Signal: IRIG-B Control Signal
IRIG-B.Control Signal15 Signal: IRIG-B Control Signal
IRIG-B.Control Signal16 Signal: IRIG-B Control Signal
IRIG-B.Control Signal17 Signal: IRIG-B Control Signal
IRIG-B.Control Signal18 Signal: IRIG-B Control Signal
SNTP.SNTP active Signal: If there is no valid SNTP signal for 120 sec, SNTP is
regarded as inactive.
Statistics.ResFc all Signal: Resetting of all Statistic values (Current Demand, Power
Demand, Min, Max)
Statistics.ResFc I Demand Signal: Resetting of Statistics - Current Demand (avg, peak avg)
Statistics.ResFc P Demand Signal: Resetting of Statistics - Power Demand (avg, peak avg)
Statistics.ResFc Max Signal: Resetting of all Maximum values
Statistics.ResFc Min Signal: Resetting of all Minimum values
Statistics.StartFc 1-I State of the module input: Start of Statistics 1 (Update the
displayed Demand )
Statistics.StartFc 2-I State of the module input: Start of Statistics 2 (Update the
displayed Demand )
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE1.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE1.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE1.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE1.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE1.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
www.eaton.com 651
IM02602009E EMR-4000
Name Description
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE2.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE2.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE2.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE2.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE3.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE3.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE3.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE3.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE4.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE4.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE4.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE4.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE5.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE5.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE5.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE5.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate In1-I State of the module input: Assignment of the Input Signal
652 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE6.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE6.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE6.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE6.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE7.Gate Out Signal: Output of the logic gate
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE7.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE7.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE7.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE7.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE8.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE8.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE8.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE8.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE8.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE9.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE9.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE9.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE9.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE10.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE10.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE10.Gate In4-I State of the module input: Assignment of the Input Signal
www.eaton.com 653
IM02602009E EMR-4000
Name Description
Logic.LE10.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE11.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE11.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE11.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE11.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE12.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE12.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE12.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE12.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE13.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE13.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE13.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE13.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE14.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE14.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE14.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE14.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
654 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE15.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE15.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE15.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE15.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE16.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE16.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE16.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE16.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE17.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE17.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE17.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE17.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE17.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE18.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE18.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE18.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE18.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate In1-I State of the module input: Assignment of the Input Signal
www.eaton.com 655
IM02602009E EMR-4000
Name Description
Logic.LE19.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE19.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE19.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE19.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE20.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE20.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE20.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE20.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE21.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE21.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE21.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE21.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE22.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE22.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE22.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE22.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE23.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE23.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE23.Gate In4-I State of the module input: Assignment of the Input Signal
656 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE23.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE24.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE24.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE24.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE24.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE25.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE25.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE25.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE25.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE26.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE26.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE26.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE26.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE27.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE27.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE27.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE27.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
www.eaton.com 657
IM02602009E EMR-4000
Name Description
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE28.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE28.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE28.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE28.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE29.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE29.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE29.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE29.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE30.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE30.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE30.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE30.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE31.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE31.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE31.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE31.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate In1-I State of the module input: Assignment of the Input Signal
658 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE32.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE32.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE32.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE32.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE33.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE33.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE33.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE33.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE34.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE34.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE34.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE34.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE35.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE35.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE35.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE35.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE36.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE36.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE36.Gate In4-I State of the module input: Assignment of the Input Signal
www.eaton.com 659
IM02602009E EMR-4000
Name Description
Logic.LE36.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE37.Gate Out Signal: Output of the logic gate
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE37.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE37.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE37.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE37.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE38.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE38.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE38.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE38.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE39.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE39.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE39.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE39.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE40.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE40.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE40.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE40.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
