Вы находитесь на странице: 1из 10

SIRIUS NET Communication-Capable Controlgear

3UF18 Current Transformer


Dimensions
4NC31 current transformer

60

30

78

40

26

12

6,5

4NC36 current transformer

6,5

NSK-8680

30

60

30

78

20 40
NSK-8678

27 10

6,5

4NC37 current transformer

6,5

30

49,5

30

70

29,5 30
NSK-8679

24 10

6,5

6,5

30

Siemens NS K 2000

1/157

SIRIUS NET Communication-Capable Controlgear


3UF18 Current Transformer
Dimensions
3UF18 43 current transformer M4 9

75

87

35

2)

35 45

NS2-5521

94

3UF18 45 current transformer for individual installation; for screw mounting and snap-on mounting onto 35 mm standard mounting rail to EN 50 022
6
1 )

5 5 4 5

1 )

1 0 2

M 4 M 3 ,5 8 5

2 )

56 89
N S K -6 1 8 0

4 ,5

3UF18 47 to 3UF18 52 current transformers for snap-on mounting onto 75 mm standard mounting rail to EN 50 023 with base plate
j c b

1 0 9 8 3

5 6 8 8

13 r

Current transformers 3UF18 47, 3UF18 48 Base plate 3UF19 00-0KA00

3UF18 50-0JA00 3UF19 00-0JA00 (for snap-on mounting only) 3TX7 500-0E 3TX7 506-0A

3UF18 52-0JA00 3UF19 00-0JA00 (for snap-on mounting only) 3TX7 506-0A

i o

Box terminal block 130 Additional cover d k e f

3TX7 460-0E 3TX7 466-0A

l
g
NSK-6181a

1
2

$ Additional cover, can be shortened % Box terminal block


c 50 50 d 82 82 71.5 71.5 e 111 111 99 102 f 122 122 114 122 g 10.5 10.5 15 20 h 90 90 110 110 i 46 46 41 42 j 90 90 120 120 k 105 105 95 95 l 35 35 33 33 m 62 62 67 67 n 89 89 98 98 o p 19 19 q r

Current transformers 3UF18 47 3UF18 48 3UF18 50 3UF18 52

Contactors 3) 3RT10 44 3RT10 45 3RT10 46 3TF50 3TF51/3TF52

a 26.5 26.5 37 42

b 25 25 37.5 37.5

6.2 5.8 (M5) 6.2 5.8 (M5) 6.6 7 (M6) 9 7 (M6)

23 M8 25 23

1) Clearance to earthed parts. 2) For snap-on mounting onto standard mounting rails EN 50 022-35 7.5 or EN 50 022-35 15. 3) For dimensions of the contactors, see Part 3.

1/158

Siemens NS K 2000

SIRIUS NET Communication-Capable Controlgear


3UF18 Current Transformer
Dimensions
3UF18 54 to 3UF18 57 current transformers for 3TF53 to 3TF57 contactors a 9 b i j

A N S 2 -5 4 8 8 b

c
4 fo r M

3 ,5 1 1 fo r M

1 0 g d f

1 3 4 1 1 0

5 0 1 4 5

i
1 1 fo r M

8 8

1 0
c

0 ,5 1 0

6 1 2 7
d 278 287 297 310 e

6 6

1 5

Current transformers 3UF18 54 3UF18 54 3UF18 56 3UF18 56 3UF18 57

Contactors 3TF53 3TF54 3TF55 3TF56 3TF57

a 135 145 160 160

b 110 120 130 130

6 2 k l
f 180 200 200 210 g 160 180 180 180

h 303 312 322 340

i 48 48 48 52

j 25 25 25 30

k 134 134 134 133

l 159 159 159 163

42 48 48 48

296 311 316 333

3UF18 68-3FA00, 3UF18 68-3GA00 current transformers for 3TF68 contactors 7 0 c 7 0 1 4 fo r M 1 2

