Protecting values

P r o t a n Te r r a c e s a n d B a l c o n i e s
Te c n i c a l D r a w i n g s

P r o t a n Te r r a c e s a n d B a l c o n i e s
Drawing No.: 80-10-01 80-10-02 80-10-03 80-10-04 80-10-05 80-10-06 80-10-07 80-10-08 80-15-01 80-15-02 Name: Pedestrian Pedestrian Pedestrian Pedestrian Pedestrian Pedestrian Pedestrian Pedestrian Deck Deck Deck Deck Deck Deck Deck Deck Page: with concrete tiles uninsulated ...................... 5 with wooden lattice uninsulated ..................... 5 with ceramic tiles uninsulated ....................... 6 insulated................................................... 6 insulated duo construction............................ 7 parapet detail ........................................... 7 edge trim ................................................. 8 termination with wall flashing detail ............... 8

Exposed Terrace membrane ................................................... 9 Exposed Terrace membrane joint detail ................................. 9

S e p a ra t i o n l aye r s fo r P r o t a n P VC m e m b ra n e s
A separation layer/barrier between the roofing membrane and its underlying deck, is sometimes necessary to protect the roofing material from chemical and/or mechanical influences. The separation layer must be functional under all conditions that the roofing membrane might experience during its entire lifetime. Migration barriers are installed between two layers to avoid chemical interaction between them. Sliding layers are installed between two layers to prevent friction between them. Levelling layers are installed between two layers mainly for aesthetic reasons. Protection layers are installed on top of the membrane mainly to protect it from mechanical stress etc. (Protan recommends a layer of PVC 1,2-2,0mm, alternatively a very thick polypropylene fleece > 300g/m2.)

Table: Separation layers for Protan PVC


Unde rla y ing de c k P ro tan P V C -m em b ran e Protan SE Protan SE requires a separate migration barrier installed on top of the bitumen surface to avoid migration. Protan recommends: Fibertex F2B, 140g/m2 polypropylene, supplied by Protan AS Protan SE Protan SE requires a separate migration barrier installed on top of the bitumen surface to avoid migration. Protan recommends: Glass fleece 50g/m2 supplied by Protan AS

Old bitumen roofs

Protan EX Protan EX has a 140 g/m2 polypropylene fleece migration barrier laminated on the reverse side

EPS/XPS-insulation

Protan EXG Protan EXG has a 60g/m2 glass fleece migration barrier laminated on the reverse side

Bases of smooth concrete or light weight concrete

Protan SE Protan SE requires a sliding/levelling layer installed on top of the concrete deck. Protan recommends: Fibertex F4M 300 g/m2 PP, supplied by Protan AS. Note! Polyester felt must not be used on concrete! As for old bitumen roofs As for old bitumen roofs As for old bitumen roofs (140g/m polypropylene fleece/geo-textile). Existing membrane to be slit at perimeters, change of angle, fixing lines etc to alleviate any stress/tension transfer to new fasteners and to assist in the drying out of any trapped moisture Where possible the existing membrane should be removed, if this is not feasible, the existing membrane should be slit at perimeters, change of angle, fixing points etc to alleviate any stress/tension transfer to new fasteners and to assist in the drying out of any trapped moisture Lubricated roofs should be evaluated, please contact Protan Technical Services

Timber decks Rubber, such as underlying blocks, mats, packing etc.

Old mechanically fastened polymeric membrane

Old gravel ballasted polymeric membrane

Lubricated roofs

Please contact Protan for a list of other tested and approved products for the use as separation layers.

Pr o tan T er r ac es and Bal c oni es

Pe d e s t r i a n D e c k w i t h c o n c r e t e t i l e s uninsulated
Drawing No.: Version No.: Not to scale 80-10-01 02-2008

CONCRETE TILES ON BRICKS OF EXTRUDED POLYSTYRENE PROTECTION LAYER OF PVC MEMBRANE 1,2-2,0mm PROTAN G GEOTEXTILE SUPPORTING DECK

Pe d e s t r i a n D e c k w i t h wo o d e n l a t t i c e uninsulated
Drawing No.: Version No.: Not to scale 80-10-02 02-2008