660 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE41.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE41.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE41.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE41.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE42.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE42.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE42.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE42.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE43.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE43.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE43.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE43.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE44.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE44.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE44.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE44.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate In1-I State of the module input: Assignment of the Input Signal
www.eaton.com 661
IM02602009E EMR-4000
Name Description
Logic.LE45.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE45.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE45.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE45.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE46.Gate Out Signal: Output of the logic gate
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE46.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE46.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE46.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE46.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE47.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE47.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE47.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE47.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE47.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE48.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE48.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE48.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE48.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE49.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE49.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE49.Gate In4-I State of the module input: Assignment of the Input Signal
662 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE49.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE50.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE50.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE50.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE50.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE51.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE51.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE51.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE51.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE52.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE52.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE52.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE52.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE53.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE53.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE53.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE53.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
www.eaton.com 663
IM02602009E EMR-4000
Name Description
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE54.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE54.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE54.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE54.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE55.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE55.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE55.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE55.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE56.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE56.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE56.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE56.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE56.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE57.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE57.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE57.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE57.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate In1-I State of the module input: Assignment of the Input Signal
664 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE58.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE58.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE58.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE58.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE59.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE59.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE59.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE59.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE60.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE60.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE60.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE60.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE61.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE61.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE61.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE61.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE62.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE62.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE62.Gate In4-I State of the module input: Assignment of the Input Signal
www.eaton.com 665
IM02602009E EMR-4000
Name Description
Logic.LE62.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE63.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE63.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE63.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE63.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE64.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE64.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE64.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE64.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE65.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE65.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE65.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE65.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE66.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE66.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE66.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE66.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
666 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE67.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE67.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE67.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE67.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE68.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE68.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE68.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE68.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE69.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE69.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE69.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE69.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE70.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE70.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE70.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE70.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate In1-I State of the module input: Assignment of the Input Signal
www.eaton.com 667
IM02602009E EMR-4000
Name Description
Logic.LE71.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE71.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE71.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE71.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE72.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE72.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE72.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE72.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE73.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE73.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE73.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE73.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE74.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE74.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE74.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE74.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE75.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE75.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE75.Gate In4-I State of the module input: Assignment of the Input Signal
668 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE75.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE76.Gate Out Signal: Output of the logic gate
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE76.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE76.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE76.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE76.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE77.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE77.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE77.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE77.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE78.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE78.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE78.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE78.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE79.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE79.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE79.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE79.Reset Latch-I State of the module input: Reset Signal for the Latching
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
www.eaton.com 669
IM02602009E EMR-4000
Name Description
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate In1-I State of the module input: Assignment of the Input Signal
Logic.LE80.Gate In2-I State of the module input: Assignment of the Input Signal
Logic.LE80.Gate In3-I State of the module input: Assignment of the Input Signal
Logic.LE80.Gate In4-I State of the module input: Assignment of the Input Signal
Logic.LE80.Reset Latch-I State of the module input: Reset Signal for the Latching
SysA.Active Signal: Active
SysA.ExBlo Signal: External Blocking
SysA.Alarm Watt Power Signal: Alarm WATTS peak
SysA.Alarm VAr Power Signal: Alarm VArs peak
SysA.Alarm VA Power Signal: Alarm VAs peak
SysA.Alarm Watt Demand Signal: Alarm WATTS demand value
SysA.Alarm VAr Demand Signal: Alarm VARs demand value
SysA.Alarm VA Demand Signal: Alarm VAs demand value
SysA.Alm Current Demd Signal: Alarm Current demand value
SysA.Alarm I THD Signal: Alarm Total Harmonic Distortion Current
SysA.Alarm V THD Signal: Alarm Total Harmonic Distortion Voltage
SysA.Trip Watt Power Signal: Trip WATTS peak
SysA.Trip VAr Power Signal: Trip VArs peak
SysA.Trip VA Power Signal: Trip VAs peak
SysA.Trip Watt Demand Signal: Trip WATTS demand value
SysA.Trip VAr Demand Signal: Trip VARs demand value
SysA.Trip VA Demand Signal: Trip VAs demand value
SysA.Trip Current Demand Signal: Trip Current demand value
SysA.Trip I THD Signal: Trip Total Harmonic Distortion Current
SysA.Trip V THD Signal: Trip Total Harmonic Distortion Voltage
SysA.ExBlo-I Module Input State: External Blocking
Sgen.Running Signal: Measuring value simulation is running
Sgen.ExBlo Module Input State: External Blocking
Sgen.Ex ForcePost-I State of the module input:Force Post state. Abort simulation.