2 8

1 0 0

2 3 0
A N S 2 -5 4 8 7 b

1 2

2 3 2 2 2 0 2 1 0

1 0 5

1 2

1 7 4 1 4 0

2 3 0

1 4 f o r M

1 2

0 ,5

1 5

d 4 0
f 175 195

1 5 1 7 0
g 420 450

Current transformers

Contactors

a 390 410

b 398 408

c 30 40

d 5 8

e 145 155

3UF18 68-3FA00 3TF68 3UF18 68-3GA00 3TF68

7 4 e f

Siemens NS K 2000

1/159

6ED1 Logic Modules


Description
Application
LOGO! is universally applicable, e.g.: Building installation and wiring (lighting, shutters, awnings, doors, access control, barriers, ventilation systems, etc.) Cabinet installation Machine and component manufacturing (pumps, small presses, compressors, etc.) Special controllers for conservatories, greenhouses Signal preprocessing for other controllers

r You IC ATine: SIM otl 11 H -9 +49-7000 895

Features
LOGO! is simple: Key operator panel and display panel in one unit; no other accessories are required Stored basic functions (e.g. AND, OR) and special functions (e.g. latching relay) for electrical engineering Program generation simply by combining stored functions at the press of a key Non-volatile storage of control program and setpoints (e.g. times) in integrated EEPROM Easy-to-use and simple duplication of the control program with an optional program module LOGO! saves space: e.g. LOGO! 230RC: 72 90 55 mm (W H D) Fitted mounting in the distribution box (same mounting dimensions as the groundfault circuit interrupter) LOGO! is extremely flexible: Flexible options for making changes by recombining functions at the press of a key; no more time-consuming rewiring Optional operation on the PC; writing, simulating and archiving the control program on the PC, incl. documentation options LOGO! is communication-capable: Variants with AS-Interface connection (slave) permit data exchange with higherlevel controllers (e.g. with SIMATIC S7-200)

Design
LOGO! is available in various versions for supply voltages of 12 V DC, 24 V DC; 115/230 V AC. All versions have: Relay outputs with up to 10 A output current (not LOGO! 24/24L versions) Integrated display panel Integrated keypad Integrated basic and special functions Integrated EEPROM for storing control program and setpoints Optional program module Integrated clock (not LOGO!24/24L versions) A maximum of 56 linkable functions The basic versions have: 6 digital inputs 4 digital outputs The Long/Bus versions have: 12 digital inputs 8 digital outputs Additionally 4 inputs and 4 outputs with AS-Interface versions for data exchange with AS-Interface master

Integrated functions
All versions have: Basic functions: AND, OR, NOT, NAND, NOR, XOR Special functions: ON delay, latching ON delay, OFF delay, pulse relay, latching relay, clock counter (up/ down), timer, impulse relay, hours-run counter, threshold switch

LOGO! Power
Two LOGO! Power variants for different output currents are available for all LOGO! 12 V DC and LOGO! 24 V DC modules: 12 V DC: Output current 1.9 or 4.5 A 24 V DC: Output current 1.3 or 2.5 A LOGO! Power can be used with all LOGO! 12 V or LOGO! 24 V variants.

N
Additional functionality with all variants: Asynchronous pulse encoder Twelve-month time switch Bit memories Integrated retentivity Optional functions: Know-how protection with the optional program module for copy protection Now also for the standard variants.

LOGO! Contact
LOGO! Contact is a switching module for direct switching of resistive loads up to 20 A and motors up to 4 kW, hum-free. LOGO! Contact can be used: in domestic/installation environments in trade and industrial environments. LOGO! Contact is available in two variants: 24 V DC, 230 V AC, 50/60 Hz

LOGO! and sonar BERO


The sonar BERO ultrasonic proximity switches enable contactless object detection and distance measurement (e.g. fill levels). The acquired values can be evaluated with the LOGO! threshold value function.

1/160

Siemens NS K 2000

r You IC ATine: SIM otl 11 H -9 +49-7000 895


Design

6ED1 Logic Modules


Selection and ordering data
Order No. Price 1 unit Weight approx. kg

Basic versions
6ED1 052-1BB00-0AB1 6ED1 052-1CA00-0BA1 6ED1 052-1HB00-0BA1 6ED1 052-1FB00-0BA1 LOGO! 12RC Supply voltage 12 V DC, 6 digital inputs 12 V DC, 4 relay outputs 10 A LOGO! 24 Supply voltage 24 V DC, 6 digital inputs 24 V DC, 4 digital outputs 24 V DC, 0.3 A LOGO! 24RC Supply voltage 24 V AC/DC, 6 digital inputs 24 V AC/DC, 4 relay outputs 10 A LOGO! 230RC Supply voltage 115, 230 V AC 6 digital inputs 115, 230 V AC 4 relay outputs 10 A 6ED1 052-1BB00-0BA1 0.19