IMPREGNATED WOODEN LATTICE PROTECTION LAYER OF PVC MEMBRANE 1,2-2,0mm PROTAN G GEOTEXTILE SUPPORTING DECK

Pr otan T er r ac es and Bal c oni es

Pe d e s t r i a n D e c k w i t h c e r a m i c t i l e s uninsulated
Drawing No.: Version No.: Not to scale 80-10-03 02-2008

CONCRETE LAYER WITH CERAMIC TILES PROTECTION LAYER OF PVC MEMBRANE 1,2-2,0mm PROTAN G GEOTEXTILE SUPPORTING DECK

Pe d e s t r i a n D e c k i n s u l a t e d
Drawing No.: Version No.: Not to scale 80-10-04 02-2008

CONCRETE TILES ON BRICKS OF EXTRUDED POYSTYRENE, IMPREGNATED WOODEN LATTICE OR CONCRETE LAYER WITH TILES ON TOP PROTECTION LAYER OF PVC MEMBRANE 1,2-2,0mm PROTAN G MIGRATION BARRIER INSULATION SUBJECT TO REQUIREMENTS VAPOUR CONTROL LAYER SUPPORTING DECK

Pr o tan T er r ac es and Bal c oni es

Pe d e s t r i a n D e c k i n s u l a t e d d u o c o n s t r u c t i o n
Drawing No.: Version No.: Not to scale 80-10-05 01-2004

TOP LAYER (REINFORCED) OF CONCRETE WITH TILES ON TOP SLIDING LAYER EXTRUDED POLYSTYRENE (XPS) 50mm MIGRATION BARRIER PROTAN G MIGRATION BARRIER INSULATION (EPS) VAPOUR CONTROL LAYER SUPPORTING DECK

Pe d e s t r i a n D e c k p a r a p e t d e t a i l
Drawing No.: Version No.: Not to scale 80-10-06 02-2008

UPRIGHT FOR FENCE

METAL FLASHING

CONCRETE TILES ON I.E. BRICKS OF EXTRUDED POLYSTYRENE

EXTRUDED POLYSTYRENE MIGRATION BARRIER PROTAN G GEOTEXTILE 300G/M2 SUPPORTING DECK

Pr otan T er r ac es and Bal c oni es

Pe d e s t r i a n D e c k e d g e t r i m
Drawing No.: Version No.: Not to scale 80-10-07 02-2008

UPRIGHT FOR THE FENCE INSTALLED ON THE OUTSIDE OF THE MEMBRANE AND METAL FLASHING HEAT WELDED SEAM IMPREGNATED WOODEN DECK PROTECTION LAYER, PVC 1,2-2,0mm PROTAN G 1,5mm PROTAN GB 1,5mm GEOTEXTILE 300G/M2 PLYWOOD OR WOODEN DECK

Pe d e s t r i a n D e c k t e r m i n a t i o n w i t h wa l l flashing detail
Drawing No.: Version No.: Not to scale 80-10-08 02-2008

CHASE FLASHING

CONCRETE TILES ON BRICKS OF EXTRUDED POLYSTYRENE

EXTRUDED POLYSTYRENE MIGRATION BARRIER PROTAN G GEOTEXTILE 300G/M2 SUPPORTING DECK

Pr o tan T er r ac es and Bal c oni es

E x p o s e d Te r r a c e m e m b r a n e
Drawing No.: Version No.: Not to scale 80-15-01 01-2004

PROTAN GT, 2,4mm GEOTEXTILE 300G/M2 SUPPORTING DECK

E x p o s e d Te r r a c e m e m b r a n e - j o i n t d e t a i l
Drawing No.: Version No.: Not to scale 80-15-02 01-2004

WELDING CORD HEAT WELDED SEAM HEAT WELDED SEAM PROTAN GT 2,4mm GEOTEXTILE 300G/M2 SUPPORTING DECK FASTENER

Other technical drawings


The information in this document is believed to be correct at the date of publication. Protan AS does not accept any liability for errors or omissions, or for any consequences resulting therefrom.

Protan Exposed Membrane Roof

Protan Protected Membrane Roof

Protan Roof Renovation

ProtanTerraces and Balconies


Protan Technical Drawings

Protan AS P O. Box 420 Brakerya - N-3002 Drammen - Norway . Telephone +47 32 22 16 00 - Fax +47 32 22 17 00 www.protan.com