PRESSURISED STAIRCASE ONLY

MODE 1 (B5588 Part 4 - 1998) ALL SYSTEMS ALL DOORS CLOSED

a) To calculate pressure required in stairwell to exhaust 1.2 m3/sec to atmosphere via fire floor (see fig 17). Area of single leaf door = 2.0 x 0.8 = 1.6 m2 Area of exhaust vent = 1.2/2.5 = 0.48 m2

Double Doors Stairs

Accomodation

Exhaust Vent

6 Floors

Fig 16- Plan of Staircase A = 1 x double door at 0.03 = 0.03 m2 6 x single doors at 0.01 = 0.06 m2 0.09 m2 1/ 2 Q = 0.83AEP = 0.83 x 0.09 x 50 /2 Increase by 50%
1

AE = 1 + 1 A22 A12 = 0.46 m2

-1/2

1 + 1 1.62 0.482

1/ / --122

P1 =

Q 0.83 x AE

1.2 0.83 x 0.46

= 0.53m3/sec + 0.26 m3/sec 0.79 m3/sec Say 0.80 m3/sec

= 10.01 Pa This is more than covered by 50 Pa assumed. b) To calculate area of Pressure Relief. Quantity of air to be wasted = (2.0 - 0.8) = 1.2m3/sec = = Q 0.83 x P 1.2
1/ 2 1/ 2

MODE 2 (BS5588 Part 4 - 1998) CLASS A SYSTEMS ESCAPE

Area of Pressure Relief

V = 0.75 m/sec P0 P1

Exit vent A= Q 2.5

0.83 x (50) = 0.204 m2 MODE 2 CLASS E SYSTEM ESCAPE PRESSURE CRITERION

P0

Door Closed Staircase Accomodation

Open Open

Fig 17

A= = V= Q=

Area of single leaf door 2.0 m x 0.8 m = 1.6 m2 Velocity through door = 0.75 m/sec V x A = 0.75 x 1.6 = 1.20 m3/sec Add MODE 1 = 0.80 m3/sec 2.00m3/sec

10 Pa Door Open Staircase Accomodation

Fig 18