Sys.PS 1 Signal: Parameter Set 1
Sys.PS 2 Signal: Parameter Set 2
Sys.PS 3 Signal: Parameter Set 3
Sys.PS 4 Signal: Parameter Set 4
Sys.PSS manual Signal: Manual switch over of a Parameter Set
Sys.PSS via Comm Signal: Parameter Set Switch via Communication
Sys.PSS via Inp fct Signal: Parameter Set Switch via Input Function
Sys.Min. 1 param changed Signal: At least one parameter has been changed
670 www.eaton.com
EMR-4000 IM02602009E
Name Description
Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance Active
Sys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive
Sys.MaintMode Manually Signal: Arc Flash Reduction Maintenance Manual Mode
Sys.Maint Mode Comm Signal: Arc Flash Reduction Maintenance Comm Mode
Sys.Maint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input Mode
Sys.Ack LED Signal: LEDs Acknowledgment
Sys.Ack RO Signal: Acknowledgment of the Relay Outputs
Sys.Ack Comm Signal: Acknowledge Communication
Sys.Ack TripCmd Signal: Reset Trip Command
Sys.Ack LED-HMI Signal: LEDs Acknowledgment :HMI
Sys.Ack RO-HMI Signal: Acknowledgment of the Relay Outputs :HMI
Sys.Ack Comm-HMI Signal: Acknowledge Communication :HMI
Sys.Ack TripCmd-HMI Signal: Reset Trip Command :HMI
Sys.Ack LED-Comm Signal: LEDs Acknowledgment :Communication
Sys.Ack RO-Comm Signal: Acknowledgment of the Relay Outputs :Communication
Sys.Ack Counter-Comm Signal: Reset of all Counters :Communication
Sys.Ack Comm-Comm Signal: Acknowledge Communication :Communication
Sys.Ack TripCmd-Comm Signal: Reset Trip Command :Communication
Sys.Res OperationsCr Signal: Res OperationsCr
Sys.Res AlarmCr Signal: Res AlarmCr
Sys.Res TripCr Signal: Res TripCr
Sys.Res TotalCr Signal: Res TotalCr
Sys.Ack LED-I Module Input State: LEDs Acknowledgment by Digital Input.
Sys.Ack RO-I Module Input State: Acknowledgment of the Relay Outputs.
Sys.Ack Comm-I Module Input State: Acknowledge Communication via Digital Input.
The replica that Communication has received from the device is to
be reset.
Sys.PS1-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS2-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS3-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.PS4-I State of the module input, respectively of the signal, that should
activate this Parameter Setting Group.
Sys.Lock Settings-I State of the module input: No parameters can be changed as long
as this input is true. The parameter settings are locked.
Sys.Maint Mode-I Module Input State: Arc Flash Reduction Maintenance Switch
www.eaton.com 671
IM02602009E EMR-4000
Special Assignment List for all Digital Input Signals and all Logic Outputs
Name Description
-.- No assignment
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE4.Gate Out Signal: Output of the logic gate
Logic.LE4.Timer Out Signal: Timer Output
Logic.LE4.Out Signal: Latched Output (Q)
Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE5.Gate Out Signal: Output of the logic gate
Logic.LE5.Timer Out Signal: Timer Output
Logic.LE5.Out Signal: Latched Output (Q)
Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE6.Gate Out Signal: Output of the logic gate
Logic.LE6.Timer Out Signal: Timer Output
Logic.LE6.Out Signal: Latched Output (Q)
Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE7.Gate Out Signal: Output of the logic gate
Logic.LE7.Timer Out Signal: Timer Output
Logic.LE7.Out Signal: Latched Output (Q)
Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)
672 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE8.Gate Out Signal: Output of the logic gate
Logic.LE8.Timer Out Signal: Timer Output
Logic.LE8.Out Signal: Latched Output (Q)
Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE9.Gate Out Signal: Output of the logic gate
Logic.LE9.Timer Out Signal: Timer Output
Logic.LE9.Out Signal: Latched Output (Q)
Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE10.Gate Out Signal: Output of the logic gate
Logic.LE10.Timer Out Signal: Timer Output
Logic.LE10.Out Signal: Latched Output (Q)
Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE11.Gate Out Signal: Output of the logic gate
Logic.LE11.Timer Out Signal: Timer Output
Logic.LE11.Out Signal: Latched Output (Q)
Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE12.Gate Out Signal: Output of the logic gate
Logic.LE12.Timer Out Signal: Timer Output
Logic.LE12.Out Signal: Latched Output (Q)
Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE13.Gate Out Signal: Output of the logic gate