6ED1 052-1CA00-0BA1

0.19

6ED1 052-1HB00-0BA1

0.19

6ED1 052-1FB00-0BA1

0.19

Long versions
6ED1 053-1BB00-0BA1 6ED1 053-1CA00-0BA1 6ED1 053-1HB00-0BA1 6ED1 053-1FB00-0BA1 LOGO! 12RCL Supply voltage 12 V DC, 12 digital inputs 12 V DC, 8 relay outputs 10 A LOGO! 24L Supply voltage 24 V DC, 12 digital inputs 24 V DC, 8 digital outputs 24 V DC, 0.3 A LOGO! 24RCL Supply voltage 24 V DC, 12 digital inputs 24 V DC, 8 relay outputs 10 A LOGO! 230RCL Supply voltage 115, 230 V AC, 12 digital inputs 115, 230 V AC, 8 relay inputs 10 A 6ED1 053-1BB00-0BA1 0.36

6ED1 053-1CA00-0BA1

0.36

6ED1 053-1HB00-0BA1

0.36

6ED1 053-1FB00-0BA1

0.36

Bus versions
6ED1 053-1HH00-0BA1 6ED1 053-1FH00-0BA1 LOGO! 24RCLB11 AS-Interface slave; Supply voltage 24 V DC, 12 digital inputs 24 V DC, 8 relay outputs 10 A 4 inputs and 4 outputs for AS-Inference LOGO! 230RCLB11 AS-Interface slave; Supply voltage 115, 230 V AC, 12 digital inputs 115, 230 V AC, 8 relay outputs 10 A each terminal, 4 inputs and 4 outputs for AS-Interface 6ED1 053-1HH00-0BA1 0.36

6ED1 053-1FH00-0BA1

0.36

The programming instructions are included in the scope of delivery of each logic module. Recommended power supply unit for LOGO! 24 V versions: LOGO! Power.

Siemens NS K 2000

1/161

6ED1 Logic Modules


Accessories
Design Order No.

r You IC ATine: SIM otl 11 H -9 +49-7000 895


Price 1 unit Weight approx. kg

For basic, long and bus versions


6ED1 057-4CA00-0AA0 6ED1 057-4EA00-0AA0 LOGO! Contact 24 Switching module for direct switching of resistive loads up to 20 A and motors up to 4 kW, switching voltage 24 V DC LOGO! Contact 230 Switching module for direct switching of resistive loads up to 20 A and motors up to 4 kW, switching voltage 230 V AC LOGO! Power 24 V/1.3 A Power supply to convert the line voltage 120/230 V AC to the operating voltage 24 V DC, for LOGO! 24 V versions, rated output current 1.3 A LOGO! Power 24 V/2.5 A Power supply to convert the line voltage 120/230 V AC to the operating voltage 24 V DC, for LOGO! 24 V versions, rated output current 2.5 A LOGO! Power 12 V/1.9 A Power supply to convert the line voltage 120/230 V AC to the operating voltage 12 V DC, for LOGO! 24 V versions, output current 1.9 A LOGO! Power 12 V/4.5 A Power supply to convert the line voltage 120/230 V AC to the operating voltage 12 V DC, for LOGO! 24 V versions, Output current 4.5 A LOGO! Manual, Version 4 German English French Italian Spanish Portuguese LOGO! PC cable for transferring control programs from a PC to LOGO! and vice versa 6ED1 057-4CA00-0AA0 0.19

6ED1 057-4EA00-0AA0

0.19

6EP1 331-1SH01

0.19

6EP1 331-1SH01 6EP1 332-1SH41 6EP1 321-1SH01 6EP1 322-1SH01

6EP1 332-1SH41

0.36

6EP1 321-1SH01

0.19

6EP1 322-1SH01

0.36

6ED1 050-1AA00-0AE2 6ED1 050-1AA00-0BE2 6ED1 050-1AA00-0CE2 6ED1 050-1AA00-0EE2 6ED1 050-1AA00-0DE2 6ED1 050-1AA00-0GE2 6ED1 057-1AA00-0BA0

