FULSCOPE 120R Series, 251R Model A Pneumatic Circular Chart Recording Controller

Specification Sheet 1-3A Issue 2, October 1999

DESCRIPTION
The ABB 120R Series LARGECASE is an air-operated recording controller, designed for accurate and long, dependable service. It is used in connection with a variety of standard ABB sensing elements or pneumatic receiver elements for remote transmission systems. Controllers may be furnished in either single duty (one variable controlled) or double duty (two variables controlled). Up to three variables may be recorded on the 12 in. circular chart.

PERFORMANCE SPECIFICATIONS
PERFORMANCE CHARACTERISTICS FUNCTIONAL CHARACTERISTICS Environmental Controller Response Adjustment Ambient Temp. Limits* (Continuous) Sensitivity psig per % Prop. 23F (-5C) minimum and inch Band 140F (60C) maximum Fixed High 1000 0.29 for fiber tip pens. Adjustable 1 to 1000 290 to 0.29 Adjustable per -25F (-32C) minimum and SIS-86 3 to 300 97 to 0.97 150F (66C)maximum for Limited Range 30 to 400 9.7 to 0.73 V -Type and Reservoir Pens. Specify 251R -20F (-29C) minimum PRE-ACT Time: 0.2 to 10 minutes and 180F (82C) Reset Rate: 0.05 to 5 repeats per minute maximum Electric clocks Action Accuracy Output Air Supply Air Consumption Air Connections Direct or reverse Calibrated to 1% of chart range 3-15 psig/0.2 to 1.0 Kg/cm2 20 psig normal, 25 psig maximum 0.4 scfm 1/4 in. NPT (Internal) 25F (-4C) minimum and 180F (82 C) maximum for standard spring wound clocks

Warning: Use of supply gas other than air can create a hazardous environment because a small amount of gas continuously vents to atmosphere. Trademark * NOTE : The proper clock, and linking system combinations chosen should conform to the temperature limits indicated above.

ABB

PHYSICAL SPECIFICATIONS
Case and Drive Cast aluminium corrosion resisistant, semi-gloss black baked enamel
Glass Surface or Flush (Panel) Vertical pipe mounting brackets(Yoke) 16-1/2 in. high x 13-25/32 in wide x 5-1/2 in. deep (420 mm high x 350 mm wide x 140 mm deep) Chart 12 in. (300 mm) Circular 100 Charts furnished with each recorder 120V or 240V, 50/60 Hz 12 or 24 hour Rotation 50 Hz-3.4W 60 Hz-5W

Window and Gages Standard Mounting Standard Optional Dimensions

Chart Drive (Electric) Standard

Power Consumption

Process Connections Standard Optional

Bottom (3 maximum) Back (3 maximum)

Chart Drive, (Spring Wound) Standard

9 day wind; 24 hour or 7 day rotation

Weight Approx. 25 lb (11.4 kg) plus sensing element Pens Standard Optional Style Fibre Tip V-Type Reservoir Ink per Pen 15 ml 15 ml Gauges Size Standard Range Air Supply and Output 2 in. 0-30 psig/0-2.0 kg/cm2 Dual range

ORDERING INFORMATION
1. 2. 3. 4. 5. 6. 7. 8. Select one code from each category and substitute in the sequence of the sample catalog number. For Actuation ordering information refer to the appropriate Specification Sheet in File 4. State type of mounting - Surface, Flush (Panel) or pipe mounting. State process connection location - bottom standard; back optional State chart drive rotation; on electric drive include voltage and frequency. On spring wound drive include wind period. Refer to File 9-12 Circular Chart Catalog for range and chart rotation availability. State Action: Direct (increase in measured variable causes increase in output) or Reverse (increase in measured variables causes decrease in output). List Accessories: A to M units, Air Filters and Regulators. (Accessory numbers are added in parenthesses after the catalog number).

BASE INSTRUMENT 120R 121R 122R 123R 124R 251R Fixed High Sensitivity Adjustable Sensitivity Adjustable Sensitivity with Automatic Reset Adjustable Sensitivity with Pre-Act Adjustable Sensitivity with Automatic Reset and Pre-Act Limited Range Sensitivity Adjustable 30 to 400 ACTUATION - Specified by the 2nd character F F G M Gage Pressure - Bellows and Capsules Gage Pressure - Bourdon Springs Gas Thermal Mercury Thermal Refer to Refer to Refer to Refer to File File File File 4-2 4-2A 4-1 4-1 Note 2 Note 2 Note 2 Note 2

COMBINATION LETTERS B Gas Thermal and Pressure W Mercury Thermal and Pressure Refer to File Numbers above for the individual actuations

PENS AND SERVICE - Specified by the 3rd character 1 2 3 4 5 6 7 Single Duty Double Duty Single Duty Double Duty Double Duty Single Duty Double Duty One pen controlling Two pens, both controlling. Note 1 Two pens, one pen controlling, other pen recording only One pen; Single system actuates two controllers having a single set-point adjustments. Note 1 One pen; Single system actuates two controllers having individual set-point adjustments. Note 1 Three pens; one pen controlling, two pens recording only Notes 3,4,5 Three pens; two pens controlling, one pen recording only Notes 1,6,7 Specified by the 4th and 5th characters or 4th, 5th and 6th characters For information about sensing elements refer to the corresponding file number as listed for the actuation.

SENSING ELEMENT -

121R

M 1

17

SAMPLE CATALOG NUMBER (Standard type plain bulb and 5 ft. capillary)

ACCESSORIES AND OPTIONAL ATTACHMENTS Air sets Piped and Mounted Accessories and Optional Attachments Charts Automatic to Manual Units NOTES 1. 2. 3. 4. For Double Duty Instruments with Different Control Responses, add the price of the Double Duty Responses of each type required and divide by two. For 3 to 300 Sensitivity Range Specify SIS-86 and NOTE: Not applicable to 251R. 3 pen Type 36 Gage Pressure Bellows, or Type 37 bellows, Type 42 Capsules can be provided in any combination however one of these elements must mount in lower half of case. Two 90 Botton Helical Springs 2000 psi and above or any two combinations of these can be mounted, always only in upper right and upper left of case; the 3rd pen (non control) must be actuated by a Type 36 Gag Bellows, Type 37 Receiver, Type 42 Capsule located in lower portion of case. Standard Spring Wound Chart Drives can only be provided when all actuation elements are mounted in half of case. 3 pen Bellows Type 36 or 37 not available. Only one Type 36 Gage pressure or Type 37 Receiver Bellows, Type 42 Capsule, 90 Button Helical above 2000 psi can be installed in upper left control position, the upper right control position is available for dual stacking of Type 38 or Thermal System Spiral Bourdon Springs. Type 38 or Thermal System Spiral Bourdon Springs can be stacked only in upper right and/or upper left position of case. Refer to File 7-1B Refer to File 1-3H Refer to File 9-12 Refer to File 1-3G

5. 6. 7.

8.

ABB
Asea Brown Boveri Limited
14, Mathura Road, P.O. Amar Nagar, Faridabad-121003, Haryana (India) Phone: 5275592/5593/5597 5276350/6354/6362/6367 Fax: 0129-5275019

2002 ABB

Printed in India

SS 1-3A ISSUE 2

The Companys policy is one of continuous product improvement and the right is reserved to modify the specifications contained herein without notice.