Logic.LE13.Timer Out Signal: Timer Output
Logic.LE13.Out Signal: Latched Output (Q)
Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE14.Gate Out Signal: Output of the logic gate
Logic.LE14.Timer Out Signal: Timer Output
Logic.LE14.Out Signal: Latched Output (Q)
Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE15.Gate Out Signal: Output of the logic gate
Logic.LE15.Timer Out Signal: Timer Output
Logic.LE15.Out Signal: Latched Output (Q)
Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE16.Gate Out Signal: Output of the logic gate
Logic.LE16.Timer Out Signal: Timer Output
Logic.LE16.Out Signal: Latched Output (Q)
Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE17.Gate Out Signal: Output of the logic gate
Logic.LE17.Timer Out Signal: Timer Output
Logic.LE17.Out Signal: Latched Output (Q)
www.eaton.com 673
IM02602009E EMR-4000
Name Description
Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE18.Gate Out Signal: Output of the logic gate
Logic.LE18.Timer Out Signal: Timer Output
Logic.LE18.Out Signal: Latched Output (Q)
Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE19.Gate Out Signal: Output of the logic gate
Logic.LE19.Timer Out Signal: Timer Output
Logic.LE19.Out Signal: Latched Output (Q)
Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE20.Gate Out Signal: Output of the logic gate
Logic.LE20.Timer Out Signal: Timer Output
Logic.LE20.Out Signal: Latched Output (Q)
Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE21.Gate Out Signal: Output of the logic gate
Logic.LE21.Timer Out Signal: Timer Output
Logic.LE21.Out Signal: Latched Output (Q)
Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE22.Gate Out Signal: Output of the logic gate
Logic.LE22.Timer Out Signal: Timer Output
Logic.LE22.Out Signal: Latched Output (Q)
Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE23.Gate Out Signal: Output of the logic gate
Logic.LE23.Timer Out Signal: Timer Output
Logic.LE23.Out Signal: Latched Output (Q)
Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE24.Gate Out Signal: Output of the logic gate
Logic.LE24.Timer Out Signal: Timer Output
Logic.LE24.Out Signal: Latched Output (Q)
Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE25.Gate Out Signal: Output of the logic gate
Logic.LE25.Timer Out Signal: Timer Output
Logic.LE25.Out Signal: Latched Output (Q)
Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE26.Gate Out Signal: Output of the logic gate
Logic.LE26.Timer Out Signal: Timer Output
Logic.LE26.Out Signal: Latched Output (Q)
Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE27.Gate Out Signal: Output of the logic gate
Logic.LE27.Timer Out Signal: Timer Output
674 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE27.Out Signal: Latched Output (Q)
Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE28.Gate Out Signal: Output of the logic gate
Logic.LE28.Timer Out Signal: Timer Output
Logic.LE28.Out Signal: Latched Output (Q)
Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE29.Gate Out Signal: Output of the logic gate
Logic.LE29.Timer Out Signal: Timer Output
Logic.LE29.Out Signal: Latched Output (Q)
Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE30.Gate Out Signal: Output of the logic gate
Logic.LE30.Timer Out Signal: Timer Output
Logic.LE30.Out Signal: Latched Output (Q)
Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE31.Gate Out Signal: Output of the logic gate
Logic.LE31.Timer Out Signal: Timer Output
Logic.LE31.Out Signal: Latched Output (Q)
Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE32.Gate Out Signal: Output of the logic gate
Logic.LE32.Timer Out Signal: Timer Output
Logic.LE32.Out Signal: Latched Output (Q)
Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE33.Gate Out Signal: Output of the logic gate
Logic.LE33.Timer Out Signal: Timer Output
Logic.LE33.Out Signal: Latched Output (Q)
Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE34.Gate Out Signal: Output of the logic gate
Logic.LE34.Timer Out Signal: Timer Output
Logic.LE34.Out Signal: Latched Output (Q)
Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE35.Gate Out Signal: Output of the logic gate
Logic.LE35.Timer Out Signal: Timer Output
Logic.LE35.Out Signal: Latched Output (Q)
Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE36.Gate Out Signal: Output of the logic gate
Logic.LE36.Timer Out Signal: Timer Output