LOGO! Soft 6ED1 058-0AA00-0BA1 Programming software V3.0, for creating, simulating and archiving the control program on a PC (requires at least Windows 3.1) 4 floppy disks 3.5 German/French/Italian/English/Spanish/Dutch/Portuguese/Chinese LOGO! Soft Comfort V1.0 6ED1 058-0BA00-0YC0 User-friendly programming software; program writing by drag&drop, simulation, detailed program documentation; from Windows 95 upward (on CD-ROM); detailed online help in German/English/French/Italian/Spanish/Dutch/Portuguese/Chinese LOGO! Program module, yellow Features: program duplication and retentivity LOGO! Program module, red Features: copy protection and retentivity, with know-how protection 3RG60 12 3RG60 13 Sonar BERO for LOGO! Ultrasonic proximity switch for contactless distance measurement 24 V DC Sensing range (cm): 6ED1 056-1BA00-0AA0 6ED1 056-4BA00-0AA0

6 to 30 20 to 130 40 to 300 60 to 600

3RG60 12-3RS00 3RG60 13-3RS00 3RG60 15-3RS00 3RG60 14-3RS00 3RX1 536

3RG60 15

3RG60 14

Cable socket 4-pole, 5 m long For further information on Sonar BEROs, see Part 10, compact range I to III.

1/162

Siemens NS K 2000

r You IC ATine: SIM otl 11 H -9 +49-7000 895


Basic versions
Type Order No. Inputs Input/supply voltage for signal 0 for signal 1 Input current Outputs Output voltage Output current, rated value with resistive load with inductive load Short-circuit protection A A A max. V min. V mA LOGO! 12RC 6ED1 0521BB00-0BA1 6 12 V DC 4 8 1.5 4 Relay 10 3 External protection required with resistive load with inductive load max. Hz Hz W 2 0.5 1.0 LOGO! 24 6ED1 0521CA00-0BA1 6 24 V DC 5 15 3.0 4 24 V DC 0.3 Electronic (approx. 1 A) 10 0.5 0.8

6ED1 Logic Modules


Technical data

LOGO! 24RC 6ED1 0521HB00-0BA1 6 24 V AC/DC 5 15 5.0 4 Relay 10 3 External protection required 2 0.5 1.5

LOGO! 230RC 6ED1 0521FB00-0BA1 6 115/230 V AC 40 79 0.24 4 Relay 10 3 External protection required 2 0.5 3.0

Switching frequency Power loss

Max. conductor cross-sections

2 1.5 mm2 solid 1 0.5 mm2 to 2.5 mm2 solid 1 0.5 mm2 to 2.5 mm2 finely stranded with end sleeve 0 C to +55 C, horizontal or vertical installation 40 C to +70 C acc. to EN 55 011 (Limit Class B, Group 1) IP 20 acc. to VDE 0631, IEC 61 131 onto 35 mm standard mounting rail

Ambient temperature Storage temperature Interference suppression Degree of protection Certification Mounting

Switching modules
Type Order No. Operating voltage Switching capacity, utilization category AC-1: Switching of resistive loads at 55 C Operating current I e at 400 V Output of three-phase loads at 400 V Switching capacity, utilization category AC-2, AC-3: Motors with slip-ring or squirrel cage rotors Operating current Ie at 400 V Output of three-phase loads at 400 V Short-circuit protection Type of coordination 1 Type of coordination 2 acc. to IEC 60 947-4/ DIN VDE 0660 Part 102 Connecting leads finely stranded with end sleeves solid 2 (0.75 to 2.5) mm2 2 (1 to 2.5) mm2 1 4 mm 2 25 C to +55 C 50 C to +80 C finely stranded with end sleeves solid 2 (0.75 to 2.5) mm2 2 (1 to 2.5) mm2 1 4 mm2 25 C to +55 C 50 C to +80 C A kW A A 8.4 4 25 10 8.4 4 25 10 A kW 20 13 20 13 LOGO! Contact 24 6ED1 057-4CA00-0AA0 24 V DC LOGO! Contact 230 6ED1 057-4EA00-0AA0 230 V AC 50/60 Hz