Logic.LE36.Out Signal: Latched Output (Q)
Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE37.Gate Out Signal: Output of the logic gate
www.eaton.com 675
IM02602009E EMR-4000
Name Description
Logic.LE37.Timer Out Signal: Timer Output
Logic.LE37.Out Signal: Latched Output (Q)
Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE38.Gate Out Signal: Output of the logic gate
Logic.LE38.Timer Out Signal: Timer Output
Logic.LE38.Out Signal: Latched Output (Q)
Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE39.Gate Out Signal: Output of the logic gate
Logic.LE39.Timer Out Signal: Timer Output
Logic.LE39.Out Signal: Latched Output (Q)
Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE40.Gate Out Signal: Output of the logic gate
Logic.LE40.Timer Out Signal: Timer Output
Logic.LE40.Out Signal: Latched Output (Q)
Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE41.Gate Out Signal: Output of the logic gate
Logic.LE41.Timer Out Signal: Timer Output
Logic.LE41.Out Signal: Latched Output (Q)
Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE42.Gate Out Signal: Output of the logic gate
Logic.LE42.Timer Out Signal: Timer Output
Logic.LE42.Out Signal: Latched Output (Q)
Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE43.Gate Out Signal: Output of the logic gate
Logic.LE43.Timer Out Signal: Timer Output
Logic.LE43.Out Signal: Latched Output (Q)
Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE44.Gate Out Signal: Output of the logic gate
Logic.LE44.Timer Out Signal: Timer Output
Logic.LE44.Out Signal: Latched Output (Q)
Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE45.Gate Out Signal: Output of the logic gate
Logic.LE45.Timer Out Signal: Timer Output
Logic.LE45.Out Signal: Latched Output (Q)
Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE46.Gate Out Signal: Output of the logic gate
Logic.LE46.Timer Out Signal: Timer Output
Logic.LE46.Out Signal: Latched Output (Q)
Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)
676 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE47.Gate Out Signal: Output of the logic gate
Logic.LE47.Timer Out Signal: Timer Output
Logic.LE47.Out Signal: Latched Output (Q)
Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE48.Gate Out Signal: Output of the logic gate
Logic.LE48.Timer Out Signal: Timer Output
Logic.LE48.Out Signal: Latched Output (Q)
Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE49.Gate Out Signal: Output of the logic gate
Logic.LE49.Timer Out Signal: Timer Output
Logic.LE49.Out Signal: Latched Output (Q)
Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE50.Gate Out Signal: Output of the logic gate
Logic.LE50.Timer Out Signal: Timer Output
Logic.LE50.Out Signal: Latched Output (Q)
Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE51.Gate Out Signal: Output of the logic gate
Logic.LE51.Timer Out Signal: Timer Output
Logic.LE51.Out Signal: Latched Output (Q)
Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE52.Gate Out Signal: Output of the logic gate
Logic.LE52.Timer Out Signal: Timer Output
Logic.LE52.Out Signal: Latched Output (Q)
Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE53.Gate Out Signal: Output of the logic gate
Logic.LE53.Timer Out Signal: Timer Output
Logic.LE53.Out Signal: Latched Output (Q)
Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE54.Gate Out Signal: Output of the logic gate
Logic.LE54.Timer Out Signal: Timer Output
Logic.LE54.Out Signal: Latched Output (Q)
Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE55.Gate Out Signal: Output of the logic gate
Logic.LE55.Timer Out Signal: Timer Output
Logic.LE55.Out Signal: Latched Output (Q)
Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE56.Gate Out Signal: Output of the logic gate
Logic.LE56.Timer Out Signal: Timer Output
Logic.LE56.Out Signal: Latched Output (Q)
www.eaton.com 677
IM02602009E EMR-4000
Name Description
Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE57.Gate Out Signal: Output of the logic gate
Logic.LE57.Timer Out Signal: Timer Output
Logic.LE57.Out Signal: Latched Output (Q)
Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE58.Gate Out Signal: Output of the logic gate
Logic.LE58.Timer Out Signal: Timer Output
Logic.LE58.Out Signal: Latched Output (Q)
Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE59.Gate Out Signal: Output of the logic gate
Logic.LE59.Timer Out Signal: Timer Output