Ambient temperature Storage temperature

Siemens NS K 2000

1/163

6ED1 Logic Modules


Technical data
Long versions
Type Order No. Inputs AS-Interface inputs Input/supply voltage for signal 0 for signal 1 Input current Outputs AS-Interface outputs Output voltage Output current, rated value with resistive load with inductive load Short-circuit protection Switching frequency with resistive load with inductive load Max. conductor cross-sections A A A max. V min. V mA LOGO! 12RCL 6ED1 0531BB00-0BA1 12 12 V DC 4 8 1.5 8 Relay 10 3 External protection required Hz Hz 2 0.5 LOGO! 24L 6ED1 0531CA00-0BA1 12 24 V DC 5 12 5 8 24 V DC 0.3 Electronic (approx. 1 A) 10 0.5 LOGO! 24RCL 6ED1 0531HB00-0BA1 12 24 V DC 5 12 5 8 Relay 10 3 External protection required 2 0.5

r You IC ATine: SIM otl 11 H -9 +49-7000 895

LOGO! 230RCL 6ED1 0531FB00-0BA1 12 115/230 V AC 40 79 2.0 8 Relay 10 3 External protection required 2 0.5

LOGO! 24RCLB11 LOGO! 230RCLB11 6ED1 0531HH00-0BA1 12 4 24 V DC 5 12 5 8 4 Relay 10 3 6ED1 0531FH00-0BA1 12 4 115/230 V AC 40 79 2.0 8 4 Relay 10 3

External protection External protection required required 2 0.5 2 0.5

2 1.5 mm2 solid 1 0.5 to 2.5 mm2 solid 1 0.5 to 2.5 mm2 finely stranded with end sleeve C C 0 to +55, horizontal or vertical installation 40 to +70 acc. to EN 55 011 (Limit Class B, Group 1) IP 20 acc. to VDE 0631, IEC 61 131 onto 35 mm standard mounting rail

Ambient temperature Storage temperature Interference suppression Degree of protection Certification Mounting

1/164

Siemens NS K 2000

r You IC ATine: SIM otl 11 H -9 +49-7000 895


Power supplies
Type Order No. Input voltage Input voltage range Input voltage frequency Output voltage Output current, rated value Overcurrent limitation Stable at no load and short-circuit proof Connecting leads at the input at the output Interference suppression Noise immunity Isolation primary/secondary Degree of protection Ambient temperature Storage temperature C C one terminal each, max. 2.5 mm2 two terminals each, max. 2.5 EN 50 081-1, EN 55 022 Class B EN 50 082-2 yes, SELV (to EN 60 950/VDE 0805) IP 20 0 to +55 40 to +70 mm2 A A Hz

6ED1 Logic Modules


Technical data

LOGO! Power 24 V/1.3 A LOGO! Power 24 V/2.5 A LOGO! Power 24 V/2.5 A LOGO! Power 12 V/4.5 A 6EP1 331-1SH01 120 V AC, 230 V AC 85 to 264 V AC 47 to 63 24 V DC 1.3 1.35 yes 2.5 2.8 6EP1 332-1SH41 6EP1 332-1SH41 120 V AC, 230 V AC 85 to 264 V AC 47 to 63 24 V DC 2.5 2.8 yes 4.5 > 4.5 6EP1 322-1SH01

one terminal each, max. 2.5 mm2 two terminals each, max. 2.5 mm2 EN 50 081-1, EN 55 022 Class B EN 50 082-2 yes, SELV (to EN 60 950/VDE 0805) IP 20 0 to +55 40 to +70

Siemens NS K 2000

1/165

6ED1 Logic Modules


Dimensions
Basic versions 6ED1 052-1..-00-0BA1 Long/Bus versions 6ED1 053-1..-00-0BA1

r You IC ATine: SIM otl 11 H -9 +49-7000 895

90

90

72

55

126

55

Power supply 6EP1 331-1SH01 6EP1 321-1SH01

Power supply 6EP1 331-1SH41 6EP1 322-1SH01

90

90

NSK-8542

72

55

126

55

Switching modules 6ED1 057-4.A00-0AA0

72

36

55

1/166

NSK-8544

NSK-8543

NSK-8476a

NSK-8475a

Siemens NS K 2000

Вам также может понравиться