Logic.LE59.Out Signal: Latched Output (Q)
Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE60.Gate Out Signal: Output of the logic gate
Logic.LE60.Timer Out Signal: Timer Output
Logic.LE60.Out Signal: Latched Output (Q)
Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE61.Gate Out Signal: Output of the logic gate
Logic.LE61.Timer Out Signal: Timer Output
Logic.LE61.Out Signal: Latched Output (Q)
Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE62.Gate Out Signal: Output of the logic gate
Logic.LE62.Timer Out Signal: Timer Output
Logic.LE62.Out Signal: Latched Output (Q)
Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE63.Gate Out Signal: Output of the logic gate
Logic.LE63.Timer Out Signal: Timer Output
Logic.LE63.Out Signal: Latched Output (Q)
Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE64.Gate Out Signal: Output of the logic gate
Logic.LE64.Timer Out Signal: Timer Output
Logic.LE64.Out Signal: Latched Output (Q)
Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE65.Gate Out Signal: Output of the logic gate
Logic.LE65.Timer Out Signal: Timer Output
Logic.LE65.Out Signal: Latched Output (Q)
Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE66.Gate Out Signal: Output of the logic gate
Logic.LE66.Timer Out Signal: Timer Output
678 www.eaton.com
EMR-4000 IM02602009E
Name Description
Logic.LE66.Out Signal: Latched Output (Q)
Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE67.Gate Out Signal: Output of the logic gate
Logic.LE67.Timer Out Signal: Timer Output
Logic.LE67.Out Signal: Latched Output (Q)
Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE68.Gate Out Signal: Output of the logic gate
Logic.LE68.Timer Out Signal: Timer Output
Logic.LE68.Out Signal: Latched Output (Q)
Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE69.Gate Out Signal: Output of the logic gate
Logic.LE69.Timer Out Signal: Timer Output
Logic.LE69.Out Signal: Latched Output (Q)
Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE70.Gate Out Signal: Output of the logic gate
Logic.LE70.Timer Out Signal: Timer Output
Logic.LE70.Out Signal: Latched Output (Q)
Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE71.Gate Out Signal: Output of the logic gate
Logic.LE71.Timer Out Signal: Timer Output
Logic.LE71.Out Signal: Latched Output (Q)
Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE72.Gate Out Signal: Output of the logic gate
Logic.LE72.Timer Out Signal: Timer Output
Logic.LE72.Out Signal: Latched Output (Q)
Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE73.Gate Out Signal: Output of the logic gate
Logic.LE73.Timer Out Signal: Timer Output
Logic.LE73.Out Signal: Latched Output (Q)
Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE74.Gate Out Signal: Output of the logic gate
Logic.LE74.Timer Out Signal: Timer Output
Logic.LE74.Out Signal: Latched Output (Q)
Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE75.Gate Out Signal: Output of the logic gate
Logic.LE75.Timer Out Signal: Timer Output
Logic.LE75.Out Signal: Latched Output (Q)
Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE76.Gate Out Signal: Output of the logic gate
www.eaton.com 679
IM02602009E EMR-4000
Name Description
Logic.LE76.Timer Out Signal: Timer Output
Logic.LE76.Out Signal: Latched Output (Q)
Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE77.Gate Out Signal: Output of the logic gate
Logic.LE77.Timer Out Signal: Timer Output
Logic.LE77.Out Signal: Latched Output (Q)
Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE78.Gate Out Signal: Output of the logic gate
Logic.LE78.Timer Out Signal: Timer Output
Logic.LE78.Out Signal: Latched Output (Q)
Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE79.Gate Out Signal: Output of the logic gate
Logic.LE79.Timer Out Signal: Timer Output
Logic.LE79.Out Signal: Latched Output (Q)
Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE80.Gate Out Signal: Output of the logic gate
Logic.LE80.Timer Out Signal: Timer Output
Logic.LE80.Out Signal: Latched Output (Q)
Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)
Name Description
-.- No assignment
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
680 www.eaton.com
EMR-4000 IM02602009E
Notes:
www.eaton.com 681
IM02602009E EMR-4000
E at o n Corpor atio n
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2011 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IM02602009E
682 www.eaton.com